ADD - ON COILS
FOR USE WITH SPLIT -SYSTEM
COOLING & HEAT PUMPS
MODELS: CF, CM, CU
600 - 2000 CFM 1.5 - 5 TON COILS
Due to continuous product improvement,
specifications are subject to change without notice.
Visit us on the web at:
www.upgnet.com and www.york.com
Additional rating information can be found at:
www.ahridirectory.org
UPFLOW/DOWNFLOW
FULL CASED
CF
FULL CASED
MULTI-POSITION
CM
UPFLOW
UNCASED
CU
A0368-001
ISO 9001
Certified Quality
Management System
5005743-YTG-C-0815
DESCRIPTION
These indoor coils are designed to be installed with UPG furnaces or modular air handlers and matched with UPG cooling
and heat pump outdoor units. All coil models are available as
“flex-coil” units without a factory installed metering device. Flexcoil models allow these coils to be used with R-410A or R-22 for
added flexibility to meet refrigerant system choice. A piston or
TXV metering device should be installed in the field to meet
your system requirements.
CF Models, Full Case Coils - Full cased coils are suitable for
use in upflow or downflow applications.
CM Models, Multi-Position Coils - CM coils have the added
flexibility that allow them to be installed in any position - upflow,
downflow, or horizontal (right or left). This coil can be easily
installed with a UPG furnace or modular air handler in any configuration.
CU Models, Uncased Coils - These coils are designed for
installation on top of upflow furnaces, and they are to be used
for upflow only applications. The uncased coils require field
modification of the furnace duct for the coil installation.
FEATURES
RC2 - Rigid Case Construction interior endoskeleton for struc-
tural support, flush side, and locks in insulation.
Powder-painted - G30 galvanized steel case provide a coated
edge that resists corrosion and rust creep.
MaxAlloy
TM
Coil - Long life aluminum coils built to deliver last-
ing performance, efficiency and reliability.
Quality Construction - Structural components are made of
Aluminum or G90 galvanized steel to prevent corrosion.
Improved Insulation Design - Single piece with no external
screws to reduce thermal transmission paths to prevent sweating. Foil faced insulation for ease of cleaning.
Thermostatic Expansion Valve - Bolt-on TXV provides easy
installation to convert the indoor coil to the required refrigerant
that does not require brazing to replace or install. Some models
are available with factory installed TXVs.
Case Depth - These models have 20.5” casing which provide
ease of attic access and tight applications.
Thermal Plastic Drain Pan
- Positive slope for drainage to
reduce cause for potential mold or contaminates.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
ACCESSORIES
Refer to Price Manual for specific model numbers.
TXV Kits - Thermal expansion valve kits are available for flex-
coil applications with R-410A refrigerant. All TXV kits are nonbraze. All connections are bolt-on including the valve assembly
and equalizer tube. No orifice or any other metering device is to
be used in conjunction with the TXV.
Partial Case – Available to be used with CU coils in four widths.
This option is intended for upflow applications where height limitations in the application prevent the installation of full cased
coils. The partial case design allows the top section of the
indoor coil to be installed in the duct or plenum.
Coil Casing Without Coil - Coil casings are available in four
widths that can be installed with the furnace or modular air handler during initial installation. This option is available to allow the
installer the flexibility to add the coil at a later date without duct
modifications.
UVC Germicidal Light - The UVC technology effectively prevents mold, bacteria, and other microorganisms that develop in
air handling systems. The UVC Light Kit provides safe, continuous cleaning while actually saving money by reducing HVAC
system maintenance and energy consumption.
*Do not exceed minimum/maximum CFM limits shown under Air Flow Data.
APPLICATION LIMITATIONS
These units must be installed in accordance with all national
and local safety codes.
Air flow must be within the minimum and maximum limits
approved for electric heat, evaporator coils and outdoor units.
Johnson Controls Unitary Products9
5005743-YTG-C-0815
PHYSICAL DATA
COIL TECHNICAL DATA1 - CASED UPFLOW/DOWNFLOW
ModelApplication
CF18A
CF18B4.28214(3) 12 x 17.1
CF24A4.99214(3) 14 x 17.1
CF24B4.99214(3) 14 x 17.1
CF24C4.99214(3) 14 x 17.1
CF30A6.41214(3) 18 x 17.1
CF30B6.41214(3) 18 x 17.1
CF30C6.41214(3) 18 x 17.1
CF30D6.41214(3) 18 x 17.1
CF36A7.12214(3) 20 x 17.1
CF36B7.12214(3) 20 x 17.1
CF36C7.12214(3) 20 x 17.1
CF36D7.12214(3) 20 x 17.1
CF42B7.84214(3) 22 x 17.1
CF42C7.84214(3) 22 x 17.1
CF42D7.84214(3) 22 x 17.1
CF48C8.55214(3) 24 x 17.1
CF48D8.55214(3) 24 x 17.1
CF60C9.98214(3) 28 x 17.1
CF60D9.98214(3) 28 x 17.1
CF64D9.98312(3) 28 x 17.1
1. Refer to the matching outdoor unit Technical Guide for correct TXV.
Cooling/Heat PumpSweat
Refrig.
Conn.
Types
Face
Area
(Sq. Ft.)
4.28214(3) 12 x 17.1
Rows
Deep
Fin
Per
In.
Coil Size
COIL TECHNICAL DATA1 - FULL CASED “N” TYPE MULTI-POSITION
CM18A
CM18B4.28214(3) 12 x 17.1
CM24A4.99214(3) 14 x 17.1
CM24B4.99214(3) 14 x 17.1
CM24C4.99214(3) 14 x 17.1
CM30A6.41214(3) 18 x 17.1
CM30B6.41214(3) 18 x 17.1
CM30C6.41214(3) 18 x 17.1
CM30D6.41214(3) 18 x 17.1
CM36A7.12214(3) 20 x 17.1
CM36B7.12214(3) 20 x 17.1
CM36C7.12214(3) 20 x 17.1
CM36D7.12214(3) 20 x 17.1
CM42C7.84214(3) 22 x 17.1
CM42D7.84214(3) 22 x 17.1
CM48C8.55214(3) 24 x 17.1
CM48D8.55214(3) 24 x 17.1
CM60C9.98214(3) 28 x 17.1
CM60D9.98214(3) 28 x 17.1
CM64D9.98
1.Refer to the matching outdoor unit Technical Guide for correct TXV .
Note: CM coils supplied with a factory installed horizontal drain pan (H)
CU24B4.99(3) 14 x 17.1
CU24C4.99(3) 14 x 17.1
CU30A6.41(3) 18 x 17.1
CU30B6.41(3) 18 x 17.1
CU30C6.41(3) 18 x 17.1
CU30D6.41(3) 18 x 17.1
CU36B7.12(3) 20 x 17.1
Cooling /Heat Pump Sweat
214
1 x 0.8663/8”Sine Wave
CU36C7.12(3) 20 x 17.1
CU36D7.12(3) 20 x 17.1
CU42C7.84(3) 22 x 17.1
CU42D7.84(3) 22 x 17.1
CU48C8.55(3) 24 x 17.1
CU48D8.55(3) 24 x 17.1
CU60C9.98(3) 28 x 17.1
CU60D9.98(3) 28 x 17.1
1. Refer to the matching outdoor unit Technical Guide for correct TXV.
1. Dry coil conditions only, tested without filters.
For optimal performance, external static pressures of 0.2" to 0.5" are recommended. Applications above 0.6" are not recommended.
1. Dry coil conditions only, tested without filters.
For optimal performance, external static pressures of 0.2" to 0.5" are recommended. Applications above 0. 6" are not recommended.
UNCASED UPFLOW "N" TYPE COIL - AIR FLOW DATA (CFM)
1. Dry coil conditions only, tested without filters.
For optimal performance, external static pressures of 0.2" to 0.5" are recommended. Applications above 0.6" are not recommended.