York DH 180, DH 240, DH 210, DH 300 User Manual

SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS
DH 180, 210, 240 & 300
15, 17.5, 20 & 25 NOMINAL TONS
®
TECHNICAL GUIDE
262260-YTG-E-1008

DESCRIPTION

YORK Sunline Ultra™ units are convertible single package high efficiency rooftops. All models have independent dual refrigerant circuits for efficient part load operation. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof.
All units include:
Powder Paint finish that meets ASTM-B-117 1000 hour salt spray standards
Two-stage cooling provide d by d ual indepen dent refriger­ation circuits with expansion valves, filter-driers, high and low pressure/loss of charge switches and freezestats
Hermetically sealed scroll compressors with crankcase heaters
Two-stage heating provided by dual independent heat exchangers with aluminized steel tubes, redundant gas valves, spark ignition with induced draft logic
Permanently lubricated motors
Bottom or side air discharge configuration capability (field convertible)
Belt drive blower motor with high static drive options
Constant supply air volume (CV) with optional variable air volume (VAV)
Manufactured under the quality standards of ISO9001
Twenty-four volt control circuit with compressor lock-out
Zero-25% fixed air damper with hood
Copper tube/aluminum fin coils
Hinged filter access and tool free latched doors optional
Hinged tool free blower, blower motor, filters and electri­cal panel access optional
Rigging holes in base rails for lifting
Single point power connection
Complete factory package - tested, charged and wired
CSA agency approvals on all units
WARRANTY
Factory Limited Parts Warranty
One-year parts warranty
A Five-year parts warranty on the compressor and electric heat elements.
Ten-year parts warranty on the gas-fired heat exchangers.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
262260-YTG-E-1008

TABLE OF CONTENTS

DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 5
FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . . 8
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 41
LIST OF FIGURES
Fig. #
1 UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 ALTITUDE/TEMPERATURE CONVERSION
FACTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
3 TYPICAL DH FIELD WIRING DIAGRAM . . . . . . . . . . . 32
4 UNIT DIMENSIONS DH180, 210, 240 & 300
(FRONT VIEW) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
5 REAR VIEW DIMENSIONS . . . . . . . . . . . . . . . . . . . . . 35
6 UNIT DIMENSIONS DH180, 210, 240 & 300
(RAINHOOD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
7 UNIT CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . 37
8 TYPICAL UNIT APPLICATIONS . . . . . . . . . . . . . . . . . 37
9 UNIT 4 POINT LOAD . . . . . . . . . . . . . . . . . . . . . . . . . . 38
10 UNIT 6 POINT LOAD . . . . . . . . . . . . . . . . . . . . . . . . . . 38
11 UNIT ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . . 39
12 ROOF CURB DUCT OPENINGS DIMENSIONS . . . . . 39
13 CUT AWAY OF ROOF CURB . . . . . . . . . . . . . . . . . . . 39
14 TYPICAL ROOFTOP INSTALLATION . . . . . . . . . . . . . 40
15 TYPICAL SIMPLICITY
DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
®
CONTROL WIRING
Pg. #
LIST OF TABLES
Tbl. #
1 INDOOR SOUND POWER RATING . . . . . . . . . . . . . . . 9
2 CAPACITY RATINGS - (ARI 360) . . . . . . . . . . . . . . . . . 9
3 GAS HEAT RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4 DH 180 COOLING CAPACITIES (15 TON) . . . . . . . . . 10
5 DH 210 COOLING CAPACITIES (17.5 TON) . . . . . . . . 12
6 DH 240 COOLING CAPACITIES (20 TON) . . . . . . . . . 14
7 DH 300 COOLING CAPACITIES (25 TON) . . . . . . . . . 16
8 ALTITUDE CORRECTION FACTORS . . . . . . . . . . . . . 18
9 SUPPLY AIR BLOWER PERFORMANCE (15 TON) -
COOLING ONLY 180 MBH - BOTTOM DUCT
CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Pg. #
Tbl. # Pg. #
10 SUPPLY AIR BLOWER PERFORMANCE (17.5 TON) -
COOLING ONLY 210 MBH - BOTTOM DUCT
CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
11 SUPPLY AIR BLOWER PERFORMANCE (20 TON) -
COOLING ONLY 240 MBH - BOTTOM DUCT
CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
12 SUPPLY AIR BLOWER PERFORMANCE (15 TON) -
GAS HEAT 180 MBH - BOTTOM DUCT
CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
13 SUPPLY AIR BLOWER PERFORMANCE (17.5 TON) -
GAS HEAT 210 MBH - BOTTOM DUCT
CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
14 SUPPLY AIR BLOWER PERFORMANCE (20 TON) -
GAS HEAT 240 MBH - BOTTOM DUCT
CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
15 SUPPLY AIR BLOWER PERFORMANCE (25 TON) -
GAS HEAT 300 MBH - BOTTOM DUCT
CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
16 BLOWER MOTOR AND DRIVE DATA . . . . . . . . . . . . 27
17 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . . . . . 27
18 POWER EXHAUST PERFORMANCE . . . . . . . . . . . . . 27
19 DH 180, 210 & 240 ELECTRICAL DATA WITHOUT
POWERED CONVENIENCE OUTLET . . . . . . . . . . . . 28
20 DH 300 ELECTRICAL DATA STANDARD MOTOR
WITHOUT POWERED CONVENIENCE OUTLET . . . 29 21 DH 300 ELECTRICAL DATA HIGH STATIC MOTOR
WITHOUT POWERED CONVENIENCE OUTLET . . . 29 22 DH 180, 210 & 240 ELECTRICAL DATA WITH
POWERED CONVENIENCE OUTLET . . . . . . . . . . . . 30
23 DH 300 ELECTRICAL DATA STANDARD MOTOR
WITH POWERED CONVENIENCE OUTLET . . . . . . . 31
24 DH 300 ELECTRICAL DATA HIGH STATIC MOTOR
WITH POWERED CONVENIENCE OUTLET . . . . . . . 31
25 DH VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . . . 32
26 ELECTRIC HEAT CORRECTION FACTORS . . . . . . . 32
27 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
28 OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . . . . . . 33
29 SUPPLY FAN VFD WEIGHTS, IN LBS. . . . . . . . . . . . . 33
30 UTILITIES ENTRY DATA . . . . . . . . . . . . . . . . . . . . . . . 34
31 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . . . . . 36
32 DH 180, 210, 240 & 300 4 POINT LOAD WEIGHT
DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
33 DH 180, 210, 240 & 300 6 POINT LOAD WEIGHT
DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
2 Johnson Controls Unitary Products
D H 180 N24 A 2 A AA 1 0 1 2 4 A
D = A/C, Single Pkg., R-22
Product Category
Airflow
1 = First Generation
Product Generation
2 = Second Generation
C00 = Cooling Only. No field installed
electric heat
Heat Type and Nominal Heat Capacity
N24 = 240 MBH Output Aluminized Steel N32 = 320 MBH Output Aluminized Steel S24 = 240 MBH Output Stainless Steel S32 = 320 MBH Output Stainless Steel
E18 = 18 KW E36 = 36 KW E54 = 54 KW E72 = 72 KW
Gas Heat Options
Electric Heat Options
180 = 15 Ton
Nominal Cooling Capacity
210 = 17.5 Ton 240 = 20 Ton 300 = 25 Ton
Product Identifier
H = 10.0-11.0 EER A/C
Voltage
2 = 208/230-3-60 4 = 460-3-60 5 = 575-3-60
Product Style
A = Style A
AA = None
Standard Cabinet
AB = Phase Monitor AC = Coil Guard AD = Dirty Filter Switch AE = Phase Monitor & Coil Guard AF = Phase Monitor & Dirty Filter Switch AG = Coil Guard & Dirty Filter Switch AH = Phase Monitor, Coil Guard & Dirty Filter Switch RC = Coil Guard & American Flag TA = Technicoat Condenser Coil TJ = Technicoat Evaporator Coil TS = Technicoat Evaporator & Condenser Coils
BA = Hinged Filter Door & Tool Free Access Panels
Additional Options
Hinged Filter Door & Tool Free Access Cabinet
BB = Phase Monitor, Hinged Filter Door & Tool Free
Access Panels
BC = Coil Guard, Hinged Filter Door & Tool Free
Access Panels
BD = Dirty Filter Switch, Hinged Filter Door &
Tool Free Access Panels
BE = Phase Monitor & Coil Guard, Hinged Filter
Door & Tool Free Access Panels
BF = Phase Monitor & Dirty Filter Switch, Hinged
Filter Door & Tool Free Access Panels
BG = Coil Guard & Dirty Filter Switch, Hinged Filter
Door & Tool Free Access Panels
BH = Phase Monitor, Coil Guard & Dirty Filter Switch,
Hinged Filter Door & Tool Free Access Panels
15-25 Ton Sunline Ultra™ Model Number Nomenclature
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
SS Drain Pan
Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.
CPC Controller, DFS, APS
Johnson Controller UNT 1126 (N2 protocol), DFS, APS
Honeywell Controller, DFS, APS
Novar Controller, DFS, APS
Simplicity IntelliComfort Controller
Simplicity IntelliComfort Controller w/ModLinc
York Commercial Comfort System (YCCS) Rtu Controller
2" Pleated filters
4" Pleated filters
BAS Ready Economizer (2-10 V.D.C. Actuator without a controller)
Double Wall Construction
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
Hot Gas Bypass (Standard on VAV, Optional on CV)
Variable Air Volume, VFD (not available with factory installed BAS options)
Variable Air Volume, VFD with ModLINC (not available with factory installed BAS options)
Variable Air Volume, VFD and Manual Bypass (not available with factory installed BAS options)
Variable Air Volume, VFD and Manual Bypass with ModLINC (not available with factory installed BAS options)
Variable Air Volume, VFD (BAS ready)
Variable Air Volume, VFD and Manual Bypass (BAS ready)
Variable Air Volume, VFD Ready (for customer provided, field installed drive)
Variable Air Volume, VFD Ready with ModLINC (for customer-provided, field-installed drive)
A = No Options Installed
Installation Options
B = Option 1 C = Option 2 D = Options 1 & 2 E = Option 3 F = Option 4 G = Options 1 & 3 H = Options 1 & 4 J = Options 1, 2 & 3 K = Options 1, 2, & 4 L = Options 1,3 & 4 M = Options 1, 2, 3, & 4
1 = Disconnect 2 = Non-Pwr'd Conv. Outlet 3 = Smoke Detector S.A.
4 = Smoke Detector R.A. 5 = Pwr'd Conv. Outlet
Options
N = Options 2 & 3 P = Options 2 & 4 Q = Options 2, 3, & 4 R = Options 3 & 4 S = Option 5 T = Options 1 & 5 U = Options 1, 3, & 5 V = Options 1, 4, & 5 W = Options 1, 3, 4, & 5 X = Options 3 & 5 Y = Options 4 & 5 Z = Options 3, 4 & 5
A = Std. Motor B = Std. Motor/Economizer C = Std. Motor/Economizer/Power Exhaust
(Downflow Only) D = Std. Motor/Motorized Damper E = Std. Motor/Motorized Damper/Barometric Relief J = Std. Motor/Economizer/Barometric Relief N = Hi Static P = Hi Static/Economizer Q = Hi Static/Economizer/Power Exhaust
(Downflow Only) R = Hi Static/Motorized Damper K = Hi Static/Motorized Damper/Barometric Relief S = Hi Static/Economizer/Barometric Relief
262260-YTG-E-1008

PRODUCT NOMENCLATURE

Johnson Controls Unitary Products 3
262260-YTG-E-1008

FEATURES

All models are available with a wide variety of factory­mounted options such as stainless steel heat exchangers, phase monitor, dirty filter switch, and coil guard to make them suitable for almost every application.
All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation.
All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with
factory installed power exhaust are suitable for bottom duct connections only. For bottom duct, you remove the
sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, you replace the supply and return air panels on the rear of the unit with a side duct flange accessory.
All models are available with these “factory mounted” outdoor air damper options:
Single enthalpy economizer with or without power exhaust
BAS-ready economizer with or without power exhaust
Motorized outdoor air damper
Barometric Relief Damper
A fixed outdoor air intake assembly will be shipped in the return air compartment of all units ordered without an econo­mizer or motorized outdoor air damper option. The assembly includes a rain hood with a damper that can be set for 10, 15 or 25% outdoor air. With bottom duct connections, the intake damper assembly should be mounted over the opening in the return air panel. With horizontal ductwork, it should be mounted on the return air duct.
All supply air blowers are equipped with a b el t dri ve th at can be adjusted to meet the exact requirements of the job. A high static drive option is available for applications with a higher CFM and/or static pressure requirement. A variable air volume (VAV) option using a variable frequency drive is available for applications requiring a constant supply duct pressure. A dif­ferential pressure transducer is used to monitor supply duct static pressure and return a speed reference signal to the VFD to control the output of the indoor blower motor.
All compressors include scroll compressors and internal pres­sure relief. Every refrigerant circuit includes an expansion valve, a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/ loss of charge switch to protect all system components. A hot gas bypass option, consisting of an adjustable compressor discharge bypass valve, is available for low cooling load applications.
®
Simplicity standardized a number of features previously available only as options or by utilizing additional controls.
Controls - Simplicity ® control boards have
Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0°F outdoor ambient without additional assis­tance. Optionally, the control board can be pro­grammed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.
The Simplicity® control board used in this product will effectively operate the cooling system down to 0°F when this product is applied in a comfort cooling application for people. An economizer is typically included in this type of application. When applying this product for process cooling applications (computer rooms, switchgear, etc.), please reference applications bulletin AE-011-07 or call the applications department for Unitary Products @ 1-877-UPG-SERV for guidance. Additional accessories may be needed for stable operation at temperatures below 30°F.
Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti short cycle delay can be temporarily overridden with the push of a button.
Lead-Lag - An integrated Lead-Lag option allows equal run time hours on all compressors, thereby extending the life of all compressors. This option is selectable on the unit control board.
Fan Delays - Fan on and fan off delays are fully pro­grammable. Furthermore, the heating and cooling fan delay times are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat.
Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the gas valve, if applicable, and the temperature limit switch on gas and electric heat units. The unit con­trol board will alarm on ignition failures, compressor lockouts and repeated limit switch trips.
Nuisance Trip Protection and Strikes - To prevent nuisance trouble calls, the control board uses a “three times, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the associated compressor.
On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power.
4 Johnson Controls Unitary Products
262260-YTG-E-1008
ELECTRICAL DISCONNECT MOUNTING LOCATION (Field installed)
KNOCKOUT FOR SIDE CONTROL WIRING ENTRY
KNOCKOUT FOR SIDE POWER WIRING ENTRY SIDE
TERMINAL BLOCK (For Single Point Power Supply with Electric Heat) ELECTRIC\ELECTRIC UNITS
BOTTOM POWER & CONTROL WIRING ENTRY
KNOCKOUTS FOR SIDE GAS SUPPLY ENTRY
HOLE FOR BOTTOM GAS SUPPLY ENTRY
POWER VENTOR MOTOR WITH POST PURGE CYCLE
BELT-DRIVE BLOWER MOTOR
FULL PERIMETER 14 GAUGE BASE RAILS WITH LIFTING HOLES
1" NPTI CONDENSATE DRAIN
SIDE AND BOTTOM SUPPLY & RETURN AIR DUCT OPENINGS(SIDE X SIDE)
OUTDOOR AIR OPENING FOR SLIDE-IN/PLUG-IN INTERNAL ECONOMIZER(OPTION)
2" DISPOSABLE FILTERS
ECONOMIZER HOOD
LONG LASTING POWDER PAINT FINISH
20 GAUGE ALUMINIZED STEEL TUBULAR HEAT EXCHANGERS
COPPER TUBE/ALUMINUM FIN CONDENSER COILS
LOW VOLTAGE RELAY BOARD AND TERMINAL STRIP
GAS/ELECTRIC
UNIT SHOWN
ELECTRIC HEATER LOCATION (OPTIONAL ELECTRIC/ELECTRIC UNITS)
HIGH EFFICIENCY COMPRESSORS WITH CRANKCASE HEATERS
LOCATION OF VFD (Optional)
LOCATION OF VFD BYPASS (Optional)

FIGURE 1 - UNIT CUTAWAY

All units have long lasting powder paint cabinets with 1000 hour salt spray test approval under ASTM-B117 procedures.
All models are CSA approved.
Warranty - All models include a one-year limited parts
Electric Heat Operation - All electric heat models (fac-
Johnson Controls Unitary Products 5
warranty on the complete unit. Compressors and electric heater elements carry a five-year warranty. Gas heat exchangers carry a 10-year parts warranty.
Gas Heat Operation - All gas heat units are built with two heating sections for two equal stages of capacity control. Each section includes a durable heat exchanger with aluminized steel or optional stainless steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards.
The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit.
tory installed only) are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to pro­vide a high velocity and uniform distribution of air across the heating elements. Every element is fully protected against excessive current and temperature by fuses and two thermal limit switches.
The power supply wiring can be routed into the control box through a threaded pipe connection in the base pan of the unit or through a knockout in the wiring panel on the front of the unit.
BAS Controls - Y ork’ s Sunline™ series unit s offer facto ry
mounted BAS controls such as Simplicity
Comfort
, Novar®, Honeywell, Johnson, York Commer-
®
Intelli-
cial Comfort System (YCCS) and CPC.

F A CTORY-INSTALLED OPTIONS

SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa­ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must be field-assembled before installing.
BAS-READY ECONOMIZER - Includes a slide-in / plug-
in damper assembly with fully modulating spring-return motor actuator with zero to 95-degree rotation capable of introducing up to 100% outdoor air with nominal 1% leak­age type dampers.
Actuator requires 2-10 VDC input from an external source, such as a field-installed or factory-installed BAS controller. BAS-ready actuators have an adjustable auxil­iary end-switch for optional power exhaust control.
For units with optional VAV or Simplicity® Intelli-Com­fort™ control, a factory-installed, dry bulb sensor deter­mines if outdoor air temperature is low enough to provide free-cooling operation. (Field-installed humidity sensors for either outdoor air or outdoor & return air streams are
262260-YTG-E-1008
available for single enthalpy and differential enthalpy configurations, respectively).
The rainhood is painted to match the basic unit and must be field-assembled before installing.
POWER EXHAUST - Our economizer options are avail­able with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation. BAS­ready economizer actuators have an adjustable auxiliary end-switch to provide a range of damper positions available to energize power exhaust. For units with optional VAV, power exhaust is energized by means of a binary output signal from the unit's VAV control board.
The exhaust fan, motor and controls are installed and wired at the factory. The rain hood must be assembled and installed in the fiel d .
The power exhaust option can only be used on bot­tom duct configurations.
MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2­position, spring return motor actuator which opens to a pre-set position whenever the supply air blower is oper­ating and will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must be field assembled before installing.
BAROMETRIC RELIEF DAMPER - This damper option can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.
PHENOLIC COATED EVAPORATOR AND CON- DENSER COILS - Special coating process that utilizes Techni coat 10-1" proce s ses. Coating is applied by total immersion of the complete coil for maximum protection.
ELECTRIC HEA T ERS wired for single point power sup­ply. These nickel chromium heater elements are pro­vided with limit and automatic reset capability to prevent operation at excessive temperatures.
VARIABLE AIR VOLUME (VAV) - A factory-installed variable frequency drive (VFD), mounted in the Blower Access compartment, is used to control the speed of the indoor blower motor in order to maintain a constant static pressure in the supply duct. A pressure transducer and VAV control board are mounted inside the control box. The drive comes completely wired and pre-programmed from the factory.
An optional, factory-installed manual bypass switch available with factory-installed VFD can be found in the
Blower Motor Access compartment. The switch can be used to either route power to the VFD for modulating control of the blower motor, to bypass the drive and oper­ate the motor at full speed, or to power the drive (and not the motor) for diagnostic purposes.
Due to space limitations, VAV is not available with any of the factory-installed BAS options described below, but is available with ‘BAS-ready’ models. Terminal blocks are provided in the control box for field wiring of the cus­tomer-installed BAS.
A ‘VFD-ready’ option provides the provisions for a cus­tomer-installed drive. The unit comes with a mounting bracket installed in the Blower Access compartment which may accommodate other vendor’s drives depend­ing on their size. In order to utilize the unit’s mounting bracket, the maximum recommended drive dimensions are as follows:
For 5-hp motor applications........................10” H x 6” W x 7” D
For 7.5 thru 15-hp motor applications.........13” H x 8” W x 8” D
If the drive will not fit in the allotted space, then it will have to be mounted elsewhere; either within the building on a perpendicular wall which is not subjected to exces­sive temperature, vibration, humidity, dust, corrosive gas, explosive gas, etc., or within an appropriate enclo­sure rated for outside installation to safeguard against moisture, dust and excessive heat.
A terminal block located in the control box is provided for field connection of the VFD controls.
HOT GAS BYPASS - To allow for low cooling load oper­ation, a direct-acting pressure-modulating bypass control valve installed on the system #1 discharge line is used to divert high temperature, high pressure refrigerant around the TXV in order to maintain a desired minimum evapo­rator pressure. HGBP is standard on all units with VAV and optional with CV units.
FILTER OPTIONS - Standard units are shipped with 2” throw-away filters installed. 2” pleated and 4” pleated fil­ters are offered as a factory installed option.
CONVENIENCE OUTLET - This 110 volt outlet can be “powered” by the unit with a stepdown transformer or you may order the unit with a “non-powered” conve­nience outlet that can be wired in the field.
DISCONNECT SWITCH - A HACR breaker sized to the unit max fuse size is provided. Factory installed option only.
BAS - Building Automation System Controls (avail­able on two-system cooling product only).
Simplicity® INTELLI-Comfort™ CONTROL - The York® Simplicity® INTELLI-Comfort™ control is factory
installed. It includes a supply air sensor, a return air sen­sor, and an outside air sensor . There are provisions for a field installed dirty filter indicator switch, an air-proving
6 Johnson Controls Unitary Products
262260-YTG-E-1008
switch, an Outside Air Humidity sensor, a Return Air Humidity sensor, an Inside IAQ sensor, and an Outside Air IAQ sensor. Construction mode operation, 365-day real time clock with 7 day programming plus holiday scheduling is built-in. Two different modes of demand ventilation are achieved through the INTELLI-Comfort™ using CO
sensors. It uses an inside CO2 sensor to per-
2
form Demand Ventilation. It can also use an Outside CO sensor to perform Differential Demand Ventilation. It
uses a Patented Comfort Ventilation algorithm to provide comfortable ventilation air temperature. The patented economizer-loading algorithm will protect the equipment when harsh operating conditions exist. Humidity in the occupied space or return duct can be monitored and controlled via humidity sensors and the on-board con­nection for hot gas re-heat system. It uses the INTELLI­Start™ algorithm to maximize energy savings by recov­ering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the Occupied Time Period to begin. The Simplicity® INTELLI-Comfort™ bal­ances space temperature, ve nt il a t i o n a ir te mp erature,
and humidity for ultimate comfort.
CO
2
Simplicity® INTELLI-Comfort™ with ModLINC CON- TROL - The York® Simplicity® INTELLI-Comfort™ with
ModLINC control is factory installed. It includes all the features of the INTELLI-Comfort™ control with an addi­tional control to translate communications from MOD­BUS to the BACnet MSTP protocol.
Novar® BAS CONTROL - The Novar® building automa­tion system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.
JOHNSON CONTROLS BAS CONTROL - The John­son Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sen­sor, return air sensor, dirty filter indicator switch, and air proving switch.
CPC BAS CONTROL - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building auto­mation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch and air proving switch.
HONEYWELL BAS CONTROL - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch.
YORK COMMERCIAL COMFORT SYSTEM (YCCS) ­Provides rooftop system integration for YCCS single zone, change-over bypass and VAV systems.
SMOKE DETECTORS - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the
2
air compartment.
Factory installed smoke detectors in the return air, may be subjected to freezing temperatures during “off” times due to out side air infiltration. these smoke detectors have an operational limit of 32°F to 131°F. smoke detectors installed in areas that could be out side those limitations will have to be moved to prevent having false alarms.
COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.
STAINLESS STEEL HEAT EXCHANGER - For applica- tions in corrosive environments, this option provides a full stainless steel heat exchanger assembly.
ST AINLESS STEEL DRAIN PAN- An optional rust-proof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environments.
PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of­phase condition.
HIGH ST ATIC DRIVE - May include a belt, blower pulley, motor pulley or a motor change to enhance blower per­formance.
DIRTY FILTER SWITCH - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.
HINGED FILTER DOOR/”T OOL FREE” BLOWER AND ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance.
NOTE: Knobs are shipped separately within the unit to pre-
vent shipping damage. These must be field installed for tool free operation.
Johnson Controls Unitary Products 7
262260-YTG-E-1008
HINGED/"TOOL FREE" BLOWER, BLOWER MOTOR, FIL TER AND ELECTRIC ACCESS PANELS - This option allows for complete hinged and tool free access to the unit's blower, blower motor , filters and electrical panel sections.

FIELD-INSTALLED ACCESSORIES

SINGLE INPUT ELECTRONIC ENTHALPY ECONO­MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa­ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must be field-assembled before installing.
MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2­position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basic unit and must be field assembled before installing.
ROOF CURBS - Fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly.
They're designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports.
HIGH ALTITUDE NATURAL GAS - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet.
PROPANE - Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane.
HIGH ALTITUDE PROPANE - Burner orifices and pilot orifices are provided for proper furnace operation at alti-
tudes up to 6,000 feet. This accessory supplements the basic propane conversion kit.
SIDE DUCT FLANGES - One-inch flanges replace the supply and return air panels on the rear of the unit to accommodate horizontal duct connections. These flanges can also be used individually for bottom supply/ horizontal return or horizontal supply/bottom return. They cannot be used on units with power exhaust.
BAROMETRIC RELIEF DAMPER - This damper acces­sory can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.
HIGH ST ATIC DRIVE - May include a belt, blower pulley, motor pulley or a motor change to enhance blower per­formance.
ENTHALPY ACCESSORY CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.
BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work.
FLUE EXHAUST EXTENSION KIT - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes.
WOOD SKID - Allows unit to be handled with 90” forks.
CO
COIL GUARD - Customers can purchase a coil guard kit
PHASE MONITORS - Designed to prevent unit damage.
SENSOR - Senses CO2 levels and automatically
2
overrides the economizer when levels rise above the present limits.
to protect the condenser coil from damage. This is not a hail guard kit.
The phase monitor will shut the unit down in an out-of­phase condition.
8 Johnson Controls Unitary Products
262260-YTG-E-1008

TABLE 1: INDOOR SOUND POWER RATING

UNIT SIZE
CFM
ESP BLOWER
IWG RPM BHP 63 125 250 500 1,000 2,000 4,000 8,000
1
SOUND POWER (db 10
Octave Band Centerline Frequency (Hz)
-12
Watts)
SWL
dB(A)
180 6,000 1.00 1,080 4.60 99 99 89 82 84 77 72 67 89 56
210, 240 8,000 1.00 1,120 6.65 102 102 92 85 87 80 75 70 92 59
300 10,000 1.30 1,160 12.5 108 108 98 91 93 86 81 76 98 65
1. These values have bee n accessed using a model of sound propagation from a point source into the hemispheri c\free field. The dBA val­ues provided are to be used for refe rence o nly. Calculation of dBA values cover matters of system design and the fan manu facture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA value or sound data in any other form than soun d power level ratings.
2. At a distance of 10 feet from the blower.

TABLE 2: CAPACITY RATINGS - (ARI 360)

MODEL MBH
COOLING ONLY DH180C00 DH210C00 DH240C00 DH300C00
COOLING WITH GAS HEAT DH180N/S DH210N/S DH240N/S DH300N/S
COOLING WITH ELECTRIC HEAT
DH180E18 DH180E36 DH180E54 DH180E72 DH210E18
DH210E36 DH210E54 DH210E72 DH240E18 DH240E36 DH240E54 DH240E72 DH300E18 DH300E36 DH300E54 DH300E72
4
178
205 10.2 10.8 223 9.7 10.2 271 9.6 9.6
4
178
205 10.2 10.8 223 9.7 10.2 271 9.6 9.6
4
178
4
178
4
176
4
176
205 10.2 10.8 205 10.2 10.8 203 10.0 10.6 203 10.0 10.6 223 9.6 10.1 223 9.6 10.1 221 9.5 9.7 219 9.5 9.7 271 9.6 9.6 271 9.6 9.6 269 9.5 9.4 269 9.5 9.4
1. 80/67°F Indoor and 95°F outdoor.
2. EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu’s per hour (Btuh) divided by the power
2
EER
10.8 11.3
10.8 11.3
10.8 11.3
10.8 11.3
10.5 11.0
10.5 11.0
1
3
IPLV

TABLE 3: GAS HEAT RATINGS

MODEL MBH INPUT MBH OUTPUT DH180N/S24 DH180N/S32 DH210N/S24 DH210N/S32 DH240N/S24 DH240N/S32 DH300N/S24 DH300N/S32
300 240 400 320 300 240 400 320 300 240 400 320 300 240 400 320
1. All units are two-stage heat ing. First stage is 50% of total.
SSE = Steady State Efficiency (80%) - Output divided by Input
For units with VFD and electric or gas heat, the speed of the indoor blower motor continues to be controlled by duct static pressure via the VAV con trol board.
If there are VAV boxes present in the duct system, the boxes must be driven to the full-open position using a customer-supplied power source to assure adequate airflow across electric heating elements or gas heat exchanger tubes.
1
input in watts, expressed in Btuh per watt (Btuh/watt).
3. IPLV = Integrated part load value.
4. Deduct 2 MBH @ 208V.
dB(A)
@
10Ft.
-
2
Johnson Controls Unitary Products 9
262260-YTG-E-1008

TABLE 4: DH 180 COOLING CAPACITIES (15 TON)

AIR ON
EVAPORATOR
COIL
CFM
WB
°F
77 223.0 11.3 100.4 79.0 57.7 - - - 218.1 12.9 99.3 77.9 56.5 - - ­72 211.0 11.2 133.1 111.7 90.3 68.9 - - 203.0 12.6 130.5 109.2 87.8 66.4 - -
4500
67 199.0 11.1 165.8 144.4 123.0 101.6 80.2 - 188.0 12.3 161.8 140.4 119.0 97.6 76.2 ­62 181.3 10.8 181.3 178.6 157.3 135.9 114.5 93.1 173.0 12.1 173.0 169.9 148.5 127.2 105.8 84.4 57 178.5 10.5 178.5 179.1 162.3 140.9 119.6 98.2 170.1 12.1 170.1 170.1 151.1 129.7 108.3 86.9 77 231.5 11.3 107.2 87.6 62.3 - - - 225.0 12.9 112.3 87.0 61.8 - - ­72 219.0 11.2 148.2 122.9 97.7 72.4 - - 209.5 12.6 146.4 121.2 95.9 70.6 - -
5250
67 206.5 11.2 189.2 158.3 133.0 107.7 82.5 - 194.0 12.4 180.5 155.3 130.0 104.7 79.5 ­62 188.1 10.9 188.1 186.8 170.1 144.9 119.6 94.3 178.5 12.2 178.5 177.0 162.3 137.0 111.7 86.5 57 185.3 10.6 185.3 185.5 175.7 150.4 125.1 99.8 175.6 12.2 175.6 175.6 165.0 139.8 114.5 89.2 77 240.0 11.4 114.0 96.2 67.0 - - - 232.0 13.0 125.3 96.2 67.0 - - ­72 227.0 11.3 163.3 134.2 105.0 75.8 - - 216.0 12.7 162.3 133.2 104.0 74.8 - -
6000
67 214.0 11.2 212.6 172.2 143.0 113.8 84.7 - 200.0 12.4 199.3 170.2 141.0 111.8 82.7 ­62 195.0 10.9 195.0 195.0 183.0 153.8 124.7 95.5 184.0 12.2 184.0 184.0 176.0 146.8 117.7 88.5 57 192.0 10.6 192.0 192.0 189.0 159.8 130.7 101.5 181.0 12.2 181.0 181.0 179.0 149.8 120.7 91.5 72 226.4 11.2 178.0 144.8 111.6 78.4 - - 217.6 12.8 176.0 142.7 109.5 76.3 - -
6750
67 213.5 11.2 212.8 185.2 152.0 118.8 85.6 - 201.5 12.5 201.2 181.7 148.5 115.3 82.1 ­62 194.5 10.8 194.5 194.5 188.5 155.3 122.1 88.9 185.4 12.2 185.4 185.4 181.4 148.2 115.0 81.8 57 191.5 10.5 191.5 191.5 190.0 156.8 123.6 90.4 182.4 12.2 182.4 182.4 181.4 148.1 114.9 81.7 72 225.8 11.2 192.8 155.5 118.2 81.0 - - 219.2 12.8 189.6 152.3 115.1 77.8 - -
7500
67 213.0 11.1 213.0 198.3 161.0 123.7 86.5 - 203.0 12.5 203.0 193.3 156.0 118.7 81.5 ­62 194.0 10.8 194.0 194.0 194.0 156.7 119.5 82.2 186.8 12.3 186.8 186.8 186.8 149.5 112.2 75.0 57 191.0 10.5 191.0 191.0 191.0 153.8 116.5 79.3 183.7 12.3 183.7 183.7 183.7 146.5 109.2 71.9
TOTAL
CAP.
MBH
1
POWER
INPUT
KW
75°F 85°F
SENSIBLE CAPACITY, MBH
2
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
90 85 80 75 70 65 90 85 80 75 70 65
TEMPERATURE OF AIR ON CONDENSER COIL
TOTAL
CAP.
MBH
POWER
1
INPUT
KW
2
SENSIBLE CAPACITY, MBH
AIR ON
EVAPORATOR
COIL
CFM
WB
°F
77 213.2 14.5 98.2 76.8 55.4 - - - 198.8 16.1 97.0 75.6 54.2 - - ­72 195.1 14.0 128.0 106.6 85.2 63.8 - - 182.7 15.4 125.1 103.7 82.4 61.0 - -
4500
67 177.0 13.5 157.8 136.4 115.0 93.6 72.2 - 166.5 14.8 153.3 131.9 110.5 89.1 67.7 ­62 164.6 13.4 164.6 161.2 139.8 118.4 97.1 75.7 155.6 14.7 155.6 153.8 135.7 114.3 93.0 71.6 57 161.8 13.7 161.8 161.2 139.8 118.4 97.1 75.7 152.2 15.0 152.2 151.9 134.0 112.6 91.3 69.9 77 218.6 14.5 117.4 86.5 61.2 - - - 203.9 16.2 117.3 84.6 59.4 - - ­72 200.0 14.0 144.7 119.4 94.1 68.8 - - 187.3 15.5 140.7 115.5 90.2 64.9 - -
5250
67 181.5 13.6 171.9 152.3 127.0 101.7 76.5 - 170.8 14.8 164.1 146.3 121.0 95.7 70.5 ­62 168.8 13.5 168.8 167.1 154.4 129.1 103.9 78.6 159.5 14.8 159.5 158.7 148.6 123.3 98.1 72.8 57 165.9 13.7 165.9 165.6 154.4 129.1 103.9 78.6 156.1 15.1 156.1 156.0 146.8 121.5 96.2 70.9 77 224.0 14.6 136.6 96.2 67.0 - - - 209.0 16.3 137.6 93.7 64.5 - - ­72 205.0 14.1 161.3 132.2 103.0 73.8 - - 192.0 15.6 156.3 127.2 98.0 68.8 - -
6000
67 186.0 13.6 186.0 168.2 139.0 109.8 80.7 - 175.0 14.9 175.0 160.7 131.5 102.3 73.2 ­62 173.0 13.5 173.0 173.0 169.0 139.8 110.7 81.5 163.5 14.9 163.5 163.5 161.5 132.3 103.2 74.0 57 170.0 13.8 170.0 170.0 169.0 139.8 110.7 81.5 160.0 15.2 160.0 160.0 159.5 130.3 101.2 72.0 72 208.9 14.3 173.9 140.7 107.4 74.2 - - 195.8 15.7 170.2 137.0 103.8 70.6 - -
6750
67 189.5 13.8 189.5 178.2 145.0 111.8 78.6 - 178.5 15.0 178.5 170.1 139.3 106.0 72.8 ­62 176.3 13.6 176.3 176.3 174.3 141.0 107.8 74.6 166.8 15.0 166.8 166.8 165.8 132.6 99.4 66.1 57 173.2 14.0 173.2 173.2 172.7 139.5 106.3 73.1 163.2 15.3 163.2 163.2 163.0 129.7 96.5 63.3 72 212.7 14.4 186.4 149.2 111.9 74.6 - - 199.7 15.9 184.1 146.8 109.6 72.3 - -
7500
67 193.0 13.9 193.0 188.3 151.0 113.7 76.5 - 182.0 15.2 182.0 179.6 147.0 109.7 72.5 ­62 179.5 13.8 179.5 179.5 179.5 142.3 105.0 67.7 170.0 15.1 170.0 170.0 170.0 132.8 95.5 58.3 57 176.4 14.1 176.4 176.4 176.4 139.1 101.9 64.6 166.4 15.5 166.4 166.4 166.4 129.1 91.9 54.6
TOTAL
CAP.
MBH
1
POWER
INPUT
KW
95°F 105°F
TEMPERATURE OF AIR ON CONDENSER COIL
SENSIBLE CAPACITY, MBH
2
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
90 85 80 75 70 65 90 85 80 75 70 65
TOTAL
CAP.
MBH
POWER
1
INPUT
KW
2
SENSIBLE CAPACITY, MBH
10 Johnson Controls Unitary Products
262260-YTG-E-1008
Nominal Rating

TABLE 4: DH 180 COOLING CAPACITIES (15 TON) (CONTINUED)

AIR ON
EVAPORATOR
COIL
CFM
4500
5250
6000
6750
7500
WB
°F
77 184.5 17.8 95.8 74.4 53.0 - - ­72 170.3 16.9 122.3 100.9 79.5 58.1 - ­67 156.0 16.0 148.8 127.4 106.0 84.6 63.2 ­62 146.5 16.1 146.5 146.5 131.6 110.3 88.9 67.5 57 142.7 16.4 142.7 142.7 128.2 106.8 85.5 64.1 77 189.3 17.9 117.2 82.8 57.5 - - ­72 174.6 17.0 136.8 111.5 86.3 61.0 - ­67 160.0 16.1 156.4 140.3 115.0 89.7 64.5 ­62 150.2 16.2 150.2 150.2 142.8 117.6 92.3 67.0 57 146.3 16.5 146.3 146.3 139.1 113.8 88.6 63.3 77 194.0 18.0 138.6 91.2 62.0 - - ­72 179.0 17.1 151.3 122.2 93.0 63.8 - ­67 164.0 16.2 164.0 153.2 124.0 94.8 65.7 ­62 154.0 16.3 154.0 154.0 154.0 124.8 95.7 66.5 57 150.0 16.6 150.0 150.0 150.0 120.8 91.7 62.5 72 182.8 17.2 166.5 133.3 100.1 66.9 - ­67 167.5 16.3 167.5 162.1 133.5 100.3 67.1 ­62 157.3 16.4 157.3 157.3 157.3 124.1 90.9 57.7 57 153.2 16.7 153.2 153.2 153.2 120.0 86.8 53.6 72 186.6 17.3 181.8 144.5 107.3 70.0 - ­67 171.0 16.4 171.0 171.0 143.0 105.7 68.5 ­62 160.6 16.5 160.6 160.6 160.6 123.3 86.1 48.8 57 156.4 16.8 156.4 156.4 156.4 119.1 81.9 44.6
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Perfor­mance Table for the KW of the supply air blower motor.
2. These ratings include the condenser fan motors (Total 2.3 KW) and the compressor motors but not the supply air blower motor.
TEMPERATURE OF AIR ON CONDENSER COIL
MBH
1
POWER
INPUT
KW
2
TOTAL
CAP.
115°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
90 85 80 75 70 65
Johnson Controls Unitary Products 11
262260-YTG-E-1008

TABLE 5: DH 210 COOLING CAPACITIES (17.5 TON)

AIR ON
EVAPORATOR
COIL
CFM
WB
°F
77 241.5 13.9 119.5 94.6 69.6 - - - 240.2 15.6 119.7 94.8 69.9 - - ­72 232.2 13.2 159.7 134.8 109.8 84.9 - - 226.1 15.1 156.3 131.4 106.4 81.5 - -
5250
67 223.0 12.6 199.9 174.9 150.0 125.1 100.1 - 212.0 14.5 192.9 167.9 143.0 118.1 93.1 ­62 204.4 12.4 204.4 204.4 182.1 157.1 132.2 107.2 193.5 14.3 193.5 193.5 170.5 145.5 120.6 95.6 57 200.4 12.6 200.4 200.4 183.1 158.2 133.2 108.3 191.2 14.3 191.2 191.2 171.8 146.9 121.9 97.0 77 250.1 14.5 136.3 104.8 75.3 - - - 248.8 16.0 140.3 105.8 76.3 - - ­72 240.5 13.8 177.8 148.3 118.9 89.4 - - 234.2 15.4 175.2 145.7 116.2 86.7 - -
6125
67 231.0 13.1 219.4 191.9 162.4 132.9 103.4 - 219.6 14.9 210.0 185.6 156.2 126.7 97.2 ­62 211.7 12.9 211.7 211.7 197.2 167.7 138.2 108.7 200.5 14.7 200.5 200.5 186.1 156.6 127.2 97.7 57 207.6 13.1 207.6 207.6 198.3 168.8 139.3 109.9 198.0 14.7 198.0 198.0 187.6 158.1 128.6 99.1 77 258.7 15.1 153.0 115.0 81.0 - - - 257.4 16.4 160.9 116.7 82.7 - - ­72 248.8 14.4 195.9 161.9 127.9 93.9 - - 242.3 15.8 194.0 160.0 126.0 92.0 - -
7000
67 238.9 13.7 238.9 208.8 174.8 140.8 106.8 - 227.2 15.2 227.2 203.3 169.3 135.3 101.3 ­62 219.0 13.5 219.0 219.0 212.3 178.3 144.3 110.2 207.4 15.0 207.4 207.4 201.8 167.8 133.8 99.7 57 214.7 13.7 214.7 214.7 213.5 179.5 145.5 111.4 204.9 15.0 204.9 204.9 203.4 169.4 135.4 101.3 72 253.0 14.5 214.9 176.1 137.4 98.6 - - 246.9 15.9 212.6 173.9 135.2 96.4 - -
7875
67 243.0 13.8 243.0 227.9 187.8 149.0 110.3 - 231.6 15.3 231.6 219.6 181.6 142.9 104.1 ­62 222.7 13.6 222.7 222.7 219.4 180.6 141.9 103.1 211.4 15.1 211.4 211.4 208.6 169.8 131.1 92.3 57 218.3 13.8 218.3 218.3 217.7 179.0 140.2 101.5 208.8 15.1 208.8 208.8 208.1 169.3 130.6 91.8 72 257.2 14.6 233.8 190.3 146.9 103.4 - - 251.6 16.0 231.2 187.8 144.3 100.8 - -
8750
67 247.0 13.9 247.0 247.0 200.7 157.2 113.8 - 235.9 15.4 235.9 235.9 193.9 150.4 107.0 ­62 226.4 13.7 226.4 226.4 226.4 183.0 139.5 96.0 215.3 15.2 215.3 215.3 215.3 171.9 128.4 84.9 57 222.0 13.9 222.0 222.0 222.0 178.5 135.0 91.6 212.7 15.2 212.7 212.7 212.7 169.3 125.8 82.3
TOTAL
CAP.
MBH
1
POWER
INPUT
KW
75°F 85°F
SENSIBLE CAPACITY, MBH
2
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
90 85 80 75 70 65 90 85 80 75 70 65
TEMPERATURE OF AIR ON CONDENSER COIL
TOTAL
CAP.
MBH
POWER
1
INPUT
KW
2
SENSIBLE CAPACITY, MBH
AIR ON
EVAPORATOR
COIL
CFM
WB
°F
77 238.9 17.4 120.0 95.0 70.1 - - - 228.3 15.0 116.1 91.2 66.2 - - ­72 219.9 16.9 152.9 128.0 103.0 78.1 - - 209.9 14.6 148.0 123.0 98.1 73.1 - -
5250
67 201.0 16.5 185.9 160.9 136.0 111.1 86.1 - 191.5 14.2 179.8 154.8 129.9 105.0 80.0 ­62 182.6 16.3 182.6 182.6 158.8 133.9 108.9 84.0 176.2 14.0 176.2 176.2 152.7 127.8 102.9 77.9 57 182.0 16.1 182.0 182.0 160.5 135.5 110.6 85.6 176.4 13.9 176.4 176.4 153.3 128.3 103.4 78.4 77 247.5 17.6 144.4 106.7 77.2 - - - 235.7 17.2 143.3 102.8 73.3 - - ­72 235.0 17.2 172.5 143.1 124.0 84.1 - - 223.4 19.0 167.5 138.0 108.6 79.1 - -
6125
67 215.5 16.7 200.7 179.4 163.8 120.4 90.9 - 203.8 18.5 191.8 173.3 143.8 114.3 84.8 ­62 195.8 16.5 189.2 189.2 191.3 145.6 116.1 86.6 187.4 18.2 181.8 181.8 169.1 139.6 110.1 80.6 57 195.1 16.3 188.5 188.5 193.3 147.4 117.9 88.4 187.8 18.1 182.1 182.1 169.7 140.2 110.7 81.2 77 256.1 17.7 168.8 118.4 84.4 - - - 243.0 19.5 170.4 114.4 80.4 - - ­72 235.8 17.2 192.1 158.1 124.1 90.1 - - 223.4 19.0 187.1 153.1 119.1 85.0 - -
7000
67 215.5 16.7 215.5 197.8 163.8 129.8 95.8 - 203.8 18.5 203.8 191.7 157.7 123.7 89.7 ­62 195.8 16.5 195.8 195.8 191.3 157.3 123.3 89.2 187.5 18.2 187.5 187.5 185.5 151.4 117.4 83.4 57 195.1 16.3 195.1 195.1 193.3 159.3 125.3 91.2 187.8 18.1 187.8 187.8 186.1 152.0 118.0 84.0 72 240.9 17.3 210.4 171.7 132.9 94.2 - - 228.3 19.1 205.3 166.5 127.8 89.0 - -
7875
67 220.2 16.8 220.2 211.3 175.5 136.7 98.0 - 208.3 18.6 208.3 202.2 169.3 130.5 91.8 ­62 200.0 16.6 200.0 200.0 197.8 159.0 120.3 81.5 191.6 18.3 191.6 191.6 190.6 151.8 113.1 74.3 57 199.3 16.4 199.3 199.3 198.4 159.7 120.9 82.2 191.9 18.2 191.9 191.9 191.0 152.3 113.5 74.8 72 246.0 17.4 228.7 185.2 141.8 98.3 - - 233.2 19.2 223.5 180.0 136.5 93.1 - -
8750
67 224.8 16.9 224.8 224.8 187.1 143.6 100.2 - 212.8 18.7 212.8 212.8 180.9 137.4 93.9 ­62 204.2 16.7 204.2 204.2 204.2 160.8 117.3 73.8 195.7 18.4 195.7 195.7 195.7 152.2 108.7 65.3 57 203.5 16.5 203.5 203.5 203.5 160.0 116.6 73.1 196.0 18.3 196.0 196.0 196.0 152.5 109.1 65.6
TOTAL
CAP.
MBH
1
POWER
INPUT
KW
95°F 105°F
TEMPERATURE OF AIR ON CONDENSER COIL
SENSIBLE CAPACITY, MBH
2
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
90 85 80 75 70 65 90 85 80 75 70 65
TOTAL
CAP.
MBH
POWER
1
INPUT
KW
2
SENSIBLE CAPACITY, MBH
12 Johnson Controls Unitary Products
262260-YTG-E-1008
Nominal Rating

TABLE 5: DH 210 COOLING CAPACITIES (17.5 TON) (CONTINUED)

AIR ON
EVAPORATOR
COIL
CFM
5250
6125
7000
7875
8750
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Performa nce Table for the KW of the supply air blower motor.
2. These ratings include the condenser fan motors (Total 1 KW) and the compressor motors but not the supply air blower motor.
TOTAL
CAP.
WB
°F
77 217.8 12.5 112.3 87.3 62.4 - - - 207.3 10.1 108.4 83.5 58.5 - - ­72 199.9 12.2 143.0 118.0 93.1 68.1 - - 189.9 9.9 138.0 113.1 88.1 63.2 - ­67 182.0 12.0 173.7 148.7 123.8 98.9 73.9 - 172.5 9.7 167.6 142.6 117.7 92.8 67.8 ­62 169.7 11.8 169.7 169.7 146.7 121.7 96.8 71.8 163.2 9.5 163.2 163.2 140.6 115.6 90.7 65.7 57 170.9 11.8 170.9 170.9 146.0 121.1 96.1 71.2 165.4 9.6 165.4 165.4 138.8 113.8 88.9 63.9 77 223.9 16.9 142.1 98.9 69.4 - - - 212.0 16.5 141.0 95.0 65.5 - - ­72 205.5 16.5 162.5 133.0 103.5 74.1 - - 194.2 16.2 157.5 128.0 98.5 69.1 - ­67 187.1 16.1 182.9 167.2 137.7 108.2 78.7 - 176.5 15.8 174.0 161.1 131.6 102.1 72.6 ­62 174.4 15.8 174.4 174.4 163.1 133.6 104.2 74.7 167.0 15.6 167.0 167.0 157.2 127.7 98.2 68.7 57 175.7 15.8 175.7 175.7 162.4 132.9 103.4 74.0 169.2 15.7 169.2 169.2 155.2 125.7 96.2 66.7 77 229.9 21.2 172.0 110.4 76.4 - - - 216.8 23.0 173.6 106.4 72.4 - - ­72 211.0 20.7 182.0 148.0 114.0 80.0 - - 198.6 22.5 177.0 143.0 109.0 74.9 - ­67 192.1 20.2 192.1 185.6 151.6 117.6 83.6 - 180.4 22.0 180.4 179.5 145.5 111.5 77.5 ­62 179.1 19.9 179.1 179.1 179.6 145.6 111.6 77.5 170.8 21.6 170.8 170.8 170.8 139.7 105.7 71.7 57 180.4 19.9 180.4 180.4 178.8 144.8 110.8 76.7 173.1 21.7 173.1 173.1 171.6 137.5 103.5 69.5 72 215.7 20.8 200.1 161.4 122.6 83.9 - - 203.1 22.6 195.0 156.3 117.5 78.8 - ­67 196.4 20.3 196.4 193.2 163.1 124.4 85.6 - 184.5 22.1 184.5 184.1 156.9 118.2 79.4 ­62 183.1 20.0 183.1 183.1 183.4 144.6 105.9 67.1 174.7 21.7 174.7 174.7 174.7 137.4 98.7 59.9 57 184.4 20.0 184.4 184.4 183.6 144.9 106.1 67.4 177.0 21.8 177.0 177.0 176.3 137.5 98.8 60.0 72 220.4 20.9 218.2 174.8 131.3 87.8 - - 207.7 22.7 207.7 169.5 126.1 82.6 - ­67 200.7 20.4 200.7 200.7 174.6 131.1 87.7 - 188.7 22.2 188.7 188.7 168.4 124.9 81.4 ­62 187.1 20.1 187.1 187.1 187.1 143.6 100.2 56.7 178.6 21.8 178.6 178.6 178.6 135.1 91.6 48.1 57 188.5 20.1 188.5 188.5 188.5 145.0 101.5 58.1 181.0 21.9 181.0 181.0 181.0 137.5 94.0 50.5
MBH
1
POWER
INPUT
KW
2
115°F 125°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
90 85 80 75 70 65 90 85 80 75 70 65
TEMPERATURE OF AIR ON CONDENSER COIL
TOTAL
CAP.
MBH
1
POWER
INPUT
KW
2
SENSIBLE CAPACITY, MBH
Johnson Controls Unitary Products 13
262260-YTG-E-1008

TABLE 6: DH 240 COOLING CAPACITIES (20 TON)

AIR ON
EVAPORATOR
COIL
CFM
WB
°F
77 277.0 19.1 159.2 130.7 102.2 - - - 262.0 20.5 153.7 125.2 96.7 - - ­72 263.0 18.6 196.1 167.6 139.1 110.6 - - 249.0 20.1 190.4 161.8 133.3 104.8 - -
6000
67 249.0 18.0 233.0 204.5 176.0 147.5 119.0 - 236.0 19.6 227.0 198.5 170.0 141.5 113.0 ­62 240.6 17.9 240.6 240.6 215.3 186.8 158.3 129.8 228.6 19.4 228.6 228.6 204.2 175.7 147.1 118.6 57 237.8 17.7 237.8 237.8 213.7 185.2 156.7 128.1 226.7 19.1 226.7 226.7 203.3 174.8 146.3 117.8 77 287.0 17.9 189.9 145.8 112.1 - - - 272.0 19.4 187.6 140.0 106.3 - - ­72 272.5 17.4 219.9 186.3 152.6 118.9 - - 258.5 18.9 214.1 180.4 146.7 113.0 - -
7000
67 258.0 16.9 250.0 226.7 193.0 159.3 125.6 - 245.0 18.5 240.5 220.7 187.0 153.3 119.6 ­62 249.3 16.7 249.3 249.3 236.2 202.5 168.8 135.1 237.3 18.3 237.3 237.3 224.6 190.9 157.2 123.5 57 246.4 16.5 246.4 246.4 234.3 200.6 166.9 133.3 235.4 18.1 235.4 235.4 223.7 190.0 156.3 122.6 77 297.0 16.7 220.5 160.9 122.0 - - - 282.0 18.2 221.5 154.9 116.0 - - ­72 282.0 16.2 243.8 204.9 166.0 127.1 - - 268.0 17.8 237.8 198.9 160.0 121.1 - -
8000
67 267.0 15.7 267.0 248.9 210.0 171.1 132.2 - 254.0 17.4 254.0 242.9 204.0 165.1 126.2 ­62 258.0 15.6 258.0 258.0 257.0 218.1 179.2 140.4 246.0 17.2 246.0 246.0 245.0 206.1 167.2 128.4 57 255.0 15.4 255.0 255.0 255.0 216.1 177.2 138.4 244.0 17.0 244.0 244.0 244.0 205.1 166.2 127.4 72 295.2 13.7 275.1 228.1 183.8 139.5 - - 280.7 15.3 265.0 220.8 176.5 132.2 - -
9000
67 279.5 13.3 279.5 270.4 232.5 188.2 143.9 - 266.0 15.0 266.0 260.4 225.0 180.7 136.4 ­62 270.1 13.2 270.1 270.1 269.6 225.3 181.0 136.7 257.6 14.8 257.6 257.6 257.1 212.8 168.6 124.3 57 266.9 13.0 266.9 266.9 266.9 222.7 178.4 134.1 255.5 14.6 255.5 255.5 255.5 211.2 167.0 122.7 72 308.4 11.2 306.4 251.2 201.5 151.9 - - 293.3 12.8 292.3 242.6 192.9 143.3 - -
10000
67 292.0 10.8 292.0 292.0 255.0 205.3 155.6 - 278.0 12.5 278.0 278.0 246.0 196.3 146.6 ­62 282.2 10.7 282.2 282.2 282.2 232.5 182.8 133.1 269.2 12.4 269.2 269.2 269.2 219.6 169.9 120.2 57 278.9 10.6 278.9 278.9 278.9 229.2 179.5 129.8 267.1 12.2 267.1 267.1 267.1 217.4 167.7 118.0
TOTAL
CAP.
MBH
1
POWER
INPUT
KW
75°F 85°F
SENSIBLE CAPACITY, MBH
2
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
90 85 80 75 70 65 90 85 80 75 70 65
TEMPERATURE OF AIR ON CONDENSER COIL
TOTAL
CAP.
MBH
POWER
1
INPUT
KW
2
SENSIBLE CAPACITY, MBH
AIR ON
EVAPORATOR
COIL
CFM
WB
°F
77 247.1 21.9 148.1 119.6 91.1 - - - 232.2 23.3 144.0 115.5 87.0 - - ­72 235.0 21.5 184.6 156.1 127.6 99.0 - - 221.1 22.9 180.0 151.5 123.0 94.5 - -
6000
67 223.0 21.2 221.0 192.5 164.0 135.5 107.0 - 210.0 22.6 209.0 187.5 159.0 130.5 102.0 ­62 216.5 20.9 216.5 216.5 193.0 164.5 136.0 107.5 205.4 22.2 205.4 205.4 183.0 154.5 126.0 97.5 57 215.6 20.6 215.6 215.6 193.0 164.5 136.0 107.5 204.0 21.9 204.0 204.0 182.6 154.1 125.6 97.1 77 257.0 20.8 185.3 134.3 100.6 - - - 241.6 22.3 184.7 132.6 96.0 - - ­72 244.5 20.5 208.2 174.5 140.8 107.1 - - 230.1 21.9 203.1 169.4 135.7 102.0 - -
7000
67 236.0 20.1 231.0 214.7 182.0 147.3 113.6 - 218.5 21.6 218.0 206.2 175.5 141.8 108.1 ­62 225.3 19.8 225.3 225.3 213.0 179.3 145.6 111.9 213.7 21.2 213.7 213.7 202.0 168.3 134.6 100.9 57 224.3 19.6 224.3 224.3 213.0 179.3 145.6 111.9 212.2 21.0 212.2 212.2 201.6 167.9 134.2 100.5 77 267.0 19.7 222.5 148.9 110.0 - - - 251.0 21.3 225.5 149.8 105.0 - - ­72 254.0 19.4 231.8 192.9 154.0 115.1 - - 239.0 20.9 226.3 187.4 148.5 109.6 - -
8000
67 241.0 19.1 241.0 236.9 198.0 159.1 120.2 - 227.0 20.6 227.0 224.9 192.0 153.1 114.2 ­62 234.0 18.8 234.0 234.0 233.0 194.1 155.2 116.4 222.0 20.2 222.0 222.0 221.0 182.1 143.2 104.4 57 233.0 18.6 233.0 233.0 233.0 194.1 155.2 116.4 220.5 20.0 220.5 220.5 220.5 181.6 142.7 103.9 72 266.1 16.9 255.0 213.4 169.2 124.9 - - 251.1 18.4 244.7 208.0 163.7 119.4 - -
9000
67 252.5 16.7 252.5 250.4 217.5 173.2 128.9 - 238.5 18.1 238.5 237.5 211.6 167.3 123.1 ­62 245.2 16.4 245.2 245.2 244.7 200.4 156.1 111.8 233.3 17.8 233.3 233.3 232.8 188.5 144.2 99.9 57 244.1 16.2 244.1 244.1 244.1 199.8 155.6 111.3 231.7 17.6 231.7 231.7 231.7 187.4 143.1 98.8 72 278.2 14.4 278.2 234.0 184.3 134.7 - - 263.2 16.0 263.2 228.5 178.9 129.2 - -
10000
67 264.0 14.2 264.0 264.0 237.0 187.3 137.6 - 250.0 15.7 250.0 250.0 231.3 181.6 131.9 ­62 256.3 14.0 256.3 256.3 256.3 206.7 157.0 107.3 244.5 15.4 244.5 244.5 244.5 194.8 145.1 95.5 57 255.2 13.8 255.2 255.2 255.2 205.6 155.9 106.2 242.8 15.3 242.8 242.8 242.8 193.2 143.5 93.8
TOTAL
CAP.
MBH
1
POWER
INPUT
KW
95°F 105°F
TEMPERATURE OF AIR ON CONDENSER COIL
SENSIBLE CAPACITY, MBH
2
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
90 85 80 75 70 65 90 85 80 75 70 65
TOTAL
CAP.
MBH
POWER
1
INPUT
KW
2
SENSIBLE CAPACITY, MBH
14 Johnson Controls Unitary Products