York YUHC 07-18, YUHC 18-60 User Manual

Installation & Owner’s Manual
MODELS
YUHC 18-60 YUKC 07-18
MINISPLIT AIR BLOWER
EN 035M00065-000
J368-EN.indd 1 2/1/07 9:40:52 AM
Safety Precautions ...................................................3
Part Names ................................................................4
Technical Specifications ..........................................
5
Outdoor Unit Dimensions ........................................ 9
Preparation Before Installation .............................10
Installation ...............................................................10
Condensate Drainage ............................................14
Refrigerant Piping Connects ................................. 15
Fan Speeds .............................................................16
Wiring Diagrams .....................................................
17
Defrosting Operation ..............................................20
Service and Maintenance ......................................20
Operation Tips ........................................................
21
Trouble Shooting Guide .........................................
22
Declaration of Conformity .....................................23
Please read this installation manual carefully before starting the installation. It will tell you necessary information.
Quality POLICY
We will continuously strive to satisfy our customers with consistent reli­ability in product, service and support through superior quality, service culture and distinctive technology.
Standard
Refrigerant R-410A
Model 18-24 30-60
Set YUHCxxFUAAAR YUHCxxFUAACR
Outdoor YUJCxxFU-AAR YUJCxxFU-ACR
Indoor YUKCxxFU-AAR YUKCxxFU-ACR
With Low Ambient Kit
Refrigerant R-410A
Model 18-24 30-60
Set YUHCx xFUBAAR YUHCx xFUBACR
Outdoor YUJCx xFU-AAR YUJCx xFU-ACR
Indoor YUKCxxF U-AAR YUKCxxF U-ACR
Multi Inverter R-410A
50Hz/1Ph
Outdoor RRJCxxAA-AAA
Indoor YUKCxxAA-AAR
Refrigerant DC INVERTER R-410A
Model 18-24 36-48 60
Set YUHCxxDUBAAR-K YUHCxxDUBACR-K YUHCxxDSBACR-K
Outdoor YUJCxxDU-BAR YUJCxxDU-BCR YUJCxxDS-BCR
Indoor YUKCxxDU-BAR-K YUKCxxDU-BCR-K YUKCxxDS-BCR-K
J368-EN.indd 2 2/1/07 9:40:52 AM
3
ENGLISH
EXTENDED PARTS
1. Refrigerant Pipe : See Technical Specification
2.
Pipe insulation material (Polyethylene foam 9 mm thick)
3. Vinyl tape
4. Putty
REQUIRED TOOLS
1. Screw driver 9. Manifold gauge
2. Hexagonal wrench 10. Gas leak detector
3. Torque wrench 11. Vacuum pump
4. Spanner 12. Pipe clamp
5. Reamer 13. Pipe cutter
6. Hole core drill 14. Flare tool set
7. Tape measure 15. Electrical circuit tester
8. Thermometer
SAFETY PRECAUTIONS
• Please read this installation manual carefully before starting installation of the unit.
• This air conditioning system contains refrigerant under pressure, rotating parts and electrical connection which may be dangerous and can cause injury. Installation and maintenance of this air conditioning system should only be carried out by trained and qualified personnel.
• After unpacking, please check the unit carefully for possible damage.
• Before undertaking any work on the unit, make sure that the power supply has been disconnected.
WARNING & CAUTIONS
Never put hands or objects into the Air Outlet of indoor or outdoor units. These units are installed with a fan running at high speed. To touch the moving fan will cause serious injury.
DANG ER
To avoid the risk of serious electrical shock, never sprinkle or spill water or liquids on unit.
DANG ER
To prevent electric shock, turn off the power or disconnect the power supply plug before beginning any cleaning or other routine maintenance. Follow the directions for cleaning in this manual.
WARNING
Do not use liquid cleaners or aerosol cleaners, use a soft and dry cloth for cleaning the unit. To avoid electric shock, never attempt to clean the unit by sprinkling water.
WARNING
Do not use caustic household drain cleaners in the unit. Drain cleaners can quickly destroy the unit components (drain pan and heat exchanger coil, etc.)
WARNING
For proper performance, operate the unit in temperature and humidity ranges indicated in this manual. If the unit is operated beyond these conditions, it may cause abnormal functions of the unit or dew dripping from the unit.
WARNING
Ventilate the room regularly while the air conditioner is in use, especially if there is also a gas appliance in use in this room. Failure to follow these directions may result in a loss of oxygen in the room.
WARNING
Do not attempt to service the unit yourself. This unit has no user serviceable components. Opening or removing the cover will expose you to dangerous voltage. Turning off the power supply will not prevent potential electric shock.
DANG ER
Do not attempt to install this unit by yourself. This unit requires installation by qualified persons.
CAUT IO N
Danger
No
Thinner
J368-EN.indd 3 2/1/07 9:40:54 AM
4
ENGLISH
I
J
A
F
G
C
H
E
N
M
L
K
B
E
D
PART NAMES
INDOOR & OUTDOOR UNIT
A. Indoor unit B. Outdoor unit C. Remote controller D. Air-in E. Air-out F. Air inlet G. Connecting pipe H. Drain hose
All the pictures in this manual are for explanation purpose only. They may be sightly different from the air conditioner you purchased. The actual shape shall prevail.
OUTDOOR UNIT
INDOOR UNIT
DISPLAY PANEL
I. Infrared signal receiver J. Emergency button K. Running indicator L. Timer indicator M. Frost indicator (cooling and heating type) or fan indicator (cooling only type) N. Pump indicator
Display Panel
NOTE
J368-EN.indd 4 2/1/07 9:40:55 AM
5
ENGLISH
TECHNICAL SPECIFICATIONS
Technical Specifications : Duct Type YUHC “R-410A” -50Hz
Models
Indoor
Unit
YUKC
18 24 30 36 48 60
Outdoor
Unit
YUJC
18 24 30 36 48 60
Power Supply
V/Ph/Hz 220-240/1/50 380/3/50
Ph 1 1 3 3 3 3
Power Consumption W 1,900/1,900 2,560/2,500 3,250/3,250 3,700/3,350 4,700/4,900 6,000/6,000
Running Current A 8.8/8.8 12.2/11 5.5/5.5 6.5/5.8 8.2/8.6 9.8/9.8
Refrigerant Type
R-410A
Refrigerant Charge gr 2,050 2,600 3,100 3,100 4,000 4,200
Noise level
Indoor
dB(A)
38 38 44 44 46 47
Outdoor 48 55 57 57 58 58
Indoor Unit
Power Supply
V/Ph/Hz 220-240/1/50
Ph 1 1 1 1 1 1
Fan
Air flow m3/h 1,160 1,460 2,070 2,070 2,400 2,800
Input Power W 117 170 118 118 118 227
Running Current A 0.53 0.77 0.54 0.54 0.54 1.03
Dimension
Height mm 300 300 300 300 300 320
Width
mm 1,000 1,000 1,350 1,350 1,350 1,350
Depth mm 800 800 800 800 800 800
Weight
kg 36 38 48 48 50 70
System Operation Control Wireless Control with LCD Display
Outdoor Unit
Power Supply
V/Ph/Hz 220-240/1/50 380/3/50
Ph 1 1 3 3 3 3
Compressor
Qty 1 1 1 1 1 1
Compressor Type
Rotary Scroll
Dimension
Height mm 695 860 960 960 1,245 1,245
Width
mm 845 895 990 990 940 940
Depth mm 335 330 360 360 360 360
Weight
kg 55 79 101 101 110 110
Piping
Type Flare + Nuts
Pipe Size
Suction inch 1/2 5/8 3/4 3/4 3/4 3/4
Liquid inch 1/4 3/8 1/2 1/2 1/2 1/2
J368-EN.indd 5 2/1/07 9:40:56 AM
6
ENGLISH
Technical Specification: Ducted Dc Inverter “YUHC” R-410A, 50Hz.
Model
Set YUHC18DUBAAR-K YUHC24DUBAAR-K YUHC36DUBACR-K YUHC48DUBACR-K YUHC60DSBACR-K
Indoor YUKC18DU-BAR-K YUKC24DU-BAR-K YUKC36DU-BCR-K YUKC48DU-BCR-K YUKC60DS-BCR-K
Outdoor YUJC18DU-BAR YUJC24DU-BAR YUJC36DU-BCR YUJC48DU-BCR YUJC60DS-BCR
Power supply V-Ph-Hz 220~240-1-50 220~240-1-50 380V~3~50Hz 380V~3~50Hz 380V~3~50Hz
Cooling
Capacity Btu/h 18,000 24,000 36,000 48,000 60,000 Input W 1,570 2,130 3,260 4,250 4,840 Rated current A 7 10 9 11 11
Heating
Capacity Btu/h 21,000 28,000 40,000 53,000 62,000 Input W 1,630 2,190 3,120 4,140 4,800
Rated current A 7 10 8 11 11 Max. input consumption W 2,600 2,800 3,560 4,750 5,950 Max. current A 10 11 10 13 16 Starting current A 1 1 1 1 1
Compressor
Type
DC Inverter Rotary DC Inverter Scroll
Input W 1,650 1,650 3,665 3,665 3,665
Rated current (RLA)
A 8 8 8 8 8
Locked rotor
Amp (LRA)
A 28 28 28 28 28
Protector Thermal
Capacitor µF 50 50 50 50 50
Refrigerant oil ml 480 480 500 500 500
Indoor fan motor
Type AC Motor
Input W 117 170 118 324 160
Capacitor µF 3 7 3 10 10
Speed (Hi/Me/Lo)
r/min 900/800/690 1,100/1,020/900 820/695/620 870/770/700 870/770/700
Indoor coil
Number of rows 3 3 3 3 3
Fin spacing mm 2 2 2 2 2
Fin type Hydrophilic aluminium
Tube outside dia.
mm Ø9.52
Material Type
Innergroove tube
Coil length x
height x width
mm 800×254×66 800×254×66 1,150×254×66 1,150×254×66 1,150×305×66
Indoor air flow (Hi/Me/Lo)
m3/h 1,020/870/700
1,275/1,170/1,030 2,070/1,950/1,860 2,400/2,300/2,200 2,800/2,700/2,600
Indoor external static pressure (Hi) Pa 40 40 70 70 96 Indoor noise level (Hi/Me/Lo) dB(A) 50/-/- 53/-/- 49/47/44 51/47/44 52/48/46
Indoor unit
Dimension
(WxHxD)
mm 1,095×805×290 1,095×805×290 1,350×298×800 1,350×320×800 1,350×320×800
Packing
(WxHxD)
mm 1,205×940×370 1,205×940×370 1,555×940×370 1,555×440×940 1,555×440×940
Net/Gross weight
kg 38/45 38/45 48/57 70/80 70/80
Outdoor fan motor
Input W 129 150 307 150×2 150×2
Capacitor µF 3 3 10 3.5×2 3.5×2
Speed r/min 770 800 740 800 800
Outdoor coil
Number of rows 2 2 1 1 1
Fin spacing mm 2 2 2 2 2
Fin type Hydrophilic aluminium
Tube outside dia.
mm Ø9.52
Tube Material
Innergroove tube
Coil length x
height x width
mm 630×660×44 620×813×44 955×915×22 715×610×22 1150×305×66
Outdoor air flow
m3/h 2,400 3,000 5,000 6,000 6,000
Outdoor noise level dB(A) 56 55 57 58 58
Outdoor unit
Dimension
(WxHxD)
mm 840×677×310 894×860×302 990×960×340 940×1,245×340 940×1245×340
Packing
(WxHxD)
mm 965×770×395 1,043×915×395 1,120×1015×435 1,058×1300×435 1,058×1,300×435
Net/Gross weight
kg 62.5/66.5 72/76.5 106/111 117/126 112/127 Refrigerant R-410A g 1,650 2,200 2,600 3,550 4,200 Throttle type EXV&Capillary
Refrigerant piping
Liquid side/ Gas side
mm 6.35/12.7 9.53/16 9.53/16 9.53/16 9.53/16
J368-EN.indd 6 2/1/07 9:40:56 AM
7
ENGLISH
TECHNICAL SPECIFICATION: EVEREST MULTI INVERTER “YUKC-RRJC” 50Hz Indoor Unit Duct Type YUKC 07-18
Model YUKC 07AA-AAR YUKC 09AA-AAR YUKC 12AA-AAR YUKC 18AA-AAR
Power supply Ph-V-Hz 1Ph, 220-240V~, 50Hz 1Ph, 220-240V~, 50Hz 1Ph, 220-240V~, 50Hz
1Ph, 220-240V~, 50Hz
Capacity
Cooling Capacity
BTU/h 7,000 9,000 12,000 18,000
Heating Capacity
BTU/h 8,000 11,000 14,000 21,000
Power input w 40 40 40 65
Indoor fan motor
Input W 38 38 38 63
Capacitor µF 1.0µF/450V 1.0µF/450V 1.0µF/450V 2.5µF/450V
Speed (Hi/Mi/Lo) r/min 735/650/560 735/650/560 735/650/560 930/830/660
Indoor coil
Number of rows 2 2 2 2
Fin spacing mm 1.5 1.5 1.5 1.7
Fin type Hydrophilic aluminium
Tube outside dia.
mm Ø7 Ø7 Ø7 Ø9.53
Tube Material Innergroove tube
Coil length x height x width
mm 700x26x350 700x26x350 700x26x350 800x254x44
Number of circuits 4 4 4 3
Indoor air flow (Hi/Mi/Lo) m3/h 480/410/360 480/410/360 580/480/400 660/550/480
Indoor noise level (Hi/Mi/Lo) dB(A) 35/32/30 36/33/30 38/35/33 40/38/35
Pipe size Liquid side/ Gas side mm Ø6.35/Ø9.53 Ø6.35/Ø9.53 Ø6.35/Ø12.7 Ø6.35/Ø12.7
Indoor unit
Dimension (W*H*D) mm 955×210×385 955×210×385 955×210×385 1,301X210X385
Packing (W*H*D) mm 1,114x277x469 1,114x277x469 1,114x277x469 1,114x277x469
Net/Gross weight Kg 15/19 15/19 15/19 18/22
J368-EN.indd 7 2/1/07 9:40:56 AM