YOKOGAWA EJX510B, EJX530B User Manual

User’s Manual
Yokogawa Electric Corporation
EJX510B and EJX530B Absolute and Gauge Pressure Transmitters
IM 01C27F01-01EN
2nd Edition
i
IM 01C27F01-01EN
EJX510B and EJX530B Absolute and Gauge Pressure Transmitters
IM 01C27F01-01EN 2nd Edition
2nd Edition: Aug. 2010 (YK) All Rights Reserved, Copyright © 2010, Yokogawa Electric Corporation
Contents
1. Introduction ............................................................................................... 1-1
1.1 Safe Use of This Product .................................................................................1-2
1.2 Radio Wave ........................................................................................................1-3
1.3 Warranty .............................................................................................................1-3
1.4 Trademarks ........................................................................................................1-3
1.5 ATEX Documentation .......................................................................................1-4
2. Handling Cautions .................................................................................... 2-1
2.1 Model and Specications Check ..................................................................... 2-1
2.2 Unpacking ..........................................................................................................2-1
2.3 Storage ...............................................................................................................2-1
2.4 Selecting the Installation Location ................................................................2-2
2.5 Pressure Connection ........................................................................................ 2-2
2.6 Restrictions on Use of Radio Transceivers ...................................................2-3
2.7 Insulation Resistance and Dielectric Strength Test ......................................2-3
2.8 Installation of an Explosion-Protected Instrument .......................................2-4
2.8.1 FM Approval .......................................................................................2-4
2.8.2 CSA Certication ................................................................................2-5
2.9 EMC Conformity Standards .............................................................................2-5
2.10 Pressure Equipment Directive (PED) .................................................. 2-5
2.11 Low Voltage Directive .......................................................................................2-6
2.12 Regulatory Compliance for Radio and Telecommunication ........................ 2-7
2.12.1 Radio and Telecommunications Terminal Equipment Directive (R&TTE)
....................................................................................................2-7
2.12.2 FCC compliance ................................................................................2-7
2.12.3 Industry Canada (IC) compliance ......................................................2-7
3. Component Names .................................................................................. 3-1
4. Installation ................................................................................................. 4-1
4.1 Precautions .......................................................................................................4-1
4.2 Mounting ............................................................................................................4-1
4.3 Rotating Transmitter Section ...........................................................................4-2
4.4 Changing the Direction of Integral Indicator .................................................4-2
4.5 Changing the direction of the antenna ...........................................................4-3
ii
IM 01C27F01-01EN
5. Installing Impulse Piping .........................................................................5-1
5.1 Impulse Piping Installation Precautions ........................................................5-1
5.1.1 Connecting Impulse Piping to a Transmitter ...................................... 5-1
5.1.2 Routing the Impulse Piping ................................................................5-1
5.2 Impulse Piping Connection Examples ...........................................................5-2
6. Grounding ................................................................................................. 6-1
7. Operation ................................................................................................... 7-1
7.1 Preparation for Starting Operation .................................................................7-1
7.2 Zero Point Adjustment .....................................................................................7-2
7.3 Starting Operation ............................................................................................ 7-2
7.4 Connecting to the Field Wireless Network ..................................................... 7-3
7.5 Shutting Down the Transmitter .......................................................................7-4
8. Setting Parameters ................................................................................... 8-1
8.1 Environment for parameter setting .................................................................8-1
8.2 Preparing Software for the Conguration Tool .............................................8-1
8.3 Setting Parameters ...........................................................................................8-2
8.3.1 Parameter Usage and Selection ........................................................8-2
8.3.2 Function Block and Menu Tree .......................................................... 8-3
8.3.3 Parameters for Wireless Communication ........................................8-10
8.3.4 Tag and Device Information ............................................................. 8-11
8.3.5 Unit ................................................................................................... 8-11
8.3.6 Range Change ................................................................................. 8-11
8.3.7 Output Signal Low Cut Mode Setup ................................................ 8-11
8.3.8 Integral Indicator Scale Setup ..........................................................8-12
8.3.9 Unit for Displayed Temperature .......................................................8-12
8.3.10 Zero Point Adjustment and Span Adjustment ..................................8-12
8.3.11 Software Write Protect .....................................................................8-14
8.3.12 Switching to Deep Sleep Mode ........................................................8-14
8.3.13 Switching to Silence Mode ...............................................................8-14
8.4 Self-Diagnostics ..............................................................................................8-15
8.4.1 Identify Problems by Using the Communicator ...............................8-15
8.4.2 Checking with Integral Indicator .......................................................8-17
9. Maintenance .............................................................................................. 9-1
9.1 Overview ............................................................................................................ 9-1
9.2 Calibration Instruments Selection ..................................................................9-1
9.3 Calibration .........................................................................................................9-1
9.4 Disassembly and Reassembly ........................................................................9-3
9.4.1 Replacing the Integral Indicator .........................................................9-3
9.4.2 Replacing the RF Assembly ...............................................................9-4
9.4.3 Replacing the CPU Assembly ............................................................9-4
9.4.4 Cleaning and Replacing the Capsule Assembly ...............................9-5
iii
IM 01C27F01-01EN
9.4.5 Replacing the Battery Pack ...............................................................9-5
9.4.6 Replacing the Batteries ...................................................................... 9-6
9.4.7 Handling Batteries ..............................................................................9-6
9.5 Troubleshooting ................................................................................................9-7
9.5.1 Basic Troubleshooting ....................................................................... 9-7
9.5.2 Troubleshooting Flowcharts ...............................................................9-8
9.5.3 Alarms and Countermeasures .........................................................9-10
10. Parameter Summary ..............................................................................10-1
11. General Specications .......................................................................... 11-1
11.1 Standard Specications .................................................................................11-1
11.2 Model and Sufx Codes ................................................................................. 11-3
11.3 OPTIONAL SPECIFICATIONS ........................................................................ 11-3
11.4 Dimensions ...................................................................................................... 11-5
Revision Information ...............................................................................................i
<1. Introduction>
1-1
IM 01C27F01-01EN
1. Introduction
Thank you for purchasing the DPharp EJX Absolute and Gauge Pressure transmitter.
Your EJX Pressure Transmitter was precisely calibrated at the factory before shipment. To ensure both safety and efciency, please read this manual carefully before you operate the instrument.
NOTE
This manual covers the EJX510B absolute pressure transmitter and EJX530B gauge pressure transmitter. Unless otherwise stated, the illustrations in this manual are of the EJX530B differential pressure transmitter. Users of the other models should bear in mind that certain features of their instrument will differ from those shown in the illustrations of the EJX530B.
Model
EJX510B EJX530B
Regarding This Manual
• This manual should be provided to the end user.
• The contents of this manual are subject to change without prior notice.
• All rights reserved. No part of this manual may be reproduced in any form without Yokogawa’s written permission.
• Yokogawa makes no warranty of any kind with regard to this manual, including, but not limited to, implied warranty of merchantability and tness for a particular purpose.
• If any question arises or errors are found, or if any information is missing from this manual, please inform the nearest Yokogawa sales ofce.
• The specications covered by this manual are limited to those for the standard type under the specied model number break-down and do not cover custom-made instruments.
• Please note that changes in the specications, construction, or component parts of the instrument may not immediately be reected in this manual at the time of change, provided that postponement of revisions will not cause difculty to the user from a functional or performance standpoint.
• Yokogawa assumes no responsibilities for this product except as stated in the warranty.
• If the customer or any third party is harmed by the use of this product, Yokogawa assumes no responsibility for any such harm owing to any defects in the product which were not predictable, or for any indirect damages.
• The following safety symbols are used in this manual:
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury or physical damage. It may also be used to alert against unsafe practices.
IMPORTANT
Indicates that operating the hardware or software in this manner may damage it or lead to system failure.
NOTE
Draws attention to information essential for understanding the operation and features.
<1. Introduction>
1-2
IM 01C27F01-01EN
1.1 Safe Use of This Product
For the safety of the operator and to protect the instrument and the system, please be sure to follow this manual’s safety instructions when handling this instrument. If these instructions are not heeded, the protection provided by this instrument may be impaired. In this case, Yokogawa cannot guarantee that the instrument can be safely operated. Please pay special attention to the following points:
(a) Installation
• This instrument may only be installed by an engineer or technician who has an expert knowledge of this device. Operators are not allowed to carry out installation unless they meet this condition.
• With high process temperatures, care must be taken not to burn yourself by touching the instrument or its casing.
• Never loosen the process connector nuts when the instrument is installed in a process. This can lead to a sudden, explosive release of process uids.
• When draining condensate from the pressure detector section, take appropriate precautions to prevent the inhalation of harmful vapors and the contact of toxic process uids with the skin or eyes.
• When removing the instrument from a hazardous process, avoid contact with the uid and the interior of the meter.
• All installation shall comply with local installation requirements and the local electrical code.
(b) Wiring
• The instrument must be installed by an engineer or technician who has an expert knowledge of this instrument. Operators are not permitted to carry out wiring unless they meet this condition.
(c) Maintenance
• Please carry out only the maintenance procedures described in this manual. If you require further assistance, please contact the nearest Yokogawa ofce.
• Care should be taken to prevent the build up of dust or other materials on the display glass and the name plate. To clean these surfaces, use a soft, dry cloth.
(d) Explosion Protected Type Instrument
• Users of explosion proof instruments should refer rst to Section 2.8 (Installation of an Explosion-Protected Instrument) of this manual.
• The use of this instrument is restricted to those who have received appropriate training in the device.
• Take care not to create sparks when accessing the instrument or peripheral devices in a hazardous location.
• Repair or modication to this instrument by customer will cause malfunction of explosion protect function and hazardous situation. If you need to repair or modication, please contact the nearest Yokogawa ofce.
(e) Modication
• Yokogawa will not be liable for malfunctions or damage resulting from any modication made to this instrument by the customer.
WARNING
- Do not loosen bolts or nuts used for
connecting impulse piping to the transmitter pressure-detector section when they are pressured because loosen bolts or nuts causes spout of process liquid.
- Take appropriate care to avoid contact with
the body or eyes, or inhalation of vapors when venting or draining if the accumulated liquid (or gas) is toxic or harmful.
- Take appropriate care to avoid contact with
the body or eyes, or inhalation of vapors when the transmitter is removed from process for maintenance if process liquid is toxic or harmful.
CAUTION
This instrument is certied as explosion protected type instrument. Structure, installing location, maintenance and repair of this instrument are restricted. Violation of this restriction causes hazardous situation. Users of explosion proof type instruments should refer rst to section 2.8 “Installation of an Explosion­Protected Instrument” of this manual.
<1. Introduction>
1-3
IM 01C27F01-01EN
1.2 Radio Wave
IMPORTANT
- This instrument is equipped with a wireless module which is designated as a certication of construction type as a wireless facility for 2.4 GHz band low-power data communication system of the Radio Act. Refer to 2.12 “Regulatory Compliance for Radio and Telecommunication” for detail.
- Due to the designated certication of construction type, users may be subject to legal punishment in case of:
- Disassembling or modifying the wireless
module or antenna in this instrument
- Peeling off the certication label attached
to the wireless module in this instrument
- Preventing interference with other wireless stations
The operating frequency bandwidth of this
instrument may overlap the same range as industrial devices, scientic devices, medical devices, microwave ovens, licensed premises radio stations and non-licensed specied low-power radio stations for mobile object identication systems used in factory production lines.
Before using this instrument, ensure that
neither a premises radio station nor specied low power radio station for mobile object identication systems is in use nearby.
If this instrument causes radio wave
interference to a wireless station for mobile object identication systems, promptly change the frequency being used or turn off the source of radio wave emissions. Then, contact a Yokogawa ofce regarding countermeasures to prevent interference, such as setting up partitions.
1.3 Warranty
• The warranty shall cover the period noted on
the quotation presented to the purchaser at the time of purchase. Problems occurring during the warranty period shall basically be repaired free of charge.
• If any problems are experienced with this instrument, the customer should contact the Yokogawa representative from which this instrument was purchased or the nearest Yokogawa ofce.
• If a problem arises with this instrument, please inform us of the nature of the problem and the circumstances under which it developed, including the model specication and serial number. Any diagrams, data and other information you can include in your communication will also be helpful.
• The party responsible for the cost of xing the problem shall be determined by Yokogawa following an investigation conducted by Yokogawa.
• The purchaser shall bear the responsibility for repair costs, even during the warranty period, if the malfunction is due to:
- Improper and/or inadequate maintenance by
the purchaser.
- Malfunction or damage due to a failure
to handle, use, or store the instrument in accordance with the design specications.
- Use of the product in question in a location
not conforming to the standards specied by Yokogawa, or due to improper maintenance of the installation location.
- Failure or damage due to modication or
repair by any party except Yokogawa or an approved representative of Yokogawa.
- Malfunction or damage from improper
relocation of the product in question after delivery.
- Reason of force majeure such as res,
earthquakes, storms/oods, thunder/ lightening, or other natural disasters, or disturbances, riots, warfare, or radioactive contamination.
1.4 Trademarks
In this document, trademarks or registered trademarks are not marked with “™” or “®”.
Product names and company names in this document are trademarks or registered trademarks of the respective companies.
<1. Introduction>
1-4
IM 01C27F01-01EN
1.5 ATEX Documentation
This is only applicable to the countries in European Union.
GB
DK
I
E
NL
SF
P
F
D
S
LT
LV
PL
EST
SLO
H
BG
RO
M
CZ
SK
GR
<2. Handling Cautions>
2-1
IM 01C27F01-01EN
2. Handling Cautions
This chapter provides important information on how to handle the transmitter. Read this carefully before using the transmitter.
EJX Series transmitters are thoroughly tested at the factory before shipment. When taking delivery of an instrument, visually check them to make sure that no damage occurred during shipment.
Also check that all transmitter mounting hardware and a bar magnet shown in gure 2.1 is included. If the transmitter is ordered without the mounting bracket and the process connector, the transmitter mounting hardware will not be included. After checking the transmitter, carefully repack it in its box and keep it there until you are ready to install it.
U-bolt Nut (L type)
Mounting bracket
U-bolt (L type)
U-bolt (S type)
U-bolt Nut (S type)
Figure 2.1 Transmitter Mounting Hardware
2.1 Model and Specications Check
The model name and specications are written on the name plate attached to the case.
: Refer to USER'S MANUAL.
Made in Japan TOKYO 180-8750 JAPAN
MODEL SUFFIX
SUPPLY OUTPUT MWP
mA DC
V DC
STYLE
CAL RNG
NO.
F0202.ai
Figure 2.2 Name Plate
2.2 Unpacking
Keep the transmitter in its original packaging to prevent it from being damaged during shipment. Do not unpack the transmitter until it reaches the installation site.
2.3 Storage
The following precautions must be observed when storing the instrument, especially for a long period.
(a) Select a storage area which meets the following
conditions:
• It is not exposed to rain or subject to water seepage/leaks.
• Vibration and shock are kept to a minimum.
• It has an ambient temperature and relative humidity within the following ranges.
• For maximum battery life, storage temperature should not exceed 30°C.
Ambient temperature: –40 to 85°C without integral indicator –30 to 80°C with integral indicator Relative humidity: 0% to 100% R.H. Preferred temperature and humidity: approx. 25°C and 65% R.H.
(b) When storing the transmitter, repack it carefully in
the packaging that it was originally shipped with.
(c) If the transmitter has been used, thoroughly
clean the chambers inside the cover anges, so that there is no process uid remaining inside. Before placing it in storage, also make sure that the pressure-detector is securely connected to the transmitter section.
NOTE
When storing the instrument with a battery pack, it is recommended to put the instrument in Deep Sleep mode to conserve the batteries. For details on how to switch to Deep Sleep mode, refer to subsection 8.3.12 “Switching to Deep Sleep Mode”.
<2. Handling Cautions>
2-2
IM 01C27F01-01EN
2.4 Selecting the Installation Location
The transmitter is designed to withstand severe environmental conditions. However, to ensure that it will provide years of stable and accurate performance, take the following precautions when selecting the installation location.
(a) Wireless Communication
The installation location of this transmitter must meet the following conditions:
- Adjust the direction of the antenna to be in the upright position regardless of the orientation of this transmitter. See section 4 for adjusting the antenna.
- Install the transmitter at least 1.5m above the ground or oor.
F0203.ai
1.5m or over
- Ensure that there are no obstacles such as walls or pipes within a 30-cm radius of each antenna.
- Conrm that each eld wireless equipment compliant with ISA100.11a can see the antenna of other devices which locate within its own communication range. In the star topology network, the visibility to the antenna of gateway is a mandatory clause.
(b) Ambient Temperature
Avoid locations subject to wide temperature variations or a signicant temperature gradient. If the location is exposed to radiant heat from plant equipment, provide adequate thermal insulation and/or ventilation.
(c) Ambient Atmosphere
Do not install the transmitter in a corrosive atmosphere. If this cannot be avoided, there must be adequate ventilation.
(d) Shock and Vibration
Although the transmitter is designed to be relatively resistant to shock and vibration, an installation site should be selected where this is kept to a minimum.
(e) Installation of Explosion-protected Transmitters
An explosion-protected transmitters is certied for installation in a hazardous area containing specic gas types. See subsection
2.8 “Installation of an Explosion-Protected
Transmitters.”
2.5 Pressure Connection
WARNING
• Never loosen the process connector bolts when an instrument is installed in a process. The device is under pressure, and a loss of seal can result in a sudden and uncontrolled release of process uid.
• When draining toxic process uids that have condensed inside the pressure detector, take appropriate steps to prevent the contact of such uids with the skin or eyes and the inhalation of vapors from these uids.
The following precautions must be observed in order to safely operate the transmitter under pressure.
(a) Make sure that all the process connector bolts
are tightened rmly.
(b) Make sure that there are no leaks in the impulse
piping.
(c) Never apply a pressure higher than the
specied maximum working pressure.
<2. Handling Cautions>
2-3
IM 01C27F01-01EN
2.6 Restrictions on Use of Radio Transceivers
IMPORTANT
Although the transmitter has been designed to resist high frequency electrical noise, if a radio transceiver is used near the transmitter or its external wiring, the transmitter may be affected by high frequency noise pickup. To test this, start out from a distance of several meters and slowly approach the transmitter with the transceiver while observing the measurement loop for noise effects. Thereafter use the transceiver outside the range where the noise effects were rst observed.
2.7 Insulation Resistance and Dielectric Strength Test
Since the transmitter has undergone insulation resistance and dielectric strength tests at the factory before shipment, normally these tests are not required. If the need arises to conduct these tests, heed the following:
(a) Do not perform such tests more frequently than
is absolutely necessary. Even test voltages that do not cause visible damage to the insulation may degrade the insulation and reduce safety margins.
(b) Never apply a voltage exceeding 500 V DC
(100 V DC with an internal lightning protector) for the insulation resistance test, nor a voltage exceeding 500 V AC (100 V AC with an internal lightning protector) for the dielectric strength test.
(c) The procedure for conducting these tests is as
follows:
Insulation Resistance Test
1) Remove the battery pack. See subsection 9.4.5 for details on how to remove it.
2) Short-circuit the battery connection terminals in the terminal box.
3) Turn OFF the insulation tester. Then connect the insulation tester plus (+) lead wire to the shorted battery connection terminals and the minus (–) leadwire to the grounding terminal.
4) Turn ON the insulation tester power and measure the insulation resistance. The voltage should be applied as briey as possible to verify that the insulation resistance is at least 20 MΩ.
5) After completing the test and being very careful not to touch exposed conductors disconnect the insulation tester and connect a 100 kΩ resistor between the grounding terminal and the short­circuiting battery connection terminals. Leave this resistor connected at least one second to discharge any static potential. Do not touch the terminals while it is discharging.
NOTE
When storing the instrument with a battery pack, it is recommended to put the instrument in Deep Sleep mode to conserve the batteries. For details on how to switch to Deep Sleep mode, refer to subsection 8.3.12 “Switching to Deep Sleep Mode”.
Dielectric Strength Test
1) Remove the battery pack. See subsection 9.4.5 for details on how to remove it.
2) Short-circuit the battery connection terminals in the terminal box.
3) Turn OFF the dielectric strength tester. Then connect the tester between the shorted battery connection terminals and the grounding terminal. Be sure to connect the grounding lead of the dielectric strength tester to the ground terminal.
4) Set the current limit on the dielectric strength tester to 10 mA, then turn ON the power and gradually increase the test voltage from ‘0’ to the specied voltage.
5) When the specied voltage is reached, hold it for one minute.
6) After completing this test, slowly decrease the voltage to avoid any voltage surges.
NOTE
When storing the instrument with a battery pack, it is recommended to put the instrument in Deep Sleep mode to conserve the batteries. For details on how to switch to Deep Sleep mode, refer to subsection 8.3.12 “Switching to Deep Sleep Mode”.
<2. Handling Cautions>
2-4
IM 01C27F01-01EN
2.8 Installation of an Explosion­Protected Instrument
If a customer makes a repair or modication to an intrinsically safe instrument and the instrument is not restored to its original condition, its intrinsically safe construction may be compromised and the instrument may be hazardous to operate. Please contact Yokogawa before making any repair or modication to an instrument.
CAUTION
This instrument has been tested and certied as being intrinsically safe. Please note that severe restrictions apply to this instrument’s construction, installation, external wiring, maintenance and repair. A failure to abide by these restrictions could make the instrument a hazard to operate.
2.8.1 FM Approval
Caution for FM intrinsically safe type. (Following contents refer “DOC. No. IFM037-A20”)
Note 1. Model EJX Series Differential, gauge
and absolute pressure transmitters with optional code /FS17 are applicable for use in hazardous locations.
• Applicable Standard: FM3600, FM3610, FM3611, FM3810
• Intrinsically Safe for Class I, Division 1, Groups A, B, C & D. Class II, Division 1, Groups E, F & G and Class III, Division 1, Class I, Zone 0 in Hazardous Locations, AEx ia IIC
• Nonincendive for Class I, Division 2, Groups A, B, C & D. Class II, Division 2, Groups F & G and Class III, Division 1, Class I, Zone 2, Groups IIC, in Hazardous Locations.
• Enclosure: NEMA 4X (Indoors and outdoors)
• Temperature Class: T4
• Ambient temperature: -50 to 70°C
Note 2. Installation
• Installation should be in accordance with ANSI/ISA RP12.6 “Installation of Intrinsically Safe Systems for Hazardous (Classied) Locations” and the National Electric Code (ANSI/NFPA 70).
• Dust-tight conduit seal must be used when installed in a Class II, III, Group E, F and G environments.
• Note a warning label worded “SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY,” and “INSTALL IN ACCORDANCE WITH DOC. No. IFM037-A20”.
Note 3. Maintenance and Repair
• The instrument modication or parts replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void Factory Mutual Intrinsically safe and Nonincendive Approval.
Transmitter
Hazardous Location
[Intrinsically Safe] Class I, II, III, Division 1, Groups A,B,C,D,E,F,G Class I, Zone 0 in Hazardous (Classified) Locations AEx ia IIC
[Nonincendive] Class I, II, Division 2, Groups A, B, C, D, F, G Class III, Division 1. Class I, Zone 2, Group IIC, in Hazardous (Classified) Locations
F0204.ai
Note 4. Battery Pack USE ONLY YOKOGAWA BATTERY PACK
F9915MA or F9915NS.
Note 5. Special Conditions for safe use POTENTIAL ELECTROSTATIC CHARGING
HAZARD-SECURE DISTANCE OF 100MM FROM ANTENNA.
DO NOT OPEN WHEN CL II, III, DIV 1,2
ATMOSPHERE IS PRESENT.
<2. Handling Cautions>
2-5
IM 01C27F01-01EN
2.8.2 CSA Certication
Caution for CSA Intrinsically safe type. (Following contents refer to “DOC No. ICS030”)
Note 1. Model EJX Series differential, gauge,
and absolute pressure transmitters with optional code /CS17 are applicable for use
in hazardous locations Certicate: 2325443 [For CSA C22.2]
• Applicable Standard: C22.2 No.0, C22.2
No.0.4, C22.2 No.25, C22.2 No.94, C22.2 No.157, C22.2 No.213, C22.2 No.61010-1
• Intrinsically Safe for Class I, Division 1,
Groups A, B, C & D, Class II, Division 1, Groups E, F & G, Class III, Division 1
• Nonincendive for Class I, Division2,
Groups A, B, C&D, Class II, Division2, Groups F&G, Class III, Division1
• Enclosure: Type 4X,
• Temp. Code: T4
• Amb. Temp.:-50 to 70°C
• Process Temperature: 120°C max. [For CSA E60079]
• Applicable Standard: CAN/CSA E60079-0,
CAN/CSA E60079-11, IEC 60529:2001-02
• Ex ia IIC T4
• Ambient Temperature: -50 to 70°C
• Max. Process Temp.: 120°C
• Enclosure: IP66 and 67
Note 2. Installation
• Installation should be in accordance with
Canadian Electrical Code Part I and Local Electrical Code.
• Do not alter drawing without authorization
from CSA.
• The instrument modication or parts
replacement by other than authorized representative of Yokogawa Electric Corporation of America is prohibited and will void Canadian Standards Intrinsically safe and nonincendive Certication.
Transmitter
Hazardous Location
[Intrinsically Safe] Group IIC, Zone 0 Class I, II, III, Division 1, Groups A,B,C,D,E,F,G
[Nonincendive] Class I, II, Division 2, Groups A,B,C,D,F,G Class III, Division 1
F0205.ai
Note 3. Battery Pack
• Use only YOKOGAWA battery pack F9915MA or F9915NS.
Note 4. Special Conditions for safe use
• Potential electrostatic charging hazard ­secure distance of 100mm from antenna.
2.9 EMC Conformity Standards
EN61326-1 Class A, Table 2 (For use in industrial locations), EN61326-2-3
CAUTION
This instrument is a Class A product, and it is designed for use in the industrial environment. Please use this instrument in the industrial environment only.
2.10 Pressure Equipment Directive (PED)
(1) General
• EJX Series pressure transmitters are categorized as pressure accessories under the vessel section of directive 97/23/EC, which corresponds to Article 3, Paragraph 3 of PED, denoted as Sound Engineering Practice (SEP).
• EJX110B-MS, EJX110B-HS, EJX110B-VS, EJX510B-D, and EJX530B-D can be used above 200 bar and therefore considered as a part of a pressure retaining vessel where category III, Module H applies. These models with option code /PE3 conform to that category.
<2. Handling Cautions>
2-6
IM 01C27F01-01EN
(2) Technical Data
• Models without /PE3 Article 3, Paragraph 3 of PED, denoted as Sound Engineering Practice (SEP).
• Models with /PE3
Module: H Type of Equipment: Pressure Accessory-Vessel Type of uid: Liquid and Gas Group of uid: 1 and 2
Model
Capsule
codePS(bar)*
1
V(L)
PS·V
(bar·L)
Category*
2
EJX110B
L 160 0.01 1.6
Article 3,
Paragraph 3
(SEP)
M, H, V 250 0.01 2.5
EJX110B with code
/PE3
M, H, V 250 0.01 2.5 III
EJX310B L, M, A, B 160 0.01 1.6
Article 3,
Paragraph 3
(SEP)
EJX430B H, A, B 160 0.01 1.6
Article 3,
Paragraph 3
(SEP)
EJX510B
A, B, C 100 0.1 10
Article 3,
Paragraph 3
(SEP)
D 700 0.1 70
EJX510B with code
/PE3
D 700 0.1 70 III
EJX530B
A, B, C 100 0.1 10
Article 3,
Paragraph 3
(SEP)
D 700 0.1 70
EJX530B with code
/PE3
D 700 0.1 70 III
*1: PS is maximum allowable pressure for vessel itself. *2: Referred to Table 1 covered by ANNEX II of EC Directive
on Pressure Equipment Directive 97/23/EC
(3) Operation
CAUTION
• The temperature and pressure of uid should be maintained at levels that are consistent with normal operating conditions.
• The ambient temperature should be maintained at a level that is consistent with normal operating conditions.
• Please take care to prevent water hammer and the like from inducing excessive pressures in pipes and valves. If phenomena are likely, install a safety valve or take some other appropriate measure to prevent pressure from exceeding PS.
• Take appropriate measures at the device or system level to protect transmitters if they are to be operated near an external heat source.
2.11 Low Voltage Directive
Applicable standard: EN61010-1
(1) Pollution Degree 2
"Pollution degree" describes the degree to which a solid, liquid, or gas which deteriorates dielectric strength or surface resistivity is adhering. " 2 " applies to normal indoor atmosphere. Normally, only non-conductive pollution occurs. Occasionally, however, temporary conductivity caused by condensation must be expected.
(2) Installation Category I
"Overvoltage category (Installation category)" describes a number which denes a transient overvoltage condition. It implies the regulation for impulse withstand voltage. " I " applies to electrical equipment which is supplied from the circuit when appropriate transient overvoltage control means (interfaces) are provided.
<2. Handling Cautions>
2-7
IM 01C27F01-01EN
2.12 Regulatory Compliance for Radio and Telecommunication
Please conrm that a installation region fullls a standards, require additional regulatory information and approvals, contact to Yokogawa Electric Corporation.
2.12.1 Radio and Telecommunications Terminal Equipment Directive (R&TTE)
We, Yokogawa Electric Corporation hereby declare that this equipment, model EJX-L series is in compliance with the essential requirements and other relevant provisions of Directive 1999/5/EC. The CE declaration of conformity for R&TTE for this product can be found at http://www.yokogawa.com/ d/
NOTE
France restricts outdoor use to 10mW (10dBm) EIRP in the frequency range of 2,454
- 2,483.5MHz. Installation in France must congure the network with conguration tool not to use channel 10 to 14. To congure the network, refer to IM 01W01F01-01EN.
2.12.2 FCC compliance
This device complies with Part 15 of FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of this device.
Co-located:
This transmitter must not be co-located or operated in conjunction with any other antenna or transmitter.
FCC WARNING:
Changes or modications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
NOTE
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of he FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual,may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
2.12.3 Industry Canada (IC) compliance
This Class A digital apparatus complies with Canadian ICES-003.
French: Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.
Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
<3. Component Names>
3-1
IM 01C27F01-01EN
3. Component Names
WR E D
F0301.ai
H L
E D
H L
E D
YES
(Note 2)
(Write disabled)
NO
(Write enabled)
Zero-adjustment screw
Ground terminal
RF assembly
CPU assembly
Not in use
Write protection switch
Transmitter section
Amplifier Cover
Mounting screw
Integral indicator
Slide switch
Hardware write protection switch (WR)
Write Protection
Write Protection Switch Position
(Note 1)
Pressure-detector section
Note 1: Set the switch as shown in the gure above to set the write protection. The hardware write protection switch is set to E side. Set
to H side for the switch of not-in-use.
Note 2: When the switch is D side (write protection setting), provisioning is acceptable. For details of provisioning, refer to section 7.4 “
Connecting to the Field Wireless Network “.
Figure 3.1 Component Names
Table 3.1 Display Symbol
Display Symbol Meaning of Display Symbol
The output signal being zero-adjusted is increasing.
The output signal being zero-adjusted is decreasing.
Write protect function is enabled.
<4. Installation>
4-1
IM 01C27F01-01EN
4. Installation
4.1 Precautions
Before installing the transmitter, read the cautionary notes in section 2.4, “Selecting the Installation Location.” For additional information on the ambient conditions allowed at the installation location, refer to section11.1 “Standard Specications.”
NOTE
To connect this transmitter to the Field Wireless Network, information for connecting to the eld wireless devices needs to be set beforehand. Refer to 7.4 “Connecting to the Field Wireless Network.”
IMPORTANT
• When welding piping during construction, take care not to allow welding currents to ow through the transmitter.
• Do not step on this instrument after installation.
• For the EJX530B whose capsule code is A, B or C, the pipe of the atmospheric opening is located on the pressure detecting section. The opening must not face upward. See subsection 5.1.1.
• D capsule of EJX530B is of sealed gauge reference and the change in atmospheric pressure may affect the measurement.
4.2 Mounting
■ The impulse piping connection port of the transmitter is covered with a plastic cap to protect against dust. This cap must be removed before connecting the piping. (Be careful not to damage the threads when removing these caps. Do not insert a screw driver or other tool between the cap and the port threads to remove the cap.)
■ The transmitter can be mounted on a nominal 50 mm (2-inch) pipe using the mounting bracket supplied, as shown in Figure 4.1.
■ The user should prepare the mating gasket for the transmitters with Process connection code 8 and 9. See Figure 4.2.
Horizontal pipe mounting
F0401.ai
Vertical pipe mounting
50 mm (2-inch) pipe
U-bolt (L)
U-bolt (S)
Mounting bracket
U-bolt nut (S)
U-bolt nut (L)
U-bolt nut (L)
Mounting bracket
50 mm (2-inch) pipe
U-bolt (L)
U-bolt (S)
U-bolt nut (S)
Figure 4.1 Transmitter Mounting
Gasket
F0402.ai
Figure 4.2 Gasketing
<4. Installation>
4-2
IM 01C27F01-01EN
IMPORTANT
Tighten the hexagonal nut part of the capsule assembly. See Figure 4.3.
F0403.ai
Capsule assembly
Figure 4.3 Tightening Transmitter
4.3 Rotating Transmitter Section
WARNING
Intrinsic safe type transmitters must be, as a rule, do not rotate transmitter section if it is powered. In case you need to rotate when the transmitter is powered, using gas detector and conrm no existence of explosive gas before rotating.
The transmitter section can be rotated approximately 360° (180° to either direction or 360° to one direction from the original position at shipment, depending on the conguration of the instrument.) It can be xed at any angle within above range.
1) Remove the ve setscrews that fasten the transmitter section and capsule assembly, using the Allen wrench.
2) Rotate the transmitter section slowly and stop it at designated position. For the EJX530B whose capsule code is A, B or C, the pipe of the atmospheric opening may interfere with the stopper and disturb further rotation. In that case, screw off the pipe rst, rotate the housing, and then screw in the pipe by hand again.
3) Tighten the ve setscrews to a torque of 1.5 N·m.
IMPORTANT
Do not rotate the transmitter section more than the above limit.
Stopper
Setscrew
Transmitter section
Pressure-detector section
F0404.ai
Figure 4.4 Rotating Transmitter Section
4.4 Changing the Direction of Integral Indicator
WARNING
Intrinsic safe type transmitters must be, as a rule, remove a battery pack in non-hazardous area before open/close the Amplier Cover or disassembling and reassembling the Integral Indicator.
An integral indicator can be installed in the following three directions. Follow the instructions in section
9.4.1 for removing and attaching the integral
indicator.
<4. Installation>
4-3
IM 01C27F01-01EN
4.5 Changing the direction of the antenna
Adjust the direction of the antenna to be in the upright position. Figure 4.5 show factory setup antenna position. If the transmitter is installed to horizontal impulse piping, follow the procedure below and change the antenna position.
1) Loosen the two mounting screws at the bottom of the antenna by using a 2.5mm Allen wrench (see Figure 4.5).
2) Press forward and down 90 degrees by rotating the axis at the bottom of the antenna.
3) Tighten the two screws to a torque of 1.5 N-m by using a torque wrench. When doing this, be careful not leave a gap between the antenna and housing.
F0405.ai
Figure 4.5 Mounting Screw Position
F0406.ai
Figure 4.6 Adjusting Antenna Position
<5. Installing Impulse Piping>
5-1
IM 01C27F01-01EN
5. Installing Impulse Piping
5.1 Impulse Piping Installation Precautions
The impulse piping that connects the process outputs to the transmitter must convey the process pressure accurately. If, for example, gas collects in a liquidlled impulse line, or the drain for a gas-lled impulse line becomes plugged, it will not convey the pressure accurately. Since this will cause errors in the measurement output, select the proper piping method for the process uid (gas, liquid, or steam). Pay careful attention to the following points when routing the impulse piping and connecting the impulse piping to a transmitter.
5.1.1 Connecting Impulse Piping to a Transmitter
IMPORTANT
The transmitter can be installed in horizontal impulse piping conguration, tilting the transmitter's position up to 90°. When tilting, observe that the pipe (for Model EJX530A with measurement span code A, B, and C) is positioned horizontal downwards, or any place between them, as shown in Figure 5.1 The zero-adjustment screw must be positioned downwards for all the models.
F0501.ai
Zero-adjustment screw Pipe
(backside of the instrument)
The pipe (open to atmosphere) is positioned horizontal.
If the zero-adjustment screw is positioned other than downwards after installation, rotate the housing until it is positioned downwards.
Figure 5.1 Horizontal Impulse Piping Connection
5.1.2 Routing the Impulse Piping
(1) Process Pressure Tap Angles
If condensate, gas, sediment or other extraneous material in the process piping gets into the impulse piping, pressure measurement errors may result. To prevent such problems, the process pressure taps must be angled as shown in gure 5.2 according to the kind of uid being measured.
NOTE
• If the process uid is a gas, the taps must be vertical or within 45° either side of vertical.
• If the process uid is a liquid, the taps must be horizontal or below horizontal, but not more than 45° below horizontal.
• If the process uid is steam or other condensing vapor, the taps must be horizontal or above horizontal, but not more than 45° above horizontal.
[Gas]
Pressure
taps
Process
piping
[Steam][Liquid]
45°
45°
45° 45°
45°
45°
F0502.ai
Figure 5.2 Process Pressure Tap Angle
(For Horizontal Piping)
(2) Position of Process Pressure Taps and
Transmitter
If condensate (or gas) accumulates in the impulse piping, it should be removed periodically by opening the drain (or vent) plugs. However, this will generate a transient disturbance in the pressure measurement, and therefore it is necessary to position the taps and route the impulse piping so that any extraneous liquid or gas generated in the leadlines returns naturally to the process piping.
• If the process uid is a gas, then as a rule the transmitter must be located higher than the process pressure taps.
• If the process uid is a liquid or steam, then as a rule the transmitter must be located lower than the process pressure taps.
<5. Installing Impulse Piping>
5-2
IM 01C27F01-01EN
(3) Impulse Piping Slope
The impulse piping must be routed with only an upward or downward slope. Even for horizontal routing, the impulse piping should have a slope of at least 1/10 to prevent condensate (or gases) from accumulating in the pipes.
(4) Preventing Freezing
If there is any risk that the process uid in the impulse piping or transmitter could freeze, use a steam jacket or heater to maintain the temperature of the uid.
NOTE
After completing the connections, close the valves on the process pressure taps (main valves), the valves at the transmitter (stop valves), and the impulse piping drain valves, so that condensate, sediment, dust and other extraneous material cannot enter the impulse piping.
5.2 Impulse Piping Connection Examples
Figure 5.3 shows examples of typical impulse piping connections. Before connecting the transmitter to the process, study the transmitter installation location, the process piping layout, and the characteristics of the process uid (corrosiveness, toxicity, ammability, etc.), in order to make appropriate changes and additions to the connection congurations.
Note the following points when referring to these piping examples.
• If the impulse line is long, bracing or supports should be provided to prevent vibration.
• The impulse piping material used must be compatible with the process pressure, temperature, and other conditions.
• A variety of process pressure tap valves (main valves) are available according to the type of connection (anged, screwed, welded), construction (globe, gate, or ball valve), temperature and pressure. Select the type of valve most appropriate for the application.
F0503.ai
Tee
Stop valve
Stop valve
Drain valve
Drain plug
Union
or
flange
Union
or
flange
Tap valve
Figure 5.3 Impulse Piping Connection Examples
<6. Grounding>
6-1
IM 01C27F01-01EN
6. Grounding
Always ground the transmitter case in accordance with national and local electrical codes. The most effective transmitter case grounding method is a direct connection to earth ground with minimal impedance.
F0601.ai
Ground terminal
Figure 6.1 Ground Terminal
CAUTION
Grounding is recommended for safe operation.
Loading...
+ 51 hidden pages