When using the Transmitters in a Safety Instrumented Systems(SIS)
application, refer to Appendix A in either IM 01C25T01-06EN for the
HART protocol or IM 01C25T03-01E for the BRAIN protocol.
IM 01C25F01-01E
<1. Introduction>
1. Introduction
Thank you for purchasing the DPharp EJX and EJA
Differential Pressure and pressure transmitter.
NOTE
1-1
Your transmitter was precisely calibrated at the
factory before shipment. To ensure both safety and
efciency, please read this manual carefully before
you operate the instrument.
NOTE
This manual describes the hardware
congurations of the transmitters listed in below.
For information on the software conguration
and operation, please refer to either
IM 01C25T03-01E for the BRAIN communication
type, or IM 01C25T01-06EN for the HART
communication type.
For FOUNDATION Fieldbus protocol type,
please refer to IM 01C25T02-01E.
For PROFIBUS PA protocol type, please refer to
IM 01C25T04-01EN.
To ensure correct use of this instrument, read
both the hardware and software manuals
thoroughly before use.
WARNING
When using the transmitters in a Safety
Instrumented Systems (SIS) application, refer
to Appendix 1 in either IM 01C25T01-06EN for
the HART protocol or IM 01C25T03-01E for the
BRAIN protocol. The instructions and procedures
in this section must be strictly followed in order to
maintain the transmitter for this safety level.
Unless otherwise stated, the illustrations in this
manual are of the EJ530 gauge pressure
transmitter.
Users of the EJ510, EJX610A and EJX630A
should bear in mind that certain features of their
instrument will differ from those shown in the
illustrations of the EJ530.
Regarding This Manual
• This manual should be provided to the end
user.
• The contents of this manual are subject to
change without prior notice.
• All rights reserved. No part of this manual may
be reproduced in any form without Yokogawa’s
written permission.
• Yokogawa makes no warranty of any kind with
regard to this manual, including, but not limited
to, implied warranty of merchantability and
tness for a particular purpose.
• If any question arises or errors are found, or if
any information is missing from this manual,
please inform the nearest Yokogawa sales
ofce.
• The specications covered by this manual are
limited to those for the standard type under the
specied model number break-down and do not
cover custom-made instruments.
• Please note that changes in the specications,
construction, or component parts of the
instrument may not immediately be reected
in this manual at the time of change, provided
that postponement of revisions will not cause
difculty to the user from a functional or
performance standpoint.
• Yokogawa assumes no responsibility for this
product except as stated in the warranty.
NOTE
When describing the model name like EJ510
or EJ530, it shows the applicability for
both EJX510A and EJA510E or EJX530A and
EJA530E.
• If the customer or any third party is harmed by
the use of this product, Yokogawa assumes
no responsibility for any such harm owing to
any defects in the product which were not
predictable, or for any indirect damages.
IM 01C25F01-01E
<1. Introduction>
1-2
• The following safety symbols are used in this
manual:
WARNING
Indicates a potentially hazardous situation which,
if not avoided, could result in death or serious
injury.
CAUTION
Indicates a potentially hazardous situation which,
if not avoided, may result in minor or moderate
injury. It may also be used to alert against unsafe
practices.
IMPORTANT
Indicates that operating the hardware or software
in this manner may damage it or lead to system
failure.
1.1 Safe Use of This Product
For the safety of the operator and to protect the
instrument and the system, please be sure to follow
this manual’s safety instructions when handling this
instrument. If these instructions are not heeded,
the protection provided by this instrument may be
impaired. In this case, Yokogawa cannot guarantee
that the instrument can be safely operated. Please
pay special attention to the following points:
(a) Installation
• This instrument may only be installed by an
engineer or technician who has an expert
knowledge of this device. Operators are not
allowed to carry out installation unless they
meet this condition.
• With high process temperatures, care must
be taken not to burn yourself by touching the
instrument or its casing.
• Never loosen the process connector nuts when
the instrument is installed in a process. This can
lead to a sudden, explosive release of process
uids.
NOTE
Draws attention to information essential for
understanding the operation and features.
Direct current
• When draining condensate from the pressure
detector section, take appropriate precautions
to prevent the inhalation of harmful vapors and
the contact of toxic process uids with the skin
or eyes.
• When removing the instrument from a
hazardous process, avoid contact with the uid
and the interior of the meter.
• All installation shall comply with local installation
requirements and the local electrical code.
(b) Wiring
• The instrument must be installed by an
engineer or technician who has an expert
knowledge of this instrument. Operators are not
permitted to carry out wiring unless they meet
this condition.
• Before connecting the power cables, please
conrm that there is no current owing through
the cables and that the power supply to the
instrument is switched off.
IM 01C25F01-01E
<1. Introduction>
1-3
(c) Operation
• Wait 5 min. after the power is turned off, before
opening the covers.
(d) Maintenance
• Please carry out only the maintenance
procedures described in this manual. If you
require further assistance, please contact the
nearest Yokogawa ofce.
• Care should be taken to prevent the build up of
dust or other materials on the display glass and
the name plate. To clean these surfaces, use a
soft, dry cloth.
(e) Explosion Protected Type Instrument
• Users of explosion proof instruments should
refer rst to section 2.9 (Installation of an
Explosion Protected Instrument) of this manual.
• The use of this instrument is restricted to those
who have received appropriate training in the
device.
• Take care not to create sparks when accessing
the instrument or peripheral devices in a
hazardous location.
(f) Modication
1.2 Warranty
• The warranty shall cover the period noted on
the quotation presented to the purchaser at the
time of purchase. Problems occurring during
the warranty period shall basically be repaired
free of charge.
• If any problems are experienced with this
instrument, the customer should contact the
Yokogawa representative from which this
instrument was purchased or the nearest
Yokogawa ofce.
• If a problem arises with this instrument,
please inform us of the nature of the problem
and the circumstances under which it
developed, including the model specication
and serial number. Any diagrams, data and
other information you can include in your
communication will also be helpful.
• The party responsible for the cost of xing the
problem shall be determined by Yokogawa
following an investigation conducted by
Yokogawa.
• The purchaser shall bear the responsibility for
repair costs, even during the warranty period, if
the malfunction is due to:
• Yokogawa will not be liable for malfunctions or
damage resulting from any modication made
to this instrument by the customer.
- Improper and/or inadequate maintenance by
the purchaser.
- Malfunction or damage due to a failure
to handle, use, or store the instrument in
accordance with the design specications.
- Use of the product in question in a location
not conforming to the standards specied by
Yokogawa, or due to improper maintenance
of the installation location.
- Failure or damage due to modication or
repair by any party except Yokogawa or an
approved representative of Yokogawa.
- Malfunction or damage from improper
relocation of the product in question after
delivery.
- Reason of force majeure such as res,
earthquakes, storms/oods, thunder/
lightening, or other natural disasters, or
disturbances, riots, warfare, or radioactive
contamination.
IM 01C25F01-01E
<1. Introduction>
1.3 ATEX Documentation
This is only applicable to the countries in European Union.
1-4
GB
DK
E
NL
SK
CZ
I
LT
LV
EST
PL
SF
P
F
D
S
SLO
H
BG
RO
M
GR
IM 01C25F01-01E
<2. Handling Cautions>
2. Handling Cautions
2-1
This chapter provides important information on how
to handle the transmitter. Read this carefully before
using the transmitter.
The transmitters are thoroughly tested at the
factory before shipment. When taking delivery of an
instrument, visually check them to make sure that
no damage occurred during shipment.
Also check that all transmitter mounting hardware
shown in gure 2.1 is included. If the transmitter
is ordered without the mounting bracket and the
process connector, the transmitter mounting
hardware will not be included. After checking the
transmitter, carefully repack it in its box and keep it
there until you are ready to install it.
U-bolt nut (L)
Mounting bracket
U-bolt nut (S)
2.2 Unpacking
Keep the transmitter in its original packaging to
prevent it from being damaged during shipment.
Do not unpack the transmitter until it reaches the
installation site.
2.3 Storage
The following precautions must be observed when
storing the instrument, especially for a long period.
(a) Select a storage area which meets the following
conditions:
• It is not exposed to rain or subject to water
seepage/leaks.
• Vibration and shock are kept to a minimum.
• It has an ambient temperature and relative
humidity within the following ranges.
Ambient temperature:
–40* to 85°C without integral indicator
–30* to 80°C with integral indicator
* –15°C when /HE is specied.
Relative humidity:
0% to 100% R.H.
Preferred temperature and humidity:
approx. 25°C and 65% R.H.
U-bolt (S)
U-bolt (L)
F0201.ai
Figure 2.1 Transmitter Mounting Hardware
2.1 Model and Specications
Check
The model name and specications are written on
the name plate attached to the case.
F0202.ai
Figure 2.2 Name Plate
(b) When storing the transmitter, repack it carefully
in the packaging that it was originally shipped
with.
(c) If the transmitter has been used, thoroughly
clean the chambers inside the cover anges, so
that there is no process uid remaining inside.
Before placing it in storage, also make sure that
the pressure-detector is securely connected to
the transmitter section.
2.4 Selecting the Installation
Location
The transmitter is designed to withstand severe
environmental conditions. However, to ensure
that it will provide years of stable and accurate
performance, take the following precautions when
selecting the installation location.
IM 01C25F01-01E
<2. Handling Cautions>
2-2
(a) Ambient Temperature
Avoid locations subject to wide temperature
variations or a signicant temperature gradient.
If the location is exposed to radiant heat from
plant equipment, provide adequate thermal
insulation and/or ventilation.
(b) Ambient Atmosphere
Do not install the transmitter in a corrosive
atmosphere. If this cannot be avoided, there
must be adequate ventilation as well as
measures to prevent the leaking of rain water
and the presence of standing water in the
conduits.
(c) Shock and Vibration
Although the transmitter is designed to be
relatively resistant to shock and vibration, an
installation site should be selected where this is
kept to a minimum.
(d) Installation of Explosion-protected Transmitters
An explosion-protected transmitters is
certied for installation in a hazardous area
containing specic gas types. See subsection
2.9 “Installation of an Explosion-Protected
Transmitters.”
2.5 Pressure Connection
WARNING
• Never loosen the process connector bolts
when an instrument is installed in a process.
The device is under pressure, and a loss of
seal can result in a sudden and uncontrolled
release of process uid.
• When draining toxic process uids that have
condensed inside the pressure detector,
take appropriate steps to prevent the contact
of such uids with the skin or eyes and the
inhalation of vapors from these uids.
The following precautions must be observed
in order to safely operate the transmitter under
pressure.
(a) Make sure that all the process connector bolts
are tightened rmly.
(b) Make sure that there are no leaks in the impulse
piping.
(c) Never apply a pressure higher than the
specied maximum working pressure.
2.6 Waterproong of Cable
Conduit Connections
Apply a non-hardening sealant to the threads
to waterproof the transmitter cable conduit
connections. (See gure 6.8, 6.9 and 6.10.)
2.7 Restrictions on Use of Radio
Transceivers
IMPORTANT
Although the transmitter has been designed to
resist high frequency electrical noise, if a radio
transceiver is used near the transmitter or its
external wiring, the transmitter may be affected
by high frequency noise pickup. To test this, start
out from a distance of several meters and slowly
approach the transmitter with the transceiver
while observing the measurement loop for noise
effects. Thereafter use the transceiver outside
the range where the noise effects were rst
observed.
2.8 Insulation Resistance and
Dielectric Strength Test
Since the transmitter has undergone insulation
resistance and dielectric strength tests at the factory
before shipment, normally these tests are not
required. If the need arises to conduct these tests,
heed the following:
(a) Do not perform such tests more frequently than
is absolutely necessary. Even test voltages that
do not cause visible damage to the insulation
may degrade the insulation and reduce safety
margins.
IM 01C25F01-01E
<2. Handling Cautions>
2-3
(b) Never apply a voltage exceeding 500 V DC
(100 V DC with an internal lightning protector)
for the insulation resistance test, nor a voltage
exceeding 500 V AC (100 V AC with an internal
lightning protector) for the dielectric strength
test.
(c) Before conducting these tests, disconnect
all signal lines from the transmitter terminals.
The procedure for conducting these tests is as
follows:
• Insulation Resistance Test
1) Short-circuit the + and – SUPPLY terminals in
the terminal box.
2) Turn OFF the insulation tester. Then connect
the insulation tester plus (+) lead wire to the
shorted SUPPLY terminals and the minus (–)
leadwire to the grounding terminal.
3) Turn ON the insulation tester power and
measure the insulation resistance. The voltage
should be applied as briey as possible to verify
that the insulation resistance is at least 20 MΩ.
4) After completing the test and being very careful
not to touch exposed conductors disconnect the
insulation tester and connect a 100 kΩ resistor
between the grounding terminal and the shortcircuiting SUPPLY terminals. Leave this resistor
connected at least one second to discharge any
static potential. Do not touch the terminals while
it is discharging.
2.9 Installation of an ExplosionProtected Instrument
NOTE
For FOUNDATION Fieldbus explosion protected
type, please refer to IM 01C22T02-01E.
For PROFIBUS PA explosion protected type,
please refer to IM 01C25T04-01EN.
If a customer makes a repair or modication to
an intrinsically safe or explosionproof instrument
and the instrument is not restored to its original
condition, its intrinsically safe or explosionproof
construction may be compromised and the
instrument may be hazardous to operate. Please
contact Yokogawa before making any repair or
modication to an instrument.
CAUTION
This instrument has been tested and certied
as being intrinsically safe or explosionproof.
Please note that severe restrictions apply to this
instrument’s construction, installation, external
wiring, maintenance and repair. A failure to abide
by these restrictions could make the instrument a
hazard to operate.
• Dielectric Strength Test
1) Short-circuit the + and – SUPPLY terminals in
the terminal box.
2) Turn OFF the dielectric strength tester. Then
connect the tester between the shorted
SUPPLY terminals and the grounding terminal.
Be sure to connect the grounding lead of the
dielectric strength tester to the ground terminal.
3) Set the current limit on the dielectric strength
tester to 10 mA, then turn ON the power and
gradually increase the test voltage from ‘0’ to
the specied voltage.
4) When the specied voltage is reached, hold it
for one minute.
5) After completing this test, slowly decrease the
voltage to avoid any voltage surges.
WARNING
Maintaining the safety of explosionproof
equipment requires great care during mounting,
wiring, and piping. Safety requirements also
place restrictions on maintenance and repair.
Please read the following sections very carefully.
WARNING
The range setting switch must not be used in a
hazardous area.
IM 01C25F01-01E
<2. Handling Cautions>
2-4
IMPORTANT
For combined approval types
Once a device of multiple approval type is
installed, it should not be re-installed using any
other approval types. Apply a permanent mark
in the check box of the selected approval type
on the certication label on the transmitter to
distinguish it from unused approval types.
IMPORTANT
All the blind plugs which accompany the EJX/
EJA-E transmitters upon shipment from the
factory are certied by the applicable agency
in combination with the transmitters. The plugs
which are marked with the symbols “◊ Ex” on
their surfaces are certied only in combination
with the EJX/EJA-E series transmitters.
2.9.1 FM Approval
Note 2. Entity Parameters
• Intrinsically Safe Apparatus Parameters
[Groups A, B, C, D, E, F and G]
Vmax = 30 VCi = 6 nF
Imax = 200 mALi = 0 µH
Pmax = 1 W
Voc ≤ 30 VCa > 6 nF
Isc ≤ 225 mALa > 0 µH
Pmax ≤ 1 W
a. FM Intrinsically Safe Type
Caution for FM intrinsically safe type. (Following
contents refer “DOC. No. IFM022-A12”)
Note 1. Model EJX/EJA-E Series Differential,
gauge and absolute pressure transmitters
with optional code /FS1 are applicable for
use in hazardous locations.
• Applicable Standard: FM3600, FM3610,
FM3611, FM3810
• Intrinsically Safe for Class I, Division 1,
Groups A, B, C & D. Class II, Division 1,
Groups E, F & G and Class III, Division 1,
Class I, Zone 0 in Hazardous Locations, AEx
ia IIC
• Nonincendive for Class I, Division 2, Groups
A, B, C & D. Class II, Division 2, Groups F &
G, Class I, Zone 2, Groups IIC, in Hazardous
Locations.
• Outdoor hazardous locations, NEMA TYPE
4X.
• Temperature Class: T4
• Ambient temperature: –60 to 60°C
• Entity Installation Requirements
Vmax ≥ Voc or Uo or Vt, Imax ≥ Isc or Io or It,
Pmax (or Po) ≤ Pi, Ca or Co ≥ Ci + Ccable,
La or Lo ≥ Li + Lcable
Note 3. Installation
• Barrier must be installed in an enclosure that
meets the requirements of ANSI/ISA S82.01.
• Control equipment connected to barrier must
not use or generate more than 250 V rms or
V dc.
• Installation should be in accordance with
ANSI/ISA RP12.6 “Installation of Intrinsically
Safe Systems for Hazardous (Classied)
Locations” and the National Electric Code
(ANSI/NFPA 70).
• The conguration of associated apparatus
must be FMRC Approved.
• Dust-tight conduit seal must be used when
installed in a Class II, III, Group E, F and G
environments.
• Associated apparatus manufacturer’s
installation drawing must be followed when
installing this apparatus.
• The maximum power delivered from the
barrier must not exceed 1 W.
• Note a warning label worded
“SUBSTITUTION OF COMPONENTS MAY
IMPAIR INTRINSIC SAFETY,” and “INSTALL
IN ACCORDANCE WITH DOC. No. IFM022A12”
IM 01C25F01-01E
<2. Handling Cautions>
2-5
Note 4. Maintenance and Repair
• The instrument modication or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation is prohibited and will void
Factory Mutual Intrinsically safe and
Nonincendive Approval.
[Intrinsically Safe]
Hazardous LocationNonhazardous Location
Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G
Class 1, Zone 0 in
Hazardous (Classified)
Locations AEx ia IIC
Pressure Transmitters
+
Supply
Hazardous LocationNonhazardous Location
Class I, II, Division 2,
Groups A, B, C, D, F, G
Class 1, Zone 2, Group IIC,
in Hazardous (Classified)
Locations
Pressure Transmitters
Supply
–
[Nonincendive]
+
–
Safety Barrier
+
+
–
–
Not Use
Safety Barrier
b. FM Explosionproof Type
Caution for FM explosionproof type.
Note 1. Model EJX/EJA-E Series pressure
transmitters with optional code /FF1 are
applicable for use in hazardous locations.
• Explosionproof for Class I, Division 1,
Groups B, C and D.
• Dust-ignitionproof for Class II/III, Division 1,
Groups E, F and G.
• Enclosure rating: NEMA TYPE 4X.
• Temperature Class: T6
• Ambient Temperature: –40 to 60°C
• Supply Voltage: 42 V dc max.
• Output signal: 4 to 20 mA
General
Purpose
Equipment
+
–
F0203-1.ai
General
Purpose
Equipment
+
–
F0203-2.ai
Note 2. Wiring
• All wiring shall comply with National Electrical
Code ANSI/NFPA70 and Local Electrical
Codes.
• When installed in Division 1, “FACTORY
SEALED, CONDUIT SEAL NOT
REQUIRED.”
Note 3. Operation
• Keep the “WARNING” nameplate attached to
the transmitter.
WARNING: OPEN CIRCUIT BEFORE
REMOVING COVER. FACTORY SEALED,
CONDUIT SEAL NOT REQUIRED.
INSTALL IN ACCORDANCE WITH THE
USERS MANUAL IM 01C25.
• Take care not to generate mechanical
sparking when accessing to the instrument
and peripheral devices in a hazardous
location.
Note 4. Maintenance and Repair
• The instrument modication or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation is prohibited and will void
Factory Mutual Explosionproof Approval.
c. FM Intrinsically Safe Type/FM
Explosionproof Type
Model EJX/EJA-E Series pressure transmitters
with optional code /FU1 or /V1U1 can be
selected the type of protection (FM Intrinsically
Safe or FM Explosionproof) for use in
hazardous locations.
Note 1. For the installation of this transmitter,
once a particular type of protection is
selected, any other type of protection
cannot be used. The installation must be in
accordance with the description about the
type of protection in this instruction manual.
Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label other
than the selected type of protection when
the transmitter is installed.
IM 01C25F01-01E
<2. Handling Cautions>
2-6
2.9.2 CSA Certication
a. CSA Intrinsically Safe Type
Caution for CSA Intrinsically safe and
nonincendive type. (Following contents refer to
“DOC No. ICS013-A13”)
Note 1. Model EJX/EJA-E Series differential,
gauge, and absolute pressure transmitters
with optional code /CS1 are applicable for
use in hazardous locations
Certicate: 1606623
[For CSA C22.2]
Groups A, B, C & D, Class II, Division 1,
Groups E, F & G, Class III, Division 1
• Nonincendive for Class I, Division 2, Groups
A, B, C & D, Class II, Division 2, Groups E, F
& G, Class III, Division 1
• Enclosure: NEMA TYPE 4X
• Temp. Code: T4
• Amb. Temp.: –50* to 60°C
* –15°C when /HE is specied.
• Process Temperature: 120°C max.
[For CSA E60079]
• Applicable Standard: CAN/CSA E60079-11,
CAN/CSA E60079-15, IEC 60529:2001
• Ex ia IIC T4, Ex nL IIC T4
• Ambient Temperature: –50* to 60°C
* –15°C when /HE is specied.
• Max. Process Temp.: 120°C
• Enclosure: IP66/IP67
Note 2. Entity Parameters
• Intrinsically safe ratings are as follows:
Maximum Input Voltage (Vmax/Ui) = 30 V
Maximum Input Current (Imax/Ii) = 200 mA
Maximum Input Power (Pmax/Pi) = 0.9 W
Maximum Internal Capacitance (Ci) = 10 nF
Maximum Internal Inductance (Li) = 0 µH
• Type "n" or Nonincendive ratings are as
follows:
Maximum Input Voltage (Vmax/Ui) = 30 V
Maximum Internal Capacitance (Ci) = 10 nF
Maximum Internal Inductance (Li) = 0 µH
• Installation Requirements
Uo ≤ Ui, Io ≤ Ii, Po ≤ Pi,
Co ≥ Ci + Ccable, Lo ≥ Li + Lcable
Voc ≤ Vmax, Isc ≤ Imax,
Ca ≥ Ci + Ccable, La ≥ Li + Lcable
Uo, Io, Po, Co, Lo, Voc, Isc, Ca and La are
parameters of barrier.
Note 3. Installation
• In any safety barreir used output current
must be limited by a resistor 'R' such that
Io=Uo/R or Isc=Voc/R.
• The safety barrier must be CSA certied.
• Input voltage of the safety barrier must be
less than 250 Vrms/Vdc.
• Installation should be in accordance with
Canadian Electrical Code Part I and Local
Electrical Code.
• Dust-tight conduit seal must be used when
installed in Class II and III environments.
• The instrument modication or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation and Yokogawa Corporation
of America is prohibited and will void
Canadian Standards Intrinsically safe and
nonincendive Certication.
[Intrinsically Safe]
Hazardous LocationNonhazardous Location
Group IIC, Zone 0
Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G
Pressure Transmitters
+
Supply
Hazardous LocationNonhazardous Location
Group IIC, Zone 2
Class I, II, Division 2,
Groups A, B, C, D, F, G
Class III, Division 1.
Pressure Transmitters
Supply
–
[Nonincendive]
+
–
Safety Barrier
+
+
–
–
Not Use
Safety Barrier
CSA Certified
Equipment
([nL] or
nonincendive)
b. CSA Explosionproof Type
Caution for CSA explosionproof type.
Note 1. Model EJX/EJA-E Series pressure
transmitters with optional code /CF1 are
applicable for use in hazardous locations:
• Dustignition-proof for Class II/III, Groups E, F
and G.
• Enclosure: NEMA TYPE 4X
• Temperature Code: T6...T4
• Ex d IIC T6...T4
• Enclosure: IP66/IP67
• Maximum Process Temperature: 120°C (T4),
100°C (T5), 85°C (T6)
• Ambient Temperature: –50* to 75°C (T4),
–50* to 80°C (T5), –50* to 75°C (T6)
* –15°C when /HE is specied.
• Supply Voltage: 42 V dc max.
• Output Signal: 4 to 20 mA dc
Note 2. Wiring
• All wiring shall comply with Canadian
Electrical Code Part I and Local Electrical
Codes.
• In hazardous location, wiring shall be in
conduit as shown in the gure.
• WARNING:
A SEAL SHALL BE INSTALLED WITHIN
50cm OF THE ENCLOSURE.
UN SCELLEMENT DOIT ÊTRE INSTALLÉ À
MOINS DE 50cm DU BOÎTIER.
• WARNING:
WHEN INSTALLED IN CL.I, DIV 2, SEAL
NOT REQUIRED.
UNE FOIS INSTALLÉ DANS CL I, DIV 2,
AUCUN JOINT N'EST REQUIS.
Non-Hazardous
Locations
Non-hazardous
Location
Equipment
42 V DC Max.
4 to 20 mA DC
Signal
Non-Hazardous
Locations
Non-hazardous
Location
Equipment
42 V DC Max.
4 to 20 mA DC
Signal
Hazardous Locations Division 1
50 cm Max.
Sealing Fitting
Hazardous Locations Division 2
Sealing Fitting
Conduit
Transmitter
Transmitter
PULSE
SUPPLY
CHECK
ALARM
F0205-1.ai
PULSE
SUPPLY
CHECK
ALARM
F0205-2.ai
• All wiring shall comply with local installation
requirements and local electrical code.
• In hazardous locations, the cable entry
devices shall be of a certied ameproof
type, suitable for the conditions of use and
correctly installed.
• Unused apertures shall be closed with
suitable ameproof certied blanking
elements. (The plug attached is ameproof
certied.)
Note 3. Operation
• WARNING:
AFTER DE-ENERGIZING, DELAY 5
MINUTES BEFORE OPENING.
APRÉS POWER-OFF, ATTENDRE 5
MINUTES AVANT D'OUVRIR.
• WARNING:
WHEN AMBIENT TEMPERATURE ≥ 65°C,
USE THE HEAT-RESISTING CABLES ≥
90°C.
QUAND LA TEMPÉRATURE AMBIANTE
≥ 65°C, UTILISEZ DES CÂBLES
RÉSISTANTES Á LA CHALEUR ≥ 90°C.
• Take care not to generate mechanical
sparking when accessing to the instrument
and peripheral devices in a hazardous
location.
Note 4. Maintenance and Repair
• The instrument modication or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation and Yokogawa Corporation of
America is prohibited and will void Canadian
Standards Explosionproof Certication.
c CSA Intrinsically Safe Type/CSA
Explosionproof Type
Model EJX/EJA-E Series pressure transmitters
with optional code /CU1 or /V1U1 can be
selected the type of protection (CSA Intrinsically
Safe or CSA Explosionproof) for use in
hazardous locations.
Note 1. For the installation of this transmitter,
once a particular type of protection is
selected, any other type of protection
cannot be used. The installation must be in
accordance with the description about the
type of protection in this instruction manual.
Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label other
than the selected type of protection when
the transmitter is installed.
IM 01C25F01-01E
<2. Handling Cautions>
2-8
2.9.3 ATEX Certication
(1) Technical Data
a. ATEX Intrinsically Safe Ex ia
Caution for ATEX Intrinsically safe type.
Note 1. Model EJX/EJA-E Series pressure
transmitters with optional code /KS21 for
potentially explosive atmospheres:
• No. DEKRA 11ATEX0228 X
• Applicable Standard:
EN 60079-0:2009, EN 60079-11:2007,
EN 60079-26:2007, EN 61241-11:2006
• Type of Protection and Marking code:
Ex ia IIC T4 Ga
Ex ia IIIC T85 ºC T100 ºC T120 ºC Db
• Group: II
• Category: 1G, 2D
• Ambient Temperature for EPL Ga:
–50 to 60°C
• Ambient Temperature for EPL Db:
–30* to 60°C
* –15°C when /HE is specied.
• Process Temperature (Tp.): 120°C max.
• Maximum Surface Temperature for EPL Db:
T85°C (Tp.: 80°C)
T100°C (Tp.: 100°C)
T120°C (Tp.: 120°C)
• Enclosure: IP66 / IP67
Note 2 Electrical Data
• In type of explosion protection intrinsic safety
Ex ia IIC or Ex ia IIIC, only for connection to a
certied intrinsically safe circuit with following
maximum values:
Ui = 30 V
Ii = 200 mA
Pi = 0.9 W
(Linear Source)
Maximum internal capacitance; Ci = 27.6 nF
Maximum internal inductance; Li = 0 µH
Note 3. Installation
• Refer to the control drawing. All wiring shall
comply with local installation requirements.
[Control Drawing]
Hazardous Location
Transmitter
+
Supply
–
*1: In any safety barriers used the output current must be
limited by a resistor “R” such that Io=Uz/R.
Nonhazardous Location
+
Safety Barrier
–
F0206.ai
*1
Note 4. Maintenance and Repair
• The instrument modication or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation is prohibited and will void
DEKRA Intrinsically safe Certication.
Note 5. Special Conditions for Safe Use
WARNING
• In the case where the enclosure of the
Pressure Transmitter is made of aluminium,
if it is mounted in an area where the use of
category 1 G apparatus is required, it must
be installed such, that, even in the event of
rare incidents, ignition sources due to impact
and friction sparks are excluded.
• Electrostatic charge may cause an exlosion
hazard. Avoid any actions that cause the
gerenation of eletrostatic charge, such as
rubbing with a dry cloth on coating face of
the product.
• In case of the enclosure of the Pressure
Transmitter with paint layers, if it is mounted
in an area where the use of category 2D
apparatus is required, it shall be installed in
such a way that the risk from electrostatic
discharges and propagating brush
discharges caused by rapid ow of dust is
avoided.
• To satisfy IP66 or IP67, apply waterproof
glands to the electrical connection port.
• When the lightning protector option is
specied, the apparatus is not capable
of withstanding the 500V insulation test
required by EN60079-11. This must be taken
into account when installing the apparatus.
IM 01C25F01-01E
<2. Handling Cautions>
2-9
b. ATEX Flameproof Type
Caution for ATEX ameproof type.
Note 1. Model EJX/EJA-E Series pressure
transmitters with optional code /KF22 for
potentially explosive atmospheres:
• No. KEMA 07ATEX0109 X
• Applicable Standard: EN 60079-0:2009,
EN 60079-1:2007, EN 60079-31:2009
• Type of Protection and Marking Code:
Ex d IIC T6...T4 Gb, Ex tb IIIC T85°C Db
• Group: II
• Category: 2G, 2D
• Enclosure: IP66/IP67
• Temperature Class for gas-poof:
T6, T5, and T4
• Ambient Temperature for gas-proof:
–50 to 75°C (T6), –50 to 80°C (T5), and
–50 to 75°C (T4)
• Maximum Process Temperature (Tp.) for
gas-proof:
85°C (T6), 100°C (T5), and 120°C (T4)
• Maximum Surface Temperature for dustproof:
T85°C (Tamb.: –30* to 75°C, Tp.: 85°C)
* –15°C when /HE is specied.
Note 2. Electrical Data
• Supply voltage: 42 V dc max.
• Output signal: 4 to 20 mA
Note 3. Installation
• All wiring shall comply with local installation
requirement.
• The cable entry devices shall be of a certied
ameproof type, suitable for the conditions of
use.
Note 4. Operation
• Keep the “WARNING” label attached to the
transmitter.
WARNING: AFTER DE-ENERGIZING,
DELAY 5 MINUTES BEFORE OPENING.
WHEN THE AMBIENT TEMP.≥65°C, USE
HEAT-RESISTING CABLE AND CABLE
GLAND ≥90°C.
• Take care not to generate mechanical
sparking when accessing to the instrument
and peripheral devices in a hazardous
location.
Note 5. Special Conditions for Safe Use
WARNING
• Electrostatic charge may cause an exlosion
hazard. Avoid any actions that cause the
gerenation of eletrostatic charge, such as
rubbing with a dry cloth on coating face of the
product.
• In the case where the enclosure of the
Pressure Transmitter is made of aluminium,
if it is mounted in an area where the use of
category 2D apparatus is required, it shall
be installed in such a way that the risk from
electrostatic discharges and propagating
brush discharges caused by rapid ow of
dust is avoided.
• The instrument modication or parts
replacement by other than an authorized
Representative of Yokogawa Electric
Corporation is prohibited and will void the
certication.
• To satisfy IP66 or IP67, apply waterproof
glands to the electrical connection port.
c. ATEX Intrinsically Safe Type/ATEX
Flameproof Type
Model EJX/EJA-E Series pressure transmitters
with optional code /KU22 or /V1U1 can
be selected the type of protection ATEX
Flameproof, Intrinsically Safe. Ex ia, or Ex ic for
use in hazardous area.
Note 1. For the installation of this transmitter,
once a particular type of protection is
selected, any other type of protection
cannot be used. The installation must be in
accordance with the description about the
type of protection in this user’s manual.
Note 2. For combined approval types Once a
device of multiple approval type is installed,
it should not be re-installed using any
other approval types. Apply a permanent
mark in the check box of the selected
approval type on the certication label on
the transmitter to distinguish it from unused
approval types.
IM 01C25F01-01E
<2. Handling Cautions>
● ATEX Intrinsically Safe Ex ic
Caution for ATEX intrinsically safe Ex ic
• Applicable Standard:
EN 60079-0:2009/EN 60079-0:2012,
EN 60079-11:2012
• Type of Protection and Marking Code:
II 3G Ex ic IIC T4 Gc
• Ambient Temperature: –30* to +60°C
* –15°C when /HE is specied.
• Ambient Humidity:
0 to 100% (No condensation)
• Maximum Process Temperature: 120°C
• IP Code: IP66
WARNING
• Electrostatic charge may cause an explosion
hazard. Avoid any actions that cause the
gerenation of eletrostatic charge, such as
rubbing with a dry cloth on coating face of
the product.
• When the lightning protector option is
specied, the apparatus is not capable
of withstanding the 500V insulation test
required by EN60079-11. This must be taken
into account when installing the apparatus.
• Ambient pollution degree: 2
• Overvoltage category: I
Note 1. Electrical Data
Ui = 30 V
Ci = 27.6 nF
Li = 0 µH
(2) Electrical Connection
A mark indicating the electrical connection type
is stamped near the electrical connection port.
These marks are as followed.
Screw SizeMarking
Note 2. Installation
• All wiring shall comply with local installation
requirements. (refer to the control drawing)
ISO M20 × 1.5 female
ANSI 1/2 NPT female
• Cable glands, adapters and/or blanking
elements shall be of Ex “n”, Ex “e” or Ex “d”
and shall be installed so as to maintain the
specied degree of protection (IP Code) of
the transmitters.
Location of the mark
Note 3. Maintenance and Repair
• The instrument modication or parts
replacement by other than authorized
representative of Yokogawa Electric
(3) Installation
Corporation is prohibited and will void ATEX
intrinsically safe.
Hazardous Area
Transmitter
[Control drawing]
+
–
Nonhazardous Area
Associated
Apparatus
WARNING
• All wiring shall comply with local installation
requirements and the local electrical code.
• There is no need for conduit seal in Division
1 and Division 2 hazardous locations
because this product is sealed at the factory.
2-10
M
N orW
F0208.ai
Note 4. Specic Conditions of Use
F0207.ai
(4) Operation
WARNING
• OPEN CIRCUIT BEFORE REMOVING
COVER. INSTALL IN ACCORDANCE WITH
THIS USER’S MANUAL
• Take care not to generate mechanical
sparking when access to the instrument and
peripheral devices in a hazardous location.
IM 01C25F01-01E
<2. Handling Cautions>
2-11
(5) Maintenance and Repair
WARNING
The instrument modication or parts replacement
by other than an authorized Representative of
Yokogawa Electric Corporation is prohibited and
will void the certication.
(6) Name Plate
Name plate
Tag plate for flameproof type
No. KEMA 07ATEX0109 X
Ex d IIC T6...T4 Gb, Ex tb IIIC T85°C Db
Enlcosure : IP66/IP67
TEMP. CLASS T6 T5 T4
MAX PROCESS TEMP.(Tp.) 85 100 120 °C
Tamb. -50 to 75 80 75 °C
T85°C(Tamb.:-30(-15) to 75°C, Tp.:85°C)(for Dust)
*3
WARNING
Tag plate for intrinsically safe type
D
AFTER DE-ENERGIZING, DELAY 5 MINUTES BEFORE
OPENING.
WHEN THE AMBIENT TEMP. ≥ 65°C, USE THE
HEAT-RESISTING CABLE & CABLE GLAND ≥ 90°C
POTENTIAL ELECTROSTATIC CHARGING HAZARD
No. DEKRA 11ATEX 0228 X
Ex ia IIC T4 Ga Ta: -50 TO 60°C
Ex ia IIIC T85°C T100°C T120°C Db Ta:-30(-15) TO 60°C
IP66/IP67
MAX. PROCESS TEMP.(Tp.) 120°C
T85°C(Tp.:80°C), T100°C(Tp.:100°C), T120°C(Tp.:120°C)
Ui=30V, Ii=200mA , Pi=0.9W, Ci=27.6nF, Li=0µH
*1: The rst digit in the three numbers next to the nine
letters of the serial number appearing after “NO.”
on the nameplate indicates the year of production.
The following is an example of a serial number for a
product that was produced in 2010:
91K819857 032
The year 2010
*2: “180-8750” is a zip code which represents the
following address.
2-9-32 Nakacho, Musashino-shi, Tokyo Japan
*3: The identication number of Notied Body.
2.9.4 IECEx Certication
Model EJX Series pressure transmitters with
optional code /SU2 can be selected the type of
protection (IECEx Intrinsically Safe/type n or
ameproof) for use in hazardous locations.
Note 1. For the installation of this transmitter,
once a particular type of protection is
selected, any other type of protection
cannot be used. The installation must be in
accordance with the description about the
type of protection in this instruction manual.
Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label other
than the selected type of protection when
the transmitter is installed.
a. IECEx Intrinsically Safe Type / type n
Caution for IECEx Intrinsically safe and type n.
*3
WARNING
D
POTENTIAL ELECTROSTATIC
CHARGING HAZARD
- SEE USER’S MANUAL
Tag plate for intrinsically safe Ex ic
Ex ic IIC T4 Gc
IP66
Tamb -30(-15) TO 60°C
MAX. PROCESS TEMP. 120°C
Ui=30V, Ci=27.6nF, Li=0µH
WARNING
POTENTIAL ELECTROSTATIC
CHARGING HAZARD
- SEE USER’S MANUAL
MODEL: Specied model code.
STYLE: Style code.
SUFFIX: Specied sufx code.
SUPPLY: Supply voltage.
OUTPUT: Output signal.
MWP: Maximum working pressure.
CAL RNG: Specied calibration range.
NO.: Serial number and year of production*1.
TOKYO 180-8750 JAPAN:
The manufacturer name and the address*2.
F0209.ai
Note 1. Model EJX Series differential, gauge,
and absolute pressure transmitters with
optional code /SU2 are applicable for use
in hazardous locations
• Intrinsically safe ratings are as follows:
Maximum Input Voltage (Vmax/Ui) = 30 V
Maximum Input Current (Imax/Ii) = 200 mA
Maximum Input Power (Pmax/Pi) = 0.9 W
Maximum Internal Capacitance (Ci) = 10 nF
Maximum Internal Inductance (Li) = 0 µH
• Type "n" ratings are as follows:
Maximum Input Voltage (Vmax/Ui) = 30 V
Maximum Internal Capacitance (Ci) = 10 nF
Maximum Internal Inductance (Li) = 0 µH
IM 01C25F01-01E
<2. Handling Cautions>
2-12
• Installation Requirements
Uo ≤ Ui, Io ≤ Ii, Po ≤ Pi,
Co ≥ Ci + Ccable, Lo ≥ Li + Lcable
Voc ≤ Vmax, Isc ≤ Imax,
Ca ≥ Ci + Ccable, La ≥ Li + Lcable
Uo, Io, Po, Co, Lo, Voc, Isc, Ca and La are
parameters of barrier.
Note 3. Installation
• In any safety barrier used output current
must be limited by a resistor 'R' such that
Io=Uo/R.
• The safety barrier must be IECEx certied.
• Input voltage of the safety barrier must be
less than 250 Vrms/Vdc.
• The instrument modication or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation and will void IECEx Intrinsically
safe and type n certication.
[Intrinsically Safe]
Hazardous LocationNonhazardous Location
Group IIC, Zone 0
[type n]
IECEx certified
Safety Barrier
+
+
–
–
Not Use
Safety Barrier
IECEx Certified
Equipment [nL]
Pressure Transmitters
+
Supply
Hazardous LocationNonhazardous Location
Group IIC, Zone 2
Pressure Transmitters
Supply
–
+
–
b. IECEx Flameproof Type
Caution for IECEx ameproof type.
General
Purpose
Equipment
+
–
F0210-1.ai
+
–
F0210-2.ai
• Maximum Process Temperature: 120°C (T4),
100°C (T5), 85°C (T6)
• Ambient Temperature: –50 to 75°C (T4),
–50 to 80°C (T5), –50 to 75°C (T6)
• Supply Voltage: 42 V dc max.
• Output Signal: 4 to 20 mA dc
Note 2. Wiring
• In hazardous locations, the cable entry
devices shall be of a certied ameproof
type, suitable for the conditions of use and
correctly installed.
• Unused apertures shall be closed with
suitable ameproof certied blanking
elements.
Note 3. Operation
• WARNING:
AFTER DE-ENERGIZING, DELAY 5
MINUTES BEFORE OPENING.
• WARNING:
WHEN AMBIENT TEMPERATURE ≥ 65°C,
USE THE HEAT-RESISTING CABLES ≥
90°C.
• Take care not to generate mechanical
sparking when accessing to the instrument
and peripheral devices in a hazardous
location.
Note 4. Maintenance and Repair
• The instrument modication or parts
replacement by other than authorized
representative of Yokogawa Electric
Corporation is prohibited and will void IECEx
Certication.
2.10 EMC Conformity Standards
EN61326-1 Class A, Table2 (For use in industrial
locations)
EN61326-2-3
CAUTION
Note 1. Model EJX/EJA-E Series pressure
transmitters with optional code /SF2 or
/SU2 are applicable for use in hazardous
locations:
To meet EMC regulations, Yokogawa
recommends that customers run signal wiring
through metal conduits or use shielded twistedpair cabling when installing EJX/EJA-E series
transmitters in a plant.
IM 01C25F01-01E
<2. Handling Cautions>
2-13
2.11 Pressure Equipment
Directive (PED)
(1) General
• EJX/EJA-E Series pressure transmitters are
categorized as piping under the pressure
accessories section of directive 97/23/EC,
which corresponds to Article 3, Paragraph 3 of
PED, denoted as Sound Engineering Practice
(SEP).
• EJ510-D, EJ530-D, EJX610A-D,
and EJX630A-D can be used above 200
bar and therefore considered as a part of a
pressure retaining vessel where category III,
Module H applies. These models with option
code /PE3 conform to that category.
(2) Technical Data
• Models without /PE3
Article 3, Paragraph 3 of PED, denoted as
Sound Engineering Practice (SEP).
• Models with /PE3
Module: H
Type of Equipment: Pressure Accessory-Vessel
Type of uid: Liquid and Gas
Group of uid: 1 and 2
Model
EJ510
EJX610A
EJ510,
EJX610A
with code /
PE3
EJ530,
EJX630A
EJ530,
EJX630A
with code /
PE3
*1: PS is maximum pressure for vessel itself based on
*2: Referred to Table 1 covered by ANNEX II of EC Directive
Capsule
code
A, B, C1000.110
D7000.170
D7000.170III
A, B, C1000.110
D7000.170
D7000.170III
Pressure Equipment Directive 97/23/EC. Refer to
General Specication for maximum working pressure of a
transmitter.
on Pressure Equipment Directive 97/23/EC
PS*
(bar)
1
V(L)
PS.V
(bar.L)
Category*
Article 3,
Paragraph 3
(SEP)
Article 3,
Paragraph 3
(SEP)
(3) Operation
CAUTION
• The temperature and pressure of uid should
be maintained at levels that are consistent
with normal operating conditions.
• The ambient temperature should be
maintained at a level that is consistent with
normal operating conditions.
• Please take care to prevent water hammer
and the like from inducing excessive
pressures in pipes and valves. If phenomena
are likely, install a safety valve or take
some other appropriate measure to prevent
pressure from exceeding PS.
• Take appropriate measures at the device or
system level to protect transmitters if they
are to be operated near an external heat
source.
2.12 Low Voltage Directive
Applicable standard: EN61010-1
(1) Pollution Degree 2
"Pollution degree" describes the degree to
2
which a solid, liquid, or gas which deteriorates
dielectric strength or surface resistivity is
adhering. " 2 " applies to normal indoor
atmosphere. Normally, only non-conductive
pollution occurs. Occasionally, however,
temporary conductivity caused by condensation
must be expected.
(2) Installation Category I
"Overvoltage category (Installation category)"
describes a number which denes a transient
overvoltage condition. It implies the regulattion
for impulse withstand voltage. " I " applies to
electrical equipment which is supplied from the
circuit when appropriate transient overvoltage
control means (interfaces) are provided.
IM 01C25F01-01E
<3. Component Names>
3. Component Names
3-1
Integral
indicator
Mounting screw
Amplifier Cover
(Note 1)
(Note 2)
Slide switch
Range-setting
(Note 1)
switch
(See section 7.5)
Transmitter section
External indicator
conduit connection
CPU assembly
Burnout direction switch
BO HL
WR ED
Write protection switch
(Note 1)
Conduit
connection
Zeroadjustment
screw
Burnout direction switch (BO)
Burnout Direction
Switch Position
Burnout Direction
Note 1: See subsection 9.2, “Model and Sufx Codes,” for details.
Note 2: Applicable for BRAIN/HART communication type. Set the switches as shown in the gure above to set the burn-out direction
and write protection. The Burnout switch is set to the H side for delivery (unless option code /C1 or /C2 is specied in the order),
and the hardware write protection switch is set to E side.The setting of the switches can be conrmed via communication. An
external zero adjustment screw can only be disabled by communication. To disable the screw, set a parameter before activating
the hardware write protect function. See each communication manual.
HLHL
HIGHLOW
Write Protection
Switch Position
Write Protection
Hardware write protection switch (WR)
HL
ED
NO
(Write enabled)
HL
ED
YES
(Write disabled)
Figure 3.1 Component Names
Table 3.1 Display Symbol
Display SymbolMeaning of Display Symbol
The output signal being zero-adjusted is increasing.
The output signal being zero-adjusted is decreasing.
Write protect function is enabled.
F0301.ai
F0302.ai
IM 01C25F01-01E
<4. Installation>
4. Installation
4-1
4.1 Precautions
Before installing the transmitter, read the cautionary
notes in section 2.4, “Selecting the Installation
Location.” For additional information on the ambient
conditions allowed at the installation location, refer
to section 9.1 “Standard Specications.”
IMPORTANT
• When welding piping during construction,
take care not to allow welding currents to
ow through the transmitter.
• Do not step on this instrument after
installation.
• For the EJ530 and EJX630A whose
capsule code is A, B or C, the pipe of the
atmospheric opening is located on the
pressure detecting section. The opening
must not face upward. See subsection 5.1.1.
• D capsule of EJ530 and EJX630A is
of sealed gauge reference and the change
in atomospheric pressure may affect the
measurement.
Vertical pipe mounting
U-bolt nut (L)
U-bolt nut (S)
Mounting bracket
U-bolt (S)
Horizontal pipe mounting
50 mm (2-inch) pipe
U-bolt (L)
U-bolt nut (L)
Mounting bracket
50 mm (2-inch) pipe
4.2 Mounting
■ The impulse piping connection port of the
transmitter is covered with a plastic cap to
protect against dust. This cap must be removed
before connecting the piping. (Be careful not
to damage the threads when removing these
caps. Do not insert a screw driver or other
tool between the cap and the port threads to
remove the cap.)
■ The transmitter can be mounted on a nominal
50 mm (2-inch) pipe using the mounting bracket
supplied, as shown in Figure 4.1.
■ The user should prepare the mating gasket for
the transmitters with Process connection code
8 and 9. See Figure 4.2.
U-bolt nut (S)
U-bolt (S)
U-bolt (L)
Figure 4.1 Transmitter Mounting
Gasket
Figure 4.2 Gasketing
F0401.ai
F0402.ai
IM 01C25F01-01E
<4. Installation>
4-2
IMPORTANT
Tighten the hexagonal nut part of the capsule
assembly. See Figure 4.3.
Capsule assembly
F0403.ai
Figure 4.3 Tightening Transmitter
4.3 Rotating Transmitter Section
The transmitter section can be rotated
approximately 360° (180° to either direction or
between -90° and +270° from the original position
at shipment, depending on the conguration of
the instrument.) It can be xed at any angle within
above range.
Transmitter section
Setscrew
Pressure-detector section
Stopper
Figure 4.4 Rotating Transmitter Section
4.4 Changing the Direction of
Integral Indicator
IMPORTANT
Always turn OFF power, release pressure and
remove a transmitter to non-hazardous area
before disassembling and reassmbling an
indicator.
F0404.ai
1) Remove the two setscrews that fasten the
transmitter section and capsule assembly,
using the Allen wrench.
2) Rotate the transmitter section slowly and stop it
at designated position. For the EJ530 and
EJX630A whose capsule code is A, B or C, the
pipe of the atmospheric opening may interfere
with the stopper and disturb further rotation.
In that case, screw off the pipe rst, rotate the
housing, and then screw in the pipe by hand
again.
3) Tighten the two setscrews to a torque of
1.5 N·m.
IMPORTANT
Do not rotate the transmitter section more than
the above limit.
An integral indicator can be installed in the
following three directions. Follow the instructions in
section 8.4 for removing and attaching the integral
indicator.
F0405.ai
Figure 4.5 Integral Indicator Direction
IM 01C25F01-01E
<5. Installing Impulse Piping>
5. Installing Impulse Piping
5-1
5.1 Impulse Piping Installation
Precautions
The impulse piping that connects the process
outputs to the transmitter must convey the process
pressure accurately. If, for example, gas collects in
a liquidlled impulse line, or the drain for a gas-lled
impulse line becomes plugged, it will not convey the
pressure accurately. Since this will cause errors in
the measurement output, select the proper piping
method for the process uid (gas, liquid, or steam).
Pay careful attention to the following points when
routing the impulse piping and connecting the
impulse piping to a transmitter.
5.1.1 Connecting Impulse Piping to a
Transmitter
IMPORTANT
The transmitter can be installed in horizontal
impulse piping conguration, tilting the
transmitter's position up to 90°. When tilting,
observe that the pipe (for Model EJ530 and
EJX630A with measurement span code A, B,
and C) is positioned horizontal downwards, or
any place between them, as shown in Figure 5.1
The zero-adjustment screw must be positioned
downwards for all the models.
The pipe (open to atmosphere) is positioned horizontal.
5.1.2 Routing the Impulse Piping
(1) Process Pressure Tap Angles
If condensate, gas, sediment or other extraneous
material in the process piping gets into the impulse
piping, pressure measurement errors may result. To
prevent such problems, the process pressure taps
must be angled as shown in gure 5.2 according to
the kind of uid being measured.
NOTE
• If the process uid is a gas, the taps must be
vertical or within 45° either side of vertical.
• If the process uid is a liquid, the taps must
be horizontal or below horizontal, but not
more than 45° below horizontal.
• If the process uid is steam or other
condensing vapor, the taps must be
horizontal or above horizontal, but not more
than 45° above horizontal.
[Gas]
45°
Pressure
taps
Process
piping
Figure 5.2 Process Pressure Tap Angle
45°
45°45°
(For Horizontal Piping)
(2) Position of Process Pressure Taps and
Transmitter
45°
[Steam][Liquid]
45°
F0502.ai
Pipe
(backside of the instrument)
Zero-adjustment screw
If the zero-adjustment screw is positioned other than
donwards after installation, rotate the housing unitl it is
positioned downwards.
F0501.ai
Figure 5.1 Horizontal Impulse Piping Connection
If condensate (or gas) accumulates in the impulse
piping, it should be removed periodically by
opening the drain (or vent) plugs. However, this will
generate a transient disturbance in the pressure
measurement, and therefore it is necessary to
position the taps and route the impulse piping so
that any extraneous liquid or gas generated in the
leadlines returns naturally to the process piping.
• If the process uid is a gas, then as a rule the
transmitter must be located higher than the
process pressure taps.
• If the process uid is a liquid or steam, then as a
rule the transmitter must be located lower than
the process pressure taps.
IM 01C25F01-01E
<5. Installing Impulse Piping>
5-2
(3) Impulse Piping Slope
The impulse piping must be routed with only an
upward or downward slope. Even for horizontal
routing, the impulse piping should have a slope of
at least 1/10 to prevent condensate (or gases) from
accumulating in the pipes.
(4) Preventing Freezing
If there is any risk that the process uid in the
impulse piping or transmitter could freeze, use a
steam jacket or heater to maintain the temperature
of the uid.
NOTE
After completing the connections, close the
valves on the process pressure taps (main
valves), the valves at the transmitter (stop
valves), and the impulse piping drain valves,
so that condensate, sediment, dust and other
extraneous material cannot enter the impulse
piping.
Tap valve
Union or flange
Stop valve
Tee
Union or flange
Drain valve
Drain plug
Figure 5.3 Impulse Piping Connection Examples
Stop valve
F0503.ai
5.2 Impulse Piping Connection
Examples
Figure 5.3 shows examples of typical impulse
piping connections. Before connecting the
transmitter to the process, study the transmitter
installation location, the process piping layout,
and the characteristics of the process uid
(corrosiveness, toxicity, ammability, etc.), in order
to make appropriate changes and additions to the
connection congurations.
Note the following points when referring to these
piping examples.
• If the impulse line is long, bracing or supports
should be provided to prevent vibration.
• The impulse piping material used must
be compatible with the process pressure,
temperature, and other conditions.
• A variety of process pressure tap valves (main
valves) are available according to the type
of connection (anged, screwed, welded),
construction (globe, gate, or ball valve),
temperature and pressure. Select the type of
valve most appropriate for the application.
IM 01C25F01-01E
<6. Wiring>
6. Wiring
6-1
6.1 Wiring Precautions
IMPORTANT
• Lay wiring as far as possible from electrical
noise sources such as large capacity
transformers, motors, and power supplies.
• Remove the electrical connection dust cap
before wiring.
• All threaded parts must be treated with
waterproong sealant. (A non-hardening
silicone group sealant is recommended.)
• To prevent noise pickup, do not pass signal
and power cables through the same ducts.
• Explosion-protected instruments must
be wired in accordance with specic
requirements (and, in certain countries,
legal regulations) in order to preserve the
effectiveness of their explosion-protected
features.
• The terminal box cover is locked by an
Allen head bolt (a shrouding bolt) on ATEX
ameproof type transmitters. When the
shrouding bolt is driven clockwise using
an Allen wrench, it goes in. The cover lock
can then be released and the cover can
be opened by hand. See subsection 8.4
“Disassembly and Reassembly” for details.
• Plug and seal an unused conduit connection.
6.2 Selecting the Wiring
6.3 Connections of External
Wiring to Terminal Box
6.3.1 Power Supply Wiring Connection
Connect the power supply wiring to the SUPPLY +
and – terminals. When /AL is specied, also refer to
subsection 6.3.5.
Power supply
+
–
Figure 6.1 Power Supply Wiring Connection
6.3.2 External Indicator Connection
Available only when /AL is not specied.
Connect wiring for external indicators to the CHECK
+ and – terminals.
(Note) Use a external indicator whose internal resistance is 10 Ω
or less.
Power supply
+
–
Transmitter terminal box
Figure 6.2 External Indicator Connection
Transmitter terminal box
External indicator
PULSE
SUPPLY
CHECK
ALARM
PULSE
SUPPLY
CHECK
ALARM
F0601.ai
F0602.ai
Materials
(a) Use stranded leadwires or cables which are
the same as or better than 600 V grade PVC
insulated wire (JIS C3307) or its equivalent.
(b) Use shielded wires in areas that are susceptible
to electrical noise.
(c) In areas with higher or lower ambient
temperatures, use appropriate wires or cables.
(d) In environment where oils, solvents, corrosive
gases or liquids may be present, use wires or
cables that are resistant to such substances.
(e) It is recommended that crimp-on solderless
terminal lugs (for 4 mm screws) with insulating
sleeves be used for leadwire ends.
6.3.3 Communicator Connection
Connect the BT200 or HART Communicator to the
SUPPLY + and – terminals. (Use hooks.)
Transmitter terminal box
PULSE
SUPPLY
CHECK
ALARM
Ignore the polarity since the
BT200 is AC-coupled to the
terminal box.
BT200
Figure 6.3 BT200 Connection
Power supply
+
–
F0603.ai
IM 01C25F01-01E
<6. Wiring>
6-2
6.3.4 Check Meter Connection
Available only when /AL is not specied.
Connect the check meter to the CHECK + and
– terminals. (Use hooks.)
• A 4 to 20 mA DC output signal from the CHECK
+ and – terminals.
(Note) Use a check meter whose internal resistance is 10 Ω or
less.
Check meter
Figure 6.4 Check Meter Connection
Transmitter terminal box
PULSE
SUPPLY
CHECK
ALARM
Power supply
+
–
F0604.ai
6.3.5 Status Output Connection
When option code /AL is specied, connect the
external wiring as shown in Figure 6.5.
To congure and activate the process alarm
function and status output, it is necessary to set
some parameters. Refer to each communication
manual for procedures.
Transmitter
terminal box
SUPPLY
Use two-wire separately shielded cables.
PULSE
CHECK
ALARM
Shielded cable
External power
supply 30V DC,
120mA max
Figure 6.5 Status Output Connection
24V DC
+
250
Ω
Distributor
AC power supply
Magnetic
valve
F0605.ai
–
(1) General-use Type and Flameproof Type
Hazardous LocationNonhazardous Location
Transmitter terminal box
Distributor
(Power supply unit)
PULSE
SUPPLY
CHECK
ALARM
Receiver
instrument
F0606.ai
Figure 6.6 Connection between Transmitter and
Distributor
(2) Intrinsically Safe Type
With the intrinsically safe type, a safety barrier must
be included in the loop.
Hazardous LocationNonhazardous Location
Transmitter terminal box
Distributor
(Power supply unit)
PULSE
SUPPLY
CHECK
ALARM
Receiver
instrument
Safety barrier
F0607.ai
Figure 6.7 Connection between Transmitter and
Distributor
6.4.2 Wiring Installation
(1) General-use Type and Intrinsically Safe
Type
With the cable wiring, use a metallic conduit or
waterproof glands.
• Apply a non-hardening sealant to the terminal
box connection port and to the threads on the
exible metal conduit for waterproong.
6.4 Wiring
6.4.1 Loop Conguration
Since the DPharp uses a two-wire transmission
system, signal wiring is also used as power wiring.
DC power is required for the transmitter loop. The
transmitter and distributor are connected as shown
below.
For details of the power supply voltage and load
resistance, see section 6.6; for communications line
requirements, see section 9.1.
Flexible metal conduit
Wiring metal
conduit
Apply a non-hardening
sealant to the threads for
waterproofing.
Tee
Drain plug
Figure 6.8 Typical Wiring Using Flexible Metal
Conduit
IM 01C25F01-01E
F0608.ai
<6. Wiring>
6-3
(2) Flameproof Type
Wire cables through a ameproof packing adapter,
or use a ameproof metal conduit.
■ Wiring cable through ameproof packing
adapter.
• Apply a non-hardening sealant to the terminal
box connection port and to the threads on the
ameproof packing adapter for waterproong.
Flameproof packing
adapter
Flexible metal conduit
Wiring metal
conduit
Tee
Drain plug
Apply a non-hardening
sealant to the threads for
waterproofing.
F0609.ai
Figure 6.9 Typical Cable Wiring Using Flameproof
Packing Adapter
■ Flameproof metal conduit wiring
• A seal tting must be installed near the terminal
box connection port for a sealed construction.
• Apply a non-hardening sealant to the threads of
the terminal box connection port, exible metal
conduit and seal tting for waterproong.
Non-hazardous area
Hazardous area
Flameproof
heavy-gauge
steel conduit
Tee
Drain plug
Figure 6.10 Typical Wiring Using Flameproof Metal
Conduit
Gas sealing device
Flameproof flexible
metal conduit
Apply a non-hardening
sealant to the threads of
these fittings for
waterproofing
Seal fitting
After wiring, impregnate the fitting
with a compound to seal tubing.
F0610.ai
6.5 Grounding
Grounding is always required for the proper
operation of transmitters. Follow the domestic
electrical requirements as regulated in each
country. For a transmitter with a built-in lightning
protector, grounding should satisfy ground
resistance of 10Ω or less.
Ground terminals are located on the inside and
outside of the terminal box. Either of these terminals
may be used.
PULSE
SUPPLY
CHECK
Ground terminal
(inside)
Ground terminal
(outside)
Figure 6.11 Ground Terminals
ALARM
F0611.ai
6.6 Power Supply Voltage and
Load Resistance
When conguring the loop, make sure that the
external load resistance is within the range in the
gure below.
(Note) In case of an intrinsically safe transmitter, external load
resistance includes safety barrier resistance.
600
External
load
resistance
R (Ω)
250
R=
E–10.5
0.0244
Communication
applicable range
BRAIN and HART
010.5 16.625.242
Power supply voltage E (V DC)
Figure 6.12 Relationship between Power Supply
Voltage and External Load Resistance
IM 01C25F01-01E
F0612.ai
<7. Operation>
7. Operation
7-1
7.1 Preparation for Starting
Operation
This section describes the operation procedure for
the EJ530 as shown in gure 7.1.
NOTE
Check that the process pressure tap valves,
drain valves, and stop valves are closed.
(a) Follow the procedures below to introduce
process pressure into the impulse piping and
transmitter.
1) Open the tap valve (main valve) to ll the
impulse piping with process uid.
2) Gradually open the stop valve to introduce
process uid into the transmitter pressuredetector section.
3) Conrm that there is no pressure leak in
the impulse piping, transmitter, or other
components.
(b) Turn ON power and connect the communicator.
Open the terminal box cover, and connect
the communicator to the SUPPLY + and
– terminals.
(c) Using the communicator, conrm that the
transmitter is operating properly. Check
parameter values or change the setpoints as
necessary.
See IM 01C25T03-01E (BRAIN
communication) or IM 01C25T01-06EN (HART
communication) for communicator operation.
If the transmitter is equipped with an integral
indicator, its indication can be used to conrm
that the transmitter is operating properly.
Tap valve
Vent plug (Fill plug)
Union or flange
Stop valve
Tee
Union or flange
Drain valve
Drain plug
Figure 7.1 Liquid Flow Measurement
(Gauge Pressure Transmitters)
F0701.ai
■ Conrming that Transmitter is Operating
Properly
Using the BT200
• If the wiring system is faulty, ‘communication
error’ appears on the display.
• If the transmitter is faulty, ‘SELF CHECK
ERROR’ appears on the display.
PARAM
C60:SELF CHECK
ERROR
communication error
DATA DIAG PRNTESC
Communication error
(Faulty wiring)
Figure 7.2 BT200 Display
Self-diagnostic error
(Faulty transmitter)
F0702.ai
IM 01C25F01-01E
<7. Operation>
7-2
Using the integral indicator
• If the wiring system is faulty, the display stays
blank.
• If the transmitter is faulty, an error code is
displayed.
Self-diagnostic error on the integral indicator
(Faulty transmitter)
Figure 7.3 Integral Indicator with Error Code
F0703.ai
NOTE
If any of the above errors are indicated on
the display of the integral indicator or the
communicator, refer to subsection 8.5.3 for the
corrective action.
IMPORTANT
Do not turn off the power to the transmitter
immediately after performing a zero point
adjustment. Powering off within 30 seconds of
performing this procedure will return the zero
point to its previous setting.
NOTE
Before performing this adjustment, make sure
that the external zero adjustment function has
NOT been disabled by a parameter setting.
To check the output signal, use a digital multimeter,
calibrator, or communicator.
■ Verify and Change Transmitter Parameter
Setting and Values
The parameters related to the following items are
set at factory as specied in order.
• Calibration range
• Integral indicator display
• Software damping (optional)
Other parameters like following are shipped with the
default setting.
• Low-cut
• Process alarm setting
• Signal characterizer
• Write protection
To conrm or change the values, see IM 01C25T0106EN or 01C25T03-01E.
7.2 Zero Point Adjustment
After completing preparations for operating the
transmitter, adjust the zero point.
Zero point adjustment can be done by turning the
transmitter’s zero-adjustment screw or by using
the communicator. This section describes the
procedure for the zero-adjustment screw. For the
communicator procedure, see the communication
manual.
Zero-adjustment
screw cover
F0704.ai
Figure 7.4 External Zero-adjustment Screw
The zero-adjustment screw is located inside the
cover.
(1) When you can obtain the Low Range Value
from the actual measured value of 0% (0
kPa, atmospheric pressure);
For pressure measurement using gauge pressure
transmitters, follow the steps below before
performing zero point adjustment.
1) Close the tap valve (main valve).
2) Loosen the ll plug so that the pressure applied
to the transmitter is only the head of the seal
liquid.
3) Adjust the zero point at this status.
4) After the adjustment, close the ll plug and then
gradually open the tap valve.
IM 01C25F01-01E
<7. Operation>
7-3
Use a slotted screwdriver to turn the zeroadjustment screw. Turn the screw clockwise
to increase the output or counterclockwise to
decrease the output. The zero point adjustment can
be made with a resolution of 0.01% of the setting
range. Since the degree of the zero adjustment
varies with the screw turning speed, turn the screw
slowly to make a ne adjustment and quickly to
make a rough adjustment.
(2) When you cannot obtain the Low Range
Value from the actual measured value of
0%;
Adjust the transmitter output to the actual measured
value obtained by a digital manometer or a glass
gauge.
[Example]
The measuring range of 50 to 250 kPa; the actual
measured value of 130 kPa.
Actual measured value=
130–50
250–50
x100=40.0%
(=10.4mA)
IMPORTANT
• Remove the communicator from the terminal
box, and conrm that none of the terminal
screws are loose.
• Close the terminal box cover and the
amplier cover. Screw each cover in tightly
until it will not turn further.
• There are two covers that must be locked
on the ATEX Flameproof type transmitters.
An Allen head bolt (shrouding bolt) under
the edge of each cover is used to lock the
cover. When the shrouding bolt is driven
counterclockwise with an Allen wrench, the
bolt rotates upward and locks the cover. (See
section 8.4.) After locking the covers, conrm
that they are secure and cannot be opened
by hand.
Tighten the zero-adjustment cover mounting
screw to secure the cover.
• Tighten the zero-adjustment cover mounting
screw to secure the cover.
Turn the screw to match the output signal to the
actual measured value.
7.3 Starting Operation
After completing the zero point adjustment, follow
the procedures below to start operation. Steps
1) and 2) are specic to the differential pressure
transmitters.
1) Conrm the operating status. If the output
signal exhibits wide uctuations (hunting) due to
periodic variation in the process pressure, use
the communicator to dampen the transmitter
output signal. Conrm the hunting using a
receiving instrument or the integral indicator,
and set the optimum damping time constant.
2) After conrming the operating status, perform
the following.
7.4 Shutting Down the
Transmitter
Shut down the transmitter as follows.
Steps 2) and 3) are specic to the differential
pressure transmitters.
1) Turn off the power.
2) Close the stop valve.
3) Open the equalizing valve.
4) Close the high pressure stop valve.
5) Close the tap valves.
NOTE
• Whenever shutting down the transmitter for a
long period, remove any process uid that is
in the transmitter pressure-detector section.
• The equalizing valve must be left OPEN.
IM 01C25F01-01E
<7. Operation>
7-4
7.5 Setting the Range Using the
Range-setting Switch
WARNING
The range setting switch must not be used in the
hazardous area.
When it is necessary to use the switch, operate it
in a non-hazardous location.
When pressure is applied to the transmitter, the lowand high-limit values for the measurement range
(LRV and URV) can be changed (re-ranged) using
the range-setting switch (push-button) located on
the optional integral indicator plate and the external
zero adjustment screw. This procedure does
not require use of the communicator. However,
changes in the scale range and engineering unit
display settings for the integral indicator require use
of the communicator.
Follow the procedure below to change the LRV and
URV settings.
[Example]
Rerange LRV to 0 and URV to 3 MPa.
Note 1: Wait until the pressure inside the pressure-detector
section has stabilized before proceeding to the next
step.
Note 2: If the pressure applied to the transmitter exceeds the
previous LRV (or URV), the integral indicator may
display error number “AL.30” (In this case, the output
signal percent and “AL.30” are displayed alternately
every two seconds). Although “AL.30” is displayed,
you may proceed to the next step. However, should
any other error number be displayed, take the
appropriate measure in reference to , “Errors and
Countermeasures” in each communication manual.
IMPORTANT
• Do not turn off the power to the transmitter
immediately after completion of the change
in the LRV and/or URV setting(s). Note
that powering off within thirty seconds after
setting will cause a return to the previous
settings.
• Changing LRV automatically changes URV
to the following value.
URV=previous URV+(new LRV–previous LRV)
• If the range-setting push-button and external
zero-adjustment screw are not touched
during a range-change operation, the
transmitter automatically switches back to
the normal operation mode.
1) Connect the transmitter and apparatus as
shown in Figure 8.1 and warm it up for at least
ten minutes.
2) Press the range-setting push-button.
The integral indicator then displays “LRV.SET.”
3) Apply a pressure of 0 kPa (atmospheric
pressure) to the transmitter.
(Note 1)
4) Turn the external zero-adjustment screw in the
desired direction. The integral indicator displays
the output signal in %.
(Note 2)
5) Adjust the output signal to 0% (1 V DC) by
rotating the external zero-adjustment screw.
Doing so completes the LRV setting.
6) Press the range-setting push-button. The
integral indicator then displays “URV.SET.”
7) Apply a pressure of 3 MPa to the transmitter.
(Note 1)
8) Turn the external zero-adjustment screw in the
desired direction. The integral indicator displays
the output signal in %.
(Note 2)
9) Adjust the output signal to 100% (5 V DC) by
rotating the external zero-adjustment screw.
Doing so completes the URV setting.
10) Press the range-setting push-button. The
transmitter then switches back to the normal
operation mode with the measurement range of
0 to 3 MPa.
Integral indicator
Figure 7.5 Range-setting Switch
Note 1: Use a thin bar which has a
blunt tip, e.g., a hexagonal
wrench, to press the
range-setting push-button.
Note 2: The push-button is located
in either lower right or
lower left portion of the
LCD indicator.
Range-setting switch
(Push-button)
F0705.ai
IM 01C25F01-01E
<8. Maintenance>
8. Maintenance
8-1
8.1 Overview
WARNING
Since the accumulated process uid may be
toxic or otherwise harmful, take appropriate care
to avoid contact with the body or inhalation of
vapors when draining condensate or venting gas
from the transmitter pressure-detector section
and even after dismounting the instrument from
the process line for maintenance.
Maintenance of the transmitter is easy due to its
modular construction. This chapter describes the
procedures for calibration, adjustment, and the
disassembly and reassembly procedures required
for component replacement.
Transmitters are precision instruments. Please
carefully and thoroughly read the following sections
for information on how to properly handle them
while performing maintenance.
IMPORTANT
• As a rule, maintenance of this transmitter
should be done in a shop that has all the
necessary tools.
• The CPU assembly contains sensitive parts
that can be damaged by static electricity.
Take precautions such as using a grounded
wrist strap when handling electronic parts or
touching the board circuit patterns. Also be
sure to place the removed CPU assembly
into a bag with an antistatic coating.
8.3 Calibration
Use the procedure below to check instrument
operation and accuracy during periodic
maintenance or troubleshooting.
1) Connect the instruments as shown in gure 8.1
and warm up the instruments for at least ten
minutes.
IMPORTANT
• To adjust the transmitter for highest
accuracy, make adjustments with the
power supply voltage and load resistance
including leadwire resistances set close to
the conditions under which the transmitter is
installed.
• If the measurement range 0% point is
0 kPa or shifted in the positive direction
(suppressed zero), the reference pressure
should be applied as shown in the gure.
If the measurement range 0% point is shifted
in the negative direction (elevated zero), the
reference pressure should be applied using
a vacuum pump.
2) Apply reference pressures of 0%, 50%,
and 100% of the measurement range to the
transmitter. Calculate the errors (differences
between digital voltmeter readings and
reference pressures) as the pressure is
increased from 0% to 100% and is decreased
from 100% to 0%, and conrm that the errors
are within the required accuracy.
8.2 Calibration Instruments
Selection
Table 8.1 lists the instruments that can be used
to calibrate a transmitter. When selecting an
instrument, consider the required accuracy level.
Exercise care when handling these instruments to
ensure they maintain the specied accuracy.
IM 01C25F01-01E
<8. Maintenance>
Table 8.1 Instruments Required for Calibration
NameYokogawa-recommended InstrumentRemarks
Power supply Model SDBT or SDBS distributor4 to 20 mA DC signal
Load resistorModel 2792 standard resistor [250 Ω ±0.005%, 3 W]
Load adjustment resistor [100 Ω ±1%, 1 W]
VoltmeterModel 2501 A digital multimeter
Accuracy (10V DC range): ±(0.002% of rdg + 1 dgt)
Digital
manometer
Model MT220 precision digital manometer
1) For 10 kPa class
Accuracy: ±(0.015% of rdg + 0.015% of F.S.). . . . for 0 to 10 kPa
Select a manometer having
a pressure range close to
that of the transmitter.
±(0.2% of rdg + 0.1% of F.S.). . . . . . . . for -10 to 0 kPa
2) For 130 kPa class
Accuracy: ±0.02% of rdg. . . . . . . . . . . . . . . . . . . . for 25 to 130 kPa
±(0.2% of rdg + 0.1% of F.S.). . . . . . . . for -80 to 0 kPa
4) For 3000 kPa class
Accuracy: ±(0.02% of rdg + 10 digits). . . . . . . . . . for 0 to 3000 kPa
±(0.2% of rdg + 0.1% of F.S.). . . . . . . . for -80 to 0 kPa
5) For 130 kPa abs class
Accuracy: ±(0.03% of rdg + 6 digits). . . . . . . . . . . for 0 to 130 kPa abs
Pressure
generator
Model 7674 pneumatic pressure standard for 200 kPa {2 kgf/cm2}, 25 kPa
{2500 mmH2O}
Requires air pressure
supply.
Accuracy: ±0.05% of F.S.
Dead weight gauge tester 25 kPa {2500 mmH2O}
Accuracy: ±0.03% of setting
Select the one having a
pressure range close to that
of the transmitter.
Pressure
source
Model 6919 pressure regulator (pressure pump)
Pressure range: 0 to 133 kPa {1000 mmHg}
Prepare the vacuum pump
for negative pressure
ranges.
Note: The above table contains the instruments capable of performing calibration to the 0.2% level. Since special maintenance and
management procedures involving traceability of each instrument to higher-level standards are required for calibration to the 0.1%
or higher level, there may be difculties in calibration to this level in the eld. For calibration to the 0.1% or higher level, use proper
instruments for required level or contact Yokogawa representatives from which the instrument was purchased or the nearest
Yokogawa ofce.
8-2
If a pressure generator
is used:
Load resistance,
Load
adjustment
resistance,
100Ω
Reference pressure
P
Model 7674 pneumatic
pressure standards
Supply pressure
Figure 8.1 Instrument Connections
Power
250Ω
RRc
V
Digital voltmeter
supply
E
If a pressure source and
a manometer are combined:
Reference pressure
Pressure source
Load resistance,
Load
adjustment
resistance,
100Ω
P
Model MT220
precision digital manometer
250Ω
RRc
V
Digital voltmeter
IM 01C25F01-01E
Power
supply
E
F0801.ai
<8. Maintenance>
8-3
8.4 Disassembly and
Reassembly
This section describes procedures for disassembly
and reassembly for maintenance and component
replacement.
Always turn OFF power and shut off and release
pressures before disassembly. Use proper tools for
all operations. Table 8.2 shows the tools required.
Table 8.2 Tools for Disassembly and Reassembly
ToolQuantityRemarks
Phillips
screwdriver
Slotted
screwdriver
Allen wrenches3JIS B4648
Wrench1Width across ats, 17 mm
Torque wrench1
Adjustable
wrench
Socket wrench1Width across ats, 16 mm
Socket driver1Width across ats, 5.5 mm
Tweezers1
1JIS B4633, No. 2
1
One each, nominal 3, 4 and
2.5 mm Allen wrenches
1
CAUTION
Precautions for ATEX Flameproof Type
Transmitters
• Flameproof type transmitters must be, as
a rule, removed to a non-hazardous area
for maintenance and be disassembled and
reassembled to the original state.
• On the ameproof type transmitters the two
covers are locked, each by an Allen head bolt
(shrouding bolt). When a shrouding bolt is
driven clockwise by an Allen wrench, it is going
in and cover lock is released, and then the
cover can be opened.
When a cover is closed it should be locked
by a shrouding bolt without fail. Tighten the
shrouding bolt to a torque of 0.7 N·m.
8.4.1 Replacing the Integral Indicator
CAUTION
Cautions for Flameproof Type Transmitters
Users are prohibited by law from modifying the
construction of a ameproof type transmitter.
This would invalidate the agency approval for the
use of the transmitter in a rated area.
It follows that the user is prohibited from using
a ameproof type transmitter with its integral
indicator removed, or from adding an integral
indicator to a transmitter. If such modication is
absolutely required, contact Yokogawa.
This subsection describes the procedure for
replacing an integral indicator. (See gure 8.3)
■ Removing the Integral Indicator
1) Remove the cover.
2) While supporting the integral indicator with one
hand, loosen its two mounting screws.
3) Dismount the LCD board assembly from the
CPU assembly.
When doing this, carefully pull the LCD board
assembly straight forward so as not to damage
the connector pins between it and the CPU
assembly.
■ Attaching the Integral Indicator
1) Align both the LCD board assembly and CPU
assembly connectors and engage them.
2) Insert and tighten the two mounting screws.
3) Replace the cover.
Output terminal cable
Press
forward
Slide
switch
Integral
indicator
LCD board assembly
Mounting screw
Amplifier Cover
Boss
CPU assembly
Bracket
(for zero-adjustment
screw pin)
Zero-adjustment
screw pin
Zeroadjustment
screw
Shrouding Bolt
Figure 8.2 Shrouding Bolts
Shrouding Bolt
F0802.ai
F0803.ai
Figure 8.3 Removing and Attaching LCD Board
Assembly and CPU Assembly
IM 01C25F01-01E
<8. Maintenance>
8-4
8.4.2 Replacing the CPU Board Assembly
This subsection describes the procedure for
replacing the CPU assembly. (See gure 8.3)
■ Removing the CPU Assembly
1) Remove the cover. If an integral indicator is
mounted, refer to subsection 8.4.1 and remove
the indicator.
2) Turn the zero-adjustment screw to the position
(where the screw head slot is horizontal) as
shown in gure 8.3.
3) Disconnect the output terminal cable (cable
with brown connector at the end). When doing
this, lightly press the side of the CPU assembly
connector and pull the cable connector to
disengage.
4) Use a socket driver (width across ats, 5.5mm)
to loosen the two bosses.
5) Carefully pull the CPU assembly straight
forward to remove it.
6) Disconnect the at cable (cable with white
connector at the end) that connects the CPU
assembly and the capsule.
NOTE
Be careful not to apply excessive force to the
CPU assembly when removing it.
■ Mounting the CPU Assembly
1) Connect the at cable (with white connector)
between the CPU assembly and the capsule.
2) Connect the output terminal cable (with brown
connector).
NOTE
Make certain that the cables do not get pinched
between the case and the edge of the CPU
assembly.
NOTE
Conrm that the zero-adjustment screw pin is
placed properly in the groove on the bracket prior
to tightening the two bosses. If it is not, the zeroadjustment mechanism will be damaged.
5) Replace the cover.
8.4.3 Cleaning and Replacing the Capsule
Assembly
This subsection describes the procedures for
cleaning and replacing the capsule assembly. (See
gure 8.4.)
CAUTION
Cautions for Flameproof Type Transmitters
Users are prohibited by law from modifying the
construction of a ameproof type transmitter. If
you wish to replace the capsule assembly with
one of a different measurement range, contact
Yokogawa.
The user is permitted, however, to replace a
capsule assembly with another of the same
measurement range. When doing so, be sure to
observe the following.
• The replacement capsule assembly must
have the same part number as the one being
replaced.
• The section connecting the transmitter and
capsule assembly is a critical element in
preservation of ameproof performance, and
must be checked to verify that it is free of
dents, scratches, and other defects.
• After completing maintenance, be sure to
securely tighten the setscrews that fasten the
transmitter section and pressure-detector
section together.
3) Align and engage the zero-adjustment screw
pin with the groove on the bracket on the CPU
assembly. Then insert the CPU board assembly
straight onto the post in the amplier case.
4) Tighten the two bosses. If the transmitter is
equipped with an integral indicator, refer to
subsection 8.4.1 to mount the indicator.
IM 01C25F01-01E
<8. Maintenance>
8-5
■ Removing the Capsule Assembly
IMPORTANT
Exercise care as follows when cleaning the
capsule assembly.
• Handle the capsule assembly with care, and
be especially careful not to damage or distort
the diaphragms that contact the process
uid.
• Do not use a chlorinated or acidic solution for
cleaning.
• Rinse thoroughly with clean water after
cleaning.
1) Remove the CPU assembly as shown in
subsection 8.4.2.
2) Remove the two setscrews that connect the
transmitter section and pressure-detector
section.
3) Remove the hexagon-head screw and the
stopper.
4) Separate the transmitter section and capsule
assembly.
5) Clean the capsule assembly or replace with a
new one.
■ Reassembling the Capsule Assembly
1) Insert the capsule assembly to the transmitter
section. Reattach the sopper with the hexagonhead screw.
2) Tighten the two setscrews. (Tighten the screws
to a torque of 1.5 N·m)
3) Install the CPU assembly according to
subsection 8.4.2.
4) After completing reassembly, adjust the zero
point and recheck the parameters.
Transmitter section
Hexagon
head screw
Stopper
Setscrew
Capsule assembly
F0804.ai
Figure 8.4 Removing and Mounting the Pressure-
detector Section
8.5 Troubleshooting
If any abnormality appears in the measured values,
use the troubleshooting ow chart below to isolate
and remedy the problem. Since some problems
have complex causes, these ow charts may
not identify all. If you have difculty isolating or
correcting a problem, contact Yokogawa service
personnel.
IM 01C25F01-01E
<8. Maintenance>
8-6
8.5.1 Basic Troubleshooting
First determine whether the process variable
is actually abnormal or a problem exists in the
measurement system.
If the problem is in the measurement system,
isolate the problem and decide what corrective
action to take.
This transmitter is equipped with a self-diagnostic
function which will be useful in troubleshooting,
and the transmitter equipped with an integral
indicator will show an alarm code as a result of selfdiagnosis.
See subsection 8.5.3 for the list of alarms.
See also each communication manual.
: Areas where self-diagnostic offers support
Abnormalities appear in measurement.
YES
Is process variable
itself abnormal?
8.5.2 Troubleshooting Flowcharts
The following sorts of symptoms indicate that transmitter
may not be operating properly.
Example : • There is no output signal.
• Output signal does not change even though
process variable is known to be varying.
• Output value is inconsistent with value
inferred for process variable.
Connect communicator and check self-diagnostics.
Does the self-diagnostic
indicate problem location?
NO
Is power supply
polarity correct?
YES
Refer to error message summary in
Subsection 8.5.3 or in each
communication manual to take actions.
Refer to Section 6.3 to check/correct
polarity at each terminal from power
supply to the terminal box.
YES
NO
Inspect the
process system.
YES
Inspect receiver.
Environmental conditions
Check/correct
environmental conditions.
NO
Measurement system problem
Isolate problem in
measurement system.
Does problem exist in
receiving instrument?
NO
Operating conditions
Check/correct operating
conditions.
Transmitter itself
Check transmitter.
Figure 8.5 Basic Flow and Self-Diagnostics
F0805.ai
Are power
supply voltage and load
resistance correct?
YES
Are valves opened or
closed correctly?
YES
Is there any pressure leak?
NO
Is there
continuity through the
transmitter loop wiring?
Do the loop numbers
match?
YES
Refer to Section 6.6 for rated voltage
and load resistance.
Fully close equalizing valve, and fully
open high pressure and low pressure
valves.
Fix pressure leaks, paying particular
attention to connections for impulse
piping,pressure-detector section, etc.
Find/correct broken conductor or
wiring error.
NO
NO
YES
NO
Contact Yokogawa service personnel.
F0806.ai
IM 01C25F01-01E
<8. Maintenance>
8-7
Output travels beyond 0% or 100%.
Connect a communicator and check self-diagnostics.
Does the self-
diagnostic indicate problem
location?
NO
Is power supply
polarity correct?
YES
Are valves opened or
closed correctly?
YES
Refer to error message summary in
each communication manual to take
actions.
Refer to Section 6.3 to check/correct
polarity at each terminal from power
supply to the terminal box.
Fully close equalizing valve, and fully
open high pressure and low pressure
valves.
YES
NO
NO
Large output error.
Connect a communicator and check self-diagnostics.
Does the self-
diagnostic indicate problem
location?
NO
Are valves opened or
closed correctly?
YES
Is impulse piping
connected correctly?
YES
Refer to error message summary in
each communication manual to take
actions.
Fully close equalizing valve, and fully
open high pressure and low pressure
valves.
Refer to individual model user manuals
and connect piping as appropriate for
the measurement purpose.
YES
NO
NO
Is there any pressure leak?
NO
Is impulse piping
to high pressure and low
pressure side correct?
YES
Is zero point
adjusted correctly?
YES
Contact Yokogawa service personnel.
Fix pressure leaks, paying particular
attention to connections for impulse
piping, pressure-detector section, etc.
Refer to individual model user manuals
and connect piping as appropriate for
the measurement purpose.
Adjust the zero point.
YES
NO
NO
F0807.ai
Are power supply
voltage and load resistance
correct?
YES
Is transmitter
installed where there is
marked variation in
temperature?
NO
Were appropriate
instruments used for
calibration?
YES
Is output adjusted correctly?
YES
Refer to Section 6.6 for rated voltage
and load resistance.
Provide lagging and/or cooling, or allow
adequate ventilation.
Refer to Section 8.2 when selecting
instruments for calibration.
Adjust the output.
NO
YES
NO
NO
Contact Yokogawa service personnel.
F0808.ai
IM 01C25F01-01E
<8. Maintenance>
8.5.3 Alarms and Countermeasures
Table 8.3 Alarm Message Summary
IndicatorCause
None
AL. 01
CAP. ERR
Sensor problem.Outputs the signal (Hold, High, or
Capsule temperature sensor
problem.
Capsule EEPROM problem.
AL. 02
AMP. ERR
Amplier temperature sensor
problem.
Amplier EEPROM problem.
Amplier problem.
AL. 10
PRESS
AL. 11
Input is outside measurement
range limit of capsule.
Static pressure exceeds limit.Continues to operate and output.
ST. PRSS
AL. 12
CAP. TMP
AL. 13
AMP. TMP
AL. 30
RANGE
AL. 31
SP. RNG
AL. 35 *
P. HI
AL. 36 *
Capsule temperature is outside
range (–50 to 130°C).
Amplier temperature is outside
range (–50 to 95°C)
Output is outside upper or lower
range limit value.
Static pressure exceeds specied
range.
1
Input pressure exceeds specied
threshold.
1
P. LO
1
AL. 39 *
TMP. HI
AL. 40 *
Detected temperature exceeds
specied threshold.
1
TMP. LO
AL. 50
P. LRV
Specied value is outside of setting
range.
AL. 51
P. URV
AL. 52
P. SPN
AL. 53
P. ADJ
AL. 60
SC. CFG
Specied values or settings to
dene signal characterizer function
do not satisfy the condition.
AL. 79
Displayed value exceeds limit.
OV. DISP
Output Operation
during Error
Countermeasure
Replace capsule when error
Low) set with parameter.
keeps appearing even after
restart.
Outputs the signal (Hold, High, or
Replace amplier.
Low) set with parameter.
Outputs high range limit value or
low range limit value.
Check input or replace capsule
when necessary.
Use heat insulation or make
lagging to keep temperature
within range.
Outputs high range limit value or
low range limit value.
Check input and range setting,
and change them as needed.
Holds output immediately before
error occurred.
Continues to operate and
Check input.
output.
Holds output immediately before
error occurred.
Check setting and change them
as needed.
Continues to operate and output. Check input.
Continues to operate and output. Check setting and change
them as needed.
8-8
*1: These alarms may appear only when process alarm function is activated.
IM 01C25F01-01E
<9. General Specications>
9. General Specications
9-1
9.1 Standard Specications
Refer to IM 01C25T02-01E for FOUNDATION
Fieldbus communication type and IM 01C25T0401EN for PROFIBUS PA communication type for
the items marked with “◊”.
Performance Specications
See General Specications sheet for each model.
Functional Specications
Span & Range Limits
EJX530A
Measurement
Span/Range
Span
A
Range
Span
B
Range
Span
C
Range
Span
D
Range
EJX510A (Values are absolute pressure)
Measurement
Span/Range
Span
A
Range
Span
B
Range
Span
C
Range
Span
D
Range
EJX630A
Measurement
Span/Range
Span
A
Range
Span
B
Range
Span
C
Range
Span
D
Range
MPapsi(/D1)bar(/D3) kgf/cm2(/D4)
8 to 200kPa 1.16 to 290.08 to 20.08 to 2
-100 to
200 kPa
-14.5 to 29-1 to 2-1 to 2
0.04 to 25.8 to 2900.4 to 200.4 to 20
-0.1 to 2-14.5 to 290 -1 to 20-1 to 20
0.2 to 1029 to 14502 to 1002 to 100
-0.1 to 10 -14.5 to 1450 -1 to 100 -1 to 100
1 to 50145 to 7200 10 to 500 10 to 500
-0.1 to 50 -14.5 to 7200 -1 to 500 -1 to 500
MPapsi(/D1)bar(/D3) kgf/cm2(/D4)
8 to 200 kPa 1.16 to 290.08 to 20.08 to 2
0 to 200 kPa0 to 290 to 20 to 2
0.04 to 25.8 to 2900.4 to 200.4 to 20
0 to 20 to 2900 to 200 to 20
0.2 to 1029 to 14502 to 1002 to 100
0 to 100 to 14500 to 1000 to 100
1 to 50145 to 7200 10 to 500 10 to 500
0 to 500 to 72000 to 5000 to 500
MPapsi (/D1)bar (/D3)
kgf/cm2(/D4)
2 to 200 kPa 0.3 to 290.02 to 20.02 to 2
-100 to 200
kPa
-14.5 to 29-1 to 2-1 to 2
0.01 to 21.5 to 2900.1 to 200.1 to 20
-0.1 to 2-14.5 to 290 -1 to 20-1 to 20
0.05 to 107.3 to 1450 0.5 to 100 0.5 to 100
-0.1 to 10 -14.5 to 1450 -1 to 100 -1 to 100
0.35 to 70
-0.1 to 70
50.8 to
10150
-14.5 to
10150
3.5 to 700 3.5 to 700
-1 to 700 -1 to 700
EJX610A (Values are absolute pressure)
Measurement
Span/Range
Span
A
Range
Span
B
Range
Span
C
Range
Span
D
Range
MPapsi (/D1)bar (/D3)
2 to 200 kPa 0.3 to 290.02 to 20.02 to 2
0 to 200 kPa0 to 290 to 20 to 2
0.01 to 21.5 to 2900.1 to 200.1 to 20
0 to 20 to 2900 to 200 to 20
0.05 to 107.3 to 1450 0.5 to 100 0.5 to 100
0 to 100 to 14500 to 1000 to 100
0.35 to 70
50.8 to
10150
3.5 to 700 3.5 to 700
0 to 700 to 101500 to 7000 to 700
EJA530E
Measurement
Span/Range
Span
A
Range
Span
B
Range
Span
C
Range
Span
D
Range
MPapsi(/D1)bar(/D3) kgf/cm2(/D4)
10 to 200
kPa
-100 to
200 kPa
1.45 to 290.1 to 20.1 to 2
-14.5 to 29-1 to 2-1 to 2
0.1 to 214.5 to 2901 to 201 to 20
-0.1 to 2-14.5 to 290 -1 to 20-1 to 20
0.5 to 10 72.5 to 1450 5 to 1005 to 100
-0.1 to 10 -14.5 to 1450 -1 to 100 -1 to 100
5 to 50720 to 7200 50 to 500 50 to 500
-0.1 to 50 -14.5 to 7200 -1 to 500 -1 to 500
EJA510E (Values are absolute pressure)
Measurement
Span/Range
Span
A
Range
Span
B
Range
Span
C
Range
Span
D
Range
MPapsi(/D1)bar(/D3) kgf/cm2(/D4)
10 to 200
kPa
1.45 to 290.1 to 20.1 to 2
0 to 200 kPa0 to 290 to 20 to 2
0.1 to 214.5 to 2901 to 201 to 20
0 to 20 to 2900 to 200 to 20
0.5 to 10 72.5 to 1450 5 to 1005 to 100
0 to 100 to 14500 to 1000 to 100
5 to 50720 to 7200 50 to 500 50 to 500
0 to 500 to 72000 to 5000 to 500
Output “◊”
Two wire 4 to 20 mA DC output with digital
communications, linear or square root
programmable. BRAIN or HART FSK protocol
are superimposed on the 4 to 20 mA signal.
Output range: 3.6 mA to 21.6 mA
Output limits conform to NAMUR NE43 can be
pre-set by option C2 or C3.
kgf/cm2(/D4)
IM 01C25F01-01E
<9. General Specications>
9-2
Failure Alarm “◊”
Output status at CPU failure and hardware
error;
Up-scale: 110%, 21.6 mA DC or more
(standard)
Down-scale: –5%, 3.2 mA DC or less
Note: Applicable for Output signal code D and E
Damping Time Constant (1st order)
Amplier damping time constant is adjustable
from 0 to 100.00 seconds and added to
response time.
Note: For BRAIN protocol type, when amplier damping
is set to less than 0.5 seconds, communication
may occasionally be unavailable during the
operation, especially while output changes
dynamically. The default setting of damping
ensures stable communication.
Update Period “◊”
45 ms
Zero Adjustment Limits
Zero can be fully elevated or suppressed, within
the lower and upper range limits of the capsule.
External Zero Adjustment “◊”
External Zero is continuously adjustable with
0.01% incremental resolution of span. Re-range
can be done locally using the digital indicator
with range-setting switch.
Integral Indicator (LCD display)
5-digit Numerical Display, 6-digit Unit Display
and Bar graph.
The indicator is congurable to display one or
up to four of the following variables periodically.;
Pressure in %, Scaled pressure, pressure in
Engineering unit.
See “Setting When Shipped” for factory setting.
Burst Pressure Limits
EJ510 and EJ530
CapsulePressure
A, B, C30 MPa (4350 psi)
D 132 MPa (19100 psi)
Normal Operating Condition
(Selected features may affect limits.)
Ambient Temperature Limits
–40 to 85°C (–40 to 185°F)
–30 to 80°C (–22 to 176°F) with LCD display
(Optional features or approval codes may
affect electrical requirements.)
With 24 V DC supply, up to a 550 Ω load can be
used. See graph below.
600
E-10.5
R=
External
load
resistance
250
(Ω)
R
0.0244
10.516.625.242
Power supply voltage E (V DC)
Digital
Communication
range
BRAIN and HART
F0903.ai
Figure 9.3 Relationship Between Power Supply
Voltage and External Load Resistance
Supply Voltage “◊”
10.5 to 42 V DC for general use and ameproof
type.
10.5 to 32 V DC for lightning protector (Option
code /A).
10.5 to 30 V DC for intrinsically safe, type n or
non-incendive type.
Minimum voltage limited at 16.6 V DC for digital
communications, BRAIN and HART
Load (Output signal code D, E and J)
0 to 1290 Ω for operation
250 to 600 Ω for digital communication
IM 01C25F01-01E
<9. General Specications>
9-4
Communication Requirements “◊”
(Safety approvals may affect electrical
requirements.)
BRAIN
Communication Distance
Up to 2 km (1.25 miles) when using CEV
polyethylene-insulated PVC-sheathed cables.
Communication distance varies depending on
type of cable used.
Load Capacitance
0.22 μF or less
Load Inductance
3.3 mH or less
Input Impedance of communicating device
10 kΩ or more at 2.4 kHz.
HART
Communication Distance
Up to 1.5 km (1 mile) when using multiple
twisted pair cables. Communication distance
varies depending on type of cable used.
Use the following formula to determine cable
length for specic applications:
65 × 10
L= –
(R × C)
6
(Cf + 10,000)
C
Where:
L = length in meters or feet
R = resistance in Ω (including barrier
resistance)
C = cable capacitance in pF/m or pF/ft
Cf = maximum shunt capacitance of receiving
devices in pF/m or pF/ft
Physical Specications
Wetted Parts Materials
Diaphragm, Process Connector
Refer to “Model and Sufx Code.”
Non-wetted Parts Materials
Housing
Low copper cast aluminum alloy with
polyurethane paint or ASTM CF-8M stainless
steel
Degrees of Protection
IP66/IP67, NEMA TYPE 4X
Pipe
Polypropylene
Cover O-rings
Buna-N, uoro-rubber (option)
Nameplate and tag
316SST (including /N4 wired tag)
Fill Fluid
Silicone, Fluorinated oil (option)
Weight
Capsule A, B and C: 1. 2kg (2.6 lb)*
Capsule D: 1.4 kg (3.1 lb)*
*: Without integral indicator and mounting bracket.
Add 1.5 kg (3.3lb) for Amplier housing code 2.
Connections
Refer to “Model and Sufx Code.”
EMC Conformity Standards ,
EN61326-1 Class A, Table2 (For use in industrial
locations)
EN61326-2-3
IM 01C25F01-01E
<9. General Specications>
9.2 Model and Sufx Codes
ModelSufx CodesDescription
EJX510A
EJX530A
Output
signal
Measurement
span (capsule)
Wetted parts
material
Process
connections
—N. . . . . . . . . . . . . .Always N
—
Amplier housing1 . . . . . . . . . .
Electrical connection
Integral indicator
Mounting bracket
Optional codes
The “►” marks indicate the most typical selection for each specication. Example: EJX530A-DAS4N-012NN/.
*1: Hastelloy C-276 or ASTM N10276.
*2: Not applicable for combination of capsule code D and wetted parts material code H.
*3: Not applicable for output signal code F.
*4: Not applicable for electrical connection code 0, 5, 7 and 9.
*5: Not applicable for output signal code G.
4 to 20 mA DC Output with digital communication (BRAIN protocol)
4 to 20 mA DC Output with digital communication (HART protocol)
4 to 20 mA DC with digital communication (HART 5/HART 7 protocol)
Digital communication (FOUNDATION Fieldbus protocol,
refer to IM 01C25T02-01E)
Digital communication (PROFIBUS PA protocol,
refer to IM 01C25T04-01EN)
8 to 200 kPa (1.16 to 29 psi)
0.04 to 2 MPa (5.8 to 290 psi)
0.2 to 10 MPa (29 to 1450 psi)
1 to 50 MPa (145 to 7200 psi)
1/2 NPT female
1/2 NPT male
G1/2 DIN 16 288 male
M20×1.5 DIN 16 288 male
*2
*2
Always 0
Cast aluminum alloy
ASTM CF-8M Stainless steel
*4
Cast aluminum alloy with corrosion resistance properties
G1/2 female, one electrical connection without blind plugs
1/2 NPT female, two electrical connections without blind plugs
M20 female, two electrical connections without blind plugs
G1/2 female, two electrical connections with a blind plug
1/2 NPT female, two electrical connections with a blind plug
M20 female, two electrical connections with a blind plug
G1/2 female, two electrical connections with a 316SST blind plug
1/2 NPT female, two electrical connections with a 316SST blind plug
M20 female, two electrical connections with a 316SST blind plug
Digital indicator
Digital indicator with the range setting switch
4 to 20 mA DC Output with digital communication (BRAIN protocol)
4 to 20 mA DC Output with digital communication (HART protocol)
Digital communication (FOUNDATION Fieldbus protocol,
refer to IM 01C25T02-01E)
-G . . . . . . . . . . . . . . . . . . . .
Digital communication (PROFIBUS PA protocol,
refer to IM 01C25T04-01EN)
Measurement
span (capsule)
Wetted parts
material *4
Process
connections
A. . . . . . . . . . . . . . . . . . .
B. . . . . . . . . . . . . . . . . . .
C. . . . . . . . . . . . . . . . . . .
D. . . . . . . . . . . . . . . . . . .
S . . . . . . . . . . . . . . . . . .
H. . . . . . . . . . . . . . . . . .
4 . . . . . . . . . . . . . . . .
7 . . . . . . . . . . . . . . . .
8 . . . . . . . . . . . . . . . .
9 . . . . . . . . . . . . . . . .
2 to 200 kPa (0.3 to 29 psi)
0.01 to 2 MPa (1.5 to 290 psi)
0.05 to 10 MPa (7.3 to 1450 psi)
0.35 to 70 MPa (50.8 to 10150 psi)
Process connection Diaphragm
316L SST # Hastelloy C-276
Hastelloy C-276
*1 #
Hastelloy C-276
1/2 NPT female
1/2 NPT male
G1/2 DIN 16 288 male *2
M20×1.5 DIN 16 288 male *
2
*1 #
*1 #
—N. . . . . . . . . . . . . .Always N
—
Amplier housing ► 1 . . . . . . . . . .
Electrical connection
Integral indicator
Mounting bracket
Optional codes
-0 . . . . . . . . . . .
2 . . . . . . . . . .
3 . . . . . . . . . .
0 . . . . . . . . .
►
2 . . . . . . . . .
4 . . . . . . . . .
5 . . . . . . . . .
7 . . . . . . . . .
9 . . . . . . . . .
A. . . . . . . . .
C. . . . . . . . .
D. . . . . . . . .
D. . . . . . .
E . . . . . . .
►
N. . . . . . .
F . . . . .
L . . . . .
►
N. . . . .
Always 0
Cast aluminum alloy
ASTM CF-8M Stainless Steel *
5
Cast aluminum alloy with corrosion resistance properties
G1/2 female, one electrical connection without blind plugs
1/2 NPT female, two electrical connections without blind plugs
M20 female, two electrical connections without blind plugs
G1/2 female, two electrical connections with a blind plug *
1/2 NPT female, two electrical connections with a blind plug *
M20 female, two electrical connections with a blind plug *
G1/2 female, two electrical connections and a 316 SST blind plug
1/2 NPT female, two electrical connections and a 316 SST blind plug
M20 female, two electrical connections and a 316 SST blind plug
Digital indicator
Digital indicator with the range setting switch *
*7
3
None
304 SST 2-inch pipe mounting
316 SST 2-inch pipe mounting
None
/ Optional specication
9-6
6
6
6
The “►” marks indicates the most typical selection for each specication. Example: EJX630A-DAS4N-012NN/.
*1: Hastelloy C-276 or ASTM N10276.
*2: Not applicable for combination of capsule code D and wetted parts material code H.
*3: Not applicable for output signal code F.
*4: Users must consider the characteristics of selected wetted parts material and the inuence of process uids. The use of
inappropriate materials can result in the leakage of corrosive process uids and cause injury to personnel and/or damage to plant
facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm and the ll uid
can contaminate the user’fs process uids.
Be very careful with highly corrosive process uids such as hydrochloric acid, sulfuric acid, hydrogen sulde, sodium hypochlorite,
and high-temperature steam (150°C [302°F] or above). Contact Yokogawa for detailed information of the wetted parts material.
*5: Not applicable for electrical connection code 0, 5, 7 or 9.
*6: Material of a blind plug is aluminum alloy or 304 SST.
*7: Not applicable for output signal code G.
# The ‘#’ marks indicate the construction materials conform to NACE material recommendations per MR01-75. For the use of 316
SST material, there may be certain limitations for pressure and temperature. Please refer to NACE standards for details.
4 to 20 mA DC Output with digital communication (BRAIN protocol)
4 to 20 mA DC Output with digital communication
(HART 5/HART 7 protocol)
*1
Digital communication (FOUNDATION Fieldbus protocol,
refer to IM 01C25T02-01EN)
-G . . . . . . . . . . . . . . . . . . . .
Digital communication (PROFIBUS PA protocol,
refer to IM 01C25T04-01EN)
Measurement
span (capsule)
Wetted parts
material
*2
Process
connections
A. . . . . . . . . . . . . . . . . . .
B. . . . . . . . . . . . . . . . . . .
C. . . . . . . . . . . . . . . . . . .
D. . . . . . . . . . . . . . . . . . .
S . . . . . . . . . . . . . . . . . .
H. . . . . . . . . . . . . . . . . .
4 . . . . . . . . . . . . . . . .
7 . . . . . . . . . . . . . . . .
8 . . . . . . . . . . . . . . . .
9 . . . . . . . . . . . . . . . .
10 to 200 kPa (1.45 to 29 psi)
0.1 to 2 MPa (14.5 to 290 psi)
0.5 to 10 MPa (72.5 to 1450 psi)
5 to 50 MPa (720 to 7200 psi)
Process connection Diaphragm
316L SST# Hastelloy C-276
Hastelloy C-276
*3#
Hastelloy C-276
1/2 NPT female
1/2 NPT male
G1/2 DIN 16 288 male
M20×1.5 DIN 16 288 male
*4
*4
*3#
*3#
—N. . . . . . . . . . . . . .Always N
—-0 . . . . . . . . . . .Always 0
Amplier housing ► 1 . . . . . . . . . .
2 . . . . . . . . . .
3 . . . . . . . . . .
Electrical connection
0 . . . . . . . . .
►
2 . . . . . . . . .
4 . . . . . . . . .
5 . . . . . . . . .
7 . . . . . . . . .
9 . . . . . . . . .
A. . . . . . . . .
C. . . . . . . . .
D. . . . . . . . .
Integral indicator
D. . . . . . .
E . . . . . . .
►
N. . . . . . .
Mounting bracket
►
L . . . . .
N. . . . .
Optional codes
The “►” marks indicates the most typical selection for each specication. Example: EJA530E-DAS4N-012NN/.
*1: HART 5 or HART 7 is selectable. Specify upon ordering.
*2: Users must consider the characteristics of selected wetted parts material and the inuence of process uids. The use of
inappropriate materials can result in the leakage of corrosive process uids and cause injury to personnel and/or damage to plant
facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm and the ll uid
can contaminate the user’fs process uids.
Be very careful with highly corrosive process uids such as hydrochloric acid, sulfuric acid, hydrogen sulde, sodium hypochlorite,
and high-temperature steam (150°C [302°F] or above). Contact Yokogawa for detailed information of the wetted parts material.
*3: Hastelloy C-276 or ASTM N10276.
*4: Not applicable for combination of capsule code D and wetted parts material code H.
*5: Not applicable for electrical connection code 0, 5, 7, 9 and A. Content rate of copper in the material is 0.03% or less and content rate
of iron is 0.15% or less.
*6: Not applicable for electrical connection code 0, 5, 7 or 9.
*7: Material of a blind plug is aluminum alloy or 304 SST.
*8: Not applicable for output signal code F.
*9: Not applicable for output signal code G.
G1/2 female, one electrical connection without blind plugs
1/2 NPT female, two electrical connections without blind plugs
M20 female, two electrical connections without blind plugs
G1/2 female, two electrical connections with a blind plug
1/2 NPT female, two electrical connections with a blind plug
M20 female, two electrical connections with a blind plug
*7
*7
*7
G1/2 female, two electrical connections and a 316 SST blind plug
1/2 NPT female, two electrical connections and a 316 SST blind plug
M20 female, two electrical connections and a 316 SST blind plug
Digital indicator
Digital indicator with the range setting switch
*9
*8
None
316 SST 2-inch pipe mounting
None
/ Optional specication
The ‘#’ marks indicate the construction materials conform to NACE material recommendations per MR0175/ISO 15156.
Please refer to the latest standards for details. Selected materials also conform to NACE MR0103.
IM 01C25F01-01E
<9. General Specications>
9.3 Optional Specications “◊”
ItemDescriptionCode
Factory Mutual (FM)FM Explosionproof *
Explosionproof for Class I, Division 1, Groups B, C and D
Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G
Hazardous (classied) locations, indoors and outdoors (NEMA 4X)
FM Intrinsically safe *1*
Intrinsically Safe for Class I, Division 1, Groups A, B, C and D, Class II,
Division 1,Groups E, F and G and Class III, Division 1 Hazardous Locations.
Nonincendive for Class I, Division 2, Groups A, B, C and D, Class II,
Division 2, Groups F and G, Hazardous Locations.
Combined FF1 and FS1 *1*
ATEXATEX Flameproof *
II 2G, 2D Ex d IIC T6...T4 Gb, Ex tb IIIC T85°C Db
Special fastener: ClassA2-50(A4-50) or more
ATEX Intrinsically safe Ex ia *1*
II 1G, 2D Ex ia IIC T4 Ga, Ex ia IIIC T85°C T100°C T120°C Db
Combined KF22, KS21 and ATEX Intrinsically safe Ex ic
Ex ic: II 3G Ex ic IIC T4 Gc
Canadian Standards
Association (CSA)
CSA Explosionproof *
[For CSA C22.2]
Explosionproof for Class I, Division 1, Groups B, C and D
Dustignitionproof for Class II/III, Division 1, Groups E, F and G
[For CSA E60079]
Flameproof for Zone1, Ex d IIC T6...T4 Enclosure IP66/IP67
Process Sealing Certication
Dual Seal Certied by CSA to the requirement of ANSI/ISA 12.27.01
No additional sealing required
Primary seal failure annunciation: at the zero adjustment screw
CSA Intrinsically safe *1 *
[For CSA C22.2]
Intrinsically safe for Class I, Division 1, Groups A, B, C and D, Class II,
Division 1, Groups E,F and G, Class III, Division 1
Nonincendive for Class I, Division 2, Groups A, B, C and D, Class II,
Division 2, Groups F and G, Class III, Division 1
[For CSA E60079]
Ex ia IIC T4, Ex nL IIC T4
Process Sealing Certication
Dual Seal Certied by CSA to the requirement of ANSI/ISA 12.27.01
No additional sealing required
Primary seal failure annunciation: at the zero adjustment screw
Combined CF1 and CS1 *1*
IECExIECEx ameproof *
Flameproof for Zone1, Ex d IIC T6...T4
IECEx Intrinsically safe, type n and ameproof *1*
Intrinsically safe and type n
Ex ia IIC T4, Ex nL IIC T4
Flameproof
Flameproof for Zone1, Ex d IIC T6...T4
Combination of Approval Combination of KU22, FU1 and CU1 V1U1
High Accuracy type
*19
High accuracyHAC
PaintingColor changeAmplier cover only
Amplier cover and terminal cover, Munsell 7.5 R4/14PR
Coating change Anti-corrosion coating
316 SST exterior parts
*4
316 SST name plate, tag plate and zero adjustment screwHC
Fluoro-rubber O-ringAll O-rings of amplier housing. Lower limit of ambient temperature: –15°C (5°F)HE
Lightning protectorTransmitter power supply voltage:
10.5 to 32 V DC (10.5 to 30 V DC for intrinsically safe type, 9 to 32 V DC for
Fieldbus communication type.)
Allowable current: Max. 6000 A (1×40 μs), Repeating 1000 A (1×40 μs) 100 times
Applicable Standards: IEC 61000-4-4, IEC 61000-4-5
Status output *
5
Transistor output (sink type)
Contact rating: 10.5 to 30 VDC, 120 mA DC(max) Low level: 0 to 2 VDC
1
FF1
3
FS1
3
1
FU1
KF22
3
*1*3
1
KS21
KU22
CF1
3
CS1
3
1
3
CU1
SF2
SU2
P
*3
X2
AL
9-8
A
IM 01C25F01-01E
<9. General Specications>
9-9
ItemDescriptionCode
Oil-prohibited useDegrease cleansing treatment.K1
Degrease cleansing treatment with uorinated oillled capsule.
Operating temperature –20 to 80°C( –4 to 176°F)
Capsule ll uidFluorinated oil lled in capsule
Operating temperature –20 to 80°C( –4 to 176°F)
Calibration units *
6
P calibration (psi unit)
bar calibration (bar unit)D3
M calibration (kgf/cm2 unit)D4
Output limits and failure
operation *
7
Failure alarm down-scale: Output status at CPU failure and hardware error is
–5%, 3.2 mA DC or less.
NAMUR NE43 Compliant
Output signal limits:
3.8 mA to 20.5 mA
Failure alarm down-scale: Output status at CPU
failure and hardware error is –5%, 3.2 mA DC or less.
Failure alarm up-scale: Output status at CPU
failure and hardware error is 110%, 21.6 mA or more.
(See Table for Span and
Range Limits.)
K2
K3
D1
C1
C2
C3
Gold-plated diaphragm *15Surface of isolating diaphragm is gold plated, effective for hydrogen permeation. A1
Wired tag plate304 SST tag plate wired onto transmitterN4
Data conguration at
factory *
8
Advanced diagnostics *
Data conguration for HART
communication type
Data conguration for BRAIN
communication type
16
Multi-sensing process monitoring
• Impulse line blockage detection *
Software damping, Descriptor, Message
Software damping
17
CA
CB
DG6
• Heat trace monitoring
European Pressure
Equipment Directive *
PED 97/23/EC
18
Category: III, Module: H, Type of Equipment; Pressure Accessory-Vessel,
PE3
Type of Fluid; Liquid and gas, Group of Fluid: 1 and 2
Material Certicate
Pressure test/
Leak test certicate
Contact Yokogawa representative for the codes indicated as ‘-’.
*1: Applicable for Electrical connection code 2, 4, 7, and 9.
*2: Not applicable for option code /AL.
*3: Not applicable with color change option.
*4: This specication is included when amplier case code 2 is specied.
*5: Check/External indicator terminals cannot be used when this option code is specied. Not applicable for output signal code F.
*6: The unit of MWP (Max. working pressure) on the name plate of a housing is the same unit as specied by option codes D1, D3, and
D4.
*7: Applicable for output signal codes D, E and J. The hardware error indicates faulty amplier or capsule.
*8: Also see ‘Ordering Information’.
*9: Material traceability certication, per EN 10204 3.1B.
*10: Applicable for capsule code A.
*11: Applicable for capsule code B.
*12: Applicable for capsule code C.
*13: Applicable for capsule code D of EJ510 and EJ530.
*14: Pure nitrogen gas or pure water is used for oil-prohibited use (option codes K1 and K2).
*15: Applicable for wetted parts material code S.
*16: Applicable only for output signal code -E and -J.
*17: The change of pressure uctuation is monitored and then detects the impulse line blockage. See TI 01C25A31-01E for detailed
technical information required for using this function.
*18: Applicable for measurement span code D. If compliance with category III is needed, specify this option code.
*19: Applicable for EJX630A, EJA510E and EJA530E.
Not applicable for the combination of measurement span code A and wetted parts material code H.
Not applicable for option code K2, K3 or A1.
When specied range value includes minus value for A capsule, the accuracy shall be the standard accuracy even if high accuracy
option (/HAC) is specied.
*20: Applicable for capsule code D of EJX610A and EJX630A.
*9
Process connector M15
Test Pressure: 200 kPa (2 kgf/cm2) *
Test Pressure: 2 MPa (20 kgf/cm2) *
Test Pressure: 10 MPa (100 kgf/cm2) *
Test Pressure: 50 MPa (500 kgf/cm2) *
Test Pressure: 70 MPa (10150 psi) *
10
11
12
13
20
Nitrogen(N2) Gas or Water *
Retention time: one minute
14
T05
T06
T07
T08
T15
IM 01C25F01-01E
<9. General Specications>
9.4 Dimensions
Model EJ510, EJ530, EJX610A and EJX630A
With Process connections code 7
188(7.40)
110(4.33)
12
(0.47)
39
(1.54)
Extenal indicator
Conduit connection
(optional)
95(3.74)
60(2.36)*
2
Integral indicator
(optional)
Conduit connection
Shrouding bolt*
Zero
adjustment
4
9-10
Unit: mm (approx. inch)
54
(2.13)
6
(0.24)
Electrical connection
for code 5, 9, A, and D.
Mounting bracket
(optional)
*1: Only for EJ530 and EJX630A whose measurement span code is A, B, or C.
*2: 58 mm(2.28 inch) for measurement span code D.
*3: 11 mm(0.43 inch) for measurement span code D.
*4: Available only when specifying the option code including ATEX, IECEx or TIIS flameproof type.
126(4.96)
159(6.26)
12*3
(0.47)
With Process connections code 4
156
With Process connections code 8 and 9
24(0.94)
172
ø6
5(0.20)
(0.24)
(6.14)
(6.77)
165
(6.50)
2-inch pipe
(O.D. 60.5 mm)
ø78(3.07)
Ground terminal
Open to
atmosphere*
ø70
(2.76)
110(4.33)
1
129(5.08)
F0904.ai
Terminal Configuration
Communication
terminals (BT200 etc.)
connection hook
SUPPLY +
SUPPLY –
Check meter
connection hook
CHECK + or
ALARM +
CHECK – or ALARM –
*5*6
Terminal Wiring
+
SUPPLY
CHECK
or
ALARM
*5: When using an external indicator or check meter, the internal
resistance must be 10 Ω or less. A check meter or indicator
cannot be connected when /AL option is specified.
*6: Not available for fieldbus and PROFIBUS communication types.
Power supply and output terminal
–
+
External indicator (ammeter) terminal
–
or
Status contact output terminal
+
–
(when /AL is specified)
Ground terminal
*5*6
*6
F0905.ai
IM 01C25F01-01E
Revision Information
Title : Absolute Pressure and Gauge Pressure Transmitters
EJ510, EJ530, EJX610A and EJX630A
Manual No. : IM 01C25F01-01E
EditionDatePageRevised Item
1stAug. 2004—New publication.
2ndFeb. 2005—Re-number gure and table title.
—2.Revise words and phrases.
2-32.9.1• Add 'a. FM Intrinsically safe Approval.'
2-5• Add 'c. FM Intrinsically safe/FM Explosionproof Type.'
2-52.9.2• Add subsection '2.9.2 CSA Certication.'
2-72.9.3(1)• Add 'a. CENELEC ATEX (KEMA) Intrinsically safe Type.'
2-8• Correct number in Note 4. 10 MINUTES → 5 MINUTES
3-13.• Add descriptions in Note 2.
4-24.4• Add subsection 4.4.
7-17.1• Delete unnecessary description.
8-48.4.2• Correct calbe color in 1). black → white
8-58.4.3• Add description about stopper in 1).
9-1 to 9-59.• Add notes for FOUNDATION eldbus communication type.
9-19.1• Correct Span & Range Limits.
• Correct Burst Pressure Limits.
9-59.3• Add codes for CSA approval and note *3.
3rdJuly 20062-3 to 2-10• Add/change applicable standards.
2-62.9.2• Add descriptions for Note 2.
2-112.10• Change reference number for Australian standard.
2-112.11• Add descriptions for European Pressure Equipment Directive.
2-12• Add "2.12 Low Voltage Directive."
9-39.1• Add descriptions for stainless steel housing.
9-49.2• Add amplier housing code 2.
9-59.3• Add code of /SU2.
9-69.3• Add code of /PE3.
4thFeb. 2008—Change of the style code.
General• Change the gure of amplier housing.
1-11• Add style code table.
2-12.1• Update the Figure 2.2.
2-52.9.1• Add code /V1U.
2-62.9.2• Revise information for CSA Explosionproof type.
2-72.9.2• Add code /V1U.
2-7 to 2-82.9.3• Revise information for KEMA ameproof type. Add code /V1U.
2-92.9.3• Revise Figure in (2) Electrical connection and (6) Nameplate.
2-102.9.4• Revise information for IECEx ameproof type.
9-39.1• Revise weight information.
9-49.2• Add new sufx codes for 316 SST blind plugs and brackets.
9-59.3• Remove /KF2 and /KU2. Add /KF21, /KU21, /SF2 and /V1U.
9-6• Add /HC.
9-79.4• Revise external dimensions.
5thAug. 20092.12.1• Replace a name plate.
2-62.9.2• Correct certicate No. for CSA explosionproof type.
2-102.10• Revise standards.
2-11 to 2-122.11• Revise information of PED.
9-59.3• Add process sealing statement for CSA approval.
9-69.3• Add /A1, and /DG6.
i
IM 01C25F01-01E
EditionDatePageRevised Item
6thApr. 20102-12.3• Add limitation of ambient temperature for /HE.
2-4 to 2-112.9• Add limitation of ambient temperature for /HE.
9-39.1• Add material for cover O-rings.
9-5 to 9-69.3 • Add /HE.
7thMay 2010—Addition of EJX610A and EJX630A
1-11.• Add EJX610A and EJX630A.
2-122.11• Add EJX610A and EJX630A.
4-14.1• Add EJX630A. Add note for D capsule.
4-24.3• Add EJX630A.
5-15.1.1• Add EJX630A.
7-47.5• Revise warm up time.
8-18.3• Revise warm up time.
9-1 to 9-39.1• Add specications of EJX610A and EJX630A.
9-49.1• Delete JIS C0920 from Degrees of Protection.
9-69.2• Add codes of EJX610A and EJX630A.
9-7 to 9-89.3• Add option codes of EJX610A and EJX630A.
9-99.4• Add EJX610A and EJX630A.
9-10• Add EJX610A and EJX630A.
8thMar. 20122-3
9-4
9-5
9thJune 2012—
1-1
2.3 to 2.12
2-7 to 2-10
9.1 to end
10thJune 2013—Add note for PROFIBUS PA communication type.
2-3• Add note for multiple approval type.
2-6, 2-72.9.2 • Correct CSA applicable standards.
2-8 to 2-112.9.3 • Replace ATEX type n by ATEX Intrinsically safe Ex ic.
2-132.11
9-5 to 9-79.2 • Add PROFIBUS PA communication type.
9-89.3 • Replace ATEX type n by ATEX Intrinsically safe Ex ic.
9-109.4 • Update the drawing for process connection codes 8 and 9.
2.9
9.1
9.2
2.9
2.9.3
• Add note for blind plugs.
• Change description for a plate material.
• Add amplier housing code 3.
Add EJA-E series.
• Add Note. Add model name of EJA-E series.
• Delete /V1U.
• Delete /KS2, /KF21, and /KU21. Add /KS21, /KF22, and /KU22.
• Add information for EJA510E and EJA530E. Add output signal
code –J.
• Add note for CE marking notied body number.
• Delete information other than EJ50 and EJX60A.
• Add /V1U1.
• Add note for shrouding bolt.
ii
IM 01C25F01-01E
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.