A7.10Comments on System/Network Management VFD Parameters
Relating to Software Download ........................................................A-66
REVISION RECORD
v
IM 01C25T02-01E
1.INTRODUCTION
1. INTRODUCTION
This manual is for the DPharp EJX Series Differential
Pressure/Pressure Transmitter Fieldbus Communication
Type. The Fieldbus communication type is based on
the same silicon resonant sensing technology used in
the BRAIN/HART communication type, and is similar
to the communication types in terms of basic performance and operation. This manual describes only those
topics that are required for operation of the Fieldbus
communication type. For information on the installation, wiring, and maintenance of EJX series pressure
transmitters, refer to the user’s manual for each model.
Also note that the contents of this manual are applicable for device revision 3 of EJX series pressure
transmitters. See a device information sheet attached to
the instrument to check the device revision.
Regarding This Manual
•This manual should be passed on to the end user.
• The contents of this manual are subject to change
without prior notice.
• All rights reserved. No part of this manual may be
reproduced in any form without Yokogawa’s written
permission.
WARNING
Indicates a potentially hazardous situation which,
if not avoided, could result in death or serious
injury.
CAUTION
Indicates a potentially hazardous situation which,
if not avoided, may result in minor or moderate
injury. It may also be used to alert against
unsafe practices.
IMPORTANT
Indicates that operating the hardware or software
in this manner may damage it or lead to system
failure.
• Yokogawa makes no warranty of any kind with
regard to this manual, including, but not limited to,
implied warranty of merchantability and fitness for a
particular purpose.
• If any question arises or errors are found, or if any
information is missing from this manual, please
inform the nearest Yokogawa sales office.
• The specifications covered by this manual are
limited to those for the standard type under the
specified model number break-down and do not
cover custom-made instruments.
• Please note that changes in the specifications,
construction, or component parts of the instrument
may not immediately be reflected in this manual at
the time of change, provided that postponement of
revisions will not cause difficulty to the user from a
functional or performance standpoint.
• The following safety symbols are used in this
manual:
NOTE
Draws attention to information essential for
understanding the operation and features.
1-1
IM 01C25T02-01E
1. INTRODUCTION
1.1Safe Use of This Product
For the safety of the operator and to protect the
instrument and the system, please be sure to follow this
manual’s safety instructions when handling this
instrument. If these instructions are not heeded, the
protection provided by this instrument may be impaired. In this case, Yokogawa cannot guarantee that
the instrument can be safely operated. Please pay
special attention to the following points:
(a) Installation
• This instrument may only be installed by an engineer or technician who has an expert knowledge of
this device. Operators are not allowed to carry out
installation unless they meet this condition.
•With high process temperatures, care must be taken
not to burn yourself by touching the instrument or
its casing.
• Never loosen the process connector nuts when the
instrument is installed in a process. This can lead to
a sudden, explosive release of process fluids.
•When draining condensate from the pressure
detector section, take appropriate precautions to
prevent the inhalation of harmful vapors and the
contact of toxic process fluids with the skin or eyes.
• When removing the instrument from a hazardous
process, avoid contact with the fluid and the interior
of the meter.
(c) Operation
•Wait 5 min. after the power is turned off, before
opening the covers.
(d) Maintenance
• Please carry out only the maintenance procedures
described in this manual. If you require further
assistance, please contact the nearest Yokogawa
office.
•Care should be taken to prevent the build up of dust
or other materials on the display glass and the name
plate. To clean these surfaces, use a soft, dry cloth.
(e) Explosion Protected Type Instrument
•Users of explosion proof instruments should refer
first to section 2.1 (Installation of an Explosion
Protected Instrument) of this manual.
• The use of this instrument is restricted to those who
have received appropriate training in the device.
• Take care not to create sparks when accessing the
instrument or peripheral devices in a hazardous
location.
(f)Modification
• Yokogawa will not be liable for malfunctions or
damage resulting from any modification made to this
instrument by the customer.
•All installation work shall comply with local
installation requirements and the local electrical
code.
(b) Wiring
• The instrument must be installed by an engineer or
technician who has an expert knowledge of this
instrument. Operators are not permitted to carry out
wiring unless they meet this condition.
• Before connecting the power cables, please confirm
that there is no current flowing through the cables
and that the power supply to the instrument is
switched off.
1-2
IM 01C25T02-01E
1. INTRODUCTION
1.2Warranty
•The warranty shall cover the period noted on the
quotation presented to the purchaser at the time of
purchase. Problems occurring during the warranty
period shall basically be repaired free of charge.
• If any problems are experienced with this instrument, the customer should contact the Yokogawa
representative from which this instrument was
purchased or the nearest Yokogawa office.
• If a problem arises with this instrument, please
inform us of the nature of the problem and the
circumstances under which it developed, including
the model specification and serial number. Any
diagrams, data and other information you can
include in your communication will also be helpful.
• The party responsible for the cost of fixing the
problem shall be determined by Yokogawa following an investigation conducted by Yokogawa.
1.3ATEX Documentation
This is only applicable to the countries in European
Union.
GB
All instruction manuals for ATEX Ex related products
are available in English, German and French. Should
you require Ex related instructions in your local
language, you are to contact your nearest Yokogawa
office or representative.
DK
Alle brugervejledninger for produkter relateret til
ATEX Ex er tilgængelige på engelsk, tysk og fransk.
Skulle De ønske yderligere oplysninger om håndtering
af Ex produkter på eget sprog, kan De rette
henvendelse herom til den nærmeste Yokogawa
afdeling eller forhandler.
• The purchaser shall bear the responsibility for repair
costs, even during the warranty period, if the
malfunction is due to:
- Improper and/or inadequate maintenance by the
purchaser.
- Malfunction or damage due to a failure to handle,
use, or store the instrument in accordance with the
design specifications.
- Use of the product in question in a location not
conforming to the standards specified by
Yokogawa, or due to improper maintenance of the
installation location.
- Failure or damage due to modification or repair by
any party except Yokogawa or an approved
representative of Yokogawa.
- Malfunction or damage from improper relocation
of the product in question after delivery.
- Reason of force majeure such as fires, earthquakes,
storms/floods, thunder/lightening, or other natural
disasters, or disturbances, riots, warfare, or
radioactive contamination.
I
Tutti i manuali operativi di prodotti ATEX
contrassegnati con Ex sono disponibili in inglese,
tedesco e francese. Se si desidera ricevere i manuali
operativi di prodotti Ex in lingua locale, mettersi in
contatto con l’ufficio Yokogawa più vicino o con un
rappresentante.
E
Todos los manuales de instrucciones para los productos
antiexplosivos de ATEX están disponibles en inglés,
alemán y francés. Si desea solicitar las instrucciones de
estos artículos antiexplosivos en su idioma local,
deberá ponerse en contacto con la oficina o el
representante de Yokogawa más cercano.
NL
Alle handleidingen voor producten die te maken
hebben met ATEX explosiebeveiliging (Ex) zijn
verkrijgbaar in het Engels, Duits en Frans. Neem,
indien u aanwijzingen op het gebied van
explosiebeveiliging nodig hebt in uw eigen taal, contact
op met de dichtstbijzijnde vestiging van Yokogawa of
met een vertegenwoordiger.
1-3
IM 01C25T02-01E
SF
Kaikkien ATEX Ex -tyyppisten tuotteiden käyttöhjeet
ovat saatavilla englannin-, saksan- ja ranskankielisinä.
Mikäli tarvitsette Ex -tyyppisten tuotteiden ohjeita
omalla paikallisella kielellännne, ottakaa yhteyttä
lähimpään Yokogawa-toimistoon tai -edustajaan.
P
Todos os manuais de instruções referentes aos
produtos Ex da ATEX estão disponíveis em Inglês,
Alemão e Francês. Se necessitar de instruções na sua
língua relacionadas com produtos Ex, deverá entrar em
contacto com a delegação mais próxima ou com um
representante da Yokogawa.
F
1. INTRODUCTION
Tous les manuels d’instruction des produits ATEX Ex
sont disponibles en langue anglaise, allemande et
française. Si vous nécessitez des instructions relatives
aux produits Ex dans votre langue, veuillez bien
contacter votre représentant Yokogawa le plus proche.
D
Alle Betriebsanleitungen für ATEX Ex bezogene
Produkte stehen in den Sprachen Englisch, Deutsch
und Französisch zur Verfügung. Sollten Sie die
Betriebsanleitungen für Ex-Produkte in Ihrer
Landessprache benötigen, setzen Sie sich bitte mit
Ihrem örtlichen Yokogawa-Vertreter in Verbindung.
S
Alla instruktionsböcker för ATEX Ex
(explosionssäkra) produkter är tillgängliga på
engelska, tyska och franska. Om Ni behöver
instruktioner för dessa explosionssäkra produkter på
annat språk, skall Ni kontakta närmaste
Yokogawakontor eller representant.
If a customer makes a repair or modification to an
intrinsically safe or explosionproof instrument and the
instrument is not restored to its original condition, its
intrinsically safe or explosionproof construction may
be compromised and the instrument may be hazardous
to operate. Please contact Yokogawa before making
any repair or modification to an instrument.
CAUTION
This instrument has been tested and certified as
being intrinsically safe or explosionproof. Please
note that severe restrictions apply to this
instrument’s construction, installation, external
wiring, maintenance and repair. A failure to
abide by these restrictions could make the
instrument a hazard to operate.
WARNING
Maintaining the safety of explosionproof equipment requires great care during mounting,
wiring, and piping. Safety requirements also
place restrictions on maintenance and repair.
Please read the following sections very carefully.
WARNING
The range setting switch must not be used in a
hazardous area.
2.1.1 FM approval
a. FM Explosionproof Type
Caution for FM Explosionproof type
Note 1. EJX Series differential gauge, and absolute
pressure transmitters with optional code /FF1
are applicable for use in hazardous locations:
• Explosionproof for Class I, Division 1,
Groups B, C and D.
•Dust-ignitionproof for Class II/III, Division
1, Groups E, F and G.
• Enclosure rating: NEMA 4X.
• Temperature Class: T6
• Ambient Temperature: –40 to 60°C
• Supply Voltage: 32V dc max.
• Current Draw: 15 mA dc
Note 2. Wiring
• All wiring shall comply with National
Electrical Code ANSI/NFPA70 and Local
Electrical Codes.
•When installed in Division 1, “FACTORY
SEALED, CONDUIT SEAL NOT REQUIRED.”
Note 3. Operation
•Keep the “WARNING” nameplate attached
to the transmitter.
WARNING: OPEN CIRCUIT BEFORE
REMOVING COVER.
FACTORY SEALED, CONDUIT
SEAL NOT REQUIRED.
INSTALL IN ACCORDANCE
WITH THE USERS MANUAL IM
01C25.
• Take care not to generate mechanical
sparking when accessing the instrument and
peripheral devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modification or parts
replacement by other than authorized
representative of Yokogawa Electric Corporation is prohibited and will void Factory
Mutual Explosionproof Approval.
2-1
IM 01C25T02-01E
2. HANDLING CAUTIONS
b. FM Nonincendive Type
EJX Series differential, gauge, and absolute
pressure transmitters with optional code /FN15.
• Applicable Standard: Class 3600, Class 3611,
Class 3810,ANSI/NEMA250
• Class I, Division 2, Groups A, B, C & D
Temperature Class T4 Ta=60°C, Type 4X and
Class II, Division 2, Groups F & G Temperature
Class T4 Ta=60°C, Type 4X and Class III,
Division 1, Temperature Class T4 Ta=60°C,
Type 4X and Class I, Zone 2, Group IIC,
Temperature Class T4 Ta=60°C, Type 4X
• Electrical Connection: 1/2 NPT female and M20
female
• Caution for FM Nonincendive type. (Following
contents refer to “DOC. No. IFM024-A12 p.3,
p.4-1, and p.4-2.”)
IFM024-A12
Installation Diagram for Nonincendive
(Division 2 Installation)
Terminator
Pressure
Transmitter
SUPPLY
Transmitter
Transmitter
Hazardous location
Note 1. Installation should be in accordance with the
National Electrical Code ® (ANSI/NFPA 70)
Article 500.
Note 2. The configuration of Associated Nonincendive
Field Wiring Apparatus must be FM
Approved.
Note 3. Approved under FNICO Concept.
Note 4. Dust-tight conduit seal must be used when
this apparatus.
Note 6. No revision to drawing without prior FM
Approvals.
Note 7. Terminator must be FM Approved.
Note 8. The nonincendive field wiring circuit concept
allows interconection of nonincendive field
wiring apparatus with associated nonincendive
field wiring apparatus, using any of the wiring
methods permitted for unclassified locations.
Note 9. Installation requirements;
Vmax Voc or Vt
Imax = see note 10.
Ca Ci + Ccable
La Li + Lcable
Note 10. For this current controlled circuit, the param-
eter (Imax 3) is not required and need not be
aligned with parameter (Isc 3) of the barrier
or associated nonincendive field wiring
apparatus.
Note 11. If ordinary location wiring methods are used,
the transmitter shall be connected to FM
Approved associated non-incendive field
wiring apparatus.
Electrical data:
Vmax: 32V
Ci:1.76 nF
Li: 0 H
Terminator
General Purpose
Equipment
Non-Hazardous location
FM Approved
Associated Nonincendive Field
Wiring Apparatus
Vt or Voc
It or Isc
Ca
La
F0204.EPS
2-2
IM 01C25T02-01E
2. HANDLING CAUTIONS
FNICO Rules
The FNICO Concept allows the interconnection of
nonincendive field wiring apparatus to associated
nonincendive field wiring apparatus not specifically
examined in such combination. The criterion for such
interconnection is that the voltage (Vmax), the current
(Imax) and the power (Pmax) which nonincendive field
wiring apparatus can receive and remain nonincendive,
considering faults, must be equal or greater than the
voltage (Uo, Voc or Vt), the current (Io, Isc or It) and
the power (Po) which can be provided by the associated nonincendive field wiring apparatus (supply unit).
In addition the maximum unprotected residual capacitance (Ci) and inductance (Li) of each apparatus (other
than terminators) connected to the Fieldbus must be
less than or equal to 5nF and 10uH respectively.
In each N.I. Fieldbus segment only one active source,
normally the associated nonincendive field wiring
apparatus, is allowed to provide the necessary power
for the Fieldbus system. The allowed voltage (Uo, Voc
or Vt) of the associated nonincendive field wiring
apparatus used to supply the bus cable must be limited
to the range 14Vdc to 17.5Vdc. All other equipment
connected to the bus cable has to be passive, meaning
that the apparatus is not allowed to provide energy to
the system, except a leakage current of 50É A for each
connected device. Separately powered equipment needs
galvanic isolation to ensure the nonincendive field
wiring Fieldbus circuit remains passive.
Cable
The cable used to interconnect the devices needs to
comply with the following parameters:
Loop resistance R': 15...150 Ω/km
Inductance per unit length L': 0.4...1 mH/km
Capacitance per unit length C': 80....200 nF/km
C' =C' line/line+0.5 C' line/screen, if both lines are
floating or C' = C' line/line + C'line/screen, if
thescreen is connected to one line.
Length of spur cable: max. 30 m
Length of trunk cable: max. 1 km
Length of splice: max = 1 m
Terminators
At the end of each trunk cable an FM Approved line
terminator with the following parameters is suitable:
R= 90...100 Ω
C = 0 ....2.2 uF
2.1.2 CSA Certification
a. CSA Explosionproof Type
Caution for CSA explosionproof type.
Note 1. Model EJX Series differential, gauge, and
absolute pressure transmitters with
optional code /CF1 are applicable for use
in hazardous locations:
• Dustignition-proof for Class II/III, Groups E, F and
G.
• Enclosure: TYPE 4X
• Temperature Code: T6...T4
[For CSA E60079]
• Applicable Standard: CAN/CSA E60079-0,
CAN/CSA E60079-1
• Flameproof for Zone 1, Ex d IIC T6...T4
• Enclosure: IP66 and IP67
• Maximum Process Temperature: 120°C (T4),
100°C (T5), 85°C (T6)
• Ambient Temperature: –50 to 75°C (T4), –50 to
80°C (T5), –50 to 72 õ (T6)
• Supply Voltage: 32 V dc max.
• Output Signal: 15 mA dc
Note 2. Wiring
• All wiring shall comply with Canadian Electrical
Code Part I and Local Electrical Codes.
• In hazardous location, wiring shall be in conduit as
shown in the figure.
• WARNING:
A SEAL SHALL BE INSTALLED WITHIN 50cm
OF THE ENCLOSURE.
UN SCELLEMENT DOIT ÊTRE INSTALLÉ À
MOINS DE 50cm DU BOÎTIER.
• WARNING:
WHEN INSTALLED IN CL.I, DIV 2, SEAL NOT
REQUIRED.
UNE FOIS INSTALLÉ DANS CL I, DIV 2,
AUCUN JOINT N'EST REQUIS.
Note 3. Operation
• WARNING:
AFTER DE-ENERGIZING, DELAY 5 MINUTES
BEFORE OPENING.
APRÉS POWER-OFF, ATTENDRE 5 MINUTES
AVANT D'OUVRIR.
2-3
IM 01C25T02-01E
2. HANDLING CAUTIONS
• WARNING:
WHEN AMBIENT TEMPERATURE ≥ 65°C,
USE THE HEAT-RESISTING CABLES ≥ 90°C.
QUAND LA TEMPÉRATURE AMBIANTE ≥
65°C, UTILISEZ DES CÂBLES RÉSISTANTES Á
LA CHALEUR ≥ 90°C.
• Take care not to generate mechanical sparking
when accessing to the instrument and peripheral
devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement
by other than authorized representative of
Yokogawa Electric Corporation and Yokogawa
Corporation of America is prohibited and will void
Canadian Standards Explosionproof Certification.
Non-Hazardous
Locations
Non-hazardous
Location
Equipment
32 V DC Max.
15 mA DC
Signal
Non-Hazardous
Locations
Non-hazardous
Location
Equipment
32 V DC Max.
15 mA DC
Signal
Hazardous Locations Division 1
50 cm Max.
Sealing Fitting
Conduit
EJX Series
Hazardous Locations Division 2
Sealing Fitting
EJX Series
S
U
P
PL
Y
CHECK
RM
A
L
A
S
U
P
P
L
Y
K
C
E
H
C
M
R
A
L
A
F0205.EPS
2.1.3 CENELEC ATEX Certification
(1) Technical Data
a. CENELEC ATEX (KEMA) Intrinsically Safe
Type
Caution for CENELEC ATEX (KEMA) Intrinsically
safe type.
Note 1. EJX Series differential, gauge, and absolute
pressure transmitters with optional code /KS25
for potentially explosive atmospheres:
• No. KEMA 04ATEX1116 X
• Applicable Standard: EN 50014, EN 50020,
EN 50284, EN50281-1-1
Note 2. Ratings
[EEx ia IIC T4]
Type of Protection and Marking Code:
EEx ia IIC T4
Group: II
Category: 1GD
Ambient Temperature: –40 to 60°C
Maximum Process Temperature (Tp.): 120°C
Maximum Surface Temperature for dust
proof.
T85°C (Tamb.: –40°C to 60°C, Tp.: 80°C)
T100°C (Tamb.: –40°C to 60°C, Tp.: 100°C)
T120°C (Tamb.: –40°C to 60°C, Tp.: 120°C)
Degree of Protection of the Enclosure: IP66
and IP67
Electrical Data
• When combined with Trapezoidal and
Rectangular output characteristic FISCO
model IIC barrier
Ui = 17.5 V, Ii = 380 mA, Pi = 5.32 W,
Ci = 1.76 nF, Li = 0 H
SE
PUL
• When combined with Linear characteristic
barrier
Ui = 24.0 V, Ii = 250 mA, Pi = 1.2 W,
Ci = 1.76 nF, Li = 0 H
[EEx ia IIB T4]
Type of Protection and Marking Code:
EEx ia IIB T4
Group: II
Category: 1GD
E
S
UL
P
Ambient Temperature: –40 to 60°C
Maximum Process Temperature (Tp.): 120°C
Maximum Surface Temperature for dust
proof.
T85°C (Tamb.: –40°C to 60°C, Tp.: 80°C)
T100°C (Tamb.: –40°C to 60°C, Tp.: 100°C)
T120°C (Tamb.: –40°C to 60°C, Tp.: 120°C)
Degree of Protection of the Enclosure: IP66
and IP67 Electrical Data
• When combined with Trapezoidal or
Rectangular output characteristic FISCO
model IIB barrier
Ui = 17.5 V, Ii = 460 mA, Pi = 5.32 W,
Ci = 1.76 nF, Li = 0 H
Note 3. Installation
• All wiring shall comply with local installation requirements. (Refer to the installation
diagram)
Note 4. Maintenance and Repair
• The instrument modification or parts
replacement by other than authorized
representative of Yokogawa Electric Corporation is prohibited and will void KEMA
Intrinsically safe Certification.
2-4
IM 01C25T02-01E
2. HANDLING CAUTIONS
Note 5. Special Conditions for Safe Use
• In the case where the enclosure of the
Pressure Transmitter is made of aluminium,
if it is mounted in an area where the use of
category 1 G apparatus is required, it must
be installed such, that even in the event of
rare incidents, ignition sources due to impact
and friction sparks are excluded.
Note 6. Installation instructions
• From the safety point of view the circuit
shall be considered to be connected to earth.
As this deviates from the FISCO system in
acordance with IEC TS 60079-27 care has to
be taken that the (local) installation requirements are taken into account as well.
When used in a potentially explosive
atmosphere, requiring the use of apparatus of
equipment category 1D or 2D, certified
cable entry devices shall be used that are
suitable for the application and correctly
installed.
FISCO Model
Supply unit
The supply unit must be certified by a Notified body as
FISCO model and following trapezoidal or rectangular
output characteristic is used.
Uo = 14...17.5 V (I.S. maximum value)
Io based on spark test result or other assessment,
No specification of Lo and Co is required on the
certificate or label.
Cable
The cable used to interconnect the devices needs to
comply with the following parameters:
Loop resistance Rc: 15...150 Ω/km
Inductance per unit length Lc: 0.4...1 mH/km
Capacitance per unit length Cc: 80...200 nF/km
Length of spur cable: max. 30 m (IIC and IIB)
Length of trunk cable: max. 1 km (IIC) or 5 km
(IIB)
Terminators
The terminator must be certified by a Notified body as
FISCO model and at each end of the trunk cable an
approved line terminator with the following parameters
is suitable:
Non-Hazardous
Locations
Supply Unit and
Safety Barrier
(FISCO Model)
U
U
I
Terminator
Data
I.S. fieldbus system complying with FISCO
Hazardous Locations
Ex i
Hand-
held-
Terminal
Field Instruments
(Passive)
Terminator
(FISCO Model)
F0201-1.EPS
The criterion for such interconnection is that the
voltage (Ui), the current (Ii) and the power (Pi), which
intrinsically safe apparatus can receive, must be equal
or greater than the voltage (Uo), the current (Io) and the
power (Po) which can be provided by the associated
apparatus (supply unit).
Po Pi, Uo Ui, Io Ii
In addition, the maximum unprotected residual capaci-
tance (Ci) and inductance (Li) of each apparatus (other
than the terminators) connected to the fieldbus line
must be equal or less than 5 nF and 10 H respectively.
Ci 5 nF, Li 10H
R = 90 . . . 102 Ω
C = 0 . . . 2.2 F. (0.8...1.2 F is required in
operation)
The resistor must be infallible according to IEC 60079-
11.
Number of Devices
The number of devices (max. 32) possible on a
fieldbus link depends on factors such as the power
consumption of each device, the type of cable used,
use of repeaters, etc.
The number of devices (max. 32) possible on a
fieldbus link depends on factors such as the power
consumption of each device, the type of cable used,
use of repeaters, etc.
b. CENELEC ATEX (KEMA) Flameproof Type
Caution for CENELEC ATEX (KEMA) flameproof
type
Note 1. EJX Series differential, gauge, and absolute
pressure transmitters with optional code /KF2
for potentially explosive atmospheres:
• No. KEMA 03ATEX2570
• Applicable Standard: EN 50014, EN 50018,
EN 50281-1-1
• Type of Protection and Marking Code: EEx
d IIC T6...T4
• Group: II
• Category: 2G, 1D
• Temperature Class: T6, T5, and T4
• Enclosure: IP66 and IP67
• Ambient Temperature for gas-proof:
–50 to 70°C (T6), –50 to 80°C (T5), and
–50 to 75°C (T4)
• Maximum Process Temperature (Tp.) for
gas-proof:
85°C (T6), 100°C (T5), and 120°C (T4)
• Maximum Surface Temperature for dust-
proof:
T80°C (Tamb.: –40 to 40°C, Tp.: 80°C)
T100°C (Tamb.: –40 to 60°C, Tp.: 100°C)
T120°C (Tamb.: –40 to 80°C, Tp.: 120°C)
Note 2. Electrical Data
• Supply voltage: 32 V dc max.
Output current: 15 mA dc
Note 3. Installation
• All wiring shall comply with local installation requirements.
•The cable entry devices shall be of a
certified flameproof type, suitable for the
conditions of use.
Note 4. Operation
• Keep the “WARNING” label attached to the
transmitter.
WARNING: AFTER DE-ENERGIZING,
DELAY 5 MINUTES BEFORE
OPENING. WHEN THE AMBIENT
TEMP.65°C, USE HEAT-RESISTING
CABLES90°C.
• Take care not to generate mechanical
sparking when accessing the instrument and
peripheral devices in hazardous location.
Note 5. Maintenance and Repair
• The instrument modification or part replacement by other than an authorized representative of Yokogawa Electric Corporation is
prohibited and will void KEMA Flameproof
Certification.
c. CENELEC ATEX Type of Protection “n”
Caution for CENELEC ATEX Type of Protection “n”
type
Note 1. EJX Series differential, gauge, and absolute
pressure transmitters with option code /KN25
for potentially explosive atmospheres:
• Applicable standard: EN 50021, EN 60529
• Type of Protection and Marking Code:
EEx nL IIC T4
• Group: II
• Category: 3G
• Ambient Temperature: –50 to 60°C
• Ambient humidity: 0 to 100%RH
(No condensation)
• Maximum Process Temperature : 120°C
• Enclosure: IP66 and IP67
Note 2. Electrical Data
Ui = 32 Vdc
Ci = 1.76 nF
Li = 0 µH
Note 3. Installation
• All wiring shall comply with local installation requirements. (refer to the installation
diagram)
Note 4. Maintenance and Repair
• The instrument modification or parts
replacement by other than authorized
representative of Yokogawa Electric Corporation is prohibited and will void Type of
Protection “n”.
[Installation Diagram]
U
2-6
Non-Hazardous
Locations
(Zone2)
Power
Supply
[EEx nL]
Terminator
Hazardous Locations
Terminator
Hand-
held-
Terminal
Field Instruments
(Passive)
IM 01C25T02-01E
F0202-2.EPS
2. HANDLING CAUTIONS
(2) Electrical Connection
A mark indicating the electrical connection type is
stamped near the electrical connection port. These
marks are as follows.
T0201.EPS
Location of the mark
F0201.EPS
(3) Installation
WARNING
•All wiring shall comply with local installation
requirements and the local electrical code.
• There is no need for a conduit seal in Division
1 and Division 2 hazardous locations because
this product is sealed at the factory.
(4) Operation
(6) Name Plate
Name plate
Tag plate for intrinsically safe type
No. KEMA 04ATEX1116 X
EEx ia IIB/IIC T4 Tamb.:-40 to 60°C
MAX PROCESS TEMP.(Tp.):120°C
T85°C(Tp.:80°C), T100°C(Tp.:100°C), T120°C(Tp.:120°C)
Enclosure: IP66 and IP67
FISCO Field device(IIC) FISCO Field device(IIB) Entity Parameters
Ui=17.5V Ui=17.5V Ui=24V
Ii=380mA Ii=460mA Ii=250mA
Pi=5.32W Pi=5.32W Pi=1.2W
Ci=1.76nF Ci=1.76nF Ci=1.76nF
Li=0µH Li=0µH Li=0µH
Tag plate for flameproof type
No. KEMA 03ATEX2570
EEx d IIC T6...T4 IP66 andIP67
TEMP. CLASS T6 T5 T4
MAX PROCESS TEMP.(Tp.) 85 100 120 °C
Tam b. -50 to 70 80 75 °C
T80°C(Tamb.:40°C, Tp.:80°C),T100°C(Tamb.:60°C, Tp.:100°C),
T120°C(Tamb.:80°C, Tp.:120°C) Min.Tamb.:-40°C(for DUST)
D
WARNING
EEx nL IIC T4
IP66 and IP67
Tam b. -5 0 to 60°C
MAX PROCESS TEMP. 120°C
Ui=32V Ci=1.76nF Li=0µH
AFTER DE-ENERGIZING, DELAY 5 MINUTES
BEFORE OPENING.
WHEN THE AMBIENT TEMP. 65°C,
USE THE HEAT-RESISTING CABLES 90°C
WARNING
• OPEN CIRCUIT BEFORE REMOVING
COVER. INSTALL IN ACCORDANCE WITH
THIS USER’S MANUAL
• Take care not to generate mechanical sparking
when accessing the instrument and peripheral
devices in a hazardous location.
(5) Maintenance and Repair
WARNING
The instrument modification or part replacement
by other than an authorized Representative of
Yokogawa Electric Corporation is prohibited and
will void the certification.
F0202.EPS
MODEL: Specified model code.
STYLE: Style code.
SUFFIX: Specified suffix code.
SUPPLY: Supply voltage.
OUTPUT: Output signal.
MWP: Maximum working pressure.
CAL RNG: Specified calibration range.
NO.: Serial number and year of production*1.
TOKYO 180-8750 JAPAN:
The manufacturer name and the address*2.
*1: The first digit in the final three numbers of the
serial number appearing after “NO.” on the name
plate indicates the year of production. The following is an example of a serial number for a product
that was produced in 2004:
12A819857 432
The year 2004
*2: “180-8750” is the Zip code for the following
address.
2-9-32 Nakacho, Musashino-shi, Tokyo Japan
2-7
IM 01C25T02-01E
3.ABOUT FIELDBUS
3. ABOUT FIELDBUS
3.1 Outline
Fieldbus is a wide l y u se d bi-directional digital communication protocol for field devices that enable the simultaneous output to many types of data to the process
control system.
The EJX Series Fieldbus communication type employs
the specification standardized by The Fieldbus Foundation, and provides interoperability between Yokogawa
devices and those produced by other manufacturers.
Fieldbus comes with software consisting of three AI
function blocks that enable the flexible implementation
of systems.
For information on other features, engineering, design,
construction work, startup and maintenance of
Fieldbus, refer to “Fieldbus Technical Information” (TI
38K03A01-01E).
3.2 Internal Structure of EJX
The EJX contains two virtual field devices (VFD) that
share the following functions.
3.2.1 System/network Management VFD
• Sets node addresses and Physical Device tags (PD
Tag) necessary for communication.
• Controls the execution of function blocks.
•Manages operation parameters and communication
resources (Virtual Communication Relationship:
VCR).
• Carry out scaling, damping and square root extraction.
(5)PID function block
• Performs the PID control computation based on the
deviation of the measured value from the setpoint.
3.3 Logical Structure of Each
Block
EJX
Fieldbus
LCD
Sensor
input
Sensor
System/network management VFD
PD Tag
Node address
Link Master
Function block VFD
LCD
Transducer block
Block tag
Parameters
SENSOR
Transducer block
Block tag
Parameters
Communication
parameters
VCR
Function block
execution schedule
PID function
block (option)
AR function
block
IS function
block
IT function
block
SC function
block
AI function
block
AI function
block
AI function
block
Block tag
Parameters
OUT
OUT_D
Output
3.2.2 Function Block VFD
(1)Resource block
•Manages the status of EJX hardware.
•Automatically informs the host of any detected
faults or other problems.
(2)SENSOR Transducer block
• Converts sensor output to pressure, static pressure,
and capsule temperature signals, and transfers to the
AI function blocks.
(3)LCD Transducer block
• Controls the display of the integral indicator.
(4)AI1 function block
• Condition raw data from the Transducer block.
• Output differential pressure, static pressure and
capsule temperature signals.
Resource block
Block tag
Parameters
Figure 3.1 Logical Structure of Each Block
Setting of various parameters, node addresses, and PD
Tags shown in Figure 3.1 is required before starting
operation.
3.4 Wiring System Configuration
The number of devices that can be connected to a
single bus and the cable length vary depending on
system design. When constructing systems, both the
basic and overall design must be carefully considered
to achieve optimal performance.
3-1
IM 01C25T02-01E
F0301.EPS
4.GETTING STARTED
4. GETTING STARTED
Fieldbus is fully dependent upon digital communication protocol and differs in operation from conventional 4 to 20 mA transmission and the BRAIN
communication protocol. It is recommended that
novice users use field devices in accordance with the
procedures described in this section. The procedures
assume that field devices will be set up on a bench or
in an instrument shop.
4.1 Connection of Devices
The following are required for use with Fieldbus
devices:
• Power supply:
Fieldbus requires a dedicated power supply. It is
recommended that current capacity be well over the
total value of the maximum current consumed by all
devices (including the host). Conventional DC
current cannot be used as is.
• Terminator:
Fieldbus requires two terminators. Refer to the
supplier for details of terminators that are attached
to the host.
•Field devices:
Connect Fieldbus communication type EJX. Two or
more EJX devices or other devices can be connected.
• Host:
Used for accessing field devices. A dedicated host
(such as DCS) is used for an instrumentation line
while dedicated communication tools are used for
experimental purposes. For operation of the host,
refer to the instruction manual for each host. No
other details on the host are given in this manual.
•Cable:
Used for connecting devices. Refer to “Fieldbus
Technical Information” (TI 38K03A01-01E) for
details of instrumentation cabling. For laboratory or
other experimental use, a twisted pair cable two to
three meters in length with a cross section of
0.9 mm2 or more and a cycle period of within 5 cm
(2 inches) may be used. Termination processing
depends on the type of device being deployed. For
EJX, use an M4 screw terminal claw. Some hosts
require a connector.
Refer to Yokogawa when making arrangements to
purchase the recommended equipment.
Connect the devices as shown in Figure 4.1. Connect
the terminators at both ends of the trunk, with a
minimum length of the spur laid for connection.
The polarity of signal and power must be maintained.
Fieldbus power
supply
Terminator
Figure 4.1 Cabling
EJX
HOST
Terminator
F0401.EPS
NOTE
No CHECK terminal is used for Fieldbus communication EJX. Do not connect the field indicator and check meter.
Before using a Fieldbus configuration tool other than
the existing host, confirm it does not affect the loop
functionality in which all devices are already installed
in operation. Disconnect the relevant control loop from
the bus if necessary.
IMPORTANT
Connecting a Fieldbus configuration tool to a
loop with its existing host may cause communication data scrambling resulting in a functional
disorder or a system failure.
4-1
IM 01C25T02-01E
4. GETTING STARTED
4.2 Host Setting
To activate Fieldbus, the following settings are
required for the host.
IMPORTANT
Do not turn off the power immediately after
setting. When the parameters are saved to the
EEPROM, the redundant processing is executed
for an improvement of reliability. If the power is
turned off within 60 seconds after setting is
made, the modified parameters are not saved
and the settings may return to the original
values.
Table 4.1 Operation Parameters
SymbolParameterDescription and Settings
V (ST)
V (MID)
V (MRD)
V (FUN)
V (NUN)
Slot-Time
Minimum-Inter-PDUDelay
Maximum-ReplyDelay
First-Unpolled-Node
Number-ofconsecutiveUnpolled-Node
Indicates the time
necessary for immediate
reply of the device. Unit of
time is in octets (256 µs).
Set maximum specification
for all devices. For EJX,
set a value of 4 or greater.
Minimum value of
communication data
intervals. Unit of time is in
octets (256 µs). Set the
maximum specification for
all devices. For EJX, set a
value of 4 or greater.
The worst case time
elapsed until a reply is
recorded. The unit is Slottime; set the value so that
V (MRD) V (ST) is the
maximum value of the
specification for all
devices. For EJX, the
setting must be a value of
12 or greater.
Indicate the address next
to the address range used
by the host. Set 015 or
greater.
Unused address range.
T0401.EPS
0x00
Not used
0x0F
0x10
0x13
0x14
V(FUN)
V(FUN)V(NUN)
0xF7
0xF8
0xFB
0xFC
0xFF
Note 1: Bridge device: A linking device which brings data from one
or more H1 networks.
Note 2: LM device: with bus control function (Link Master function)
Note 3: BASIC device: without bus control function
Figure 4.2 Available Address Range
Bridge device
LM device
UnusedV(NUN)
BASIC device
Default address
Portable device address
F0402.EPS
4-2
IM 01C25T02-01E
4. GETTING STARTED
4.3 Bus Power ON
Turn on the power of the host and the bus. Where the
EJX is equipped with an LCD indicator, first all
segments are lit, then the display begins to operate. If
the indicator is not lit, check the polarity of the power
supply.
Using the host device display function, check that the
EJX is in operation on the bus.
The device information, including PD tag, Node
address, and Device ID, is described on the sheet
attached to the EJX. The device information is given in
duplicate on this sheet.
Device ID : 594543000CXXXXXXXX
PD Tag : PT2001
Device Revision : 3
Node Address : 0xf3
Serial No. : XXXXXXXXXXXXXXXXX
Physical Location :
Note:
Our Device Description Files and Capabilities Files available at
http://www.yokogawa.com/fld (English) or
http://www.yokogawa.co.jp/Sensor/fieldbus/fieldbus.htm (Japanese)
DEVICE INFORMATION
4.4 Integration of DD
If the host supports DD (Device Description), the DD
of the EJX needs to be installed. Check if host has the
following directory under its default DD directory.
594543\000C
(594543 is the manufacturer number of Yokogawa
Electric Corporation, and 000C is the EJX device
number, respectively.)
If this directory is not found, the DD of the EJX has
not been included. Create the above directory and copy
the DD file (0m0n.ffo, 0m0n.sym) (m, n is a numeral)
into the directory. ‘0m’ in the file name shows the
device revision, and ‘0n’ shows the DD revision. If
you do not have the DD or capabilities files, you can
download them from our web site:
http://www.yokogawa.com/fld
Once the DD is installed in the directory, the name and
attribute of all parameters of the EJX are displayed.
Off-line configuration is possible by using capabilities
files.
EJX has two capabilities levels, “1” and “2”.
Device ID : 594543000CXXXXXXXX
PD Tag : PT2001
Device Revision : 3
Node Address : 0xf3
Serial No. : XXXXXXXXXXXXXXXXX
Physical Location :
Note:
Our Device Description Files and Capabilities Files available at
http://www.yokogawa.com/fld (English) or
http://www.yokogawa.co.jp/Sensor/fieldbus/fieldbus.htm (Japanese)
Figure 4.3 Device Information Sheet Attached to EJX
DEVICE INFORMATION
F0403.EPS
If no EJX is detected, check the available address
range and the polarity of the power supply. If the node
address and PD tag are not specified when ordering,
default value is factory set. If two or more EJXs are
connected at a time with default value, only one EJX
will be detected from the host as EJXs have the same
initial address. Separately connect each EJX and set a
different address for each.
Select “Capabilities level = 1” when the EJX don’t
have LC1(PID function) option.
Select “Capabilities level = 2” when the EJX has
LC1(PID function) option.
The capabilities level defines the kind and the number
of function blocks that can be used.
The table below shows the relation.
The relation between and function blocks that can be used
Capabilities
Level
1
2
AISCITISARPID
3
11110
311111
T0402.EPS
4.5 Reading the Parameters
To read EJX parameters, select the AI1 block of the
EJX from the host screen and read the OUT parameter.
The current selected signal is displayed. Check that
MODE_BLOCK of the function block and resource
block is set to AUTO, and change the signal input and
read the parameter again. A new designated value
should be displayed.
4-3
IM 01C25T02-01E
4.6 Continuous Record of Values
If the host has a function that continuously records the
indications, use this function to list the indications
(values). Depending on the host being used, it may be
necessary to set the schedule of Publish (the function
that transmits the indication on a periodic basis).
4.7 Generation of Alarm
Generation of an alarm can be attempted from EJX.
Block alarm, Output limit alarm, and Update alarm are
informed to the host. When generating alarm, a Link
Object and a VCR Static Entry need to be set. For
details of Link Object and VCR Static Entry, refer to
section 5.6.1 Link object and section 5.5.1 VCR
Setting.
4. GETTING STARTED
4-4
IM 01C25T02-01E
5.CONFIGURATION
5. CONFIGURATION
This chapter describes how to adapt the function and
performance of the EJX to suit specific applications.
Because multiple devices are connected to Fieldbus, it
is important to carefully consider the device requirements and settings when configuring the system. The
following steps must be taken.
(1)Network design
Determines the devices to be connected to Fieldbus
and checks the capacity of the power supply.
(2)Network definition
Determines the tag and node addresses for all
devices.
(3)Definition of combining function blocks
Determines how function blocks are combined.
(4)Setting tags and addresses
Sets the PD Tag and node addresses for each device.
(5)Communication setting
Sets the link between communication parameters
and function blocks.
(6)Block setting
Sets the parameters for function blocks.
The following section describes in sequence each step
of this procedure. The use of a dedicated configuration
tool significantly simplifies this procedure. Refer to
Appendix 6 when the EJX is used as Link Master.
• Terminator
Fieldbus requires two terminators. Refer to the
supplier for details of terminators that are attached
to the host.
•Field devices
Connect the field devices necessary for instrumenta-
tion. The EJX has passed the interoperability test
conducted by The Fieldbus Foundation. In order to
properly start Fieldbus, it is recommended that the
devices used satisfy the requirements of the above
test.
• Host
Used for accessing field devices. A minimum of one
device with the bus control function is needed.
• Cable
Used for connecting devices. Refer to “Fieldbus
Technical Information” for details of instrumenta-
tion cabling. Provide a cable sufficiently long to
connect all devices. For field branch cabling, use
terminal boards or a connection box as required.
First, check the capacity of the power supply. The
power supply capacity must be greater than the sum of
the maximum current consumed by all devices to be
connected to Fieldbus. The maximum current consumed (power supply voltage 9 V to 32 V) for the EJX
is 15 mA (24 mA in Software download operation).
The cable used for the spur must be of the minimum
possible length.
5.1 Network Design
Select the devices to be connected to the Fieldbus
network. The following are essential for the operation
of Fieldbus.
• Power supply
Fieldbus requires a dedicated power supply. It is
recommended that current capacity be well over the
total value of the maximum current consumed by all
devices (including the host). Conventional DC
current cannot be used as is.
5.2 Network Definition
Before connection of devices with Fieldbus, define the
Fieldbus network. Allocate PD Tag and node addresses
to all devices (excluding such passive devices as
terminators).
The PD Tag is the same as the conventional one used
for the device. Up to 32 alphanumeric characters may
be used for definition. Use a hyphen as a delimiter as
required.
The node address is used to specify devices for
communication purposes. Because this data is too long
for a PD Tag, the host uses the node address in place
of the PD Tag for communication. A range of 20 to
247 (or hexadecimal 14 to F7) can be set. The device
5-1
IM 01C25T02-01E
5. CONFIGURATION
(LM device) with bus control function (Link Master
function) is allocated from a smaller address number
(20) side, and other devices (BASIC device) without
bus control function allocated from a larger address
number (247) side respectively. Place the EJX in the
range of the BASIC device. When the EJX is used as
Link Master, place the EJX in the range of the LM
device. Set the range of addresses to be used to the LM
device. Set the following parameters.
Table 5.1 Parameters for Setting Address Range
Symbol
V (FUN) First-Unpolled-Node
V (NUN) Number-of-
ParametersDescription
Indicates the address next
to the address range used
for the host or other LM
device.
Unused address range
consecutiveUnpolled-Node
T0501.EPS
The devices within the address range written as
“Unused” in Figure 5.1 cannot be used on a Fieldbus.
For other address ranges, the range is periodically
checked to identify when a new device is mounted.
Care must be taken to keep the unused device range as
narrow as possible so as to lessen the load on the
Fieldbus.
0x00
0x0F
0x10
0x13
0x14
V(FUN)
V(FUN)V(NUN)
0xF7
0xF8
0xFB
0xFC
0xFF
Figure 5.1 Available Range of Node Addresses
Not used
Bridge device
LM device
UnusedV(NUN)
BASIC device
Default address
Portable device address
F0501.EPS
To ensure stable operation of Fieldbus, determine the
operation parameters and set them to the LM devices.
While the parameters in Table 5.2 are to be set, the
worst-case value of all the devices to be connected to
the same Fieldbus must be used. Refer to the specification of each device for details. Table 5.2 lists EJX
specification values.
Table 5.2 Operation Parameter Values of the EJX to be
Set to LM Devices
SymbolParametersDescription and Settings
V (ST)Slot-Time
V (MID) Minimum-Inter-PDU-
Delay
V (MRD) Maximum-Reply-Delay
Indicates the time
necessary for immediate
reply of the device. Unit of
time is in octets (256 µs).
Set maximum specification
for all devices. For EJX,
set a value of 4 or greater.
Minimum value of
communication data
intervals. Unit of time is in
octets (256 µs). Set the
maximum specification for
all devices. For EJX, set a
value of 4 or greater.
The worst case time
elapsed until a reply is
recorded. The unit is Slottime; set the value so that
V (MRD) V (ST) is the
maximum value of the
specification for all
devices. For EJX, the
setting must be a value of
12 or greater.
T0502.EPS
5.3 Definition of Combining
Function Blocks
The input/output parameters for function blocks are
combined. As required, they can be combined with the
input of the control block. The setting is written to the
EJX link object. See “Block setting” in Section 5.6 for
the details. It is also possible to read values from the
host at proper intervals instead of connecting the EJX
block output to other blocks.
The combined blocks need to be executed synchronously with other blocks on the communications
schedule. In this case, change the EJX schedule
according to the following table. The values in the
table are factory-settings.
Table 5.3 Execution Schedule of the EJX Function Blocks
IndexParameters
269
MACROCYCLE_
(SM)
DURATION
276
FB_START_ENTRY.1
(SM)
277 to
FB_START_ENTRY.2
289
FB_START_ENTRY.14
(SM)
to
Setting (Enclosed is
factory-setting)
Cycle (MACROCYCLE)
period of control or
measurement. Unit is 1/32
ms. (16000 = 0.5 s)
AI1 block startup time.
Elapsed time from the start
of MACROCYCLE specified
in 1/32 ms. (0 = 0 s)
Not used.
T0503.EPS
5-2
IM 01C25T02-01E
5. CONFIGURATION
A maximum of 30 ms is taken for execution of AI
block. For scheduling of communications for combination with the next function block, the execution is so
arranged as to start after a lapse of longer than 30 ms.
In no case should function blocks of the EJX be
executed at the same time (execution time is overlapped).
Figure 5.3 shows an example of schedule based on the
loop shown in Figure 5.2.
LIC100
EJX
#1
LI100
EJX
#2
FI100
Figure 5.2 Example of Loop Connecting Function Block of
Two EJX with Other Instruments
Macrocycle (Control Period)
FIC100
FC100
F0502.EPS
5.4 Setting of Tags and
Addresses
This section describes the steps in the procedure to set
PD Tags and node addresses in the EJX. There are
three states of Fieldbus devices as shown in Figure 5.4,
and if the state is other than the lowest
SM_OPERATIONAL state, no function block is
executed. EJX must be transferred to this state when an
EJX tag or address is changed.
UNINITIALIZED
(No tag nor address is set)
Tag clear Tag setting
INITIALIZED
(Only tag is set)
Address clear
SM_OPERATIONAL
(Tag and address are retained, and
the function block can be executed.)
Figure 5.4 Status Transition by Setting PD Tag and Node
Address
Address setting
F0504.EPS
LI100
OUT
Commu-
nication
Schedule
Figure 5.3 Function Block Schedule and Communication
Schedule
IN
LIC100
BKCAL_IN
FI100
OUT
CAS_IN
FIC100
IN
BKCAL_IN
Unscheduled
Communication
BKCAL_OUT
FC100
BKCAL_OUT
Scheduled
Communication
F0503.EPS
When the control period (macrocycle) is set to more
than 4 seconds, set the following intervals to be more
than 1% of the control period.
- Interval between “end of block execution” and “start
of sending CD from LAS”
- Interval between “end of block execution” and “start
of the next block execution”
EJX has a PD Tag (PT2001) and node address (245, or
hexadecimal F5) that are set upon shipment from the
factory unless otherwise specified. To change only the
node address, clear the address once and then set a new
node address. To set the PD Tag, first clear the node
address and clear the PD Tag, then set the PD Tag and
node address again.
Devices whose node addresses have been cleared will
have the default address (randomly chosen from a
range of 248 to 251, or from hexadecimal F8 to FB).
At the same time, it is necessary to specify the device
ID in order to correctly specify the device. The device
ID of the EJX is 594543000Cxxxxxxxx. (The
xxxxxxxx at the end of the above device ID is a total
of 8 alphanumeric characters.)
5-3
IM 01C25T02-01E
5. CONFIGURATION
5.5 Communication Setting
To set the communication function, it is necessary to
change the database residing in SM-VFD.
5.5.1 VCR Setting
Set VCR (Virtual Communication Relationship), which
specifies the called party for communication and
resources. EJX has 33 VCRs whose application can be
changed, except for the first VCR, which is used for
management.
EJX has VCRs of four types:
Server(QUB) VCR
A Server responds to requests from a host. This
communication needs data exchange. This type of
communication is called QUB (Queued Usertriggered Bidirectional) VCR.
Source (QUU) VCR
A Source multicasts alarms or trends to other
devices. This type of communication is called QUU
(Queued User-triggered Unidirectional) VCR.
Publisher (BNU) VCR
A Publisher multicasts AI block output to another
function block(s). This type of communication is
called BNU (Buffered Network-triggered Unidirectional) VCR.
Subscriber (BNU) VCR
A Subscriber receives output of another function
block(s) by PID block.
A Server VCR is capable to responding to requests
from a Client (QUB) VCR after the Client successfully
initiates connection to the Server. A Source VCR
transmits data without established connection. A Sink
(QUU) VCR on another device can receive it if the
Sink is configured so. A Publisher VCR transmits data
when LAS requests so. An explicit connection is
established from Subscriber (BNU) VCR(s) so that a
Subscriber knows the format of published data.
Each VCR has the parameters listed in Table 5.4.
Parameters must be changed together for each VCR
because modification of individual parameters may
cause inconsistent operation.
Table 5.4 VCR Static Entry
Sub-
index
1FasArTypeAndRole
2FasDllLocalAddr
3FasDllConfigured
4FasDllSDAP
5FasDllMaxConfirm
6FasDllMaxConfirm
7FasDllMaxDlsduSize
8FasDllResidual
9FasDllTimelinessClass
10FasDllPublisherTime
11FasDllPublisher
ParameterDescription
RemoteAddr
DelayOnConnect
DelayOnData
ActivitySupported
WindowSize
SynchronizaingDlcep
Indicates the type and role of
communication (VCR). The
following 4 types are used
for EJX.
0x32: Server (Responds to
requests from host.)
0x44: Source (Transmits
alarm or trend.)
0x66: Publisher (Sends AI
block output to other
blocks.)
0x76: Subscriber (Receives
output of other blocks
by PID block.)
Sets the local address to
specify VCR in EJX. A range
of 20 to F7 in hexadecimal.
Sets the node address of the
called party for
communication and the
address (DLSAP or DLCEP)
used to specify VCR in that
address. For DLSAP or
DLCEP, a range of 20 to F7
in hexadecimal is used.
Addresses in Subindex 2
and 3 need to be set to the
same contents of the VCR
as the called party (local and
remote are reversed).
Specifies the quality of
communication. Usually, one
of the following types is set.
0x2B: Server
0x01: Source (Alert)
0x03: Source (Trend)
0x91: Publisher/Subscriber
To establish connection for
communication, a maximum
wait time for the called
party's response is set in
ms. Typical value is 60
secounds (60000).
For request of data, a
maximum wait time for the
called party's response is
set in ms. Typical value is
60 secounds (60000).
Specifies maximum DL
Service Data unit Size
(DLSDU). Set 256 for Server
and Trend VCR, and 64 for
other VCRs.
Specifies whether
connection is monitored. Set
TRUE (0xff) for Server. This
parameter is not used for
other communication.
Not used for EJX.
Not used for EJX.
Not used for EJX.
T0504-1.EPS
5-4
IM 01C25T02-01E
5. CONFIGURATION
Sub-
index
12FasDllSubsriberTime
13FasDllSubscriber
14FmsVfdId
15FmsMaxOutstanding
16FmsMaxOutstanding
17FmsFeatures
Parameter
WindowSize
SynchronizationDlcep
ServiceCalling
ServiceCalled
Supported
Description
Not used for EJX.
Not used for EJX.
Sets VFD for EJX to be
used.
0x1: System/network
management VFD
0x1234: Function block
VFD
Set 0 to Server. It is not
used for other applications.
Set 1 to Server. It is not
used for other applications.
Indicates the type of
services in the application
layer. In the EJX, it is
automatically set according
to specific applications.
T0504-2.EPS
33 VCRs are factory-set as shown in the table below.
According to the instructions given in Section 5.3, set
the execution cycle of the function blocks and schedule
of execution.
5.6 Block Setting
Set the parameter for function block VFD.
5.6.1 Link Object
A link object combines the data voluntarily sent by the
function block with the VCR. The EJX has 40 link
objects. A single link object specifies one combination.
Each link object has the parameters listed in Table 5.6.
Parameters must be changed together for each VCR
because the modifications made to each parameter may
cause inconsistent operation.
Table 5.6 Link Object Parameters
Sub-
index
1LocalIndex
2VcrNumber
3RemoteIndex
4ServiceOperation
5StaleCountLimit
Set link objects as shown in Table 5.7.
Table 5.7 Factory-Settings of Link Objects (example)
Sets the index of function
block parameters to be
combined; set “0” for Trend
and Alert.
Sets the index of VCR to
be combined. If set to “0”,
this link object is not used.
Not used in EJX. Set to “0”.
Set one of the following.
Set only one each for link
object for Alert or Trend.
0: Undefined
2: Publisher
3: Subscriber
6: Alert
7: Trend
Set the maximum number
of consecutive stale input
values which may be
received before the input
status is set to BAD. To
avoid the unnecessary
mode transition caused
when the data is not
correctly received by
subscriber, set this
parameter to “2” or more.
T0506.EPS
Not used5 to 40
T0507.EPS
5-5
IM 01C25T02-01E
5. CONFIGURATION
5.6.2 Trend Object
It is possible to set the parameter so that the function
block automatically transmits Trend. EJX has seven
Trend objects, six of which are used for Trend in
analog mode parameters and one is used for Trend in
discrete mode parameter. A single Trend object
specifies the trend of one parameter.
Each Trend object has the parameters listed in Table
5.8. The first four parameters are the items to be set.
Before writing to a Trend object, it is necessary to
release the WRITE_LOCK parameter.
Table 5.8 Parameters for Trend Objects
Sub-
index
1Block Index
2Parameter Relative
3Sample Type
4Sample Interval
5Last Update
6 to 21 List of Status
21 to 37 List of Samples
Parameters
Index
Seven trend objects are factory-set as shown Table 5.9.
Description
Sets the leading index of
the function block that
takes a trend.
Sets the index of
parameters taking a trend
by a value relative to the
beginning of the function
block. In the EJX AI block,
the following three types of
trends are possible.
7: PV
8: OUT
19: FIELD_VAL
Specifies how trends are
taken. Choose one of the
following 2 types:
1: Sampled upon
execution of a function
block.
2: The average value is
sampled.
Specifies sampling
intervals in units of 1/32
ms. Set the integer
multiple of the function
block execution cycle.
The last sampling time.
Status part of a sampled
parameter.
Data part of a sampled
parameter.
T0508.EPS
SMIB
(System
Management
Information
Base)
NMIB
(Network
Management
Information
Base)
Link
object
VCR
Resource
block
#1
#2
FBOD
#3 #4
Transducer
block
#1#2
#8
#6
AI1 OUT
#4
#9
AI2 OUT
Alert
#3
#7
Trend
#5
EJX
DLSAP
DLCEP
Fieldbus Cable
Figure 5.5 Example of Default Configuration
0xF8 0xF3 0xF4 0xF7
Host 1
Host 2
0xF9
Device 1
0x20 0x21
Device 2
0x07
F0505.EPS
5.6.3 View Object
This object forms a group of parameters in a block.
One advantage brought by forming groups of parameters is the reduction of load for data transactions.
View Object has the parameters listed in Table 5.11 to
5.14. Purpose of View Objects is shown in Table 5.10.
Table 5.10 Purpose of Each View Object
Description
VIEW_1
VIEW_2
VIEW_3
VIEW_4
Set of dynamic parameters required by operator
for plant operation. (PV, SV, OUT, Mode etc.)
Set of static parameters which need to be
shown to plant operator at once. (Range etc.)
Set of all the dynamic parameters.
Set of static parameters for configuration or