Yokogawa EJX115A User Manual

User’s Manual
Low Flow Transmitter EJX115A and EJA115E
IM 01C25K01-01E
IM 01C25K01-01E
6th Edition
Low Flow Transmitter EJX115A and EJA115E
IM 01C25K01-01E 6th Edition
Contents
1. Introduction ............................................................................................... 1-1
Regarding This Manual ................................................................................................ 1-1
1.1 Safe Use of This Product .................................................................................1-2
1.2 Warranty ............................................................................................................. 1-3
1.3 ATEX Documentation ....................................................................................... 1-4
2. Handling Cautions .................................................................................... 2-1
2.1 Model and Specications Check ..................................................................... 2-1
2.2 Unpacking ..........................................................................................................2-1
2.3 Storage ...............................................................................................................2-1
2.4 Selecting the Installation Location ................................................................ 2-2
2.5 Pressure Connection ........................................................................................2-2
2.6 Waterproong of Cable Conduit Connections ..............................................2-2
2.7 Restrictions on Use of Radio Transceivers ................................................... 2-2
2.8 Insulation Resistance and Dielectric Strength Test ......................................2-2
2.9 Installation of an Explosion-Protected Instrument ....................................... 2-3
2.9.1 FM Approval .......................................................................................2-4
2.9.2 CSA Certication ................................................................................2-6
2.9.3 ATEX Certication ..............................................................................2-8
2.9.4 IECEx Certication ........................................................................... 2-11
2.10 EMC Conformity Standards ...........................................................................2-12
2.11 Pressure Equipment Directive (PED) ...........................................................2-13
2.12 Low Voltage Directive .....................................................................................2-13
i
3. Component Names .................................................................................. 3-1
4. Installation ................................................................................................. 4-1
4.1 Precautions .......................................................................................................4-1
4.2 Mounting ........................................................................................................... 4-1
4.3 Changing the manifold assembly ................................................................... 4-2
4.4 Swapping the High/Low-pressure Side Connection ..................................... 4-2
4.5 Rotating Transmitter Section ...........................................................................4-3
4.6 Changing the Direction of Integral Indicator .................................................4-3
6th Edition: June 2013 (YK) All Rights Reserved, Copyright © 2008, Yokogawa Electric Corporation
5. Installing Impulse Piping ......................................................................... 5-1
5.1 Process Piping Installation Precautions ........................................................ 5-1
5.1.1 Connecting Process Piping to the Transmitter ..................................5-1
5.1.2 Routing the Process Piping ...............................................................5-1
5.2 Process Piping Connection Examples ........................................................... 5-2
6. Wiring ......................................................................................................... 6-1
6.1 Wiring Precautions ...........................................................................................6-1
6.2 Selecting the Wiring Materials ......................................................................... 6-1
6.3 Connections of External Wiring to Terminal Box ..........................................6-1
6.3.1 Power Supply Wiring Connection ...................................................... 6-1
6.3.2 External Indicator Connection............................................................6-1
6.3.3 Communicator Connection ................................................................ 6-1
6.3.4 Check Meter Connection ...................................................................6-2
6.3.5 Status Output Connection ..................................................................6-2
6.4 Wiring ................................................................................................................. 6-2
6.4.1 Loop Conguration ............................................................................6-2
6.4.2 Wiring Installation ...............................................................................6-2
6.5 Grounding ..........................................................................................................6-3
6.6 Power Supply Voltage and Load Resistance ................................................. 6-3
ii
7. Operation ................................................................................................... 7-1
7.1 Preparation for Starting Operation ................................................................. 7-1
7.2 Zero Point Adjustment .....................................................................................7-2
7.3 Starting Operation ............................................................................................ 7-2
7.4 Shutting Down Operation ................................................................................7-3
7.5 Transmitter Measurement Range (Determining Differential Pressure Range)
............................................................................................................................. 7-3
7.5.1 Determining the Differential Pressure Range ....................................7-3
7.5.2 Example of Calculation ......................................................................7-4
7.6 Venting or Draining Transmitter Pressure-detector Section ....................... 7-6
7.6.1 Draining Condensate ......................................................................... 7-6
7.6.2 Venting Gas........................................................................................7-6
7.7 Setting the Range Using the Range-setting Switch ......................................7-6
8. Maintenance .............................................................................................. 8-1
8.1 Overview ............................................................................................................8-1
8.2 Calibration Instruments Selection .................................................................. 8-1
8.3 Calibration .........................................................................................................8-1
8.4 Disassembly and Reassembly ........................................................................ 8-3
8.4.1 Replacing the Integral Indicator .........................................................8-3
8.4.2 Replacing the CPU Board Assembly .................................................8-4
8.4.3 Replacing the Process Connector Gaskets .......................................8-4
8.4.4 Cleaning Manifold Assembly and Replacing Orice ..........................8-4
8.4.5 Cleaning and Replacing the Capsule Assembly ............................... 8-5
8.5 Troubleshooting ................................................................................................8-6
8.5.1 Basic Troubleshooting .......................................................................8-6
8.5.2 Troubleshooting Flowcharts ...............................................................8-7
8.5.3 Alarms and Countermeasures ...........................................................8-9
9. General Specications ............................................................................ 9-1
9.1 Standard Specications ...................................................................................9-1
9.2 Model and Sufx Codes ...................................................................................9-4
9.3 Optional Specications ...................................................................................9-5
9.4 Dimensions ........................................................................................................ 9-7
[Measurement span code M and H] ....................................................................9-7
[Measurement span code F] ...............................................................................9-8
Revision Information
iii
When using the Transmitters in a Safety Instrumented Systems(SIS) application, refer to Appendix A in either IM 01C25T01-06EN for the HART protocol or IM 01C25T03-01E for the BRAIN protocol.
<1. Introduction>

1. Introduction

1-1
Thank you for purchasing the DPharp Low ow transmitter.
Your Pressure Transmitter was precisely calibrated at the factory before shipment. To ensure both safety and efciency, please read this manual carefully before you operate the instrument.
NOTE
This manual describes the hardware congurations of the transmitters listed in below. For information on the software conguration and operation, please refer to either IM 01C25T03-01E for the BRAIN communication type, or IM 01C25T01-06EN for the HART communication type.
For FOUNDATION Fieldbus protocol type, please refer to IM 01C25T02-01E. For PROFIBUS PA protocol type, please refer to IM 01C25T04-01EN.
Model Style code
EJX115A S1 EJA115E S1
To ensure correct use of this instrument, read both the hardware and software manuals thoroughly before use.
WARNING
When using the transmitters in a Safety Instrumented Systems (SIS) application, refer to Appendix 1 in either IM 01C25T01-06EN for the HART protocol or IM 01C25T03-01E for the BRAIN protocol. The instructions and procedures in this section must be strictly followed in order to maintain the transmitter for this safety level.

Regarding This Manual

• This manual should be provided to the end user.
• The contents of this manual are subject to change without prior notice.
• All rights reserved. No part of this manual may be reproduced in any form without Yokogawa’s written permission.
• Yokogawa makes no warranty of any kind with regard to this manual, including, but not limited to, implied warranty of merchantability and tness for a particular purpose.
• If any question arises or errors are found, or if any information is missing from this manual, please inform the nearest Yokogawa sales ofce.
• The specications covered by this manual are limited to those for the standard type under the specied model number break-down and do not cover custom-made instruments.
• Please note that changes in the specications, construction, or component parts of the instrument may not immediately be reected in this manual at the time of change, provided that postponement of revisions will not cause difculty to the user from a functional or performance standpoint.
• Yokogawa assumes no responsibilities for this product except as stated in the warranty.
• If the customer or any third party is harmed by the use of this product, Yokogawa assumes no responsibility for any such harm owing to any defects in the product which were not predictable, or for any indirect damages.
• The following safety symbols are used in this manual:
NOTE
When describing the model name as EJ115, it shows the applicability for both EJX115A and EJA115E.
<1. Introduction>
1-2
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
IMPORTANT
Indicates that operating the hardware or software in this manner may damage it or lead to system failure.
NOTE
Draws attention to information essential for understanding the operation and features.
Direct current

1.1 Safe Use of This Product

For the safety of the operator and to protect the instrument and the system, please be sure to follow this manual’s safety instructions when handling this instrument. If these instructions are not heeded, the protection provided by this instrument may be impaired. In this case, Yokogawa cannot guarantee that the instrument can be safely operated. Please pay special attention to the following points:
(a) Installation
• This instrument may only be installed by an engineer or technician who has an expert knowledge of this device. Operators are not allowed to carry out installation unless they meet this condition.
• With high process temperatures, care must be taken not to burn yourself by touching the instrument or its casing.
• Never loosen the process connector nuts when the instrument is installed in a process. This can lead to a sudden, explosive release of process uids.
• When draining condensate from the pressure detector section, take appropriate precautions to prevent the inhalation of harmful vapors and the contact of toxic process uids with the skin or eyes.
• When removing the instrument from a hazardous process, avoid contact with the uid and the interior of the meter.
• All installation shall comply with local installation requirements and the local electrical code.
(b) Wiring
• The instrument must be installed by an engineer or technician who has an expert knowledge of this instrument. Operators are not permitted to carry out wiring unless they meet this condition.
• Before connecting the power cables, please conrm that there is no current owing through the cables and that the power supply to the instrument is switched off.
<1. Introduction>
1-3
(c) Operation
• Wait 5 min. after the power is turned off, before opening the covers.
(d) Maintenance
• Please carry out only the maintenance procedures described in this manual. If you require further assistance, please contact the nearest Yokogawa ofce.
• Care should be taken to prevent the build up of dust or other materials on the display glass and the name plate. To clean these surfaces, use a soft, dry cloth.
(e) Explosion Protected Type Instrument
• Users of explosion proof instruments should refer rst to section 2.9 (Installation of an Explosion Protected Instrument) of this manual.
• The use of this instrument is restricted to those who have received appropriate training in the device.
• Take care not to create sparks when accessing the instrument or peripheral devices in a hazardous location.
(f) Modication

1.2 Warranty

• The warranty shall cover the period noted on the quotation presented to the purchaser at the time of purchase. Problems occurring during the warranty period shall basically be repaired free of charge.
• If any problems are experienced with this instrument, the customer should contact the Yokogawa representative from which this instrument was purchased or the nearest Yokogawa ofce.
• If a problem arises with this instrument, please inform us of the nature of the problem and the circumstances under which it developed, including the model specication and serial number. Any diagrams, data and other information you can include in your communication will also be helpful.
• The party responsible for the cost of xing the problem shall be determined by Yokogawa following an investigation conducted by Yokogawa.
• The purchaser shall bear the responsibility for repair costs, even during the warranty period, if the malfunction is due to:
• Yokogawa will not be liable for malfunctions or damage resulting from any modication made to this instrument by the customer.
- Improper and/or inadequate maintenance by the purchaser.
- Malfunction or damage due to a failure to handle, use, or store the instrument in accordance with the design specications.
- Use of the product in question in a location not conforming to the standards specied by Yokogawa, or due to improper maintenance of the installation location.
- Failure or damage due to modication or repair by any party except Yokogawa or an approved representative of Yokogawa.
- Malfunction or damage from improper relocation of the product in question after delivery.
- Reason of force majeure such as res, earthquakes, storms/oods, thunder/ lightening, or other natural disasters, or disturbances, riots, warfare, or radioactive contamination.
<1. Introduction>

1.3 ATEX Documentation

This is only applicable to the countries in European Union.
1-4
GB
DK
E
NL
SK
CZ
I
LT
LV
EST
PL
SF
P
F
D
S
SLO
H
BG
RO
M
GR
<2. Handling Cautions>

2. Handling Cautions

2-1
This chapter provides important information on how to handle the transmitter. Read this carefully before using the transmitter.
The transmitters are thoroughly tested at the factory before shipment. When taking delivery of an instrument, visually check them to make sure that no damage occurred during shipment.
Also check that all transmitter mounting hardware shown in gure 2.1 is included. If the transmitter is ordered without the mounting bracket and the process connector, the transmitter mounting hardware will not be included. After checking the transmitter, carefully repack it in its box and keep it there until you are ready to install it.
U-bolt
2.1 Model and Specications Check
The model name and specications are written on the name plate attached to the case.
F0202.ai
Figure 2.2 Name Plate

2.2 Unpacking

Keep the transmitter in its original packaging to prevent it from being damaged during shipment. Do not unpack the transmitter until it reaches the installation site.

2.3 Storage

Mounting bracket (L type)
U-bolt nut
U-bolt nut
Mounting bracket (Flat type)
Figure 2.1 Transmitter Mounting Hardware
Transmitter mounting bolt
Transmitter mounting bolt
U-bolt
F0201.ai
The following precautions must be observed when storing the instrument, especially for a long period.
(a) Select a storage area which meets the following
conditions:
• It is not exposed to rain or subject to water seepage/leaks.
• Vibration and shock are kept to a minimum.
• It has an ambient temperature and relative humidity within the following ranges.
Ambient temperature: –40* to 85°C without integral indicator –30* to 80°C with integral indicator
* –15°C when /HE is specied.
Relative humidity: 0% to 100% R.H. Preferred temperature and humidity: approx. 25°C and 65% R.H.
(b) When storing the transmitter, repack it carefully
in the packaging that it was originally shipped with.
(c) If the transmitter has been used, thoroughly
clean the chambers inside the cover anges and integral ow orice unit, so that there is no process uid remaining inside. Before placing it in storage, also make sure that the pressure-detector is securely connected to the transmitter section.
<2. Handling Cautions>
2-2

2.4 Selecting the Installation Location

The transmitter is designed to withstand severe environmental conditions. However, to ensure that it will provide years of stable and accurate performance, take the following precautions when selecting the installation location.
(a) Ambient Temperature
Avoid locations subject to wide temperature variations or a signicant temperature gradient. If the location is exposed to radiant heat from plant equipment, provide adequate thermal insulation and/or ventilation.
(b) Ambient Atmosphere
Do not install the transmitter in a corrosive atmosphere. If this cannot be avoided, there must be adequate ventilation as well as measures to prevent the leaking of rain water and the presence of standing water in the conduits.
(c) Shock and Vibration
Although the transmitter is designed to be relatively resistant to shock and vibration, an installation site should be selected where this is kept to a minimum.
(d) Installation of Explosion-protected Transmitters
An explosion-protected transmitters is certied for installation in a hazardous area containing specic gas types. See subsection
2.9 “Installation of an Explosion-Protected Transmitters.”
The following precautions must be observed in order to safely operate the transmitter under pressure.
(a) Make sure that all the process connector bolts
are tightened rmly.
(b) Make sure that there are no leaks in the impulse
piping.
(c) Never apply a pressure higher than the
specied maximum working pressure.
2.6 Waterproong of Cable Conduit Connections
Apply a non-hardening sealant to the threads to waterproof the transmitter cable conduit connections. (See gure 6.8, 6.9 and 6.10.)

2.7 Restrictions on Use of Radio Transceivers

IMPORTANT
Although the transmitter has been designed to resist high frequency electrical noise, if a radio transceiver is used near the transmitter or its external wiring, the transmitter may be affected by high frequency noise pickup. To test this, start out from a distance of several meters and slowly approach the transmitter with the transceiver while observing the measurement loop for noise effects. Thereafter use the transceiver outside the range where the noise effects were rst observed.

2.5 Pressure Connection

WARNING
• Never loosen the process connector bolts when an instrument is installed in a process. The device is under pressure, and a loss of seal can result in a sudden and uncontrolled release of process uid.
• When draining toxic process uids that have condensed inside the pressure detector, take appropriate steps to prevent the contact of such uids with the skin or eyes and the inhalation of vapors from these uids.

2.8 Insulation Resistance and Dielectric Strength Test

Since the transmitter has undergone insulation resistance and dielectric strength tests at the factory before shipment, normally these tests are not required. If the need arises to conduct these tests, heed the following:
(a) Do not perform such tests more frequently than
is absolutely necessary. Even test voltages that do not cause visible damage to the insulation may degrade the insulation and reduce safety margins.
<2. Handling Cautions>
2-3
(b) Never apply a voltage exceeding 500 V DC
(100 V DC with an internal lightning protector) for the insulation resistance test, nor a voltage exceeding 500 V AC (100 V AC with an internal lightning protector) for the dielectric strength test.
(c) Before conducting these tests, disconnect
all signal lines from the transmitter terminals. The procedure for conducting these tests is as follows:
• Insulation Resistance Test
1) Short-circuit the + and – SUPPLY terminals in the terminal box.
2) Turn OFF the insulation tester. Then connect the insulation tester plus (+) lead wire to the shorted SUPPLY terminals and the minus (–) leadwire to the grounding terminal.
3) Turn ON the insulation tester power and measure the insulation resistance. The voltage should be applied as briey as possible to verify that the insulation resistance is at least 20 MΩ.
4) After completing the test and being very careful not to touch exposed conductors disconnect the insulation tester and connect a 100 kΩ resistor between the grounding terminal and the short­circuiting SUPPLY terminals. Leave this resistor connected at least one second to discharge any static potential. Do not touch the terminals while it is discharging.
2.9 Installation of an Explosion­Protected Instrument
NOTE
For FOUNDATION Fieldbus explosion protected type, please refer to IM 01C22T02-01E. For PROFIBUS PA explosion protected type, please refer to IM 01C25T04-01EN.
If a customer makes a repair or modication to an intrinsically safe or explosionproof instrument and the instrument is not restored to its original condition, its intrinsically safe or explosionproof construction may be compromised and the instrument may be hazardous to operate. Please contact Yokogawa before making any repair or modication to an instrument.
CAUTION
This instrument has been tested and certied as being intrinsically safe or explosionproof. Please note that severe restrictions apply to this instrument’s construction, installation, external wiring, maintenance and repair. A failure to abide by these restrictions could make the instrument a hazard to operate.
• Dielectric Strength Test
1) Short-circuit the + and – SUPPLY terminals in the terminal box.
2) Turn OFF the dielectric strength tester. Then connect the tester between the shorted SUPPLY terminals and the grounding terminal. Be sure to connect the grounding lead of the dielectric strength tester to the ground terminal.
3) Set the current limit on the dielectric strength tester to 10 mA, then turn ON the power and gradually increase the test voltage from ‘0’ to the specied voltage.
4) When the specied voltage is reached, hold it for one minute.
5) After completing this test, slowly decrease the voltage to avoid any voltage surges.
WARNING
Maintaining the safety of explosionproof equipment requires great care during mounting, wiring, and piping. Safety requirements also place restrictions on maintenance and repair. Please read the following sections very carefully.
WARNING
The range setting switch must not be used in a hazardous area.
<2. Handling Cautions>
2-4
IMPORTANT
For combined approval types Once a device of multiple approval type is installed, it should not be re-installed using any other approval types. Apply a permanent mark in the check box of the selected approval type on the certication label on the transmitter to distinguish it from unused approval types.
IMPORTANT
All the blind plugs which accompany the EJX/ EJA-E transmitters upon shipment from the factory are certied by the applicable agency in combination with those transmitters. The plugs which are marked with the symbols “◊ Ex” on their surfaces are certied only in combination with the EJX/EJA-E transmitters.

2.9.1 FM Approval

Note 2. Entity Parameters
• Intrinsically Safe Apparatus Parameters [Groups A, B, C, D, E, F and G]
Vmax = 30 V Ci = 6 nF Imax = 200 mA Li = 0 µH Pmax = 1 W
* Associated Apparatus Parameters (FM approved barriers)
Voc ≤ 30 V Ca > 6 nF Isc ≤ 200 mA La > 0 µH Pmax ≤ 1W
• Intrinsically Safe Apparatus Parameters [Groups C, D, E, F and G]
Vmax = 30 V Ci = 6 nF Imax = 225 mA Li = 0 µH Pmax = 1 W
* Associated Apparatus Parameters (FM approved barriers)
Voc ≤ 30 V Ca > 6 nF Isc ≤ 225 mA La > 0 µH Pmax ≤ 1 W
a. FM Intrinsically Safe Type
Caution for FM intrinsically safe type. (Following contents refer “DOC. No. IFM022-A12”)
Note 1. Model EJX/EJA-E Series Differential,
gauge and absolute pressure transmitters with optional code /FS1 are applicable for use in hazardous locations.
• Applicable Standard: FM3600, FM3610,
FM3611, FM3810
• Intrinsically Safe for Class I, Division 1,
Groups A, B, C & D. Class II, Division 1, Groups E, F & G and Class III, Division 1, Class I, Zone 0 in Hazardous Locations, AEx ia IIC
• Nonincendive for Class I, Division 2, Groups
A, B, C & D. Class II, Division 2, Groups F & G, Class I, Zone 2, Groups IIC, in Hazardous Locations.
• Outdoor hazardous locations, NEMA TYPE
4X.
• Temperature Class: T4
• Ambient temperature: –60 to 60°C
• Entity Installation Requirements Vmax ≥ Voc or Uo or Vt, Imax ≥ Isc or Io or It, Pmax (or Po) ≤ Pi, Ca or Co ≥ Ci + Ccable, La or Lo ≥ Li + Lcable
Note 3. Installation
• Barrier must be installed in an enclosure that meets the requirements of ANSI/ISA S82.01.
• Control equipment connected to barrier must not use or generate more than 250 V rms or V dc.
• Installation should be in accordance with ANSI/ISA RP12.6 “Installation of Intrinsically Safe Systems for Hazardous (Classied) Locations” and the National Electric Code (ANSI/NFPA 70).
• The conguration of associated apparatus must be FMRC Approved.
• Dust-tight conduit seal must be used when installed in a Class II, III, Group E, F and G environments.
• Associated apparatus manufacturer’s installation drawing must be followed when installing this apparatus.
• The maximum power delivered from the barrier must not exceed 1 W.
• Note a warning label worded “SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY,” and “INSTALL IN ACCORDANCE WITH DOC. No. IFM022­A12”
<2. Handling Cautions>
2-5
Note 4. Maintenance and Repair
• The instrument modication or parts replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void Factory Mutual Intrinsically safe and Nonincendive Approval.
[Intrinsically Safe]
Hazardous Location Nonhazardous Location
Class I, II, III, Division 1, Groups A, B, C, D, E, F, G Class 1, Zone 0 in Hazardous (Classified) Locations AEx ia IIC
Pressure Transmitters
+
Supply
Hazardous Location Nonhazardous Location
Class I, II, Division 2, Groups A, B, C, D, F, G Class 1, Zone 2, Group IIC, in Hazardous (Classified) Locations
Pressure Transmitters
Supply
[Nonincendive]
+ –
Safety Barrier
+
+
Not Use Safety Barrier
b. FM Explosionproof Type
Caution for FM explosionproof type.
Note 1. Model EJX/EJA-E Series pressure
transmitters with optional code /FF1 are applicable for use in hazardous locations.
• Applicable Standard: FM3600, FM3615, FM3810, ANSI/NEMA 250
• Explosionproof for Class I, Division 1, Groups B, C and D.
• Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G.
• Enclosure rating: NEMA TYPE 4X.
• Temperature Class: T6
• Ambient Temperature: –40 to 60°C
• Supply Voltage: 42 V dc max.
• Output signal: 4 to 20 mA
General Purpose Equipment
+ –
F0203-1.ai
General Purpose Equipment
+ –
F0203-2.ai
Note 2. Wiring
• All wiring shall comply with National Electrical Code ANSI/NFPA70 and Local Electrical Codes.
• When installed in Division 1, “FACTORY SEALED, CONDUIT SEAL NOT REQUIRED.”
Note 3. Operation
• Keep the “WARNING” nameplate attached to the transmitter.
WARNING: OPEN CIRCUIT BEFORE
REMOVING COVER. FACTORY SEALED, CONDUIT SEAL NOT REQUIRED. INSTALL IN ACCORDANCE WITH THE USERS MANUAL IM 01C25.
• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modication or parts replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void Factory Mutual Explosionproof Approval.
c. FM Intrinsically Safe Type/FM
Explosionproof Type
Model EJX/EJA-E Series pressure transmitters with optional code /FU1 or /V1U1 can be selected the type of protection (FM Intrinsically Safe or FM Explosionproof) for use in hazardous locations.
Note 1. For the installation of this transmitter,
once a particular type of protection is selected, any other type of protection cannot be used. The installation must be in accordance with the description about the type of protection in this instruction manual.
Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label other than the selected type of protection when the transmitter is installed.
<2. Handling Cautions>
2-6
2.9.2 CSA Certication
a. CSA Intrinsically Safe Type
Caution for CSA Intrinsically safe and nonincendive type. (Following contents refer to “DOC No. ICS013-A13”)
Note 1. Model EJX/EJA-E Series differential,
gauge, and absolute pressure transmitters with optional code /CS1 are applicable for
use in hazardous locations Certicate: 1606623 [For CSA C22.2]
• Applicable Standard: C22.2 No.0, C22.2
No.0.4, C22.2 No.25, C22.2 No.94, C22.2 No.157, C22.2 No.213, C22.2 No.61010-1, C22.2 No.60079-0
• Intrinsically Safe for Class I, Division 1,
Groups A, B, C & D, Class II, Division 1, Groups E, F & G, Class III, Division 1
• Nonincendive for Class I, Division 2, Groups
A, B, C & D, Class II, Division 2, Groups E, F & G, Class III, Division 1
• Enclosure: NEMA TYPE 4X
• Temp. Code: T4
• Amb. Temp.: –50* to 60°C
* –15°C when /HE is specied.
• Process Temperature: 120°C max. [For CSA E60079]
• Applicable Standard: CAN/CSA E60079-11,
CAN/CSA E60079-15, IEC 60529:2001
• Ex ia IIC T4, Ex nL IIC T4
• Ambient Temperature: –50* to 60°C
* –15°C when /HE is specied.
• Max. Process Temp.: 120°C
• Enclosure: IP66/IP67
Note 2. Entity Parameters
• Intrinsically safe ratings are as follows: Maximum Input Voltage (Vmax/Ui) = 30 V Maximum Input Current (Imax/Ii) = 200 mA Maximum Input Power (Pmax/Pi) = 0.9 W Maximum Internal Capacitance (Ci) = 10 nF Maximum Internal Inductance (Li) = 0 µH
• Type "n" or Nonincendive ratings are as
follows: Maximum Input Voltage (Vmax/Ui) = 30 V Maximum Internal Capacitance (Ci) = 10 nF Maximum Internal Inductance (Li) = 0 µH
• Installation Requirements Uo ≤ Ui, Io ≤ Ii, Po ≤ Pi, Co ≥ Ci + Ccable, Lo ≥ Li + Lcable Voc ≤ Vmax, Isc ≤ Imax, Ca ≥ Ci + Ccable, La ≥ Li + Lcable Uo, Io, Po, Co, Lo, Voc, Isc, Ca and La are
parameters of barrier.
Note 3. Installation
• In any safety barreir used output current must be limited by a resistor 'R' such that Io=Uo/R or Isc=Voc/R.
• The safety barrier must be CSA certied.
• Input voltage of the safety barrier must be less than 250 Vrms/Vdc.
• Installation should be in accordance with Canadian Electrical Code Part I and Local Electrical Code.
• Dust-tight conduit seal must be used when installed in Class II and III environments.
• The instrument modication or parts replacement by other than authorized representative of Yokogawa Electric Corporation and Yokogawa Corporation of America is prohibited and will void Canadian Standards Intrinsically safe and nonincendive Certication.
[Intrinsically Safe]
Hazardous Location Nonhazardous Location
Group IIC, Zone 0 Class I, II, III, Division 1, Groups A, B, C, D, E, F, G
Pressure Transmitters
+
Supply
Hazardous Location Nonhazardous Location
Group IIC, Zone 2 Class I, II, Division 2, Groups A, B, C, D, F, G Class III, Division 1.
Pressure Transmitters
Supply
[Nonincendive]
+ –
Safety Barrier
+
+
Not Use Safety Barrier
CSA Certified Equipment ([nL] or nonincendive)
b. CSA Explosionproof Type
Caution for CSA explosionproof type.
Note 1. Model EJX/EJA-E Series pressure
transmitters with optional code /CF1 are applicable for use in hazardous locations:
• Certicate: 2014354
• Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25, C22.2 No.30, C22.2 No.94, C22.2 No.61010-1, C22.2 No.60079-0, C22.2 No.60079-1
General Purpose Equipment
+ –
F0204-1.ai
+ –
F0204-2.ai
<2. Handling Cautions>
2-7
• Explosion-proof for Class I, Groups B, C and D.
• Dustignition-proof for Class II/III, Groups E, F and G.
• Enclosure: NEMA TYPE 4X
• Temperature Code: T6...T4
• Ex d IIC T6...T4
• Enclosure: IP66/IP67
• Maximum Process Temperature: 120°C (T4), 100°C (T5), 85°C (T6)
• Ambient Temperature: –50* to 75°C (T4), –50* to 80°C (T5), –50* to 75°C (T6)
* –15°C when /HE is specied.
• Supply Voltage: 42 V dc max.
• Output Signal: 4 to 20 mA dc
Note 2. Wiring
• All wiring shall comply with Canadian Electrical Code Part I and Local Electrical Codes.
• In hazardous location, wiring shall be in conduit as shown in the gure.
• WARNING:
A SEAL SHALL BE INSTALLED WITHIN
50cm OF THE ENCLOSURE.
UN SCELLEMENT DOIT ÊTRE INSTALLÉ À
MOINS DE 50cm DU BOÎTIER.
• WARNING:
WHEN INSTALLED IN CL.I, DIV 2, SEAL
NOT REQUIRED.
UNE FOIS INSTALLÉ DANS CL I, DIV 2,
AUCUN JOINT N'EST REQUIS.
Non-Hazardous
Locations
Non-hazardous Location Equipment
42 V DC Max. 4 to 20 mA DC Signal
Non-Hazardous
Locations
Non-hazardous Location Equipment
42 V DC Max. 4 to 20 mA DC Signal
Hazardous Locations Division 1
50 cm Max.
Sealing Fitting
Hazardous Locations Division 2
Sealing Fitting
Conduit
Transmitter
Transmitter
PULSE
SUPPLY
CHECK ALARM
F0205-1.ai
PULSE
SUPPLY
CHECK ALARM
F0205-2.ai
• All wiring shall comply with local installation requirements and local electrical code.
• In hazardous locations, the cable entry devices shall be of a certied ameproof type, suitable for the conditions of use and correctly installed.
• Unused apertures shall be closed with suitable ameproof certied blanking elements. (The plug attached is ameproof certied.)
Note 3. Operation
• WARNING:
AFTER DE-ENERGIZING, DELAY 5
MINUTES BEFORE OPENING.
APRÉS POWER-OFF, ATTENDRE 5
MINUTES AVANT D'OUVRIR.
• WARNING:
WHEN AMBIENT TEMPERATURE ≥ 65°C,
USE THE HEAT-RESISTING CABLES ≥ 90°C.
QUAND LA TEMPÉRATURE AMBIANTE
≥ 65°C, UTILISEZ DES CÂBLES RÉSISTANTES Á LA CHALEUR ≥ 90°C.
• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modication or parts replacement by other than authorized representative of Yokogawa Electric Corporation and Yokogawa Corporation of America is prohibited and will void Canadian Standards Explosionproof Certication.
c CSA Intrinsically Safe Type/CSA
Explosionproof Type
Model EJX/EJA-E Series pressure transmitters with optional code /CU1 or /V1U1 can be selected the type of protection (CSA Intrinsically Safe or CSA Explosionproof) for use in hazardous locations.
Note 1. For the installation of this transmitter,
once a particular type of protection is selected, any other type of protection cannot be used. The installation must be in accordance with the description about the type of protection in this instruction manual.
Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label other than the selected type of protection when the transmitter is installed.
<2. Handling Cautions>
2-8
2.9.3 ATEX Certication
(1) Technical Data
a. ATEX Intrinsically Safe Ex ia
Caution for ATEX Intrinsically safe type.
Note 1. Model EJX/EJA-E Series pressure
transmitters with optional code /KS21 for potentially explosive atmospheres:
• No. DEKRA 11ATEX0228 X
• Applicable Standard: EN 60079-0:2009, EN 60079-11:2007, EN 60079-26:2007, EN 61241-11:2006
• Type of Protection and Marking code: Ex ia IIC T4 Ga
Ex ia IIIC T85 ºC T100 ºC T120 ºC Db
• Group: II
• Category: 1G, 2D
• Ambient Temperature for EPL Ga: –50 to 60°C
• Ambient Temperature for EPL Db: –30* to 60°C
* –15°C when /HE is specied.
• Process Temperature (Tp.): 120°C max.
• Maximum Surface Temperature for EPL Db: T85°C (Tp.: 80°C) T100°C (Tp.: 100°C) T120°C (Tp.: 120°C)
• Enclosure: IP66 / IP67
Note 2 Electrical Data
• In type of explosion protection intrinsic safety Ex ia IIC or Ex ia IIIC, only for connection to a certied intrinsically safe circuit with following maximum values:
Ui = 30 V Ii = 200 mA Pi = 0.9 W (Linear Source) Maximum internal capacitance; Ci = 27.6 nF Maximum internal inductance; Li = 0 µH
Note 3. Installation
• Refer to the control drawing. All wiring shall comply with local installation requirements.
[Control Drawing]
Hazardous Location
Transmitter
+
Supply
*1: In any safety barriers used the output current must be
limited by a resistor “R” such that Io=Uz/R.
Nonhazardous Location
+
Safety Barrier *
F0206.ai
Note 4. Maintenance and Repair
• The instrument modication or parts replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void DEKRA Intrinsically safe Certication.
Note 5. Special Conditions for Safe Use
WARNING
• In the case where the enclosure of the Pressure Transmitter is made of aluminium, if it is mounted in an area where the use of category 1 G apparatus is required, it must be installed such, that, even in the event of rare incidents, ignition sources due to impact and friction sparks are excluded.
• Electrostatic charge may cause an exlosion hazard. Avoid any actions that cause the gerenation of eletrostatic charge, such as rubbing with a dry cloth on coating face of the product.
• In case of the enclosure of the Pressure Transmitter with paint layers, if it is mounted in an area where the use of category 2D apparatus is required, it shall be installed in such a way that the risk from electrostatic discharges and propagating brush discharges caused by rapid ow of dust is avoided.
• To satisfy IP66 or IP67, apply waterproof glands to the electrical connection port.
• When the lightning protector option is specied, the apparatus is not capable of withstanding the 500V insulation test required by EN60079-11. This must be taken into account when installing the apparatus.
1
<2. Handling Cautions>
2-9
b. ATEX Flameproof Type
Caution for ATEX ameproof type.
Note 1. Model EJX/EJA-E Series pressure
transmitters with optional code /KF22 for potentially explosive atmospheres:
• No. KEMA 07ATEX0109 X
• Applicable Standard: EN 60079-0:2009, EN 60079-1:2007, EN 60079-31:2009
• Type of Protection and Marking Code:
Ex d IIC T6...T4 Gb, Ex tb IIIC T85°C Db
• Group: II
• Category: 2G, 2D
• Enclosure: IP66/IP67
• Temperature Class for gas-poof: T6, T5, and T4
• Ambient Temperature for gas-proof: –50 to 75°C (T6), –50 to 80°C (T5), and –50 to 75°C (T4)
• Maximum Process Temperature (Tp.) for gas-proof:
85°C (T6), 100°C (T5), and 120°C (T4)
• Maximum Surface Temperature for dust­proof: T85°C (Tamb.: –30* to 75°C, Tp.: 85°C)
* –15°C when /HE is specied.
Note 5. Special Conditions for Safe Use
WARNING
• Electrostatic charge may cause an exlosion hazard. Avoid any actions that cause the gerenation of eletrostatic charge, such as rubbing with a dry cloth on coating face of the product.
• In the case where the enclosure of the Pressure Transmitter is made of aluminium, if it is mounted in an area where the use of category 2D apparatus is required, it shall be installed in such a way that the risk from electrostatic discharges and propagating brush discharges caused by rapid ow of dust is avoided.
• The instrument modication or parts replacement by other than an authorized Representative of Yokogawa Electric Corporation is prohibited and will void the certication.
• To satisfy IP66 or IP67, apply waterproof glands to the electrical connection port.
Note 2. Electrical Data
• Supply voltage: 42 V dc max.
• Output signal: 4 to 20 mA
Note 3. Installation
• All wiring shall comply with local installation requirement.
• The cable entry devices shall be of a certied ameproof type, suitable for the conditions of use.
Note 4. Operation
• Keep the “WARNING” label attached to the transmitter.
WARNING: AFTER DE-ENERGIZING,
DELAY 5 MINUTES BEFORE OPENING. WHEN THE AMBIENT TEMP.≥65°C, USE HEAT-RESISTING CABLE AND CABLE GLAND ≥90°C.
• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.
c. ATEX Intrinsically Safe Type/ATEX
Flameproof Type
Model EJX/EJA-E Series pressure transmitters with optional code /KU22 or /V1U1 can be selected the type of protection ATEX Flameproof, Intrinsically Safe. Ex ia, or Ex ic for use in hazardous area.
Note 1. For the installation of this transmitter,
once a particular type of protection is selected, any other type of protection cannot be used. The installation must be in accordance with the description about the type of protection in this user’s manual.
Note 2. For combined approval types Once a
device of multiple approval type is installed, it should not be re-installed using any other approval types. Apply a permanent mark in the check box of the selected approval type on the certication label on the transmitter to distinguish it from unused approval types.
<2. Handling Cautions>
● ATEX Intrinsically Safe Ex ic
Caution for ATEX intrinsically safe Ex ic
• Applicable Standard: EN 60079-0:2009/EN 60079-0:2012, EN 60079-11:2012
• Type of Protection and Marking Code:
II 3G Ex ic IIC T4 Gc
• Ambient Temperature: –30* to +60°C
* –15°C when /HE is specied.
• Ambient Humidity: 0 to 100% (No condensation)
• Maximum Process Temperature: 120°C
• IP Code: IP66
WARNING
• Electrostatic charge may cause an explosion hazard. Avoid any actions that cause the gerenation of eletrostatic charge, such as rubbing with a dry cloth on coating face of the product.
• When the lightning protector option is specied, the apparatus is not capable of withstanding the 500V insulation test required by EN60079-11. This must be taken into account when installing the apparatus.
• Ambient pollution degree: 2
• Overvoltage category: I
Note 1. Electrical Data
Ui = 30 V Ci = 27.6 nF Li = 0 µH
(2) Electrical Connection
A mark indicating the electrical connection type is stamped near the electrical connection port. These marks are as followed.
Screw Size Marking
Note 2. Installation
• All wiring shall comply with local installation requirements. (refer to the control drawing)
ISO M20 × 1.5 female
ANSI 1/2 NPT female
• Cable glands, adapters and/or blanking elements shall be of Ex “n”, Ex “e” or Ex “d” and shall be installed so as to maintain the specied degree of protection (IP Code) of the transmitters.
Location of the mark
Note 3. Maintenance and Repair
• The instrument modication or parts replacement by other than authorized representative of Yokogawa Electric
(3) Installation
Corporation is prohibited and will void ATEX intrinsically safe.
[Control drawing]
Hazardous Area
Nonhazardous Area
WARNING
• All wiring shall comply with local installation requirements and the local electrical code.
Transmitter
+
Associated Apparatus
• There is no need for conduit seal in Division 1 and Division 2 hazardous locations because this product is sealed at the factory.
2-10
M
N or W
F0208.ai
Note 4. Specic Conditions of Use
F0207.ai
(4) Operation
WARNING
• OPEN CIRCUIT BEFORE REMOVING COVER. INSTALL IN ACCORDANCE WITH THIS USER’S MANUAL
• Take care not to generate mechanical sparking when access to the instrument and peripheral devices in a hazardous location.
<2. Handling Cautions>
2-11
(5) Maintenance and Repair
WARNING
The instrument modication or parts replacement by other than an authorized Representative of Yokogawa Electric Corporation is prohibited and will void the certication.
(6) Name Plate
Name plate
Tag plate for flameproof type
No. KEMA 07ATEX0109 X Ex d IIC T6...T4 Gb, Ex tb IIIC T85°C Db Enlcosure : IP66/IP67 TEMP. CLASS T6 T5 T4 MAX PROCESS TEMP.(Tp.) 85 100 120 °C Tamb. -50 to 75 80 75 °C T85°C(Tamb.:-30(-15) to 75°C, Tp.:85°C)(for Dust)
*3
WARNING
Tag plate for intrinsically safe type
D
AFTER DE-ENERGIZING, DELAY 5 MINUTES BEFORE OPENING. WHEN THE AMBIENT TEMP. 65°C, USE THE HEAT-RESISTING CABLE & CABLE GLAND ≥ 90°C POTENTIAL ELECTROSTATIC CHARGING HAZARD
No. DEKRA 11ATEX 0228 X Ex ia IIC T4 Ga Ta: -50 TO 60°C Ex ia IIIC T85°C T100°C T120°C Db Ta:-30(-15) TO 60°C IP66/IP67 MAX. PROCESS TEMP.(Tp.) 120°C T85°C(Tp.:80°C), T100°C(Tp.:100°C), T120°C(Tp.:120°C) Ui=30V, Ii=200mA , Pi=0.9W, Ci=27.6nF, Li=0µH
*1: The rst digit in the three numbers next to the nine
letters of the serial number appearing after “NO.” on the nameplate indicates the year of production. The following is an example of a serial number for a product that was produced in 2010:
91K819857 032
The year 2010
*2: “180-8750” is a zip code which represents the
following address.
2-9-32 Nakacho, Musashino-shi, Tokyo Japan
*3: The identication number of Notied Body.
2.9.4 IECEx Certication
Model EJX Series pressure transmitters with optional code /SU2 can be selected the type of protection (IECEx Intrinsically Safe/type n or ameproof) for use in hazardous locations.
Note 1. For the installation of this transmitter,
once a particular type of protection is selected, any other type of protection cannot be used. The installation must be in accordance with the description about the type of protection in this instruction manual.
Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label other than the selected type of protection when the transmitter is installed.
a. IECEx Intrinsically Safe Type / type n
Caution for IECEx Intrinsically safe and type n.
*3
WARNING
D
POTENTIAL ELECTROSTATIC CHARGING HAZARD
- SEE USER’S MANUAL
Tag plate for intrinsically safe Ex ic
Ex ic IIC T4 Gc IP66 Tamb -30(-15) TO 60°C MAX. PROCESS TEMP. 120°C Ui=30V, Ci=27.6nF, Li=0µH
WARNING
POTENTIAL ELECTROSTATIC CHARGING HAZARD
- SEE USER’S MANUAL
MODEL: Specied model code. STYLE: Style code. SUFFIX: Specied sufx code. SUPPLY: Supply voltage. OUTPUT: Output signal. MWP: Maximum working pressure. CAL RNG: Specied calibration range. NO.: Serial number and year of production*1. TOKYO 180-8750 JAPAN: The manufacturer name and the address*2.
F0209.ai
Note 1. Model EJX Series differential, gauge,
and absolute pressure transmitters with optional code /SU2 are applicable for use in hazardous locations
• No. IECEx CSA 05.0005
• Applicable Standard: IEC 60079-0:2000, IEC 60079-11:1999, IEC 60079-15:2001
• Ex ia IIC T4, Ex nL IIC T4
• Ambient Temperature: –50 to 60°C
• Max. Process Temp.: 120°C
• Enclosure: IP66/IP67
Note 2. Entity Parameters
• Intrinsically safe ratings are as follows: Maximum Input Voltage (Vmax/Ui) = 30 V Maximum Input Current (Imax/Ii) = 200 mA Maximum Input Power (Pmax/Pi) = 0.9 W Maximum Internal Capacitance (Ci) = 10 nF Maximum Internal Inductance (Li) = 0 µH
• Type "n" ratings are as follows: Maximum Input Voltage (Vmax/Ui) = 30 V Maximum Internal Capacitance (Ci) = 10 nF Maximum Internal Inductance (Li) = 0 µH
<2. Handling Cautions>
2-12
• Installation Requirements Uo ≤ Ui, Io ≤ Ii, Po ≤ Pi, Co ≥ Ci + Ccable, Lo ≥ Li + Lcable Voc ≤ Vmax, Isc ≤ Imax, Ca ≥ Ci + Ccable, La ≥ Li + Lcable Uo, Io, Po, Co, Lo, Voc, Isc, Ca and La are parameters of barrier.
Note 3. Installation
• In any safety barrier used output current must be limited by a resistor 'R' such that Io=Uo/R.
• The safety barrier must be IECEx certied.
• Input voltage of the safety barrier must be less than 250 Vrms/Vdc.
• The instrument modication or parts replacement by other than authorized representative of Yokogawa Electric Corporation and will void IECEx Intrinsically safe and type n certication.
[Intrinsically Safe]
Hazardous Location Nonhazardous Location
Group IIC, Zone 0
[type n]
IECEx certified Safety Barrier
+
+
Not Use Safety Barrier
IECEx Certified Equipment [nL]
Pressure Transmitters
+
Supply
Hazardous Location Nonhazardous Location
Group IIC, Zone 2
Pressure Transmitters
Supply
+ –
b. IECEx Flameproof Type
Caution for IECEx ameproof type.
General Purpose Equipment
+ –
F0210-1.ai
+ –
F0210-2.ai
• Maximum Process Temperature: 120°C (T4), 100°C (T5), 85°C (T6)
• Ambient Temperature: –50 to 75°C (T4), –50 to 80°C (T5), –50 to 75°C (T6)
• Supply Voltage: 42 V dc max.
• Output Signal: 4 to 20 mA dc
Note 2. Wiring
• In hazardous locations, the cable entry devices shall be of a certied ameproof type, suitable for the conditions of use and correctly installed.
• Unused apertures shall be closed with suitable ameproof certied blanking elements.
Note 3. Operation
• WARNING: AFTER DE-ENERGIZING, DELAY 5 MINUTES BEFORE OPENING.
• WARNING:
WHEN AMBIENT TEMPERATURE ≥ 65°C,
USE THE HEAT-RESISTING CABLES ≥ 90°C.
• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modication or parts replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void IECEx Certication.

2.10 EMC Conformity Standards

EN61326-1 Class A, Table2 (For use in industrial locations) EN61326-2-3
CAUTION
Note 1. Model EJX/EJA-E Series pressure
transmitters with optional code /SF2 or /SU2 are applicable for use in hazardous locations:
• No. IECEx CSA 07.0008
• Applicable Standard: IEC60079-0:2004, IEC60079-1:2003
• Flameproof for Zone 1, Ex d IIC T6...T4
• Enclosure: IP66/IP67
• This instrument is a Class A product, and it is designed for use in the industrial environment. Please use this instrument in the industrial environment only.
• To meet EMC regulations, Yokogawa recommends that customers run signal wiring through metal conduits or use shielded twisted-pair cabling when installing EJX/EJA-E series transmitters in a plant.
<2. Handling Cautions>
2-13

2.11 Pressure Equipment Directive (PED)

(1) General
EJX/EJA-E Series pressure transmitters are categorized as piping under the pressure accessories section of directive 97/23/EC, which corresponds to Article 3, Paragraph 3 of PED, denoted as Sound Engineering Practice (SEP).
(2) Technical Data
Article 3, Paragraph 3 of PED, denoted as Sound Engineering Practice (SEP).
(3) Operation
CAUTION
• The temperature and pressure of uid should be maintained at levels that are consistent with normal operating conditions.
• The ambient temperature should be maintained at a level that is consistent with normal operating conditions.
• Please take care to prevent water hammer and the like from inducing excessive pressures in pipes and valves. If phenomena are likely, install a safety valve or take some other appropriate measure to prevent pressure from exceeding PS.
• Take appropriate measures at the device or system level to protect transmitters if they are to be operated near an external heat source.
(2) Installation Category I
"Overvoltage category (Installation category)" describes a number which denes a transient overvoltage condition. It implies the regulation for impulse withstand voltage. " I " applies to electrical equipment which is supplied from the circuit when appropriate transient overvoltage control means (interfaces) are provided.

2.12 Low Voltage Directive

Applicable standard: EN61010-1
(1) Pollution Degree 2
"Pollution degree" describes the degree to which a solid, liquid, or gas which deteriorates dielectric strength or surface resistivity is adhering. " 2 " applies to normal indoor atmosphere. Normally, only non-conductive pollution occurs. Occasionally, however, temporary conductivity caused by condensation must be expected.
<3. Component Names>

3. Component Names

3-1
Vertical impulse piping type
Pressure-detector section
Cover flange
Integral indicator
Mounting screw
Amplifier Cover
(Note 1)
(Note 2)
Slide switch
Range-setting
(Note 1)
switch (See section 7.6)
Transmitter section
Process connection
Process connector
Manifold
Vent plug
Drain plug
CPU assembly
Burnout direction switch
BO H L
WR E D
Terminal box cover
External indicator conduit connection
Process connection
Horizontal impulse piping type
(Note 1)
Conduit connection
Zero­adjustment screw
Process connector
Write protection switch
Burnout direction switch (BO)
Burnout Direction
Switch Position
Burnout Direction
Note 1: See subsection 9.2, “Model and Sufx Codes,” for details. Note 2: Applicable for BRAIN/HART communication type. Set the switches as shown in the gure above to set the burn-out direction
and write protection. The Burnout switch is set to the H side for delivery (unless option code /C1 or /C2 is specied in the order), and the hardware write protection switch is set to E side. The setting of the switches can be conrmed via communication. An external zero adjustment screw can only be disabled by communication. To disable the screw, set a parameter before activating the hardware write protect function. See each communication manual.
H L H L
HIGH LOW
Write Protection
Switch Position
Write Protection
Hardware write protection switch (WR)
H L
E D
NO
(Write enabled)
H L
E D
YES
(Write disabled)
Figure 3.1 Component Names
Table 3.1 Display Symbol
Display Symbol Meaning of Display Symbol
Display mode is ‘square root’. (Display is not lit when ‘linear’ mode.)
The output signal being zero-adjusted is increasing.
The output signal being zero-adjusted is decreasing.
Write protect function is enabled.
F0301.ai
F0302.ai
<4. Installation>

4. Installation

4-1

4.1 Precautions

Before installing the transmitter, read the cautionary notes in section 2.4, “Selecting the Installation Location.” For additional information on the ambient conditions allowed at the installation location, refer to subsection 9.1 “Standard Specications.”
IMPORTANT
• When welding piping during construction, take care not to allow welding currents to ow through the transmitter.
• Do not step on this instrument after installation.

4.2 Mounting

The transmitter can be mounted on a nominal
50 mm (2-inch) pipe using the mounting bracket supplied, as shown in gure 4.1 and
4.2 The transmitter can be mounted on either a horizontal or a vertical pipe.
When mounting the bracket on the transmitter,
tighten the (four) bolts that hold the transmitter with a torque of approximately 39 N·m {4kgf·m}.
The transmitter is shipped with the manifold set
up as per the order specications.
For correct ow measurement, the ow path
must always be lled with uid; otherwise, measurement accuracy cannot be assured.
For the vertical impulse piping type, it is
recommended that the manifold be mounted facing up for liquid ow measurement; facing down for gas ow measurement, as shown in Figure 4.2.
Vertical pipe mounting
U-bolt nut
Mounting bracket
Horizontal pipe mounting
Transmitter mounting bolt
U-bolt nut
Mounting bracket
Figure 4.1 Transmitter Mounting
(Horizontal Impulse Piping Type)
Transmitter mounting bolt
50 mm(2-inch) pipe
U-bolt
50 mm(2-inch) pipe
U-bolt
F0401.ai
Figure 4.1 and 4.2 shows the mounting of the transmitter for horizontal piping and vertical piping with using the mounting bracket.
<4. Installation>
4-2
Vertical pipe mounting (Process connector downside)
U-bolt nut
Vertical pipe mounting (Process connector upside)
U-bolt nut
Transmitter mounting bolt
Mounting bracket
U-bolt
50 mm(2-inch) pipe
Mounting bracket
50 mm(2-inch) pipe
U-bolt
Vertical impulse piping type
Process connector
gasket
Drain/vent plug
Horizontal impulse piping type
Bolt
Manifold
*
1
*
2
Note: For a horizontal impulse
piping type, moving the Manifold Assembly from the front side to the back cannot be made.
Transmitter mounting bolt
Figure 4.2 Transmitter Mounting
(Vertical Impulse Piping Type)
F0402.ai

4.3 Changing the manifold assembly

The transmitter is shipped with the manifold assembly specied at the time of ordering. To change the manifold assembly, the drain (vent) plug must be repositioned.
To reposition a drain (vent) plug, use a wrench to slowly and gently unscrew it. Then, remove and remount it on the opposite side. Wrap sealing tape around the drain (vent) plug threads (*1 in the gure below), and apply a lubricant to the threads of the drain (vent) screw(s) (*2 below). To tighten the drain (vent) plugs, apply a torque of 34 to 39 N·m {3.5 to 4 kgf·m}. Manifold bolts are to be tightened uniformly to a torque of 39 to 49 N·m {4 to 5 kgf·m}.
F0403.ai
Figure 4.3 Changing Manifold Assembly
4.4 Swapping the High/Low­pressure Side Connection
This procedure can be applied only to a transmitter with a vertical impulse piping type.
The procedure below can be used to turn the pressure detector assembly 180°. Perform this operation in a maintenance shop with the necessary tools laid out and ready for use, and then install the transmitter in the eld after making the change.
1) Use an Allen wrench (JIS B4648, nominal 2.5
mm) to remove the two setscrews at the joint between the pressure-detector section and transmitter section.
2) Leaving the transmitter section in position,
rotate the pressure-detector section 180°.
<4. Installation>
4-3
3) Tighten the two setscrews to x the pressure­detector section and transmitter section together (at a torque of 1.5 N·m).
Reposition the manifold assembly and drain
(vent) plugs to the opposite side as described in subsection 4.3.
Before
Manifold
Figure 4.4 Before and After Modication
Setscrew
After rotating 180°
Manifold
F0404.ai

4.5 Rotating Transmitter Section

The transmitter section can be rotated approximately 360° (180° to either direction or 360° to one direction from the original position at shipment, depending on the conguration of the instrument.) It can be xed at any angle within above range.
1) Remove the two setscrews that fasten the transmitter section and capsule assembly, using the Allen wrench.
2) Rotate the transmitter section slowly and stop it at designated position.
3) Tighten the two setscrews to a torque of 1.5 N·m.
IMPORTANT
Do not rotate the transmitter section more than the above limit.
Vertical impulse piping type
Pressure-detector section
Horizontal impulse piping type
Transmitter section
Figure 4.5 Rotating Transmitter Section
(Left Side High Pressure Type)
Stopper
Rotate 0 to ±180° segments
Conduit connection
Transmitter section
Conduit connection
Rotate 0 to ±180° segments
Zero-adjustment screw
Pressure-detector section

4.6 Changing the Direction of Integral Indicator

IMPORTANT
Always turn OFF power, release pressure and remove a transmitter to non-hazardous area before disassembling and reassembling an indicator.
F0405.ai
An integral indicator can be installed in the following three directions. Follow the instructions in section
8.4 for removing and attaching the integral indicator.
F0406.ai
Figure 4.6 Integral Indicator Direction
<5. Installing Impulse Piping>

5. Installing Impulse Piping

5-1

5.1 Process Piping Installation Precautions

The manifold contains a small-bore orice. For the transmitter of a high pressure connection right side, the orice is placed facing such a direction as to enable normal ow measurement when uid is owed from right to left (as viewed from the front). If the orice is removed from the manifold, it must be replaced facing the correct direction. (For disassembly and reassembly procedures, see Subsection 8.4.4)
Pay careful attention to the following points when routing the process piping and connection the process piping to the transmitter.

5.1.1 Connecting Process Piping to the Transmitter

(1) Conrming the Process Fluid Flow
Direction (Figure 5.1)
The mark “ ” on the manifold indicates the direction in which the process uid is owed (from right to left). When connecting the process piping to the process connector, conrm the process uid ow direction.
Manifold
Flow direction(from right to left)
Process connection (outflow side)
Orifice name plate
Process connection
(inflow side)
(2) Tightening the Process Connector
Mounting Bolts
The transmitter is shipped with the process connector mounting bolts only loosely tightened. After connecting the process piping, tighten these bolts uniformly to prevent leaks with a torque of 39 to 49 N·m {4 to 5 kgf·m}.
(3) Removing the Process Connector Port
Dustproof Cap
The process connector port threads are covered with a plastic cap to exclude dust. This cap must be removed before connecting the piping. (Be careful not to damage the threads when removing this cap. Never insert a screwdriver or other tool between the cap and port threads to remove the cap.)

5.1.2 Routing the Process Piping

(1) Relationship between Process Fluid
and Manifold Locations (For the vertical impulse piping type)
If condensate (or gas) generated in the process piping were allowed to accumulate, then it would be necessary to remove it periodically by opening the drain (or vent) plug. However, this would generate a transient disturbance in the pressure measurement. Therefore, the process piping must be routed so that any condensate (or gas) generated in the process piping will not accumulate in the pressure­sensing assembly of the transmitter.
Bolt
Process connector (low pressure side)
Figure 5.1 Manifold and Flow Direction Indication
Process connector (high pressure side)
F0501.ai
NOTE
• If the process uid is a gas, then as a rule the manifold must be located at the downside of the pressure-sensing assembly. (Figure 5.2)
• If the process uid is a liquid, then as a rule the manifold must be located at the upside of the pressure-sensing assembly. (Figure 5.3)
(2) Pipe Size for Process Piping
Use a 15 mm (1/2-inch) pipe for process piping connection to the process connector.
<5. Installing Impulse Piping>
5-2
(3) Preventing Freezing
If there is any risk that the process uid in the transmitter pressure-sensing assembly could freeze or solidify, use a steam jacket or heater to maintain the temperature of the uid.
Manifold
Figure 5.2 Manifold Location at the Downside (for
Gas Flow Measurement)
Manifold
Figure 5.3 Manifold Location at the Upside (for
Liquid Flow Measurement)
F0502.ai
F0503.ai

5.2 Process Piping Connection Examples

Figure 5.4 shows examples of typical process piping connections. Before connecting the transmitter to the process, study the transmitter installation location, the process piping layout, and the characteristics of the process uid (corrosiveness, toxicity, ammability, etc.), in order to make appropriate changes and additions to the connection congurations.
• A variety of process piping-mounted stop valves are available according to the type of connection (anged, screwed, welded), construction (globe, gate, or ball valve), temperature and pressure. Select the type of valve most appropriate for the application.
Gas flow measurement
Union or flange
Stop valve
Manifold
Process piping
Liquid flow measurement
Manifold
Union or flange
Stop valve
Process piping
F0504.ai
Figure 5.4 Process Piping Connection Examples
Note the following points when referring to these piping examples.
• The high pressure connecting port on the transmitter is shown on the right (as viewed from the front).
• The transmitter process piping connection is shown for a vertical impulse piping connection conguration in which the direction of process ow is from right to left.
• The process piping material used must be compatible with the process pressure, temperature, and other conditions.
<6. Wiring>

6. Wiring

6-1

6.1 Wiring Precautions

IMPORTANT
• Lay wiring as far as possible from electrical noise sources such as large capacity transformers, motors, and power supplies.
• Remove the electrical connection dust cap before wiring.
• All threaded parts must be treated with waterproong sealant. (A non-hardening silicone group sealant is recommended.)
• To prevent noise pickup, do not pass signal and power cables through the same ducts.
• Explosion-protected instruments must be wired in accordance with specic requirements (and, in certain countries, legal regulations) in order to preserve the effectiveness of their explosion-protected features.
• The terminal box cover is locked by an Allen head bolt (a shrouding bolt) on ATEX ameproof type transmitters. When the shrouding bolt is driven clockwise using an Allen wrench, it goes in. The cover lock can then be released and the cover can be opened by hand. See subsection 8.4 “Disassembly and Reassembly” for details.
• Plug and seal an unused conduit connection.

6.3 Connections of External Wiring to Terminal Box

6.3.1 Power Supply Wiring Connection

Connect the power supply wiring to the SUPPLY + and – terminals. When /AL is specied, also refer to subsection 6.3.5.
+
Power supply
Figure 6.1 Power Supply Wiring Connection

6.3.2 External Indicator Connection

Available only when /AL is not specied.
Connect wiring for external indicators to the CHECK + and – terminals.
(Note) Use a external indicator whose internal resistance is 10 Ω
or less.
Power supply
+
Transmitter terminal box
Figure 6.2 External Indicator Connection
Transmitter terminal box
External indicator
PULSE
SUPPLY
CHECK ALARM
PULSE
SUPPLY
CHECK ALARM
F0601.ai
F0602.ai

6.2 Selecting the Wiring Materials

(a) Use stranded leadwires or cables which are
the same as or better than 600 V grade PVC insulated wire (JIS C3307) or its equivalent.
(b) Use shielded wires in areas that are susceptible
to electrical noise.
(c) In areas with higher or lower ambient
temperatures, use appropriate wires or cables.
(d) In environment where oils, solvents, corrosive
gases or liquids may be present, use wires or cables that are resistant to such substances.
(e) It is recommended that crimp-on solderless
terminal lugs (for 4 mm screws) with insulating sleeves be used for leadwire ends.

6.3.3 Communicator Connection

Connect the BT200 or HART Communicator to the SUPPLY + and – terminals. (Use hooks.)
Transmitter terminal box
PULSE
SUPPLY
CHECK ALARM
BT200
Figure 6.3 BT200 Connection
Power supply
+
Ignore the polarity since the BT200 is AC-coupled to the terminal box.
F0603.ai
<6. Wiring>
6-2

6.3.4 Check Meter Connection

Available only when /AL is not specied.
Connect the check meter to the CHECK + and – terminals. (Use hooks.)
• A 4 to 20 mA DC output signal from the CHECK + and – terminals.
(Note) Use a check meter whose internal resistance is 10 Ω or
less.
Check meter
Transmitter terminal box
PULSE
SUPPLY
CHECK ALARM
Figure 6.4 Check Meter Connection
Power supply
+
F0604.ai

6.3.5 Status Output Connection

When option code /AL is specied, connect the external wiring as shown in Figure 6.5.
To congure and activate the process alarm function and status output, it is necessary to set some parameters. Refer to each communication manual for procedures.
Transmitter
terminal box
PULSE
SUPPLY
CHECK ALARM
Shielded cable
24V DC
+
250
Distributor
(1) General-use Type and Flameproof Type
Hazardous Location Nonhazardous Location
Transmitter terminal box
Distributor (Power supply unit)
PULSE
SUPPLY
CHECK ALARM
Receiver instrument
F0606.ai
Figure 6.6 Connection between Transmitter and
Distributor
(2) Intrinsically Safe Type
With the intrinsically safe type, a safety barrier must be included in the loop.
Hazardous Location Nonhazardous Location
Transmitter terminal box
Distributor (Power supply unit)
PULSE
SUPPLY
CHECK ALARM
Receiver instrument
Safety barrier
F0607.ai
Figure 6.7 Connection between Transmitter and
Distributor

6.4.2 Wiring Installation

Magnetic
External power supply 30V DC, 120mA max
Use two-wire separately shielded cables.
AC power supply
valve
F0605.ai
Figure 6.5 Status Output Connection

6.4 Wiring

6.4.1 Loop Conguration
Since the DPharp uses a two-wire transmission system, signal wiring is also used as power wiring.
DC power is required for the transmitter loop. The transmitter and distributor are connected as shown below.
For details of the power supply voltage and load resistance, see section 6.6; for communications line requirements, see section 9.1.
(1) General-use Type and Intrinsically Safe
Type
With the cable wiring, use a metallic conduit or waterproof glands.
• Apply a non-hardening sealant to the terminal box connection port and to the threads on the exible metal conduit for waterproong.
Flexible metal conduit
Apply a non-hardening
Wiring metal conduit
Tee
Drain plug
Figure 6.8 Typical Wiring Using Flexible Metal
Conduit
sealant to the threads for waterproofing.
F0608.ai
<6. Wiring>
6-3
(2) Flameproof Type
Wire cables through a ameproof packing adapter, or use a ameproof metal conduit.
Wiring cable through ameproof packing
adapter.
• Apply a non-hardening sealant to the terminal box connection port and to the threads on the ameproof packing adapter for waterproong.
Flameproof packing adapter
Flexible metal conduit
Wiring metal conduit
Tee
Drain plug
Apply a non-hardening sealant to the threads for waterproofing.
F0609.ai
Figure 6.9 Typical Cable Wiring Using Flameproof
Packing Adapter
Flameproof metal conduit wiring
• A seal tting must be installed near the terminal box connection port for a sealed construction.
• Apply a non-hardening sealant to the threads of the terminal box connection port, exible metal conduit and seal tting for waterproong.
Non-hazardous area
Hazardous area
Flameproof heavy-gauge steel conduit
Tee
Drain plug
Figure 6.10 Typical Wiring Using Flameproof Metal
Conduit
Gas sealing device
Flameproof flexible metal conduit
Apply a non-hardening sealant to the threads of these fittings for waterproofing
Seal fitting
After wiring, impregnate the fitting with a compound to seal tubing.
F0610.ai

6.5 Grounding

Grounding is always required for the proper operation of transmitters. Follow the domestic electrical requirements as regulated in each country. For a transmitter with a built-in lightning protector, grounding should satisfy ground resistance of 10Ω or less.
Ground terminals are located on the inside and outside of the terminal box. Either of these terminals may be used.
PULSE
SUPPLY
CHECK
Ground terminal (inside)
Ground terminal (outside)
Figure 6.11 Ground Terminals
ALARM
F0611.ai

6.6 Power Supply Voltage and Load Resistance

When conguring the loop, make sure that the external load resistance is within the range in the gure below.
(Note) In case of an intrinsically safe transmitter, external load
resistance includes safety barrier resistance.
600
External
load
resistance
R (Ω)
250
R=
E–10.5
0.0244
Communication
applicable range
BRAIN and HART
0 10.5 16.6 25.2 42
Power supply voltage E (V DC)
Figure 6.12 Relationship between Power Supply
Voltage and External Load Resistance
F0612.ai
<7. Operation>

7. Operation

7-1

7.1 Preparation for Starting Operation

The Model EJ115 low ow transmitter measures the ow rates of liquids and gases. This section describes the operation procedure for the EJ115 as shown in Figure 7.1 (vertical impulse piping type, high-pressure connection: right side) when measuring a liquid ow rate.
(a) Follow the procedures below to introduce
process pressure into the transmitter.
1) Open the stop valve on the downstream side.
2) Gradually open the stop valve on the upstream side to introduce process uid into the transmitter pressure-detector section. This will cause process uid to ow into the orice built in the manifold, and apply ow­dependent differential pressure to the high and low pressure sides of the transmitter.
3) Conrm that there are no pressure leaks in the stop valves on the upstream and downstream sides, process piping connection or transmitter, etc.
(b) Venting Gas from the Transmitter Pressure-
detector Section.
Since the piping in the example of Figure 7.1
is constructed to be self-venting, no venting operation is required. If it is not possible to make the piping self-venting, refer to Subsection 7.6 for instructions.
(c) Turn ON power and connect the BT200. Open the terminal box cover, and connect the
BT200 to the SUPPLY + and – terminals.
(d) Using the BT200, conrm that the transmitter is
operating properly. Check parameter values or change the setpoints as necessary.
If the transmitter is equipped with an integral
indicator, its indication can be used to conrm that the transmitter is operating properly.
Stop valve(downstream side)
Manifold
Stop valve
(upstream side)
Conrming that Transmitter is Operating
Properly
Using the BT200
• If the wiring system is faulty, ‘communication error’ appears on the display.
• If the transmitter is faulty, ‘SELF CHECK ERROR’ appears on the display.
PARAM C60:SELF CHECK ERROR
communication error
DATA DIAG PRNT ESC
Communication error (Faulty wiring)
Figure 7.2 BT200 Display
Self-diagnostic error (Faulty transmitter)
F0702.ai
Using the integral indicator
• If the wiring system is faulty, the display stays blank.
• If the transmitter is faulty, an error code is displayed.
Self-diagnostic error on the integral indicator (Faulty transmitter)
Figure 7.3 Integral Indicator with Error Code
F0703.ai
NOTE
If any of the above errors are indicated on the display of the integral indicator or the communicator, refer to subsection 8.5.3 for the corrective action.
Figure 7.1 Liquid Flow Measurement
F0701.ai
<7. Operation>
F0704.ai
7-2
Verify and Change Transmitter
Parameter Setting and Values
The parameters related to the following items are set at factory as specied in order.
• Calibration range
• Integral indicator display
• Output mode
• Software damping (optional)
Other parameters like following are shipped with the default setting.
• Low-cut
• Process alarm setting
• Static pressure range
• Signal characterizer
• Write protection
To conrm or change the values, see IM 01C25T01­06EN or 01C25T03-01E.

7.2 Zero Point Adjustment

After completing preparations for operating the transmitter, adjust the zero point.
Zero point adjustment can be done by turning the transmitter’s zero-adjustment screw or by using the communicator. This section describes the procedure for the zero-adjustment screw. For the communicator procedure, see the communication manual.
IMPORTANT
Do not turn off the power to the transmitter immediately after performing a zero point adjustment. Powering off within 30 seconds of performing this procedure will return the zero point to its previous setting.
NOTE
Before performing this adjustment, make sure that the external zero adjustment function has NOT been disabled by a parameter setting.
Adjusting Zero Point for Differential
Pressure Transmitters
Before adjusting zero point, make sure that the equalizing valve is open.
Zero-adjustment screw cover
Figure 7.4 External Zero Adjustment Screw
The zero-adjustment screw is located inside the cover. Use a slotted screwdriver to turn the zero­adjustment screw. Equalize the transmitter, then turn the screw clockwise to increase the output or counterclockwise to decrease the output. The zero point adjustment can be made with a resolution of 0.01% of the setting range. The degree of zero adjustments varies with the screw turning speed; turn the screw slowly to make a ne adjustment, quickly to make a rough adjustment.

7.3 Starting Operation

After completing the zero point adjustment, follow the procedure below to start operation.
1) Open the stop valve on the upstream side.
2) Gradually open the stop valve on the downstream side. This places the transmitter in an operational condition.
3) Conrm the operating status. If the output signal exhibits wide uctuations (hunting) due to periodic variation in the process pressure, use BT200 to dampen the transmitter output signal. Conrm the hunting using a receiving instrument or the integral indicator, and set the optimum damping time constant.
4) After conrming the operating status, perform the following.
To check the output signal, use a digital multimeter, calibrator, or communicator.
<7. Operation>
7-3
IMPORTANT
• Remove the BT200 from the terminal box, and conrm that none of the terminal screws are loose.
• Close the terminal box cover and the amplier cover. Screw each cover in tightly until it will not turn further.
• There are two covers that must be locked on the ATEX Flameproof type transmitters. An Allen head bolts (shrouding bolts) are provided under edge of the each cover for locking. When a shrouding bolts are driven counterclockwise by an Allen wrench, it is coming out and locks up a cover. (See section 8.4) After locking, the covers should be conrmed not to be opened.
• Tighten the zero-adjustment cover mounting screw to x the cover in position.

7.4 Shutting Down Operation

Shut down the transmitter operation as follows.
1) Turn off the power.
2) Close the stop valves on the up and downstream sides.
NOTE
Whenever shutting down the transmitter for a long period, remove any process fluid from the transmitter pressure-detector section.
7.5 Transmitter Measurement
Range (Determining Differential Pressure Range)
The following describes the procedure for calculating the differential pressure range and the calculation example in low ow measurement.

7.5.1 Determining the Differential Pressure Range

Use the following procedures to determine a differential pressure range according to the uid conditions being measured.
(a) Calculate a water or air equivalent ow from the
ow of the uid being measured (100% ow).
Equivalent Water Flow Calculation
Qw = 0.03162 . Qf . ρf (1)
Where, Qw: Water equivalent volumetric ow
(m3/h) at 4°C, 1 atm
Qf: Volumetric liquid ow (m3/h)
at operating conditions (t°C, p kPa)
ρf: Specic liquid density (kg/m3)
at operating conditions (t°C, p kPa)
Equivalent Air Flow Calculation
Qo = 0.5356 . Qn ρn .
Where, Qo: Air equivalent volumetric ow at 0°C,
1 atm (Nm3/h)
Qn: Volumetric gas ow at 0°C,
1 atm (Nm3/h)
ρn: Specic gas density at 0°C,
1 atm (kg/Nm3)
Zn: Compression factor of gas at 0°C,
1 atm
Zf: Compression factor of gas at
operations conditions (t°C, p kPa)
(b) Obtain a differential pressure from the
above equivalent water or air ow using the nomograph shown in Figure 7.5.1 or 7.5.2. In this procedure, multiply Qw or Qo by 1000/60 to convert the ow unit into liter/min.
(c) Select an orice bore, taking into considerations
pressure loss, etc.
(d) As necessary, calculate Reynolds number at
normal ow rate and correct the differential pressure obtained from the procedure (b).
273.15 + t
101.325+ pZfZn
.
(2)
Conversion factor in pressure unit:
1 Pa = 1.01972×10-1 mmH2O 1 mmH2O = 9.80665 Pa 1 atm = 1.01325×102 kPa
<7. Operation>
7-4
Reynolds Number Calculation
Re = 354 (3)
Where, Re: Reynolds number at normal ow rate W: Weight ow at normal ow rate (kg/h)
D: Orice bore (mm) µ: Viscosity (mPa·s)
W
D.µ
(Note)
Note: Determination of W
· For liquid, W=Qf·ρf
· For gas, W=Qn·ρn
Differential Pressure Correction using
Reynolds Number
2
1
.
P =
Kaf/Ka
Where, ∆P: Corrected differential pressure ∆P0: Differential pressure obtained from
Kaf/ka: Correction factor obtained from
For details concerning determination of differential pressure correction using Reynolds number, pressure loss, etc., refer to TI 01C20K00-01E.
∆P
0
procedure (b)
Figure 7.5.3

7.5.2 Example of Calculation

Fluid: N2 gas (Nitrogen gas) Flow range: 0 to 25 Nm3/h
(ow rate at 0°C, 1 atm) Normal ow rate: 18 Nm3/h Specic density: 1.251 kg/Nm3
(specic density at 0°C, 1 atm) Temperature: 30°C Pressure: 100 kPa Viscosity: 0.018 mPa·s
From Equation (2), air equivalent volumetric ow Qo is:
Qo= 0.5356 × 25 1.251 ×
A differential pressure range of 0 to 2400 mmH2O is obtained from Figure 7.5.2 applying an orice bore of 6.350 mm (where, Zf/Zn=1 is assumed).
From Equation (3), Reynolds number at normal ow rate Re is:
Re = 354 × = 6.97 × 10
18 × 1.251
6.35 × 0.018
Since the correction factor (1.00) is constant at this Reynolds number, no differential pressure correction is required. Consequently, the differential pressure range is determined as 0 to 2400 mmH2O.
273.15 + 30
101.325 + 100
= 18.38 Nm
3
/h = 306.3 Nl/min
4
0.05
200
100
50
Differential
Pressure
(kPa)
10
5
1
0.01 0.05 0.1 0.5 1 5 10 40
Figure 7.5.1 Relationship between Equivalent Water Flow and Differential Pressure
0.508 0.864 1.511 2.527 4.039 6.350
0.1 0.5 1 5 10 40
Equivalent water flow(liter/min at 0°C, 1 atm)
200
100
50
10
5
1
F0705.ai
<7. Operation>
0.5 1 5 10 50 100 500 1000
200
7-5
200
100
50
Differential
Pressure
(kPa)
0.508 0.864 1.511 2.527 4.039 6.350
10
5
1
0.5 1 5 10 50 100 500 1000
Equivalent air flow(liter/min at 0°C, 1 atm)
Figure 7.5.2 Relationship between Equivalent Air Flow and Differential Pressure
100
50
10
5
1
F0706.ai
1.00
Correction
0.95 E
Factor
(Kaf/Ka)
0.90
0.85
0.80
0.75
86 5 862 3 4 5 862 3 42 3
4 45
10
F
D
C
B
A
2
10
3
A: F9340NL (Ø0.508) B: F9340NM (Ø0.864) C: F9340NN (Ø1.511) D: F9340NP (Ø2.527) E: F9340NQ (Ø4.039) F: F9340NR (Ø6.350)
10
Reynolds number(Re)
Figure 7.5.3 Relationship between Reynolds Number and Correction Factor
4
5 10
5
86
F0707.ai
<7. Operation>
7-6
7.6 Venting or Draining Transmitter Pressure­detector Section
Since this transmitter is designed to be self­draining and self-venting with vertical impulse piping connections, neither draining nor venting will be required if the impulse piping is congured appropriately for self-draining or self-venting operation.
If condensate (or gas) collects in the transmitter pressure-detector section, the measured pressure may be in error. If it is not possible to congure the piping for self-draining (or self-venting) operation, you will need to loosen the drain (vent) screw on the transmitter to completely drain (vent) any stagnated liquid (gas).
However, since draining condensate or bleeding off gas gives the pressure measurement disturbance, this should not be done when the loop is in operation.

7.6.2 Venting Gas

1) Gradually open the vent screw to vent gas from the transmitter pressure-detector section. (See Figure 7.6.2.)
2) When the transmitter is completely vented, close the vent screw.
3) Tighten the vent screw to a torque of 10 N·m {1kgf·m}.
Vent screw
Vent screw
When you loosen the vent screw, the gas escapes in the direction of the arrow.
Figure 7.6.2 Venting the Transmitter
F0709.ai
WARNING
Since the accumulated liquid (or gas) may be toxic or otherwise harmful, take appropriate care to avoid contact with the body, or inhalation of vapors.

7.6.1 Draining Condensate

1) Gradually open the drain screw or drain plug and drain the transmitter pressure-detector section. (See Figure 7.6.1.)
2) When all accumulated liquid is completely removed, close the drain screw or drain plug.
3) Tighten the drain screw to a torque of 10 N·m {1kgf·m}, and the drain plug to a torque of 34 to 39 N·m {3.5 to 4 kgf·m}.

7.7 Setting the Range Using the Range-setting Switch

WARNING
The range setting switch must not be used in the hazardous area. When it is necessary to use the switch, operate it in a non-hazardous location.
When pressure is applied to the transmitter, the low­and high-limit values for the measurement range (LRV and URV) can be changed (re-ranged) using the range-setting switch (push-button) located on the optional integral indicator plate and the external zero adjustment screw. This procedure does not require use of the communicator. However, changes in the scale range and engineering unit display settings for the integral indicator require use of the communicator.
Follow the procedure below to change the LRV and URV settings.
Drain screw
Drain plug
When you loosen the drain screw or drain plug, the accumulated loquid will be expelled in the direction on th earrow.
Figure 7.6.1 Draining the Transmitter
F0708.ai
<7. Operation>
7-7
[Example]
Rerange LRV to 0 and URV to 3 MPa.
1) Connect the transmitter and apparatus as shown in Figure 8.1 and warm it up for at least ve minutes.
2) Press the range-setting push-button.
The integral indicator then displays “LRV.SET.”
3) Apply a pressure of 0 kPa (atmospheric pressure) to the transmitter.
(Note 1)
4) Turn the external zero-adjustment screw in the desired direction. The integral indicator displays the output signal in %.
(Note 2)
5) Adjust the output signal to 0% (1 V DC) by rotating the external zero-adjustment screw. Doing so completes the LRV setting.
6) Press the range-setting push-button. The integral indicator then displays “URV.SET.”
7) Apply a pressure of 3 MPa to the transmitter.
(Note 1)
8) Turn the external zero-adjustment screw in the desired direction. The integral indicator displays the output signal in %.
(Note 2)
9) Adjust the output signal to 100% (5 V DC) by rotating the external zero-adjustment screw. Doing so completes the URV setting.
10) Press the range-setting push-button. The transmitter then switches back to the normal operation mode with the measurement range of 0 to 3 MPa.
IMPORTANT
• Do not turn off the power to the transmitter immediately after completion of the change in the LRV and/or URV setting(s). Note that powering off within thirty seconds after setting will cause a return to the previous settings.
• Changing LRV automatically changes URV to the following value.
URV=previous URV+(new LRV–previous LRV)
• If the range-setting push-button and external zero-adjustment screw are not touched during a range-change operation, the transmitter automatically switches back to the normal operation mode.
Integral indicator
Figure 7.7 Range-setting Switch
Note 1: Use a thin bar which has a
blunt tip, e.g., a hexagonal wrench, to press the range-setting push-button.
Note 2: The push-button is located
in either lower right or lower left portion of the LCD indicator.
Range-setting switch (Push-button)
F0710.ai
Note 1: Wait until the pressure inside the pressure-detector
section has stabilized before proceeding to the next step.
Note 2: If the pressure applied to the transmitter exceeds the
previous LRV (or URV), the integral indicator may display error number “AL.30” (In this case, the output signal percent and “AL.30” are displayed alternately every two seconds). Although “AL.30” is displayed, you may proceed to the next step. However, should any other error number be displayed, take the appropriate measure in reference to , “Errors and Countermeasures” in each communication manual.
<8. Maintenance>

8. Maintenance

8-1

8.1 Overview

WARNING
Since the accumulated process uid may be toxic or otherwise harmful, take appropriate care to avoid contact with the body or inhalation of vapors when draining condensate or venting gas from the transmitter pressure-detector section and even after dismounting the instrument from the process line for maintenance.
Maintenance of the transmitter is easy due to its modular construction. This chapter describes the procedures for calibration, adjustment, and the disassembly and reassembly procedures required for component replacement.
Transmitters are precision instruments. Please carefully and thoroughly read the following sections for information on how to properly handle them while performing maintenance.
IMPORTANT
• As a rule, maintenance of this transmitter should be done in a shop that has all the necessary tools.
• The CPU assembly contains sensitive parts that can be damaged by static electricity. Take precautions such as using a grounded wrist strap when handling electronic parts or touching the board circuit patterns. Also be sure to place the removed CPU assembly into a bag with an antistatic coating.

8.3 Calibration

Use the procedure below to check instrument operation and accuracy during periodic maintenance or troubleshooting.
1) Connect the instruments as shown in gure 8.1 and warm up the instruments for at least ve minutes.
IMPORTANT
• Do not perform the calibration procedure until the transmitter is at room temperature.
• To adjust the transmitter for highest accuracy, make adjustments with the power supply voltage and load resistance including leadwire resistances set close to the conditions under which the transmitter is installed.
• If the measurement range 0% point is 0 kPa or shifted in the positive direction (suppressed zero), the reference pressure should be applied as shown in the gure. If the measurement range 0% point is shifted in the negative direction (elevated zero), the reference pressure should be applied using a vacuum pump.
2) Apply reference pressures of 0%, 50%, and 100% of the measurement range to the transmitter. Calculate the errors (differences between digital voltmeter readings and reference pressures) as the pressure is increased from 0% to 100% and is decreased from 100% to 0%, and conrm that the errors are within the required accuracy.

8.2 Calibration Instruments Selection

Table 8.1 lists the instruments that can be used to calibrate a transmitter. When selecting an instrument, consider the required accuracy level. Exercise care when handling these instruments to ensure they maintain the specied accuracy.
<8. Maintenance>
Table 8.1 Instruments Required for Calibration
Name Yokogawa-recommended Instrument Remarks
Power supply Model SDBT or SDBS distributor 4 to 20 mA DC signal Load resistor Model 2792 standard resistor [250 Ω ±0.005%, 3 W]
Load adjustment resistor [100 Ω ±1%, 1 W]
Voltmeter Model 2501 A digital multimeter
Accuracy (10V DC range): ±(0.002% of rdg + 1 dgt)
Digital manometer
Model MT220 precision digital manometer
1) For 10 kPa class
Accuracy: ±(0.015% of rdg + 0.015% of F.S.). . . . for 0 to 10 kPa
Select a manometer having a pressure range close to that of the transmitter.
±(0.2% of rdg + 0.1% of F.S.). . . . . . . . for -10 to 0 kPa
2) For 130 kPa class
Accuracy: ±0.02% of rdg. . . . . . . . . . . . . . . . . . . . for 25 to 130 kPa
±5digits. . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 25 kPa
±(0.2% of rdg + 0.1% of F.S.). . . . . . . . for -80 to 0 kPa
3) For 700 kPa class
Accuracy: ±(0.02% of rdg + 3digits) . . . . . . . . . . . for 100 to 700 kPa
±5 digits . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 100 kPa
±(0.2% of rdg + 0.1% of F.S.). . . . . . . . for -80 to 0 kPa
4) For 3000 kPa class
Accuracy: ±(0.02% of rdg + 10 digits). . . . . . . . . . for 0 to 3000 kPa
±(0.2% of rdg + 0.1% of F.S.). . . . . . . . for -80 to 0 kPa
5) For 130 kPa abs class
Accuracy: ±(0.03% of rdg + 6 digits). . . . . . . . . . . for 0 to 130 kPa abs
Pressure generator
Model 7674 pneumatic pressure standard for 200 kPa {2 kgf/cm2}, 25 kPa {2500 mmH2O}
Requires air pressure supply.
Accuracy: ±0.05% of F.S.
Dead weight gauge tester 25 kPa {2500 mmH2O}
Accuracy: ±0.03% of setting
Select the one having a pressure range close to that of the transmitter.
Pressure source
Model 6919 pressure regulator (pressure pump)
Pressure range: 0 to 133 kPa {1000 mmHg}
Prepare the vacuum pump for negative pressure ranges.
Note: The above table contains the instruments capable of performing calibration to the 0.2% level. Since special maintenance and
management procedures involving traceability of each instrument to higher-level standards are required for calibration to the 0.1% or higher level, there may be difculties in calibration to this level in the eld. For calibration to the 0.1% level, contact Yokogawa representatives from which the instrument was purchased or the nearest Yokogawa ofce.
8-2
Using pressure generator
Low pressure side open to atmosphere
Supply pressure
Pressure generator
P
Reference pressure
High pressure side High pressure side
Load resistance,
Load adjusting resistance,
100Ω
250Ω
RRc
V
Digital voltmeter
Figure 8.1 Instrument Connections (EJX110A)
Using pressure source with manometer
Low pressure side open to atmosphere
Power supply E
Pressure source
Model MT220
P
precision digital manometer
Reference pressure
Load resistance,
Load adjusting resistance,
100Ω
250Ω
RRc
V
Digital voltmeter
Power supply E
F0801.ai
<8. Maintenance>
8-3

8.4 Disassembly and Reassembly

This section describes procedures for disassembly and reassembly for maintenance and component replacement.
Always turn OFF power and shut off and release pressures before disassembly. Use proper tools for all operations. Table 8.2 shows the tools required.
Table 8.2 Tools for Disassembly and Reassembly
Tool Quantity Remarks
Phillips screwdriver
Slotted screwdriver
Allen wrenches 3 JIS B4648
Wrench 1 Width across ats, 17 mm Torque wrench 1 Adjustable
wrench Socket wrench 1 Width across ats, 16 mm Socket driver 1 Width across ats, 5.5 mm Tweezers 1
1 JIS B4633, No. 2
1
One each, nominal 3, 4 and
2.5 mm Allen wrenches
1
CAUTION
Precautions for ATEX Flameproof Type Transmitters
• Flameproof type transmitters must be, as a rule, removed to a non-hazardous area for maintenance and be disassembled and reassembled to the original state.
• On the ameproof type transmitters the two covers are locked, each by an Allen head bolt (shrouding bolt). When a shrouding bolt is driven clockwise by an Allen wrench, it is going in and cover lock is released, and then the cover can be opened.
When a cover is closed it should be locked
by a shrouding bolt without fail. Tighten the shrouding bolt to a torque of 0.7 N·m.
Shrouding Bolt

8.4.1 Replacing the Integral Indicator

CAUTION
Cautions for Flameproof Type Transmitters
Users are prohibited by law from modifying the construction of a ameproof type transmitter. This would invalidate the agency approval for the use of the transmitter in a rated area. It follows that the user is prohibited from using a ameproof type transmitter with its integral indicator removed, or from adding an integral indicator to a transmitter. If such modication is absolutely required, contact Yokogawa.
This subsection describes the procedure for replacing an integral indicator. (See gure 8.3)
■ Removing the Integral Indicator
1) Remove the cover.
2) While supporting the integral indicator with one hand, loosen its two mounting screws.
3) Dismount the LCD board assembly from the CPU assembly.
When doing this, carefully pull the LCD board
assembly straight forward so as not to damage the connector pins between it and the CPU assembly.
■ Attaching the Integral Indicator
1) Align both the LCD board assembly and CPU assembly connectors and engage them.
2) Insert and tighten the two mounting screws.
3) Replace the cover.
Output terminal cable
Press forward
Slide switch
Integral indicator
Boss
CPU assembly
Bracket (for zero-adjustment screw pin)
LCD board assembly
Mounting screw
Amplifier Cover
Zero­adjustment screw
Zero-adjustment screw pin
Shrouding Bolt
Figure 8.2 Shrouding Bolts
F0802.ai
F0803.ai
Figure 8.3 Removing and Attaching LCD Board
Assembly and CPU Assembly
<8. Maintenance>
8-4

8.4.2 Replacing the CPU Board Assembly

This subsection describes the procedure for replacing the CPU assembly. (See gure 8.3)
■ Removing the CPU Assembly
1) Remove the cover. If an integral indicator is mounted, refer to subsection 8.4.1 and remove the indicator.
2) Turn the zero-adjustment screw to the position (where the screw head slot is horizontal) as shown in gure 8.3.
3) Disconnect the output terminal cable (cable with brown connector at the end). When doing this, lightly press the side of the CPU assembly connector and pull the cable connector to disengage.
4) Use a socket driver (width across ats, 5.5mm) to loosen the two bosses.
5) Carefully pull the CPU assembly straight forward to remove it.
6) Disconnect the at cable (cable with white connector at the end) that connects the CPU assembly and the capsule.
NOTE
NOTE
Conrm that the zero-adjustment screw pin is placed properly in the groove on the bracket prior to tightening the two bosses. If it is not, the zero­adjustment mechanism will be damaged.
5) Replace the cover.

8.4.3 Replacing the Process Connector Gaskets

This subsection describes process connector gasket replacement. (See Figure 8.4.)
(a) Loosen the two bolts, and remove the process
connectors. (b) Replace the process connector gaskets. (c) Remount the process connectors. Tighten the
bolts securely and uniformly with a torque of 39
to 49 N·m {4 to 5 kgf·m}, and verify that there
are no pressure leaks.
Process connector gasket
Process connector
Be careful not to apply excessive force to the CPU assembly when removing it.
■ Mounting the CPU Assembly
1) Connect the at cable (with white connector) between the CPU assembly and the capsule.
2) Connect the output terminal cable (with brown connector).
NOTE
Make certain that the cables do not get pinched between the case and the edge of the CPU assembly.
3) Align and engage the zero-adjustment screw pin with the groove on the bracket on the CPU assembly. Then insert the CPU board assembly straight onto the post in the amplier case.
4) Tighten the two bosses. If the transmitter is equipped with an integral indicator, refer to subsection 8.4.1 to mount the indicator.
Bolt
F0804.ai
Figure 8.4 Removing and Mounting the Process
Connector
8.4.4 Cleaning Manifold Assembly and Replacing Orice
This subsection describes the procedures for cleaning the manifold assembly and replacing the orice to change ow rate. (See Figure 8.5.)
■ Removing the Manifold Assembly
1) Remove the process connector as shown in
Subsection 9.4.3.
2) Remove the four bolts that connect the cover
ange with the manifold.
3) Remove the spacer, orice, and orice gasket
from inside the manifold.
4) Clean the manifold, spacer, and orice, or
replace them as necessary.
<8. Maintenance>
8-5
IMPORTANT
Exercise care as follows when cleaning the manifold assembly.
• Handle the manifold assembly with care, and be careful not to damage the inner part of the manifold, spacer, and orice. Be especially careful not to damage or distort the orice edge (orice bore).
• Do not use a chlorinated or acidic solution for cleaning.
• Rinse thoroughly with clean water after cleaning.
■ Reassembling the Manifold Assembly
1) Reassemble the orice gasket, orice, and spacer into the manifold in that order. When reassembling, refer to Figure 8.5 to ensure that they are placed in the correct direction. Replace the orice gasket with a new gasket.
2) Mount the process connector as shown in Subsection 9.4.3.
3) Mount the manifold on the cover ange with the four bolts. Tighten the four bolts uniformly to a torque of 39 to 49 N·m {4 to 5 kgf·m}. Replace the manifold gaskets with new gaskets.
4) After completing reassembly, a leak test must be performed to verify that there are no pressure leaks.
NOTE
Exercise care as follows when reassembling the manifold assembly. (See Figure 8.5.)
• Be careful not to reassemble the orice in the wrong direction. Note that the spacer is congured so that it cannot be placed in the reverse direction.
• When mounting the manifold on the cover ange, conrm the indication “ow direction” shown on the manifold surface and the high and low pressure sides of the pressure­detector section. Mount the manifold so that the upstream side of process uid ow is located at the high pressure side of the pressure-detector section.
Spacer
Orifice
Process connector gasket
Orifice gasket
Manifold gasket
Low pressure side
Figure 8.5 Manifold Assembly
Bolt
Manifold
Process connector
gasket
Cover flange
High pressure side
F0805.ai

8.4.5 Cleaning and Replacing the Capsule Assembly

This subsection describes the procedures for cleaning and replacing the capsule assembly. (See gure 8.6.)
CAUTION
Cautions for Flameproof Type Transmitters
Users are prohibited by law from modifying the construction of a ameproof type transmitter. If you wish to replace the capsule assembly with one of a different measurement range, contact Yokogawa. The user is permitted, however, to replace a capsule assembly with another of the same measurement range. When doing so, be sure to observe the following.
• The replacement capsule assembly must have the same part number as the one being replaced.
• The section connecting the transmitter and capsule assembly is a critical element in preservation of ameproof performance, and must be checked to verify that it is free of dents, scratches, and other defects.
• After completing maintenance, be sure to securely tighten the setscrews that fasten the transmitter section and pressure-detector section together.
<8. Maintenance>
8-6
■ Removing the Capsule Assembly
IMPORTANT
Exercise care as follows when cleaning the capsule assembly.
• Handle the capsule assembly with care, and be especially careful not to damage or distort the diaphragms that contact the process uid.
• Do not use a chlorinated or acidic solution for cleaning.
• Rinse thoroughly with clean water after cleaning.
1) Remove the CPU assembly as shown in subsection 8.4.2.
2) Remove the two setscrews that connect the transmitter section and pressure-detector section.
3) Remove the hexagon-head screw and the stopper.
4) Separate the transmitter section and pressure­detector section.
5) Remove the nuts from the four ange bolts.
6) While supporting the capsule assembly with one hand, remove the cover ange.
7) Remove the capsule assembly.
8) Clean the capsule assembly or replace with a new one.
■ Reassembling the Capsule Assembly
1) Insert the capsule assembly between the ange bolts, paying close attention to the relative positions of the H (high pressure side) and L (low pressure side) marks on the capsule assembly.
Replace the two capsule gaskets with new
gaskets.
2) Install the cover ange on the high pressure side, and use a torque wrench to tighten the four nuts uniformly to a torque 17 N·m (40 N·m for measurement span code F.)
3) After the pressure-detector section has been reassembled, a leak test must be performed to verify that there are no pressure leaks.
4) Reattach the transmitter section to the pressure-detector section. Reattach the stopper with the hexagon-head screw.
5) Tighten the two setscrews. (Tighten the screws to a torque of 1.5 N·m)
6) Install the CPU assembly according to subsection 8.4.2.
7) After completing reassembly, adjust the zero point and recheck the parameters.
Transmitter section
Setscrew
Nut
Capsule gasket
Flange bolt
Pressure-detector section
Cover flange
Figure 8.6 Removing and Mounting the Pressure-
detector Section
F0806.ai

8.5 Troubleshooting

If any abnormality appears in the measured values, use the troubleshooting ow chart below to isolate and remedy the problem. Since some problems have complex causes, these ow charts may not identify all. If you have difculty isolating or correcting a problem, contact Yokogawa service personnel.

8.5.1 Basic Troubleshooting

First determine whether the process variable is actually abnormal or a problem exists in the measurement system.
If the problem is in the measurement system, isolate the problem and decide what corrective action to take.
This transmitter is equipped with a self-diagnostic function which will be useful in troubleshooting, and the transmitter equipped with an integral indicator will show an alarm code as a result of self­diagnosis. See subsection 8.5.3 for the list of alarms. See also each communication manual.
<8. Maintenance>
8-7
: Areas where self-diagnostic offers support
Abnormalities appear in measurement.
YES
Inspect the
process system.
YES
Inspect receiver.
Environmental conditions
Check/correct
environmental conditions.
Check/correct operating
Is process variable
itself abnormal?
NO
Measurement system problem
Isolate problem in
measurement system.
Does problem exist in receiving instrument?
NO
Operating conditions
conditions.
Transmitter itself
Check transmitter.
F0807.ai

8.5.2 Troubleshooting Flowcharts

The following sorts of symptoms indicate that transmitter may not be operating properly. Example : • There is no output signal.
• Output signal does not change even though process variable is known to be varying.
• Output value is inconsistent with value inferred for process variable.
Connect communicator and check self-diagnostics.
Does the self-diagnostic
indicate problem location?
NO
Is power supply polarity correct?
Refer to Section 6.3 to check/correct
YES
Are power
supply voltage and load
resistance correct?
YES
Are valves opened or
closed correctly?
YES
polarity at each terminal from power supply to the terminal box.
Refer to Section 6.6 for rated voltage and load resistance.
Fully close equalizing valve, and fully open high pressure and low pressure valves.
Refer to error message summary in Subsection 8.5.3 or in each communication manual to take actions.
YES
NO
NO
NO
Figure 8.7 Basic Flow and Self-Diagnostics
Is there any pressure leak?
Fix pressure leaks, paying particular
NO
Is there
continuity through the
transmitter loop wiring?
Do the loop numbers
match?
YES
Is orifice clogged with
dust, etc?
NO
Contact Yokogawa service personnel.
attention to connections for impulse piping,pressure-detector section, etc.
Find/correct broken conductor or wiring error.
Refer to Subsection 8.4.4 to clean the manifold assembly.
YES
NO
YES
F0808.ai
<8. Maintenance>
8-8
Output travels beyond 0% or 100%.
Connect a communicator and check self-diagnostics.
Does the self-
diagnostic indicate problem
location?
Refer to error message summary in
NO
Is power supply
polarity correct?
YES
Are valves opened or
closed correctly?
YES
Is there any pressure leak?
NO
each communication manual to take actions.
Refer to Section 6.3 to check/correct polarity at each terminal from power supply to the terminal box.
Fully close equalizing valve, and fully open high pressure and low pressure valves.
Fix pressure leaks, paying particular attention to connections for impulse piping, pressure-detector section, etc.
YES
NO
NO
YES
Large output error.
Connect a communicator and check self-diagnostics.
Does the self-
diagnostic indicate problem
location?
Refer to error message summary in
NO
Are valves opened or
closed correctly?
YES
Is impulse piping
connected correctly?
YES
Are power supply
voltage and load resistance
correct?
YES
each communication manual to take actions.
Fully close equalizing valve, and fully open high pressure and low pressure valves.
Refer to individual model user manuals and connect piping as appropriate for the measurement purpose.
Refer to Section 6.6 for rated voltage and load resistance.
YES
NO
NO
NO
Is the transmitter
installed as appropriate for
the flow direction?
Refer to Subsection 5.1.1 and install
YES
Is zero point
adjusted correctly?
YES
Contact Yokogawa service personnel.
the transmitter as appropriate for the flow direction of fluid.
Adjust the zero point.
NO
NO
F0809.ai
Is transmitter
installed where there is
marked variation in
temperature?
Provide lagging and/or cooling, or allow
NO
Were appropriate
instruments used for
calibration?
YES
Is output adjusted correctly?
YES
Is orifice clogged with
dust, etc?
YES
Contact Yokogawa service personnel.
adequate ventilation.
Refer to Section 8.2 when selecting instruments for calibration.
Adjust the output.
Refer to Subsection 8.4.4 to clean the manifold assembly.
YES
NO
NO
NO
F0810.ai
<8. Maintenance>

8.5.3 Alarms and Countermeasures

Table 8.1 Alarm Message Summary
Indicator Cause
None AL. 01
CAP. ERR
Sensor problem. Outputs the signal (Hold, High, or Capsule temperature sensor
problem. Capsule EEPROM problem.
AL. 02 AMP. ERR
Amplier temperature sensor problem.
Amplier EEPROM problem. Amplier problem.
AL. 10 PRESS
AL. 11
Input is outside measurement range limit of capsule.
Static pressure exceeds limit. Continues to operate and output.
ST. PRSS AL. 12
CAP. TMP AL. 13
AMP. TMP AL. 30
RANGE AL. 31
SP. RNG AL. 35 *
P. HI AL. 36 *
Capsule temperature is outside range (–50 to 130°C).
Amplier temperature is outside range (–50 to 95°C)
Output is outside upper or lower range limit value.
Static pressure exceeds specied range.
1
Input pressure exceeds specied threshold.
1
P. LO AL. 37 *
SP. HI AL. 38 *
1
Input static pressure exceeds specied threshold.
1
SP. LO AL. 39 *
TMP. HI AL. 40 *
1
Detected temperature exceeds specied threshold.
1
TMP. LO AL. 50
P. LRV
Specied value is outside of setting range.
AL. 51 P. URV
AL. 52 P. SPN
AL. 53 P. ADJ
AL. 54 SP. RNG
AL. 55 SP. ADJ
AL. 60 SC. CFG
Specied values or settings to dene signal characterizer function do not satisfy the condition.
AL. 79
Displayed value exceeds limit.
OV. DISP
Output Operation
during Error
Countermeasure
Replace capsule when error
Low) set with parameter.
keeps appearing even after restart.
Outputs the signal (Hold, High, or
Replace amplier.
Low) set with parameter.
Outputs high range limit value or low range limit value.
Check input or replace capsule when necessary.
Use heat insulation or make lagging to keep temperature within range.
Outputs high range limit value or low range limit value.
Check input and range setting, and change them as needed.
Holds output immediately before error occurred.
Continues to operate and
Check input.
output.
Holds output immediately before error occurred.
Check setting and change them as needed.
Continues to operate and output. Check input.
Continues to operate and output holding static pressure in %.
Check setting and change them as needed.
Continues to operate and output. Check input.
Check setting and change them as needed.
8-9
*1: These alarms may appear only when process alarm function is activated.
<9. General Specications>
9. General Specications
9-1
9.1 Standard Specications
Refer to IM 01C25T02-01E for FOUNDATION Fieldbus communication type and IM 01C25T04­01EN for PROFIBUS PA communication type for the items marked with “◊”.
Performance Specications
See General Specications sheet, GS 01C25K01­01EN or GS 01C31K01-01EN.
Functional Specications
Span & Range Limits
Water Equivalent Flow l/min
0.016 to 5.0 0.44 to 140
0.022 to 23.0 0.63 to 635
0.07 to 33.0 2.0 to 910
Capsule
F
M
H
Differential
Pressure Span
1 to 5 kPa
{100 to 500 mmH2O}
2 to 100 kPa
{200 to 10000 mmH2O}
20 to 210 kPa
{2000 to 21000 mmH2O}
Output “◊”
Two wire 4 to 20 mA DC output with digital communications, linear or square root programmable. BRAIN or HART FSK protocol are superimposed on the 4 to 20 mA signal. Output range: 3.6 mA to 21.6 mA Output limits conform to NAMUR NE43 can be pre-set by option C2 or C3.
Air
Equivalent
Flow Nl/min
Update Period “◊”
Differential Pressure: 45 ms Static Pressure: 360 ms
Zero Adjustment Limits
Zero can be fully elevated or suppressed, within the lower and upper range limits of the capsule.
External Zero Adjustment “◊”
External Zero is continuously adjustable with
0.01% incremental resolution of span. Re-range can be done locally using the digital indicator with range-setting switch.
Integral Indicator (LCD display)
5-digit Numerical Display, 6-digit Unit Display and Bar graph. The indicator is congurable to display one or up to four of the following variables periodically.; Differential pressure in %, Scaled Differential pressure, Differential Pressure in Engineering unit, Static Pressure in Engineering unit. See “Setting When Shipped” for factory setting.
Burst Pressure Limits (Differential pressure
transmitter part)
69 MPa (10000 psi)
Normal Operating Condition
(Selected features may affect limits.)
Ambient Temperature Limits
–40 to 85°C (–40 to 185°F) –30 to 80°C (–22 to 176°F) with LCD display
Failure Alarm “◊”
Output status at CPU failure and hardware error;
Up-scale: 110%, 21.6 mA DC or more (standard) Down-scale: –5%, 3.2 mA DC or less
Note: Applicable for Output signal code D and E
Damping Time Constant (1st order)
Amplier damping time constant is adjustable from 0 to 100.00 seconds and added to response time.
Note: For BRAIN protocol type, when amplier damping
is set to less than 0.5 seconds, communication may occasionally be unavailable during the operation, especially while output changes dynamically. The default setting of damping ensures stable communication.
Process Temperature Limits
–40 to 120°C (–40 to 248°F)
Ambient Humidity Limits
0 to 100% RH
<9. General Specications>
9-2
Working Pressure Limits (Silicone oil)
Maximum Pressure Limits
All capsules 16 MPa (2300 psi)
Minimum Pressure Limit
See graph below
100(14.5)
Working pressure kPa abs
(psi abs)
10(1.4)
2.7(0.38)
1(0.14)
Figure 9.1 Working Pressure and Process
Applicable range
-40 (-40)
0
40
(32)
(104)
Process temperature °C (°F)
Temperature
80 (176)
Atmospheric pressure
120 (248)
F0901.ai
Supply Voltage
10.5 to 42 V DC for general use and ameproof type.
10.5 to 32 V DC for lightning protector (Option code /A).
10.5 to 30 V DC for intrinsically safe, type n or non-incendive type.
Minimum voltage limited at 16.6 V DC for digital
communications, BRAIN and HART
Load (Output signal code D, E and J)
0 to 1290 Ω for operation 250 to 600 Ω for digital communication
Communication Requirements “◊”
(Safety approvals may affect electrical requirements.)
BRAIN
Communication Distance
Up to 2 km (1.25 miles) when using CEV polyethylene-insulated PVC-sheathed cables. Communication distance varies depending on type of cable used.
Supply & Load Requirements “◊” (Optional
features or approval codes may affect electrical requirements.)
With 24 V DC supply, up to a 550 Ω load can be used. See graph below.
600
E-10.5
R=
External load resistance
250
(Ω)
R
Figure 9.2 Relationship Between Power Supply
0.0244
10.5 16.6
Power supply voltage E (V DC)
Voltage and External Load Resistance
Digital
Communication
range
BRAIN and HART
25.2 42
Load Capacitance
0.22 μF or less
Load Inductance
3.3 mH or less
Input Impedance of communicating device
10 kΩ or more at 2.4 kHz.
HART
Communication Distance
Up to 1.5 km (1 mile) when using multiple twisted pair cables. Communication distance varies depending on type of cable used.
EMC Conformity Standards ,
EN61326-1 Class A, Table2 (For use in industrial locations) EN61326-2-3
F0902.ai
<9. General Specications>
Physical Specications
Wetted Parts Materials
Diaphragm, Cover Flange, Process Connector, Capsule Gasket, Vent/Drain Plug, Manifold, Orice, Spacer, and Orice gasket
Non-wetted Parts Materials
Bolting
ASTM-B7 carbon steel, 316L SST stainless steel, or ASTM grade 660 stainless steel
Housing
Low copper cast aluminum alloy with polyurethane paint or ASTM CF-8M stainless steel
Degrees of Protection
IP66/IP67, NEMA TYPE 4X
Cover O-rings
Buna-N, uoro-rubber (option)
9-3
Nameplate and tag
316SST (including /N4 wired tag)
Fill Fluid
Silicone, Fluorinated oil (option)
Weight
[Installation code 7, 8, and 9 and measurement span code M and H]
4.5 kg (9.9 lb) without integral indicator and mounting bracket. [Installation code 7, 8 and 9 and measurement span code F]
5.4 kg (11.9 lb) without integral indicator and mounting bracket.
Add 1.5 kg (3.3lb) for amplier housing code 2.
Connections
Refer to “Model and Sufx Code.”
Process Connection of Cover Flange: IEC61518
<9. General Specications>
9.2 Model and Sufx Codes
Model Sufx Codes Description
EJX115A EJA115E
Output signal
Measurement span (capsule)
Wetted parts material
Process connections
Bolts and nuts
material J . . . . . . . . . . . . . .
Installation
Amplier housing 1 . . . . . . . . . .
Electrical connection
Integral indicator
Mounting bracket
-N . . . . Always -N
00 . . . Always 00 — N. . . Always N — N. . Always N — 0 . Always 0 Optional codes
The “►” marks indicate the most typical selection for each specication. *1: Not applicable for output signal code F. *2: Not applicable for electrical connection code 0, 5, 7 and 9. *3: Material of a blind plug is aluminum alloy or 304 SST. *4: Cast version of 316 SST. Equivalent to SCS14A. *5: Hastelloy C-276 or ASTM N10276. *6: Not applicable for output signal code G. The ‘#’marks indicate the construction materials conform to NACE material recommendations per MR01-75. For the use of 316 SST material, there may be certain limitations for pressure and temperature. Please refer to NACE standards for details.
. . . . . . . . . . . . . . . . . . . . . . Low ow transmitter
-D . . . . . . . . . . . . . . . . . . . .
-E . . . . . . . . . . . . . . . . . . . .
-J . . . . . . . . . . . . . . . . . . . .
-F . . . . . . . . . . . . . . . . . . . .
4 to 20 mA DC with digital communication (BRAIN protocol) 4 to 20 mA DC with digital communication (HART protocol) 4 to 20 mA DC with digital communication (HART 5/HART 7 protocol) Digital communication (FOUNDATION Fieldbus protocol,
refer to IM 01C25T02-01E)
-G . . . . . . . . . . . . . . . . . . . .
Digital communication (PROFIBUS PA protocol,
refer to IM 01C25T04-01EN)
F . . . . . . . . . . . . . . . . . . .
M . . . . . . . . . . . . . . . . . .
H. . . . . . . . . . . . . . . . . . .
1 to 5 kPa (4 to 20 inH2O) 2 to 100 kPa (8 to 400 inH2O) 20 to 210 kPa (80 to 840 inH2O)
S . . . . . . . . . . . . . . . . . . Cover ange and process connector: ASTM CF-8M
Capsule: Hastelloy C-276 (Diaphragm) # F316L SST/316L SST (Others) Capsule gasket: Teon-coated 316L SST Drain/Vent plug: 316 SST # Orice: 316 SST # Manifold: F316 SST # Spacer: 316 SST # Orice gasket: PTFE
2 . . . . . . . . . . . . . . . .
4 . . . . . . . . . . . . . . . .
Rc1/2 female 1/2 NPT female
For Cover ange For Process connector For Manifold
SNB7 SNB7 316L SST
G. . . . . . . . . . . . . .
-2 . . . . . . . . . . .
-3 . . . . . . . . . . .
-6 . . . . . . . . . . .
-7 . . . . . . . . . . .
-8 . . . . . . . . . . .
-9 . . . . . . . . . . .
316L SST 316L SST 316L SST Vertical impulse piping type, right side high pressure, manifold upside
Vertical impulse piping type, right side high pressure, manifold downside Vertical impulse piping type, left side high pressure, manifold upside Vertical piping, left side high pressure, and manifold downside Horizontal piping and right side high pressure Horizontal piping and left side high pressure
Cast aluminum alloy
2 . . . . . . . . . .
3 . . . . . . . . . .
0 . . . . . . . . .
2 . . . . . . . . .
4 . . . . . . . . .
5 . . . . . . . . .
7 . . . . . . . . .
9 . . . . . . . . .
A. . . . . . . . .
C. . . . . . . . .
D. . . . . . . . .
D. . . . . . .
E . . . . . . .
N. . . . . . .
B. . . . .
D. . . . .
J . . . . .
K. . . . .
N. . . . .
ASTM CF-8M Stainless steel Cast aluminum alloy with corrosion resistance properties
G1/2 female, one electrical connection without blind plugs 1/2 NPT female, two electrical connections without blind plugs M20 female, two electrical connections without blind plugs G1/2 female, two electrical connections and a blind plug 1/2 NPT female, two electrical connections and a blind plug M20 female, two electrical connections and a blind plug G1/2 female, two electrical connections and a SUS316 blind plug 1/2 NPT female, two electrical connections and a SUS316 blind plug M20 female, two electrical connections and a SUS316 blind plug
Digital indicator
*6
Digital indicator with the range setting switch None
304 SST 2-inch pipe mounting, at type (for horizontal piping) 304 SST 2-inch pipe mounting, L type (for vertical piping) 316 SST 2-inch pipe mounting, at type (for horizontal piping) 316 SST 2-inch pipe mounting, L type (for vertical piping) None
*2
/  Optional specication
#
*3
*3
*3
*1
9-4
#
<9. General Specications>
9.3 Optional Specications
Item Description Code
Factory Mutual (FM) FM Explosionproof *
Explosionproof for Class I, Division 1, Groups B, C and D Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G Hazardous (classied) locations, indoors and outdoors (NEMA 4X)
FM Intrinsically safe *1*
Intrinsically Safe for Class I, Division 1, Groups A, B, C and D, Class II, Division 1,Groups E, F and G and Class III, Division 1 Hazardous Locations. Nonincendive for Class I, Division 2, Groups A, B, C and D, Class II, Division 2, Groups F and G Hazardous Locations.
Combined FF1 and FS1 *1*
ATEX ATEX Flameproof *
II 2G, 2D Ex d IIC T6...T4 Gb, Ex tb IIIC T85°C Db Special fastener: ClassA2-50(A4-50) or more
ATEX Intrinsically safe Ex ia *1*
II 1G, 2D Ex ia IIC T4 Ga, Ex ia IIIC T85°C T100°C T120°C Db
Combined KF22, KS21 and ATEX Intrinsically safe Ex ic
Ex ic: II 3G Ex ic IIC T4 Gc
Canadian Standards Association (CSA)
CSA Explosionproof *
Explosionproof for Class I, Groups B, C and D Dustignitionproof for Class II/III, Groups E, F and G Enclosure TYPE 4X, Temp.Code:T6...T4 Ex d IIC T6...T4 Enclosure IP66 and IP67
Process Sealing Certication
Dual Seal Certied by CSA to the requirement of ANSI/ISA 12.27.01 No additional sealing required Primary seal failure annuniciation: at the zero adjustment screw
CSA Intrinsically safe *1 *
[For CSA C22.2] Intrinsically safe for Class I, Division 1, Groups A, B, C and D, Class II, Division 1, Groups E, F and G, Class III, Division 1 Nonincendive for Class I, Division 2, Groups A, B, C and D, Class II, Division 2, Groups E, F and G, Class III, Division 1 [For CSA E60079] Ex ia IIC T4, Ex nL IIC T4
Process Sealing Certication
Dual Seal Certied by CSA to the requirement of ANSI/ISA 12.27.01 No additional sealing required Primary seal failure annuniciation: at the zero adjustment screw
Combined CF1 and CS1 *1*
IECEx IECEx ameproof *
Flameproof for Zone1, Ex d IIC T6...T4
IECEx Intrinsically safe, type n and ameproof *1*
Intrinsically safe and type n Ex ia IIC T4, Ex nL IIC T4 Flameproof
Flameproof for Zone1, Ex d IIC T6...T4 Combination of Approval Combination of KU22, FU1 and CU1 V1U1 Painting Color change Amplier cover only *
Amplier cover and terminal cover, Munsell 7.5 R4/14 PR
Coating change Anti-corrosion coating *3* 316 SST exterior parts 316 SST name plate, tag plate and zero-adjustment screw * Fluoro-rubber O-ring All O-rings of amplier housing. Lower limit of ambient temperature: –15°C (5°F) HE
1
FF1
2
FS1
2
1
FU1
KF22
2
*1*3
1
KS21
KU22
CF1
2
CS1
2
1
2
CU1
SF2
SU2
9
9
10
P
X2
HC
9-5
<9. General Specications>
9-6
Item Description Code
Lightning protector Transmitter power supply voltage:
10.5 to 32 V DC (10.5 to 30 V DC for intrinsically safe type.)
Allowable current: Max. 6000 A (1×40 μs), Repeating 1000 A (1×40 μs) 100 times
A
Applicable Standards: IEC 61000-4-4, IEC 61000-4-5
Status output *
4
Transistor output (sink type) Contact rating: 10.5 to 30 VDC, 120 mA DC(max) Low level: 0 to 2 VDC
AL
Oil-prohibited use Degrease cleansing treatment. K1
Degrease cleansing treatment and with uorinated oillled capsule. Operating temperature –20 to 80°C( –4 to 176°F)
Oil-prohibited use with dehydrating treatment
Degrease cleansing and dehydrating treatment. Degrease cleansing and dehydrating treatment with uorinated oillled capsule.
Operating temperature –20 to 80°C( –4 to 176°F)
Capsule ll uid Fluorinated oil lled in capsule
Operating temperature –20 to 80°C( –4 to 176°F)
Calibration units *
5
P calibration (psi unit) bar calibration (bar unit) D3 M calibration (kgf/cm2 unit) D4
(See Table for Span and
Range Limits.)
K2
K5
K6
K3
D1
Gold-plated diaphragm Surface of isolating diaphragm is gold plated, effective for hydrogen permeation. A1 Long vent *
Output limits and failure operation *
6
7
Total length: 119 mm (standard: 34 mm); Total length when combining with Optional code K1, K2, K5, and K6: 130 mm. Material: 316 SST.
Failure alarm down-scale: Output status at CPU failure and hardware error is –5%, 3.2 mA DC or less.
NAMUR NE43 Compliant Output signal limits:
3.8 mA to 20.5 mA
Failure alarm down-scale: Output status at CPU failure and hardware error is –5%, 3.2 mA DC or less.
Failure alarm up-scale: Output status at CPU failure and hardware error is 110%, 21.6 mA or more.
U1
C1
C2
C3
Stainless steel tag plate 304 SST tag plate wired onto transmitter (316 SST when /HC is specied) N4 Data conguration at
factory *
8
Advanced diagnostics *
Data conguration for HART communication type
Data conguration for BRAIN communication type
14
Multi-sensing process monitoring
• Impulse line blockage detection *
Software damping, Descriptor, Message
Software damping
15
CA
CB
DG6
• Heat trace monitoring Material certicate * Pressure test/
Leak test certicate *
Contact Yokogawa representative for the codes indicated as ‘-’. *1: Applicable for Electrical connection code 2, 4, 7, 9, C, and D. *2: Not applicable for option code /AL. *3: Not applicable with color change option. *4: Check terminals cannot be used when this option code is specied. Not applicable for output signal code F. *5: The unit of MWP (Max. working pressure) on the name plate of a housing is the same unit as specied by option codes D1, D3, and
D4. *6: Applicable for vertical impulse piping type (Installation code 2, 3, 6, or 7) . *7: Applicable for output signal codes D, E and J. The hardware error indicates faulty amplier or capsule. *8: Also see ‘Ordering Information’. *9: Not applicable for amplier housing code 2. *10: 316 or 316L SST. The specication is included in amplier code 2. *11: Pure nitrogen gas is used for oil-prohibited use (option codes K1, K2, K5, and K6). *12: The unit on the certicate is always Pa unit regardless of selection of option code D1, D3 or D4. *13: Material traceability certication, per EN 10204 3.1B. *14: Applicable only for output signal code -E and -J. *15: The change of pressure uctuation is monitored and then detects the impulse line blockage. See TI 01C25A31-01E for detailed
technical information required for using this function.
13
12
Cover ange, Process connector, Manifold, Orice, and Spacer M12 Test Pressure: 16 MPa (2300 psi) Nitrogen(N2) Gas *
Retention time: one minute
11
T12
<9. General Specications>

9.4 Dimensions

[Measurement span code M and H]

Unit: mm (approx. inch)
Vertical Impulse Piping Type
Process connector upside (Installation code 6)
242(9.53)
178(7.01)
97
(3.82)
41
(1.61)
58(2.28)
231(9.09)
97(3.82)
52
(2.05)
Horizontal Impulse Piping Type (Installation code 9)
External indicator Conduit connection
(optional)
54
(2.13)
6
(0.24)
Electrical connection for code 5, 9, A, and D.
*1: When Installation code 2, 3, or 8 is selected, the flow direction on above figure is reversed. *2: When Option code K1, K2, K5, or K6 is selected, add 15 mm (0.59 inch) to the value in the figure. *3: Available only when specifying the option code including ATEX, IECEx or TIIS flameproof type.
Vent plug
Drain plug
129(5.08)
63
Process connections
(2.48)
Shrouding bolt*
Mounting bracket (L-type,optional)
145(5.71)
124
(4.88)
47
(1.85)
3
89(3.50)
External indicator Conduit connection
(optional)
Integral indicator
95(3.74)
Conduit connection
Zero adjustment
Ground terminal
Vent/Drain plugs
67
(2.64)
95(3.74)
41
(1.61)
115(4.53)
Mounting bracket (Flat-type,optional)
(optional)
Electrical connection for code 5, 9, A, and D.
6(0.24)
54
(2.13)
(0.47)
ø78(3.07)
High pressure side
Conduit connection
Integral indicator (optional)
178
(7.01)
Shrouding bolt*
Process connections
Flow direction*
163(6.42)
12
3
Process connector downside (Installation code 7)
242(9.53)
1
Manifold
39
(1.54)
2
ø70(2.76)
146(5.75)*
Low pressure side
2-inch pipe
(O.D. 60.5 mm)
Zero adjustment
Ground terminal
(6.42)
High pressure side
2-inch pipe
(O.D. 60.5 mm)
163
52
97(3.82)
231(9.09)
58(2.28)
ø78(3.07)
(2.05)
41
110(4.33)
12
(0.47)
(1.61)
(1.54)
97(3.82)
39
(2.48)
ø70
Low pressure side
Flow direction*
178(7.01)
129(5.08)
Process connections
63
(2.76)
129(5.08)
Manifold
Process connector
9-7
95(3.74)
1
F0903.ai
● Terminal Configuration
Communication terminals (BT200 etc.) connection hook
SUPPLY +
SUPPLY –
Check meter connection hook
*4*5
CHECK + or ALARM +
CHECK – or ALARM –
● Terminal Wiring
+
SUPPLY
CHECK
or
ALARM
*4: When using an external indicator or check meter, the internal resistance must be 10 Ω or less. A check meter or indicator cannot be connected when /AL option is specified. *5: Not available for fieldbus and PROFIBUS communication types.
Power supply and output terminal
– +
External indicator (ammeter) terminal
or
Status contact output terminal
+ –
(when /AL is specified)
Ground terminal
*4*5
*5
F0904.ai
<9. General Specications>

[Measurement span code F]

Unit: mm (approx. inch)
● Vertical Impulse Piping Type
Process connector upside (Installation code 6) Process connector downside (Installation code 7)
46
64(2.53)
(1.81)
242(9.53)
102(4.02)
52
(2.05)
Mounting bracket (L-type,optional)
(3.82)
256(10.08)
194(7.64)
143(5.63)97
63
(2.48)
Shrouding bolt*
Process connections
Integral indicator
(optional)
Zero adjustment
Ground terminal
4
Electrical connection for code 5, 9, A, and D.
6(0.24)
External indicator Conduit connection
(optional)
95
(3.74)
Conduit connection
High pressure side
Vent/Drain plugs
2-inch pipe
(O.D. 60.5 mm)
54
(2.13)
ø78(3.07)
Flow direction*
163(6.42)
3
39
9*
(1.54)
(0.35)
1
ø70(2.76)
Low pressure side
Manifold
2
242(9.53)
156(6.14)*
52
(2.05)
102(4.02)
46
64(2.53)
(1.81)
(3.82)
256(10.08)
194(7.64)
143(5.63)97
63
Process connections
(2.48)
9-8
95(3.74)
● Horizontal Impulse Piping Type
(Installation code 9)
External indicator Conduit connection
(optional)
54
(2.13)
6
(0.24)
Electrical connection for code 5, 9, A, and D.
Vent plug
Drain plug
*1: When Installation code 2, 3, or 8 is selected, the flow direction on above figure is reversed. (i.e. the arrow faces to the left [ ]) *2: When Option code K1, K2, K5, or K6 is selected, add 15 mm (0.59 inch) to the value in the figure. *3: 15 mm (0.59 inch) when Installation code 2, 3 or 8 is selected. *4: Available only when specifying the option code including ATEX, IECEx or TIIS flameproof type.
159(6.26)
124
(4.88)
47
(1.85)
94
(3.70)
(3.74)
72
(2.83)
95
194
46
(1.81)
134(5.28)
Mounting bracket (Flat-type,optional)
Conduit connection
Integral indicator (optional)
(7.64)
Shrouding bolt*
Process connections
Zero adjustment
Ground terminal
4
2-inch pipe
(O.D. 60.5 mm)
163(6.42)
High pressure side
(0.35)
ø78(3.07)
110(4.33)
3
9*
39
(1.54)
ø70
Flow direction*
(2.76)
143(5.63)
Manifold
Process connector
Low pressure side
1
F0905.ai

Revision Information

Title : Low Flow Transmitter
EJX115A and EJA115E
Manual No. : IM 01C25K01-01E
Edition Date Page Revised Item
1st July 2008 New publication
2nd Aug. 2009 2-1 2.1 • Replace a name plate.
2-12 2.10 • Revise standards.
2.11 • Revise information of PED. 9-3 9.2 • Modify descriptions of materials. 9-5 9.3 • Add /A1and /DG6.
3rd Apr. 2010 2-1 2.3 • Add limitation of ambient temperature for /HE.
2-4 to 2-11 2.9 • Add limitation of ambient temperature for /HE.
9-3 9.1 • Add material for cover O-rings 9-5 9.3 • Add /HE. 9-7 9.4 • Correct dimensions.
4th Mar. 2012 2-3
9-3 9-4
5th June 2012
1-1
2.3 to 2.12 2-7 to 2-10
8-6
9.1 to end
6th June 2013
2-3
2-6, 2-7
2-8 to 2-11
9-4 9-5
9-7 to 9-8
2.9
9.1
9.2
1.
2.9
2.9.3
2.9.2
2.9.3
9.2
9.3
9.4
• Add note for blind plugs.
• Change description for a plate material.
• Add amplier housing code 3.
• Add EJA115E. Delete measurement span code L and Add measurement span code F.
• Add Note. Add model name of EJA115E.
• Delete /V1U.
• Delete /KS2, /KF21, and /KU21. Add /KS21, /KF22, and
/KU22.
• Add note for measurement span code F.
• Add information for EJA115E. Delete output signal code L and add measurement span code F.
• Add note for PROFIBUS PA communication type.
• Add note for multiple approval type.
• Correct CSA applicable standards.
• Replace ATEX type n by ATEX Intrinsically safe Ex ic.
• Add note for CE marking notied body number.
• Add PROFIBUS PA communication type.
• Replace ATEX type n by ATEX Intrinsically safe Ex ic.
• Add /V1U1.
• Add not for shrouding bolt.
i
Loading...