Yokogawa EJA440E User Manual

User’s Manual
DPharp HART 5/HART 7 Communication Type (EJXA, EJAE)
IM 01C25T01-06EN
IM 01C25T01-06EN
4th Edition
DPharp HART 5/HART 7 Communication Type (EJXA, EJAE)
IM 01C25T01-06EN 4th Edition
Contents
1. Introduction ............................................................................................... 1-1
Regarding This Manual ....................................................................................1-1
1.1 Safe Use of This Product .................................................................................1-2
1.2 Warranty .............................................................................................................1-2
1.3 Abbreviation and Marking ................................................................................1-3
1.4 Applicable Conguration Files ........................................................................1-4
1.5 ATEX Documentation .......................................................................................1-5
2. Connection ................................................................................................ 2-1
2.1 Integral Indicator Display When Powering On ..............................................2-1
2.2 HART Protocol Revision ..................................................................................2-1
2.3 Device Description (DD) on a Conguration Tool and
Transmitter Device Revision............................................................................2-2
2.4 Set the parameters using DTM ........................................................................2-3
2.5 Interconnection Between DPharp and the HART Conguration Tool ........2-4
2.6 Power Supply Voltage and Load Resistance .................................................2-4
3. Parameter Setting ..................................................................................... 3-1
3.1 Menu Tree ..........................................................................................................3-1
3.1.1 Group I: DD and DTM (excluding EJX HART 5 DTM based on FDT1.2)
...........................................................................................................3-1
3.1.2 Group II: EJX HART 5 DTM based on FDT1.2 ..................................3-8
3.2 Basic Setup ......................................................................................................3-12
3.2.1 Tag and Device Information .............................................................3-12
3.2.2 Unit ...................................................................................................3-12
3.2.3 Range Change .................................................................................3-13
3.2.4 Output Mode ....................................................................................3-13
3.2.5 Damping Time Constant Setup ........................................................3-13
3.2.6 Output Signal Low Cut Mode Setup ................................................3-14
3.2.7 Impulse Line Connection Orientation Setup ....................................3-14
3.2.8 Static Pressure Setup ......................................................................3-15
3.3 Detailed Setup .................................................................................................3-15
3.3.1 Bi-directional Flow Measurement ....................................................3-15
3.3.2 Analog Output Signal Adjustable Range .........................................3-16
4th Edition: June 2013 (YK) All Rights Reserved, Copyright © 2010, Yokogawa Electric Corporation
IM 01C25T01-06EN
3.3.3 Integral Indicator Display Mode .......................................................3-16
3.3.4 Integral Indicator Scale Setup ..........................................................3-16
3.3.5 Unit for Displayed Temperature .......................................................3-18
3.3.6 Sensor Trim ......................................................................................3-18
3.3.7 Trim Analog Output ..........................................................................3-20
3.3.8 External Switch Mode ......................................................................3-20
3.3.9 CPU Failure Burnout Direction and Hardware Write Protect ..........3-21
3.3.10 Software Write Protection ................................................................3-21
3.3.11 Signal Characterizer ........................................................................3-22
3.3.12 Alarm ................................................................................................3-22
3.3.13 Status Output (only for EJX series: option code AL)
EJX
............3-23
3.3.14 Capillary Fill Fluid Density Compensation ......................................3-24
3.3.15 Test Output, Simulation, and Squawk ..............................................3-25
3.3.16 Burst Mode .......................................................................................3-27
3.3.16.1 In the case of using HART 5 ...........................................3-27
3.3.16.2 In the case of using HART 7 ...........................................3-27
3.3.17 Multidrop Mode ................................................................................3-32
3.3.17.1 Setting on HART 5 ..........................................................3-32
3.3.17.2 Setting on HART 7 ..........................................................3-33
3.3.18 Switching HART Protocol Revision .................................................3-33
ii
4. Diagnostics ............................................................................................... 4-1
4.1 Self-Diagnostics ................................................................................................4-1
4.1.1 Identify Problems by Using HART Conguration Tool .......................4-1
4.1.2 Checking with Integral Indicator .........................................................4-2
4.1.3 Status information available for HART 7
4.2 Advanced Diagnostics (Only for EJX series)
4.2.1 Multi-sensing Process Monitoring ......................................................4-3
4.2.2 Impulse Line Blockage Detection (ILBD) ...........................................4-3
4.2.2.1 Blockage Detection ...........................................................4-6
4.2.2.2 Combination of Reference Result and Blockage Detection
..........................................................................................4-8
4.2.2.3 Operation Parameters ......................................................4-9
4.2.2.4 Operating Procedure ...................................................... 4-11
4.2.2.5 Alarm and Alert Setting ...................................................4-12
4.2.2.6 Condition Check .............................................................4-14
4.2.2.7 Obtain Reference Values ................................................4-15
4.2.2.8 Capability Test of Blockage Detection Operation ...........4-16
4.2.2.9 Start ILBD Operation ......................................................4-16
4.2.2.10 Tuning .............................................................................4-17
4.2.2.11 Reset of Reference Value ...............................................4-18
4.2.2.12 ILBD Parameter List .......................................................4-19
HART 7
EJX
............................4-2
.....................................4-3
IM 01C25T01-06EN
4.2.3 Heat Trace Monitoring......................................................................4-21
4.2.3.1 Flg Temp Coef Setting ....................................................4-21
4.2.3.2 Out of Temperature Measurement Range ......................4-22
4.2.3.3 Parameter Lists for Heat Trace Monitoring .....................4-23
4.3 Alarms and Countermeasures ......................................................................4-24
5. Parameter Summary ................................................................................ 5-1
Appendix 1. Safety Instrumented Systems Installation ............................A1-1
A1.1 Scope and Purpose ....................................................................................... A1-1
A1.2 Using the transmitter for an SIS Application .............................................. A1-1
A1.2.1 Safety Accuracy ...............................................................................A1-1
A1.2.2 Diagnostic Response Time ..............................................................A1-1
A1.2.3 Setup ................................................................................................A1-1
A1.2.4 Required Parameter Settings ..........................................................A1-1
A1.2.5 Proof Testing ....................................................................................A1-1
A1.2.6 Repair and Replacement .................................................................A1-2
A1.2.7 Startup Time .....................................................................................A1-2
A1.2.8 Firmware Update .............................................................................A1-2
A1.2.9 Reliability Data .................................................................................A1-2
A1.2.10 Lifetime Limits ..................................................................................A1-2
A1.2.11 Environmental Limits .......................................................................A1-2
A1.2.12 Application Limits .............................................................................A1-2
A1.3 Denitions and Abbreviations ...................................................................... A1-3
A1.3.1 Denitions ........................................................................................A1-3
A1.3.2 Abbreviations ...................................................................................A1-3
iii
Appendix 2. ILBD Check List ........................................................................A2-1
Revision Information
IM 01C25T01-06EN
<1. Introduction>

1. Introduction

1-1
Thank you for purchasing the DPharp EJX series pressure transmitter/EJA series pressure transmitter(“transmitter”).
The transmitters are precisely calibrated at the factory before shipment. To ensure both safety and efciency, please read this manual carefully before operating the instrument. This manual describes the HART protocol communication functions of the transmitter and explains how to set the parameters for the transmitters using the HART conguration tool. For information on the installation, wiring, and maintenance of the transmitters, please refer to the user’s manual of each model.
WARNING
When using the transmitter in a Safety Instrumented Systems (SIS) application, refer to Appendix 1 in this manual. The instructions and procedures in the appendix must be strictly followed in order to maintain the designed safety integrity of the transmitter.
• Please note that changes in the specications, construction, or component parts of the instrument may not immediately be reected in this manual at the time of change, provided that postponement of revisions will not cause difculty to the user from a functional or performance standpoint.
• The following safety symbols are used in this manual:
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.

Regarding This Manual

• This manual should be provided to the end user.
• The contents of this manual are subject to change without prior notice.
• All rights reserved. No part of this manual may be reproduced in any form without Yokogawa’s written permission.
• Yokogawa makes no warranty of any kind with regard to this manual, including, but not limited to, implied warranty of merchantability and tness for a particular purpose.
• If any question arises or errors are found, or if any information is missing from this manual, please inform the nearest Yokogawa sales ofce.
• The specications covered by this manual are limited to those for the standard type under the specied model number break-down and do not cover custom-made instruments.
IMPORTANT
Indicates that operating the hardware or software in this manner may damage it or lead to system failure.
NOTE
Draws attention to information essential for understanding the operation and features.
IM 01C25T01-06EN
<1. Introduction>
1-2

1.1 Safe Use of This Product

For the safety of the operator and to protect the instrument and the system, please be sure to follow this manual’s safety instructions when handling this instrument. If these instructions are not heeded, the protection provided by this instrument may be impaired. In this case, Yokogawa cannot guarantee that the instrument can be safely operated. Please pay special attention to the following points:
(a) Installation
• This instrument may only be installed by an engineer or technician who has an expert knowledge of this device. Operators are not allowed to carry out installation unless they meet this condition.
• With high process temperatures, care must be taken not to burn yourself by touching the instrument or its casing.
• Never loosen the process connector nuts when the instrument is installed in a process. This can lead to a sudden, explosive release of process uids.
• When draining condensate from the pressure detector section, take appropriate precautions to prevent the inhalation of harmful vapors and the contact of toxic process uids with the skin or eyes.
• When removing the instrument from a hazardous process, avoid contact with the process uid and the interior of the meter.
• All installation shall comply with local installation requirements and the local electrical code.
(b) Wiring
• The instrument must be installed by an engineer or technician who has an expert knowledge of this instrument. Operators are not permitted to carry out wiring unless they meet this condition.
• Before connecting the power cables, please conrm that there is no current owing through the cables and that the power supply to the instrument is switched off.
(c) Operation
• Wait 10 min. after the power is turned off before opening the covers.
(d) Maintenance
• Please carry out only the maintenance procedures described in this manual. If you require further assistance, please contact the nearest Yokogawa ofce.
• Care should be taken to prevent the build up of dust or other materials on the display glass and the name plate. To clean these surfaces, use a soft, dry cloth.
(e) Modication
• Yokogawa will not be liable for malfunctions or damage resulting from any modication made to this instrument by the customer.

1.2 Warranty

• The warranty shall cover the period noted on the quotation presented to the purchaser at the time of purchase. Problems occurring during the warranty period shall basically be repaired free of charge.
• If any problems are experienced with this instrument, the customer should contact the Yokogawa representative from which this instrument was purchased or the nearest Yokogawa ofce.
• If a problem arises with this instrument, please inform us of the nature of the problem and the circumstances under which it developed, including the model specication and serial number. Any diagrams, data and other information you can include in your communication will also be helpful.
• The party responsible for the cost of xing the problem shall be determined by Yokogawa following an investigation conducted by Yokogawa.
• The purchaser shall bear the responsibility for repair costs, even during the warranty period, if the malfunction is due to:
- Improper and/or inadequate maintenance by
the purchaser.
- Malfunction or damage due to a failure
to handle, use, or store the instrument in accordance with the design specications.
- Use of the product in question in a location
not conforming to the standards specied by Yokogawa, or due to improper maintenance of the installation location.
- Failure or damage due to modication or
repair by any party except Yokogawa or an approved representative of Yokogawa.
- Malfunction or damage from improper
relocation of the product in question after delivery.
- Reason of force majeure such as res,
earthquakes, storms/oods, thunder/ lightening, or other natural disasters, or disturbances, riots, warfare, or radioactive contamination.
IM 01C25T01-06EN
<1. Introduction>
1-3

1.3 Abbreviation and Marking

The following models, HART protocol revisions and conguration les are applied in this manual.
HART
Model
EJAE
EJXA*
*: Not applicable for EJX9A
In order to classify multiple models, HART protocol revisions, or conguration les, abbreviated words or marks are used as below in this manual.
■ Applied models
• The following expression is used instead of model name.
[Model: EJAE] EJA series or EJA
[Model: EJXA (excluding EJX9A)] EJX series or EJX
EJX
• applied for EJX series only.
■ HART protocol revision
• Two HART protocol revisions are expressed for short as below.
Protocol
Revision
5 7 5 7
Conguration le
• DD (Device Description)
• DTM (FDT1.2)
• DTM (FDT2.0)
mark indicates specication or function
■ Conguration le
Three conguration les are applied in this manual.
• DD stands for Device Description (le).
• This manual covers two revision DTM (Device Type Manager) les based on FDT (Field Device Tool) standard. The difference of revisions is indicated as follows.
[DTM for FDT 1.2] DTM (FDT1.2) or [1.2] [DTM for FDT2.0] DTM (FDT2.0) or [2.0]
The root referring to a parameter is classied to Group I or II according to applied conguration le.
Conguration
le
DD
DTM (FDT2.0) I
Note: Only DTM (FDT1.2) for EJX with HART 5 is classied to
Group II.
EJA EJX
HART 5 HART 7 HART 5 HART 7
I
I
IDTM (FDT1.2) II
As the above, two roots referring to a parameter is shown in this manual.
Procedure to call up xxx parameter
DD and DTM (excluding EJX_HART 5[1.2])
EJX_HART 5[1.2] DTM …→…
[Root Menu] →…
HART protocol revision 5: HART 5 HART protocol revision 7: HART 7
HART 7
mark indicates specication or function applied for HART 7 only. Refer to section 2.2 for typical functions for HART 7.
HART 5
mark indicates specication or function applied for HART 5 only.
For parameter menu tree, refer to section 3.1.
IM 01C25T01-06EN
<1. Introduction>
1.4 Applicable Conguration Files
DD
File Applied device
File name
010 =2 or later 0a0 =1 or later 030 =3 or later 0a0 =2 or later
DD revision
()
Model
EJA series
EJX series
DTM
File Applied device
File name
EJA-NEXT
HART DTM
DTM
revision
3.3.0.140 or later
*2
EJA-NEXT
FDT2.0
5.0.0.0 or later
*3
HART DTM
EJA-NEXT
HART 7 DTM
3.3.0.140 or later
*2
EJA-NEXT
FDT2.0
5.0.0.0 or later
*3
HART 7 DTM
EJXV3.1 1.4.160.8 or later
EJX FDT2.0
HART DTM
EJX HART 7
DTM
EJX FDT2.0
HART 7 DTM
*1: The DTM is included in Yokogawa DTM Library HART 2012-2/Device Files R3.03.03 or later. *2: The DTM is included in Yokogawa Device DTM Library 2.3/Device Files R3.03.03 or later. *3: The DTM is included in Device DTM Library 4.0 or later.
5.0.0.0 or later
3.3.0.140 or later
5.0.0.0 or later
*1
*3
*2
*3
FDT
revision
FDT1.2
FDT2.0
FDT1.2
FDT2.0
FDT1.2
FDT2.0
FDT1.2
FDT2.0
HART protocol
revision
5 EJA-NEXT (0x5C) 1 7 EJA-NEXT(0x375C) 10 5 EJX (0x51) 3 7 EJX (0x3751) 10
Model
EJA series
EJX series
HART
protocol
revision
5
7
5
7
Device type
Device type
EJA-NEXT
(0x5C)
EJA-NEXT
(0x375C)
EJX
(0x51)
EJX
(0x3751)
1-4
Device
revision
Device
revision
1
10
3
10
Refer to section 2.2 to 2.4 for conrmation of each revision number.
IM 01C25T01-06EN
<1. Introduction>

1.5 ATEX Documentation

This is only applicable to the countries in European Union.
1-5
GB
DK
E
NL
SK
CZ
I
LT
LV
EST
PL
SF
D
SLO
P
H
F
BG
RO
S
M
GR
IM 01C25T01-06EN
<2. Connection>

2. Connection

2.1 Integral Indicator Display When Powering On

For models with the integral indicator code “D”, the display shows all segments in the LCD and then changes to the displays shown below sequentially.
All segments display
Model name (3 s)

2.2 HART Protocol Revision

NOTE
LCD display can be set to “All segments display” only.
• Procedure to call up the display
DD (HART 5/7) DTM (HART 7 /EJA:HART 5)
DTM
(EJX:HART 5)
ON
OFF
[Root Menu] (Refer to subsection
3.1.1) → Detailed setup → Display condition → Chg power on info
Conguration → Local Display → Chg power on info
Show all segments display, Model name, Communication Protocol, and Device Revision when powering on.
Show all segments display when powering on.
2-1
Communication Protocol (3 s)
Device Revision (3 s)
F0200.ai
Either “5” or “7” is displayed on the “Communication Protocol” display as HART protocol revision followed by device revision number on the “Device Revision” display.
NOTE
This function is available for software revision
2.02 or later. Software revision can be checked by the following procedure.
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu](Refer to subsection
3.1.1) → Review → Software rev
Conguration → Device information1 → Software rev
NOTE
In this User’s Manual, HART protocol revision 5 and 7 are described as HART 5 and HART 7 respectively.
For the models with the output signal code “-J”, HART protocol revision 5 or 7 is selectable. The protocol revision is set as specied in the order.
The typical function which is available by HART protocol revision 7 is listed as follows. Refer to HART 7 description in this document or
HART 7
mark
for detail.
• Long Tag Supporting Up to 32 Characters Long tag secures a better asset management
with abundant digits in its software.
• Enhanced Burst Mode and Event Notication Advanced burst mode includes the variety
of transmission setting by specifying burst variables, update period, and message trigger mode, and event notication function gives you alert signal based on the status change in preset values and self-diagnosis.
• Squawk Identifying the transmitter by displaying the
particular pattern on LCD
• Multidrop Communication Up to 63 transmitters can be connected. An
analog signal output available for one device in a loop.
How to conrm protocol revision is shown below.
There are three ways to conrm the protocol revision set to the transmitter.
IM 01C25T01-06EN
<2. Connection>
F0201.ai
: Refer to USER'S MANUAL.
Made in Japan TOKYO 180-8750 JAPAN
MODEL SUFFIX
SUPPLY OUTPUT MWP
mA DC
V DC
STYLE
CAL RNG
NO.
XXX - - - XX
Revision No.
(a) Conrmation on the name plate The last numerical number engraved after
Serial number and year of production shows HART protocol revision number at the shipment which is shown in Figure 2.1.
NOTE
HART 7 communication is supported by FieldMate R2.02 or later.
NOTE
When the output signal code of the transmitter is “-J”, HART protocol revision can be changed. Refer to subsection 3.3.18 about the procedure of the revision change of HART 5 and HART 7.
2-2
Output Signal
Code
Revision No.
HART Protocol
Revision
5 HART 5
J
7 HART 7
- HART 7
E - HART 5
Figure 2.1 Hart Protocol Revision Number on
Name Plate
(b) Conrmation on integral indicator
(A case of integral indicator code D is specied) Refer to section 2.1. (c) Conrmation by using HART conguration tool
1) Connect the conguration tool to the transmitter.
2) Conrm numerical number displayed on “Universal rev” column.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu (refer to 3.1.1) ] → Review → Universal rev
Conguration → HART →Universal rev
IMPORTANT
Protocol revision supported by HART conguration tool must be the same or higher than that of the transmitter.
Protcol revision supported by HART conguration tool
5 7
Protocol revision of the transmitter
 : Communication OK×: Communication NG
5
7 ×
2.3 Device Description (DD) on a Conguration Tool and Transmitter Device Revision
Before using a HART conguration tool, conrm that the DD for the transmitter is installed in the conguration tool.
About the DD, use the device type, device revision and DD Revision shown in the Table 2.1.
Table 2.1 HART Protocol Revision, Device
Revision and DD Revision
HART
Protocol
Revision
(*1)
5
7
*1: When the output signal code is “–E”, only “5” is available.
The device revision of the transmitter and DD can be conrmed as shown below.
If the correct DD is not installed in the conguration tool, download it from the ofcial web site of HART Communication Foundation.
(1) Conrmation of device revision for the
transmitter
● Conrmation on integral indicator (A case of integral indicator code D is specied)
Refer to the section 2.1
DPharp Pressure Transmitter
Model
EJX series
EJA series
EJX series
EJA series
Device
Type
EJX
(0x51)
EJA-NEXT
(0x5C)
EJX
(0x3751)
EJA-NEXT
(0x375C)
Device
RevisionDDRevision
3
1
10
10
3
or later
2
or later
2
or later
1
or later
IM 01C25T01-06EN
<2. Connection>
2-3
● Conrmation by using HART conguration tool
a) Connect the conguration tool to the
transmitter.
b) Conrm numerical number displayed on
“Fld dev rev” column.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu (refer to 3.1.1) ] → Review →Fld dev rev
Conguration → HART →Fld dev rev
(2) Conrmation of device revision for the
conguration tool
Conrm the device revision from the installed
DD le name according to the procedure provided for the conguration tool.
The rst two digits indicate the device revision
and the next two digits indicate the DD revision.
0 a 0 2. X X X
DD revision
Device revision

2.4 Set the parameters using DTM

When congure the parameters using FieldMate, use the DTM (Device Type Manager) shown in the Table 2.2.
NOTE
The DTM revision can be conrmed by “DTM setup”. Device Files is a Media included in FieldMate. The user registration site provides Device Files with the latest update programs. (URL: https://voc.yokogawa.co.jp/PMK/) In case update, following operation by “DTM setup” is required.
• Update DTM catalog
• Assign corresponding DTM to the device (refer to Table 2.2)
Refer to FieldMate Instruction Manual for detail.
NOTE
Device revision of DD le is given in hexadecimal
Table 2.2 Applicable DTM
File Applied device
File name
EJA-NEXT
HART DTM
EJA-NEXT
FDT2.0
HART DTM
EJA-NEXT
HART 7 DTM
EJA-NEXT
FDT2.0
HART 7 DTM
EJXV3.1 1.4.160.8 or later
EJX FDT2.0
HART DTM
EJX HART 7
DTM
EJX FDT2.0
HART 7 DTM
*1: The DTM is included in Yokogawa DTM Library HART 2012-2/Device Files R3.03.03 or later. *2: The DTM is included in Yokogawa Device DTM Library 2.3/Device Files R3.03.03 or later. *3: The DTM is included in Device DTM Library 4.0 or later.
DTM
revision
3.3.0.140 or later
5.0.0.0 or later
3.3.0.140 or later
5.0.0.0 or later
5.0.0.0 or later
3.3.0.140 or later
5.0.0.0 or later
*2
*3
*2
*3
*1
*3
*2
*3
FDT
revision
FDT1.2
FDT2.0
FDT1.2
FDT2.0
FDT1.2
FDT2.0
FDT1.2
FDT2.0
Model
EJA series
EJX series
HART
protocol
revision
5
7
5
7
Device type
EJA-NEXT
(0x5C)
EJA-NEXT
(0x375C)
EJX
(0x51)
EJX
(0x3751)
Device
revision
1
10
3
10
IM 01C25T01-06EN
<2. Connection>
F0203.ai
2-4
2.5 Interconnection Between DPharp and the HART Conguration Tool
The HART conguration tool can interface with the transmitter from the control room, the transmitter site, or any other wiring termination point in the loop, provided there is a minimum of 250 Ω between the connection and the power supply. To communicate, it must be connected in parallel with the transmitter; the connections are non-polarized. Figure 2.2 illustrates the wiring connections for direct interface at the transmitter site for the DPharp. The HART conguration tool can be used for remote access from any terminal strip as well.
Control room
Terminal
board
Distributor
DPharp
Relaying terminals
USB
FieldMate
Modem

2.6 Power Supply Voltage and Load Resistance

When conguring the loop, make sure that the external load resistance is within the range in the gure below.
(Note) With an intrinsically safe transmitter, external load
resistance includes safety barrier resistance.
600
External load resistance
R (Ω)
250
0 10.5 16.6 25.2 42
Figure 2.3 Relationship between Power Supply
E–10.5
R=
0.0244
Power supply voltage E (V DC)
Communication
applicable range
Voltage and External Load Resistance
PULSE
SUPPLY
CHECK ALARM
HART configuration tool
PC/FieldMate
USB
Figure 2.2 Connecting the HART Conguration
Tool
F0202.ai
IM 01C25T01-06EN
<3. Parameter Setting>

3. Parameter Setting

3.1 Menu Tree

The structure of menu tree varies according to conguration tool based on DD or DTM. The difference is classied into two groups (I and II) as shown in the below table.
3-1
Applied model
EJA series
EJX series
I: DD and DTM (excluding EJX HART 5 DTM based on FDT1.2) II: EJX HART 5 DTM based on FDT1.2
HART protocol
revision
DD
HART 5 HART 7 HART 5 II
I-1
HART 7 I-2
. . . . . . . . . . . . . . . . . . . . . . . . .
FDT1.2 FDT2.0
I-2
. . . . .
DTM
I-2
Refer to section 3.1.1. Refer to section 3.1.2.

3.1.1 Group I: DD and DTM (excluding EJX HART 5 DTM based on FDT1.2)

When FieldMate with DD and DTM (excluding EJX HART 5 DTM based on FDT1.2) is used in order to set or refer to parameters, there is difference on the initial root menu as below.
I-1 DD
Root Menu
• Device setup
• Pres
• AO
• LRV
• URV
I-2 DTM
Root Menu
• Device Configuration* - Configure/Setup
• Diagnostic*
• Process Variable*
• Process variables
• Diag/Service
• Basic setup
• Detailed setup
• Review
• Basic setup
• Detailed setup
• Review
• Diag/Service
• Process Variables
A B C D, E
C D, E
B A
*: The next parameter is displayed on the top menu when using the DTM based or FDT2.0.
A
Process variables
Pres
• Pres %
AO
• SP
• SP %
• Snsr temp
• Engr Disp
• Engr exp
• Engr Unit
• Device Variables and Status
HART 7
• Pres
• Pres Data Quality
• Pres Limit Status
• SP
• SP Data Quality
• SP Limit Status
• Snsr temp
• Temp Data Quality
• Temp Limit Status
• Pres %
• Percent Range Data Quality
• Percent Range Limit Status
• AO
• Loop Current Data Quality
• Loop Current Limit Status
DTM DD
• PV
• PV Data Quality
• PV Limit Status
• SV
• SV Data Quality
• SV Limit Status
• TV
• TV Data Quality
• TV Limit Status
• % rnge
• % rnge Data Quality
• % rnge Limit Status
• Loop current
• Loop current Data Quality
• Loop current Limit Status
HART 7
F0301-01.ai
: HART 7 only
F0301-02.ai
IM 01C25T01-06EN
<3. Parameter Setting>
HART 7
B
: HART 7 only
EJX
: EJX Series only
3-2
Diag/Service
• Test device (DD)
• Status (DTM)
• Loop Test(DD)
• Test (DTM)
• Calibration
• Status
• Self test
• Master test
• Squawk
• Simulate
HART 7
HART 7
• Loop test
• Self test
• Master test
• Squawk
• Simulate
HART 7
HART 7
• Test Auto Release
Time
• Re-range (DD)
• Keypad input (DTM)
• Analog output trim
• Status group 1
• Status group 2
• Status group 3
• Status group 4
• Status group 5
• Status group 6
• Status group 7
• Status group 8
• Status group 9
• Status group 10
• Device status
• Ext dev status
• Cfg chng count
HART 7
HART 7
HART 7
HART 7
• Reset Cfg chng flag
• Time Stamp
HART 7
• Keypad input
• Apply values
• D/A trim
• Scaled D/A trim
• Clear D/A trim
HART 7
• LRV
• URV
• Unit
• LSL
• USL
• Min span
• Diag Parameters
EJX
Error log
• Test Auto Release Time (DD)
• Pres sensor trim
• SP sensor trim
• Trim info.
See B1 (next page)
• Error log view
Error log Clear
• Pres Zero trim
• Pres trim
• P LTP
• P UTP
• Pres trim info.
• Static Pres trim
• SP LTP
• SP UTP
• SP trim info.
• Trim Who
• Trim Date
• Trim Loc
Trim Desc
• P LTD
• P UTD
• Clear P snsr trim
• SP LTD
• SP UTD
• Clear SP snsr trim
F0301-03.ai
IM 01C25T01-06EN
<3. Parameter Setting>
Diag Mode
Diag Applicable
Diag Variables
EJX
: EJX Series only
Ratio fDP Status
Ratio fDP
Ratio fSPl Status
Ratio fSPl
Ratio fSPh Status
Ratio fSPh
BlkF Status
BlkF
DP Avg Status
DP Avg
CRatio fDP Status
CRatio fDP
NRatio fDP Status
NRatio fDP
3-3
Diag Parameters
EJX
B1
Diag Error
Diag Option
ILBD Parameters
Status
Configuration
Diag Reference
Fluct Variables
Set Diag Mode
Diag Period
Diag Lim
Diag Description
Ref fDP Status
Ref fDP
Ref fSPl Status
Ref fSPl
Ref fSPh Status
Ref fSPh
Ref BlkF Status
Ref BlkF
Ref DP Avg Status
Ref DP Avg
fDP Status
fDP
fSPl Status
fSPl
fSPh Status
fSPh
Lim fDPmax
Lim fDPmin
Lim fSPlmax
Lim fSPlmin
Lim fSPhmax
Lim fSPhmin
Lim BlkFmax
Lim BlkFmin
Lim DPAvgmax
Lim DPAvgmin
HT Parameters
Diag Output
Status
Configuration
Diag Out Option
Diag Fixed Out Val
Diag Reference
Diag Supp Count
Diag Ref Lim
Diag DPComp
Snsr temp
Amp temp
Flg temp
Flg Temp Coef
Flg Temp Lim
Diag Description
Ref fDP
Ref fSPl
Ref fSPh
Ref BlkF
Ref DP Avg
Ref Lim fDPmin
Ref Lim fSPmin
Ref Lim BlkFmax
Flg Temp Hi Alert Val
Flg Temp Lo Alert Val
F0301-04.ai
IM 01C25T01-06EN
<3. Parameter Setting>
C
• Basic setup
Tag
HART 7
3-4
: HART 7 only
• Long tag
HART 7
• Unit
• Re-range
• Device infomation
• Xfer fnctn
• Pres Damp
• Low cut
• Low cut mode
• H/L Swap
• SP setup
• Keypad input
• Apply values
• Date
• Descriptor
• Message
• Write protect
• Model
HART 7
• SP Range
• SP Unit
• SP Damp
• SP A/G Setup
• SP H/L Select
• LRV
• URV
• Unit
• LSL
• USL
• Min span
• Keypad input
• SP Apply values
• A/G Select
• Atm. Pres Value
• SP LRV
• SP URV
• SP Unit
• SP LSL
• SP USL
• SP Min span
F0301-05.ai
IM 01C25T01-06EN
<3. Parameter Setting>
3-5
D
• Detailed setup
Review
• Sensors
• Signal condition
• Pressure sensor
• SP sensor
• Temp sensor
• Snsr temp
• Amp temp
• Temp Unit
• Process variables
• Pres
• Pres %
• Unit
• Pres sensor trim
• SP
• SP %
• SP Unit
• A/G Select
• SP H/L Select
• SP sensor trim
• SP setup
• Pres
• Pres %
• SP
• Snsr temp
• Pres Zero trim
• Pres trim
• P LTP
• P UTP
• Pres trim info.
• Static Pres trim
• SP LTP
• SP UTP
• SP trim info.
• SP Range
• SP Unit
• SP Damp
• SP A/G Setup
• SP H/L Select
HART 7
: HART 7 only
EJX
: EJX Series only
• P LTD
• P UTD
• Clear P snsr trim
• SP LTD
• SP UTD
• Clear SP snsr trim
• SP LRV
• SP URV
• SP Unit
• SP LSL
• SP USL
• SP Min Span
• Keypad input
• SP Apply values
• A/G Select
• Atm. Pres Value
• Output condition
• Display condition
• Device information
• Test Key
• Re-range
• Unit
• Xfer fnctn
• Pres Damp
• Low cut
• Low cut mode
• H/L Swap
• Bi-dir mode
• Quick resp
• T.Z. Cmp menu
• S.C. menu
• Process variables
• Analog output
See D1 (next page)
See E
• Keypad input
• Apply values
• S.C.
• Num of points
• Point setting
• X Start
• Y Start
• X End
• Y End
• Loop test
• Loop current mode
HART 7
• D/A trim
• Scaled D/A trim
• Clear D/A trim
• AO alm typ
• Channel flags
HART 7
• Auto recover
• AO lower limit
• AO upper limit
• LRV
• URV
• Unit
• LSL
• USL
• Min span
• T.Z. Cmp mode
• Temp Zero
• Pres
• Pres %
• AO
• SP
• SP %
• Snsr temp
• Engr Disp
• Engr exp
• Engr Unit
• Digital Output
EJX
F0301-06.ai
IM 01C25T01-06EN
<3. Parameter Setting>
D1
• HART output
• Poll addr
• Loop current mode
HART 7
• Num req preams
• Num resp preams
HART 7
• Burst Condition
HART 7
• Burst mode
• Burst option
HART 5
HART 5
• Burst Message 1
• Burst mode
• Burst Command
• Burst Device Variables
• Set Burst Trigger
• Set Burst Period
• Burst Msg Trigger Mode
• Burst Trigger Level
• Update Period
• Max Update Period
HART 5
HART 7
3-6
: HART 5 only : HART 7 only
EJX
: EJX Series only
• Burst Variable Code
(DD)
• Device Variable Code (DTM)
• Process Alerts (DD)
• Process Alerts (DTM)
• Pres Alert mode
• Config Pres Alerts
• SP Alert mode
• Config SP Alerts
• Temp Alert mode
• Config Temp Alerts
• DO Config
EJX
• Pres Alert
• SP Alert
• Temp Alert
• DO Config
EJX
• Burst Message 2
• Burst Message 3
• Event Notification
• PV Update time period (DD)
• SV Update time period (DD)
• TV Update time period (DD)
• Update time period (DTM)
• SP update time (DTM)
• Temp update time (DTM)
• Hi Alert Val
• Lo Alert Val
• LSL
• USL
• Temp Hi Alert Val
• Temp Lo Alert Val
• Digital Output
• DO Select
• DO Signal type
• DO Test
• Pres Alert mode
• Config Pres Alerts
• SP Alert mode
• Config SP Alerts
• Temp Alert mode
• Config Temp Alerts
• Digital Output
• DO Select
• DO Signal type
• DO Test
Same as above Same as above
• Event Notification Control
• Event Mask
• Set Event Notification Timing
• Event Notification Retry Time
• Max Update Time
• Event Debounce Interval
• Knowledge (DD)
• Knowledge (DTM)
• SP Hi Alert Val
• SP Lo Alert Val
• SP LSL
• SP USL
• Hi Alert Val
• Lo Alert Val
• LSL
• USL
• SP Hi Alert Val
• SP Lo Alert Val
• SP LSL
• SP USL
• Temp Hi Alert Val
• Temp Lo Alert Val
• Device Status Mask
• Status group 1 Mask to 10 Mask
• Ext dev status Mask
• Device Diagnostic Status 0 Mask
• Device Diagnostic Status 1 Mask
• AO saturated Mask
• AO fixed Mask
• Event Status
• Time First Unack Event Triggered
• Acknowledge Event Notificatoin
• Event Status
• Event Number
• Time First Unack Event Triggered
• Latched Cfg chng count
• Latched Device Status
• Latched Status group 1 to 10
• Latched Ext dev status
• Latched Device Diagnostic Status 0
• Latched Device Diagnostic Status 1
• Latched AO saturated
• Latched AO fixed
F0301-07.ai
IM 01C25T01-06EN
<3. Parameter Setting>
E
• Detailed setup
Review
• Sensors
• Signal condition
• Output condition
• Display condition
• Disp select
• P disp condition
• Disp Out1
• Disp Out2
• Disp Out3
• Disp Out4
• Disp Pres % fnctn
• Disp Pres % Reso
• Pres disp point
HART 7
3-7
: HART 7 only
• Device information
• Test Key
• SP disp condition
• Engr disp range
• Bar indicator
• Chg power on info
• Field device info
• Sensor infomation
• Self test (DD)
• SP disp point
• Engr LRV
• Engr URV
• Engr exp
• Engr Unit
• Engr point
• Set Engr Unit
• Modify Engr Unit
Tag
• Long tag
HART 7
Date
• Descriptor
• Message
• Model 1
• Model 2
• Model 3
• Write protect
• Wrt protect menu
• Ext SW
• Revision #’s
• Additional Info
• Option Password
• Isoltr matl
• Fill fluid
• Gasket matl
• Process Conn matl
• Drain vent matl
• Process Conn type
• RS isoltr matl
• Process Conn size
• Num of RS
• RS fill fluid
• RS type
• Write protect
• Enable wrt 10min
• New password
• Software seal
• Universal rev
• Fld dev rev
• Software rev
• Chg universal rev
• Style No.
• Serial No.
• Mftr Date
• Extra No.
• Final asmbly num
• Dev id
• Distributor
• Country
• Max dev vars
HART 7
• Device Profile
HART 7
HART 7
F0301-08.ai
IM 01C25T01-06EN
<3. Parameter Setting>

3.1.2 Group II: EJX HART 5 DTM based on FDT1.2

Root Menu
• Process Variables
• Device Status
• Diag and Service
• Easy Setup
• Configuration
• Calibration
• Write Protect
P
• Process Variables
• Pres %
• AO
• URV
• LRV
• Xfer fnctn
• Pres Damp
• Pres
• SP
• A/G Select
• Snsr temp
• Engr Disp
• Engr exp
• Engr Unit
• USL
• LSL
• P UTP
• P LTP
P Q R S T U V
3-8
Q
• Device Status
• Process Variable
• Diagnostic List
• Pres %
• Pres
• SP
• Snsr Temp
• Device Status
• Hardware Failure
• Transducer Status
• Diag Status
• Configuration
F0301-21.ai
IM 01C25T01-06EN
<3. Parameter Setting>
R
• Diag and Service
• Service
• Advanced Diag Variables
• Loop test
• Master test
• DO Test
• Error log view
• Error log Clear
• Test Key
• Test Auto Release Time
• Diag Description
• BlkF
• fDP
• fSPh
• fSPl
• DPAvg
• Ref BlkF
• Ref fDP
• Ref fSPh
• Ref fSPl
• Ref DPAvg
• CRatio fDP
• NRatio fDP
• Ratio fDP
• Ratio fSPh
• Ratio fSPl
• Cap Temp
• Amp Temp
• Flg Temp
3-9
• Advanced Diag Configurations
• Advanced Diag Alerts
• Impulse Line Blockage Detection
• Heat Trace
• Diag Out Option
• Diag Fixed Out Val
• Diag Error
• Diag Mode
• Diag Period
• Diag DPComp
• Diag Description
• Ref BlkF
• Ref fDP
• Ref fSPh
• Ref fSPl
• Ref DPAvg
• Alarm Notification
• Threshold
• Alarm Notification
• Threshold
• Flg Temp Coefficient
• Tuning
• Flg Temp
• Related to high side alarm
• Related to both side alarm
• Related to low side alarm
• Related to Flg temp alarm
• Diag Option
• Diag Suppress Count
• Sensitivity
• Fig Temp High Limit
• Fig Temp Low Limit
S
• Easy Setup
• Tag
• USL
• LSL
• Unit
• URV
• LRV
• Xfer fnctn
• Pres Damp
• Low cut
• Low cut mode
F0301-22.ai
IM 01C25T01-06EN
<3. Parameter Setting>
T
• Configuration
• Pressure Sensor
• Static Pressure Sensor
• Physical Information
• Process Input
• Analog Output
• Local Display
• Signal Characterizer Menu
• Process Alerts
• Device Information1
• Process Conn type
• Process Conn matl
• Process Conn size
• Gasket matl
• Isoltr matl
• Drain vent matl
• Fill fluid
• RS type
• RS isoltr matl
• RS fill fluid
• Num of RS
• Disp Out1
• Disp Out2
• Disp Out3
• Disp Out4
• Disp Pres % fnctn
• Disp Pres % Reso
• Pres disp point
• Engr URV
• Engr LRV
• Engr Unit
• Engr exp
• Engr point
• SP disp point
• Bar Indicator
• Chg power on info
• Model
• Manufacturer
• Hardware rev
• Software rev
• Date
• Descriptor
• Message
• Final asmbly num
• Auto recover
• Ext SW
• SP USL
• SP LSL
• SP Min Span
• SP Unit
• SP URV
• SP LRV
• SP Damp
• SP H/L Select
• A/G Select
• Atm. Pres Value
• Pres %
• AO
• Unit
• URV
• LRV
• Apply values
• Xfer fnetn
• Pres Damp
• Low cut
• Low cut mode
• AO alm typ
• AO upper limit
• AO lower limit
• Quick resp
• Bi-dir mode
• Pres Alert mode
• Hi Alert Val
• Lo Alert Val
• SP Alert mode
• SP Hi Alert Val
• SP Lo Alert Val
• Temp Alert mode
• Temp Hi Alert Val
• Temp Lo Alert Val
• Digital Output
• DO Select
• DO Signal type
3-10
• USL
• LSL
• Min span
• H/L Swap
• T.Z. Cmp mode
• Temp Zero
• Pres
• Unit
• Pres %
• SP
• SP Unit
• SP %
• Snsr temp
• Temp Unit
• S.C.
• Num of points
• X Start
• X End
• Y Start
• Y End
• X1
• X2
• X3
• X4
• X5
• X6
• X7
• X8
• X9
• Y1
• Y2
• Y3
• Y4
• Y5
• Y6
• Y7
• Y8
• Y9
• Device Information2
• HART
• Tag
• Poll addr
• Dev id
• Universal rev
• Fld dev rev
• Chg universal rev
• Num req preams
• Physical signal code
• Burst mode
• Burst option
• Model 1
• Model 2
• Model 3
• Style No.
• Serial No.
• Mftr Date
• Extra No.
F0301-23.ai
IM 01C25T01-06EN
<3. Parameter Setting>
U
• Calibration
• Trim Who
• Trim Date
• Trim Loc
• Trim Desc
• Pres Zero trim
• P UTP
• P LTP
• P UTD
• P LTD
• Pres trim
• Clear P snsr trim
• SP UTP
• SP LTP
• SP UTD
• SP LTD
• Static Pres trim
• Clear SP snsr trim
• D/A trim
• Scaled D/A trim
• Clear D/A trim
3-11
V
• Write Protect
• Write Protect
• Enter new password
F0301-24.ai
IM 01C25T01-06EN
<3. Parameter Setting>
3-12

3.2 Basic Setup

IMPORTANT
After setting and sending data with the HART conguration tool, wait 30 seconds before turning off the transmitter. If it is turned off too soon, the settings will not be stored in the transmitter.

3.2.1 Tag and Device Information

If there are specied when ordering, the desired Tag No. and device information are set and shipped. Tag No. and device information can be checked as follows.
• Procedure to call up the display using by DD and DTM (excluding EJX HART 5 DTM based on FDT1.2)
Item Procedure
Tag [Root Menu] → Basic setup → Tag Long tag
(HART 7 only) Descriptor [Root Menu] → Basic setup → Device
Message [Root Menu] → Basic setup → Device
Date [Root Menu] → Basic setup → Device
• Procedure to call up the display by EJX HART 5 DTM based on FDT1.2
Item Procedure
Tag Easy Setup → Tag
Descriptor Conguration → Device information 1
Message Conguration → Device information 1
Date Conguration → Device information 1
When the Tag No. and device information are changed, input them based on the following limitations.
[Root Menu] → Basic setup → Long Tag
information → Descriptor
information → Message
information → Date
or Conguration → HART → Tag
→ Descriptor
→ Message
→ Date
Item Limitations
Tag Up to 8 characters or numbers*
Long tag (HART 7 only)
Descriptor Up to 16 characters or numbers*
Message Up to 32 characters or numbers*
Date mm/dd/yyyy
*1: The characters bounded by the thick line in the following
table can be used.
*2: All characters in the following table can be used.
SP ! " # $ % & ' ( ) * + , - . /
0 1 2 3 4 5 6 7 8 9 : ; < = > ?
@ A B C D E F G H I J K L M N O
P Q R S T U V W X Y Z [ \ ] ^ _
` a b c d e f g h i j k l m n o
p q r s t u v w x y z { | } ~
*: SP shows one-byte space
Up to 32 characters or numbers*
- mm: month (2 digits)
- dd: days (2 digits)
- yyyy: years (4 digits)
1
2
1
1

3.2.2 Unit

The unit parameter is set at the factory before shipment if specied at the time of order. Follow the procedure below to change the unit parameter.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
Note that the Yokogawa default setting for the standard temperature is 4°C (39.2°F). For the units of mmH2O, inH2O, and ftH2O, the pressure varies according to the standard temperature denition. Select the appropriate unit with @68degF when a standard temperature of 20°C (68°F) is required.
Available pressure units are shown below.
inH2O@68degF inHg ftH2O@68degF mmH2O@68degF mmHg psi bar
[Root Menu] → Basic setup → Unit
Easy Setup → Unit or Conguration → Analog Output → Unit
mbar g/cm kg/cm Pa kPa torr atm
2
2
MPa inH2O mmH2O ftH2O hPa
IM 01C25T01-06EN
<3. Parameter Setting>
3-13

3.2.3 Range Change

The range values are factory-set as specied by the customer. To change the range, follow the steps below.
(1) Keypad input — LRV and URV
The measurement span is determined by the upper and lower range values. In this method, the upper and lower range values can be set independently, and the span changes according to the range limit values sent to the transmitter.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ LRV Lower range value → URV Upper range value
[Root Menu] → Basic setup → Re-range → Keypad input
Easy Setup → or Conguration → Analog Output →
NOTE
The measurement span is determined by the upper and lower range values. Changing the lower range value causes the upper range value to change automatically, keeping the span constant. If a change in the lower range value causes the upper range value to exceed the measuring limit of the transmitter, an error message appears and the transmitter holds the output signal right before the error occurred. Enter the correct values within the range of the sensor limits. Note that changing the upper range value does not cause the lower range value to change. Thus, changing the upper range value also changes the span.

3.2.4 Output Mode

The mode setting for the output signal and the integral indicator can be performed independently.
The output mode for the output signal is set as specied in the order when the instrument is shipped. Follow the procedure below to change the mode.
The calibration range can be set as LRV > URV under the following conditions, reversing the 4 to 20 mA output signal. When using the integral indicator, change the user set scale values accordingly.
Conditions: LSL ≤ LRV ≤ USL LSL ≤ URV ≤ USL |URV – LRV| ≥ Min Span
LSL: Lower sensor limit of range setting
USL: Upper sensor limit of range setting
(2) Apply values — changing the ranges while
applying an actual Input
This feature allows the lower and upper range values to be setup automatically with the actual input applied. If the upper and lower range values are set, URV and LRV are changed at the same time.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu] → Basic setup → Re-range → Apply values →
Conguration → Analog Output → Apply values →
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ Xfer fnctn Select “Linear” or “Sq root”
[Root Menu] → Basic setup →
Easy Setup → or Conguration → Analog Output →

3.2.5 Damping Time Constant Setup

The damping time constant is set as specied in the order when the instrument is shipped. Follow the procedure below to change the damping time constant. The damping time constant for the amplier assembly can be set here. The damping time constant for the entire transmitter is the sum of the values for the amplier assembly and the capsule assembly.
Any number from 0.00 to 100.00 can be set for the damping time constant. Note that setting the quick response parameter ON enables you to set the time constant between 0.00 and 0.49 seconds.
• Procedure to call up the Pres Damp display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu] → Basic setup → Pres Damp
Easy Setup → Pres Damp or Conguration → Analog Output → Pres Damp
IM 01C25T01-06EN
<3. Parameter Setting>
3-14
• Procedure to call up the Quick resp display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ Off Set from 0.50 to 100.00 → On Set from 0.00 to 100.00
[Root Menu] → Detailed setup → Signal condition → Quick resp →
Conguration → Analog Output → Quick resp →

3.2.6 Output Signal Low Cut Mode Setup

Low cut mode can be used to stabilize the output signal near the zero point.
The low cut point can be set in a range from 0 to 20%, the direct ratio corresponding to the output signal of 4 to 20 mA. (Hysteresis for the cut point: ±10% of the cut point)
Either “Linear” or “Zero” can be selected as the low cut mode. Unless otherwise specied, the cut mode is set to “Linear” at the factory.
The default value of Low cut is set according to the combination of the Output mode (Xfer fnctn) and Integral indicator display mode (Disp Pres % fnctn). See below table.
Example: Low cut at 20%
(%)
50
Output
20
0
Input
For low cut in linear mode
50
(%)
(%)
50
Output
20
0
Input
For low cut in zero mode
F0302.ai
50
(%)
Figure 3.1 Low Cut Mode
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ Low cut Set from 0 to 20% of output → Low cut mode Select “Linear” or “Zero”
[Root Menu] → Basic setup →
Easy Setup → or Conguration → Analog Output →
The low cut point has hysteresis so that the output around the point is behaved as below gure.
Relationship of default value of Low cut and Low cut point
Combination of
output mode and
display mode
#
Output
mode
Display
mode
Default value of Low cut
1) Linear Linear 10% 10% / 10%
2) Sq Root Sq Root 10% 10% / 10%
3) Linear Sq Root 1%* 1% / 10%
4) Sq Root Linear 10% 10% / NA
*: It is applied for software revision 2.02 or later. For
In the case 3) above, Low cut point for the display is
(Example: Low cut value; 2%, Low cut point; 14%)
previous software version, it is set in 10%.
square root of Low cut value.
Low cut
point for
the output
signal/
display
Note that when the output modes of the output signal and the display are selected as “Sq root” and “Linear” accordingly, the low cut function is not available for the display value.
<Example> Output mode: Linear Low cut mode: Zero Low cut: 20.00%
Output Low cut point
7.2mA (20%)
4mA
Setting range: 0 to 20%
Input
2% 2%
Hysteresis fixed at 10% of the cut point
F0303.ai

3.2.7 Impulse Line Connection Orientation Setup

This function reverses the impulse line orientation.
Follow the procedure below to assign the high pressure impulse line connection to the L side of the transmitter.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ H/L Swap Select “Normal” or “Reverse”
[Root Menu] → Basic setup →
Conguration → Pressure Sensor →
IM 01C25T01-06EN
<3. Parameter Setting>
3-15

3.2.8 Static Pressure Setup

The differential pressure transmitter can display the static pressure also.
(1) Setting of the unit for static pressure
Follow the procedure below to change the static pressure unit.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ SP Unit Select the unit for static pressure
(2) Setting of the measuring range for static
pressure
Follow the procedure below to change the lower range value (LRV) and upper range value (URV).
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ SP LRV Set the lower range value (0 %) of
→ SP URV Set the upper range value (100 %)
(3) Selection of Gauge pressure and Absolute
pressure
Either the gauge pressure or absolute pressure can be selected to display on the LCD display.
[Root Menu] → Basic setup → SP setup →
Conguration → Process Input (or Static Pressure Sensor) →
(Refer to subsection 3.2.2 Unit)
[Root Menu] → Basic setup → SP setup → SP Range → Keypad input →
Conguration → Static Pressure Sensor →
static pressure
of static pressure
(4) Selection of pressure side
Either the high or low pressure side of capsule can be selected to monitor the static pressure.
High pressure side is selected when the transmitter is shipped.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ SP H/L Select Select “High” or “Low”
[Root Menu] → Basic setup → SP setup →
Conguration → Static Pressure Sensor →

3.3 Detailed Setup

3.3.1 Bi-directional Flow Measurement

(a) Bi-dir mode enables selection of 50% output at
an input of 0 mmH2O.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ Bi-dir mode Select “On” or “Off”
(b) Combining Bi-dir mode with Xfer fnctn
provides a square root output computed independently for 0% to 50% output and for 50% to 100% output.
Output mode “LINEAR”
20 mA (100% display)
[Root Menu] → Detailed setup → Signal condition →
Conguration → Analog output →
Absolute pressure is selected when the transmitter is shipped.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ A/G Select Select “Gauge” or “Absolute”
→ Atm. Pres Value 0.1013 MPa when the transmitter
[Root Menu] → Basic setup → SP setup → SP A/G Setup →
Conguration → Static Pressure Sensor →
is shipped
LRV HRV
4 mA (−100% display)
Output mode “SQUARE ROOT”
20 mA (100% display)
Low Cut
LRV HRV
4 mA (−100% display)
F0304.ai
IM 01C25T01-06EN
<3. Parameter Setting>
3-16

3.3.2 Analog Output Signal Adjustable Range

Output signal adjustable range at normal operating condition are set as shown below at the factory when the instrument is shipped, and output signal are limited by these value.
Lower limit Upper limit
Standard Option code /C1
Option code /C2 and /C3 3.8 mA 20.5 mA
Output signal range can be changed between
3.6mA and 21.6mA to match it to the equipment on
the receiving side. Lower value is set at AO lower limit and upper value is set at AO upper limit respectively. Follow the procedure below to change the upper and lower values.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ AO lower limit Set the lower value (mA) → AO upper limit Set the upper value (mA)
[Root Menu] → Detailed setup → Output condition → Analog output →
Conguration → Analog output →
Set the values as below. Lower value < Upper value
3.6 mA 21.6 mA

3.3.4 Integral Indicator Scale Setup

The following ve displays are available for integral indicators: input pressure, % of range, user set scale, input static pressure*1, and % of static pressure range*1. A cycle of up to four displays can be shown by assigning variables to the parameters at Disp select.
Available displays
Input pressure
(PRES)
% of range
(PRES %)
User set scale
(ENGR. PRES)
Indicates values of input pressure with the indication limits –99999 to
99999.
PRES 456 kPa
Indicates input pressure in 110% range depending on the set range (LRV and URV).
PRES % 45.6 %
Indicates values depending on the engineering range (Engr LRV and Engr URV) with the unit (Engr Unit).
Engr LRV 0.0 Engr URV 45.0 Engr exp ×100 Engr Unit m3/min Engr point 1
Description
and related parameters
2.5 to

3.3.3 Integral Indicator Display Mode

The mode setting for the output signal and the integral indicator can be performed independently.
The output mode for the integral indicator is set as specied in the order when the instrument is shipped. Follow the procedure below to change the mode.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ Disp Pres % fnctn Select “Linear” or “Sq root”
If the instrument is equipped with an integral indicator and the transfer function is sq root, “ ” is displayed on the integral indicator.
[Root Menu] → Detailed setup → Display condition → P disp condition →
Conguration → Local Display →
Input static pressure
% of static pressure range
*1: Available for differential pressure transmitter.
(SP)*
(SP %)*
1
1
Indicates input static pressure with the indication limits –99999 to 99999. Reference pressure is factory-set in absolute.
SP 4.000 MPa
Indicates input static pressure in –10 to 110% range depending on the set range (SP LRV and SP URV).
SP % 52.6 %
See (a.) through (d.) shown below for the setting procedures.
F0305.ai
IM 01C25T01-06EN
<3. Parameter Setting>
3-17
a. Display Selection
At Disp select, select the variable that the parameter Disp Out 1 will display on the integral indicator.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ Disp Out 1 to 4 Select desired display from ve
[Root Menu] → Detailed setup → Display condition → Disp select →
Conguration → Local Display →
kinds of display shown above.
Set Disp Out 2, Disp Out 3 and Disp Out 4 in the same way if necessary. In addition to the above item, “Not used” is also displayed as a selection item.
b. Cyclic Display
Up to four displays can be displayed cyclically in the order of the parameter number.
c. Display Resolution
User can change the position of decimal point which is shown on the integral indicator.
• Procedure to call up the display for PV %
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ Disp Pres % Reso
[Root Menu] → Detailed setup → Display condition → P disp condition →
Conguration → Local Display →
Select the decimal point position of pressure Normal: Display one digit below the decimal point High Resolution: Display two digits below the decimal point
• Procedure to call up the display for Pres and SP
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
(→ P disp condition) → Pres disp point
(→ SP disp condition) → SP disp point
[Root Menu] → Detailed setup → Display condition →
Conguration → Local Display →
Select the decimal point position of differential pressure (0, 1, 2, 3 or 4)
Select the decimal point position of static pressure (0, 1, 2, 3 or 4)
d. User Setting of Engineering Unit and Scale
Setting by DD and DTM (EJX HART 5 DTM
based on FDT1.2)
Engr disp range parameters allow the engineering
unit and scale to be displayed. At Set Engr Unit, the following engineering units can be selected from a list.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
→ Set Engr Unit Select the engineering unit → Engr LRV Lower range value → Engr URV Upper range value → Engr exp Exponents for user scale display → Engr point Decimal point position for user scale
[Root Menu] → Detailed setup → Display condition → Engr disp range
display (0, 1, 2, 3 or 4)
Select the engineering unit from the list. Available units are shown below
kPa MPa mbar bar psi psia mmH2O mmHg mmHgA mmAq mmWG Torr inH2O inHg inHgA
ftH2O
2
gf/cm
2
kgf/cm kg/cm2G kg/cm2A atm kg/h t/h m3/h m3/min l/h l/min kl/h kl/min Nl/h
Nl/min Nm3/h Nm3/min ACFH ACFM SCFH SCFM GPH GPM m mm in ft
3
kg/m
3
g/cm
At Modify Engr Unit parameter, user can set your own unit also. Up to eight alphanumeric characters, spaces or one slashe (/) can be input at Modify Engr Unit; only the rst six are displayed on the integral indicator.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
→ Modify Engr
Unit
[Root Menu] → Detailed setup → Display condition → Engr disp range →
Set your own unit
Note that following symbols are not available:
# % & < > . * : + - , ’ ( )
The integral indicator shows “-- -- -- -- -- --” when these symbols or more than two slashes are entered.
IM 01C25T01-06EN
<3. Parameter Setting>
3-18
Setting by EJX HART 5 DTM based on
FDT1.2
User can input the desired unit at Engr Unit.
• Procedure to call up the display
EJX HART 5 DTM based on FDT1.2
→ Engr Unit Set the engineering unit → Engr LRV Lower range value → Engr URV Upper range value → Engr exp Exponents for user scale display → Engr point Decimal point position for user
Conguration →Local Display →
scale display
Available characters and symbols for Engr Unit are the same as for Modify Engr Unit shown above.

3.3.5 Unit for Displayed Temperature

When the instrument is shipped, the temperature units are set to “deg C” (Centigrade). Follow the procedure below to change this setting.
When this parameter is set, it also changes the temperature unit for Snsr temp at Process variables and Amp temp at Temp sensor.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ Temp Unit Select the temperature unit
[Root Menu] → Detailed setup → Sensors → Temp sensor →
Conguration → Process Input →
(deg C, deg F, Kelvin(K))

3.3.6 Sensor Trim

The transmitter is factory characterized. Factory characterization is the process of comparing a known pressure input with the output of each transmitter sensor module over the entire pressure and temperature operating range. During the characterization process, this comparison information is stored in the transmitter EEPROM. In operation, the transmitter uses this factory-stored curve to produce a process variable output (PV), in engineering units, dependent on the pressure input.
The sensor trim procedure allows you to adjust for local conditions, changing how the transmitter calculates process variables. There are two ways to trim the sensor: a zero trim and a full sensor trim. A zero trim is a one-point adjustment typically used to compensate for mounting position effects or zero shifts caused by static pressure. A full sensor trim is a two-point process, in which two accurate end-point pressures are applied (equal to or greater than the range values), and all output is linearized between them.
(1) Zero Trim
a. Zeroing—Pres Zero trim
Pres Zero trim carries out the zero adjustment and
automatically sets the applied “0” input values to the output value of “0”, keeping the span constant. Use this setting when the LRV is known to be 0 mmH2O.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ Pres Zero trim Adjust the lower point
[Root Menu] → Diag/Service → Calibration → Pres Sensor trim →
Calibration →
b. Level Adjustment—Auto, lower Pt
This zero adjustment calibrates the transmitter output corresponding to the actual tank level. To perform this adjustment, rst use a glass gauge or the like to determine the actual tank level, then enter the correct data as shown below.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ Auto, Lower Pt Auto trim for 0% point
DPharp span: 0 to 25.00 kPa Actual level: 13.50 kPa Transmitter output: 13.83 kPa
DPharp
[Root Menu] → Diag/Service → Calibration → Pres Sensor trim → Pres trim →
Calibration → Pres trim →
25.00 kPa
Actual level
13.50 kPa
0.00 kPa
F0306.ai
c. Using External Zero-adjustment Screw
This method permits zero adjustment without the HART conguration tool. Use a slotted screwdriver to turn the zero-adjustment screw. See the hardware manual for details.
Note that the parameter of Ext SW must be “Enabled” to perform this adjustment. See section 3.3.8 for the setting procedure.
IM 01C25T01-06EN
<3. Parameter Setting>
3-19
(2) Full Sensor Trim—Auto Trim and Manual
Trim
Full sensor trim is carried out by performing Auto, Lower Pt followed by Auto, Upper Pt.
Also, you can manually perform the trimming procedure with Manual, Lower Pt and Manual, Upper Pt.
The full sensor trim is a two-point adjustment, and the lower point adjustment should always be performed before the upper point adjustment in order to maintain the pitch between the zero and 100% points within the calibration range.
In the manual method, the reference pressure should also be applied to the transmitter at both the lower and upper points. Without the reference pressure, Manual, Lower Pt and Manual, Upper Pt may not represent the correct value for each adjustment point.
a. Auto Sensor Trim
Applying reference pressure of 0% and 100% of the measurement range to the transmitter, adjust the lower and upper points automatically.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ Auto, Lower Pt Auto trim for 0% point → Auto, Upper Pt Auto trim for 100% point
[Root Menu] → Diag/Service → Calibration → Pres sensor trim → Pres trim →
Calibration → Pres trim →
b. Manual Sensor Trim
Using the example below, follow the steps to perform the full sensor trim by manually. The Pres LTD (Manual, Lower Pt) and Pres UTD (Manual, Upper Pt) represent the previously adjusted values.
Example: For the range of 1000 to 3000 mmH2O
Pres LTD (Manual, Lower Pt) = −4.0 mmH2O
Pres UTD (Manual, Upper Pt) = −3.0 mmH2O
<1> Call up the Manual, Lower Pt.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ Manual, Lower Pt Manual trim for 0% point → Manual, Upper Pt Manual trim for 100% point
[Root Menu] → Diag/Service → Calibration → Pres sensor trim → Pres trim →
Calibration → Pres trim →
<2> Suppose that a standard pressure of 1000
mmH2O is applied and the value of the “Pres for trim” is 994.0. Correct for this output error of 6 mmH2O by adding 6 mmH2O to Pres LTD (Manual, Lower Pt).
−4.0+6.0=+2.0
<3> Enter the correction value of “2” to the Pres
LTD (Manual, Lower Pt).
<4> Call up the Pres UTD (Manual, Upper Pt).
<5> Suppose that a standard pressure of 3000
mmH2O is applied and the value of the Pres for trim is 3015.0. Firstly, obtain the slope error for the span as follows;
Slope Error = ×(URV−LRV)
Applied Pressure Value−Value of Pres for Trim
= × (3000−1000) = −10
Applied Pressure Value
3000−3015
3000
Then correct for this slope error of −10 by adding −10 to Pres UTD (Manual, Upper Pt).
−3.0+(−10.0)=−13.0
<6> Enter the correction value of “−13” to the Pres
UTD (Manual, Upper Pt).
(3) Sensor Trim for Static Pressure
For the transmitter, full sensor trim of the static pressure is performed in the same way as with the differential pressure.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ Auto, Lower Pt Auto trim for 0% point → Auto, Upper Pt Auto trim for 100% point → Manual, Lower Pt Manual trim for 0% point → Manual, Upper Pt Manual trim for 100% point
[Root Menu] → Diag/Service → Calibration → SP sensor trim → Static Pres trim →
Calibration → Static Pres trim →
(4) Reset Trim Adjistment to Factory Setting
The Clear P snsr trim and Clear SP snsr trim commands can reset the trim adjustment to the initial calibrated values that were set. The amount of the adjustment performed with the external zero­adjustment screw is returned to the initial setting as well.
IM 01C25T01-06EN
<3. Parameter Setting>
3-20
• Procedure to call up the display for pressure
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu] → Diag/Service → Calibration → Pres sensor trim → Pres trim info. → Clear P snsr trim
Calibration → Clear P snsr trim
• Procedure to call up the display for static pressure
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu] → Diag/Service → Calibration → SP sensor trim → SP trim info. → Clear SP snsr trim
Calibration → Clear SP snsr trim

3.3.7 Trim Analog Output

Fine current output adjustment is carried out with
D/A trim or Scaled D/A trim.
(1) D/A Trim
D/A trim is to be carried out if the calibration digital
ammeter does not exactly read 4.000 mA and
20.000 mA with an output signal of 0% and 100%.
• Procedure to call up the D/A trim display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
(2) Scaled D/A Trim
Scaled D/A trim is to be carried out if the output is
adjusted using a voltmeter or a meter whose scale is 0 to 100%.
[Root Menu] → Diag/Service → Calibration → Analog output trim → D/A trim
Calibration → D/A trim
<Example>
Adjustment using a volt meter. (4mA → 1V, 20mA → 5V)
1) Select “Change”.
2) Enter the value read on the voltmeter when the out-
put signal is 4mA.
In this case, enter the value of the voltage across a
250Ω resistor (1V).
3) Enter the value read on the meter when the output
signal is 20mA (5V).
4) Select “Proceed”.
5) Connect the voltmeter.
6) Output the 0% output signal and read the output
value.
7) Enter the reading of the voltmeter to the conguration
tool. (The output of the transmitter changes).
8) Conrm the voltmeter reading is 1.000.
9) If the reading on the voltmeter is 1.000, select “Yes”.
If the reading is not 1.000, select “No” and repeat
steps 6 and 7 until the voltmeter reads 1.000V.
10) Output the 100% output signal and read the output
value.
11) Enter the reading of the voltmeter.
12) Conrm the voltmeter reading is 5.000.
13) If the reading of the voltmeter is 5.000, select “Yes”.
If the reading on the voltmeter is not 5.000, select
“No” and repeat steps 10 and 11 until the voltmeter
reads 5.000V.
• Procedure to call up the Scaled D/A trim display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu] → Diag/Service → Calibration → Analog output trim →Scaled D/A trim
Calibration → Scaled D/A trim

3.3.8 External Switch Mode

Follow the procedure below to enable or inhibit zero point adjustment by means of the zero-adjustment screw on the transmitter.
This is set to “Enabled” when the instrument is shipped.
To change the mode, follow the procedure below.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
Enabled Enable the external zero point
Disabled Disable the external zero point
[Root Menu] → Detailed setup → Device information → Field device info → Ext SW
Conguration → Device information1 → Ext SW
adjustment
adjustment
IM 01C25T01-06EN
<3. Parameter Setting>
3-21

3.3.9 CPU Failure Burnout Direction and Hardware Write Protect

There are two slide switches on the CPU assembly board. One sets the burnout direction at CPU failure, and the other sets a write protection function which disables parameter changes through the use of a handheld terminal or some other communication method.
CPU assembly
Burnout direction switch
BO H L
WR E D
Slide switch
Write protection switch
Burnout direction switch (BO)
Burnout Direction
Switch Position
Burnout Direction
Hardware write protection switch (WR)
Write Protection
Switch Position
Write Protection
The parameter of AO alm typ parameter displays the status of 4-20 mA DC output if a CPU failure occurs. In case of a failure, communication is disabled.
Standard specications or with option code /C3
The burnout direction switch is set to “HIGH”. If a failure occurs, the transmitter outputs a 110% or higher signal.
With option code /C1 or /C2
The burnout direction switch is set to “LOW”. If a failure occurs, a –5% or lower output is generated.
To conrm the burnout direction at the CPU failure, follow the procedure below.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
High Burnout direction is set to High Low Burnout direction is set to Low
H L H L
HIGH LOW
H L
E D
NO
(Write enabled)
[Root Menu] → Detailed setup →Output condition → Analog output → AO alm typ
Conguration → Analog output → AO alm typ
H L
E D
YES
(Write disabled)
F0307.ai

3.3.10 Software Write Protection

The transmitter congured data is saved by using a write protection function. The write protection status is set to “Yes” when 8 alphanumeric characters are entered in the New password eld and transferred to the transmitter.
When write protection is set to ”Yes,” the transmitter does not accept parameter changes. When the same eight alphanumeric string entered in the New
password eld is also entered in the Enable wrt 10min eld and transferred to the transmitter, it
will be possible to change transmitter parameters during a 10 minute period.
To change the transmitter from the write protection ”Yes” status back to write protection ”No” status, use Enable wrt 10min to rst release the write protection function and then enter eight spaces in the New password eld.
• Procedure to call up the display using by DD and DTM (excluding EJX HART 5 DTM based on FDT1.2)
DD and DTM (excluding EJX_ HART 5[1.2])
→ Write protect Display current protect mode
→ Enable wrt 10
min
→ New password Set the new password or change
• Procedure to call up the display by EJX HART 5 DTM based on FDT1.2
EJX HART 5 DTM based on FDT1.2
→ Write Protect Display current protect mode
→ Enter new
password
→ Enable write Enter the password here to release
[Root Menu] → Detailed setup → Device information → Field device info → Wrt protect menu →
(Yes: protected, No: not protected)
Release the protect function for 10 min.
the password
Write Protect →
(Yes: protected, No: not protected) Enter the password here to enable
the protect function. Enter eight spaces to disable the protect function.
the protect function for 10 min.
IM 01C25T01-06EN
<3. Parameter Setting>
3-22

3.3.11 Signal Characterizer

This function is used to compensate the output for non-linear applications. The characterized values are applied to the 4-20 mA output. For the measured pressure, a maximum of nine coordinates can be specied between 0-100%. Perform the coordinate settings while the S.C. at S.C. menu parameter is “Disabled”.
To apply the settings to the output, set the S.C. parameter to “Enabled”.
Note that the transmitter rejects the activation of the function by AL. 60 with the following transmitter’s status:
• When the specied coordinates of x and y are not incremental as the input increases.
• When the output mode of the output signal is set as “Sq root”; at the same time, the low cut mode is set to “Linear”.
Y
100%
<3> Apply the settings
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ S.C. Select “Enabled” or “Disabled”
[Root Menu] → Detailed setup → Signal condition → S.C. menu →
Conguration → Signal Characterizer Menu →

3.3.12 Alarm

The function is used to display the alarm codes when the input pressure exceeds the specied value within the calibration range. The same is available for the input static pressure and the capsule temperature on the pressure sensor. Refer to table 4.5 Alarm Message Summary for the specic alarm code to be generated.
(1) Alarm Setting
Select the process variable at Process Alert which the alarm is set, then set the alert mode for that value.
INPUT
Input pressure in % Characterized value
100%0%
X
OUTPUT
F0308.ai
Follow the steps below to perform the signal characterizer.
<1> Set the desired number of coordinates on the
line graph
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ Num of points Set the number between 0 and 9
[Root Menu] → Detailed setup → Signal condition → S.C. menu →
Conguration → Signal Characterizer Menu →
<2> Set the coordinates
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ Point setting Set the coordinates (X-axis,
[Root Menu] → Detailed setup → Signal condition → S.C. menu →
Conguration → Signal Characterizer Menu →
Y-axis)
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
Selection of the process variable for alarm
Selection of alert mode
[Root Menu] → Detailed setup → Output condition → Process Alerts →
Conguration → Process Alerts →
→ Pres Alert (DTM only) → Pres Alert mode: Pressure
→ SP Alert (DTM only) → SP Alert mode: Static pressure
→ Temp Alert (DTM only) → Temp Alert mode: Capsule temperature
Off: Disable the alert function Hi. Al Detect: High side alert
detection Lo. Al Detect: Low side alert
detection Hi/Lo. Al Detect: High and Low
side alert detection
IM 01C25T01-06EN
<3. Parameter Setting>
(2) Threshold Level Setting
Set the threshold of high and low alert value for alarm generation.
• Procedure to call up the display by DD and DTM (EJX HART 5 DTM based on FDT1.2)
DD and DTM (excluding EJX_ HART 5[1.2])
→ Hi Alert Val Set the threshold value of upper
→ Lo Alert Val Set the threshold value of lower
[Root Menu] → Detailed setup→ Output condition → Process Alerts → Pres Alert (DTM only) → Cong Pres Alerts →
side for pressure
side for pressure
NOTE
When option code /DG6 is specied, Diag can be also assigned to Status. The Hi Alert Val or Lo Alert Val for Diag is dened by the following parameters.
[Impulse Line Blockage Detection] Limit meters to detect the blockage and Condition error for ILBD operation is dened. Refer to 4.2.2.1.
[Heat Trace Monitoring]
Flg temp Hi Alert Val and Flg temp Lo Alert Val parameters are used as the upper and
DD and DTM (excluding EJX_ HART 5[1.2])
→ SP Hi Alert Val Set the threshold value of upper
→ SP Lo Alert Val Set the threshold value of lower
[Root Menu] → Detailed setup→ Output condition → Process Alerts → SP Alert (DTM only) → Cong SP Alerts →
side for static pressure
side for static pressure
lower threshold for Status output. Refer to
4.2.3.2.
3.3.13 Status Output (only for EJX series: option code AL)
The transmitter has a contact output.
EJX
Select the type of output, status output, and set the
DD and DTM (excluding EJX_ HART 5[1.2])
→ Temp Hi Alert Val Set the threshold value of upper
→ Temp Lo Alert Val Set the threshold value of lower
[Root Menu] → Detailed setup→ Output condition → Process Alerts → Temp Alert (DTM only) → Cong Temp Alerts →
side for capsule temperature
side for capsule temperature
unit, value etc.
(1) Setting of status output
This feature is used for a transistor output (open collector) of an on/off signal according to the status of high and low alarm limits, which are user-congurable values as shown in subsection
3.3.12 Alarm. The status output can be assigned
as any combination of the high or low limits of the
• Procedure to call up the display by EJX HART 5 DTM based on FDT1.2
EJX HART 5 DTM based on FDT1.2
→ Hi Alert Val Set the threshold value of upper
→ Lo Alert Val Set the threshold value of lower
→ SP Hi Alert Val Set the threshold value of upper
→ SP Lo Alert Val Set the threshold value of lower
→ Temp Hi Alert Val Set the threshold value of upper
→ Temp Lo Alert Val Set the threshold value of lower
Conguration → Process Alerts →
side for pressure
side for pressure
side for static pressure
side for static pressure
side for capsule temperature
side for capsule temperature
input pressure, input static pressure, or capsule temperature.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5 [1.2] DTM
Display Item Contents (Select a output variable
Off – Pres Differential pressure SP Static pressure Temp Temperature Pres/SP Pressure and static pressure Pres/Temp Pressure and temperature SP/Temp Static pressure and temperature Pres/SP/Temp Pressure, static pressure and
Diag Alarm Alarm for advanced diagnostics
All Alarm for pressure, static pressure,
[Root Menu] → Detailed setup →Output condition → Process Alerts → DO cong → DO Select
Conguration → Process Alerts → DO Select
from the list below)
temperature
(Refer to subsection 4.2.2.5)
temperature, and advanced diagnostics
3-23
IM 01C25T01-06EN
<3. Parameter Setting>
3-24
NOTE
No status output signal has been dened for a CPU failure or hardware error. Use a 4-20 mA signal to indicate a transmitter’s failure.
Example: Status output operation of ON
WHEN AL. DETECT
Status output for higher alert value
Output
(%)
On
Status output
On Off
Status output for lower alert value
Output
(%)
On
Status output
*: 5% of setting span for differential pressure / pressure
Figure 3.2 Status Output
On
(2) Selecting of output signal
Status output can be selected for the contact output.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5 [1.2] DTM
ON WHEN AL. DETECT
OFF WHEN AL. DETECT
[Root Menu] → Detailed setup →Output condition → Process Alerts → DO cong → DO Signal type
Conguration → Process Alerts → DO Signal type
Output is “ON” when alert is detected
Output is “OFF” when alert is detected
5%* of hysteresis
Setting
Time (t)
Setting
5%* of hysteresis
Time (t)
Off
value
value
F0309.ai
CAUTION
Whenever turning on the transmitter or detecting the short interruption, check if contact output correctly reects the alarm status and test the ON/OFF action of contact output by the parameter DO test to conrm that the contact output operates correctly.

3.3.14 Capillary Fill Fluid Density Compensation

For transmitters with diaphragm seals, this function is used to compensate the zero shift caused by the ambient temperature effect on the capillary tubes.
The following equation indicates the relationship between the calculated output value and the compensating constant K (%/°C) with the measured ambient temperature at the capsule module.
Compensated output = output + K × Temp
(1) Temperature Compensation Mode Setup
When using this function, set T.Z. Cmp mode to “On” to enable or Off to disable. To set to On, follow the procedure below.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ T.Z. Comp mode Select “On” or “Off”
Select “On” at the T.Z. Cmp mode display
(2) Zero Shift Compensation Setup
Obtain the K compensating value from the equation (a) below, and enter the value to Temp Zero.
– h×B
K= ×100.............. (a)
Span
where, B: Constant value of ll uid (See Table A.)
Span: |URV – LRV|
h: Distance from high pressure side to low
pressure side (m)
EJX118A/EJA118E: Distance from high side
of diaphragm seal to low side of diaphragm seal.
[Root Menu] → Detailed setup → Signal condition → T.Z. Comp menu →
Conguration → Pressure Sensor →
EJX438A/EJA438E: Distance from
diaphragm seal (high side) to position of transmitter (low side).
IM 01C25T01-06EN
<3. Parameter Setting>
3-25
● EJX118A/EJA118E
L
h
(+)
Transmitter
● EJX438A/EJA438E
Transmitter
Transmitter
Note: When the transmitter is positioned lower than the diaphragm seal part, the value of “h” must have a negative sign (–).
Example: Enter K value obtained from the equation (a).
A value haivng up to 3 decimal places may be specied.
When h=+3 m, Fill uid code A, span=15 kPa, K=−(+3)×0.00745÷15×100=−0.149
0
H
L
L
(+)
(–)
h
0
H
h
F0310.ai

3.3.15 Test Output, Simulation, and Squawk

NOTE
Fixed current output, DO Test, and Device Variable Simulation Function continue for a given holding time, then is released automatically. Even if the HART conguration tool power supply is turned off or the communication cable is disconnected, the test output will continue for that time. The holding time can be selected from 10 min*, 30 min, 60 min, 3 hour, 6 hour or 12 hour.
*: Default value.
• Procedure to call up the display
DD [Root Menu] → Diag/Service →
DTM (excluding EJX_HART 5 [1.2])
EJX_HART 5[1.2] DTM
(1) Fixed current output
Test Auto Release Time [Root Menu] → Diag/Service →
Test → Test Auto Release Time
Diag and Service → Service → Test Auto Release Time
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ Temp Zero Set the compensation value
[Root Menu] → Detailed setup → Signal condition → T.Z. Comp menu →
Conguration → Pressure Sensor →
Input “-0.149” to Temp Zero prameter.
Note 1: The function is performed using a built-in temperature
Note 2: When the span changes, reenter the newly obtained
Table A. Constant value [B] of ll uid
sensor in the transmitter body. The temperature deviation between the transmitter body and capillaries should be minimized to achieve optimal performance of the function.
value of K to Temp Zero.
Fill uid
code
mmH2O 0.76 0.87 1.45 0.75 kgf/cm20.000076 0.000087 0.000145 0.000075 kPa 0.00745 0.00853 0.01422 0.00736 mBar 0.07453 0.08532 0.14220 0.07355 atm 0.000074 0.000084 0.000140 0.000073 inH2O 0.02992 0.03425 0.05709 0.02953 psi 0.00108 0.00124 0.00206 0.00167
Constant value [B]
mmHg 0.05592 0.06401 0.10669 0.05518
A, C,
1, 2, 4
B D E
This feature can be used to output a xed current for loop checks. The available range for test output depend on the settings for the AO lower limit and AO upper limit parameters, whose limit is from
3.6mA (-2.5%) to 21.6mA (110%).
Refer to the subsection 3.3.2 about the setting of AO lower limit and AO upper limit. While this function works, “TEST” is displayed on the integral indicator.
Setting by DD and DTM (EJX HART 5 DTM
based on FDT1.2)
Call up the test output parameter (Loop test) and select the output signal.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
Display Item Contents 4mA Output a 4mA DC signal 20mA Output a 20mA DC signal Other Set a desired output signal value End Exit
[Root Menu] → Diag/Service → Test (DTM only) → Loop test →
Note 3: Select the unit of constant value of [B] from the actual
unit used for the transmitter in operation.
IM 01C25T01-06EN
<3. Parameter Setting>
3-26
Setting by EJX HART 5 DTM based on
FDT1.2
Call up the test output parameter (Loop test) and select either manual test or auto test, and set the current value.
• Procedure to call up the display
EJX HART 5 DTM based on FDT1.2
Display Item Contents
Manual Test Set the current value or % value at
Auto Test Set the interval and rate of change
(2) DO Test (only for EJX series)
Diag and Service → Service → Loop test →
Test output value, then click the Start button.
of current output at Auto Test Setting, then click the Start button.
EJX
This function performs the contact output test. (option code: /AL)
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
Display Item Contents Off Contact output: OFF On Contact output: ON Exit Output test is canceled
[Root Menu] → Detailed setup →Output condition → Process Alerts → DO cong → DO Test →
Diag and Service → Service → DO test →
(3) Device Variable Simulation Function
(Effective only when setting to HART 7)
HART 7
Using the simulation function, the output signal can be conrmed by setting any value and status to the selected device variable. Call up the parameter and follow the message shown. After completing the step 5, the simulation starts. Integral indicator shows output value and alarm (AL.91) alternately.
• Procedure of device variable simulation
Step 1 Call up the
parameter
2 Selection of
Device Variable
3 Setting of Value Input the simulate value
4 Setting of Data
quality
5 Setting of Limit
status
[Root Menu] → Diag/ Service → Test (DTM)/Test device (DD) → Simulate
Select one parameter from the list below Off PV SV TV Percent Range Loop Current
Select one parameter from the list below Bad Poor accuracy Manual / Fixed Good
Select one parameter from the list below Not limited Low limited High limited Constant
NOTE
• All the simulations for pressure, static pressure, and capsule temperature are reected to the output. Accordingly, the loop current, LCD display, and communication output are directly corresponded to the simulate value. The alarm output is also available according to the simulate value.
• Damping is applicable for pressure, static pressure, and capsule temperature simulation.
(4) Squawk (Effective only when setting to
HART 7)
This feature can be used to identify the communicating transmitter by remotely causing LCD to display the particular pattern as shown in the Figure 3.3. “SQUAWK” continues for approximately 15 seconds, then is released automatically. Enter the larger number to “Change number of squawks to make” in order to prolong the duration of squawk indication.
HART 7
IM 01C25T01-06EN
<3. Parameter Setting>
S P
3-27
• Procedure to call up the Squawk display
[Root Menu] → Diag/Service → Test (DTM)/Test device
(DD) → Squawk
P
Figure 3.3 LCD display for Squawk
T F
F0311.ai

3.3.16 Burst Mode

3.3.16.1 In the case of using HART 5
HART 5
When the Burst mode is enabled, the transmitter continuously sends the stored data. The data is sent approximately three times per second as a digital signal when the transmitter is set in burst mode. When data is being sent in burst mode, other operations can be performed with the HART conguration tool.
(1) Selection of the transmission data.
Call up the Burst option parameter and select the data which is transferred.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
Display Item Contents
PV Process variable assigned to PV
%range/current Output in % and mA Process vars/crnt Output in mA and process variables
[Root Menu] → Detailed setup → Output condition → HART output → Burst option →
Conguration → HART → Burst option →
(Either of pressure, static pressure)
assigned to PV, SV and TV. (Output in mA, pressure, static pressure and capsule temperature)
(2) Shift to the Burst mode.
To enable the Burst mode, select “On” at the Burst mode parameter. To release the Burst mode, call up the Burst mode display and set it to “Off”.
This parameter is set to “Off” when the instrument is shipped.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
Display Item Contents Off Stop the burst mode On Start the burst mode
[Root Menu] → Detailed setup → Output condition → HART output → Burst mode
Conguration → HART → Burst mode
3.3.16.2 In the case of using HART 7
HART 7
When the Burst mode is enabled, the transmitter continuously sends up to three data listed in Table
3.1. Refer to the subsection 3.3.16.2.1 Burst Message for details.
When the Burst mode is set to “Wired HART Enabled”, transmitter continuously sends alarm signal also. Refer to subsection 3.3.16.2.2 Event Notication for detail.
When changing the setting of Burst mode, set “Off” to the Burst mode. Default setting is “Off”.
3.3.16.2.1 Burst Message and Burst Mode
(1) Burst message
The transmitter can transmit three burst messages at the maximum. The parameters for Burst Message are as follows.
• Burst Command
• Update Period and Max Update Period
• Burst Msg Trigger Mode
IM 01C25T01-06EN
<3. Parameter Setting>
Table 3.1 Burst parameters
Command parameter Burst Command
PV (Pressure • Differential Pressure)
% range/current (Percent of range, Loop current)
Process vars/current (Loop current, Pressure
• Differential Pressure
• Static Pressure • Temperature)
Process vars/% range/ current Mapping by user
Self diagnosis information Cmd48:Read
*1: Output the data with time and status.
Cmd1:PV Continuous --- ---
Cmd2:% range/current Continuous --- ---
Cmd3:Dyn vars/current Continuous --- ---
Cmd9:Device vars w/status Continuous --- ---
Additional Device Status
Burst Msg Trigger
Mode
Window PV Depend on the Rising Falling On-change
Window % range % Rising Falling On-change
Window PV Depend on the Rising Falling On-change
Window Top of Burst Rising Falling On-change Continuous --- --­On-change All status ---
Burst Trigger
Source
assigned variable to PV
assigned variable to PV
Depends on mapping
Device Variables
3-28
Burst Trigger Units
IM 01C25T01-06EN
<3. Parameter Setting>
(2) Burst mode setting procedure
• Procedure to call up the display
DD and DTM [Root Menu] → Detailed setup →
Output condition →HART output → Burst Condition → Burst Message 1,2 or 3 → Burst Command
3-29
Burst Command
Command?
Cmd1, Cmd2, Cmd3, Cmd48
Update Period
Max Update Period
Burst Msg Trigger Mode
Burst Msg
Trigger Mode?
Burst
Send to transmitter
Send to transmitter
Send to transmitter
Window Rising Falling On-change
Cmd9
Burst Variable Code (DD) Device Variable Code (DTM)
a. Burst Command
Burst Variable Code
b.
c.
Update period and Max Update Period by “Set Burst Period”
d. Burst Msg Trigger Mode
by “Set Burst Trigger”
Continuous
Burst mode
Burst Trigger Level
Send to transmitter
e. Burst Mode
Send to transmitter
F0312.ai
IM 01C25T01-06EN
<3. Parameter Setting>
3-30
a. Burst Command
Select the transmission data at Burst Command parameter.
Burst Command Command parameter
Cmd1: PV PV (Pressure • Differential
Pressure)
Cmd2: % range/current % range/current (Percent of
range, Loop current)
Cmd3: Dyn vars/current Process vars/current
(Loop current, Pressure • Differential Pressure • Static Pressure • Temperature)
Cmd9: Device vars w/ status
Cmd48: Read Additional Device Status
Process vars/% range/current Mapping by user
Self diagnosis information
b. Burst Variable Code/Device Variable Code
This parameter need to be set when Burst Command is Cmd9:Device vars w/status (up to
eight items).
• Procedure to call up the display
DD and DTM [Root Menu] → Detailed setup
→Output condition →HART output → Burst condition → Burst Message 1,2 or 3 → Burst Device Variables → Burst Variable Code (DD)/Device Variable Code (DTM) →
Display Item Contents PV Select the pressure SV Select the static pressure TV Select the capsule temperature % rnge Select the % output Loop current Select the output current Not Used
c. Update period and Max Update Period
Set to Update Period and Max Update Period. When the period that is earlier than the operation period of each process value was set, it is set automatically to become bigger than an operation period of the transmitter. For Update Period, set the value that is smaller than Max Update Period.
• Procedure to call up the display
DD and DTM [Root Menu] → Detailed setup
→Output condition →HART output → Burst condition → Burst Message 1,2 or 3 → Set Burst Period
→ Update Period
/ Max Update Period
0.5 s 1 s 2 s 4 s 8 s 16 s 32 s 1 min 5 min 10 min 15 min 30 min 45 min 60 min
d. Burst Msg Trigger Mode
Set the Burst Msg Trigger Mode from the parameters shown below. When Burst Msg Trigger Mode is Window, Rising or Falling, set the Burst Trigger Level.
• Procedure to call up the display
DD and DTM [Root Menu] → Detailed setup →
Output condition →HART output → Burst condition → Burst Message 1,2 or 3 → Set Burst Trigger →
Display Item Contents
Continuous Burst Message is transmitted
continuously.
Window In “Window” mode, the Trigger Value
must be a positive number and is the symmetric window around the last communicated value.
Rising In “Rising” mode, the Burst Message
must be published when the source value exceeds the threshold established by the trigger value.
Falling In “Falling” mode, the Burst Message
must be published when the source value fall below the threshold established by the trigger value.
On-change In “On-change” mode, the Burst
Message must be published when the source value on change established by the trigger value.
IM 01C25T01-06EN
<3. Parameter Setting>
3-31
e. Burst Mode
When the Burst mode is set to “Wired HART Enabled”, the transmitter starts to send the data.
• Procedure to call up the display
DD and DTM [Root Menu] → Detailed setup
→Output condition →HART output → Burst condition → Burst Message 1,2 or 3 → Burst mode → Wired HART Enabled
3.3.16.2.2 Event Notication
When a setting change and a change of the Self­diagnostics occur, device detect it as an event and can transmit an alarm signal continuously. Up to four events that occurred can be stored. When using this function, set to Burst mode as “Wired HART Enabled”.
(1) Set Event Notication
• Procedure to call up the display
DD and DTM [Root Menu] → Detailed setup
→Output condition →HART output → Burst Condition →
Event Notication → → Event Mask Set the status to detect → Set Event Notication Timing
→ Event
Notication Retry Time
→ Max Update
Time
→ Event
Debounce Interval
→ Event
Notication Control
Set the retry time when the event
occur.
Set the retry time when the event
does not occur.
The setting of the minimum event
duration
Stop the event monitor: Off
Shift to the monitor state: Enable
event notication on token-
passing data link layer
Therefore, the conguration changes to the device are always detected as an event regardless of the setting of the Device Status.
b) Event Notication Retry Time/ Max Update
Time/ Event Debounce Interval
Set to Event Notication Retry Time, Max Update Time and Event Debounce Interval. For Event Notication Retry Time, set the value that is smaller than Max Update Time.
Event Notication
Retry Time
/Max Update Time
--- Off
0.5 s 0.5 s 1 s 1 s 2 s 2 s 4 s 4 s 8 s 8 s 16 s 16 s 32 s 32 s 1 min 1 min 5 min 5 min 10 min 10 min 15 min 15 min 30 min 30 min 45 min 45 min 60 min 60 min
Event Debounce Interval
c) Event Notication Control
Select “Enable event notication on token-passing data link layer” in the Event Notication Control parameter to shift to the monitor state:
(2) Acknowledge Event Notication
The transmission of the event message stops when event is approved.
a) Event Mask
Set the status to detect in the Event Mask parameter.
Device Status Mask Status group 1 Mask to 10 Mask Ext dev status Mask Device Diagnostic Status 0 Mask Device Diagnostic Status 1 Mask AO saturated Mask AO xed Mask
When changing the conguration of the device, Conguration Changed (0x40) Flag (refer to Table
4.7) of Device Status is set, and Cfg chng count (refer to subsection 4.1.3 (5)) is also incremented. Conguration changed ag detection can be masked by the Device Status Mask, but it is impossible to mask the Cfg chng count.
• Procedure to call up the display
DD and DTM [Root Menu] → Detailed
setup →Output condition → HART output → Burst condition → Event Notication → Knowledge →
→ Acknowledge
Event Notication
Acquisition of the event number and approval.
a) Get Event Number
Conrm the latest event number. Execute Acknowledge Event Notication method.
1) Enter Event Number is set to “0”.
2) OK.
3) Set “Trans 0: Read Event Noticaiton” to Select Transaction.
4) OK.
5) Conrm Event Number.
IM 01C25T01-06EN
<3. Parameter Setting>
3-32
b) Acknowledge Event Notication
Execute Acknowledge Event Notication method.
1) Set to Enter Event Number is in conrmed Event Number a)5.
2) OK.
3) Set “Trans 1: Send Acknowledge” to Select Transaction.
4) OK.
5) Conrm Event Status is 0x00.
(3) Event Notication Record
• Procedure to call up the display
DD and DTM [Root Menu] → Detailed setup →
Output condition →HART output → Burst condition → Event Notication → Knowledge →
→ Acknowledge Event Notication
Acquisition of the event number and approval.
a) Get Event Number
Conrm the latest event number. Execute Acknowledge Event Notication method.
1) Enter Event Number is set to “0”.
2) OK.
3) Set “Trans 0: Read Event Noticaiton” to Select Transaction.
4) OK.
5) Conrm Event Number.
b) Conrmation record of Event Notication
Conrm four events checked in a). Execute Acknowledge Event Notication method.
1) Enter the event number to Enter Event Number which is conrmed in a)5.
2) OK.
3) Set “Trans 0: Read Event Noticaiton” to Select Transaction.
4) OK.
5) Knowledge menu displays events record.
Ex.) When the conrmed event number is 123.
Event Number Explanation
123 The latest event 122 An event before the once. 121 An event before the twice. 120 An event before three times.

3.3.17 Multidrop Mode

3.3.17.1 Setting on HART 5
HART 5
“Multidropping” transmitters refer to the connection of several transmitters to a single communication transmission line. Up to 15 transmitters can be connected when set in the multidrop mode. To activate multidrop communication, the transmitter address must be changed to a number from 1 to
15. This change deactivates the 4 to 20 mA analog output, sending it to 4 mA. The alarm current is also disabled.
Setting of Multidrop Mode
(1) Polling address
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ Poll addr Enter the number from 1 to 15
[Root Menu] → Detailed setup → Output condition → HART output →
Conguration → HART →
(2) Enabling the Multidrop Mode of
Conguration Tool
About the procedure to call up the Polling display, please refer to the User’s Manual of each conguration tool.
NOTE
When the same polling address is set for two or more transmitters in multidrop mode, communication with these transmitters is disabled.
(3) Communication when set in multidrop
mode.
• The HART conguration tool searches for a transmitter that is set in multidrop mode when it is turned on. When the HART conguration tool is connected to the transmitter, the polling address and the tag will be displayed.
• Select the desired transmitter. After that, normal communication to the selected transmitter is possible. However, the communication speed will be slow.
To release multidrop mode, call up the Poll addr display and set the address to “0”.
IM 01C25T01-06EN
<3. Parameter Setting>
3-33
3.3.17.2 Setting on HART 7
HART 7
“Multidropping” transmitters refer to the connection of several transmitters to a single communication transmission line. Up to 63 transmitters can be connected when set in the multidrop mode. To activate multidrop communication, the transmitter address must be changed to a number from 1 to 63. If it sets to multidrop mode, in order to transmit all the data in digital one, it is necessary to change a setup of the analog output signal of 4 to 20 mA.
Setting of Multidrop Mode
(1) Polling address
• Procedure to call up the display
DD and DTM [Root Menu] → Detailed setup
→Output condition →HART output →
→ Poll addr Enter the number from 1 to 63
NOTE
When the same polling address is set for two or more transmitters in multidrop mode, communication with these transmitters is disabled.
(2) Analog Output Signal Setting
Set Disabled to Loop current mode and x an analog output signal to 4mADC. It becomes impossible in this case, to also use a burnout output.
However, in the case of the application which receives and operates an analog output signal, an analog output signal can be used for one loop. In this case, set Enabled to Loop current mode.
• Procedure to call up the display
DD and DTM [Root Menu] → Detailed setup
→Output condition →Analog output
→ Loop current mode → Enabled Loop current mode is enabled. Disabled Loop current mode is disabled.
(3) Enabling the Multidrop Mode of
Conguration Tool
(4) Communication when set in multidrop
mode.
• The HART conguration tool searches for a transmitter that is set in multidrop mode when it is turned on. When the HART conguration tool is connected to the transmitter, the polling address and the tag will be displayed.
• Select the desired transmitter. After that, normal communication to the selected transmitter is possible. However, the communication speed will be slow.
To release multidrop mode, call up the Poll addr display and set the address to “0”.
Return Loop current mode to Enabled.

3.3.18 Switching HART Protocol Revision

When the output signal code is “-J”, HART protocol revision of the transmitter can be selectable from 5 or 7. The HART protocol revision is set and shipped as specied in the order. To change the HART protocol revision after shipment, follow the procedure shown below.
IMPORTANT
When changing the protocol revision, conrm the items below.
• Protocol revision supported by HART conguration tool must be the same or higher than new protocol revision of the transmitter. (Refer to Table 2.1)
• Conrm that the DD or DTM which is suitable to new protocol revision of transmitter is installed in the conguration tool. (Refer to Section 2.3 or 2.4)
1) Call up the parameter for protocol revision change
• Procedure to call up the Chg universal rev display.
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu] → Detailed setup → Device information → Field device info → Revision #’s → Chg universal rev
Conguration → HART → Chg universal rev
About the procedure to call up the Polling display, please refer to the User’s Manual of each conguration tool.
IM 01C25T01-06EN
<3. Parameter Setting>
3-34
2) Activate the “Chg universal rev” method
IMPORTANT
The message is displayed to separate the transmitter from the automatic control loop. Conrm that the transmitter is separated.
3) Input the new revision number An input column for new protocol revision number is displayed. Input the new HART protocol revision number of “5” for HART 5 or “7” for HART 7.
4) Applying the new protocol revision a. Close the conguration tool
After completion of Chg universal rev method, close the HART conguration tool.
NOTE
When using a FieldMate, close the main display of FieldMate.
b. Conrm the new HART protocol revision
number Call up the Universal rev parameter, and conrm that the new HART revision number is displayed.
• Procedure to call up the Universal rev. parameter.
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
5 HART protocol revision: 5 7 HART protocol revision: 7
[Root Menu] → Detailed setup → Device information → Field device info → Revision #’s → Universal rev →
Conguration → HART → Universal rev. →
b. Restart the transmitter
Turn off the power to the transmitter, and turn it on.
IMPORTANT
New protocol revision is applied only after having performed restart of the transmitter.
NOTE
A new HART revision number is displayed on the integral indicator for three (3) seconds after restart the transmitter. (Refer to section 2.1)
5) Conrming the new protocol revision a. Restart the HART conguration tool
NOTE
When execute the other parameter conrmation or setting change, execute after restart the conguration tool.
IM 01C25T01-06EN
<4. Diagnostics>

4. Diagnostics

4-1

4.1 Self-Diagnostics

4.1.1 Identify Problems by Using HART
Conguration Tool
The HART conguration tool can be used to run self-diagnostics on a transmitter and check for incorrect data settings.
(1) DD and DTM (excluding EJX HART 5 DTM
based on FDT1.2)
The Self test and Status commands are available for self-diagnostics. When Self test is run, the integral indicator shows an error code and alarm message if the transmitter detects any illegal parameter settings or functional faults. See Table
4.5 Alarm Message Summary for probable cause
and countermeasures.
• Procedure to call up the Self test display
[Root Menu] → Diag/Service → Test (DTM)/Test device (DD) → Self test
If no error is detected, “Self test OK” is displayed on the conguration tool. If the specic diagnostic item is known for the check, you can directly call up the item by using the Status command. The status is categorized from 1 to 9 for HART 5, and from 1 to 10 for HART 7. See Table 4.5 to determine the status group. Show an example below to conrm the status of Status group 1.
When an improper operation is performed, the error message is displayed. See Table 4.6 HART Conguration Tool Error Message.
(2) EJX HART 5 DTM based on FDT1.2
The Device Status commands are used for self- diagnostics. When Device Status is run, the integral indicator shows an error code and alarm message if the transmitter detects any illegal parameter settings or functional faults. See Table
4.5 Alarm Message Summary for probable cause and countermeasures.
• Procedure to call up the Device Status display
Device Status
If no error is detected, “Status: Normal” is displayed on the conguration tool. If the specic diagnostic item is known for the check, you can directly call up the item by using the Diagnostic List in the Device Status display. The Diagnostic List is categorized to Device Status, Hardware Failure, Transducer Status, Diag Status, and Conguration.
See Table 4.5 Alarm Message Summary. If no error is detected, color symbol which shows Normal State is displayed on top of the error message. If color symbol which shows Error State is displayed, there is an error and a countermeasure for that error is necessary.
Procedure to call up the Status display
[Root Menu] → Diag/Service → Test device (DD only)
→ Status → Status group 1
If no error is detected, “Off” is displayed on the conguration tool. If there is an error, “On” is displayed on the conguration tool, and a countermeasure for that error is necessary.
Example of display: Illegal P LRV On Illegal P URV Off Illegal P SPAN Off P SPAN trim err Off P ZERO trim err Off
The HART conguration tool diagnoses at each communication.
The HART conguration tool diagnoses at each communication. When an improper operation is performed, the error message is displayed. See Table 4.6 HART Conguration Tool Error Message.
IM 01C25T01-06EN
<4. Diagnostics>
4-2

4.1.2 Checking with Integral Indicator

NOTE
If an error is detected by running self-diagnostics, an error number is displayed on the integral indicator. If there is more than one error, the error number changes at three-second intervals. See table 4.3.1 regarding the alarm codes.
F0401.ai
Figure 4.1 Integral Indicator
4.1.3 Status information available for
HART 7
Status added to HART 7 is explained below.
(1) Device Status
Device Status indicates the current operating status of the device. (Refer to Table 4.7) Table 4.10 indicates the relationship between alarm and Device Status.
HART 7
(3) Data quality and Limit status
The transmitter can handle PV (Pres), SV (SP), TV (Snsr temp), % rnge (Percent Range), and Loop current. Each variable contains data quality and limit status for providing useful status about the data value. The data quality is normally “Good”. However, in the case of a sensor failure or out of measurement range, it turns to “Bad” or “Poor Accuracy”. The limit status indicates whether the data value is limited (i.e., not responding to the process). When the limit status is “Constant”, the value will not be changed. For detail, refer to Table 4.9 and 4.10.
• Procedure to call up the display
[Dynamic Variables]
DD and DTM [Root Menu] → Process variables
→ Device variables and Status →
→ PV (Pres) Data Quality
→ PV (Pres) Limit Status
It is the same about the SV (SP) and TV (Temp), % rnge (Percent Range), and Loop current
Good, Poor Accuracy, Manual/ Fixed, or Bad is displayed.
Constant, Low Limit, High Limit, or Not Limited is displayed.
(4) Time Stamp
Time Stamp displays the date and the time information which the transmitter maintains from the time of the power on. It is used as the additional information of the process value and the event.
• Procedure to call up the display
DD and DTM [Root Menu] → Diag/Service → Test
device (DD only) → Status → Device status
(2) Extended Device Status
Ext dev status contains commonly used device information. (Refer to Table 4.8) Table 4.10 indicates the relationship between alarm and Extended Device Status.
• Procedure to call up the display
DD and DTM [Root Menu] → Diag/Service → Test
device (DD only) → Status → Ext dev status
• Procedure to call up the display
DD and DTM [Root Menu] → Diag/Service →
Test device (DD only) → Status → Time Stamp
→ Current Date It shows the number of operating
days.
→ Current Time It shows the running time.
NOTE
Time Stamp is reset when powering on.
IM 01C25T01-06EN
<4. Diagnostics>
4-3
(5) Conguration Change Counter
The Conguration Change Counter is incremented once for every user action that changes the device’s conguration or calibration. This value is never reset or written and maintained even if power is removed from the device.
• Procedure to call up the display
DD and DTM [Root Menu] → Diag/Service →
Test device (DD only) → Status →
→ Cfg chng count
(6) Reset Conguration Changed Flag
Conguration Changed Flag can be reset by this method.
The conguration change times are counted. The counted value cannot be reset.
NOTE
Refer to Conguration Changed (0x40) in the Table 4.7.
• Procedure to call up the display
DD and DTM [Root Menu] → Diag/Service → Test
device (DD only) → Status → Reset Cfg Chng ag

4.2.2 Impulse Line Blockage Detection (ILBD)

ILBD is carried out by using statistical analysis based on the measured values of process uctuations that exist in a uid. An alarm on the transmitter LCD display or an analog alert is generated if blockage reaches a certain level. The transmitter provides the following results as blockage detection.
(1) A Blocking and B Blocking
These are blockage detections based on the uctuation value change of differential pressure/pressure. With a differential pressure transmitter, each result indicates that both or single side is plugged.
(2) L Side Blocking
It is a low-pressure side blockage detection based on the change of BlkF or low-pressure- side uctuation value.
(3) H Side Blocking
It is a high-pressure side blockage detection based on the change of BlkF or high-pressure- side uctuation value.
*: BlkF indicates blockage degree characterized
by a comparison of the high- and low-pressure­side uctuation values. For the details, refer to Figure 4.2.2.
4.2 Advanced Diagnostics (Only for EJX series)

4.2.1 Multi-sensing Process Monitoring

Multi-sensing process monitoring function (option code: /DG6) provides the advanced diagnostics to detect the abnormal conditions in process environment such as an impulse line etc. by using the EJX multisensing technology and its unique algorithm. There are following two functions.
Impulse Line Blockage Detection (ILBD)
The uctuation change of differential pressure and static pressure is monitored by a silicone resonant sensor and detects a potential blockage condition. The differential pressure transmitter gives also a result of which pressure-side was plugged.
Heat Trace Monitoring
The two temperature sensors built in the transmitter calculate the ange temperature, the change of which enables to detect the heat trace breakage or the abnormal temperature due to the failure.
EJX
IMPORTANT
• The pressure uctuation amplitude in uids must be sufciently large for blockages to be detected.
• If the pressure uctuation amplitude is too low for a reference value to be obtained, blockages detection operation cannot be performed with an alarm that the reference value is invalid.
• The pressure uctuation amplitude may decrease due to other causes unrelated with a blockage according to process condition. In above case, a false alarm of an impulse line blockage may be generated. Before taking action in response to a blockage alarm, consider the plant operating conditions.
Notes for Pressure or Level
Measurement
With pressure or level measurement, the pressure uctuation amplitude may reduce especially for the following cases.
IM 01C25T01-06EN
<4. Diagnostics>
Pressure Measurement
• Operational pressure is near outside of diagnostic range.
• Even though pressure is constant, the ow decreases than that under normal condition.
• A source of pressure uctuation (pump, compressor, blower, etc.) is shut down. As a result, the pressure uctuation amplitude decreases.
Level Measurement
• A transmitter is used to measure tank level and the ow of uid into or out of the tank comes to a stop.
• The agitator in the tank is shut down.
• A source of pressure variation (a compressor, etc.) that controls the internal pressure of a sealed (closed) tank is shut down.
Before taking action in response to a blockage alarm, consider the plant operating conditions.
4-4
IM 01C25T01-06EN
<4. Diagnostics>
Functional block diagram
The gure below shows the functional block diagram of ILBD.
4-5
EJX
Sensor
Sensor signals
Process Value
calculation
Blockage degree
Execution of
ILBD
Blockage alarm
Diag Output
Option
DO Config
Add result of blockage detection to status
Alarm
Masking
Blockage alarm
Result of blockage detection
Result of blockage detection
Blockage alarm
Pres, Pres % Engr Disp SP, SP % Snsr temp Amp temp
Output 4-20mA AO
Contact Output Digital Output
Ratio fDP Ratio fSPl Ratio fSPh BlkF, fDP fSPl, fSPh Diag Applicable
Diag Error
Response Code (Device Status) Status group 8,9
Display on LCD
Figure 4.2 Functional Block Diagram of ILBD
The following outputs are given for the ILBD results.
Table 4.1 List of Outputs for ILBD
#
OUTPUT
Parameter name
Parameters based on the fluctuation value and blockage degree.
[ Diag DPComp: Non-Compensation ]
:
Ratio fDP
[ Diag DPComp: Compensation ]:
fSPl
Ratio fSPl
(1)
Ratio fSPh
BlkF
fDP
fSPI
fSPh
Diag Applicable*
Response Code
(2)
Device Status
(3)
Status group 8, 9
(4)
Diag Error
(5)
Display on LCD
(6)
Analog Output Digital Output
(7)
*1: Available only for DD and DTM (excluding EJX HART 5 DTM based on FDT1.2). For EJX HART 5 DTM based on FDT1.2, the color of icon on the Diag Error display changes with the status.
1
Ratio fSPl
Ratio fSPh
Blockage degree characterized in comparison of high-pressure side and low-pressure side pressure fluctuation value.
Average value of the sum of squares of differential pressure fluctuations. Average value of the sum of squares of low-pressure side static pressure fluctuation. Average value of the sum of squares of high-pressure side static pressure fluctuation. After the reference value is obtained, the applicable blockage defection and the status of
abnormal fluctuation are displayed on this parameter. When an impulse line blockage is detected, “More Status Avairable” is generated in
Response Code Device Status. When an impulse line blockage is detected, the result of the blockage detection
(alarm status) is indicated. When an impulse line blockage is detected, the results of the blockage detection
(alarm status) is indicated. When impulse line blockage is detected, an alarm status is displayed on LCD.
When impulse line blockage is detected, an alarm status is output on 4 to 20mA. When impulse line blockage is detected, an alarm status is output on Status output.
=
Ref fSPl
=
Ref fSPh
fSPh
Remarks
Ratio fDP
Ratio fDP
=
=
fDP
Ref fDP
fDP
Ref fDP
Ref DPAvg
×
-------(6)
-------(7)
-------(1)
*1
-------(4)
-------(2)
-------(3)
-------(5)
F0402.ai
DPAvg
F0403.ai
IM 01C25T01-06EN
<4. Diagnostics>
4.2.2.1 Blockage Detection
Limit parameter
When the parameter based on pressure uctuation exceeds the preset value, EJX diagnoses an impulse line as blockage and gives an alarm. The threshold values are set to Limit parameter shown in below table.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
Table 4.2 Limit Parameter
# Parameter Threshold value
[1] Lim fDPmax Threshold to detect “A
[2] Lim fDPmin Threshold to detect “B
[3] Lim fSPlmax Threshold to detect “Large
[4] Lim fSPlmin Threshold to detect “L Side
[5] Lim fSPhmax Threshold to detect “Large
[6] Lim fSPhmin Threshold to detect “H Side
[7] Lim BlkFmax Threshold to detect “H Side
[8] Lim BlkFmin Threshold to detect “L Side
[9] Lim DPAvgmax Threshold to detect “ILDB over
[10] Lim DPAvgmin Threshold to detect “ILDB over
[Root Menu] → Diag/Service → Diag Parameters → ILBD Parameters → Conguration → Diag Lim →
Diag and Service → Advanced Diag Congurations → Impulse Line Blockage Detection → Threshold → Sensitivity →
Blocking” by using Ratio fDP
Blocking” by using Ratio fDP
Fluct L” by using Ratio fSPl
Blocking” by using Ratio fSPl
Fluct H” by using Ratio fSPh
Blocking” by using Ratio fSPh
Blocking” by using BlkF
Blocking” by using BlkF
range” by using DPAvg and to detect “Invalid Ref xx” by using
Ref DPAvg
range” by using DPAvg and to detect “Invalid Ref xx” by using
Ref DPAvg
4-6
Table 4.3 shows the default values at the factory setting.
NOTE
• When ILBD is performed for the rst time, use the default value. If the pressure uctuation amplitude is low or a false alarm is often generated after ILBD is performed, change the values of Limit parameters according to the procedure described in subsection 4.2.2.10. Tuning
IM 01C25T01-06EN
<4. Diagnostics>
Table 4.3 Default Values of Limit Parameter
Flange
Differential pressure
transmitter
#
[1] Lim fDPmax 3 3 10000 10000 10000 10000 10000 [2] Lim fDPmin 0.3 0.3 0.3 0.3 0.3 0.3 0.3 [3] Lim fSPlmax 5 10000 10000 10000 10000 10000 10000 [4] Lim fSPlmin 0.5 0 0 0 0 0 0 [5] Lim fSPhmax 5 10000 10000 10000 10000 10000 10000 [6] Lim fSPhmin 0.5 0 0 0 0 0 0 [7] Lim BlkFmax 0.6 10 10 10 10 10 10 [8] Lim BlkFmin -0.6 -10 -10 -10 -10 -10 -10
[9]
[10]
Parameter
Lim DPAvgmax
Note 2
Lim DPAvgmin
Note 2
EJX110A EJX115A
EJX130A
1 1 1 1 1 1 1
0.05 0.2 -1 -1 0.05 0.05 0.05
EJX120A EJX210A EJX118A
mounted
differential
pressure
transmitter
Diaphragm
sealed differential
pressure/
pressure
transmitter
Note 1
EJX438A
Absolute pressure
transmitter
EJX310A EJX430A
Gauge
pressure
transmitter
EJX440A
Gauge/
Absol ute
pressure
transmitter
EJX510A EJX530A EJX610A EJX630A
4-7
Note 1: The default values are set for level measurement. If EJX118A is applied to ow measurement, enter the same value to Limit
Note 2: It indicates the threshold value for “ILBD over range” (refer to 4.2.2.5).
A/B Blocking Detection
“A Blocking” and “B Blocking” indicates the result estimated from blockage degree based on the difference of the high- and low-pressure-side uctuation values. Ratio fDP, SQRT (fDP / Ref fDP) is used to detect A/B blocking. Ref fDP is the average value of the sum of squares of differential pressure uctuations under normal condition.
As the value of Ratio fDP exceeds the value of Lim fDPmax, EJX gives basically an alarm of “A Blocking”. On the other hand, if this value is below the value of Lim fDPmin, EJX gives an alarm of “B
parameter [1] to [10] as those of EJX110A.
H/L Blocking Detection
EJX differential pressure transmitter enables to detect both-, a high-, or low-pressure-side blockage. The blockage degree characterized by a comparison of high-pressure side and low­pressure-side uctuation values, BlkF, is used to detect it. The value changes within a range of –1 to +1. As BlkF approaches +1, the high-pressure- side blockage progresses. On the other hand, if it approaches –1, the low-pressure-side blockage progresses.
1
1
Blocking.
As a high- or low-pressure-side blockage progresses, fDP increases. Therefore, “A Blocking” with a differential pressure transmitter indicates that a single-side impulse line is plugged for a differential pressure transmitter. As the both-side blockages progress simultaneously, fDP decreases. Therefore, “B Blocking” with a differential pressure transmitter indicates that both-side impulse lines are plugged.
Threshold
0
Blockage Progress
BlkF
Blockage detection for high-pressure side
Figure 4.3 Relation between Blockage Progress
and BlkF
Blockage Progress
0
BlkF
Threshold
-1-1
Blockage detection for low-pressure side
F0404.ai
NOTE
A single-side impulse line blockage may generate “B blocking” under the condition where the uctuation amplitude is much different between high- and low-pressure sides.
The each threshold value to detect the high- or low­pressure-side blockage is set to Lim BlkFmax or Lim BlkFmin.
IM 01C25T01-06EN
<4. Diagnostics>
4-8
L Side Blocking Detection
BlkF is preferentially used to "L Side Blocking"
detection. If BlkF cannot be used, Ratio fSPl, SQRT (fSPl / Ref fSPl) is used to "L Side Blocking" detection. Ref fSPl is the average value of the sum of squares of low-pressure-side static pressure uctuations under normal condition.
As the value of Ratio fSPl is below the value of Lim fSPlmin, EJX gives an alarm of "L Side Blocking".
On the other hand, if this value exceeds the value of Lim fSPlmax, EJX gives an alarm of “Large Fluct L”.
H Side Blocking Detection
BlkF is preferentially used to "H Side Blocking"
detection. If BlkF cannot be used, Ratio fSPh, SQRT (fSPh / Ref fSPh) is used to "H Side Blocking" detection. Ref fSPh is the average value of the sum of squares of high-pressure-side static pressure uctuations under normal condition.
As the value of Ratio fSPh is below the value of Lim fSPhmin, EJX gives an alarm of "H Side Blocking".
4.2.2.2 Combination of Reference Result and Blockage Detection
Diag Applicable
The transmitter can detect four modes of impulse line blockage: both-sides, high-pressure side, low­pressure side, and/or single-side and abnormal uctuation when all the reference values are properly measured. However, the detectable alarm mode combination is limited when some of the reference values are invalid. Available Blockage Detection are shown in the below gure.
NOTE
Ref fDP must be larger than the specied level shown in Table 4.4 (refer to subsection
4.2.2.6). No blockage can be detected when Ref fDP is not large enough.
• The plausibility of blockage detection needs to be conrmed by blockage simulation test. The simulation test can be performed by the appropriate manifold operation (refer to subsection 4.2.2.8).
On the other hand, if this value exceeds the value of Lim fSPhmax, EJX gives an alarm of “Large Fluct H”.
Large Fluctuation Detection
When a pump or compressor starts, the large uctuation is generated as process condition changes rapidly. This phenomenon affects process uctuation measurement; so correct blockage detection is not performed.
If “Large Fluct L” or “Large Fluct H” is detected, consider whether a blockage result is correct.
The threshold values to detect large uctuation are set to Lim fSPlmax and Lim fSPhmax.
Since these values are enough to detect large uctuation, it is not almost necessary to change them.
IM 01C25T01-06EN
<4. Diagnostics>
[Differential pressure measurement]
Fluctuation Parameters
Ref fDP: OK
Ref fSPI: OK
Ref fSPh: OK
Ref BlkF: OK
Ref fDP: OK
Ref fSPI: OK
Ref fSPh: OK
Ref BlkF: NG
• Test for low-pressure side
• Test for high-pressure side
• Test for both-pressure sides
• Test for low-pressure side
• Test for high-pressure side
• Test for both-pressure sides
Simulation Test
Available Blockage Detection
• B Blocking detection (by using Ratio fDP)
• L Side Blocking detection (by using Ratio fSPI)
• H Side Blocking detection (by using Ratio fSPh)
• H/L Side Blocking detection (by using BlkF)
• A/B Blocking detection (by using Ratio fDP)
• L Side Blocking detection (by using Ratio fSPl)
• H Side Blocking detection (by using Ratio fSPh)
4-9
Ref fDP: OK
Ref fSPI: NG
Ref fSPh: OK
Ref BlkF: NG
Ref fDP: OK
Ref fSPI: NG
Ref fSPh: NG
Ref BlkF: NG
[Gauge/absolute pressure and level measurement]
Fluctuation Parameters Simulation Test
Ref fDP: OK
• Test for high-pressure side
• Test for both-pressure sides
• Test for high-pressure side
4.2.2.3 Operation Parameters
Diag Mode
Diag Mode gives the directive for the ILBD
operation. There are following three modes.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu] → Diag/Service → Diag Parameters → ILBD Parameters → Conguration → Set Diag Mode →
Diag and Service → Advanced Diag Congurations → Impulse Line Blockage Detection → Diag Mode →
• A Blocking detection (by using Ratio fDP)
• H Side Blocking detection (by using Ratio fSPh)
• B Blocking detection (by using Ratio fDP)
Available Blockage Detection
• B Blocking detection
(by using Ratio fDP)
F0405.ai
Diag Mode
Mode Function
Stop The blockage detection operation is
stopped.
Calculation The blockage detection operation is
performed. Alarms are generated along with the result.
Reference Reference values for the blockage
detection are obtained and updated to the latest. After sampling reference values, this mode changes to "Calculation".
When the blockage detection operation is performed, set “Calculation” to Diag Mode. “Stop” must be set when you change a threshold value or set an alarm. “Reference” is set in order to obtain the reference uctuation values under the normal conguration.
IM 01C25T01-06EN
<4. Diagnostics>
AAA
A
If Diag Supp Count is set to three times, an
NOTE
When setting ILBD parameters in the transmitter via “Online Parameter” of the EJX HART 5 DTM based on FDT1.2 menu, Diag Mode automatically changes to 0 (Stop). After the setting, Diag Mode automatically returns to the original value.
alarm is not generated at part ‘A’ in Figure 4.4. Because the rst and second values only exceeded consecutively the threshold.
When the value exceeds consecutively the threshold value three times, an alarm is generated (see part ‘B’ in Figure 4.4).
Diag Supp Count (Number of times: 3)
An alarm is generated.
4-10
NOTE
When setting ILBD parameters in the transmitter via “Download to device” of the EJX HART 5 DTM based on FDT1.2 menu, Diag Mode automatically changes to 0 (Stop).
Diag Period
The values such as Ratio fDP and BlkF are averaged based on several hundreds of pressure uctuation values in constant time. Diag Period denes the sampling time is. The default value at the shipment is set to 180 seconds.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
For the information on how to change the sampling period, refer to subsection 4.2.2.10.
Diag Supp Count
When the value as Ratio fDP or BlkF exceeds the threshold value for several times in a row, it is estimated that the impulse line is plugged. Diag Supp Count denes the number of times to estimate blockage detection.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu] → Diag/Service → Diag Parameters → ILBD Parameters → Conguration → Diag Period →
Diag and Service → Advanced Diag Congurations → Impulse Line Blockage Detection → Diag Period →
[Root Menu] → Diag/Service → Diag Parameters → ILBD Parameters → Conguration → Diag Supp Count →
Diag and Service → Advanced Diag Congurations → Impulse Line Blockage Detection → Threshold → Diag Suppress Count →
B BB
Upper Threshold (Ex.Lim fDPmax)
Diag Period
Time
Diag Period
Diag Supp Count (Number of times: 3)
Figure 4.4 Relationship of Diag Supp Count and
Alarm
Lower Threshold (Ex.Lim fDPmin)
B
An alarm is generated.
Time
F0406.ai
The number of detection to give an alarm is set for each blockage detection function. The default value at the shipment is set to three times.
If uctuating around the threshold value, an alarm may be often generated. In this case, change the threshold value (Limit parameter) or the sampling time (Diag Period) to enhance the accuracy of the blockage detection. Refer to subsection 4.2.2.10.
IM 01C25T01-06EN
<4. Diagnostics>
F0407.ai
NG
1, 2
7
3
4
5, 6
10
1-1) Alert Setting
• Enable an alert to be generated by Diag Out Option parameter.
1-2) Alarm Masking
• Select the alarm status to display on LCD or to give an alert by Diag Option parameter.
2-1) Check Stability of pressure
• Check the stability of Pres value.
2-2) Check Fluctuation Values
• Check whether the fluctuation values
are available for ILBD.
3-1) Obtain Reference Values
• Obtain a reference fluctuation value of differential pressure/pressure and static pressure under normal condition.
3-2)
Check Detection
Capability
• Simulate the blockage detection operation with a three-valve
manifold or stop valve.
Tuning
• Change the threshold value by Limit parameter.
• Change the sampling time by Diag Period parameter.
Reset Reference Values
• Reset a reference fluctuation value of differential pressure/pressure according to process condition.
4) Perform ILBD algorithm
Refer to subsection 4.2.2.11
Refer to subsection 4.2.2.10
Process condition is changed by a comparison of the condition when the reference values were obtained.
Blockage Detection Alarm is generated.
Refer to subsection 4.2.2.9
Spurious alarm detection.
Refer to subsection 4.2.2.8
Refer to subsection 4.2.2.7
Refer to subsection 4.2.2.6
Refer to subsection 4.2.2.6
Refer to subsection 4.2.2.5
Refer to subsection 4.2.2.5
1) Initial Setting
2) Condition Check
3) Start up
Items on
Check sheet
OK
4-11
4.2.2.4 Operating Procedure
The basic ow of the ILBD operation is as follows.
1) Initial setting
2) Condition check
3) Start up
4) Perform the ILBD algorithm.
If an alarm is often generated or the process condition changed in the ILBD operation, do tuning to change the alarm setting, or to reset the reference values.
Fill out the information to the checklist, at the process shown in below gure. (Refer to the Appendix 1. ILBD Check List)
Figure 4.5 Flow Chart of ILBD Operation
IM 01C25T01-06EN
<4. Diagnostics>
4-12
4.2.2.5 Alarm and Alert Setting
The abnormal results as the blockage detection and high/low ange temperature (heat trace monitoring) are given through an analog alert or the LCD display of alarm status. Before performing the ILBD operation, it is necessary to set the alarm and alert according to the following procedure.
Storage of Abnormal results
(Diag Error)
Alarm Masking
(Diag Option)
Outside Diagnosis Range/
Invalid Ref xx
Masking
Alarm on
Analog Output
Figure 4.6 Alarm and Alert Setting
Alarm on
Status Output
Field Device More Status Available
Device Status
Additional Device Status
(Status group 8 and 9)
Alarm Display
on LCD
F0408.ai
DD
Bit
(HART 5/HART 7)
DTM (HART 7)
Not used Not used
0
Not used Not used
1
A Blocking A Blocking
2
Large Fluct L
3
Large Fluct H
4
L Side Blocking Low Side Blocking
5
H Side Blocking
6
B Blocking B Blocking
7
Invalid Ref F Invalid Ref BlkF
8
Invalid Ref SPH Invalid Ref fSPh
9
Invalid Ref SPL Invalid Ref fSPl
10
Invalid Ref DP Invalid Ref fDP
11
12 ILBD over range
FT low alarm
13
FT high alarm
14
15 Not used Not used
DTM (HART 5) Category
Large Fluctuation of Low Side
Large Fluctuation of High Side
High Side Blocking
Outside Diagnosis Range
Flg Temp Low Alarm
Flg Temp High Alarm
ILBD
Heat trace monitoring
Alarm Status
When the algorithm of ILBD and Heat trace monitoring detect the abnormality, the result is stored in Diag Error. The alarm status based on the detected abnormality is displayed to Diag Error.
(Displayed to Impulse Line Blockage Detection and Heat Trace for DTM(HART 5))
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu] → Diag/Service → Diag Parameters → Diag Error →
Diag and Service → Advanced Diag Alerts → Diag Error
Note: FT indicates the ange temperature.
ILBD over range (Outside Diagnosis
Range)
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
1) Lim DPAvgmax Lim DPAvgmax is the upper limit of the diagnostic capability range. The limit value can be changed when Diag Mode is “Stop”.
DPAvg indicates the ratio of the average of differential pressure to the EJX maximum span regarded as 1. When DPAvg exceeds this limit, “ILBD over range” is generated so that the blockage detection becomes impossible.
2) Lim DPAvgmin Lim DPAvgmin is the lower limit of the diagnostic capability range. The limit value can be changed when Diag Mode is “Stop”.
[Root Menu] → Diag/Service → Diag Parameters → ILBD Parameters → Conguration → Diag Lim →
Diag and Service → Advanced Diag Congurations → Impulse Line Blockage Detection → Threshold →
When DPAvg is below this limit, “ILBD over range” is generated so that the blockage detection becomes impossible.
IM 01C25T01-06EN
<4. Diagnostics>
4-13
<Example> When the level range that can be measured by the transmitter with 100 kPa span is –80 to 80 kPa, the limits are set as follows.
Lim DPAvgmax: 0.80
Lim DPAvgmax: –0.80
1.000
0.80
0.000
ILBD over range
Detectable
range
DPAvg
-0.80
-1.000
ILBD over range
F0409.ai
Invalid Ref F, SPH, SPL, or DP
This alarm indicates that the reference value under normal condition is invalid. If Ref F is invalid, the blockage detection excluding BlkF is carried out. If blockage detection function based on BlkF is required, obtain the reference value again.
Also when Ref DPAvg is below Lim DPAvgmin or exceeds Lim DPAvgmax, all reference value becomes invalid so that “Invalid Ref DP”, “Invalid Ref SPL”, “Invalid Ref SPH”, and “Invalid Ref F” are generated.
Alarm Masking
Diag Option
DD
(HART 5/HART 7)
DTM (HART 7)
A Blocking A Blocking Large Fluct L Large Fluctuation of Low Side Large Fluct H Large Fluctuation of High Side L Side Blocking Low Side Blocking H Side Blocking High Side Blocking B Blocking B Blocking Invalid Ref DP Invalid Ref fDP
DTM (HART 5)
To Link the alarm to an analog alert and LCD display, follow the procedure below.
1) Set “Stop” to Diag Mode.
2) Check each checkbox of the alarm, which is selectable from bit 2 to 14.
Note: Set to “Calculation” after setting the parameter.
Alert Setting
Diag Out Option
When an alert regarding the impulse line blockage or high/low ange temperature is generated, the output value of 4-20 mA analog signal can be changed.
Mode Function
Off
Burnout
Fall back
Keeping PV measurement. The alert is not reected to 4-20 mA analog signal.
The analog signal is shifted to the value of AO upper limit or AO lower limit when an alert is generated. The shifted direction follows Burnout switch setting.
The analog signal is hold to the specic value, Diag Fixed Out Val, when an alert is generated.
The alarms linked to an analog alert and LCD display are selected by Diag Option.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5 [1.2] DTM
[Root Menu] → Diag/Service → Diag Parameters → Diag Option →
Diag and Service → Advanced Diag Congurations → Impulse Line Blockage Detection → Diag Option →
The bit of Diag Option is corresponding to that of Diag Error. The following alarms are set at the factory setting, which is corresponding to hexadecimal 0x08FC.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5 [1.2] DTM
[Root Menu] → Diag/Service → Diag Parameters → Diag Output → Diag Out Option →
Diag and Service → Advanced Diag Congurations → Diag Out Option →
Diag Fixed Out Val
This parameter is used when “Fall back” is selected to Diag Output Option.
When an alert is generated, the 4-20 mA analog signal is held on the value specied by this parameter.
The value can be entered within 3.6 to 21.6 mA.
IM 01C25T01-06EN
<4. Diagnostics>
4-14
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu] → Diag/Service → Diag Parameters → Diag Output → Diag Fixed Out Val →
Diag and Service → Advanced Diag Congurations → Diag Fixed Out Val →
Status Output for Advanced diagnostic
The output of the abnormal results are applicable for a transistor output (open collector) of an on/off signal according to the status of high and low alarm limits, which are values set to Limit parameters as shown in subsection 4.2.2.1. About the Flg Temp Hi Alert Val, or Flg Temp Lo Alert Val for Heat trace monitoring, refer to subsection 4.2.3.2.
DO Select
If the advanced diagnostic function is installed, the following modes can be also assigned to the status output in addition to Pres, SP and Temp.
Mode Function
Diag Alarm
All
The status regarding advanced diagnostic masked by Diag Option is output.
All status of Press, SP, Temp and advanced diagnostic are output.
4.2.2.6 Condition Check
After the transmitter was installed, it is necessary to conrm if Pres is stable under the normal operating condition or if uctuation amplitude under the normal operating condition is large enough to detect the blockage.
Stability of Pressure Value
1) Observe the value change of Pres under the normal operating condition for 10 minutes.
2) Conrm the value change is less than 10%.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu] → Detailed setup → Sensors → Pressure Sensor → Pres
Conguration → Process Input → Pres
If the value change is more than 10%, the error inuences pressure uctuation value so that the blockage detection becomes impossible. Consider the plant operating conditions.
Fluctuation Value
NOTE
Alarm Display on LCD
If the ILBD algorithm detects the abnormality, the content of the detected result is displayed with “AL.88” or “AL.89” on the LCD. “AL.88” indicates that condition is not applicable for the abnormality detection and “AL.89” indicates the abnormality is detected.
F0410.ai
Figure 4.7 Display Example of H Side Blocking
The alarm display on LCD regarding the advanced diagnostic is described in Table 4.5.
NOTE
The blockage detection may not be carried out correctly when pressure uctuation amplitude especially with the pressure and level measurement, is small.
Conrm that each value of fDP, fSPl, fSPh, and BlkF is more than the value specied in the below table.
• Procedure to call up the fDP, fSPl, fSPh display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu] → Diag/Service → Diag Parameters → ILBD parameters → Status → Fluct Variables → fDP/fSPl/fSPh
Diag and Service → Advanced Diag Variables → fDP/fSPl/fSPh
• Procedure to call up the BlkF display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu] → Diag/Service → Diag Parameters → ILBD parameters → Status → Diag Variables → BlkF
Diag and Service → Advanced Diag Variables → BlkF
The alarms of “Invalid Ref xx” and “ILBD over range” do not link to the 4-20 mA analog signal and Status output.
IM 01C25T01-06EN
<4. Diagnostics>
4-15
Table 4.4 Requirements to apply ILBD
Condition
fDP 7×10 fSPI 1×10 fSPh 1×10 BlkF -0.5 to 0.5
-10
or more
-10
or more
-10
or more
fDP is not enough.
No blockage can be detected if fDP is not larger than the specied value.
Only fDP is enough.
“A Blocking” or “B Blocking” can be detected if fSPl and fSPh are not larger than specied values.
fDP and fSPl are enough.
“H Side Blocking” and “Large Fluct H” can not be detected if fSPh is not larger than specied value.
fDP and fSPh are enough.
“L Side Blocking” and “Large Fluct L” can not be detected if fSPl is not larger than specied value.
Start of Sampling
The sampling of reference value is carried out for 180 seconds, which is the default value set to Diag Period.
1) Conrm that the sampling period (Diag Period) is set to 180 seconds.
2) Set “Reference” to Diag Mode. The sampling starts soon after the setting.
IMPORTANT
• For the each parameter, the one value is given. If Reference is set to Diag Mode again, the value is updated and overwritten.
• If the power supply is shut down during the sampling, Diag Mode becomes “Stop”. Set “Reference” to Diag Mode in order to carry out the sampling again.
End of Sampling
After about 180 seconds, the sampling automatically nishes. The “Reference” setting of Diag Mode moves automatically to “Calculation”.
Conrm that the setting of Diag Mode moves to “Calculation”.
fDP, fSPl and fSPh are enough.
All alarm modes can be detected even if BlkF is not within the specied values.
4.2.2.7 Obtain Reference Values
The pressure uctuation values are reduced when the impulse line is plugged. Therefore, the reference value is required to determine the degree of reduction.
IMPORTANT
• If the impulse line is about to be plugged at the time when a reference value is obtained, blockages cannot be detected accurately. The impulse lines on both the high-pressure and low-pressure sides need to be cleaned before a reference value is obtained.
• All air bubbles need to be adequately purged before a reference value is obtained.
• Reference values must be obtained under operating condition.
Reference Values
Conrm the latest values are obtained into the following parameters.
• Ref fDP
• Ref fSPl
• Ref fSPh
• Ref BlkF
• Ref DPAvg
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu] → Diag/Service → Diag Parameters → ILBD parameters → Status → Diag Reference → Ref fDP/Ref fSPl/Ref fSPh/Ref BlkF/Ref DPAvg
Diag and Service → Advanced Diag Conguration → Impulse Line Blockage Detection → Ref fDP/Ref fSPl/Ref fSPh/Ref BlkF/Ref DPAvg
IM 01C25T01-06EN
<4. Diagnostics>
4-16
Invalid Ref F, SPH, SPL, or DP
When the enough reference uctuation value is not obtained, an alarm of invalid reference value for each parameter is generated and also the ILBD operation is not carried out.
Conrm the alarm of Invalid Ref F, SPH, SPL, or DP is not displayed in Diag Error.
If an alarm of Invalid Ref F, SPH, SPL, or DP is generated, consider the process condition or obtain the reference uctuation values again.
NOTE
Even if an alarm of Invalid Ref F, SPH, SPL, or DP is generated, “Calculation” in Diag Mode is
kept.
4.2.2.8 Capability Test of Blockage Detection Operation
Before performing the ILBD operation, check the capability of the blockage detection operation. The simulation test is performed by closing motion of a three-valve manifold or stop valve. When simulated blockage occurs, conrm that an alarm is generated.
NOTE
The uctuation amplitude of atmospheric pressure is nearly zero with pressure or level measurement. In such case, simulate the blockage detection by closing the valve where the uctuation existed.
Simulation of Low-pressure Side
Blockage
1) Close the low-pressure-side valve.
2) Conrm the value of Pres is stable. If not, open the valve a little.
3) Set “Calculation” to Diag Mode so as to start blockage detection operation.
4) Check that an alarm of “L Side Blocking” is generated after the time that consists of Diag Period and Diag Supp Count passed.
5) Check also the operation of the analog alert if an analog alert is set.
6) Open the valve completely and check that there are no alarms.
Simulation of Both-pressure Side
Blockage
1) Close the both-pressure-side valves.
2) Conrm the value of Pres is stable. If not, open the valve a little.
3) Set “Calculation” to Diag Mode so as to start blockage detection operation.
4) Check that an alarm of “B Blocking” is generated in the Diag Error after the time that consists of Diag Period and Diag Supp Count passed.
5) Check also the operation of the analog alert if an analog alert is set.
6) Open the valve completely and check that there are no alarms.
4.2.2.9 Start ILBD Operation
If process condition and capability to detect a blockage are conrmed, you can start the ILBD operation according to the following procedure.
Simulation of High-pressure Side
Blockage
1) Close the high-pressure-side valve.
2) Conrm the value of Pres is stable. If not, open the valve a little.
3) Set “Calculation” to Diag Mode so as to start blockage detection operation.
4) Check that an alarm of “H Side Blocking” is generated after the time that consists of Diag Period and Diag Supp Count passed.
5) Check also the operation of the analog alert if an analog alert is set.
6) Open the valve completely and check that there are no alarms.
1) Check the value of sampling period (Diag Period).
2) Check the number of times that detect the blockage consecutively in order to give an alarm (Diag Supp Count). The default value at the shipment is set to 3 times.
3) Set “Calculation” to Diag Mode.
If the reference value has not yet been
obtained, set “Reference” to Diag Mode. After obtained the reference values, the ILBD starts automatically. At the same time, Diag Mode changes automatically from “Reference” to “Calculation”.
IM 01C25T01-06EN
<4. Diagnostics>
4-17
4.2.2.10 Tuning
When the pressure uctuation amplitude in uids is not sufciently large or an alarm is often generated according to the process condition, tune up by changing the threshold for the blockage detection (Limit parameters) or the sampling period (Diag Period) to enhance the accuracy of the blockage detection The ILBD operation must be stopped to tune up. Set “Stop” to Diag Mode.
Threshold Value
The gure below shows the image of tuning effect with a monochrome bar.
(a) The tuning image of the threshold values for
(1) Ratio fDP: Sqrt (fDP/Ref fDP), (2) Ratio fSPl: Sqrt (fSPl/Ref fSPl), (3) Ratio fSPh: Sqrt (fSPh/Ref fSPh)
0 1 3
Threshold (lower side) Threshold (upper side)
(1) Lim fDPmin (2) Lim fSPlmin (3) Lim fSPhmin
(b) The tuning image of the threshold values for
(4) Sqrt (BlkF/Ref BlkF)
0-1 1
Threshold (lower side) Threshold (upper side)
(4) Lim BlkFmin (4) Lim BlkFmax
Figure 4.8 Tuning Image of Threshold Value
(1) Lim fDPmax (2) Lim fSPlmax (3) Lim fSPhmax
F0411-1.ai
F0411-2.ai
(1) Setting by DD and DTM (excluding EJX
HART 5 DTM based on FDT1.2)
• Procedure to call up the threshold related display
DD and DTM (excluding EJX_HART 5[1.2])
[Root Menu] → Diag/Service → Diag Parameters → ILBD parameters → Conguration → Diag Lim →
The default values at the factory setting are the values of Lim fDPmax to Lim BlkFmin shown in Table 4.3.
Change the threshold value to solve your problem according to the above image.
1) Set “Stop” to Set Diag Mode.
2) Change the unsuitable value of Diag Lim parameters corresponding to the each blockage detection.
Note: Set to “Calculation” after setting the parameter.
Limit parameter
# Parameter Threshold value
[1] Lim fDPmax
[2] Lim fDPmin
[3] Lim fSPlmax
[4] Lim fSPlmin
[5] Lim fSPhmax
[6] Lim fSPhmin
[7] Lim BlkFmax
[8] Lim BlkFmin
Threshold to detect “A Blocking” by using Ratio fDP
Threshold to detect “B Blocking” by using Ratio fDP
Threshold to detect “Large Fluct L” by using Ratio fSPl
Threshold to detect “L Side Blocking” by using Ratio fSPl
Threshold to detect “Large Fluct H” by using Ratio fSPh
Threshold to detect “H Side Blocking” by using Ratio fSPh
Threshold to detect “H Side Blocking” by using BlkF
Threshold to detect “L Side Blocking” by using BlkF
Move the threshold toward the white.
• It becomes increasingly likely to give a false alarm due to the disturbance from environment change.
• If ow/differential pressure is below Lim DPAvgmin or exceeds Lim DPAvgmax, pressure uctuation is likely too small or too large to detect the blockage.
Move the threshold toward the black.
• It enables to be insusceptible to disturbance such as environment change and to detect the blockage easier.
• It becomes giving an alarm of the blockage after the blockage has been progressed.
(2) Setting by EJX HART 5 DTM based on
FDT1.2
Combination of threshold depend on the sensitivity of blockage detection can be selected from High, Medium, or Low in the Sensitivity parameter.
• Procedure to call up the display
EJX HART 5 DTM based on FDT1.2
Diag and Service → Advanced Diag Conguration → Impulse Line Blockage Detection → Threshold → sensitivity
When select “Custom” in the Sensitivity parameter, you can set each threshold individually. Set the Diag Mode to “Stop” before changing the threshold.
IM 01C25T01-06EN
<4. Diagnostics>
4-18
Combination of threshold for sensitivity parameter
High Medium Low
Lim fDPmax 1.50 Lim fDPmin 0.40 Lim fSPlmax 5.00 Lim fSPlmin 0.50 Lim fSPhmax 5.00 Lim fSPhmin 0.50 Lim BlkFmax 0.60 Lim BlkFmin -0.60
3.00 3.00
0.30 0.20
5.00 5.00
0.50 0.30
5.00 5.00
0.50 0.30
0.60 0.80
-0.60 -0.80
Sampling Period
If uctuating around the threshold value, an alarm maybe often generated. When the above phenomenon happens, the sampling time (Diag Period) can be changed so as to enhance the accuracy of the blockage detection.
The longer the sampling time, better the expected accuracy.
(1) Set “Stop” to Diag Mode.
(2) Enter the value to Diag Period within the
range of 20 to 65535 (seconds).
Note: Set to “Calculation” after setting the parameter.
Also, the accuracy can be improved by increasing the number of Diag Supp Count.
ILBD Range Setting
If ow/differential pressure is less than the default threshold value of Lim DPAvgmin, pressure uctuation is not large enough to detect the blockage. To prevent the fault blockage detection, the threshold should be changed to larger value.
(1) Set “Stop” to Diag Mode.
(2) Enter the value to Lim DPAvgmin or Lim
DPAvgmax.
Note Set to “Calculation” after setting the parameter.
Ratio fDP Compensation
When the ow change is too large or small, an alarm maybe often generated. When the above case happens, the Ratio fDP can be compensated so as to enhance the accuracy of the blockage detection.
Diag DPComp
When “Compensation” is selected in Diag DPComp, Ratio fDP is compensated by following
formula and used as treatable monitoring value, CRatio fDP.
CRatio fDPCRatio fDP
=
fDP
Ref fDP
Ref DPAvg
DPAvg
On the other hand, if the compensation is not necessary, “Non-compensation” is selected in Diag DPComp and Ratio fDP is used as NRatio fDP.
NRatio fDP
=
fDP
Ref fDP
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu] → Diag/Service → Diag Parameters → ILBD parameters → Status → Diag Vriables → CRatio fDP/NRatio fDP
Diag and Service → Advanced Diag Variables → CRatio fDP/NRatio fDP
4.2.2.11 Reset of Reference Value
When there are large ow change or the change of uid conditions, obtain the reference value again. If ow change by a comparison of the reference value is ±25% or more, obtain the reference value again.
• Procedure to call up the threshold display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu] → Diag/Service → Diag Parameters → ILBD parameters → Conguration → Diag Lim →
Diag and Service → Advanced Diag Conguration → Impulse Line Blockage Detection → Threshold →
IM 01C25T01-06EN
<4. Diagnostics>
4-19
4.2.2.12 ILBD Parameter List
# Parameter name Default value Explanation
1 Diag Error 0x0000 The results detected by ILBD or Heat trace monitoring are stored into this
parameter. Also the condition abnormality in the diagnostic process is stored as an error.
2 Diag Option 0x08FC The masking in this parameter enable to display each error message and the
status to the output signal or LCD. The error assigned to each bit is corresponding to that of Diag Error. Writable only when Diag Mode is "Stop".
3 Diag Out Option Off Output mode of 4-20mA when an advanced diagnostic alarm is generated.
There are following three output modes; Off, Burnout, or Fall back.
4 Diag Fixed Out
Val
5 DO Select Off The variables for status output are specied to this parameter. When the
6 Diag Mode Stop The operation mode of ILBD is set.
7 Diag Period 180 (s) The data acquisition period for ILBD is set within 20 to 65535 (s). If the process
8 Diag Supp Count 3 Detection count to generate an alarm. When the statistical value as Ratio fDP
9 Diag Description Memo eld. 32 alphanumerics
10 fDP Average value of the sum of squares of differential pressure uctuation. 11 fDP Status Status of fDP 12 fSPl Average value of the sum of squares of low-pressure-side static pressure
13 fSPl Status Status of fSPl 14 fSPh Average value of the sum of squares of high-pressure-side static pressure
15 fSPh Status Status of fSPh 16 BlkF Blockage degree characterized in comparison of high- and low-pressure side
17 BlkF Status Status of BlkF 18 DPAvg Ratio of the average of differential pressure/pressure to the maximum span of an
19 DPAvg Status Status of DPAvg 20 Ratio fDP CRatio fDP or NRatio fDP is used by Diag Comp setting.
21 Ratio fDP Status Status of Ratio fDP 22 Ratio fSPl SQRT (fSPl/Ref fSPl).
23 Ratio fSPl Status Status of Ratio fSPl 24 Ratio fSPh SQRT (fSPh/Ref fSPh).
25 Ratio fSPh
Status 26 Ref fDP Value of fDP obtained under normal condition. 27 Ref fDP Status Status of fDP obtained under normal condition.
21.6 mA Parameter for "Fall back" function in the Diag Out option. The output value of 4-20 mA analog signal is specied when an alarm is generated. The value can be entered within 3.6 to 21.6 mA.
advanced diagnostic function (option code /DG6) is installed, the parameters monitoring in diagnostic process can be also assigned to the status output.
Stop: The blockage detection is stopped. Calculate: The blockage detection is carried out. The alarms are generated along with the detected result. Reference: The reference values are obtained and the update values are
overwritten.
After setting, this mode moves automatically to "Calculation".
uctuation values are unsteady, this value is changed to the longer to enhance the accuracy of the blockage detection. Writable only when Diag Mode is "Stop".
and BlkF exceeds consecutively the threshold by number of times preset to this parameter, it is estimated that the impulse line is plugged.
uctuation. For gauge/absolute pressure transmitter, 0 is set.
uctuation. For gauge/absolute pressure transmitter, 0 is set.
pressure uctuation value.
EJX transmitter.
fDP decreases and this parameter is used to determine whether one or both sides are plugged.
fSPl decreases and this parameter is used to determine whether low-pressure­side is plugged.
fSPh decreases and this parameter is used to determine whether high-pressure­side is plugged.
Status of Ratio fSPh
IM 01C25T01-06EN
<4. Diagnostics>
# Parameter name Default value Explanation
28 Ref fSPl Value of fSPl obtained under normal condition. 29 Ref fSPl Status Status of fSPl obtained under normal condition. 30 Ref fSPh Value of fSPh obtained under normal condition. 31 Ref fSPh Status Status of fSPh obtained under normal condition. 32 Ref BlkF Value of BlkF obtained under normal condition. 33 Ref BlkF Status Status of BlkF obtained under normal condition. 34 Ref DPAvg Value of DPAvg obtained under normal condition. 35 Ref DPAvg
Status
36 Lim fDPmax Refer to
Table 4.3
37 Lim fDPmin Lower limit for Ratio fDP to detect the blockage.
38 Lim fSPlmax Upper limit for Ratio fSPl to detect the blockage.
39 Lim fSPlmin Lower limit for Ratio fSPl to detect the blockage.
40 Lim fSPhmax Upper limit for Ratio fSPh to detect the blockage.
41 Lim fSPhmin Lower limit for Ratio fSPh to detect the blockage.
42 Lim BlkFmax Upper limit for BlkF to detect the blockage.
43 Lim BlkFmin Lower limit for BlkF to detect the blockage.
44 Lim DPAvgmax Upper limit for DPAvg. Writable only when Diag Mode is "Stop". 45 Lim DPAvgmin Lower limit for DPAvg. Writable only when Diag Mode is "Stop".
46 Ref Lim fDPmin 7.0E-10 Lower limit to judge whether Ref fDP is available for ILBD operation.
47 Ref Lim fSPmin 1.0E-10 Lower limit to judge whether Ref fSPl and Ref fSPh are available for ILBD
48 Ref Lim BlkFmax 0.5 Upper limit to judge whether Ref BlkF is available for ILBD operation.
49 Status group 8 Refer to Table 4.5. 50 Status group 9 Refer to Table 4.5. 51 CRatio fDP Ratio fDP is compensated by following formula and used as treatable monitoring
52 CRatio fDP
Status
53 NRatio fDP When Non-compensation is selected in Diag DP Comp, NRatio fDP is used as
54 NRatio fDP
Status
55 Diag DPComp 0:
Compensation
56 Diag Applicable After the reference value is obtained, the applicable blockage detection is
Status of DPAvg obtained under normal condition.
Upper limit for Ratio fDP to detect the blockage. Writable only when Diag Mode is "Stop".
Writable only when Diag Mode is "Stop".
Writable only when Diag Mode is "Stop".
Writable only when Diag Mode is "Stop".
Writable only when Diag Mode is "Stop".
Writable only when Diag Mode is "Stop".
Writable only when Diag Mode is "Stop".
Writable only when Diag Mode is "Stop".
Writable only when Diag Mode is "Stop".
operation. Writable only when Diag Mode is "Stop".
Writable only when Diag Mode is "Stop".
value when the ow change is too large or small. Sqrt (fDP / Ref fDP) X | Ref DPAvg / DPAvg | When compensation is selected in Diag DP Comp, CRatio fDP is used as monitoring value.
Status of CRatio fDP
monitoring value. NRatio fDP = Sqrt (fDP / Ref fDP) Status of NRatio fDP
Whether fDP is referred by CRatio fDP or NRatio fDP is selected.
displayed on this parameter.
4-20
IM 01C25T01-06EN
<4. Diagnostics>
4-21

4.2.3 Heat Trace Monitoring

The transmitter with Heat trace monitoring function calculates the ange temperature by using the two temperature sensors built in the transmitter.
An analog alert is generated if the temperature reached to the preset level.
The ange temperature is based on the following parameters and calculation formula.
[Parameters]
Parameter name Explanation
Snsr temp (CT) Measured capsule temperature
value
Amp temp (AT) Measured amplier temperature
value
Flg temp (FT) Flange temperature value
(Calculated value)
Flg Temp Coef (Cf) Coefcient to calculate ange
temperature
Flg Temp Hi Alert Val Threshold to generate FT high
alarm
Flg Temp Lo Alert Val Threshold to generate FT low
alarm
[Calculation formula]
Flg temp (FT) = CT + Cf X (CT-AT)
If the ange temperature exceeds the value preset to Flg Temp Hi Alert Val or Flg Temp Lo Alert Val, an alert is generated.
4.2.3.1 Flg Temp Coef Setting
The value calculated according to the following procedure is set to Flg Temp Coef.
• To enhance the calculation accuracy of the ange temperature, measure the actual ange temperature by using the temperature sensor etc.
• Calculate the ratio of the capsule temperature to the capsule temperature minus the amplier temperature from the two temperature values measured by the transmitter.
• Derive the Flg Temp Coef from the measured ange temperature and the ratio of the capsule temperature to the amplier temperature in accordance with the following calculation formula.
Flg Temp Coef (Cf) =
(Actual measured value of Flange temperature) - CT
CT - AT
For DTM (HART 5), Flg Temp Coef parameter can be set by using Tuning function. By setting the measured value of ange temperature, Flg Temp Coef is calculated by using capsule temperature and amplier temperature.
• Procedure to call up the Tuning display.
Diag and Service → Advanced Diag Conguration → Heat Trace → Tuning
NOTE
The ange temperature is calculated by the calculation formula assumed that the capsule part of the transmitter is heated up or kept warm by an electrical heater or steam. In the case of an atmosphere temperature or less, the difference of temperature of approximately 3 to 4 °C, may occur because the amplier temperature becomes higher than the capsule temperature.
IM 01C25T01-06EN
<4. Diagnostics>
4-22
Sensor
Amplifier Temperature
Capsule Temperature
Sensor signals
Process Value
calculation
Amp temp
Snsr temp
Calculation of Flg temp
HTM alarm
Diag Output
Option
Flg Temp Coef
CT+(CT-AT) x Cf
Flg temp
Execution HTM
Alarm Masking
Figure 4.9 Functional Block Diagram of Heat Trace Monitoring (HTM)
4.2.3.2 Out of Temperature Measurement Range
When the ange temperature is out of measurement range, the alarm or alert is generated. For the detail of alarm and alert setting, refer to subsection 4.2.2.5.
DO Config
Result of HTM detection
Result of HTM detection
HTM alarm
HTM alarm
4-20mA DC (Analog Output)
Amp temp
Snsr temp
Contact Output (Digital Output)
Flg temp
Diag Error
Response Code (Device Status) Status group 9
Display on LCD
F0412.ai
The measurement range is set to Flg Temp Hi Alert Val and Flg Temp Lo Alert Val, which values
can be specied within -50 to 130 deg C.
An alarm is generated.
Flg Temp Hi Alert
Flg Temp Lo Alert
Flg temp
Flgtemp
An alarm is generated.
TimeTime
F0413.ai
IM 01C25T01-06EN
<4. Diagnostics>
4-23
4.2.3.3 Parameter Lists for Heat Trace Monitoring
# Parameter name Default value Explanation
1 Diag Error 0x0000 The results detected by ILBD or Heat trace monitoring are stored into this
parameter. Also the condition abnormality in the diagnostic process is stored as an error.
2 Diag Option 0x08FC The masking in this parameter enable to display each error message and
the status to the output signal or LCD. The error assigned to each bit is corresponding to that of Diag Error. Writable only when Diag Mode is "Stop".
3 Diag Out Option Off The error status can be output by 4-20 mA analog signal.
There are following three output modes; Off, Burnout, or Fall back.
4 Diag Fixed Out Val 21.6mA Parameter for "Fall back" function in the Diag Out option.
The output value in 4-20 mA analog signal is specied when an alarm is generated.
The value must be entered within 3.6 to 21.6 mA. 5 Snsr temp (Cap temp*2) Measured capsule temperature value 6 Amp temp Measured Amplier temperature value 7 Flg temp (*1) Calculated ange temperature value 8 Flg Temp Coef 0 Coefcient to calculate ange temperature (Cf: Rt1/Rt2)
Rt1: Thermal resistance between the ange and capsule. Rt2 : Thermal resistance between the cupsule and amplier.
9 Flg Temp Hi Alart Val
(Flg Temp High Limit*2)
10 Flg Temp Lo Alart Val
(Flg Temp Low Limit*2) 11 DO Select Off See subsection 3.3.13 Status Output 12 DO Signal type ON WHEN
13 Digital Output Off See subsection 3.3.13 Status Output
120 deg C Upper limit of Flg temp
-40 deg C Lower limit of Flg temp
See subsection 3.3.13 Status Output
AL DETECT
*1: The Flg Temp Coef is 0 at the shipment so that the Flg temp outputs the same value as that of Snsr temp. *2: EJX HART 5 DTM based on FDT1.2.
IM 01C25T01-06EN
<4. Diagnostics>

4.3 Alarms and Countermeasures

Table 4.5 Alarm Message Summary
Integral
indicator
AL. 01 CAP.ERR
AL. 02 AMP.ERR
AL. 10 PRESS
AL. 11 ST. PRSS
AL. 12 CAP.TMP
AL. 13 AMP.TMP
AL. 30 PRS.RNG
AL. 31 SP. RNG
AL. 35 P.HI
AL. 36 P.LO
AL. 37 SP.HI
AL. 38 SP.LO
*1: DD and DTM (excluding EJX HART 5 DTM based on FDT1.2) *2: EJX HART 5 DTM based on FDT1.2 *3: Available only for HART 7
HART conguration
tool display
P sensor error * Pressure Sensor
2
Error *
CT sensor error * Capsule Temperature Sensor Error *
1
1
2
Cap EEPROM error * Capsule EEPROM
2
Error * AT sensor error *
Amp Temp Sensor
2
Error *
1
Amp EEPROM error * Amp EEPROM Error
2
* CPU board error *
CPU Board Error * No device ID *
No Device ID * P outside limit *
Pressure Outside
2
Limit *
SP outside limit * Static Pressure Outside Limit *
CT outside limit * Cap Temp Outside
2
Limit * AT outside limit *
Amp Temp Outside
2
Limit * P over range *
Pressure Over Range
2
*
SP over range * Static Pressure Over
2
Range *
P high alarm *
1
2
1
2
1
1
2
1
1
1
1
1
Pressure High Alarm P low alarm *
1
Pressure Low Alarm SP high alarm *
Static Pressure High Alarm *
SP low alarm * Static Pressure Low Alarm *
1
2
1
2
Cause
4-20mA Output
operation during error
Sensor problem. Outputs the signal (High
or Low) set with burnout direction switch. [status output: undened]
Capsule temperature sensor problem.
1
Capsule EEPROM
(About the output signal, refer to subsection 3.3.9)
problem.
Amplier temperature sensor problem.
1
Amplier EEPROM problem.
Amplier problem.
No device ID is found. Continues to operate and
output.
Differential pressure is outside measurement range limit of capsule.
When PV is Pres Output AO upper limit or AO Lower limit. (Refer to subsection 3.3.1)
Static pressure exceeds limit.
When PV is SP Output AO upper limit or AO Lower limit. (Refer to subsection 3.3.1)
Capsule temperature is outside range (–50 to
Continues to operate and output.
130°C). Amplier temperature
is outside range (–50 to 95°C).
Differential pressure exceeds specied range.
When PV is Pres. Output AO upper limit or lower limit. (Refer to subsection 3.3.1)
Static pressure exceeds specied range.
When PV is SP Output AO upper limit or lower limit. (Refer to subsection 3.3.1)
Input pressure exceeds
2
*
specied threshold.
2
*
Continues to operate and output.
Input static pressure exceeds specied threshold.
Countermeasure
Replace capsule if the error recurs after the transmitter is restarted.
Replace capsule.
Replace amplier.
Replace amplier.
Check input or replace capsule when necessary.
Use heat insulation or make lagging to keep temperature within range.
Check input and range setting, and change them as needed.
Check input.
Status
group
1
*
1
2
2
3
4
5
4-24
Diagnostic
List
group *
Hardware Failure
Transducer Status
2
IM 01C25T01-06EN
<4. Diagnostics>
Integral
indicator
AL. 50 P. LRV
AL. 51 P. URV
AL. 52 P. SPN
AL. 53 P. ADJ
AL. 54 SP. RNG
AL. 55 SP. ADJ
AL.60 SC.CFG
*1: DD and DTM (excluding EJX HART 5 DTM based on FDT1.2) *2: EJX HART 5 DTM based on FDT1.2 *3: Available only for HART 7
HART conguration
tool display
Illegal P LRV * Illegal Pressure LRV
2
* Illegal P URV *
Illegal Pressure URV
2
* Illegal P SPAN *
Illegal Pressure SPAN
2
* P SPAN trim err *
Pressure SPAN Trim Error *
P ZERO trim err * Pressure ZERO Trim Error *
Illegal SP LRV * Illegal Static Pressure
2
LRV * Illegal SP URV *
Illegal Static Pressure URV *
Illegal SP SPAN * Illegal Static Pressure SPAN *
SP SPAN trim err * Static Pressure SPAN Trim Error *
SP ZERO trim err * Static Pressure ZERO Trim Error *
1
1
1
1
2
1
2
1
1
2
1
2
1
2
1
2
Specied value is outside of setting range.
Specied value is outside of setting range.
Cause
SC cong error Specied values or
settings to dene signal characterizer function do not satisfy the condition.
4-20mA Output
operation during error
Holds at the output value that existed immediately before the error occurred.
Continues to operate and output.
Holds at the output value that existed immediately before the error occurred.
Continues to operate and output.
Continue to operate and output.
Countermeasure
Check settings and change them as needed.
Adjust settings and change them as needed.
Check settings and change them as needed.
Adjust settings and change them as needed.
Check setting and change them as needed.
Status
group
1
*
6
7
4-25
Diagnostic
List
group *
Conguration
2
IM 01C25T01-06EN
<4. Diagnostics>
Integral
indicator
AL. 79 OV. DISP
AL.87 FLG. HI
AL.87 FLG. LO
AL.88 INVR.DP
AL.88 INVR.SL
AL.88 INVR.SH
AL.88 INVR.F
AL.89 ILBD.OV
AL.89 B BLK
AL.89 H BLK
AL.89 L BLK
AL.89 H LRG
AL.89 L LRG
AL.89 A BLK
AL. 91 * P. SIM
AL.91 * SP. SIM
AL.91 * T. SIM
*1: DD and DTM (excluding EJX HART 5 DTM based on FDT1.2) *2: EJX HART 5 DTM based on FDT1.2 *3: Available only for HART 7
HART conguration
tool display
Cause
Displayed value exceeds
limit.
FT high alarm * Flg Temp High Alarm
2
* FT low alarm *
Flg Temp Low Alarm
2
*
Invalid Ref DP * Invalid Ref fDP *
1
Flange temperature exceeds a preset upper limit.
1
Flange temperature is below a preset lower limit.
1
Differential pressure/
2
pressure uctuation does not reach the reference level required to blockage detection so that no blockage detection is carried out.
Invalid Ref SPL * Invalid Ref fSPl *
1
Low-pressure-side
2
uctuation does not reach the reference uctuation level required to blockage detection.
Invalid Ref SPH * Invalid Ref fSPh *
1
High-
2
pressure-side uctuation uctuation does not reach the reference uctuation level required to blockage detection.
Invalid Ref F * Invalid Ref BlkF *
1
BlkF can not be used for
2
blockage detection for some reasons.
ILBD over range * Outside Diagnosis
2
Range * B Blocking *1, *
1
Appointed the diagnosis range outside.
2
B Blocking (both-side blockage) is detected.
H Side Blocking * High Side Blocking *
L Side Blocking * Low Side Blocking *
Large Fluct H * Large Fluctuation of High Side *
Large Fluct L * Large Fluctuation of Low Side *
A Blocking *1, *
1
High-pressure-side
2
blockage is detected.
1
Low-pressure-side
2
blockage is detected.
1
2
1
2
2
Pressure uctuation amplitude of high­pressure side is large.
Pressure uctuation amplitude of low­pressure side is large.
A Blocking (single-side blockage) is detected.
P Simulate Mode Under Simulation Mode
3
for device variables.
SP Simulate Mode
3
T Simulate Mode
3
4-20mA Output
operation during error
Continues to operate and output.
It depends on the Diag Out Option setting.
Off: Continue to operate and output. Burnout:Outputs AO upper limit or AO lower limit. Fall back:Outputs Diag Out Fixed Val.
Continue to operate and output.
It depends on the Diag Out Option setting.
Off: Continue to operate and output. Burnout: Outputs AO upper limit or AO lower limit. Fall back: Outputs Diag Out Fixed Val.
Output the setting value of Simulate-Value
Countermeasure
Check settings and change them as needed.
Check the heater failure.
Check the capsule temp. and Amplier temp.
Adjust Flg Temp Coef.
Check process condition.
Check process condition.
Check Simulation Mode
Status
group
1
*
8
9
10
4-26
Diagnostic
List
group *
Diag Status
Diag Status
2
IM 01C25T01-06EN
<4. Diagnostics>
Table 4.6 HART Conguration Tool Error Messages
Error message Probable cause Countermeasure
Invalid selection Change the setting. Value was too high Set value is too high. Value was too low Set value is too low. Too few data bytes received — In write protect mode Operation is set in the Write Protect mode. — Lower range value too high LRV set point is too high. Change the range. Lower range value too low LRV set point is too low. Upper range value too high URV set point is too high. Upper range value too low URV set point is too low. Span too small Set span is too small. Applied process too high Applied pressure is too high. Adjust the applied pressure. Applied process too low Applied pressure is too low. New lower range value pushed upper
range value over upper sensor limit Excess correction attemted Amount of correction is too much. Adjust the amount. Lower conversion not succeeded Characters are not convertible. e.g. % Correct the setting. Not in xed current mode The xed current mode is desired but not
In multidrop mode Operation is set in the multi-drop mode. — Not write protect mode Operation is set without a password. — Lower range value and upper range
value out of limits
The shift of URV according to the new LRV setting exceeds USL.
set in that mode.
URV and LRV are out of range limits. Change the setting.
Change the URV setting within the range of USL.
Set in the xed current mode.
4-27
Table 4.7 Device Status
Item Description
Field Device Malfunction (0x80)
Conguration Changed (0x40)*
Cold Start (0x20)
More Status Available (0x10)
Loop Current Fixed (0x08)
Loop Current Saturated (0x04)
Non-Primary Variable Out of Limits (0x02)
Primary Variable Out of Limits (0x01)
*: This ag can be reset. Refer to subsection 4.1.3 (6) Reset
Conguration Changed Flag
Field device has malfunctioned due to a hardware error or failure.
A modication has been made to the conguration of the eld device.
A reset of the eld device has occurred, or power has been removed and reapplied.
Field device has more status available.
Analog output and its digital representation are in xed mode, and not responsive to input changes.
Analog output and its digital representation are outside the operating range limits, and not responding to input.
Process applied to the non-primary variable is outside the operating limits of the eld device.
Process applied to the primary variable is outside the operating limits of the eld device.
Table 4.8 Extended Device Status
Item Description
Maintenance Required (0x01)
Device Variable Alert (0x02)
Table 4.9 Data Quality and Limit Status
Data Quality Description
Good The value may be used in
Poor Accuracy The quality of the value is
Manual / Fixed The value is manually
Bad The value is not useful.
Limit Status Description
Constant The value cannot be
Low Limited The value is out of the
High Limited
Not Limited The value is free to
Device requires maintenance.
Conguration is invalid or device is under simulation mode.
control.
less than normal, but the value may still be useful.
xed.
changed, no matter what the process does.
high or low limit.
change.
IM 01C25T01-06EN
<4. Diagnostics>
Table 4.10 Relationship between Alarm and Status available for HART 7
Integral
Indicator
AL.01 CAP.ERR
HART conguration
tool display
P sensor error * Pressure Sensor
2
Error * CT sensor error *
Capsule Temperature Sensor Error *
Cap EEPROM
1
error * Capsule EEPROM Error *
AL.02 AMP.ERR
AT sensor error * Amp Temp Sensor Error *
Amp EEPROM
1
error * Amp EEPROM
2
Error * CPU board error
1
* CPU Board Error
2
*
--- No device ID * No Device ID *
AL.10 PRESS
P outside limit * Pressure Outside
2
Limit *
Device Status
1
Device Malfunction (0x80)
1
Extended
Device Status
Maintenance Required (0x01)
Differential
Pressure
(DP)
Value: Hold value Status: Bad and Constant
Value: Hold value Status: Bad and Constant
2
Value: Hold value Status: Bad and Constant
2
1
2
Value: Hold value Status: Bad and Constant
Value: Hold value Status: Bad and Constant
Value: Hold value Status: Bad and Constant
1
--- --- Value: Measured value
2
1
Primary Variable Out of Limits (0x01)
Device Variable Alert (0x02)
Status: Good and Not Limited Value:
Measured value Status: Poor Accuracy and Not Limited
Value and Status (Data Quality and Limit Status)
Static
Pressure
(SP)
Temperature
(T)
% range Loop current
Value:Hold value Status:Bad and Low Limited/ High Limited
Value: Hold value Status: Bad and Low Limited/High Limited
Value: Measured
Same as Value and Status
of PV value Status: Good and Not Limited
4-28
*3
*3
AL.11 ST.PRSS
AL.12 CAP.TMP
AL.13 AMP.TMP
AL.30 PRS.RNG
AL.31 SP. RNG
SP outside limit * Static Pressure Outside Limit *
CT outside limit * Cap Temp Outside Limit *
AT outside limit * Amp Temp Outside Limit *
P over range * Pressure Over Range *
SP over range * Static Pressure Over Range *
1
Non-Primary Variable Out of
2
Limits (0x02)
1
Non-Primary Variable Out of
2
Limits (0x02)
1
2
1
Loop Current
2
Saturated (0x04)
1
--- Value: Measured value
2
Value: Measured value Status: Good and Not Limited
Value: Measured value Status: Good and Not Limited
*1: DD and DTM (excluding EJX HART 5 DTM based on FDT1.2) *2: EJX HART 5 DTM based on FDT1.2 *3: Depend on the setting of hardware switch *4: Depend on the direction of range over (high or low)
Value: Hold value
Status: Bad and Low
Limited/High Limited
Status: Good and Not
Limited
*4
IM 01C25T01-06EN
<4. Diagnostics>
4-29
Integral
Indicator
AL.35 P. HI
AL.36 P. LO
AL.37 SP. HI
AL.38 SP. LO
AL.50 P. LRV
AL.51 P. URV
AL.52 P. SPN
AL.53 P. ADJ
HART conguration
tool display
P high alarm * Pressure High Alarm
P low alarm * Pressure Low Alarm
SP high alarm * Static Pressure High Alarm *
SP low alarm * Static Pressure Low Alarm *
Illegal P LRV * Illegal Pressure LRV *
Illegal P URV * Illegal Pressure URV *
Illegal P SPAN * Illegal Pressure SPAN *
1
2
*
1
2
*
2
2
1
2
1
2
1
1
1
2
P SPAN trim err * Pressure SPAN Trim Error *
P ZERO trim err * Pressure ZERO Trim Error *
2
1
2
Device Status
Device Status
--- Device Variable Alert (0x02)
1
Extended
Value and Status (Data Quality and Limit Status)
Differential
Pressure
(DP)
Static
Pressure
(SP)
Value: Measured value Status: Good and Not Limited
Value: Measured value Status: Good and Not Limited
Value: Measured value Status:
Value: Measured value Status:
Good and Not Limited Poor Accuracy and Not Limited
Temperature
(T)
% range Loop current
Value: Hold value Status: Bad and Constant
Value: Measured value Status: Poor Accuracy and Not Limited
AL.54 SP. RNG
AL.55 SP. ADJ
Illegal SP LRV * Illegal Static Pressure LRV *
Illegal SP URV * Illegal Static Pressure URV *
Illegal SP SPAN
1
* Illegal Static Pressure SPAN *
SP SPAN trim
1
err * Static Pressure SPAN Trim Error
2
*
1
2
1
2
2
Value: Measured value Status: Good and Not Limited
Value: Measured value Status: Good and Not Limited
SP ZERO trim
1
err * Static Pressure ZERO Trim Error
2
*
AL.60 SC.CFG
AL.79 OV.DISP
SC cong error Value: Measured value
Status: Good and Not Limited
--- --- --- Value: Measured value Status: Good and Not Limited
*1: DD and DTM (excluding EJX HART 5 DTM based on FDT1.2) *2: EJX HART 5 DTM based on FDT1.2 *3: Depend on the setting of hardware switch *4: Depend on the direction of range over (high or low)
Value: Measured value Status: Poor Accuracy and Not Limited
Value: Measured value Status: Good and Not Limited
Value: Measured value Status: Good and Not Limited
Value: Measured value Status: Good and Not Limited
IM 01C25T01-06EN
<4. Diagnostics>
4-30
Integral
Indicator
AL.87 FLG. HI
AL.87 FLG. LO
AL.88 INVR.DP
AL.88 INVR.SL
AL.88 INVR.SH
AL.88 INVR.F
AL.89 ILBD.OV
AL.89 B BLK
AL.89 H BLK
AL.89 L BLK
AL.89 H LRG
AL.89 L LRG
AL.89 A BLK
HART conguration
tool display
FT high alarm * Flg Temp High Alarm *
FT low alarm * Flg Temp Low Alarm *
Invalid Ref DP * Invalid Ref fDP *
1
2
1
2
1
2
Invalid Ref SPL * Invalid Ref fSPl *
Invalid Ref SPH * Invalid Ref fSPh
2
* Invalid Ref F *
1
Invalid Ref BlkF * ILBD over range
1
* Outside Diagnosis Range
2
* B Blocking *1, *
2
H Side Blocking * High Side Blocking *
2
L Side Blocking * Low Side Blocking *
Large Fluct H * Large Fluctuation of High Side *
Large Fluct L * Large Fluctuation of Low Side *
A Blocking *1, *
2
1
2
1
2
2
Device Status
Extended
Device Status
--- Maintenance Required (0x01)
1 2
1
2
1
1
Value and Status (Data Quality and Limit Status)
Differential
Pressure
(DP)
Static
Pressure
(SP)
Value: Measured value Status: Good and Not Limited
Value: Measured value Status: Good and Not Limited
Value: Measured value Status: Good and Not Limited
Value: Measured value Status: Good and Not Limited
Temperature
(T)
% range Loop current
In the case “Off” is set to Diag Out Option
Value: Measured value Status: Good and Not
Limited In the case “Burnout” is set to Diag Out Option
Value: Low Limited/High
Limited
Status: Bad and Low
Limited/High Limited
*3
In the case “Fall back” is set to Diag Out Option
Value: Fixed value
Status: Bad and Constant
In the case “Off” is set to Diag Out Option
Value: Measured value
Status: Good and Not
Limited In the case “Burnout” is set to Diag Out Option
Value: Low Limited/High
Limited
Status: Bad and Low
Limited/High Limited
*3
In the case “Fall back” is set to Diag Out Option
Value: Fixed value
Status: Bad and Constant
*1: DD and DTM (excluding EJX HART 5 DTM based on FDT1.2) *2: EJX HART 5 DTM based on FDT1.2 *3: Depend on the setting of hardware switch *4: Depend on the direction of range over (high or low)
IM 01C25T01-06EN
<4. Diagnostics>
4-31
Integral
Indicator
AL.91 P. SIM
HART conguration
tool display
Device Status
Extended
Device Status
P Simulate Mode --- Device
Variable Alert (0x02)
Differential
Pressure
Value and Status: Pressure simulation value
AL.91 SP.SIM
AL.91 T.SIM
SP Simulate Mode
T Simulate Mode Value: Measured value
Status: Good and Not
Limited
*1: DD and DTM (excluding EJX HART 5 DTM based on FDT1.2) *2: EJX HART 5 DTM based on FDT1.2 *3: Depend on the setting of hardware switch *4: Depend on the direction of range over (high or low)
(DP)
Value and Status (Data Quality and Limit Status)
Static
Pressure
(SP)
Value: Measured value Status: Good and Not
Temperature
(T)
% range Loop current
According to the setting of simulation
Limited
Value and Status: Static
Value: Measured value Status: Good and Not Limited
Pressure simulation value
Value and Status: Temperature simulation value
IM 01C25T01-06EN
<5. Parameter Summary>

5. Parameter Summary

5-1
Function Label Item Contents Default value Handling *
Analog output AO alm typ Analog output alarm type High or Low R
AO lower limit Lower limit of analog output 3.6000 to 21.6000 mA 3.6000 mA W AO upper limit Upper limit of analog output 3.6000 to 21.6000 mA 21.6000 mA W Auto recover Auto-recover from hardware error Off or On On W
Analog output trim
Clear D/A trim Reset analog output trim M D/A trim Analog output trim with ammeter M Scaled D/A trim Analog output trim with voltmeter M Channel ags Analog channel ags 0x00 R
Bi-directional
Bi-dir mode Bi-directional mode Off or On Off W
mode
Burst mode Burst mode Burst mode *
2
Off or On
HART 5
Off W
Off or Wired HART Enabled
HART 7
Burst option
HART 5
Burst Command
HART 7
Burst option Xmtr Variables, PV, % range/
current, Process vars/crnt
Burst Command *
2
Cmd 1: PV Cmd 2: % range/current Cmd 3: Dyn vars/current
W
Cmd 1: PV W
Cmd 9: Device vars w/status Cmd 48: Read Additional
Device Status.
Burst Variable Code (DD)
Device Variable for the Burst Message *
2
Max 8 slots. W
Device Variable Code (DTM)
HART 7
Burst Msg Trigger Mode
HART 7
Set Burst Trigger
HART 7
Set Burst Period
HART 7
Burst Trigger Level
HART 7
Update Period
HART 7
Burst Trigger Mode Selection Code
2
*
(Continuous, Window, Rising, Falling, On-change)
Congure burst trigger Congure Burst Msg Trigger
Mode and Burst Trigger Level
Congure burst period Congure Update Period and
Max Update Period
Burst Trigger Level *
Update Period for Burst mode *
2
2
Update period for burst message
Continuous R
0.0 R
Burst Message 1: 0.5s 2: 60s
M
M
R
3: 60s
Max Update Period
HART 7
Max Update Period for Burst mode
2
*
Maximum update period for burst message
60 min R
Damping Pres Damp Damping time constant for DP 0.00 to 100.00 s W
Quick resp Quick response On or Off Off W Date Date Date **/**/** W Descriptor Descriptor Descriptor 16 alphanumerics W
*1: Handling: R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,
D
=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters. *2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3) *3: The default value shows MWP (Maximum working pressure) of the capsule. Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.
1
IM 01C25T01-06EN
<5. Parameter Summary>
5-2
Function Label Item Contents Default value Handling *
Device information
Chg universal rev Change the HART universal
revision
Country
HART 7
Country code US, JP, DE, FR, ES, RU, CN JP W
HART 5 or HART 7 M
Dev id Device ID R Distributor Yokogawa R Drain vent matl Drain and vent plug material W Extra No. Customizaion number R Ext SW External zeroing permission Disabled or Enabled Enabled W Fill uid Fill uid W Final asmbly num Final assembly number W Fld dev rev Field device revision R Gasket matl Gasket material W Isoltr matl Capsule material W Mftr Date Manufactured date R Model 1 Memo eld for MS code 1 32 alphanumerics W Model 2 Memo eld for MS code 2 32 alphanumerics W Model 3 Memo eld for MS code 3 32 alphanumerics W Num of RS Number of remote seal W Process Conn matl Process connection material W Process Conn size Process connection size W Process Conn type Process connection type W RS ll uid Fill uid of remote seal W RS Isoltr matl Remote seal material W RS type Remote seal type W Serial No. Serial number R Sofftware rev Software revision R Style No. Style number Style number of product R Universal rev Universal revision 16 alphanumerics R Cfg chng count
HART 7
Reset Cfg chng ag
HART 7
Device Prole
HART 7
Max dev vars
HART 7
Model Model Model name + Measurement
Conguration change counter 0 R
Reset Conguration change ag M
Device Prole Process
automation device
Max device variables 3 R
R
R span in the Sufx Codes Ex) “EJX110 M”
Device Variable Simulation
Diag
Simulate
HART 7
Execution of device variable simulation
Execute the simulation M
Diag Applicable Appicable blockage detection Disabled or Enabled RG
Applicable Diag DPComp Diag DPComp fDP compensation selection Compensation or
Compensation WG
Non-compensation
Diag Error Diag Error Results detected by ILBD or Heat
RG
trace monitoring
*1: Handling: R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,
D
=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters. *2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3) *3: The default value shows MWP (Maximum working pressure) of the capsule. Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.
1
IM 01C25T01-06EN
<5. Parameter Summary>
5-3
Function Label Item Contents Default value Handling *
Diag Lim Lim fDPmax Upper limit for Ratio fDP
Lim fDPmin Lower limit for Ratio fDP Lim fSPlmax Upper limit for Ratio fSPl Lim fSPlmin Lower limit for Ratio fSPl Lim fSPhmax Upper limit for Ratio fSPh Lim fSPhmin Lower limit for Ratio fSPh Lim BlkFmax Upper limit for BlkF Lim BlkFmin Lower limit for BlkF Lim DPAvgmax Upper limit for DPAvg Lim DPAvgmin Lower limit for DPAvg
Diag Mode Diag Mode ILBD operation mode Stop, Calculation, or
Diag Option Diag Option Alarm masking WG Diag Output Diag Out Option Output mode of 4-20mA when
Diag Fixed Out Val 4-20 mA output when an advanced
Diag Period Diag Period Sampling period per one Diag count 180 sec WG Diag
Reference
Diag Ref Lim Ref Lim fDPmin Lower limit of fDP 7.0E-10 WG
Diag Supp Count
Diag Variables Ratio fDP SQRT (fDP/Ref fDP). RG
*1: Handling: R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3) *3: The default value shows MWP (Maximum working pressure) of the capsule. Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.
Diag Description Memo eld 32 alphanumerics WG Ref fDP Reference value of fDP WG Ref fDP Status Status of Reference fDP RG Ref fSPl Reference value of fSPl WG Ref fSPl Status Status of Reference fSPl RG Ref fSPh Reference value of fSPh WG Ref fSPh Status Status of Reference fSPh RG Ref BlkF Reference value of BlkF WG Ref BlkF Status Status of Reference BlkF RG Ref DPAvg Reference value of DPAvg WG Ref DPAvg Status Status of Reference DPAvg RG
Ref Lim fSPmin Lower limit of fSPl and fSPh 1.0E-10 WG Ref Lim BlkFmax Upper limit of BlkF 0.5 WG Diag Supp Count Detection count to generate an
Ratio fDP Status Status of Ratio fDP RG Ratio fSPl SQRT (fSPl/Ref fSPl). RG Ratio fSPl Status Status of Ratio fSPl RG Ratio fSPh SQRT (fSPh/Ref fSPh). RG Ratio fSPh Status Status of Ratio fSPh RG BlkF
BlkF Status Status of BlkF RG DPAvg Ratio of the average of differential
DPAvg Status Status of DPAvg RG CRatio fDP Compensated fDP RG CRatio fDP Status Status of CRatio fDP RG NRatio fDP Non-compensated fDP RG NRatio fDP Status Status of NRatio fDP RG
D
=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters.
an advanced diagnostic alarm is generated
diagnostic alarm is generated
alarm
Blockage degree characterized in comparison of high-pressure side and low-pressure side pressure uctuation values
pressure/pressure to the maximum span of an EJX transmitter.
Reference
Off, Burnout, or Fall back Off WG
3.6000 to 21.6000 mA 21.6 mA WG
Refer to Table 4.2.3 Refer to Table 4.2.3 Refer to Table 4.2.3 Refer to Table 4.2.3 Refer to Table 4.2.3 Refer to Table 4.2.3 Refer to Table 4.2.3 Refer to Table 4.2.3 Refer to Table 4.2.3 Refer to Table 4.2.3
WG WG WG WG WG WG WG WG WG WG WG
WG
RG
RG
1
IM 01C25T01-06EN
<5. Parameter Summary>
5-4
Function Label Item Contents Default value Handling *
Display setup Bar Indicator Bar indicator Off or On On W
Chg power on info Change the LCD display when
powering on
Disp Out 1 LCD output 1 PRES, PRES %,
On or Off
M
PRES % W
ENGR.PRES, SP, SP %
Disp Out 2 LCD output 2 PRES, PRES %,
Not used W ENGR.PRES, SP, SP % or Not used
Disp Out 3 LCD output 3 (Ditto) Not used W Disp Out 4 LCD output 4 (Ditto) Not used W Disp Pres % fnctn % display mode Linear or Sq root As specied or
W
Linear
Disp Pres % Reso % display resolution Normal or High resolution Normal W Engr exp User set exponent ---, x10, x100, x1000 --- or as
W
specied
Engr LRV User set lower range value Unit specied in Set Engr Unit As specied W Engr point Decimal place for user set 0 to 4 2 W Engr URV User set upper range value Unit specied in Set Engr Unit As specied W Modify Engr Unit User set engineering unit M Pres disp point Decimal place for differential
0 to 4 2 W
pressure Set Engr Unit Engineering unit select M SP disp point Decimal place for static pressure 0 to 4 2 WD Squawk
HART 7
Squawk Specify the device under the
communication (turn the LCD on).
M
Error log Error log Clear Clear error records M
Error log view Error records Log1 (latest) to log4 M
Event Notication
Event Notication Control
HART 7
Device Status
Event Notication (Enable event notication on
Off W token-passing data link layer, Off)
Event Masking W
Mask
HART 7
Status group 1 to 10 Mask
HART 7
Ext dev status Mask
HART 7
Device Diagnostic Status 0 Mask
HART 7
Device Diagnostic Status 1 Mask
HART 7
AO saturated Mask
HART 7
AO xed Mask
HART 7
Set Event Notication Timing
HART 7
Congure Event Notication Timing Congure Event Notication
Retry Time, Event Max Update Time and Event Debounce Interval
M
*1: Handling: R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,
D
=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters. *2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3) *3: The default value shows MWP (Maximum working pressure) of the capsule. Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.
1
IM 01C25T01-06EN
<5. Parameter Summary>
5-5
Function Label Item Contents Default value Handling *
Event Notication
Event Notication Retry Time
HART 7
Max Update Time
HART 7
Event Debounce Interval
HART 7
Acknowledge Event
Event Notication Retry Time R
Max Update Time for Event Notication
Event Debounce Interval Debounce Interval to detect
an event.
Acknowledge Event Notication W
R
R
Notication
HART 7
Event Status
HART 7
Event Status 0x00 Approved event or no
event
0x10 Conguration changed
R
event pending
0x20 Device status event
pending
0x40 More status available
event pending
Event Number
HART 7
Time First Unack
Event Number W
Time First Unack Event Triggered W
Event Triggered
HART 7
Latched Cfg chng
Latched Cfg chng count W
count
HART 7
Latched Device
Device status when event occurred W
Status
HART 7
Latched Status group 1 to 10
HART 7
Field device status when event occured
W
Latched Ext dev status
HART 7
Latched Device Diagnostic Status 0
HART 7
Latched Device Diagnostic Status 1
HART 7
Latched AO saturated
HART 7
Latched AO xed
HART 7
Flg temp Flg temp Calculated ange temperature
RG
value Flg Temp Coef Flg Temp Coef 0 WG Flg Temp Lim Flg Temp Hi Alart
Upper limit of Flange temperature
120 °C (deg C)
WG
Val Flg Temp Lo Alart
Lower limit of Flange temperature -40 °C (deg C) WG
Val
*1: Handling: R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,
D
=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters. *2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3) *3: The default value shows MWP (Maximum working pressure) of the capsule. Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.
1
IM 01C25T01-06EN
<5. Parameter Summary>
5-6
Function Label Item Contents Default value Handling *
Fluct Variables fDP Average value of the sum of
RG squares of differential pressure/ pressure uctuations
fDP Status Status of fDP RG fSPl Average value of the sum of
RG squares of low-pressure-sidestatic pressure uctuations
fSPl Status Status of fSPl RG fSPh Average value of the sum of
RG squares of high-pressure-side static pressure uctuations
fSPh Status Status of fSPh RG
Loop test Loop test Test output setting Within AO lower and upper
M
limits
Test Auto Release Time
Auto release time for the test function. Coverage is Loop test,
10min, 30min, 60min, 3h, 6h, 12h
10 min W
DO test and Device Variable Simulation.
Low cut Low cut Low cut 0.00 to 20.00% Refer to
W
subsection
3.2.6
Low cut mode Low cut mode Linear or Zero Linear W Master test Master test Software reset and self test M Message Message Message 32 alphanumerics As specied W Number of
requested preambles
Optional function
Piping
Num req preams Number of requested preambles R
Num resp preams
HART 7
Option Password
Number of response preambles 5 W
Optional function activation password
W
H/L Swap Impulse piping accessing direction Normal or Reverse Normal WD orientation
Poll address Poll addr Poll address for multidrop use 0 to 15(HART 5), 0 to
0 W
63(HART 7)
Loop current mode
HART 7
Process Alerts Digital Output
EJX
DO Select
EJX
DO Signal type
EJX
DO Test
EJX
Pres Alert Mode Alert Mode for differential pressure Off, Hi Al Detect,Lo Al Detect,
Loop current mode in Multi Drop
(Disabled, Enabled) Disabled W
mode
Display of contact output Off or On Off RA
Contact output select Off, Combination of Pres, SP
Off WA
and Temp
Signal type select ON WHEN AL. DETECT, OFF
WHEN AL. DETECT
ON WHEN AL. DETECT
WA
Test output contact Status High, Status Low, Exit MA
Off W
Hi/Lo Al Detect
Hi Alert Val High alert value for differential
pressure
Lo Alert Val Low alert value for differential
pressure
SP Alert Mode Alert Mode for static pressure Off, Hi Al Detect,Lo Al Detect,
Set the threshold value for high side alarm
Set the threshold value for low side alarm
W
W
Off WD
Hi/Lo Al Detect
SP Hi Alert Val High alert value for static pressure Set the threshold value for
WD
high side alarm
SP Lo Alert Val Low alert value for static pressure Set the threshold value for
WD
low side alarm
Temp Alert Mode Alert Mode for temperature Off, Hi Al Detect,Lo Al Detect,
Off W
Hi/Lo Al Detect
*1: Handling: R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,
D
=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters. *2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3) *3: The default value shows MWP (Maximum working pressure) of the capsule. Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.
1
IM 01C25T01-06EN
<5. Parameter Summary>
5-7
Function Label Item Contents Default value Handling *
Process Alerts Temp Hi Alert Val High alert value for temperature Set the threshold value for
120°C (deg C) W
high side alarm
Temp Lo Alert Val Low alert value for temperature Set the threshold value for
-40°C (deg C) W
low side alarm
Process variables
Engr Disp User scaled value R Engr Unit User set engineering unit Unit specied in Set Engr Unit
8 alphanumerics
Loop Current (DD) AO (DTM)
HART 7
Loop Current Data Quality
HART 7
Loop Current Limit Status
HART 7
PV (DD) Pres (DTM)
PV (Pres) Data Quality
HART 7
PV (Pres) Limit Status
HART 7
PV Update time
Loop current value
3.6 to 21.6 mA R
(Analog Output Current)
Device variable process data quality
Device variable limit status Device variable limit status of
Device variable process data quality of Loop Current (mA)
Good R
Not limited R
Loop Current (mA)
Pressure/Differential pressure value
Device variable process data quality
Device variable limit status Device variable limit status of
Device variable process data quality of pressure
Good R
Not limited R
pressure
PV (Pres) Update time period 45 ms R period (DD) Update time period (DTM)
HART 7
% range (DD)
Pressure value in % -2.50 to 110.00% R Pres % (DTM)
HART 7
% rnge (Percent Range) Data Quality
HART 7
% rnge (Percent Range) Limit Status
HART 7
Device variable process data
quality
Device variable process data quality of % range (Percent Range)
Device variable limit status Device variable limit status of
% range (Percent Range)
Good R
Not limited R
SV (DD), SP (DTM) Static pressure value RD SP % Static pressure value in % -10.0 to 100.00 % RD SV (SP) Data
Quality
HART 7
SV (SP) Limit Status
HART 7
SV Update time
Device variable process data
quality
Device variable limit status Device variable limit status of
Device variable process data quality of SV (SP)
Good R
Not limited R
SV (SP)
SV (SP) Update time period 360 ms R period (DD) SP update time (DTM)
HART 7
1
R
R
*1: Handling: R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,
D
=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters. *2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3) *3: The default value shows MWP (Maximum working pressure) of the capsule. Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.
IM 01C25T01-06EN
<5. Parameter Summary>
5-8
Function Label Item Contents Default value Handling *
Process variables
TV (DD) Snsr temp (DTM)
TV (Temp) Data Quality
HART 7
TV (Temp) Limit Status
HART 7
TV Update time
Temperature value Capsule temperature R
Device variable process data quality
Device variable limit status Device variable limit status of
Device variable process data quality of TV (Temp)
Good R
Not limited R
TV (Temp)
TV (Temp) Update time period 1s R period (DD) Temp update time (DTM)
HART 7
Range change Apply values Re range for measured pressure 4 mA, 20 mA, or Exit M
Min Span Minimum span for pressure R LRV Lower range value for pressure As specied W LSL Lower sensor limit for pressure R URV Upper range value for pressure As specied W USL Upper sensor limit for pressure R
Self test Self test Self-diagnostics M Sensor trim Clear P snsr trim Reset pressure trim to factory
M
setting Clear SP snsr trim Reset SP trim to factory setting MD P LTD Lower pressure trim deviation R P LTP Lower temperature trim point R P UTD Upper pressure trim deviation R P UTP Upper temperature trim point R Pres trim Pressure trim M Pres Zero trim Zeroing M SP LTD Lower SP trim deviation RD SP LTP Lower SP trim point RD SP UTD Upper SP trim deviation RD SP UTP Upper SP trim point RD Static Pres trim Static pressure trim MD Trim Date Trim date **/**/** W Trim Desc Trim description 16 alphanumerics W Trim Loc Trim location 8 alphanumerics W Trim Who Trim person 8 alphanumerics W
Set Diag Mode Set Diag Mode ILBD operation mode Stop, Calculation, or
WG
Reference
Signal characterizer
Num of points Number of coordinates 0 to 9 9 W Point setting Coordinates editor M S.C. Signal characterizer permission Disabled or Enabled Disabled W X End End point of X 100.00% R X Start Start point of X 0.00% R Y End End point of Y 100.00% R Y Start Start point of Y 0.00% R
*1: Handling: R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,
D
=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters. *2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3) *3: The default value shows MWP (Maximum working pressure) of the capsule. Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.
1
IM 01C25T01-06EN
<5. Parameter Summary>
5-9
Function Label Item Contents Default value Handling *
SP setup A/G Select Gauge/Abs select for static
Gauge or Absolute Absolute WD
pressure Atm. Pres Value Conversion coefcient 101.3 kPa WD SP Apply values Rerange for static pressure “0%, 100%, or Exit” MD SP Damp Damping time constant for SP 0.00 to 100.00 2.00 s WD SP H/L Select H/L select for static pressure High or Low High WD SP Min Span Minimum span for static pressure RD SP LRV Lower range value for static
Within measurement range 0.0 MPa WD
pressure SP LSL Lower sensor limit for static
RD
pressure
*3
SP URV
Upper range value for static
Within measurement range WD
pressure SP USL Upper sensor limit for static
RD
pressure
Status Device Status Current operating status R
Status group 1 Device status information for
Display the hardware error R
hardware Status group 2 Device status information for
Display the hardware error R
hardware Status group 3 Device status information for
process Status group 4 Device status information for
process Status group 5 Device status information for
process Status group 6 Status group 7 Status group 8 Status group 9 Status group 10
HART 7
Ext dev status
HART 7
Device status information for data
Device status information for data
Device status information for data
Device status information for data
Device status information for data
Extended Device Status R
Display the process error (Out of specication)
Display the process error (Out of setting range)
Display the process error (Alarm)
Display the setting error R Display the setting error R Display the diagnostic alarm R Display the diagnostic alarm R Display the simulation mode R
R
R
R
Time Stamp Time Stamp 00:00:00 R
Tag Tag Tag number 8 alphanumerics As specied W
Long tag
HART 7
Temperature compensation
Temperature sensor
Transfer
T.Z. Cmp mode Temperature compensation mode Off or On Off W Temp Zero Zero shift compensation –99.999 to 99.999%/degC 0.000%/degC W Amp temp Amplier temperature R Snsr temp Capsule temperature R Xfer fnctn Output mode Linear or Sq root As specied or
function
Units Unit Pressure, Differential pressure unit As specied or
Long tag Max 32 alphanumerics As specied W
W
Linear
W
kPa SP Unit Static pressure unit MPa WD Temp Unit Temperature unit deg C, deg F, or Kelvin deg C W
Write protection menu
Enable wrt 10min Write protection release 8 alphanumerics M New password User set password for write
8 alphanumerics M
protection
Write protect Write protection indicator Yes or No No R
*1: Handling: R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,
D
=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters. *2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3) *3: The default value shows MWP (Maximum working pressure) of the capsule. Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.
1
IM 01C25T01-06EN
<Appendix1. Safety Instrumented Systems Installation>
A1-1
Appendix 1. Safety Instrumented Systems
Installation
The calibration of the transmitter must be performed
WARNING
after parameters are set.
The contents of this appendix are cited from exida.com safety manual on the transmitters specically observed for the safety transmitter purpose. When using the transmitter for Safety Instrumented Systems (SIS) application, the instructions and procedures in this section must be strictly followed in order to preserve the transmitter for that safety level.

A1.1 Scope and Purpose

This section provides an overview of the user responsibilities for installation and operation of the transmitter in order to maintain the designed safety level for Safety Instrumented Systems (SIS) applications. Items that will be addressed are proof testing, repair and replacement of the transmitter, reliability data, lifetime, environmental and application limits, and parameter settings.
A1.2 Using the transmitter for an
SIS Application

A1.2.1 Safety Accuracy

The transmitter has a specied safety accuracy of 2%. This means that the internal component failures are listed in the device failure rate if they will cause an error of 2% or greater.

A1.2.2 Diagnostic Response Time

The transmitter will report an internal failure within 5 seconds of the fault occurrence.

A1.2.4 Required Parameter Settings

The following parameters need to be set in order to maintain the designed safety integrity.
Table A1.1 Required Parameter Settings
Item Description
Burnout direction switch
Write protection switch
To specify if the output should go
21.6 mA or higher or 3.6 mA or lower upon detection of an internal failure.
The write function should be disabled.

A1.2.5 Proof Testing

The objective of proof testing is to detect failures within the transmitter that are not detected by the diagnostics of the transmitter. Of main concern are undetected failures that prevent the safety instrumented function from performing its intended function. See table A1.2 for proof testing method.
The frequency of the proof tests (or the proof test interval) is to be determined in the reliability calculations for the safety instrumented functions for which the transmitter is applied. The actual proof tests must be performed more frequently or as frequently as specied in the calculation in order to maintain required safety integrity of the safety instrumented function.
The following tests need to be specically executed when a proof test is performed. The results of the proof test need to be documented and this documentation should be part of a plant safety management system. Failures that are detected should be reported to Yokogawa.

A1.2.3 Setup

During installation the transmitter must be setup with engineering units parameters. This is typically done with a handheld terminal. These parameters must be veried during the installation to insure that the correct parameters are in the transmitter. Engineering range parameters can be veried by reading these parameters from the optional local display or by checking actual calibration of the transmitter.
The personnel performing the proof test of the transmitter should be trained in SIS operations including bypass procedures, transmitter maintenance, and company management of change procedures.
IM 01C25T01-06EN
<Appendix1. Safety Instrumented Systems Installation>
Table A1.2 Proof Testing
Testing method Tools required Expected outcome Remarks
Functional test:
1. Follow all Management of Change procedures to bypass logic solvers if necessary.
2. Execute HART/BRAIN command to send value to high alarm (21.5 mA) and verify that current has reached this level.
3. Execute HART/BRAIN command to send value to low alarm (3.6 mA) and verify that current has reached this level.
4. Restore logic solvers operation and verify.
Perform three point calibration along with the functional test listed above.
• Handheld terminal Proof Test Coverage =52%
• Handheld terminal
• Calibrated pressure
source
Proof Test Coverage =99%
The output needs to be monitored to assure that the transmitter communicates the correct signal.
A1-2

A1.2.6 Repair and Replacement

If repair is to be performed with the process online the transmitter will need to be bypassed during the repair. The user should setup appropriate bypass procedures.
In the unlikely event that the transmitter has a failure, the failures that are detected should be reported to Yokogawa.
When replacing the transmitter, the procedure in the installation manual should be followed.
The personnel performing the repair or replacement of the transmitter should have a sufcient skill level.

A1.2.7 Startup Time

The transmitter generates a valid signal within 1 second of power-on startup.

A1.2.8 Firmware Update

In case rmware updates are required, they will be performed at factory. The replacement responsibilities are then in place. The user will not be required to perform any rmware updates.

A1.2.9 Reliability Data

A detailed Failure Mode, Effects, and Diagnostics Analysis (FMEDA) report is available from Yokogawa with all failure rates and failure modes.
The development process of the transmitter is certied up to SIL3, allowing redundant use of the transmitter up to this Safety Integrity Level, depending the PFDavg calculation of the entire Safety Instrumented Function.
When using the transmitter in a redundant conguration, the use of a common cause factor (β-factor) of 2% is suggested. (However, if the redundant transmitters share an impulse line or if clogging of the separate impulse lines is likely, a common cause factor of 10% is suggested.)
Note that the failure rates of the impulse lines need to be accounted for in the PFDavg calculation.

A1.2.10 Lifetime Limits

The expected lifetime of the transmitter is 50 years. The reliability data listed the FMEDA report is only valid for this period. The failure rates of the transmitter may increase sometime after this period. Reliability calculations based on the data listed in the FMEDA report for transmitter lifetimes beyond 50 years may yield results that are too optimistic, i.e. the calculated Safety Integrity Level will not be achieved.

A1.2.11 Environmental Limits

The environmental limits of the transmitter are specied in the user’s manual IM 01C25.
The transmitter is certied up to SIL2 for use in a simplex (1oo1) conguration, depending on the PFDavg calculation of the entire Safety Instrumented Function.

A1.2.12 Application Limits

The application limits of the transmitter are specied in the user’s manual IM 01C25. If the transmitter is used outside of the application limits, the reliability data listed in A1.2.9 becomes invalid.
IM 01C25T01-06EN
<Appendix1. Safety Instrumented Systems Installation>
A1-3
A1.3 Denitions and
Abbreviations
A1.3.1 Denitions
Safety Freedom from unacceptable
risk of harm
Functional Safety The ability of a system to carry
out the actions necessary to achieve or to maintain a dened safe state for the equipment/machinery/plant/ apparatus under control of the system
Basic Safety The equipment must be
designed and manufactured such that it protects against risk of damage to persons by electrical shock and other hazards and against resulting re and explosion. The protection must be effective under all conditions of the nominal operation and under single fault condition

A1.3.2 Abbreviations

FMEDA Failure Mode, Effects and Diagnostic
Analysis
SIF Safety Instrumented Function
SIL Safety Integrity Level
SIS Safety Instrumented System
SLC Safety Lifecycle
Verication The demonstration for each
phase of the life-cycle that the (output) deliverables of the phase meet the objectives and requirements specied by the inputs to the phase. The verication is usually executed by analysis and/or testing
Validation The demonstration that the
safety-related system(s) or the combination of safety­related system(s) and external risk reduction facilities meet, in all respects, the Safety Requirements Specication. The validation is usually executed by testing
Safety Assessment The investigation to arrive at a
judgment -based on evidence­of the safety achieved by safety-related systems
Further denitions of terms used for safety techniques and measures and the description of safety related systems are given in IEC 61508-4.
IM 01C25T01-06EN
<Appendix2. ILBD Check List>

Appendix 2. ILBD Check List

Fill out the below checklist according to the operation ow of the ILBD in order to keep the important information for the blockage detection.
Checklist (1/5)
No. Items Parameters Result Example
1 4-20 mA Analog Signal Setting
• Select the output mode when an alarm is generaed.
2 Status Output
3 Stability of Pres
(differential pressure/pressure) under normal condition
Diag Out Option
Diag Fixed Out Val mA 21.6 mA
DO Select
Status Good
Off: Burnout: Fall back:
Pres: SP: Temp: Diag: All:
A2-1
• Check that the status of Pres is “GOOD”.
• Check the maximum and minimum values of Pres.
4 fDP under normal condition
• Check that the value of fDP is more than
-10
7x10
.
5 Start to obtain Reference values
• Set "Reference" to Diag Mode.
6 End of Reference Value Sampling
• Check that Diag Mode is “Calculation” after the time set to "Diag Period" passed.
7 Alarm setting
• Record the status of Checkbox in Diag Option.
Pres
fDP
Diag Mode
Diag Mode
Diag Option
A Blocking Large Fluct L Large Fluct H L Side Blocking H Side Blocking B Blocking Invalid Ref F Invalid Ref SPH Invalid Ref SPL Invalid Ref DP ILBD over range
Max.:
Min.:
                   
Max.: 12.3 kPa
Min.: 12.1 kPa
IM 01C25T01-06EN
<Appendix2. ILBD Check List>
Checklist (2/5)
No. Items Parameters Result Example
Alarm status
8
• Check the alarm status shown in Diag Error.
• Check that the alarm status of “ILBD over range” is not shown in Diag Error.
ILBD parameters
9
• Record the values of parameters for ILBD operation.
• Check the status of parameters for ILBD operation.
*: Record the value after checked that the
status of each parameter is “GOOD”.
Diag Error
A Blocking
Large Fluct L
Large Fluct H
L Side Blocking
H Side Blocking
B Blocking
Invalid Ref F
Invalid Ref SPH
Invalid Ref SPL
Invalid Ref DP
ILBD over range
Diag Period 180 Lim fDPmax 3.000000 Lim fDPmin 0.300000 Lim fSPlmax 5.000000 Lim fSPlmin 0.500000 Lim fSPhmax 5.000000 Lim fSPhmin 0.500000 Lim BlkFmax 0.600000 Lim BlkFmin -0.600000 Lim DPAvgmax 1.000000 Lim DPAvgmin 0.050000 Diag Supp Count 3 Ref fDP* 7.43245E-09 Ref fSPl* 7.25765E-09 Ref fSPh* 7.18374E-09 Ref DPAvg* 5.36425E+00 fDP* 7.48562E-09 fSPl* 7.23277E-09 fSPh* 7.14085E-09 BlkF* -0.287259 DPAvg* 0.055957
A2-2
IM 01C25T01-06EN
<Appendix2. ILBD Check List>
A2-3
Checklist (3/5)
Go to the following step according to the result of "Invalid Ref xx" shown in the Diag Error of 8th check item.
Diag Error
Invalid Ref SPH Invalid Ref SPL Invalid Ref DP
: The alarm is generated.: The alarm is not generated.
No. Items Parameters Result Example
10-a
10-a-1
Simulation of Blockage detection operation
• H Side Blocking: 10-a-1
• L Side Blocking: 10-a-2
• Both Side Blocking: 10-a-3
H Side Blocking
• Close the high-pressure side valve completely.
• Record the values of fDP, fSPl, fSPh, BlkF, and DPAvg after the certain time, (Diag Period X Diag Supp Count), passed.
*: Record the value after checked that the
status is “GOOD”.
• Record the status of Checkbox in Diag Option.
• Check that the alarms status of “A Blocking” and “H Side Blocking” are set.
Note: If the alarm of “ILBD over range” is generated,
the valve may be closed too much tightly. Open valve a little and record the updated status of the parameters.
• Check that the alarm of “H Side Blocking” is generated.
• Check that the alarm of “L Side Blocking” is not generated.
fDP* 7.48562E-09
fSPI* 7.23277E-09
fSPh* 7.14085E-09
BlkF -0.287259
Diag Option A Blocking
Large Fluct L
Large Fluct H
L Side Blocking
H Side Blocking
B Blocking
Invalid Ref F
Invalid Ref SPH
Invalid Ref SPL
Invalid Ref DP
ILBD over range
Diag Error
L Side Blocking
H Side Blocking
→ →
Check
item
10-a
10-b
IM 01C25T01-06EN
<Appendix2. ILBD Check List>
Checklist (4/5)
No. Items Parameters Result Example
10-a-2
10-a-3
L Side Blocking
• Close the low-pressure side valve completely.
• Record the values of fDP, fSPl, fSPh, BlkF, and DPAvg after the certain time, (Diag Period X Diag Supp Count), passed.
*: Record the value after checked that the
status is “GOOD”.
• Record the status of Checkbox in Diag Option.
• Check that the alarms status of “A Blocking” and “L Side Blocking” are set.
Note: If the alarm of “ILBD over range” is generated,
the valve may be closed too much tightly. Open valve a little and record the updated status of the parameters.
• Check that the alarm of “L Side Blocking” is generated.
• Check that the alarm of “H Side Blocking” is not generated.
Both Side Blocking
• Close the both-pressure side valves completely.
• Record the values of fDP, fSPl, fSPh, BlkF, and DPAvg after the certain time, (Diag Period X Diag Supp Count), passed.
*: Record the value after checked that the
status is “GOOD”.
• Record the status of Checkbox in Diag Option.
• Check that the alarms status of “H Side Blocking”, “L Side Blocking”, and “B Blocking” are set.
Note: If the alarm of “ILBD over range” is generated,
the valve may be closed too much tightly. Open valve a little and record the updated status of the parameters.
• Check that the alarm of “B Blocking” is generated.
fDP* 7.48562E-09
fSPI* 7.23277E-09
fSPh* 7.14085E-09
BIkF -0.287259
Diag Option A Blocking
Large Fluct L
Large Fluct H
L Side Blocking
H Side Blocking
B Blocking
Invalid Ref F
Invalid Ref SPH
Invalid Ref SPL
Invalid Ref DP
ILBD over range
Diag Error
L Side Blocking
H Side Blocking
fDP* 7.48562E-09
fSPI* 7.23277E-09
fSPh* 7.14085E-09
BIkF -0.287259
Diag Option A Blocking
Large Fluct L
Large Fluct H
L Side Blocking
H Side Blocking
B Blocking
Invalid Ref F
Invalid Ref SPH
Invalid Ref SPL
Invalid Ref DP
ILBD over range
Diag Error
B Blocking
A2-4
IM 01C25T01-06EN
<Appendix2. ILBD Check List>
Checklist (5/5)
No. Items Parameters Result Example
10-b Simulation of Blockage detection operation
• Close completely the valve for the side where the alarm of Invalid Reference Value is not generated.
For the case that the high-pressure side value is closed;
• Record the values of fDP, fSPl, fSPh, BlkF, and DPAvg after the certain time, (Diag Period X Diag Supp Count), passed.
*: Record the value after checked that the
status is “GOOD”.
For the case that the low-pressure side value is closed;
• Record the values of fDP, fSPl, fSPh, BlkF, and DPAvg after the certain time, (Diag Period X Diag Supp Count), passed.
*: Record the value after checked that the
status is “GOOD”.
• Record the status of Checkbox in Diag Option.
• Check that the alarms status of “B Blocking” is set.
Note: If the alarm of “ILBD over range” is generated,
the valve may be closed too much tightly. Open valve a little and record the updated status of the parameters.
• Check that the alarm of “B Blocking” is not generated.
fDP* 7.48562E-09
fSPh* 7.14085E-09
fDP* 7.48562E-09
fSPI* 7.23277E-09
Diag Option
A Blocking
Large Fluct L
Large Fluct H
L Side Blocking
H Side Blocking
B Blocking
Invalid Ref F
Invalid Ref SPH
Invalid Ref SPL
Invalid Ref DP
ILBD over range
Diag Error
B Blocking
A2-5
IM 01C25T01-06EN

Revision Information

Title : DPharp
HART 5/HART 7 Communication Type (EJXA, EJAE)
Manual No. : IM 01C25T01-06EN
Edition Date Page Revised Item
1st June 2010 New publication
2nd Apr. 2012
2-1
3-34
3rd June 2012 Add EJA series
4th June 2013 Add DTM for EJX and EJA based on FDT 2.0.
Re-edit to a common User’s Manual of HART 5 and HART 7.
2.1 Add integral indicator display when powering on.
3.3.18 Add switching procedure for HART protocol revision (HART 5/HART 7)
IM 01C25T01-06EN
Loading...