York YR User Manual

Page 1

FORM 160.81-EG1 (502)

Model YR
Twin-Screw Compressor Liquid Chillers
Design Level A
Rated in Accordance
with the latest edition of ARI
ST ANDARD 550/590
200 through 430 tons (60 Hz) 700 through 1500 kW (50 Hz) 170 through 365 tons (50 Hz) 600 through 1280 kW (50 Hz)
Utilizing HFC-134a
00562VIP
ASHRAE
90.1
COMPLIANT
Metric Conversions
Page 2

Table of Contents

PAGE
INTRODUCTION.......................................................... 3
FORM 160.81-EG1
LIST OF TABLES
RATINGS ..................................................................... 4
OPTIVIEW CONTROL CENTER ................................. 5
MECHANICAL SPECIFICATIONS............................... 13
ACCESSORIES & MODIFICATIONS .......................... 17
SI METRIC CONVERSION.......................................... 18
APPLICATION DATA.................................................... 19
DIMENSIONS – STD. .................................................. 26
Evaporator, Condenser & Water Boxes ................... 26
Evaporators, Compact Water Boxes (ft.-in.)............ 28
Evaporators, Compact Water Boxes (mm).............. 29
Condensers, Compact Water Boxes (ft.-in.) ............ 30
Condensers, Compact Water Boxes (mm) .............. 31
Floor Layout, Neoprene Isolators (In.) ..................... 32
Floor Layout, Neoprene Isolators (mm) ................... 33
Floor Layout, Spring Isolators (In. and mm) ............ 34
WEIGHTS – Std. and Metric........................................ 35
GUIDE SPECIFICATIONS ........................................... 36
TABLE
NO.
1 Water Flow Rate Limits................ 19
2 Motor Voltage Variations .............. 22
3 60 Hz Electrical Data.................... 23
4 Motor Starters............................... 24
5 50 Hz Electrical Data.................... 24
6 Available Compressor/Shell/
Motor Combinations ..................... 24
PAGE
Model
Evaporator Code
Condenser Code
The model number denotes the following characteristics of the unit:
Compressor Code

NOMENCLATURE

YR TD TD T0 46 A S
Special Features
Design Level
Motor Code
Power Supply:
– for 60 Hz 5 for 50 Hz
2
YORK INTERNATIONAL
Page 3

Introduction

FORM 160.81-EG1
The YORK MAXE YR Chiller offers a complete combina­tion of features for total owner satisfaction.
MATCHED COMPONENTS MAXIMIZE EFFICIENCY
Actual chiller efficiency cannot be determined by ana­lyzing the theoretical efficiency of any one chiller com­ponent. It requires a specific combination of heat ex­changer, compressor , and motor performance to achieve the lowest system IPL V/NPL V . YORK M
AXE chiller tech-
nology matches chiller system components to provide maximum chiller efficiency under actual – not just theo­retical – operating conditions.
REAL-WORLD ENERGY PERFORMANCE
YORK pioneered the term “Real-World Energy” to il­lustrate the energy-saving potential of focusing on chiller performance during off-design conditions. Off-design is not only part-load, but full-load operation as well, with reduced entering condenser water temperatures (ECWT s). This is where chillers operate 99% of the time, and where operating costs add up.
The YR M
AXE chillers are the only chillers designed to
operate on a continuous basis with cold ECWT and full condenser flow at all load points, taking full advantage of Real-World conditions. This type of operation benefits the cooling tower as well; reducing cycling of the fan motor and ensuring good coverage of the cooling fill.
YORK M
AXE chillers offer the most efficient Real-World
operation of any chiller, meaning lower operating costs and an excellent return on your chiller investment.
HIGH-EFFICIENCY OIL SEPARATOR
HIGH-EFFICIENCY HEA T EXCHANGERS
M
AXE chiller heat exchangers offer the latest technology
in heat transfer surface design to give you maximum efficiency and compact design. Waterside and refrigerant-side design enhancements minimize both en­ergy consumption and tube fouling. The “skip-fin” design at all intermediate tube supports provides maximum tube wall thickness at the support area to extend tube life.
FACTORY PACKAGING REDUCES FIELD LABOR COSTS
YORK M
AXE screw chillers are designed to keep instal-
lation costs low. Where installation access is not a problem, the unit can be shipped completely packaged, requiring minimal piping and wiring to complete the installation.
For those units utilizing a factory installed Solid-State Starter, the three power leads provide all power to the chiller and its auxiliaries.
T AKE ADVANTAGE OF COLDER COOLING TOWER WATER TEMPERATURES
YORK M
AXE screw chillers are designed to take full ad-
vantage of colder cooling tower water temperatures, which are naturally available during most operating hours. Considerable energy savings are available by letting tower water temperature drop, rather than artifi­cially holding it above 75°F (23.9°C), especially at low load, as some chillers require.
U.L. ACCEPTANCE – YOUR ASSURANCE OF RELIABILITY
M
AXE YR Screw Chillers utilize high-efficiency oil sepa-
ration, limiting oil carry-over to less than 500 ppm. Oil is vital in screw compressors for lubrication, rotor seal­ing and cooling. However, oil in the evaporator can lead to reduced heat transfer and reduced system perfor­mance. The high-efficiency oil separator keeps the oil in the lube circuit and maximizes heat transfer efficiency .
YORK INTERNATIONAL
YORK M
AXE screw chillers are approved for listing by
Underwriter’s Laboratories for the United States and Canada. Recognition of safety and reliability is your as­surance of trouble-free performance in day-to-day build­ing operation.
3
Page 4

Ratings

FORM 160.81-EG1
Rated in accordance with the latest issue of ARI Standard 550/590.
ARI CERTIFICATION PROGRAM
The performance of YORK M to the Air Conditioning and Refrigeration Institute (ARI) complying with the certification sections of the latest issue of ARI Standard 550/590. Under this Certification Program, chillers are regularly tested in strict compli­ance with this Standard. This provides an independent, third-party verification of chiller performance.
YORK YR screw chillers are designed to comply with ASHRAE Standard 90.1-1999 and 90.1-2001. The su­perior part-load performance of the YORK YR chillers far exceeds the IPLV/NPLV requirements of ASHRAE
90.1, providing superior Real World Energy savings for efficiency conscious owners.
COMPUTERIZED PERFORMANCE RATINGS
Each chiller is custom-matched to meet the individual building load and energy requirements. A large num­ber of standard heat exchangers and pass arrange­ments are available to provide the best possible match.
It is not practical to provide tabulated performance for each combination, as the energy requirements at both
AXE chillers is certified
full- and part-load vary significantly with each heat ex­changer and pass arrangement. Computerized ratings are available through each YORK sales office. These ratings can be tailored to specific job requirements, and are part of the ARI Certification Program.
OFF-DESIGN PERFORMANCE
Since the vast majority of its operating hours are spent at off-design conditions, a chiller should be chosen not only to meet the full-load design, but also for its ability to perform efficiently at lower loads and lower tower water temperatures. It is not uncommon for chillers with the same full-load kW/TON to have an operating cost difference of over 10% due to part-load operation.
Part-load information can be easily and accurately gen­erated by computer. And because it is so important to an owner’s operating budget, this information is now standard within the ARI Certification Program in the form of an Integrated Part-Load V alue (IPL V), and Non­Standard Part-Load Value (NPLV).
The IPL V / NPLV formulas from ARI Standard 550/590 closely track chiller operations, and provide a more ac­curate indication of chiller performance than the previ­ous IPL V / APLV formula. A more detailed analysis must take into account actual building load profiles, and lo­cal weather data. Part-load performance data should be obtained for each job using its own design criteria.
4
YORK INTERNATIONAL
Page 5

OptiView Control Center

FORM 160.81-EG1
OPTIVIEW CONTROL CENTER
The YORK OptiView Control Center , furnished as stan­dard on each chiller, provides the ultimate in ef ficiency, monitoring, data recording, chiller protection and oper­ating ease. The control center is a factory-mounted, wired and tested state-of-the-art microprocessor based control system for R-134a screw chillers. The panel is configured with a 10.4 inch diagonal color Liquid Crys­tal Display (LCD) surrounded by “soft” keys, which are redefined with one keystroke based on the screen dis­play at that time. This revolutionary development makes chiller operation quicker and easier than ever before. Instead of requiring keystroke after keystroke to hunt for information on a small monochrome LCD screen, a single button reveals a wide array of information on a large, full-color illustration of the appropriate compo­nent, which makes information easier to interpret. This is all mounted in the middle of a keypad interface and installed in a locked enclosure.
The LCD display allows graphic animated display of the chiller, chiller sub-systems and system parameters; this allows the presentation of several operating param­eters at once. In addition, the operator may view a graphical representation of the historical operation of the chiller as well as the present operation. A Status Bar is displayed at all times on all screens. It contains the System - Status Line and Details Line, the Control Source, Access Level, Date and Time.
00550VIP
During the Start Sequence and System Lockout Delay , the system status will include a countdown timer indi­cating the time remaining. The control panel is com­patible with the YORK Solid State Starter (optional), Electro-mechanical (E-M) starter, or any customer sup­plied E-M starter that complies with the YORK R-1131 standard. The locations of various chiller parameters are clearly marked and instructions for specific opera­tions are provided. The panel verbiage is available in other languages as an option, with English always avail­able. Data can be displayed in either English or Metric units, plus keypad entry setpoints of 0.1 increments.
Security access is provided to prevent unauthorized change of setpoints. This is accomplished with three dif­ferent levels of access and passwords for each level. There are screens, displayed values, programmable setpoints and manual controls only available with ser­vice level access to the chiller. They are only displayed when logged in at the service access level. The Advanced Diagnostics and troubleshooting information for the chiller and the panel is also included at this access level.
The panel is fused through a 1-1/2 KVA transformer in the compressor motor starter to provide individual over­current protected power for all controls. Numbered ter­minal strips for wiring such as Remote Start/Stop, Flow Switch, Chilled Water Pump and Local or Remote Cy­cling Device are provided. The Panel also provides field interlocks that indicate the chiller status. These con-
YORK INTERNATIONAL
5
Page 6
OptiView Control Center (continued)
FORM 160.81-EG1
tacts include a Remote Mode Ready To Start, a Cy­cling Shutdown, a Safety Shutdown and a chiller Run Contact. Pressure transducers sense system pressures and thermistors sense system temperatures. The out­put of each transducer is a DC voltage that is analo­gous to the pressure input. The output of each ther­mistor is a DC voltage that is analogous to the tem­perature it is sensing.
Setpoints can be changed from a remote location via 0-10VDC, 4-20mA, contact closures or through serial communications. The adjustable remote reset range [up to 20°F (11.1°C)] provides flexible, efficient use of re­mote signal depending on reset needs. Serial data inter­face to the YORK ISN Building Automation System (BAS) is through the General Protocol Interface Card (GPIC), which can be mounted inside the Control Center.
This printed circuit board requests the required data from the Micro Board and makes it available for the YORK ISN network. This optional board is available through the YORK BAS group. The operating program is stored in non-volatile memory (EPROM) to eliminate chiller failure due to AC power failure/battery discharge. Pro­grammed setpoints are retained in lithium battery­backed RTC memory for 11 years minimum.
Smart Freeze Point Protection can operate the chiller as low as 36°F (2.22°C) leaving chilled water tempera­ture, without nuisance trips on Low Water Temperature. The sophisticated program and sensor monitors the chiller water temperature to prevent freeze-up. Each programmable point has a pop-up screen with the al­lowable ranges, so the chiller cannot be programmed to operate outside of its design limits.
Thermal ice storage systems are based on the concept of using off-peak, lower cost electricity to build ice for handling the cooling load during peak hours. The most efficient way to build ice is to maximize chiller load and minimize run time. Standard chiller control systems are not designed for this operating mode. In a typical appli­cation, chillers will load and unload to maintain a leaving chilled liquid setpoint. When the YORK YR chiller oper­ates in the thermal storage control mode, the unit will remain at 100% load until the setpoint shutdown tem­perature is reached. To add greater operating flexibility and eliminate unnecessary chiller cycling, two different Low Water (Liquid) T emperature Restart Thresholds can be programmed, one for the ice mode and one for the standard cooling mode. This control enhancement is stan­dard on all YR chillers. The chiller can also be left in the standard control mode for temperatures ranging between 20 and 70°F (-6.7 and 21.1°C), for applications involving a process or comfort cooling duty that requires leaving chilled liquid temperature setpoint control.
When power is applied to the chiller, the HOME screen is displayed. This screen displays a visual representation of the chiller and a collection of data detailing important op­erations and parameters. When the chiller is running, the flow of chilled liquid is animated by the alternating shades of color moving in and out of the pipe nozzles. The pri­mary values that need to be monitored and controlled are shown on this screen. They are as follows:
Display Only:
• Chilled Liquid Temperature – Leaving
• Chilled Liquid Temperature – Return
• Condenser Liquid Temperature – Return
• Condenser Liquid Temperature – Leaving
• Motor Run (LED)
• % Full-load Amps
• Operating Hours
With the “soft” keys the operator is only one touch away from the 8 main screens that allow access to the major information and components of the chiller. The 8 screens are the SYSTEM, EV APORAT OR, CONDENSER, COM-
PRESSOR, OIL SUMP, MOTOR, SETPOINTS, and the HISTORY. Also on the Home Screen is the ability to Log IN, Log OUT and Print. Log In and Log Out is the means
by which different security levels are accessed. The SYSTEM screen gives a general overview of com-
mon chiller parameters for both shells. This is an end view of the chiller with a 3-D cutaway of both the shells. The following can be viewed from this screen:
Display Only:
• Discharge Temperature
• Chilled Liquid Temperature – Leaving
• Chilled Liquid Temperature – Return
• Chilled Liquid Temperature – Setpoint
• Evaporator Pressure
• Evaporator Saturation Temperature
• Condenser Liquid Temperature – Leaving
• Condenser Liquid Temperature – Return
• Condenser Pressure
• Condenser Saturation Temperature
• Oil Temperature
• Differential Oil Pressure
• % Full-load Amps
• Current Limit
• Slide Valve Position
6
YORK INTERNATIONAL
Page 7
FORM 160.81-EG1
The EVAPORATOR screen displays a cutaway view of the chiller evaporator. All setpoints relating to the evapo­rator side of the chiller are maintained on this screen. Animation of the evaporation process indicates whether the chiller is presently in RUN condition (bubbling) and liquid flow in the pipes is indicated by alternating shades of color moving in and out of the pipes. Adjustable lim­its on the low water temperature setpoints allow the chiller to cycle on and off for greater efficiency and less chiller cycling. The chiller cycles off when the leaving chilled water temperature is below setpoint and is ad­justable from 1°F (0.55°C) below to a minimum of 36°F (2.22°C). Restart is adjustable from setpoint up to a max. of 80°F (26.6°C). The Panel will check for flow to avoid freeze-up of the tubes. If flow is interrupted, shut­down will occur after a minimum of two seconds. The following can also be performed through this screen:
Display Only:
• Chilled Liquid Flow Switch (Open/Closed)
• Chilled Liquid Pump (Run/Stop)
• Evaporator Pressure
• Evaporator Saturation Temperature
• Return Chilled Liquid Temperature
• Leaving Chilled Liquid Temperature
• Evaporator Refrigerant Temperature
• Small Temperature Difference
• Leaving Chilled Liquid Temperature Setpoints – Setpoint
• Leaving Chilled Liquid Temperature Setpoints – Remote Range
• Leaving Chilled Liquid Temperature Setpoints – Shutdown
• Leaving Chilled Liquid Temperature Setpoints – Shutdown Offset
• Leaving Chilled Liquid Temperature Setpoints – Restart
• Leaving Chilled Liquid Temperature Setpoints – Restart Offset
• Ice Storage Active (LED)
Programmable:
• Local Leaving Chilled Liquid Temperature – Range
• Local Leaving Chilled Liquid T emperature – Setpoint
• Leaving Chilled Liquid Temperature Cycling Offset – Shutdown
• Leaving Chilled Liquid Temperature Cycling Offset – Restart
The CONDENSER screen displays a cutaway view of the chiller condenser. The liquid flow is animated to in­dicate flow through the condenser. All setpoints relat­ing to the condenser side of the chiller are maintained on this screen. With the proper access level this screen also serves as a gateway to controlling the Refrigerant Level. The following can also be viewed through this screen:
Display Only:
• Leaving Condenser Liquid Temperature
• Return Condenser Liquid Temperature
• Condenser Pressure
• Condenser Saturation Temperature
• Small Temperature Difference
• High Pressure Switch (Open/Closed)
• Condenser Liquid Flow Switch
• Condenser Liquid Pump (Run/Stop)
Programmable:
• High Pressure Warning Threshold
• Freeze Warning (Enabled/Disabled)
• Freeze Time
The COMPRESSOR screen displays a cutaway view of the chiller compressor, revealing the rotary screw, and shows all conditions associated with the compres­sor. The slide valve positioning is animated and with the proper Access level, it can be manually controlled. Animation of the compressor rotors indicates whether the chiller is presently in a RUN condition. This screen also serves as a gateway to sub-screens for calibrating the slide valve or configuring the optional Hot Gas By­pass. From this screen you can view the following:
Display Only:
• Differential Oil Pressure
• Oil Temperature
• Discharge Temperature
• Discharge Superheat
• Slide Valve Position
• Oil Return Solenoid (LED)
• Full-load Amps (E.M. Starter Only)
• Phase A, B, C Current (SSS Only)
Programmable:
• Slide Valve Load (Manual)
• Slide Valve Hold (Manual)
YORK INTERNATIONAL
7
Page 8
OptiView Control Center (continued)
FORM 160.81-EG1
• Slide Valve Unload (Manual)
• Slide Valve Auto
• Max. Load Temperature
• Minimum Load FLA
• Minimum Load Control Source
The HOT GAS BYPASS screen, accessed from the COMPRESSOR screen, displays a pictorial of the by­pass line and solenoid valve location on the chiller. The Hot Gas ON and OFF Setpoints are programmed on this screen and system parameters pertinent to Hot Gas Bypass operation are displayed. An LED illuminates when the Hot Gas solenoid is ON. If the chiller is equipped with the Hot Gas Bypass option, operation must be enabled on the OPERATIONS screen. From this screen you can perform the following:
Display Only:
• Slide Valve Position
• Return Chilled Liquid Temperature
• Leaving Chilled Liquid Temperature
• Hot Gas Solenoid (LED)
Programmable:
• On Setpoint
• Off Setpoint
The SLIDE VALVE CALIBRATION screen displays a cutaway view of the chiller compressor, revealing the rotary screw and slide valve and provides the capabil­ity of calibrating the slide valve. From this screen, you can perform the following:
Display Only:
• Slide Valve Loading (LED)
• Slide Valve Unloading (LED)
• Calibration Message
Programmable:
• Start Calibration
• Cancel Calibration
The OIL SEPARATOR screen displays a close-up view of the chiller oil separator/sump.
Display Only:
• Discharge Temperature
• Discharge Superheat
• Oil Pressure
• Discharge Pressure
8
• Differential Oil Pressure
• Differential Filter Pressure
• Oil Return Solenoid (LED)
• Evaporator Pressure
• Condenser Pressure
• Condenser Saturation
1. The MOTOR “soft” key on the HOME screen, when pressed, shows a picture of either a YORK Electro­Mechanical Starter or a Solid State Starter, depend­ing on chiller configuration. The Programmable pulldown demand to automatically limit motor load­ing can be used to minimize building demand charges. Pulldown time period control over four hours, and verification of time remaining in pulldown cycle from display readout. Separate digital setpoint for current limiting between 30 and 100%.
The ELECTRO-MECHANICAL STARTER (E–M) screen displays a picture of the starter and the follow­ing values. The ones below are common among both offerings and the values will be displayed on both types of starter screens. From this screen you can perform the following:
Display Only:
• Motor Run (LED)
• Motor Current % Full-load Amps
• Current Limit Setpoints
• Pulldown Demand Time Left
Programmable:
• Local Motor Current Limit
• Pulldown Demand Limit
• Pulldown Demand Time
The SOLID STATE STARTER (SSS) screen displays a picture of the starter and the following values, which are displayed in addition to the common ones listed above. From this screen, you can perform the following:
Display Only:
• Input Power kW
• kW Hours
• Starter Model
• Voltage – Phase A, B, C
• Current – Phase A, B, C
• Temperature – Phase A, B, C
YORK INTERNATIONAL
Page 9
FORM 160.81-EG1
Programmable:
• Full-load Amps
• Voltage Range
• Starting Current
• Open SCR
• Shorted SCR
• kWH Reset
The SETPOINTS screen provides a convenient loca­tion for programming the most common setpoints in­volved in the chiller control. The Setpoints are shown on other individual screens, but to cut down on need­less searching, they can all be found on this screen. This screen also serves as a gateway to a sub-screen for defining the setup of general system parameters. From this screen you can perform the following:
Display Only:
• Leaving Chilled Liquid Temperature – Setpoint
• Leaving Chilled Liquid Temperature Cycling – Shutdown
• Leaving Chilled Liquid Temperature Cycling – Restart
• Current Limit Setpoint
Programmable:
• Local Leaving Chilled Liquid Temperature – Range
• Local Leaving Chilled Liquid T emperature – Setpoint
• Leaving Chilled Liquid Temperature Cycling Offset – Shutdown
• Leaving Chilled Liquid Temperature Cycling Offset – Restart
• Remote Analog Input Range
• Local Motor Current Limit
• Pulldown Demand Limit
• Pulldown Demand Time
• Print
The SETUP is the top level of the general configura­tion parameters. It allows programming of the time and date, along with specifications as to how the time will be displayed. In addition, the chiller configuration as determined by the Micro Board program jumpers and program switches is displayed. From this screen you can perform the following:
Display Only:
• Chilled Liquid Pump Operation (Displays Standard or Enhanced)
• Anti-Recycle (Displays Disabled or Enabled)
• Power Failure Restart (Displays Manual or Automatic)
• Liquid Type (Displays Water or Brine)
Programmable:
• Set Date
• Set Time
• Clock (Enabled/Disabled)
• 12/24 Hour
The following six subscreens can be accessed from the SETUP screen:
The SCHEDULE screen contains more programmable values than a normal display screen. Each program­mable value is not linked to a specific button; instead, the select key is used to enable the cursor arrows and check key to program the Start/Stop times for any day of the week up to 6 weeks in advance. The user has the ability to define a standard set of Start/Stop times that are utilized every week or specify exceptions to create a special week.
Programmable:
• Exception Start/Stop Times
• Schedule (Enable/Disable)
• Repeat Sunday Schedule
• Standard Week Start/Stop Times
• Reset All Exception Days
• Select
• Print
YORK INTERNATIONAL
9
Page 10
OptiView Control Center (continued)
FORM 160.81-EG1
The USER screen allows definition of the language for the chiller to display and defines the unit of measure.
Programmable:
• System Language
• English/Metric Units
The COMMS screen allows the user to define commu­nications parameters.
Programmable:
• Chiller ID
• COM 2 Baud Rate
• COM 2 Data Bit(s)
• COM 2 Parity Bit(s)
• COM 2 Stop Bit(s)
• Printer Baud Rate
• Printer Data Bit(s)
• Printer Parity Bit(s)
• Printer Stop Bit(s)
The PRINTER screen permits the user to define com­munications Parameters for the Printer.
Display Only
• Time Remaining Until Next Print
Programmable
• Log Start Time
• Output Interval
• Automatic Printer Logging (Enabled/Disabled)
• Print Type
• Print Report
• Print All Histories
The SALES ORDER screen allows definition of the or­der parameters. Note: This information is loaded at the
factory or by the installation service technician.
The OPERATIONS screen permits definition of param- eters pertaining to operation of the chiller. What is de­fined is whether the control of the chiller will be Local, Digital Remote, Analog Remote, Modem Remote or ISN Remote.
Programmable
• Control Source
The HISTORY screen allows the user to browse through the last ten faults; either safety or cycling shutdowns with the conditions, while the chiller is running or stopped. The faults are color coded for ease in deter­mining the severity at a glance, recording the date, time and description. (See Display Messages for Color Code meanings.)
Display Only
• Last Normal Shutdown
• Last Fault While Running
• Last Ten Faults
Programmable:
• Print History
• Print All Histories
By pressing the VIEW DETAILS key you will move to the HISTORY DETAILS screen. From these screens you are able to see an on-screen printout of all the sys­tem parameters at the time of the selected shutdown.
Display Only:
• History Printout
Programmable:
• Page Up
• Page Down
• Print History
Display Only
• Model Number
• Panel Serial Number
• Chiller Serial Number
• YORK Order Number
• System Information
• Condenser and Evaporator Design Load Information
• Nameplate Information
10
Also under the HISTORY screen is the TRENDING screen, accessible by the key marked the same. On this screen, up to six operator-selected parameters, se­lected from a list of over 140, can be plotted in an X/Y graph format. The graph can be customized to record points once every second up to once every hour. There are two types of charts that can be created: single screen, or continuous screen. The single screen col­lects data for one screen width (450 data points across the X-axis), then stops. The continuous screen keeps
YORK INTERNATIONAL
Page 11
FORM 160.81-EG1
collecting the data, but the oldest data drops off the graph from left to right at the next data collection inter­val. For ease of identification, each plotted parameter, title and associated Y-axis labeling is color coordinated.
Display Only:
• This screen allows the user to view the graphical trending of the selected parameters and is a gate­way to the graph setup screens.
Programmable:
• Start
• Stop
• y-axis
• x-axis
The TREND SETUP screen is used to configure the trending screen. The parameters to be trended are se­lected from the Trend Common Slots screen, accessed from the Slot Numbers button or the Master Slot Num­bers List found in the Operating Manual. The interval at which all the parameters are sampled is selected under the Collection Interval button. The data point minimum and maximum values may be adjusted closer to in­crease viewing resolution.
DISPLAY MESSAGES
The Control Center continuously monitors the operat­ing system, displaying and recording the cause of any shutdowns (Safety, Cycling or Normal). The condition of the chiller is displayed at the System Status line that contains a message describing the operating state of the chiller; whether it is stopped, running, starting or shutting down. A System Details Line displays Warn­ing, Cycling, Safety, Start Inhibit and other messages that provide further details of the Status Bar messages. Messages are color-coded: Green – Normal Operations; Yellow – Warnings; Orange – Cycling Shutdowns; and Red – Safety Shutdowns to aid in identifying problems quickly.
Status messages include:
• System Ready To Start
• Cycling Shutdown – Auto Restart
• Safety Shutdown – Manual Restart
• Start Sequence Initiated
• System Run (with countdown timers)
• Start Inhibit
• Slide Valve Closing Before Shutdown
• System Lockout Delay
Programmable:
• Chart Type (select continuous or one screen)
• Collection Interval
• Select
• Data Point Slot Number (1 - 6)
• Data Point Min. (1 - 6)
• Data Point Max (1 - 6)
The TREND COMMON SLOTS screen displays the Master Slot Numbers List of the monitored parameters.
Display Only:
• Slot Numbers
Programmable:
• Page Up
• Page Down
• Print
Run Messages include:
• Leaving Chilled Liquid Control
• Motor Pulldown Limit
• Motor – High Current Limit
Start Inhibit Messages include:
• Anti-Recycle XX min/sec.
• Slide Valve – Position >30%
• Motor Current >15% FLA
• LCSSS – High-Temperature Phase X - Stopped
Warning Messages include:
• Real Time Clock Failure
• Setpoint Override
• Condenser – High Pressure Limit
• Evaporator – Low Pressure Limit
• Freeze Threat From Operating Chiller
• Freeze Threat, Condenser Flow Switch Open
• Low Discharge Superheat Limit
YORK INTERNATIONAL
11
Page 12
OptiView Control Center (continued)
FORM 160.81-EG1
• Low Discharge Superheat Detected
• Maximum Load – Load Limit
• Minimum Load – Load Limit
• Oil – Dirty Filter
• Oil – High Temperature
• Slide Valve Uncalibrated
Routine Shutdown Messages Include:
• Remote Stop
• Local Stop
• Place Compressor Switch In Run Position
Cycling Shutdown Messages Include:
• Multiunit Cycling – Contacts Open
• System Cycling – Contacts Open
• Control Panel – Power Failure
• Leaving Chilled Liquid – Low Temperature
• Leaving Chilled Liquid – Flow Switch Open
• Condenser – Flow Switch Open
• Motor Controller – Contacts Open
• Motor Controller – Loss of Current
• Power Fault
• Control Panel – Schedule
Solid State Starter Only (LCSSS)
• Initialization Failed
• Serial Communications
• Requesting Fault Data
• Stop Contacts Open
• Power Fault
• Low Phase (X) Temperature Sensor
• Run Signal
• Invalid Current Scale Selection
• Phase Locked Loop
• Low Supply Line Voltage
• High Supply Line Voltage
• Logic Board Processor
• Logic Board Power Supply
• Phase Loss
Safety Shutdown Messages include:
• Evaporator – Low Pressure
• Evaporator – Low Pressure – Smart Freeze
• Evaporator – Transducer or Leaving Liquid Probe
• Evaporator – Transducer or Temperature Sensor
• Condenser – High Pressure Contacts Open
• Condenser – High Pressure
• Condenser – Pressure Transducer Out of Range
• Auxiliary Safety – Contacts Closed
• Discharge – High Temperature
• Discharge – Low Temperature
• Oil – Low Differential Pressure
• Oil or Condenser Transducer Error
• Oil – Clogged Filter
• Oil – High Pressure
• Control Panel – Power Failure
• Watchdog – Software Reboot
Solid State Starter Only (LCSSS)
• Shutdown – Requesting Fault Data . . .
• High Instantaneous Current
• High Phase (X) Heatsink Temperature – Running
• 105% Motor Current Overload
• Motor or Starter – Current Imbalance
• Open SCR
• Phase Rotation
12
YORK INTERNATIONAL
Page 13

Mechanical Specifications

FORM 160.81-EG1
GENERAL
Each YORK M factory-packaged including evaporator, condenser , com­pressor, motor, OptiView control center and all inter­connecting unit piping and wiring. The chiller will be painted prior to shipment and will be packaged to pro­tect the unit during shipment.
Performance will be certified in accordance with ARI Standard 550/590.
The initial charge of refrigerant and oil will be supplied for each unit.
DRIVELINE
The compressor will be twin-screw, rotary-screw type. The compressor housing will be of cast iron, precision machined to provide minimal clearance for the rotors. The rotors will be manufactured from forged steel and use asymmetric profiles operating at a maximum speed of 3570 RPM (60 Hz) or 2975 RPM (50 Hz). The com­pressor will incorporate a complete anti-friction bearing design to reduce power and increase reliability; cylin­drical roller bearings to handle radial loads; and 4 point angular contact ball bearings to handle axial loads. The compressor will have an internal oil reservoir to assure a constant supply of oil to the bearings at all times. A check valve will be incorporated in the compressor hous­ing to prevent rotor backspin during shutdown.
Capacity control will be achieved by use of a slide valve to provide fully modulating control from 100% to 20% of full-load. The slide valve will be actuated by system differential pressure, controlled by external solenoid valves through the OptiView control center. The unit will be capable of operating with off-design cooling tower water during part-load operation in accordance with ARI Standard 550/590.
The motor will be 2-pole, continuous-duty, cage-induc­tion type, and will utilize suction gas cooling (semi-her­metic design). Motor full-load amperes at design condi­tions will not exceed chiller nameplate (FLA). Motor will be designed for use with the type starter specified.
LUBRICATION SYSTEM
An adequate supply of oil will be available to the com­pressor at all times. During operation, oil will be deliv­ered by positive system pressure differential.
An immersion oil heater will be provided, (temperature actuated), to effectively remove refrigerant from the oil during the chiller off-cycle. An external, replaceable car­tridge, oil filter will be provided, along with manual isola-
AXE YR Screw Chiller will be completely
tion stop valves for ease of servicing. An oil eductor will be provided to automatically remove oil which may have migrated to the evaporator, and return it to the compres­sor. The oil separator will be of a vertical design with no moving parts, and will provide high-efficiency oil separa­tion before the refrigerant enters the heat exchangers. The oil separator will be designed, tested, and stamped in accordance with the ASME Boiler and Pressure Ves­sel Code, Section VIII Division 1. Liquid refrigerant in­jection will be provided to maintain satisfactory oil tem­peratures and allow operation of the chiller over the full range of conditions.
EVAPORATOR
Evaporator will be of the shell-and-tube, flooded type designed for 235 PSIG (1620 kPa) working pressure on the refrigerant side, and will be tested in accordance with ASME code. The shell will be fabricated from rolled car­bon steel plate with fusion welded seams or carbon steel pipe; have carbon steel tube sheets, drilled and reamed to accommodate the tubes; and intermediate tube sup­ports spaced no more than four feet apart. The refriger­ant side will be designed, tested and stamped in accor­dance with the ASME Boiler and Pressure Vessel Code, Section VIII Division 1. Tubes shall be high-efficiency, internally and externally enhanced type having plain cop­per lands at all intermediate tube supports to provide maximum tube wall thickness at the support area. Each tube will be roller expanded into the tube sheets provid­ing a leak-proof seal, and be individually replaceable. Water velocity through the tubes will not exceed 12 fps. A liquid level sight glass will be located on the side of the shell to aid in determining proper refrigerant charge. The evaporator will have a refrigerant relief device to meet the requirements of the ASHRAE 15 Safety Code for Mechanical Refrigeration.
Water boxes will be removable to permit tube cleaning and replacement. Stubout water connections having victaulic grooves will be provided. Vent and drain con­nections with plugs will be provided on each water box.
CONDENSER
Condenser will be of the shell-and-tube type, designed for 235 psig (1620 kPa) working pressure on the refrig­erant side, and be tested in accordance with ASME code. The shell will be fabricated from rolled carbon steel plate with fusion welded seams or carbon steel pipe; have carbon steel tube sheets, drilled and reamed to accom­modate the tubes; and intermediate tube supports spaced no more than four feet apart. A refrigerant subcooler will be provided for improved cycle efficiency . The refrigerant side will be designed, tested and stamped in accordance with the ASME Boiler and Pres-
YORK INTERNATIONAL
13
Page 14
Mechanical Specifications (continued)
FORM 160.81-EG1
sure Vessel Code, Section VIII, Division 1. Tubes shall be high-efficiency, internally and externally enhanced type having plain copper lands at all intermediate tube supports to provide maximum tube wall thickness at the support area. Each tube will be roller expanded into the tube sheets providing a leak proof seal, and be indi­vidually replaceable. Water velocity through the tubes will not exceed 12 fps. The condenser will have refrig­erant relief devices to meet the requirements of the ASHRAE 15 Safety Code for Mechanical Refrigeration.
Water boxes will be removable to permit tube cleaning and replacement. Stubout water connections having victaulic grooves will be provided. Vent and drain con­nections with plugs will be provided on each water box.
REFRIGERANT SYSTEM
A modulating variable orifice controlled by the OptiV iew Control Center to accommodate varying head condi­tions will meter refrigerant flow to the evaporator.
The condenser shell will be capable of storing the en­tire system refrigerant charge during servicing. Service valves will be provided to facilitate removal of refriger­ant charge from the system.
The unit will be equipped with a suction strainer to pre­vent any foreign debris introduced to the system during maintenance or service to be allowed into the motor housing. Motors cooled by refrigerant must be protected by means of filter or strainer to protect the motor and prolong motor life.
OPTIVIEW CONTROL CENTER
General
The chiller will be controlled by a stand-alone micro­processor based control center. The chiller control panel will provide control of chiller operation and monitoring of chiller sensors, actuators, relays and switches.
Control Panel
The control panel will include a 10.4 inch diagonal color liquid crystal display (LCD) surrounded by “soft “ keys which are redefined based on the screen displayed at that time. It will be mounted in the middle of a keypad interface and installed in a locked enclosure. The screen will detail all operations and parameters, using a graphi­cal representation of the chiller and its major compo­nents. Panel verbiage is available in other languages as an option with English always available. Data can be displayed in either English or Metric units. Smart Freeze Point Protection will run the chiller at 36 °F (2.2°C) leav-
ing chilled water temperature, and not have nuisance trips on low water temperature. The sophisticated pro­gram and sensor will monitor the chiller water tempera­ture to prevent freeze up. When needed, Hot Gas By­pass is available as an option. The panel displays count­down timer messages so the operator knows when func­tions are starting and stopping. Every programmable point will have a pop-up screen with the allowable ranges, so that the chiller can not be programmed to operate outside of its design limits.
The control panel is provided with a thermal ice stor­age control mode to enhance system performance dur­ing ice building operation. In the thermal storage con­trol mode, the chiller will stay at 100% load until the setpoint shutdown temperature is reached. To add greater operating flexibility and eliminate unnecessary chiller cycling, two different Low Water (Liquid) Tem­perature Restart Thresholds are programmable, one for the ice mode and one for the standard cooling mode. The chiller has the capability to remain in the standard control mode for temperatures between 20 to 70°F (-
6.6 to 21.1°C) for applications involving a process or comfort cooling duty that requires leaving chilled liquid temperature setpoint control.
The chiller control panel also provides:
1. System operating information including: a. return and leaving chilled liquid temperature b. return and leaving condenser liquid
temperature
c. evaporator and condenser saturation
temperature
d. oil pressure at compressor and oil filter
differential e. percent motor current f. evaporator and condenser saturation
temperature g. compressor discharge temperature h. oil temperature i. percent slide valve position j. operating hours k. number of unit starts
2. Digital programming of setpoints through the uni­versal keypad including:
a. leaving chilled liquid temperature b. percent current limit c. pull-down demand limiting d. six-week schedule for starting and stopping the
chiller, pumps and tower
e. remote reset temperature range
14
YORK INTERNATIONAL
Page 15
FORM 160.81-EG1
3. Status messages indicating: a. system ready to start b. system running c. system coastdown d. system safety shutdown-manual restart e. system cycling shutdown-auto restart f. start sequence initiated g. start inhibit
4. The text displayed within the system status and system details field will be displayed as a color coded message to indicate severity: red for safety fault, orange for cycling faults, yellow for warnings, and green for normal messages.
5. Safety shutdowns enunciated through the display and the status bar, and consist of system status, system details, day, time, cause of shutdown, and type of restart required. Safety shutdowns with a fixed speed drive will include:
a. evaporator – low pressure b. evaporator – low pressure – smart freeze c. evaporator – transducer or leaving liquid probe d. evaporator – transducer or temperature sensor e. condenser – high pressure contacts open f. condenser – high pressure g. condenser – pressure transducer out of range h. auxiliary safety – contacts closed i. discharge – high temperature j. discharge – low temperature k. oil – low differential pressure l. oil or condenser transducer error m. oil – clogged filter n. oil – high pressure o. control panel – power failure p. watchdog – software reboot
5.1. Safety shutdowns with a Solid State Starter (LCSSS) will include:
a. shutdown – requesting fault data… b. high instantaneous current c. high phase (X) heatsink temperature - running d. 105% motor current overload e. motor or starter – current imbalance f. phase (X) shorted SCR g. open SCR h. phase rotation
6. Cycling shutdowns enunciated through the display and the status bar, and consists of system status, system details, day , time, cause of shutdown, and
type of restart required. Cycling shutdowns with a fixed speed drive will include:
a. multiunit cycling – contacts open b. system cycling - contacts open c. control panel - power failure d. leaving chilled liquid - low temperature e. leaving chilled liquid - flow switch open f. condenser – flow switch open g. motor controller – contacts open h. motor controller – loss of current i. power fault j. control panel - schedule
6.1. Cycling shutdowns with a Solid State Starter (LCSSS) will include:
a. initialization failed b. serial communications c. requesting fault data d. stop contacts open e. power fault f. low phase (X) temperature sensor g. run signal h. invalid current scale selection i. phase locked loop j. low supply line voltage k. high supply line voltage l. logic board processor m. logic board power supply n. phase loss
7. Security access to prevent unauthorized change of setpoints, to allow local or remote control of the chiller, and to allow manual operation of the slide valve. Access is through ID and password recog­nition, which is defined by three different levels of user competence: view, operator, and service.
8. Trending data with the ability to customize points of once every second to once every hour. The panel shall trend up to 6 different parameters from a list of over 140, without the need of an external moni­toring system.
9. The operating program stored in non-volatile memory (EPROM) to eliminate reprogramming the chiller due to AC power failure or battery discharge. Programmed setpoints will be retained in lithium battery-backed RTC memory for a minimum of 11 years with power removed from the system.
10. A fused connection through a transformer in the compressor motor starter to provide individual over-current protected power for all controls.
YORK INTERNATIONAL
15
Page 16
Mechanical Specifications (continued)
FORM 160.81-EG1
11. A numbered terminal strip for all required field in­terlock wiring.
12. An RS-232 port to output all system operating data, shutdown / cycling message, and a record of the last 10 cycling or safety shutdowns to a field-sup­plied printer. Data logs to a printer at a set pro­grammable interval. This data can be preprogrammed to print from 1 minute to 1 day.
13. The capability to interface with a building automa­tion system to provide:
a. remote chiller start and stop b. remote leaving chiller liquid temperature adjust c. remote current limit setpoint adjust d. remote ready to start contacts e. safety shutdown contacts f. cycling shutdown contacts g. run contacts
STARTUP AND OPERATOR TRAINING
The services of a factory-trained, field service repre­sentative will be provided to supervise the initial startup and conduct concurrent operator instruction.
CODES AND STANDARDS
• ASME Boiler and Pressure Vessel Code – Section Vlll Division 1.
• ARI Standard 550/590
• c/U.L. – Underwriters Laboratory
• ASHRAE 15 – Safety Code for Mechanical Refrig­eration
• ASHRAE Guideline 3 – Reducing Emission of Ha­logenated Refrigerants in Refrigeration and Air-Con­ditioning Equipment and Systems
• NEC – National Electrical Code
• OSHA – Occupational Safety and Health Act
ISOLATION MOUNTING
The unit is provided with four vibration isolation mounts consisting of 1" (25.4 mm) thick neoprene isolation pads for field mounting under the steel mounting pads lo­cated on the tube sheets.
REFRIGERANT CONTAINMENT
The standard unit has been designed as a complete and compact factory packaged chiller. As such, it has minimum joints from which refrigerant can leak. The entire assembly has been thoroughly leak tested at the factory prior to shipment. The YORK chiller in­cludes service valves conveniently located to facili­tate transfer of refrigerant to a remote refrigerant stor­age/recycling system. Optional condenser isolation valves permit storage of the charge in the condenser.
PAINT
Exterior surfaces are protected with one coat of Carib­bean blue, durable alkyd-modified, vinyl enamel, ma­chinery paint.
SHIPMENT
The unit shall be completely assembled, with all main, auxiliary, and control piping installed, controls wired, leak tests completed, functional run tests completed, and refrigerant charge in place. The oil charge, relief device and other miscellaneous materials shall be packed separately.
Protective covering is furnished on the Control Center and unit-mounted controls. The entire unit is then shrink­wrapped with high-quality reinforced plastic to provide maximum protection during transit. Water nozzles are capped with fitted plastic enclosures.
16
YORK INTERNATIONAL
Page 17

Accessories and Modifications

FORM 160.81-EG1
SOLID STATE STARTER
The Solid State Starter is a reduced voltage starter that controls and maintains a constant current flow to the motor during startup. It is compact and mounted on the chiller at the motor terminals. Power and control wiring is factory supplied. Available for 200-600 volts, the starter enclosure is NEMA-1 with a hinged access door with lock and key. Electrical lugs for incoming power wiring are provided.
Standard features include: digital readout at the OptiV­iew Control Center of the following:
Display Only:
• 3-phase voltage A, B, C
• 3-phase current A, B, C
• Input power (kW)
• kW Hours
• Starter Model
• Motor Run (LED)
• Motor Current % Full-load Amps
• Current Limit Setpoints
• Pulldown Demand Time Left
Programmable:
• Local Motor Current Limit
• Pulldown Demand Limit
• Pulldown Demand Time
FACTORY INSULATION OF EVAPORATOR
Factory-applied thermal insulation of the flexible, closed­cell plastic type, 3/4" (19mm) thick is attached with va­por-proof cement to the evaporator shell, flow cham­ber, evaporator tube sheets, suction connection, and (as necessary) to the auxiliary tubing. Not included is the insulation of water boxes and nozzles. This insula­tion will normally prevent condensation in environments with relative humidities up to 75% and dry bulb tem­peratures ranging from 50° to 90°F (10° to 32°C). 1-1/ 2" (38mm) thick insulation is also available for relative humidities up to 90% and dry bulb temperatures rang­ing from 50° to 90°F (10° to 32°C).
WATER FLANGES
Four 150 Ib. ANSI raised-face flanges, for condenser and evaporator water connections, are factory welded to water nozzles. Companion flanges, bolts, nuts and gaskets are not included.
SPRING ISOLATION MOUNTING
Spring Isolation mounting is available instead of stan­dard isolation mounting pads when desired. Four level­adjusting/spring-type vibration isolator assemblies with non-skid pads are provided with mounting brackets for field installation. Isolators are designed for one-inch (25.4 mm) deflection.
Other features include: low line voltage; 115-volt con­trol transformer; three-leg sensing overloads; phase ro­tation and single-phase failure protection; high tempera­ture safety protection; motor current imbalance and undervoltage safeties; open and close SCR protection; momentary power interruption protection. The LCSSS is cooled by a closed-loop, fresh water circuit consist­ing of a water-to-water heat exchanger and 1/25 HP circulating pump. All interconnecting water piping is factory installed and rated for 150 PSIG working pres­sure. Optional unit-mounted circuit breaker includes ground fault protection and provides 65,000 amp short­circuit withstand rating in accordance with UL Standard
508. A non-fused disconnect switch is also available. Both options are padlockable.
BAS REMOTE CONTROL
A communication interface permitting complete ex­change of chiller data with any BAS system is available with optional ISN translator. ISN translator also allows BAS system to issue commands to the chiller to control its operation. ISN translators come in two models, con­trolling up to four chillers and eight chillers respectively .
WATER FLOW SWITCHES
Paddle-type, vapor-proof water flow switches suitable for 150 psig (1034 kPa) DWP for chilled and condenser water circuits. Switch for 115V-1-50/60 Hz service. A chilled water flow switch is required. Condenser water flow switch is optional.
SEQUENCE CONTROL KIT
For two, three or four units with chilled water circuits connected in series or parallel, the kit consists of return water thermostat, lead-lag selector switch for sequence starting, and time delay relay , with NEMA-1 enclosures, designed for 115V-1-50/60 Hz.
STARTER – FIELD INSTALLED
A field installed, electro-mechanical compressor motor starter is available, selected for proper size and type for job requirements and in accordance with YORK En­gineering Standard R-1131 for Starters.
YORK INTERNATIONAL
17
Page 18
FORM 160.81-EG1
Accessories and Modifications (continued)
MARINE WATER BOXES
required to rig into tight spaces. This is particularly con­venient for existing buildings where equipment room
Marine water boxes allow service access for cleaning
access does not allow rigging a factory packaged chiller. of the heat exchanger tubes without the need to break the water piping. Bolted-on covers are arranged for con-
REFRIGERANT STORAGE/RECYCLING SYSTEM
venient access. Victaulic nozzle connections are stan­dard; flanges are optional. Marine water boxes are avail­able for condenser and/or evaporator.
A refrigerant storage/recycling system is a self-contained
package consisting of a refrigerant compressor with oil
separator, storage receiver , water-cooled condenser , fil-
KNOCK-DOWN SHIPMENT
ter drier and necessary valves and hoses to remove,
replace and distill refrigerant. All necessary controls and The chiller can be shipped knocked-down into major assemblies (evaporator, condenser, driveline, etc.) as
safety devices are a permanent part of the system. T ypi-
cally not required if unit isolation valves are provided.

SI Metric Conversion

The following factors can be used to convert from English to the most common Sl Metric values.
MEASUREMENT
MULTIPLY THIS
ENGLISH VALUE METRIC VALUE
BY
TO OBTAIN THIS
CAPACITY TONS REFRIGERANT EFFECT (ton) 3.516 KILOWATTS (kW)
POWER
FLOW RATE GALLONS / MINUTE (gpm) 0.0631 LITERS / SECOND (L/s)
LENGTH WEIGHT POUNDS (lb) 0.4536 KILOGRAMS (kg)
VELOCITY FEET / SECOND (fps) 0.3048 METERS / SECOND (m/s)
PRESSURE DROP
Integrated Part Load Value (IPLV)
In the English I-P system, IPLV is calculated by the fol-
KILOWATTS (kW) NO CHANGE KILOWATTS (kW)
HORSEPOWER (hp) 0.7457 KILOWATTS (kW)
FEET (ft) 304.8 MILLIMETERS (mm)
INCHES (in) 25.4 MILLIMETERS (mm)
FEET OF WATER (ft) 2.989 KILOPASCALS (k Pa)
POUNDS / SQ. INCH (psi) 6.895 KILOPASCALS (k Pa)
In SI Metric, the formula is:
IPLV* = 0.01A + 0.42B + 0.45C + 0.12D
lowing formula. A full explanation is shown on page 4:
1
IPLV*=
Where: A = kW / ton at 100% Load @ 85°F ECFT
0.01 ABCD
B = kW / ton at 75% Load @ 75°F ECFT C = kW / ton at 50% Load @ 65°F ECFT D = kW / ton at 25% Load @ 65°F ECFT
0.42
+
0.45
+
0.12
+
Where: A = COP at 100% Load @ 29.4°C ECFT
B = COP at 75% Load @ 23.9°C ECFT C = COP at 50% Load @ 18.3°C ECFT D = COP at 25% Load @ 18.3°C ECFT
NOTE:
* The Non-Standard Part-Load V alue (NPL V) uses the IPL V formula
with the following exceptions: the ECFT for part-load points varies linearly from the selected EFT to 65°F (18.3°C) from 100% to 50% loads, and fixed at 65°F (18.3°C) for 50% to 0% loads.
18
YORK INTERNATIONAL
Page 19

Application Data

FORM 160.81-EG1
The following is a user’s guide in the application and installation of MAXE Chillers, and will ensure the reli­ability and trouble-free life for which this equipment was designed. While this guide is directed towards normal, water-chilling applications, the YORK sales represen­tatives can provide complete recommendations on other types of applications.
Location
M
AXE Chillers are virtually vibration-free and generally
can be located at any level in a building where the con­struction will support the total system operating weight.
The unit site must be a floor, mounting pad or founda­tion which is level within 1/4" (6.4 mm) and capable of supporting the operating weight of the chiller.
Sufficient clearance to permit normal service and main­tenance work should be provided all around and above the unit. Additional space should be provided at one end of the unit to permit cleaning of evaporator and condenser tubes as required. A doorway or other prop­erly located opening may be used.
The chiller should be installed in an indoor location where temperatures range from 40°F to 1 10°F (4.4°C to 43.3°C).
Water Circuits Flow Rate – For normal water chilling duty, evaporator
flow rates are permitted at water velocity levels in the heat exchangers tubes of between 3 ft./second and 12 ft./sec­ond (0.91 m/s and 3.66 m/s). Condenser flow rates are permitted between 3.33 ft./sec. and 12 ft./sec. (1.01 m/s and 3.66 m/s). V ariable flow applications are possible, and initial chiller selections should be made accordingly to permit proper range of flow while maintaining the mini-
mum velocity noted above. V ariable flow in the condenser is not recommended, as it generally raises the energy con­sumption of the system by keeping the condenser pres­sure high in the chiller. Additionally, the rate of fouling in the condenser will increase at lower water velocities asso­ciated with variable flow, raising system maintenance costs. Cooling towers typically have narrow ranges of operation with respect to flow rates, and will be more effective with full design flow. Ref. Table 1 for flow limits.
Temperature Ranges – For normal water chilling duty, leaving chilled water temperatures may be selected be­tween 38°F (3.3°C) [36°F (2.2°C) with Smart Freeze en­abled) and 70°F (21.1°C) for water temperature ranges between 3°F and 30°F (1.7°C and 16.7°C).
Water Quality – The practical and economical application of liquid chillers requires that the quality of the water supply for the condenser and evaporator be analyzed by a water treatment specialist. Water quality may affect the perfor­mance of any chiller through corrosion, deposition of heat­resistant scale, or sedimentation or organic growth. These will degrade chiller performance and increase operating and maintenance costs. Normally , performance may be main­tained by corrective water treatment and periodic cleaning of tubes. If water conditions exist which cannot be corrected by proper water treatment, it may be necessary to provide a larger allowance for fouling, and/or to specify special mate­rials of construction.
General Piping – All chilled water and condenser water piping should be designed and installed in accordance with accepted piping practice. Chilled water and condenser water pumps should be located to discharge through the chiller to assure positive pressure and flow through the unit. Piping should include offsets to provide flexibility and should be arranged to prevent drainage of water from the
TABLE 1 – WATER FLOW RATE LIMITS – GPM (L/s)
SHELL
CODE
TB, VB
TC, VC
TD, VD
WB, XB
WC, XC
WD, XD
YORK INTERNATIONAL
PASS
1 3 83 (24.2) 1525 (96.2) 613 (38.7) 2204 (139.1) 2 1 92 (12.1) 762 (48.1) 307 (19.4) 1102 (69.5) 3 1 28 (8.1) 508 (32.1) 205 (12.9) 734 (46.3) 1 4 68 (29.5) 1866 (118.0) 683 (43.1) 2455 (154.9) 2 2 34 (14.8) 932 (58.8) 342 (21.6) 1227 (77.4) 3 1 57 (9.9) 621 (39.2) 228 (14.4) 818 (51.6) 1 5 70 (36.0) 2277 (143.7) 771 (48.7) 2774 (175.0) 2 2 86 (18.0) 1 1 3 8 (71.8) 386 (24.4) 1386 (87.5) 3 ––– ––– ––– ––– ––– ––– ––– ––– 1 6 93 (43.7) 2771 (174.9) 866 (54.6) 3462 (218.5) 2 3 46 (21.8) 1385 (87.4) 433 (27.3) 1731 (109.2) 3 2 31 (14.6) 924 (58.3) 289 (18.2) 1154 (72.8) 1 8 22 (51.9) 3287 (207.4) 1082 (68.3) 4328 (273.1) 2 411 (25.9) 1644 (103.7) 541 (34.1) 2164 (136.5) 3 2 74 (17.3) 1096 (69.2) 361 (22.8) 1443 (91.1) 1 9 86 (62.2) 3945 (248.9) 1350 (85.2) 5400 (340.1) 2 4 93 (31.1) 1972 (124.4) 675 (42.6) 2700 (170.0) 3 ––– ––– ––– ––– ––– ––– ––– –––
MINIMUM
EVAPORATOR CONDENSER
MAXIMUM
MINIMUM
MAXIMUM
19
Page 20
Application Data (continued)
FORM 160.81-EG1
evaporator and condenser when the pumps are shut off. Piping should be adequately supported and braced inde­pendently of the chiller to avoid the imposition of strain on chiller components. Hangers must allow for alignment of the pipe. Isolators in the piping and in the hangers are highly desirable in achieving sound and vibration control.
Convenience Considerations – T o facilitate the perfor­mance of routine maintenance work, some or all of the following steps may be taken by the purchaser. Evapora­tor and condenser water boxes are equipped with plugged vent and drain connections. If desired, vent and drain valves may be installed with or without piping to an open drain. Pressure gauges with stop cocks, and stop valves, may be installed in the inlets and outlets of the condenser and chilled water line as close as possible to the chiller. An overhead monorail or beam may be used to facilitate servicing.
Connections – The standard chiller is designed for 150 psig (1034 kPa) design working pressure in both the chilled water and condenser water circuits. The con­nections (water nozzles) to these circuits are furnished with grooves for Victaulic couplings. Piping should be arranged for ease of disassembly at the unit for tube cleaning. All water piping should be thoroughly cleaned of all dirt and debris before final connections are made to the chiller.
Chilled Water – A flow switch must be installed in the chilled water line of every unit. The switch must be lo­cated in the horizontal piping close to the unit, where the straight horizontal runs on each side of the flow switch are at least five pipe diameters in length. The switch must be electrically connected to the chilled water inter­lock position in the unit control center. A water strainer of maximum 1/8" (3.2 mm) perforated holes must be field­installed in the chilled water inlet line as close as pos­sible to the chiller. If located close enough to the chiller, the chilled water pump may be protected by the same strainer. The flow switch and strainer assure chilled wa­ter flow during unit operation. The loss or severe reduc­tion of water flow could seriously impair the chiller per­formance or even result in tube freeze-up.
°F Min ECWT = LCHWT + 16 + [(% load/100) x
(10 - full-load condenser water T)]
°C Min ECWT = LCHWT + 8.9 + [(% load/100) x
(5.6 - full-load condenser water T)]
Where: ECWT = entering condenser water temperature
LCHWT = leaving chilled water temperature
MULTIPLE UNITS Selection – Many applications require multiple units to
meet the total capacity requirements as well as to pro­vide flexibility and some degree of protection against equipment shutdown. There are several common unit arrangements for this type of application. The M chiller has been designed to be readily adapted to the requirements of these various arrangements.
Parallel Arrangement (Refer to Fig. 1) – Chillers may be applied in multiples with chilled and condenser wa­ter circuits connected in parallel between the units. Fig. 1 represents a parallel arrangement with two chillers. Parallel chiller arrangements may consist of equally or unequally sized units. When multiple units are in op­eration, they will load and unload at equal percentages of design full-load for the chiller.
Depending on the number of units and operating char­acteristics of the units, loading and unloading schemes should be designed to optimize the overall efficiency of the chiller plant. It is recommended to use an evaporator bypass piping arrangement to bypass fluid around evapo­rator of any unit which has cycled off at reduced load conditions. It is also recommended to alternate the chiller cycling order to equalize chiller starts and run hours.
AXE
Condenser Water – The chiller is engineered for maxi­mum efficiency at both design and part-load operation by taking advantage of the colder cooling tower water temperatures which naturally occur during the winter months. Appreciable power savings are realized from these reduced heads.
The minimum entering condenser water temperature for other full and part-load conditions is provided by the following equation:
20
LD00507
FIG. 1 –
Series Arrangement (Refer to Fig. 2) The chillers
may be applied in pairs with chilled water circuits con-
PARALLEL EVAPORATORS PARALLEL CONDENSERS
YORK INTERNATIONAL
Page 21
FORM 160.81-EG1
nected in series and condenser water circuits connected in parallel. All of the chilled water flows through both cool­ers with each unit handling approximately one-half of the total load. When the load decreases to a customer se­lected load value, one of the units will be shut down by a sequence control. Since all water is flowing through the operating unit, that unit will cool the water to the de­sired temperature.
LD00508
FIG. 2 – SERIES EVAPORATORS
P ARALLEL CONDENSERS
BRINE APPLICA TIONS
The YR Screw Chiller , utilizing the Frick Refrigeration com­pressor, is a good match for the high head requirements of low temperature brine applications. This is particularly true of thermal ice storage systems, typically requiring 22°F (–5.6°C) to 24°F (–4.4°C) leaving brine temperatures. This performance is enhanced with the standard thermal stor­age control mode described on page 6.
Particular attention must be paid to the application of two or more chillers with evaporators in parallel or se­ries when the brine temperature is below 32°F (0°C). The brine MUST NOT flow through the evaporator of the idle chiller, because it can cause the condenser wa­ter to freeze. A bypass or other type of arrangement is required that shuts off flow to the idle evaporator . When units are applied in series with lead/lag capability, the units should be identical.
REFRIGERANT RELIEF PIPING
Each chiller is equipped with pressure relief devices. The purpose of the relief devices is to quickly relieve excess pressure of the refrigerant charge to atmosphere, as a safety precaution in the event of an emergency such as a fire. They are set to relieve at an internal pressure of 235 psig (1620 kPa) and are located on the condenser, evaporator and oil separator; and are pro­vided in accordance with ASHRAE 15 Safety Code and ASME or applicable pressure vessel code. Under these circumstances the relief devices may be relief valves,
overflow valves or type tested Safety Pressure switches or a combination of these devices.
Sized to the requirements of applicable codes, a vent line must run from the relief device to the outside of the building. This refrigerant relief piping must include a cleanable, vertical-leg dirt trap to catch vent-stack con­densation. Vent piping must be arranged to avoid im­posing a strain on the relief connections and should include one flexible connection.
SOUND AND VIBRATION CONSIDERATIONS
A M
AXE chiller is not a source of objectionable sound
and vibration in normal air conditioning applications. Neo­prene isolation mounts are furnished as standard with each unit. Optional level-adjusting spring isolator assem­blies designed for 1" static deflection are available.
M
AXE chiller sound pressure level ratings will be fur-
nished upon request. Control of sound and vibration transmission must be taken
into account in the equipment room construction as well as in the selection and installation of the equipment.
THERMAL INSULATION
No appreciable operating economy can be achieved by thermally insulating the chiller. However , the chiller’s cold surfaces should be insulated with a vapor barrier insulation sufficient to prevent condensation. A chiller can be factory insulated with 3/4" (19mm) or 1-1/2" (38mm) thick insulation, as an option. This insulation will normally prevent condensation in environments with dry bulb temperatures of 50°F to 90°F (10°C to 32°C) and relative humidities up to 75% [3/4" (19mm) thickness] or 90% [1-1/2" (38mm) thickness]. The in­sulation is painted and the surface is flexible and rea­sonably resistant to wear. It is intended for a chiller installed indoors and, therefore, no protective cover­ing of the insulation is usually required. If insulation is applied to the water boxes at the job site, it must be removable to permit access to the tubes for routine maintenance.
VENTILATION
The ASHRAE Standard 15 Safety Code for Mechani­cal Refrigeration requires that all machinery rooms be vented to the outdoors utilizing mechanical ventilation by one or more power-driven fans. This standard, plus National Fire Protection Association Standard 90A, state, local and other related codes should be reviewed for specific requirements.
YORK INTERNATIONAL
21
Page 22
Application Data (continued)
FORM 160.81-EG1
In addition, the ASHRAE Standard 15 requires a refriger­ant vapor detector to be employed for all refrigerants. It is to be located in area where refrigerant from a leak would be likely to concentrate. An alarm is to be activated and the mechanical ventilation started at a value no greater than the TL V (Threshold Limit V alue) of the refrigerant.
ELECTRICAL CONSIDERATIONS Motor Voltage – Low voltage motors (200 - 600 volts)
are furnished with six leads. Motor circuit conductor size must be in accordance with the National Electrical Code (NEC), or other applicable codes, for the motor full­load amperes (FLA). Flexible conduit should be used for the last several feet to the chiller in order to provide vibration isolation. Table 2 lists the allowable variation in voltage supplied to the chiller motor. The unit name­plate is stamped with the specific motor voltage and fre­quency for the appropriate motor.
TABLE 2 – MOTOR VOLTAGE VARIATIONS
FREQ.
60 HZ
50 HZ
RA TED
VOLTAGE
200 200/208 180 220 230 220/240 208 254 380 380 342 415 460 440/460/480 414 508 575 575/600 520 635 380 380/400 342 423 415 415 374 440
NAMEPLATE
VOLTAGE
OPERATING VOL T AGE
MIN. MAX.
Starters – The chiller is available with a factory-mounted
and wired YORK Solid State Starter for 200 - 600 volt applications. Other types of remote mounted starters are available. These electro-mechanical starters must be furnished in accordance with YORK Standard R-
1131. Specification. This will ensure that starter com­ponents, controls, circuits, and terminal markings will be suitable for required overall system performance.
Controls – A 115 volt, single phase, 60 or 50 Hertz (4.5 kV a) power supply must be furnished to the chiller from a separate, fused disconnect or from a control transformer included as an option with electro-mechani­cal starters. No field control wiring is required, when the YORK SSS is supplied.
Copper Conductors – Only copper conductors should be connected to compressor motors and starters. Alu-
minum conductors have proven to be unsatisfactory when connected to copper lugs. Aluminum oxide and the difference in thermal conductivity between copper and aluminum cannot guarantee the required tight con­nection over a long period of time.
Power Factor Correction Capacitors – Capacitors can be applied to a chiller for the purpose of power factor correction. For remote-Mounted Electro-Mechanical Starters, the capacitors should be located on the load side of the starter. For YORK SSS, the capacitors must be located on the line side of the starter. The capacitors must be sized and installed to meet the National Elec­trical Code (NEC) and be verified by YORK.
Ampacity on Load Side of Starter – Electrical power wire size to the chiller is based on the minimum unit ampacity. For YORK SSS, this wiring is done at the factory . For remote starters, the National Electrical Code defines the calculation of ampacity , as summarized be­low. More specific information on actual amperage rat­ings will be supplied with the submittal drawings.
• Six-lead type of starting (Star-Delta) Minimum circuit ampacity per conductor (1 of 6):
Ampacity = .721 x compressor motor amps.
• Three-lead type of starting (Across-the-Line, Autotransformer and Primary Reactor)
Minimum circuit ampacity per conductor (1 of 3): Ampacity = 1.25 x compressor motor amps.
Ampacity on Line Side of Starter –
The only additional load on the circuit for the chiller would be the control transformer, unless it is supplied by a separate source.
Min. Circuit Ampacity =
125% of compr. + FLA of all other
motor amps loads on the circuit
Branch Circuit Overcurrent Protection – The branch circuit overcurrent protection device(s) should be a time­delay type, with a minimum rating equal to the next stan­dard fuse/breaker rating above the calculated value. It is calculated taking into account the compressor motor amps and may also include control transformer. Refer to submittal drawings for the specific calculations for each application.
MOTOR ELECTRICAL DATA
The full-load amperes (FLA) listed in Tables 3 and 4 are maximum values and correspond to the maximum motor kW listed. When the Input power (kW) is less than maximum motor kW, the FLA should be reduced using the following equation:
22
YORK INTERNATIONAL
Page 23
FORM 160.81-EG1
FLA =
Motor kW
Max. Motor kW
x Max. Motor FLA
The locked rotor amperes (LRA) are read directly from T ables 3 and 4 for specific Motor Code and voltage. This is because the LRA is dependent only on motor size and
The benefit from the FLA correction is the possible use
voltage and is independent of input power (kW).
of smaller power wiring and/or starter size.
Inrush amperes (IRA) depend on LRA and the type of starter applied. The inrush can be calculated using a percentage of LRA shown in Table 5.
TABLE 3 – 60 HZ ELECTRICAL DATA
NAME­COMP. PLATE
T0/T1 380 438 1727 89.3 94.6 89.3 95.0 89.2 95.4 88.5 95.7 87.8 96.0 85.1 96.1 82.4 96.2 73.5 95.6 64.6 95.0 251.6
T2/T3 380 464 2130 90.3 94.8 90.1 95.2 89.9 95.5 89.1 95.8 88.2 96.0 85.6 96.0 82.9 96.0 73.8 95.3 64.7 94.6 275.9
AMP
(MAX)
VOLT.
FLA LR A PF EFF PF EFF PF EFF PF EFF P F EFF PF EFF P F EFF PF EFF PF EFF KW (hp)
200 850 3634 88.2 94.8 87.8 95.2 87.3 95.5 85.8 95.7 84.3 95.9 80.4 96.0 76.5 96.0 65.8 95.2 55.1 94.4 208 825 3779 86.6 95.0 85.6 95.3 84.6 95.5 82.6 95.7 80.5 95.9 75.5 95.8 70.5 95.7 59.0 94.8 47.4 93.8 230 725 2901 89.2 94.5 89.1 95.0 89.0 95.4 88.2 95.7 87.3 96.0 84.5 96.1 81.6 96.2 72.4 95.6 63.1 94.9 240 695 3027 88.2 94.9 87.7 95.2 87.2 95.5 85.8 95.8 84.3 96.0 80.4 96.0 76.5 96.0 65.8 95.2 55.0 94.4
440 370 1390 89.6 94.2 89.8 94.7 90.0 95.2 89.6 95.6 89.2 95.9 87.2 96.1 85.2 96.3 77.7 95.9 70.1 95.4 (321) 460 354 1453 89.2 94.6 89.1 95.0 88.9 95.4 88.1 95.7 87.3 96.0 84.5 96.1 81.6 96.2 72.4 95.6 63.1 94.9 480 339 1516 88.2 94.9 87.7 95.2 87.2 95.5 85.8 95.8 84.3 96.0 80.4 96.0 76.5 96.0 65.8 95.2 55.0 94.4 575 300 1162 89.2 94.6 89.1 95.0 88.9 95.4 88.1 95.7 87.3 96.0 84.4 96.1 81.5 96.2 72.3 95.6 93.1 95.0 600 288 1213 88.2 94.9 87.7 95.3 87.2 95.6 85.8 95.8 84.3 96.0 80.4 96.0 76.5 96.0 65.8 95.3 55.0 94.5 200 882 4048 90.4 94.8 90.2 95.2 90.0 95.5 89.2 95.8 88.3 96.0 85.6 96.0 82.9 96.0 73.8 95.3 64.7 94.6 208 860 4210 89.1 95.0 88.5 95.3 87.8 95.6 86.4 95.8 94.9 96.0 81.3 96.0 77.6 95.9 67.1 95.0 56.5 94.1 230 760 3520 90.5 94.7 90.4 95.1 90.2 95.4 89.5 95.7 88.7 95.9 86.2 96.0 83.7 96.0 75.0 95.4 66.3 94.7 240 737 3673 89.3 95.0 88.8 95.3 88.3 95.5 86.9 95.7 85.4 95.9 81.9 95.9 78.3 95.9 67.9 95.0 57.5 94.1
440 400 1603 91.0 94.4 91.2 94.9 91.4 95.3 91.1 95.6 90.8 95.9 89.3 96.1 87.7 96.2 80.9 95.7 74.0 95.1 (351) 460 383 1676 90.5 94.7 90.4 95.1 90.2 95.5 89.5 95.8 88.7 96.0 86.2 96.1 83.7 96.1 75.0 95.4 66.2 94.7 480 372 1749 89.3 95.0 88.8 95.3 88.2 95.6 86.8 95.8 85.4 96.0 81.8 96.0 78.2 95.9 67.9 95.0 57.5 94.1 575 305 1408 90.7 94.7 90.7 95.1 90.6 95.5 90.0 95.8 89.4 96.0 87.2 96.1 85.0 96.2 77.0 95.5 68.9 94.8 600 293 1469 89.9 95.0 89.5 95.3 89.1 95.6 88.0 95.8 86.9 96.0 83.8 96.0 80.7 96.0 71.0 95.2 61.2 94.4
100% 90% 80% 70% 60% 50% 40% 30% 20% MAX.
MOTOR DATA
NOTE: FLA = Full-load Amps; LRA = Locked Rotor Amps; PF = Power Factor; EFF = Motor Ef ficiency
100% Loading is Percentage of Maximum Motor Load; not of Specific Application
YORK INTERNATIONAL
23
Page 24
TABLE 4 – 50 HZ ELECTRICAL DATA
FORM 160.81-EG1
NAME­COMP. PLATE
T0/T1 4 00 348 1488 88.2 94.1 87.7 94.6 87.2 95.0 85.9 95.3 84.5 95.6 80.4 95.7 76.3 95.7 65.6 94.9 54.9 94.1
T2/T3 400 371 1725 89.6 94.4 89.1 94.8 88.6 95.2 87.3 95.5 85.9 95.7 82.4 95.8 78.9 95.8 68.5 95.1 58.1 94.3
NOTE: FLA = Full-load Amps; LRA = Locked Rotor Amps; PF = Power Factor; EFF = Motor Efficiency
AMP
(MAX)
VOLT.
FLA LR A PF EFF PF EFF PF EFF PF EFF P F EFF PF EFF P F EFF PF EFF PF EFF KW (hp)
380 364 1414 89.3 93.7 89.2 94.3 89.1 94.8 88.4 95.2 87.7 95.6 84.9 95.8 82.1 95.9 73.3 95.3 64.5 94.7
415 333 1544 89.2 93.8 89.1 94.4 88.9 94.9 88.1 95.3 87.3 95.6 84.3 95.8 81.3 95.9 72.2 95.3 93.1 94.6 380 390 1639 90.4 94.0 90.3 94.5 90.1 94.9 89.4 95.3 88.6 95.6 86.2 95.8 83.7 96.0 75.2 95.4 66.6 94.8
415 354 1790 90.4 94.0 90.3 94.5 90.1 94.9 89.3 95.3 88.5 95.6 86.1 95.8 83.6 95.9 75.1 95.4 66.5 94.8
100% Loading is Percentage of Maximum Motor Load; not of Specific Application
100% 90% 80% 70% 60% 50% 40% 30% 20% MAX.
MOTOR DATA
TABLE 5 – MOTOR STARTERS
TYPE
STARTER
60HZ
50 HZ
TRANSITION
% TAP
INRUSH
AS A % OF LRA
SOLID STATE
STARTER
200-600 380-415
NONE
— 45
ST AR DELTA AUTO TRANSFORMER
200-600 380-415
CLOSED
33
200-600 380-415
OPEN
— 33
200-600 380-415
CLOSED
57.7 33
200-600 380-415
CLOSED
65
42.3
200-600 380-415
CLOSED
80 64
ACROSS
THE LINE
200-600 380-415
— —
100
210.2 (267)
231.9 (292)
TABLE 6 – AVAILABLE COMPRESSOR/SHELL COMBINATIONS
COMPRESSOR EVAPORATOR CONDENSER
CODE SHELL SHELL T0, T1
T1 WB, WC, WD WB, WC, WD
T2/T3
TB, TC, TD TB, TC, TD VB, VC, VD VB, VC, VD
WB, WC, WD WB, WC, WD
XB, XC, XD XB, XC, XD
24
YORK INTERNATIONAL
Page 25
OPTIVIEW GRAPHIC CONTROL CENTER
OPTIONAL UNIT MOUNTED SOLID STA TE STARTER
FORM 160.81-EG1
2-STAGE HIGH EFFICIENCY OIL SEP ARA TO R
MOTOR END
CONDENSER SIGHT GLASS
LIQUID LINE VARIABLE ORIFICE
COMPRESSOR END
00562VIP
YORK INTERNATIONAL
25
Page 26

Dimensions

FORM 160.81-EG1
MOTOR
END
8-1/2"
(216 mm)
MOTOR
END
RELIEF VALVES (SEE TABLE)
L
2' - 3-1/2" (698 mm)
M
OPTIVIEW
CONTROL PANEL
MOTOR
COMPRESSOR
TOP VIEW
SOLID STATE STARTER
(OPTIONAL)
COMPRESSOR
END
RELIEF VALVE (SEE TABLE)
ISOLATION VALVE
NOTE: OPTIONAL
RELIEF VALVES*
LOCATION
WITH ISOLATION WITHOUT ISOLATION
VALVES VALVES
EVAPORATOR 1" SINGLE 1" DUAL CONDENSER 1" DUAL 1" SINGLE DISCHARGE LINE
1-1/4" SINGLE NONE
*All are NPT female
OIL SEPARATOR
COMPRESSOR
END
ISOLATION VALVE
NOTE: OPTIONAL
RELIEF VALVE
NOTE: ONLY SUPPLIED ON UNITS WITH OPTIONAL ISOLATION VALV ES
2' - 6-1/4" (768 mm)
3'-8-3/4 "
(1136.7 mm)
K
U
B
C
A
H
FRONT OF UNIT
P
J
B
CONDENSER
F
D
EVAPORATOR
C
E
SECTION A - A
FIG . 3 – T0 & T3 COMPRESSORS – EV APORA T OR, CONDENSER AND W A TER BOXES DIMENSIONS
26
YORK INTERNATIONAL
G
LD07981
Page 27
FORM 160.81-EG1
EVAPORATOR – CONDENSER SHELL CODES
DIM. T0 & T1 COMPRESSORS T1 COMPRESSORS T2 & T3 COMPRESSORS
T - T V - V T - T V - V W - W W - W W - W X - X W - W X - X
A 10'–0" 14'–0" 3048 mm 4267 mm 12'–0" 3657 mm 12'–0" 16'-0" 3658 mm 4877 mm B 7'–5-1/8" 7'–5-1/8" 2264 mm 2264 mm 7'–9-3/4" 2381 mm 8'–10-7/8" 8'–10-7/8" 2715 mm 2715 mm C 5'–1" 5'–1" 1550 mm 1550 mm 5'–6" 1676 mm 5'–6" 5'–6" 1676 mm 1676 mm D 2'–6" 2'–6" 762 mm 762 mm 2'–7" 787 mm 2'–7" 2'–7" 787 mm 787 mm E 2'–7" 2'–7" 787 mm 787 mm 2'–11" 889 mm 2'–11" 2'–11" 889 mm 889 mm F 1'–3" 1'–3" 381 mm 381 mm 1'–3-1/2" 114 mm 1'–3-1/2" 1'–3-1/2" 394 mm 394 mm G 1'–3-1/2" 1'–3-1/2" 394 mm 394 mm 1'–5-1/2" 165 mm 1'–5-1/2" 1'–5-1/2" 445 mm 445 mm L 2-3/4" 2'– 2-3/4" 70 mm 679 mm 2-3/4" 70 mm 2-3/4" 2'–2-3/4" 70 mm 679 mm M 1'–3" 3'–3" 381 mm 991 mm 1'–3" 381 mm 1'–3" 3'–3" 381 mm 991 mm
WATER BOX DIMENSIONS (FT. - IN)
DIM.
1 PASS 2 PASS 3 PASS 1 PASS 2 PASS 3 PASS
EVAPORATORS T & V CONDENSER T & V
H 1'–2-3/4" 1'–1-1/2" 1'–1-1/2" J 1'–2-3/4" 1'–0-1/2" 1'–0-1/2"
DIM. REAR HEAD 2 PASS REAR HEAD 2 PASS
K 8-3/4" 7-5/8"
WATER BOX DIMENSIONS (mm)
DIM.
1 PASS 2 PASS 3 PASS 1 PASS 2 PASS 3 PASS
EVAPORATORS T & V CONDENSER T & V
H 375 343 343 J 375 318 318
DIM. REAR HEAD 2 PASS REAR HEAD 2 PASS
K 222 194
WATER BOX DIMENSIONS (FT. - IN)
DIM.
1 PASS 2 PASS 3 PASS 1 PASS 2 PASS 3 PASS
EVAPORATORS W & X CONDENSER W & X
H 1'–2-1/4" 1'–2-1/4" 1'–2-1/4" J 1'–2-1/4" 1'–2-1/4" 1'–2-1/4"
DIM. REAR HEAD 2 PASS REAR HEAD 2 PASS
K 5-5/8" 5-5/8"
WATER BOX DIMENSIONS (mm)
DIM.
1 PASS 2 PASS 3 PASS 1 PASS 2 PASS 3 PASS
EVAPORATORS W & X CONDENSER W & X
H 362 362 362 J 362 362 362
DIM. REAR HEAD 2 PASS REAR HEAD 2 PASS
K 143 143
YORK INTERNATIONAL
27
Page 28
FORM 160.81-EG1

Dimensions (Ft.-In.) – Nozzle Arrangements

EVAPORATORS – COMPACT W ATER BOXES
REAR
OF UNIT
AH
CC CC
REAR
OF UNIT
REAR
OF UNIT
EVAPORATOR
1" 1"
MOTOR END COMPRESSOR END
DD
BB
EVAPORATOR EVAPORATOR
1"
MOTOR END COMPRESSOR END
GG GG
FLOOR LINE
B
C
GG GG
FLOOR LINE
EVAPORATOR
REAR
OF UNIT
1-PASS
NOZZLE
ARRANGEMENTS
NO. OF EVAP.
PASSES IN OUT
1
REAR
OF UNIT
J
K
DD
BB
1"
REAR
OF UNIT
ARRANGEMENTS
NO. OF EVAP.
PASSES IN OUT
2
NOTE: Water must enter through bottom connection to achieve rated performance.
AH HA
2-PASS
NOZZLE
CB KJ
3-PASS
NOZZLE
ARRANGEMENTS
NO. OF EVAP.
PASSES IN OUT
3
GN
PF
DD
F
G
BB
EVAPORATOR EVAPORATOR
N
P
DD
BB
NOTE: Water must enter
1" 1"
MOTOR END COMPRESSOR END
GG GG
FLOOR LINE
EVAPORATOR NOZZLE PIPE SIZE
SHELL
CODE
NO. OF PASSES 1-PASS 2-PASS 3-PASS
123CC
2
GG BB
through bottom connection to achieve rated performance.
EVAPORATOR
NOZZLE DIMENSIONS
2
DD
2
GG BB
2
LD07615
DD GG
T, V 8" 6" 4" 1'–10-3/4" 1'–3-1/2" 1'–3" 2'–6-1/2" 1'–3-1/2" 1'–3" 2'–6-1/2" 1'–3-1/2"
W, X 10" 8" 6" 2'–0-3/4" 1'–5-1/2" 1'–4-3/4" 2'–8-3/4" 1'–5-1/2" 1'–4-3/4" 2'–8-3/4" 1'–5-1/2"
NOTES:
1. Standard water nozzles are furnished as welding stub-outs with Victaulic grooves, allowing the option of welding, flanges, or use of Victaulic couplings. Factory installed, class 150 (ANSI B16.5, round slip-on, forged carbon steel with 1/16" raised face), water flanged nozzles are optional (add 1/2" to nozzle length). Companion flanges, nuts, bolts, and gaskets are not furnished.
2. Add 1" for isolators as shown.
3. One-, two- and three-pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of evaporator nozzles may be used in combination with any pair of condenser nozzles.
4. Connected piping should allow for removal of compact water boxes for tube access and cleaning.
5. Rear of unit is defined as side of chiller opposite control center.
28
YORK INTERNATIONAL
Page 29
FORM 160.81-EG1

Dimensions (mm) – Nozzle Arrangements

EVAPORATORS – COMPACT WATER BOXES
REAR
OF UNIT
AH
CC CC
REAR
OF UNIT
REAR
OF UNIT
EVAPORATOR
1" 1"
MOTOR END COMPRESSOR END
DD
BB
EVAPORATOR EVAPORATOR
1"
MOTOR END COMPRESSOR END
GG GG
FLOOR LINE
B
C
GG GG
FLOOR LINE
EVAPORATOR
REAR
OF UNIT
1-PASS
NOZZLE
ARRANGEMENTS
NO. OF EVAP.
PASSES IN OUT
1
REAR
OF UNIT
AH HA
2-PASS
NOZZLE
J
K
DD
BB
1"
REAR
OF UNIT
ARRANGEMENTS
NO. OF EVAP.
PASSES IN OUT
2
NOTE: Water must enter through bottom connection to achieve rated performance.
CB KJ
3-PASS
F
G
DD
BB
EVAPORATOR EVAPORATOR
1" 1"
MOTOR END COMPRESSOR END
GG GG
FLOOR LINE
EVAPORATOR NOZZLE PIPE SIZE
SHELL
CODE
NO. OF PASSES 1-PASS 2-PASS 3-PASS
123CC
N
P
DD
BB
PASSES IN OUT
NOTE: Water must enter through bottom connection to achieve rated performance.
EVAPORATOR
NOZZLE DIMENSIONS
2
GG BB
2
DD
NOZZLE
ARRANGEMENTS
NO. OF EVAP.
3
2
GN PF
GG BB
2
LD07615
DD GG
T, V 8" 6" 4" 578 343 330 775 343 330 775 394
W, X 10" 8" 6" 629 445 425 832 445 425 832 445
NOTES:
1. Standard water nozzles are furnished as welding stub-outs with Victaulic grooves, allowing the option of welding, flanges, or use of Victaulic couplings. Factory installed, class 150 (ANSI B16.5, round slip-on, forged carbon steel with 1/16" raised face), water flanged nozzles are optional (add 1/2" to nozzle length). Companion flanges, nuts, bolts, and gaskets are not furnished.
2. Add 1" for isolators as shown.
3. One-, two- and three-pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of evaporator nozzles may be used in combination with any pair of condenser nozzles.
4. Connected piping should allow for removal of compact water boxes for tube access and cleaning.
5. Rear of unit is defined as side of chiller opposite control center.
YORK INTERNATIONAL
29
Page 30
FORM 160.81-EG1

Dimensions (Ft.-In.) – Nozzle Arrangements

CONDENSERS – COMPACT W ATER BOXES
FRONT
OF UNIT
QP
CC
CONDENSER CONDENSER
GG
COMPRESSOR END
U
T
CONDENSER CONDENSER
GG
COMPRESSOR END
Y
X
CONDENSER CONDENSER
GG
COMPRESSOR END
1"
OF UNIT
DD
BB
1"
OF UNIT
DD
BB
1"
FLOOR LINE
FRONT
FLOOR LINE
FRONT
FLOOR LINE
FRONT
OF UNIT
CC
1"
MOTOR END
FRONT
OF UNIT
DD
BB
1"
MOTOR END
FRONT
OF UNIT
W
DD
BB
1"
MOTOR END
1-PASS
NOZZLE
ARRANGEMENTS
NO. OF COND.
PASSES IN OUT
1
GG
PQ
QP
2-PASS
S
R
NOTE: Water must enter through bottom connection to
GG
achieve rated performance
NOZZLE
ARRANGEMENTS
NO. OF COND.
PASSES IN OUT
2
RS TU
3-PASS
NOZZLE
ARRANGEMENTS
V
GG
NO. OF COND.
PASSES IN OUT
3
NOTE: Water must enter through bottom connection to achieve rated performance
VY XW
LD07982
CONDENSER NOZZLE PIPE SIZE
SHELL
CODE
NO. OF PASSES 1-PASS 2-PASS 3-PASS
12 3CC
2
GG BB
CONDENSER
NOZZLE DIMENSIONS
2
DD
2
GG BB
2
DD
2
GG
T, V 10" 6" 6" 2'–4-3/4" 1'–3" 1'–9-3/4" 2'–11-3/4" 1'–3" 1'–9-3/4" 2'–11-3/4" 1'–3"
W, X 12" 8" 6" 2'–6-3/4" 1'–3-1/2" 1'–11" 3'–2-1/2" 1'–3-1/2" 1'–11" 3'–2-1/2" 1'–3-1/2"
NOTES:
1. Standard water nozzles are furnished as welding stub-outs with Victaulic grooves, allowing the option of welding, flanges, or use of Victaulic couplings. Factory installed, class 150 (ANSI B16.5, round slip-on, forged carbon steel with 1/16" raised face), water flanged nozzles are optional (add 1/2" to nozzle length). Companion flanges, nuts, bolts, and gaskets are not furnished.
2. Add 1" for isolators as shown.
3. One-, two- and three-pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of condenser nozzles may be used in combination with any pair of evaporator nozzles.
4. Connected piping should allow for removal of compact water boxes for tube access and cleaning.
5. Front of unit is defined as side of chiller where control center is mounted.
30
YORK INTERNATIONAL
Page 31
FORM 160.81-EG1

Dimensions (mm) – Nozzle Arrangements

CONDENSERS – COMPACT W ATER BOXES
FRONT
OF UNIT
QP
CC CC
CONDENSER CONDENSER
GG
COMPRESSOR END
U
T
CONDENSER CONDENSER
GG GG
COMPRESSOR END
1" 1"
FRONT
OF UNIT
DD
BB
1"
FRONT
OF UNIT
OF UNIT
FLOOR LINE
OF UNIT
FLOOR LINE
OF UNIT
FRONT
MOTOR END
FRONT
S
R
DD
BB
1"
MOTOR END
FRONT
GG
NOZZLE
ARRANGEMENTS
NO. OF COND.
PASSES IN OUT
1
PQ QP
NOZZLE
ARRANGEMENTS
NO. OF COND.
PASSES IN OUT
2
NOTE: Water must enter through bottom connection to achieve rated performance
RS TU
1-PASS
2-PASS
3-PASS
Y
X
DD
BB
CONDENSER CONDENSER
GG GG
COMPRESSOR END
1"
FLOOR LINE
DD
BB
1"
CONDENSER NOZZLE PIPE SIZE
SHELL
CODE
NO. OF PASSES 1-PASS 2-PASS 3-PASS
12 3CC
W
V
MOTOR END
2
GG BB
ARRANGEMENTS
NO. OF COND.
PASSES IN OUT
3
NOTE: Water must enter through bottom connection to achieve rated performance
CONDENSER
NOZZLE DIMENSIONS
2
DD
2
VY XW
GG BB
LD07983
2
DD
2
GG
T, V 10" 6" 6" 730 381 553 908 381 553 908 381
W, X 12" 8" 6" 781 394 584 978 394 584 978 394
NOTES:
1. Standard water nozzles are furnished as welding stub-outs with Victaulic grooves, allowing the option of welding, flanges, or use of Victaulic couplings. Factory installed, class 150 (ANSI B16.5, round slip-on, forged carbon steel with 1.59 mm raised face), water flanged nozzles are optional (add 12.7 mm to nozzle length). Companion flanges, nuts, bolts, and gaskets are not furnished.
2. Add 25.4 mm for isolators as shown.
3. One-, two- and three-pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of condenser nozzles may be used in combination with any pair of evaporator nozzles.
4. Connected piping should allow for removal of compact water boxes for tube access and cleaning.
5. Front of unit is defined as side of chiller where control center is mounted.
NOZZLE
YORK INTERNATIONAL
31
Page 32

Dimensions (In.) – Floor Layout

NEOPRENE ISOLA TORS
FLOOR LAYOUT
C
EVAPORATOR
L
C
SHELLS
END SHEET
C
CONDENSER
L
L
FORM 160.81-EG1
END SHEET
DIMENSION "C" From Fig. 3 (pgs. 26 & 27)
7/8" DIA. HOLE
3"
3"
8"
5-1/2" 4-1/2"
3/8" STEEL PLATE
1"
SUPPORT FOOT
6"
DIMENSIONS ARE
TYPICAL ALL 4 CORNERS
1/2"
4-1/2"
5-1/2"
DIMENSION "A" From Fig. 3 (pgs. 26 & 27)
ISOLATOR TO BE CENTERED
UNDER SUPPORT FOOT
7"
6"
3/8" STEEL PLATE
1/2"
4-1/2"
5-1/2"
1/2"
32
1" DEFLECTED HEIGHT
UNIT WEIGHT UP TO 16,365 LBS.
1" DEFLECTED HEIGHT
UNIT WEIGHT 16,366 TO 28,835 LBS.
LD07610
YORK INTERNATIONAL
Page 33

Dimensions (mm) – Floor Layout

NEOPRENE ISOLATORS
FLOOR LAYOUT
C
EVAPORATOR
L
C
SHELLS
END SHEET
C
CONDENSER
L
L
END SHEET
FORM 160.81-EG1
DIMENSION "C" From Fig. 3 (pgs. 26 & 27)
22 mm DIA. HOLE
76.2
76.2
152.4
25
203.2
140 114
13 mm STEEL PLATE
SUPPORT FOOT
DIMENSIONS ARE
TYPICAL ALL 4 CORNERS
13
ISOLATOR TO BE CENTERED
UNDER SUPPORT FOOT
114
140
25 mm DEFLECTED HEIGHT
DIMENSION "A" From Fig. 3 (pgs. 26 & 27)
178
152
13 mm STEEL PLATE
13
114
140
13
25 mm DEFLECTED HEIGHT
UNIT WEIGHT UP TO 7,423 KGS.
YORK INTERNATIONAL
UNIT WEIGHT 7,423 TO 13,107 KGS.
LD07611
33
Page 34

Dimensions – Floor Layout

SPRING ISOLA T ORS
FORM 160.81-EG1
(Pgs. 26 & 27)
(Pgs. 26 & 27)
ALL DIMENSIONS ARE IN INCHES
LD07378
(Pgs. 26 & 27)
34
(Pgs. 26 & 27)
ALL DIMENSIONS ARE IN MILLIMETERS
LD07379
YORK INTERNATIONAL
Page 35
FORM 160.81-EG1

Weights

UNIT WEIGHTS
SHIPPING OPERATING REFRIGERANT LOADING PER
COMP. SHELLS WEIGHT WEIGHT CHARGE ISOLATOR
(LBS) (KG) (LBS) (KG) (LBS) (KG) (LBS) (KG)
TBTB 11,860 5,380 13,110 5,948 650 295 3,278 1,485 TBTC 11,910 5,400 13,200 5,988 650 295 3,303 1,495 TBTD 12,010 5,450 13,350 6,053 650 295 3,338 1,515 TCTB 11,960 5,425 13,250 6,013 650 295 3,313 1,500 TCTC 12,010 5,450 13,340 6,053 650 295 3,338 1,515 TCTD 12,110 5,495 13,490 6,123 650 295 3,373 1,530 TDTB 12,070 5,475 13,410 6,083 650 295 3,353 1,520 TDTC 12,120 5,500 13,500 6,123 650 295 3,378 1,530
T0/T1
T1 WCWC 15,110 6,854 17,800 8,074 1,250 567 4,450 2,019
T2/T3 WDWD 18,810 8,532 21,740 9,861 1,250 567 5,435 2,465
TDTD 12,220 5,540 13,650 6,193 650 295 3,413 1,545 VBVB 12,680 5,750 14,320 6,495 900 408 3,580 1,625 VBVC 12,750 5,785 14,450 6,555 900 408 3,615 1,640 VBVD 12,890 5,845 14,660 6,649 900 408 3,665 1,665 VCVB 12,820 5,815 14,520 6,586 900 408 3,630 1,645 VCVC 12,900 5,850 14,650 6,645 900 408 3,665 1,665 VCVD 13,030 5,910 14,850 6,735 900 408 3,715 1,685 VDVB 12,990 5,890 14,750 6,690 900 408 3,690 1,675 VDVC 13,070 5,930 14,890 6,755 900 408 3,725 1,690
VDVD 13,200 5,990 15,090 6,845 900 408 3,775 1,710 WBWB 14,660 6,650 17,160 7,784 1,250 567 4,290 1,946 WBWC 14,930 6,772 17,550 7,961 1,250 567 4,388 1,990 WBWD 15,520 7,040 18,020 8,174 1,250 567 4,505 2,043 WCWB 14,840 6,731 17,410 7,897 1,250 567 4,353 1,975
WCWD 15,440 7,004 18,280 8,292 1,250 567 4,570 2,073 WDWB 15,070 6,836 17,730 8,042 1,250 567 4,433 2,011 WDWC 15,340 6,958 18,120 8,219 1,250 567 4,530 2,055 WDWD 15,670 7,108 18,600 8,437 1,250 567 4,650 2,109 WBWB 17,810 8,079 20,310 9,213 1,250 567 5,078 2,303 WBWC 18,070 8,197 20,690 9,384 1,250 567 5,172 2,346 WBWD 18,400 8,346 21,170 9,603 1,250 567 5,293 2,400 WCWB 17,990 8,160 20,560 9,326 1,250 567 5,140 2,331 WCWC 18,260 8,283 20,950 9,503 1,250 567 5,238 2,375 WCWD 18,580 8,428 21,420 9,716 1,250 567 5,355 2,429 WDWB 18,220 8,265 20,880 9,471 1,250 567 5,220 2,367 WDWC 18,490 8,387 21,270 9,648 1,250 567 5,318 2,412
XBXB 19,110 8,669 22,200 10,070 1,550 703 5,550 2,518
XBXC 19,370 8,786 22,620 10,260 1,550 703 5,655 2,565
XBXD 19,700 8,935 23,150 10,500 1,550 703 5,788 2,625
XCXB 19,360 8,782 22,540 10,224 1,550 703 5,635 2,556
XCXC 19,620 8,900 22,960 10,415 1,550 703 5,740 2,603
XCXD 19,950 9,049 23,490 10,655 1,550 703 5,873 2,664
XDXB 19,670 8,922 22,970 10,419 1,550 703 5,743 2,605
XDXC 19,940 9,045 23,400 10,614 1,550 703 5,850 2,654
XDXD 20,260 9,190 23,920 18,850 1,550 703 5,980 2,713
SOLID STATE STARTER WEIGHT
SIZE LBS KGS
7L, 14L 200 91
26L, 33L 300 136
YORK INTERNATIONAL
35
Page 36

Guide Specifications

FORM 160.81-EG1
GENERAL
Furnish and install where indicated on the drawings YORK M unit shall produce a capacity of GPM of with °F. Power input shall not exceed (NPLV) of selected for maximum liquid pressure drop of shall be designed for 150 or 300 psig working pressure. The condenser shall be selected for factor and maximum liquid pressure drop of ____ ft. Water side shall be designed for 150 or 300 psig work­ing pressure. Power shall be supplied to the compres­sor motor at controls at 115 volts –1-phase – (60)(50) Hertz.
Furnish and install where indicated on the drawings YORK M unit shall produce a capacity of of ____ L/S of condenser water at °C. Power input shall not exceed ____. The evaporator shall be selected for fouling factor and a maximum liquid pressure drop of ___ kPa. Water side shall be designed for 1034 or 2068 kPa working pressure. The condenser shall be selected for pressure drop of for 1034 or 2068 kPa working pressure. Power shall be supplied to the compressor motor at – 50 Hz and controls at 115 volts – 1-phase – 50 Hz.
Performance shall be certified or rated in accordance with the latest edition of ARI Standard 550/590-98 as applicable. Only chillers that are listed in the ARI Certi­fication Program for Water Chilling Packages using the vapor compression cycle are acceptable.
Each unit shall be completely factory packaged includ­ing evaporator, condenser , subcooler , oil separator, com­pressor/motor, lubrication system, OptiView Control Center, Solid State Starter (optional), refrigerant isola­tion valves (optional) and all interconnecting piping and wiring. The factory package shall consist of a “Leaktight”
AXE Rotary Screw Liquid Chilling Unit(s). Each
tons, cooling
from °F to °F when supplied
_____ GPM of condenser water at
kW with an IPLV
_____. The evaporator shall be
ft2 °F hr/BTU fouling factor and a
ft. Water side
fouling
volts – 3-phase – (60)(50) Hertz and
– (or) –
AXE Rotary Screw Liquid Chilling Unit(s). Each
kW, cooling L/S
from °C to °C when supplied with
kW with an IPLV (NPLV) of
M2 °C/W
M2 °C/W fouling factor and maximum liquid
kPa. Water side shall be designed
volts – 3-phase
design, with no pipe thread connections that can loosen and leak over time. All units shall ship with a full charge of refrigerant HFC-134a and oil. Alternatively , the chiller shall be shipped with the compressor, control panel and oil separator removed (Form 3) or also with the shells separated (Form 7) to allow rigging into the equipment room. All units that ship disassembled shall be assembled and factory run tested prior to disassembly and shipment).
Compressor
The compressor shall be a rotary-screw type. The com­pressor housing shall be of cast iron, precision machined to provide minimal clearance for the rotors. The rotors shall be manufactured from forged steel and use asym­metric profiles operating at a maximum speed of (3570 RPM/60 Hz) (2975 RPM/50 Hz). The compressor shall incorporate a complete anti-friction bearing design to re­duce power and increase reliability; four separate cylin­drical roller bearings to handle radial loads; and two 4­point angular contact ball bearings to handle axial loads. A check valve shall be incorporated in the compressor housing to prevent rotor backspin during shutdown.
Capacity control shall be achieved by use of a slide valve to provide fully modulating control from 100% to 20% of full-load. The slide valve shall be actuated by system differential pressure, controlled by external so­lenoid valves through the OptiView Control Center . The unit shall be capable of operating with lower tempera­ture cooling tower water during part-load operation in accordance with ARI Standard 550/590.
Lubrication System
An adequate supply of oil shall be available to the com­pressor at all times. During start-up and coastdown, this shall be achieved by oil reservoirs in the compressor. During operation, oil shall be delivered by positive sys­tem pressure differential.
All chillers shall be provided with a single oil filter hous­ing with isolation valves. An optional dual filter is avail­able which allows immediate switching from one filter to the other, eliminating downtime during filter changes. The off-line oil filter must be capable of being changed during chiller operation. The chiller shall ship with a 3 micron absolute oil filter, (two filters for dual filter op­tion) maintaining a clean oil system and ensuring supe­rior compressor life.
36
YORK INTERNATIONAL
Page 37
FORM 160.81-EG1
A 500W immersion oil heater shall be provided and temperature actuated to effectively remove refrigerant from the oil. Power wiring to the Control Center shall be factory installed. An oil eductor shall be provided to au­tomatically remove oil which may have migrated to the evaporator and return it to the compressor. The oil sepa­rator shall be of a vertical design with no moving parts, and shall provide high-efficiency oil separation before the refrigerant enters the heat exchangers. The oil sepa­rator shall be designed, tested and stamped in accor­dance with ASME Boiler and Pressure Vessel Code, Section VIII – Division 1.
Motor
The motor shall be 2-pole, continuous duty , cage induc­tion type, and shall utilize suction gas cooling (semi-her­metic design). Motor full-load amperes at design condi­tions shall not exceed motor nameplate (FLA). Motor shall be designed for use with the type starter specified.
For units utilizing remote electromechanical starters, a large steel terminal box with gasketed front access cover shall be provided for field connected conduit. Overload/ overcurrent transformers shall be furnished with all units. (For units furnished with factory packaged Solid State Starters, refer to the “Options” section.)
Water boxes shall be removable to permit tube clean­ing and replacement. Stubout water connections hav­ing Victaulic grooves shall be provided. Water boxes shall be designed for 150 psig (1034 kPa) design work­ing pressure. Vent and drain connections with plugs shall be provided on each water box.
Condenser
Condenser shall be of the shell-and-tube type, designed for 235 psig (1620 kPa) working pressure on the refrig­erant side. Shell shall be fabricated from rolled carbon steel plate with fusion welded seams or carbon steel pipe; have carbon steel tube sheets, drilled and reamed to accommodate the tubes; and intermediate tube sup­ports spaced no more than four feet apart. A refrigerant subcooler shall be provided for improved cycle effi­ciency. The refrigerant side shall be designed, tested and stamped in accordance with ASME Boiler and Pres­sure Vessel Code, Section VIII – Division 1. Tubes shall be high-efficiency, internally enhanced type. Each tube shall be roller expanded into the tube sheets providing a leak-proof seal, and be individually replaceable. Wa­ter velocity through the tubes shall not exceed 12 FPS. The condenser shall have refrigerant relief device to meet the requirements of ASHRAE 15 Safety Code for Mechanical Refrigeration.
Evaporator
Evaporator shall be of the shell-and-tube, flooded type designed for 235 psig (1620 kPa) working pressure on the refrigerant side. Shell shall be fabricated from rolled carbon steel plate with fusion welded seams or carbon steel pipe; have carbon steel tube sheets, drilled and reamed to accommodate the tubes; and intermediate tube supports spaced no more than four feet apart. The refrigerant side shall be designed, tested and stamped in accordance with ASME Boiler and Pressure Vessel Code, Section VIII – Division 1. Tubes shall be high­efficiency , internally enhanced type. Each tube shall be roller expanded into the tube sheets providing a leak­proof seal, and be individually replaceable. Water ve­locity through the tubes shall not exceed 12 FPS (3.6 m/s). Liquid level sight glass shall be located on the side of the shell to aid in determining proper refrigerant charge. The evaporator shall have a refrigerant relief device to meet the requirements of ASHRAE 15 Safety Code for Mechanical Refrigeration.
Water boxes shall be removable to permit tube clean­ing and replacement. Stubout water connections hav­ing Victaulic grooves shall be provided. Water Boxes shall be designed for 150 psig (1034 kPa) design work­ing pressure. Vent and drain connections with plugs shall be provided on each water box.
Refrigerant System
The YR chiller is equipped with a refrigerant metering device consisting of a fully modulating variable orifice controlled via the OptiView Control Center. This control ensures proper refrigerant flow to the evaporator over a wide range of operating conditions, including thermal stor­age applications and chilled water reset. V alve operation is programmable and can be customized for a specific application via the OptiView Control Center keypad.
The condenser shell shall be capable of storing the en­tire system refrigerant charge during servicing. Isola­tion from the rest of the system shall be by manually
YORK INTERNATIONAL
37
Page 38
Guide Specifications
FORM 160.81-EG1
operated isolation valves located at the inlet to the oil separator and outlet of the condenser (isolation valves optional). Additional valves shall be provided to facili­tate removal of refrigerant charge from the system.
OPTIVIEW CONTROL CENTER General – The chiller shall be controlled by a stand-alone
microprocessor based control center. The chiller control panel shall provide control of chiller operation and moni­toring of chiller sensors, actuators, relays and switches.
Control Panel – The control panel shall include a 10.4­in. diagonal color liquid crystal display (LCD) surrounded by "soft " keys which are redefined based on the screen displayed at that time. This shall be mounted in the middle of a keypad interface and installed in a locked enclosure. The screen shall detail all operations and parameters, using a graphical representation of the chiller and its ma­jor components. Panel verbiage shall be available in other languages as an option with English always available. Data shall be displayed in either English or Metric units. Smart Freeze Point Protection shall run the chiller at 36°F (2.22°C) leaving chilled water temperature, and not have nuisance trips on low water temperature. The sophisti­cated program and sensor shall monitor the chiller water temperature to prevent freeze-up. When needed, Hot Gas Bypass is available as an option. The panel shall display countdown timer messages so the operator knows when functions are starting and stopping. Every programmable point shall have a pop-up screen with the allowable ranges, so that the chiller can not be programmed to operate outside of its design limits.
The control panel shall be provided with a thermal ice storage control mode to enhance system performance during ice building operation. In the thermal storage con­trol mode, the chiller shall stay at 100% load until the setpoint shutdown temperature is reached. To add greater operating flexibility and eliminate unnecessary chiller cycling, two different Low Water (Liquid) Tem­perature Restart Thresholds shall be programmable, one for the ice mode and one for the standard cooling mode. The chiller shall have the capability to remain in the standard control mode for temperatures between 20 to 70°F (-6.7 to 21.1°C) for applications involving a pro­cess cooling duty that requires leaving chilled liquid tem­perature setpoint control.
The chiller control panel shall also provide:
1. System operating information including: a. Return and leaving chilled water temperature b. Return and leaving condenser water temp. c. Evaporator and condenser saturation temp.
d. Oil pressure at compressor and oil filter
differential e. Percent motor current f. Evaporator and condenser saturation temp. g. Compressor discharge temperature h. Percent slide valve position i. Operating hours j. Number of unit starts
2. Digital programming of setpoints through the uni­versal keypad including:
a. Leaving chilled water temperature b. Percent current limit c. Pull-down demand limiting d. Six-week schedule for starting and stopping the
chiller, pumps and tower
e. Remote reset temperature range
3. Status messages indicating: a. System ready to start b. System running c. System lockout d. System safety shutdown-manual restart e. System cycling shutdown-auto restart f. System startup g. Start inhibit
4. The text displayed within the system status and system details field shall be displayed as a color coded message to indicate severity: red for safety fault, orange for cycling faults, yellow for warnings, and green for normal messages.
5. Safety shutdowns enunciated through the display and the status bar, and consist of system status, system details, day, time, cause of shutdown, and type of restart required. Safety shutdowns shall include:
a. Evaporator - low pressure b. Evaporator - low pressure - smart freeze c. Evaporator - transducer or leaving liquid probe d. Evaporator - transducer or temperature sensor e. Condenser - high pressure contacts open f. Condenser - high pressure g. Condenser - pressure transducer out of range h. Auxiliary safety - contacts closed i. Discharge - high temperature j. Discharge - low temperature k. Oil - low differential pressure l. Oil or condenser transducer error m. Oil - clogged filter
38
YORK INTERNATIONAL
Page 39
FORM 160.81-EG1
n. Oil - high pressure o. Control panel - power failure p. Watchdog - software reboot
5.1. Safety shutdowns with a Solid State Starter (LCSSS) shall include:
a. Shutdown - requesting fault data... b. High instantaneous current c. High phase (X) heatsink temperature - running d. 105% motor current overload e. Motor or starter - current imbalance f. Phase (X) shorted SCR g. Open SCR h. Phase rotation
6. Cycling shutdowns enunciated through the display and the status bar, and consisting of system sta­tus, system details, day , time, cause of shutdown, and type of restart required.
Cycling shutdowns shall include: a. Multiunit cycling - contacts open b. System cycling - contacts open c. Control panel - power failure d. Leaving chilled liquid - low temperature e. Leaving chilled liquid - flow switch open f. Condenser - flow switch open g. Motor controller - contacts open h. Motor controller - loss of current i. Power fault j. Control panel - schedule
6.1 Cycling shutdowns with a Solid State Starter (LCSSS) shall include:
a. Initialization failed b. Serial communications c. Requesting fault data d. Stop contacts open e. Power fault f. Low phase (X) temperature sensor g. Run signal h. Invalid current scale selection i. Phase locked loop j. Low supply line voltage k. High supply line voltage l. Logic board processor m.Logic board power supply n. Phase loss
7. Security access to prevent unauthorized change of setpoints, to allow local or remote control of the chiller, and to allow manual operation of the variable orifice and slide valve position. Access shall be through ID and password recognition, which is defined by three different levels of user competence: view, operator, and service.
8. Trending data with the ability to customize points of once every second to once every hour. The panel shall trend up to 6 different parameters from a list of over 140, without the need of an external moni­toring system.
9. The operating program stored in non-volatile memory (EPROM) to eliminate reprogramming the chiller due to AC power failure or battery discharge. Programmed setpoints shall be retained in lithium battery-backed RTC memory for a minimum of 11 years with power removed from the system.
10. A fused connection through a transformer in the compressor motor starter to provide individual over-current protected power for all controls.
11. A numbered terminal strip for all required field in­terlock wiring.
12. An RS-232 port to output all system operating data, shutdown/cycling message, and a record of the last 10 cycling or safety shutdowns to a field-supplied printer. Data logs to a printer at a set program­mable interval. This data can be preprogrammed to print from 1 minute to 1 day.
13. The capability to interface with a building automa­tion system to provide:
a. Remote chiller start and stop b. Remote leaving chiller liquid temperature adjust c. Remote current limit setpoint adjust d. Remote ready to start contacts e. Safety shutdown contacts f. Cycling shutdown contacts g. Run contacts
COMPRESSOR MOTOR STARTER (OPTION, 200 - 600V)
The chiller manufacturer shall furnish a reduced-volt­age Solid State Starter for the compressor motor. Starter shall be factory-mounted and wired on the chiller. The starter shall provide, through the use of silicon controlled rectifiers, a smooth acceleration of the motor without current transitions or transients. The starter enclosure shall be NEMA 1, with a hinged access door with lock and key . Electrical lugs for incoming power wiring shall be provided.
YORK INTERNATIONAL
39
Page 40
Guide Specifications
Standard features include: digital readout at the OptiV­iew Control Center of the following:
Display Only:
• 3-phase voltage A, B, C
• 3-phase current A, B, C
• Input power (kW)
• kW Hours
• Starter Model
• Motor Run (LED)
• Motor Current % Full-load Amps
• Current Limit Setpoints
• Pulldown Demand Time Left
Programmable:
• Local Motor Current Limit
• Pulldown Demand Limit
• Pulldown Demand Time
Other features include: low-line voltage, 115-volt con­trol transformer; three-leg sensing overloads; phase ro­tation and single-phase failure protection; high tempera­ture safety protection, motor current imbalance and undervoltage safeties; open and close SCR protection; momentary power interruption protection. The LCSSS is cooled by a closed loop, fresh water circuit consist­ing of a water-to-water heat exchanger and 1/25 HP circulating pump. All interconnecting water piping is factory installed and rated for 150 PSIG working pres­sure. Optional unit-mounted circuit breaker includes
ground fault protection and provides 65,000 amp. Short circuit withstand rating in accordance with UL Standard
508. A non-fused disconnect switch is also available. Both options are padlockable.
REMOTE ELECTRO-MECHANICAL COMPRES­SOR MOTOR STARTER (OPTIONAL)
A remote electro-mechanical starter of the R-1131 type shall be furnished for each compressor motor. The starter shall be furnished in accordance with the chiller manufacturer’s starter specifications and as specified elsewhere in these specifications.
PORTABLE REFRIGERANT STORAGE/RECY­CLING SYSTEM
A portable, self-contained refrigerant storage/recycling system shall be provided consisting of a refrigerant com­pressor with oil separator, storage receiver , water cooled condenser, filter drier and necessary valves and hoses to remove, replace and distill refrigerant. All necessary controls and safety devices shall be a permanent part of the system.
START-UP AND OPERATOR TRAINING
The chiller manufacturer shall include the services of a factory-trained, field service representative to super­vise the final leak testing, charging and the initial start­up and concurrent operator instruction.
P.O. Box 1592, York, Pennsylvania USA 17405-1592 Subject to change without notice. Printed in USA Copyright © by York International Corporation 2002 ALL RIGHTS RESERVED
Form 160.81-EG1 (502) Supersedes 160.81-EG1 (302)
T ele. 800-861-1001
www.york.com
Loading...