York E1FB180, E1FB240 User Manual


SPLIT-SYSTEM HEAT PUMPS
OUTDOOR UNITS
INSTALLATION INSTRUCTION
Supersedes: 035-16192-000 (0601)
MODELS E1FB180 & E1FB240
O
O
O
O
035-16192-001-A-1001
O
O
O
O
O
O
GENERAL
The outdoor units are completely piped and wired at the fac-
tory and are shipped ready for immediate installation. Only
the interconnecting liquid and suction lines, sight glasses,
control wiring, and the main power wiring are required to
complete the installation. Every unit is dehydrated, evacu
ated, leak tested and pressure tested at 450 psig before be
shipment and/or storage.
To eliminate the costly cabinet deterioration problems usually
associated with outdoor equipment, all sheet metal parts are
constructed of commercial grade (G90) galvanized steel. Af
ter fabrication, each part is thoroughly cleaned to remove
any grease or dirt from its surfaces. The parts that will be
exposed to the weather are then coated with a “desert sand”
powder paint to assure a quality finish for many years. This coating system has passed the 750-hour, salt spray test per
ASTM Standard B117.
Every unit includes 2 heavy-duty scroll compressors, 2 suc
tion line accumulators, 2 4-way reversing valves with a 24
volt solenoid, 2 outdoor fan motors with inherent protection,
and a copper tube/aluminum fin coil that is positioned verti
cally for better drainage of the water that will condense on it
during the heating cycle.
They also include 2 filter driers, 2 expansion valves and dis
tributors that are only used during the heating cycle plus a
check valve to provide the proper flow of refrigerant through
the unit during both the cooling and heating cycles.
All controls are located in the front of the unit and are readily accessible for maintenance, adjustment and service. All wir-
ing (Power and Control) can be made through the front of
the unit.
-
-
REFERENCE
This instruction covers the installationandoperationoftheba sic condensing unit. For information on the installationandop eration of the matching indoor units, refer to Installation Instruction part no. 035-16626-000 (form 515.41-N4Y).
­All accessories come with a separate Installation Manual.
RefertoPartsManualfor complete listingof replacement parts on this equipment.
All forms may be ordered from:
-
-
Standard Register Norman, OK 73069 Toll Free: Tel. 877-318-9675/Fax. 877-379-7920
INSPECTION
As soon as a unit is received, it should be inspected for pos
-
sible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier's freight bill. A separate request for inspection by the carrier's agent should
be made in writing.
-
-
-
Installershouldpayparticularattention tothewords: NOTE,CAUTIONand WARNING.Notes
installation easier.Cautions
are given to prevent equipment damage. Warnings are given to alert installer that personal
injury and/or equipment damage may result if installation procedure is not handled properly.
areintendedto clarifyormake
035-16192-001-A-1001
GENERAL REFERENCE INSPECTION NOMENCLATURE
.............................................................................
.............................................................................
.............................................................................
......................................................................
INSTALLATION
TABLE OF CONTENTS
1 1 1 2
CLEANING LUBRICATION REPLACEMENT PARTS NOTICE TO OWNER
.............................................................................
............................................................................
MAINTENANCE
............................................................
..................................................................
14 14 14 14
LIMITATIONS LOCATION
Roof-Top Locations
Ground Level Locations RIGGING AND HANDLING CLEARANCES COMPRESSOR CRANKCASE HEATER POWER AND CONTROL WIRING
Power Wiring
Control Wiring REFRIGERANT PIPING
General Guidelines
Line Sizing
Service Valves
Installation EXTENDING THE SERVICE PORTS EVACUATING AND CHARGING BALANCE POINT SETTING
ALTERNATE CHARGING METHODS........................................ 10
.............................................................................
.............................................................
......................................................
........................................................
...........................................................................
...................................
......................................................................
.....................................................................
.............................................................
..........................................................................
....................................................................
...........................................................................
.........................................
................................................
.......................................................
OPERATION
GENERAL ............................................................................. 11
SYSTEM SEQUENCE OF OPERATION
Cooling Operation............................................................... 11
Heating Operation............................................................... 12
Defrost Cycle...................................................................... 12
Operation Below 0°F........................................................... 13
Emergency Heat Operation................................................ 13
START-UP
CRANKCASE HEATER (10 Ton Unit Only) PRE-START CHECK INITIAL START-UP SAFETY FEATURES SECURE OWNER'S APPROVAL
..................................................................
.....................................................................
..................................................................
...............................................
................................
14 14 14 14 14
3 3
3 3 4 4
4 4
7 7 7 7 9 9 9
Figure
No.
1 Center of Gravity 2 Typical Rigging 3 Typical Field Wiring 4 Unit Dimensions & Clearances 5 Extending The Service Ports 6 Refrigerant Flow Diagram 7 Charging Curves EFB180A 8 Charging Curves EFB240A 9 Heating Mode Charging Chart At 4800 CFM
EFB180A
10 Heating Mode Charging Chart At 6000 CFM
EFB180A
11 Heating Mode Charging Chart At 6600 CFM
EFB180A
12 Heating Mode Charging Chart At 6400 CFM....... 17
EFB240A
13 Heating Mode Charging Chart At 7000 CFM....... 18
EFB 240A
14 Heating Mode Charging Chart At 7600 CFM....... 18
EFB 240A
LIST OF FIGURES
Description Page
..................................................
.....................................................
..............................................
............................
................................
....................................
..................................
..................................
.......
.......
.......
10 11 15 15 16
16 17
3 4 5 6
LIST OF TABLES
Table
No.
1 Unit Application Data 2 Physical Data 3 Electrical Data 4 Suction Lines 5 Liquid Lines 6 Refrigerant Line Charge
Description Page
..........................................................
............................................
.......................................................
......................................................
........................................................
.......................................
3 4 5 7 8 8
PRODUCT NOMENCLATURE
1 F B 2 58 A
PRODUCT CATEGORY
E = Split-System Heat Pump
Outdoor
2 Unitary Products Group
Unit
PRODUCT GENERATION
1 = First Generation
PRODUCT IDENTIFIER
E
FB = Outdoor Unit
1 0
NOMINAL COOLING
CAPACITY
180 = 15 Ton 240 = 20 Ton
VOLTAGE CODE
25 = 208/230-3-60 46 = 460-3-60
FACTORYINSTALLED HEAT
A = Not Applicable
INSTALLATION
035-16192-001-A-1001
LIMITATIONS
These units must be installed in accordance with all national andlocal safetycodes. Ifno localcodes apply,installationmust conform with the appropriate national codes. See Table 1 for
Thesebeamscan usuallybeset directlyonthe roof.Flashingis not required.
NOTE: On bonded roofs, check for special installation re
quirements.
unit application data. Units are designed to meet National SafetyCodeStandards.Ifcomponents aretobe addedtoa unit to meet local codes, they are to be installed at the dealer's and/or the customer's expense.
TABLE 1 - UNIT APPLICATION DATA
APPLICATION LIMITATIONS MIN MAX Voltage Variation (208/230-3-60) - Volts Voltage Variation (460-3-60) - Volts Ambient Air on Outdoor Coil (Cooling Cycle) - °F 45 115 Ambient Air on Indoor Coil (Cooling Cycle) - °F 68 86 Ambient Air on Outdoor Coil (Heating Cycle) - °F 0 Ambient Air on Indoor Coil (Heating Cycle) - °F 60 80
1
Rated in accordance with ARI Standard 110, utilization range “A”.
2
Below 0 °F, the control circuit will lock out the compressor and allow the
electric heat accessory to cycle at its standby capacity.
2
2
187 253 414 506
1
70
LOCATION
Use the following guidelines to select a suitable location for
GROUND LEVEL LOCATIONS
The units must be installed on a substantial base that will not settle. Any strain on the refrigerant lines may cause a refriger antleak. Aone-piececoncrete slabwith footersthat extendbe low the frost line is recommended. The slab should not be tied tothe buildingfoundation becausenoise and vibrationwill tele graph.
A unit can also be supported by concrete piers. These piers should:(1) extend below the frostline, (2) be located underthe unit's four corners and (3) be sized to carry the entire unit weight. Refer to Figure 1 and Table 2 for the center of gravity and unit weight.
Agravel bed or some other means of handling the condensate thatwill drop fromthe underside ofthe unit coil duringthe heat ing and defrost cycles may have to be provided.
APPROXIMATE
CENTER OF GRAVITY
B
BACK
(COIL END)
these units.
1. The outdoor units must be installed outside the building. Theoutdoor fansare the propellertype andare not suitable for use with duct work.
76 - 7/8
FRONT
A
39 - 7/8
2. The outdoor and indoor units should be installed as close together as possible and with a minimum number of bends in the refrigerant piping. Refer to REFRIGERANT PIPING for additional information.
3. The outdoor unit should not be installed beneath windows orbetween structureswhere normal operating sounds may be objectionable.
WARNING: The outdoor unit should not be installed in an area
wheremud and/or ice could causepersonal injury. Remember that condensate will drip from the un dersideof the unit coilsduring heat and defrost cy cles and that this condensate will freeze when the temperature of the outdoor air is below 32°F.
4. Allunitsrequire certainclearancesfor properoperation and
Unit
15 Ton 16 38 20 Ton 16 38
FIG. 1 - CENTER OF GRAVITY
CAUTION: Care should be taken to protect the unit from
-
-
tampering and unauthorized persons from injury. Screws on access panels will prevent casual tampering. Additional safety precautions such as fences around the unit or locking devices on the panels may be advisable. Check local authori ties for safety regulations.
Dim. (in.)
AB
-
service.
On either rooftop or ground level installations, rubber padding can be applied between the base rails and their supports to lessen any transmission of vibration.
ROOF-TOP LOCATIONS
Becarefulnot todamage theroof. Consultthe buildingcontrac tororarchitect iftheroof isbonded. Choosealocation withade quate structural strength to support the unit.
The unit must be mounted on solid level supports. The sup ports can be channel iron beams or wooden beams treated to reduce deterioration.
Aminimum of two (2) beams are required to support each unit. The beams should: (1) Be positioned perpendicular to the roof
RIGGING AND HANDLING
Exercise care when moving the unit. Do not remove any pack aging until the unit is near the place of installation.
Rigthe unit by attaching chainor cable slings with hooks tothe round lifting holes provided in the base rails.
-
-
CAUTION: Spreaders, longer than the largest dimension
-
WARNING: BEFORE LIFTING A UNIT, MAKE SURE THAT
across the unit, MUST be used across the top of the unit. See Figure 2.
ITS WEIGHT IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT WILLLIFT EVENLY.
joists.(2)Extend beyondthedimensions ofthe unit todistribute the load on the roof, (3) Be capable of adequately supporting theentire unitweight. Refer toFigure 1and Table2 for loaddis tribution and weights.
Unitary Products Group 3
Units may also be moved or lifted with a fork-lift from the front,
-
rear or the compressor end only through the slotted openings provided in the base rails.
-
-
-
-
-
-
035-16192-001-A-1001
O
O
O
O
O
O
O
O
O
O
CAUTION: LENGTH OF FORKS MUST BE A MINIMUM OF
54" (when lifting from the compressor end of the unit)and a MINIMUMOF 42"(when lifting fromthe front or rear of the unit).
Remove the nesting brackets from the four corners on top of the unit. All screws that are removed to take these brackets off must be replaced on the unit.
CLEARANCES
5 ft.
MIN
All units require certain minimum clearances for proper opera
-
tion and service. Refer to Figure 4 for these clearances.
WARNING: Do not permit overhanging structures or shrubs
to obstruct air discharge.
Additional height may be required for snow clearance if winter operation is expected.
COMPRESSOR CRANKCASE HEATER
The compressor is equipped with a crankcase heater to pre
vent refrigerant from mixing with crankcase oil during the
“OFF” cycle. The heaters will be energized when the com
pressor is not running providing the unit disconnect switch is
closed.
TABLE 2 - PHYSICAL DATA
DESCRIPTION
1
Compressor
Rating - (Qty) Tons (2) 7-1/2 (2) 10 Quantity 2 2
Fans
Diameter - inches 24 26 Blades/Pitch (°) 3/32 3/36 Nominal CFM 10862 11395 HP 1 1
Fan Motors
2
RPM 1100 1100 Rows Deep X Rows High 2 X 40 2 X 40 Finned Length - inches 130 130 Face Area - square feet 36.11 36.11 Tube(Copper) OD - inches 3/8 3/8 Fins (Aluminum) per inch 18 20 Holding Charge
(Sys 1 / Sys 2)
3
Operating Charge (Sys 1 / Sys 2)
4
Shipping 970 1020 Operating 980 1040
1
These compressors are fully hermetic.
2
The ball bearing, 48 frame, single phase condenser fan motor have internal
protection and are directly connected to the condenser fins. Motor rotation is counterclockwise when viewing the lead end, which is opposite the shaft end.
3
The amount of charge in the unit as shipped from the factory.
4
Totaloperatingchargeforthecondensingunit,matchingindoor unit, and 25 feet
of interconnecting pipe.
CAUTION: Do not attempt to start the compressor without at
leasteight hours of crankcase heat or compressor damage will occur.
4 Unitary Products Group
UNIT MODEL
EFB180 EFB240
1-0/1-0 1-0/1-0
16-8/17-8 19-0/19-0
FIG. 2 - TYPICAL RIGGING
-
-
Ifa unit hasjust beeninstalled orthe unitdisconnect switchhas beenopen fora longperiod of time,move thesystem switch on the room thermostat to the “OFF” position before closing the unit disconnect switch. Eight hours of crankcase heat are re quired to drive the liquid refrigerant out of the compressor bef ore the compressor can be started.
POWER AND CONTROL WIRING
Install electrical wiring in accordance with the latest National Electrical Code (NFPAStandard No. 70) and/or local regula­tions. The unit should be grounded in accordance with these
codes.
POWER WIRING
Check the voltage of the power supply against the data on
the unit nameplate. Check the size of the power wire, the
disconnect switch and the fuses against the data in Table 3.
NOTE: Copper conductors must be installed between the dis
connect switch and the unit.
Refer to Figure 4 for the location of the power wire access
opening through the front of the unit. This opening will re
quire a field-supplied conduit fitting.
The field-supplied disconnect switch must be suitable for an outdoor location. Although it should be installed near the unit, do NOT
secure it to the unit cabinet.
Refer to Figure 3 for typical field wiring.
CONTROL WIRING
Refer to Figure 4 for the location of the control wire access opening through the front of the unit.
Route the necessary low voltage control wires from terminal
block TB2 of the unit control box through this access open
ing to the indoor unit and to the room thermostat. Refer to
Figure 3 for typical field wiring.
The room thermostat should be mounted about 5 feet above
the floor and located where it will be exposed to normal room
air circulation. Do not locate it on an outside wall, near a
supply air grille, or where it may be affected by sunlight
-
-
-
-
-
TERMINALS ON:
- Supply Air Blower Motor Contactor 10M
OR
- Terminal Block Electric Heat Control Box
035-16192-001-A-1001
3-PHASELINEVOLTAGEPOWERSUPPLY
Refer to electrical data to size the power wiring, disconnect switch and overcurrent protection*.
USE COPPER CONDUCTORS ONLY
TERMINALS ON COMPRESSOR CONTACTORS 1M &3M
GROUND SCREW
"Heat Pump only" Units
GROUND LUG
Units with Electric Heat Accessory
R
C Y1 Y2
O
W1
X
G
TERMINALS ON HEAT
INDOOR UNIT
PUMP THERMOSTAT
WIRE IN ACCORDANCE WITH LOCAL AND NATIONAL ELECTRICAL CODES
TB1 TB2
R C O
G Y1 Y2
1
W1
1
X HR HC
Control wiring (24-volt) refer to electrical data to determine the proper
1
Only required when an electric heat
accessory is used.
wire size.
*All outdoor units and all heat pump only indoor units
require dual element, time delay fuses. Circuit breakers can be used in lieu of fuses for indoor units with an electric heat accessory.
GROUND LUG
R C X
O Y1 Y2 W1
OUTDOOR UNIT
FIG. 3 - TYPICAL FIELD WIRING
TABLE 3 - ELECTRICAL DATA
Model Number
E1FB180A25 208/230-3-60 32.1 195.0 32.1 195.0 208/230-1-60 1 4.7 1 4.7 81.6 90
E1FB180A46 460-3-60 16.4 95.0 16.4 95.0 460-1-60 1 2.5 1 2.5 41.9 45 60
E1FB240A25 208/230-3-60 42.0 239.0 42.0 239.0 208/230-1-60 1 4.7 1 4.7 103.9 110
E1FB240A46 460-3-60 19.2 125.0 19.2 125.0 460-1-60 1 50 602.5 1 2.5 48.2
1
Maximum fuse or maximum circuit breaker (HACR type per NEC).
2
Based on three 75°C insulated copper conductors in conduit and ambient of 30°C.
3
Based on 5% voltage drop, since unit controls are powered off the unit supply. Two minute time delay between system 1 and system 2.
Power Supply Power Supply
Compressors Outdoor Fan Motors
System 1 System 2
RLA LRA RLA LRA Qty FLA (Each) Qty FLA (Each)
System 1 System 2
Minimum
Ampacity
Unitary Products Group 5
Circuit
Maximum
Fuse
1
Size
Minimum
Wire Size
AWG
4AWG
2AWG
8 AWG 142 6 AWG 224
2AWG
0AWG
8 AWG 111 6 AWG 176
Maximum
Wire Length
2
80 @ 208 V
88 @ 230 V 126 @ 208 V 140 @ 230 V
104 @ 208 V 115 @ 230 V 165 @ 208 V 182 @ 230 V
feet
3
Minimum
Disconnect
Amps
100
150
035-16192-001-A-1001
Unit
Dim. (in.)
AB 15 Ton 16 38 20 Ton 16 38
CENTER OF GRAVITY
Connection
Entry Suction Line A 1-1/8 ID 1-3/8 ID Liquid Line B 5/8 ID 5/8 ID
All dimensions are in inches. They are subject to change without notice. Certified dimensionswillbeprovideduponrequest.
Power Wiring C 2-1/8 KO 2-1/8KO Control Wiring D 7/8 KO 7/8 KO
FIG. 4 - UNIT DIMENSIONS AND CLEARANCES
Connection Size
15 Ton 20 Ton
CLEARANCES
Overhead (Top) Front
(Piping and Access Panels) Left Side 24" Right Side 24" Rear 24"
2
Bottom
1
Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge.
2
Adequate snow clearance must be provided if winter operation is expected.
1
120"
30"
0"
6 Unitary Products Group
Loading...
+ 14 hidden pages