YORK Model DEG units are single package air conditioners with
gas heat designed for outdoor installation on a rooftop or a slab.
The units are completely assembled on rigid, permanently
attached base rails. All piping, refrigerant charge, and
electrical wiring is factory-installed and tested. The units
require only electric power, gas piping and duct connections
at the point of installation.
The gas-fired heaters have aluminized steel tubular heat
exchangers and spark ignition with intermittent pilot.
This appliance is not to be used for temporary heating of
buildings or structures under construction.
INSPECTION
As soon as a unit is received, it should be inspected for possible
damage during transit. If damage is evident, the extent of the
damage should be noted on the carrier's freight bill. A separate
request for inspection by the carrier's agent should be made in
writing. Refer to Form 50.15-NM for additional information.
REFERENCE
Additional information on the design, installation, operation
and service of this equipment is available in the following
reference forms:
•
55.70-N1-General Installation
•
55.70-N2-Pre-start & Post-start Check List
•
530.18-N1.2V-Economizer Accessory
•
530.18-N1.13V -Man. Outdoor Air Damper Accy 0-35%
Supersedes: 035-14832-002-A-0302
(11 SEER)
530.18-N1.14V -Man. Outdoor Air Damper Accy 0-100%
•
530.18-N1.12V -Motorized Outdoor Air Damper Accy.
•
530.18-N1.8V-Coil Guard
•
530.18-N2.11V -Low NOx Accessory
•
530.18-N8.2V-High Altitude Accy. (Natural Gas)
•
530.18-N8.3V-High Altitude Accy. (Propane)
•
530.18-N8.4V-Gas Piping Accessory
•
530.18-N8.12V-Propane Conversion Accessory
•
690.15-N25V-Low Ambient Accessory
•
Renewal Parts:
•
Refer to Parts Manual for complete listing of replacement
parts on this equipment.
All forms referenced in this instruction may be ordered from:
Standard Register
Toll Free Tel.: 877-318-9675
Fax: 877-379-7920
APPROVALS
Design certified by CGA and UL listed as follows:
1. For use as a forced air furnace with cooling unit.
2. For outdoor installation only.
3. Forinstallationdirectlyoncombustibleflooringor,in theU.S.A.,
on wood flooring or Class A, B, or C roof covering material.
4. For use with natural gas and/or propane (LP) gas.
Not suitable for use with conventional venting systems.
035-14832-003-A-0204
FOR YOUR SAFETY
Do not store or use gasoline or
other flammable vapors or liquids
in the vicinity of this or any other
appliance.
If you smell gas:
1. Open windows
2. Don't touch electrical switches.
3. Extinguish any open flame.
4. Immediately call your gas supplier.
Installer should pay particular attention to the words: NOTE, CAUTION and WARNING. Notes are intended to clarify or make
the installation easier. Cautions
jury and/or equipment damage may result if installation procedure is not handled properly.
are given to prevent equipment damage. Warnings are given to alert installer that personal in
CAUTION
THIS PRODUCT MUST BE INSTALLED IN STRICT COMPLIANCE WITH THE ENCLOSED INSTALLATION INSTRUC
TIONS AND ANY APPLICABLE LOCAL, STATE, AND NATIONAL CODES INCLUDING, BUT NOT LIMITED TO, BUILDING,
ELECTRICAL, AND MECHANICAL CODES
-
WARNING
INCORRECT INSTALLATION MAY CREATE A CONDITION WHERE THE OPERATION OF THE PRODUCT COULD
CAUSE PERSONAL INJURY, PROPERTY DAMAGE AND/OR DEATH.
WARNING
DE-ENERGIZE THE ELECTRICAL POWER AND TURN OFF THE GAS SUPPLY TO THE UNIT BEFORE ATTEMPTING TO
INSPECT, REPAIR OR PERFORM MAINTENANCE TO THE UNIT.
-
TABLE OF CONTENTS
General
Inspection
Reference
Approvals
Nomenclature
Limitations
Location
Rigging and Handling
Clearances
Ductwork
Filters
Condensate Drain
Service Access
Thermostat
Power and Control Wiring
Blower Speed Selection
Compressors
Combustion Discharge
Disconnect Switch Bracket For Optional Belt-Drive
Gas Piping
Gas Connection
L.P. Units, Tanks and Piping
Low NOx Application
Vent and Combustion Air Hoods
Optional Economizer Rain Hood
Cooling System .................................................................13
Pre-Start Check List ..........................................................14
Operating Instructions
Post-Start Check List (Gas)
Manifold Gas Pressure Adjustment
Pilot Checkout
Burner Instructions
Burner Air Shutter Adjustment
Supply Air Blower and Temperature Rise Adj.
Supply Air Blower and Temperature Rise Adj.
Checking Gas Input
Secure Owner's Approval
1Unit Application Data
2Gas Heat Application Data
3Pipe Sizing
4Physical Data
.................................................
.............................................
5Supply Air Perf. Direct-Drive Units
6Supply Air Perf.3 & 4Ton Belt-Drive Units
7Supply Air Perf.5 Ton Belt-Drive Units
8Static Resistances
9Motor & Drive Data
......................................
.....................................
10Electrical Data (Direct-Drive Units)
11Electrical Data (Belt-Drive Units)
12Limit Control Setting
13Belt-Drive Supply Air Motor Pulley Adj.
14Gas Rate - Cubic Feet Per Hour
FIGURES
No. Description Page
1Center of Gravity ........................................3
2Recommended Drain Piping ......................4
3Typical Field Wiring....................................5
These units must be installed in accordance with the current
edition of the following national and local safety codes:
In the U.S.A.:
1. National Electrical Code ANSI/NFPA No. 70.
2. National Fuel Gas Code Z223.1.
3. Gas-Fired Central Furnace Standard ANSI Z21.47-1993.
4. Local gas utility requirements.
In Canada:
1. Canadian Electrical Code CSA C22.1
2. Current Gas Installation Codes CAN/CGA-2.3-M93.
3. Local plumbing and waste water codes.
4. Other applicable local codes.
Refer to Table 1 for UnitApplication Dataand toTable 2 for Gas
Heat Application Data.
If components are to be added to a unit to meet local codes, they
are to be installed at the dealer'sand /or the customer's expense.
Size of unit for proposed installation should be based on heat
loss / heat gain calculation made according to the methods of
Air Conditioning Contractors of America (ACCA).
LOCATION
TABLE 1 - UNIT APPLICATION DATA
Model DEG036048060
Voltage Variation
Min. / Max.
Supply Air CFM, Nom.120016002000
Wet Bulb Temperature (°F) of
Air on Evaporator Coil,
Min. / Max.
Dry Bulb Temperature (°F) of
Air on Condenser Coil,
1
Utilization range “A” in accordance with ARI Standard 110.
2
A low ambient accessory is available for operation down to 0°F.
Min
2
/ Max.
Use the following guidelines to select a suitable location for
these units.
1. Unit is designed for outdoor installation only.
2. Condenser coils must have an unlimited supply of air.
Where a choice of location is possible, position the unit on
either north or east side of building.
WARNING:Excessive exposure of this furnace to contami
nated combustion air may result equipment dam
age or personal injury. Typical contaminates
include: permanent wave solutions, chlorinated
waxes and cleaners, chlorine based swimming
pool chemicals, water softeningchemicals, carbon
tetrachloride, Halogen type refrigerants, cleaning
solvents (e.g. perchloroethylene), printing inks,
paint removers, varnishes, hydrochloric acid, ce
ments and glues, antistatic fabric softeners for
clothes dryers, masonry acid washing materials.
3. For ground level installation, a level pad or slab should be
used. The thickness and size of the pad or slab used should
meet local codes and unit weight. Do not tie the slab to the
building foundation.
4. Roof structures must be able to support the weight of the
unit and its options and / or accessories. Unit must be
installed on a solid level roof curb or appropriate angle iron
frame.
208/230V187 / 253
460V414 / 506
1
575V518 / 630
57 / 7257 / 7257 / 72
45 / 12045 / 12045 / 120
CAUTION: If a unit is to be installed on a roof curb or special
frame other than a YORK roof curb, gasketing
must be applied to all surfaces thatcome in contact
with the unit underside.
5. Maintain level tolerance to 1/2" maximum across the entire
length or width of the unit.
6. Elevate the unit sufficiently to prevent any blockage of the
air entrances by snow in areas where there will be snow
accumulation. Check the local weather bureau for the
expected snow accumulation in your area.
RIGGING AND HANDLING
Exercise care when moving the unit. Do not remove any
packaging until the unit is near the place of installation. Rig the
unit by attaching chain or cable slings to the lifting holes
provided in the base rails. Spreaders, whose length exceeds
the largest dimension across the unit, MUST be used across
the top of the unit.
BEFORE LIFTING A UNIT, MAKE SURE THAT ITS WEIGHT
IS DISTRIBUTED EQUALLY ON THE CABLES SO THAT IT
WILL LIFT EVENLY.
Units may also be moved or lifted with a forklift. Slotted
openings in the base rails are provided for this purpose.
LENGTH OF FORKS MUST BE A MINIMUM OF 42".
Remove the nesting brackets from the four corners on top of
the unit. All screws that are removed when taking these
brackets off must be replaced on the unit.
CAUTION: An adhesive backed label is provided over the out-
side of the combustion air inlet opening to prevent
moisture from entering the unit which could cause
damage to electrical components. Allow this closure label to remain in place until the combustion
air hood is to be installed (refer to Figure 6).
Refer to Table 4 for unit weights and to Figure 1 for approximate
center of gravity.
CLEARANCES
APPROXIMATE
CENTER OF
GRAVITY
%
30-1/2
44
“
&
15-1/8
A
BACK
FIG. 1 - CENTER OF GRAVITY
67-3/4
82
30
B
CONDENSER
COIL END
FRONT
“
"
DIM.3-5 TON
A19-3/4"
B40-3/4"
All units require certain clearances for proper operation and
service. Installer must make provisions for adequate
-
combustion and ventilation air in accordance with Section 5.3,
-
Air for Combustion and Ventilation of the National Fuel Gas
Code, ANSI Z223.1 (in U.S.A.) or Sections 7.2, 7.3 or 7.4 of
Gas Installation Codes CAN/CGA-B149.1 and .2 (in Canada)
and/or applicable provisions of the local building codes. Refer
to Figure 9 for the clearances required for combustible
construction, servicing, and proper unit operation.
WARNING:Do not permit overhanging structures or shrubs to
obstruct condenser air discharge outlet, combus
tion air inlet or vent outlet.
DUCTWORK
Ductwork should be designed and sized according to the
methods in Manual Q of the Air Conditioning Contractors of
America (ACCA).
A closed return duct system shall be used. This shall not
preclude use of economizers or outdoor fresh air intake. The
supply and return air duct connections at the unit should be
made with flexible joints to minimize the transmission of noise.
-
Unitary Products Group3
The supply and return air duct systems should be designed for the
CFM and static requirements of the job. They should NOT
be
sized tomatch thedimensions ofthe ductconnections onthe unit.
CAUTION: When fastening ductwork to the side duct flanges on
the unit, insert the screws through the duct flanges
only.DO NOT insert the screws through the casing.
Outdoor ductworkmust beinsulated andwaterproofed.
Refer to Figure 9 for information concerning side and bottom
supply and return air duct openings.
FILTERS
1" filters are supplied with each unit. 2" replacement filters may
be used with no modification to the filter racks. Filters must
always be installed ahead of the evaporator coil and must be
kept clean or replaced with same size and type. Dirty filters will
reduce the capacity of the unit and will result in frosted coils or
safety shutdown. Minimum filter area and required sizes are
shown in Table 4.
CONDENSATE DRAIN
Plumbing must conform to local codes. Use a sealing compound
on male pipe threads. Install a condensate drain line from the 3/4"
PVC female connection on the unit to spill into an open drain.
NOTE: The condensate drain line MUST be trapped to pro
vide proper drainage. See Figure 2.
FIG. 2 - RECOMMENDED DRAIN PIPING
SERVICE ACCESS
Access to all serviceable components is provided by the
following removable panels:
•
Compressor compartment
•
Burner compartment
•
Blower compartment
•
Main control box
•
Filter compartment
•
Motor access (on units with belt-drive option)
Refer to Figure 9 for location of these access panels.
CAUTION: Make sure that all screws are replaced on the unit
to maintain an air-tight seal.
THERMOSTAT
The room thermostat should be located on an inside wall
approximately 56" above the floor where it will not be subject to
drafts, sun exposure, or heat from electrical fixtures or
appliances. Follow manufacturer's instructions enclosed with
thermostat for general installation procedure. Color coded
insulated wires (#18 AWG) should be used to connect
thermostat to unit. See Figure 3 for wiring details.
NOTE: If the unit has an economizer, remove jumper J1 from
terminals 8 and 10 on the relay board to prevent si
multaneous operation of the compressor and the
economizer. If you want to energize the compressor
for supplemental cooling during the economizer op
eration, use athermostat with two stages of cooling.
POWER AND CONTROL WIRING
Field wiring to the unit must conform to provisions of the National
Electrical Code (NEC) ANSI/NFPA No. 70 and/or local
035-14832-003-A-0204
ordinances. The unit must be electrically grounded in
accordance with the NEC (as specified above) and/or local
codes.
Voltage tolerances which must be maintained at the
compressor terminals during start-up and running conditions
are indicated on the unit Rating Plate and Table 1.
The internal wiring harness furnished with this unit is an
integral part of a UL design certified unit. Field alteration to
comply with electrical codes should not be required.
A disconnect switch should be field provided for the unit. The
switch must be separate from all other circuits. Refer to Figure
9 for installation location. If any of the wire supplied with the unit
must be replaced, replacement wire must be of the type shown
on the wiring diagram.
Electrical lines must be sized properly to carry the load. USE
COPPER CONDUCTORS ONLY. Each unit must be wired
with a separate branch circuit fed directly from the meter panel
and properly protected.
CAUTION: When connecting electrical power and control wir
ing to the unit, waterproof type connectors MUST
BE USED so that water or moisture cannot be
drawn into the unit during normal operation. The
above waterproofing conditions will also apply
-
when installing a field-supplied disconnect switch.
Refer to Figure 3 for typical field wiring and to the appropriate unit
wiring diagram for control circuit and power wiring information.
BLOWER SPEED SELECTION
Three blower motor speeds are available on the direct-drive
units. The speed selection for the direct-drive units is
determined by the CFM and ESP requirements of the
applications. All units with belt-drive option have an adjustable
motor pulley to achieve the above conditions.
All direct-drive units with 208/230 voltage are shipped with the
wire labeled #116 connected to the “HIGH” speed tap on the
blower motor. If a lower blower motor speed is desired, this wire
should be moved to the “MED” or “LOW” speed tap on the
motor for the speed desired.
All direct-drive units with 460 and 575 voltage are shipped with
the wire labeled #116 connected to the “HIGH” speed tap on
the blower motor. If the medium speed is required, connect
wire #116 to the “MED” speed tap and the blue motor lead to
the “HIGH” speed tap. If the low speed is required, connect wire
#116to the “LOW” speed tap, theblue motor lead to the“HIGH”
speed tap and the orange motor lead to the “MED” speed tap.
COMPRESSORS
On some units the compressor is mounted on springs which
have been tightened down for shipment only.
After this unit is installed, back out the compressor bolts until
the sleeve clears the top grommet.
CAUTION: Do Not
loosen compressor mounting bolts.
TABLE 2 - GAS HEAT APPLICATION DATA
Input
Capacity,
(Mbh)
50403 Ton471545
75604 Ton702555
100793/5 Ton9340/2570/55
-
-
125994/5 Ton11645/3575/65
NOTE: Gas Heaters are shipped available for natural gas, but can be converted to L.P. with
1Based on 1075 Btu/Ft
2The air flow must be adjusted to obtain a temperature rise within the range shown.
Output
Capacity,
(Mbh)
Kit Model No. 1NP0434. All furnaces meet the latest California seasonal efficiency
requirements.
Available
Models
3
.
on
Gas Rate
(Ft.3/Hr.)
Temp. Rise °F
1
At Full Input
Min.Max.
COMBUSTION DISCHARGE
The products of combustion are discharged horizontally
through a screened opening on the gas heat access panel.
-
2
4Unitary Products Group
035-14832-003-A-0204
COOLING / HEATING (24 VOLT THERMOSTAT)
C O O L I N G / H E A T I N G ( 2 4 V O L T T H E R M O S T A T )
T H E R M O S T A T
T E R M I N A L S
A D D
J U M P E R
J U M P E R
R H
R C
Y
W
G
1
2 4 V O L T T H E R M O S T A T 2 T H 0 7 7 0 1 0 2 4 . I F T H E U N I T H A S A N E C O N O M I Z E R ,
R E M O V E J U M P E R J 1 F R O M T E R M I N A L S 8 A N D 1 0 O N T H E R E L A Y B O A R D
T O P R E V E N T S I M U L T A N E O U S O P E R A T I O N O F T H E C O M P R E S S O R A N D
T H E E C O N O M I Z E R . I F Y O U W
S E C O N D S T A G E O F C O O L I N G O R H A V E A N D E L E C T R I C H E A T A C C E S S O R Y
W I T H T W
O S T A G E S O F H E A T , U S E T H E R M O S T A T 2 T H 0 4 7 1 0 2 4
C O O L I N G / H E A T I N G ( E L E C T R O N I C T H E R M O S T A T )
T H E R M O S T A T
T E R M I N A L S
A D D
1
E L E C T R O N I C P R O G R A M M A B L E T H E R M O S T A T 2 E T 0 7 7 0 1 0 2 4 ( I N C L U D E S S U B B A S E ) .
I F T H I S U N I T H A S A N D E C O N O M I Z E R , R
1 0 O N T H E R E L A Y B O A R D T O P R E V E N T S I M U L T A N E O U S O P E R A T I O N O F T H E
O M P R E S S O R A N D T H E E C O N O M I Z E R . I F Y O U W A N T T O C O N T R O L T H E
C
E C O N O M I Z E R O N A S E C O N D S T A G E O F C O O L I N G , U S
R H
R C
Y
W
G
1
U N I T T E R M I N A L
S T R I P T B 1
R
Y 1
Y 2
W 1
W 2
G
B
A N T T O C O N T R O L T H E R E C O N O M I Z E R O N A
2 4 V O L T
T R A N S F O R M E R
S I N G L E S T A G E
1
U N I T T E R M I N A L
S T R I P T B 1
R
Y 1
W 1
G
B
2 4 V O L T
T R A N S F O R M E R
E M O V E J U M P E R J 1 F R O M T E R M I N A L S 8 A N D
E T H E R M O S T A T 2 E T 0 4 7 0 0 2 2 4 .
CONTROL WIRING
POWER WIRING
COOLING / HEATING (ELECTRONIC THERMOSTAT)
L E D 1
L E D 2
C O M
1
U N I T T E R M I N A L
R C
R H
Y 1
Y 2
2
W 1
W 2
G
B
N O T
U S E D
A 1
A 2
3
T
T
S T R I P T B 1
R
Y 1
2
Y 2
W 1
3
W 2
G
B
X
N
4
T O R E M O T E S E N S O R
2 T H 0 4 0 7 0 2 2 2 4 I F U S E D
N A L S A 1 A N D A 2 P R O V I D E A R E L A Y
2 4 V O L T
T R A N S F O R M E R
T H E R M O S T A T
T E R M I N A L S
A D D
J U M P E R
4
A D D
J U M P E R
1
E L E C T R O N I C P R O G R A M M A B L E T H E R M O S T A T 2 E T 0 4 7 0 0 2 2 4 ( I N C L U D E S S U B B A S E )
2
S E C O N D S T A G E C O O L I N G I S N O T R E Q U I R E D O N U N I T S L E S S E C O N O M I Z E R .
3
S E C O N D S T A G E H E A T I N G I S O N L Y R E Q U I R E D O N U N I T S W I T H A T W O S T A G E
E L E C T R I C H E A T E R .
4
R E M O V E J U M B E R J 2 F R O M T E R M I N A L S 4 A N D 9 O N J U M P E R P L U G C O N N E C T O R
P 6 O N U N I T S W I T H E C O N M I Z E R . T E R M I
O U T - P U T T O C L O S E T H E O U T D O O R E C O N O M I Z E R D A M P E R S W H E N T H E
T H E R M O S T A T S W I T C H E S T O T H E S E T - B A C K P O S I T I O N .
REFER TO THE ELECTRICAL
DATA TO SIZE THE DISCONNECT
SWITCH, THE WIRING AND THE
OVERCURRENT PROTECTION
REFER TO THE ELECTRICAL
DATA TO SIZE THE DISCONNECT
SWITCH, THE WIRING AND THE
OVERCURRENT PROTECTION
FIG. 3 - TYPICAL FIELD WIRING
DISCONNECT SWITCH BRACKET FOR UNITS
WITH OPTIONAL BELT-DRIVE BRACKET
A special bracket for mounting a field-supplied disconnect
switch is provided in each unit ordered with an optional beltdrive supply air blower. The bracket is shipped inside the
blower compartment taped to the top of the blower housing.
Install the bracket on the left hand side of the unit as shown in
Figure 9. Several existing screws at the top of the unit and one
approximately midway down from the top will be used for
mounting the bracket. Screws should be loosened only - NOT
REMOVED. Mounting holes in the bracket have elongated
keyways allowing easy installation. Re-tighten screws after
bracket is in place to ensure panels will remain leak tight.
GAS PIPING
Proper sizing of gas piping depends on the cubic feet per hour
of gas flow required, specific gravity ofthe gas and the lengthof
run. “National Fuel Gas Code” Z223.1 should be followed in all
cases unless superseded by local codes or gas company
requirements. Refer to Table 3.
Unitary Products Group5
The heating value of the gas may differ with locality. The value
should be checked with the local gas utility.
NOTE: There may be a local gasutility requirement specifying
a minimum diameter for gas piping. All units require a
1/2 inch pipe connection at the entrance fitting.
TABLE 3 - PIPE SIZING
Length in Feet
10
20
30
40
50
60
70
80
90
100
Maximum capacity of pipe in cubic feet of gas per hour. (Based upon a pressure drop of 0.3 inch
water column and 0.6 specific gravity gas).
1/2 in.
132
92
73
63
56
50
46
43
40
38
Nominal Iron Pipe Size
3/4 in.
278
190
152
130
115
105
96
90
84
79
1 in.1-1/4 in.
520
350
285
245
215
195
180
170
160
150
1,050
730
590
500
440
400
370
350
320
305
035-14832-003-A-0204
FIG. 4 - EXTERNAL SUPPLY CONNECTION
EXTERNAL SHUT-OFF
GAS CONNECTION
The gas supply line can be routed through the knockouts
located on the front of the unit or through the opening provided
in the unit's base. Refer to Figure 9 to locate these access
openings. Typical supply piping arrangements are shown in
Figures 4 and 5. All shaded items are field-supplied.
Twogrommets are shipped in the blower compartment (in parts
bag taped to the blower housing) of every unit with gas heat
and should be used in the knockouts when the gas piping
penetrates the front of the unit.
After the gas supply piping has been installed, the bottom
opening should be sealed to preventwater from leaking into the
building.
Gas piping recommendations:
1. A drip leg and a ground joint union must be installed in the
gas piping.
2. When required by local codes, a manual shut-off valve may
have to be installed outside of the unit.
3. Use wrought iron or steel pipe for all gas lines. Pipe
compound should be applied sparingly to male threads
only.
WARNING:Natural gas may contain some propane. Propane,
being an excellent solvent, will quickly dissolve
white lead or most standard commercial com
pounds. Therefore, a special pipe compound must
be applied when wrought iron or steel pipe is used.
Shellac base compounds such as Gaskolac or
Stalastic, and compounds such as Rectorseal #5,
Cyde's or John Crane may be used.
4. Allpiping should becleaned of dirtand scale by hammering
on the outside of the pipe and blowing out the loose dirt and
scale. Before initial start-up, be sure that all of the gas lines
external to the unit have been purged of air.
5. The gas supply should be a separate line and installed in
accordance with all safety codes as prescribed under
“Limitations”. After the gas connections have been
completed, open the main shut-off valve admitting normalgas pressure to the mains. Check all joints for leaks with
soap solution or other material suitable for the purpose.
NEVER USE A FLAME.
6. The furnace and its individual manual shut-off valve must
be disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in
excess of 1/2 psig (3.48kPa).
FIG. 5 - BOTTOM SUPPLY CONNECTION
EXTERNAL SHUT-OFF
The furnace must be isolated from the gas supply piping
system by closing its individual manual shut-off valve
during any pressure testing of the gas supply piping system
at test pressures equal to or less than 1/2 psig (3.48kPa).
7. A 1/8 inch NPT plugged tapping, accessible for test gage
connection, must be installed immediately upstream of the
gas supply connection to the furnace.
L.P./PROPANE UNITS, TANKS AND PIPING
All gas heat units are shipped from the factory equipped for
natural gas use only. The unit may be converted in the field for
use with L.P./propane gas with accessory kit model number
1NP0434.
All L.P./propane gas equipment must conform to the safety
standards of the National Fire Protection Association.
For satisfactory operation, L.P./propane gas pressure must be
10.5 inch W.C at theunit under full load. Maintaining proper gas
pressure depends on three main factors:
1. The vaporization rate which depends on (a) the
temperature of the liquid and (b) the “wetted surface” area
of the container or containers.
2. The proper pressure regulation. (Two-stage regulation is
recommended from the standpoint of both cost and
efficiency.)
-
3. The pressure drop in the lines between regulators and
between the second stage regualtor and the appliance.
Pipe size required will depend on the length of the pipe run
and the total load of all appliances.
Complete information regarding tank sizing for vaporization,
recommended regulator settings, and pipe sizing is available
from most regulator manufacturers and L.P./propane gas
suppliers.
L.P./propane gas is an excellent solvent and special pipe
compound must be used when assembling piping for this gas
as it will quickly dissolve white lead or most standard
commercial compounds. Shellac base compunds such as
Rectorseal #5 are satisfactory for this type of gas.
Check all connections for leaks when piping is completed,
using a soap solution. NEVER USE A FLAME.
LOW NOx APPLICATION
For natural gas heat installations in locations which require low
Nitros Oxide emmissions, accessory model 1LN0404 must be
installed.
6Unitary Products Group
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.