York YPHH, YCHBC, YRHBC, YPHYB, YHBC User Manual

...
5 (2)
York YPHH, YCHBC, YRHBC, YPHYB, YHBC User Manual

FAN COIL

AIR CONDITIONERS

INSTALLATION, OPERATION, & MAINTENANCE Supersedes: Form 115.20-NOM2 (1199) Form 115.20-NOM2 (105)

00168VIP

MODEL YHBC – Ceiling Concealed Model

00170VIP

MODEL YHH – Ceiling Concealed Model with Electric Heat

00171VIP

MODEL YPHBC – Ceiling Concealed Model with Insulated Return. Plenum and Filter

MODEL YPHH – Ceiling Concealed Model with Electric Heat, Insulated Return Plenum and Filter

00172VIP

MODEL YCHBC – Ceiling Cabinet Model

00173VIP

MODEL YRHBC – Telescoping / Recessed Ceiling Model

00174VIP

MODEL YHYB – High Capacity Ceiling Concealed Model

00175VIP

 

MODEL YPHYB – High Capacity Ceiling Concealed Model

Notes:

with Insulated Return Plenum and Filter

 

1.2-Pipe units have one water coil. 4-Pipe units have two water coils.

2.Changeover is used to select heating or cooling mode.

3.YORK International does not recommend “fan cycle” applications for cooling on unit mounted thermostats.

4.For proper operation, control valve must be normally closed.

5.Aquastats provided where required.

6.Electric Heat is only available in the YHH and YPHH units. These units require a remote thermostat (low voltage 4 wire thermostat).

***** WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER *****

Altering the product or replacing parts with non authorized factory parts voids all warranty or implied warranty and may result in adverse operational performance and/or a possible hazardous safety condition to service personnel and occupants. Company employees and/or contractors are not authorized to waive this warning.

L23952Y 1-05

 

FORM 115.20-NOM2 (105)

 

TABLE OF CONTENTS

RECEIVING..........................................................................................................................................................

3

STORAGE............................................................................................................................................................

3

PREPARE CEILING FOR MOUNTING................................................................................................................

3

WIRING...............................................................................................................................................................

3

PIPING .................................................................................................................................................................

6

DRAIN PIPING.....................................................................................................................................................

7

DRAWINGS...................................................................................................................................................

8 - 14

STARTUP...........................................................................................................................................................

15

MAINTENANCE.................................................................................................................................................

16

Reference Documents:

• IOM for YVC-YVF-YVS

Form 115.20-NOM3 (Latest)

• IOM for YSHW, YSHX

Form115.22-NOM5 (Latest)

• IOM for YSVW, YSVX

Form 115.22-NOM2(Latest)

• Parts List

Form 115.20-RP2(Latest)

These documents can be ordered through Publications Dept.

or downloaded @ http://intranet.york.com/web0003/library/default.asp

 

 

NOTE:

 

 

Use direction of airflow

 

 

for selecting rightand

 

 

left-hand units.

 

TABLE 1 - NOMINAL AIRFLOWS

 

 

 

 

 

UNIT SIZE

CFM

 

 

3

300

 

 

4

400

 

 

5

500

 

 

6

600

 

 

8

800

 

 

10

1000

 

PLENUM

12

1200

 

 

(OPTIONAL)

13

1300

 

 

16

1600

 

 

20

2000

 

FIG. 1 – DETERMINATION OF RIGHT-HAND /

 

 

 

 

 

 

LEFT-HAND REFERENCES

2

YORK INTERNATIONAL

FORM 115.20-NOM2 (105)

INSTALLATION

RECEIVING

Material in this shipment has been inspected at the factory and released to the transportation agency in good condition. When received, a visual inspection of all cartons should be made immediately.Any evidence of rough handling or apparent damage should be noted on the delivery receipt and the material inspected in the presence of the carrier's representative.

If damage is found, a claim should be filed against the carrier immediately.

STORAGE

Iftheequipmentisnottobeimmediatelyinstalled,store it in a dry location with the motor protected against moisture, dust, corrosion and physical damage.

PREPARE CEILING FOR MOUNTING

Depending upon building construction, provisions for mounting the unit must be made by the contractor according to architects; drawings.

It is important to ensure that the fan coils are securely mounted and the structure is sufficient to support the weight of the equipment.All anchors for mounting the equipment must be placed and sized to ensure a safe and durable installation.

The YHBC, YPHBC, YRHBC, YHH, YHHS, YPHH, YHYB, andYPHYB units are designed for installation in a horizontal position above a dropped ceiling. The YCHBC is a cabinet unit intended for horizontal exposed surface mounting.

In free (non-ducted return air) return installations of YHBC, YHH, YHHS and YHYB units; the furred down area must be completely sealed (except return air grille) to ensure that all return air is pulled from the conditioned space and not from other areas of the building structure.

Access must be provided for servicing the unit. If this access is provided by a removable ceiling panel, amplespacemustbeallowedforremovaloftheblower panel and to provide access to electrical and plumbing controls.

Unit must not be operated during building construction due to excessive airborne dust and debris. The units must not be operated under any circumstances without an air filter in place.

WIRING

Allwiringmustcomplywiththelocalandnationalcode requirements. Units are provided with wiring diagrams and nameplate data to provide information required for necessary field wiring.

For power wiring a 4 x 4 electrical box is provided on thecabinetforconnectionofpowersupplyandislocated on the same side as piping.

On YHBC units, the box is shipped unattached, it is field attached to the unit in a location convenient to electrical entrance.

Any devices such as fan switches or thermostats that have been furnished by the factory for field installation must be wired in strict accordance with the wiring diagram that is supplied with the unit. Failure to do so could result in damage or injury.

YORK INTERNATIONAL

3

FORM 115.20-NOM2 (105)

INSTALLATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

������

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

��� ��� ��� ��� ��� ��� ���

��� ��� ���

 

 

 

 

 

 

 

 

 

 

 

 

 

LD010198

 

 

 

 

 

 

FIG. 2 – HORIZONTAL UNITS - TYPICAL WIRING

4

YORK INTERNATIONAL

FORM 115.20-NOM2 (105)

INSTALLATION

T334 THERMOSTAT

Heat-Off Cool, Fan Auto-On, 24V, Manual changeover, 4-Wire Thermostat (R, G, Y, W) Adj. Heat Anticipator, Fixed Cooling Anticipator, Fan Cycling (Cooling) or (Heating/Cooling), No Heating Required.

T404 THERMOSTAT

Heat-Off Cool, Fan Auto-On, 24V, Manual changeover, 6-Wire Thermostat (R, G, O, Y, W, B) Adj. Heat / Fixed Cool Anticipator, Fixed Cooling Anticipator, Fan Cycling.

(O & B can be used for cool and heat relays respectively, or for cool & heat water valves.)

T200 THERMOSTAT OPTION (W/CONTROLLER)

Heat-Off Cool, Fan -On, 24V, Manual changeover, 7-Wire Thermostat (R, C, Hi, Med, Lo, 24V Heat, 24V Coil), Auto fan speed control, digital readout, auto-overide.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LD010200

FIG. 3 – WIRING SCHEMATIC FOR HBC/PHBC/CHBC/RHBC/HYB/PHYB

YORK INTERNATIONAL

5