Appendix 2. ILBD Check List ........................................................................A2-1
Revision Information
IM 01C25T01-06EN
<1. Introduction>
1. Introduction
1-1
Thank you for purchasing the DPharp EJX
series pressure transmitter/EJA series pressure
transmitter(“transmitter”).
The transmitters are precisely calibrated at the
factory before shipment.
To ensure both safety and efciency, please
read this manual carefully before operating the
instrument.
This manual describes the HART protocol
communication functions of the transmitter
and explains how to set the parameters for the
transmitters using the HART conguration tool.
For information on the installation, wiring, and
maintenance of the transmitters, please refer to the
user’s manual of each model.
WARNING
When using the transmitter in a Safety
Instrumented Systems (SIS) application, refer
to Appendix 1 in this manual. The instructions
and procedures in the appendix must be strictly
followed in order to maintain the designed safety
integrity of the transmitter.
• Please note that changes in the specications,
construction, or component parts of the
instrument may not immediately be reected
in this manual at the time of change, provided
that postponement of revisions will not cause
difculty to the user from a functional or
performance standpoint.
• The following safety symbols are used in this
manual:
WARNING
Indicates a potentially hazardous situation which,
if not avoided, could result in death or serious
injury.
CAUTION
Indicates a potentially hazardous situation which,
if not avoided, may result in minor or moderate
injury. It may also be used to alert against unsafe
practices.
Regarding This Manual
• This manual should be provided to the end
user.
• The contents of this manual are subject to
change without prior notice.
• All rights reserved. No part of this manual may
be reproduced in any form without Yokogawa’s
written permission.
• Yokogawa makes no warranty of any kind with
regard to this manual, including, but not limited
to, implied warranty of merchantability and
tness for a particular purpose.
• If any question arises or errors are found, or if
any information is missing from this manual,
please inform the nearest Yokogawa sales
ofce.
• The specications covered by this manual are
limited to those for the standard type under the
specied model number break-down and do not
cover custom-made instruments.
IMPORTANT
Indicates that operating the hardware or software
in this manner may damage it or lead to system
failure.
NOTE
Draws attention to information essential for
understanding the operation and features.
IM 01C25T01-06EN
<1. Introduction>
1-2
1.1 Safe Use of This Product
For the safety of the operator and to protect the
instrument and the system, please be sure to follow
this manual’s safety instructions when handling this
instrument. If these instructions are not heeded,
the protection provided by this instrument may be
impaired. In this case, Yokogawa cannot guarantee
that the instrument can be safely operated. Please
pay special attention to the following points:
(a) Installation
• This instrument may only be installed by an
engineer or technician who has an expert
knowledge of this device. Operators are not
allowed to carry out installation unless they
meet this condition.
• With high process temperatures, care must
be taken not to burn yourself by touching the
instrument or its casing.
• Never loosen the process connector nuts when the
instrument is installed in a process. This can lead
to a sudden, explosive release of process uids.
• When draining condensate from the pressure
detector section, take appropriate precautions to
prevent the inhalation of harmful vapors and the
contact of toxic process uids with the skin or eyes.
• When removing the instrument from a
hazardous process, avoid contact with the
process uid and the interior of the meter.
• All installation shall comply with local installation
requirements and the local electrical code.
(b) Wiring
• The instrument must be installed by an engineer
or technician who has an expert knowledge of
this instrument. Operators are not permitted to
carry out wiring unless they meet this condition.
• Before connecting the power cables, please
conrm that there is no current owing through
the cables and that the power supply to the
instrument is switched off.
(c) Operation
• Wait 10 min. after the power is turned off before
opening the covers.
(d) Maintenance
• Please carry out only the maintenance
procedures described in this manual. If you
require further assistance, please contact the
nearest Yokogawa ofce.
• Care should be taken to prevent the build up of dust
or other materials on the display glass and the name
plate. To clean these surfaces, use a soft, dry cloth.
(e) Modication
• Yokogawa will not be liable for malfunctions or
damage resulting from any modication made
to this instrument by the customer.
1.2 Warranty
• The warranty shall cover the period noted on
the quotation presented to the purchaser at the
time of purchase. Problems occurring during
the warranty period shall basically be repaired
free of charge.
• If any problems are experienced with this
instrument, the customer should contact the
Yokogawa representative from which this
instrument was purchased or the nearest
Yokogawa ofce.
• If a problem arises with this instrument,
please inform us of the nature of the problem
and the circumstances under which it
developed, including the model specication
and serial number. Any diagrams, data and
other information you can include in your
communication will also be helpful.
• The party responsible for the cost of xing the
problem shall be determined by Yokogawa
following an investigation conducted by Yokogawa.
• The purchaser shall bear the responsibility for
repair costs, even during the warranty period, if
the malfunction is due to:
- Improper and/or inadequate maintenance by
the purchaser.
- Malfunction or damage due to a failure
to handle, use, or store the instrument in
accordance with the design specications.
- Use of the product in question in a location
not conforming to the standards specied by
Yokogawa, or due to improper maintenance
of the installation location.
- Failure or damage due to modication or
repair by any party except Yokogawa or an
approved representative of Yokogawa.
- Malfunction or damage from improper
relocation of the product in question after
delivery.
- Reason of force majeure such as res,
earthquakes, storms/oods, thunder/
lightening, or other natural disasters, or
disturbances, riots, warfare, or radioactive
contamination.
IM 01C25T01-06EN
<1. Introduction>
1-3
1.3 Abbreviation and Marking
The following models, HART protocol revisions and
conguration les are applied in this manual.
HART
Model
EJAE
EJXA*
*: Not applicable for EJX9A
In order to classify multiple models, HART protocol
revisions, or conguration les, abbreviated words
or marks are used as below in this manual.
■ Applied models
• The following expression is used instead of
model name.
[Model: EJAE]
EJA series or EJA
[Model: EJXA (excluding EJX9A)]
EJX series or EJX
EJX
•
applied for EJX series only.
■ HART protocol revision
• Two HART protocol revisions are expressed for
short as below.
Protocol
Revision
5
7
5
7
Conguration le
• DD (Device Description)
• DTM (FDT1.2)
• DTM (FDT2.0)
mark indicates specication or function
■ Conguration le
Three conguration les are applied in this
manual.
• DD stands for Device Description (le).
• This manual covers two revision DTM (Device
Type Manager) les based on FDT (Field
Device Tool) standard. The difference of
revisions is indicated as follows.
[DTM for FDT 1.2]
DTM (FDT1.2) or [1.2]
[DTM for FDT2.0]
DTM (FDT2.0) or [2.0]
The root referring to a parameter is classied to
Group I or II according to applied conguration le.
Conguration
le
DD
DTM (FDT2.0)I
Note: Only DTM (FDT1.2) for EJX with HART 5 is classied to
Group II.
EJAEJX
HART 5 HART 7 HART 5 HART 7
I
I
IDTM (FDT1.2)II
As the above, two roots referring to a parameter is
shown in this manual.
mark indicates specication or function
applied for HART 7 only.
Refer to section 2.2 for typical functions for
HART 7.
HART 5
•
mark indicates specication or function
applied for HART 5 only.
For parameter menu tree, refer to section 3.1.
IM 01C25T01-06EN
<1. Introduction>
1.4 Applicable Conguration Files
DD
FileApplied device
File name
010=2 or later
0a0=1 or later
030=3 or later
0a0=2 or later
DD revision
()
Model
EJA series
EJX series
DTM
FileApplied device
File name
EJA-NEXT
HART DTM
DTM
revision
3.3.0.140 or later
*2
EJA-NEXT
FDT2.0
5.0.0.0 or later
*3
HART DTM
EJA-NEXT
HART 7 DTM
3.3.0.140 or later
*2
EJA-NEXT
FDT2.0
5.0.0.0 or later
*3
HART 7 DTM
EJXV3.11.4.160.8 or later
EJX FDT2.0
HART DTM
EJX HART 7
DTM
EJX FDT2.0
HART 7 DTM
*1: The DTM is included in Yokogawa DTM Library HART 2012-2/Device Files R3.03.03 or later.
*2: The DTM is included in Yokogawa Device DTM Library 2.3/Device Files R3.03.03 or later.
*3: The DTM is included in Device DTM Library 4.0 or later.
Refer to section 2.2 to 2.4 for conrmation of each revision number.
IM 01C25T01-06EN
<1. Introduction>
1.5 ATEX Documentation
This is only applicable to the countries in European Union.
1-5
GB
DK
E
NL
SK
CZ
I
LT
LV
EST
PL
SF
D
SLO
P
H
F
BG
RO
S
M
GR
IM 01C25T01-06EN
<2. Connection>
2. Connection
2.1 Integral Indicator Display
When Powering On
For models with the integral indicator code “D”, the
display shows all segments in the LCD and then
changes to the displays shown below sequentially.
All segments display
Model name (3 s)
2.2 HART Protocol Revision
NOTE
LCD display can be set to “All segments display”
only.
• Procedure to call up the display
DD (HART 5/7)
DTM (HART 7
/EJA:HART 5)
DTM
(EJX:HART 5)
ON
OFF
[Root Menu] (Refer to subsection
3.1.1) → Detailed setup → Display
condition → Chg power on info
Conguration → Local Display
→ Chg power on info
Show all segments display, Model
name, Communication Protocol, and
Device Revision when powering on.
Show all segments display when
powering on.
2-1
Communication Protocol (3 s)
Device Revision (3 s)
F0200.ai
Either “5” or “7” is displayed on the “Communication
Protocol” display as HART protocol revision
followed by device revision number on the “Device
Revision” display.
NOTE
This function is available for software revision
2.02 or later.
Software revision can be checked by the
following procedure.
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
[Root Menu](Refer to subsection
3.1.1) → Review → Software rev
Conguration → Device
information1 → Software rev
NOTE
In this User’s Manual, HART protocol revision
5 and 7 are described as HART 5 and HART 7
respectively.
For the models with the output signal code “-J”,
HART protocol revision 5 or 7 is selectable. The
protocol revision is set as specied in the order.
The typical function which is available by HART
protocol revision 7 is listed as follows. Refer to
HART 7 description in this document or
HART 7
mark
for detail.
• Long Tag Supporting Up to 32 Characters
Long tag secures a better asset management
with abundant digits in its software.
• Enhanced Burst Mode and Event Notication
Advanced burst mode includes the variety
of transmission setting by specifying burst
variables, update period, and message trigger
mode, and event notication function gives
you alert signal based on the status change in
preset values and self-diagnosis.
• Squawk
Identifying the transmitter by displaying the
particular pattern on LCD
• Multidrop Communication
Up to 63 transmitters can be connected. An
analog signal output available for one device in
a loop.
How to conrm protocol revision is shown below.
There are three ways to conrm the protocol
revision set to the transmitter.
IM 01C25T01-06EN
<2. Connection>
F0201.ai
: Refer to USER'S MANUAL.
Made in Japan
TOKYO 180-8750 JAPAN
MODEL
SUFFIX
SUPPLY
OUTPUT
MWP
mA DC
V DC
STYLE
CAL
RNG
NO.
XXX - - - XX
Revision No.
(a) Conrmation on the name plate
The last numerical number engraved after
Serial number and year of production shows
HART protocol revision number at the shipment
which is shown in Figure 2.1.
NOTE
HART 7 communication is supported by
FieldMate R2.02 or later.
NOTE
When the output signal code of the transmitter
is “-J”, HART protocol revision can be changed.
Refer to subsection 3.3.18 about the procedure
of the revision change of HART 5 and HART 7.
2-2
Output Signal
Code
Revision No.
HART Protocol
Revision
5HART 5
J
7HART 7
-HART 7
E-HART 5
Figure 2.1 Hart Protocol Revision Number on
Name Plate
(b) Conrmation on integral indicator
(A case of integral indicator code D is specied)
Refer to section 2.1.
(c) Conrmation by using HART conguration tool
1) Connect the conguration tool to the
transmitter.
2) Conrm numerical number displayed on
“Universal rev” column.
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
[Root Menu (refer to 3.1.1) ]
→ Review → Universal rev
Conguration → HART
→Universal rev
IMPORTANT
Protocol revision supported by HART
conguration tool must be the same or higher
than that of the transmitter.
Protcol revision
supported by HART
conguration tool
57
Protocol revision of
the transmitter
: Communication OK
×: Communication NG
5
7×
2.3 Device Description (DD) on
a Conguration Tool and
Transmitter Device Revision
Before using a HART conguration tool, conrm
that the DD for the transmitter is installed in the
conguration tool.
About the DD, use the device type, device revision
and DD Revision shown in the Table 2.1.
Table 2.1 HART Protocol Revision, Device
Revision and DD Revision
HART
Protocol
Revision
(*1)
5
7
*1: When the output signal code is “–E”, only “5” is available.
The device revision of the transmitter and DD can
be conrmed as shown below.
If the correct DD is not installed in the conguration
tool, download it from the ofcial web site of HART
Communication Foundation.
(1) Conrmation of device revision for the
transmitter
● Conrmation on integral indicator
(A case of integral indicator code D is
specied)
Refer to the section 2.1
DPharp Pressure Transmitter
Model
EJX series
EJA series
EJX series
EJA series
Device
Type
EJX
(0x51)
EJA-NEXT
(0x5C)
EJX
(0x3751)
EJA-NEXT
(0x375C)
Device
RevisionDDRevision
3
1
10
10
3
or later
2
or later
2
or later
1
or later
IM 01C25T01-06EN
<2. Connection>
2-3
● Conrmation by using HART conguration
tool
a) Connect the conguration tool to the
transmitter.
b) Conrm numerical number displayed on
“Fld dev rev” column.
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
[Root Menu (refer to 3.1.1) ]
→ Review →Fld dev rev
Conguration → HART
→Fld dev rev
(2) Conrmation of device revision for the
conguration tool
Conrm the device revision from the installed
DD le name according to the procedure
provided for the conguration tool.
The rst two digits indicate the device revision
and the next two digits indicate the DD revision.
0 a 0 2. X X X
DD revision
Device revision
2.4 Set the parameters using
DTM
When congure the parameters using FieldMate,
use the DTM (Device Type Manager) shown in the
Table 2.2.
NOTE
The DTM revision can be conrmed by “DTM
setup”.
Device Files is a Media included in FieldMate.
The user registration site provides Device Files
with the latest update programs.
(URL: https://voc.yokogawa.co.jp/PMK/)
In case update, following operation by “DTM
setup” is required.
• Update DTM catalog
• Assign corresponding DTM to the device
(refer to Table 2.2)
Refer to FieldMate Instruction Manual for detail.
NOTE
Device revision of DD le is given in hexadecimal
Table 2.2 Applicable DTM
FileApplied device
File name
EJA-NEXT
HART DTM
EJA-NEXT
FDT2.0
HART DTM
EJA-NEXT
HART 7 DTM
EJA-NEXT
FDT2.0
HART 7 DTM
EJXV3.11.4.160.8 or later
EJX FDT2.0
HART DTM
EJX HART 7
DTM
EJX FDT2.0
HART 7 DTM
*1: The DTM is included in Yokogawa DTM Library HART 2012-2/Device Files R3.03.03 or later.
*2: The DTM is included in Yokogawa Device DTM Library 2.3/Device Files R3.03.03 or later.
*3: The DTM is included in Device DTM Library 4.0 or later.
DTM
revision
3.3.0.140 or later
5.0.0.0 or later
3.3.0.140 or later
5.0.0.0 or later
5.0.0.0 or later
3.3.0.140 or later
5.0.0.0 or later
*2
*3
*2
*3
*1
*3
*2
*3
FDT
revision
FDT1.2
FDT2.0
FDT1.2
FDT2.0
FDT1.2
FDT2.0
FDT1.2
FDT2.0
Model
EJA series
EJX series
HART
protocol
revision
5
7
5
7
Device type
EJA-NEXT
(0x5C)
EJA-NEXT
(0x375C)
EJX
(0x51)
EJX
(0x3751)
Device
revision
1
10
3
10
IM 01C25T01-06EN
<2. Connection>
F0203.ai
2-4
2.5 Interconnection Between
DPharp and the HART
Conguration Tool
The HART conguration tool can interface with the
transmitter from the control room, the transmitter
site, or any other wiring termination point in the
loop, provided there is a minimum of 250 Ω
between the connection and the power supply. To
communicate, it must be connected in parallel with
the transmitter; the connections are non-polarized.
Figure 2.2 illustrates the wiring connections for
direct interface at the transmitter site for the
DPharp. The HART conguration tool can be used
for remote access from any terminal strip as well.
Control room
Terminal
board
Distributor
DPharp
Relaying
terminals
USB
FieldMate
Modem
2.6 Power Supply Voltage and
Load Resistance
When conguring the loop, make sure that the
external load resistance is within the range in the
gure below.
(Note) With an intrinsically safe transmitter, external load
resistance includes safety barrier resistance.
600
External
load
resistance
R (Ω)
250
010.5 16.625.242
Figure 2.3 Relationship between Power Supply
E–10.5
R=
0.0244
Power supply voltage E (V DC)
Communication
applicable range
Voltage and External Load Resistance
PULSE
SUPPLY
CHECK
ALARM
HART configuration tool
PC/FieldMate
USB
Figure 2.2 Connecting the HART Conguration
Tool
F0202.ai
IM 01C25T01-06EN
<3. Parameter Setting>
3. Parameter Setting
3.1 Menu Tree
The structure of menu tree varies according to conguration tool based on DD or DTM. The difference is
classied into two groups (I and II) as shown in the below table.
3-1
Applied model
EJA series
EJX series
I: DD and DTM (excluding EJX HART 5 DTM based on FDT1.2)
II: EJX HART 5 DTM based on FDT1.2
HART protocol
revision
DD
HART 5
HART 7
HART 5II
I-1
HART 7I-2
. . . . . . . . . . . . . . . . . . . . . . . . .
FDT1.2FDT2.0
I-2
. . . . .
DTM
I-2
Refer to section 3.1.1.
Refer to section 3.1.2.
3.1.1 Group I: DD and DTM (excluding EJX HART 5 DTM based on FDT1.2)
When FieldMate with DD and DTM (excluding EJX HART 5 DTM based on FDT1.2) is used in order to set or
refer to parameters, there is difference on the initial root menu as below.
I-1 DD
Root Menu
• Device setup
• Pres
• AO
• LRV
• URV
I-2 DTM
Root Menu
• Device Configuration* - Configure/Setup
• Diagnostic*
• Process Variable*
• Process variables
• Diag/Service
• Basic setup
• Detailed setup
• Review
• Basic setup
• Detailed setup
• Review
• Diag/Service
• Process Variables
A
B
C
D, E
C
D, E
B
A
*: The next parameter is displayed on the top menu when using the DTM based or FDT2.0.
A
•
Process variables
• Pres
• Pres %
• AO
• SP
• SP %
• Snsr temp
• Engr Disp
• Engr exp
• Engr Unit
• Device Variables
and Status
HART 7
• Pres
• Pres Data Quality
• Pres Limit Status
• SP
• SP Data Quality
• SP Limit Status
• Snsr temp
• Temp Data Quality
• Temp Limit Status
• Pres %
• Percent Range Data Quality
• Percent Range Limit Status
• AO
• Loop Current Data Quality
• Loop Current Limit Status
DTMDD
• PV
• PV Data Quality
• PV Limit Status
• SV
• SV Data Quality
• SV Limit Status
• TV
• TV Data Quality
• TV Limit Status
• % rnge
• % rnge Data Quality
• % rnge Limit Status
• Loop current
• Loop current Data Quality
• Loop current Limit Status
HART 7
F0301-01.ai
: HART 7 only
F0301-02.ai
IM 01C25T01-06EN
<3. Parameter Setting>
HART 7
B
: HART 7 only
EJX
: EJX Series only
3-2
• Diag/Service
• Test device (DD)
• Status (DTM)
• Loop Test(DD)
• Test (DTM)
• Calibration
• Status
• Self test
• Master test
• Squawk
• Simulate
HART 7
HART 7
• Loop test
• Self test
• Master test
• Squawk
• Simulate
HART 7
HART 7
• Test Auto Release
Time
• Re-range (DD)
• Keypad input (DTM)
• Analog output trim
• Status group 1
• Status group 2
• Status group 3
• Status group 4
• Status group 5
• Status group 6
• Status group 7
• Status group 8
• Status group 9
• Status group 10
• Device status
• Ext dev status
• Cfg chng count
HART 7
HART 7
HART 7
HART 7
• Reset Cfg chng flag
• Time Stamp
HART 7
• Keypad input
• Apply values
• D/A trim
• Scaled D/A trim
• Clear D/A trim
HART 7
• LRV
• URV
• Unit
• LSL
• USL
• Min span
• Diag Parameters
EJX
• Error log
• Test Auto Release
Time (DD)
• Pres sensor trim
• SP sensor trim
• Trim info.
See B1
(next page)
• Error log view
• Error log Clear
• Pres Zero trim
• Pres trim
• P LTP
• P UTP
• Pres trim info.
• Static Pres trim
• SP LTP
• SP UTP
• SP trim info.
• Trim Who
• Trim Date
• Trim Loc
• Trim Desc
• P LTD
• P UTD
• Clear P snsr trim
• SP LTD
• SP UTD
• Clear SP snsr trim
F0301-03.ai
IM 01C25T01-06EN
<3. Parameter Setting>
• Diag Mode
• Diag Applicable
• Diag Variables
EJX
: EJX Series only
• Ratio fDP Status
• Ratio fDP
• Ratio fSPl Status
• Ratio fSPl
• Ratio fSPh Status
• Ratio fSPh
• BlkF Status
• BlkF
• DP Avg Status
• DP Avg
• CRatio fDP Status
• CRatio fDP
• NRatio fDP Status
• NRatio fDP
3-3
• Diag Parameters
EJX
B1
• Diag Error
• Diag Option
• ILBD Parameters
• Status
• Configuration
• Diag Reference
• Fluct Variables
• Set Diag Mode
• Diag Period
• Diag Lim
• Diag Description
• Ref fDP Status
• Ref fDP
• Ref fSPl Status
• Ref fSPl
• Ref fSPh Status
• Ref fSPh
• Ref BlkF Status
• Ref BlkF
• Ref DP Avg Status
• Ref DP Avg
• fDP Status
• fDP
• fSPl Status
• fSPl
• fSPh Status
• fSPh
• Lim fDPmax
• Lim fDPmin
• Lim fSPlmax
• Lim fSPlmin
• Lim fSPhmax
• Lim fSPhmin
• Lim BlkFmax
• Lim BlkFmin
• Lim DPAvgmax
• Lim DPAvgmin
• HT Parameters
• Diag Output
• Status
• Configuration
• Diag Out Option
• Diag Fixed Out Val
• Diag Reference
• Diag Supp Count
• Diag Ref Lim
• Diag DPComp
• Snsr temp
• Amp temp
• Flg temp
• Flg Temp Coef
• Flg Temp Lim
• Diag Description
• Ref fDP
• Ref fSPl
• Ref fSPh
• Ref BlkF
• Ref DP Avg
• Ref Lim fDPmin
• Ref Lim fSPmin
• Ref Lim BlkFmax
• Flg Temp Hi Alert Val
• Flg Temp Lo Alert Val
F0301-04.ai
IM 01C25T01-06EN
<3. Parameter Setting>
C
• Basic setup
• Tag
HART 7
3-4
: HART 7 only
• Long tag
HART 7
• Unit
• Re-range
• Device infomation
• Xfer fnctn
• Pres Damp
• Low cut
• Low cut mode
• H/L Swap
• SP setup
• Keypad input
• Apply values
• Date
• Descriptor
• Message
• Write protect
• Model
HART 7
• SP Range
• SP Unit
• SP Damp
• SP A/G Setup
• SP H/L Select
• LRV
• URV
• Unit
• LSL
• USL
• Min span
• Keypad input
• SP Apply values
• A/G Select
• Atm. Pres Value
• SP LRV
• SP URV
• SP Unit
• SP LSL
• SP USL
• SP Min span
F0301-05.ai
IM 01C25T01-06EN
<3. Parameter Setting>
3-5
D
• Detailed setup
• Review
• Sensors
• Signal condition
• Pressure sensor
• SP sensor
• Temp sensor
• Snsr temp
• Amp temp
• Temp Unit
• Process variables
• Pres
• Pres %
• Unit
• Pres sensor trim
• SP
• SP %
• SP Unit
• A/G Select
• SP H/L Select
• SP sensor trim
• SP setup
• Pres
• Pres %
• SP
• Snsr temp
• Pres Zero trim
• Pres trim
• P LTP
• P UTP
• Pres trim info.
• Static Pres trim
• SP LTP
• SP UTP
• SP trim info.
• SP Range
• SP Unit
• SP Damp
• SP A/G Setup
• SP H/L Select
HART 7
: HART 7 only
EJX
: EJX Series only
• P LTD
• P UTD
• Clear P snsr trim
• SP LTD
• SP UTD
• Clear SP snsr trim
• SP LRV
• SP URV
• SP Unit
• SP LSL
• SP USL
• SP Min Span
• Keypad input
• SP Apply values
• A/G Select
• Atm. Pres Value
• Output condition
• Display condition
• Device information
• Test Key
• Re-range
• Unit
• Xfer fnctn
• Pres Damp
• Low cut
• Low cut mode
• H/L Swap
• Bi-dir mode
• Quick resp
• T.Z. Cmp menu
• S.C. menu
• Process variables
• Analog output
See D1
(next page)
See E
• Keypad input
• Apply values
• S.C.
• Num of points
• Point setting
• X Start
• Y Start
• X End
• Y End
• Loop test
• Loop current mode
HART 7
• D/A trim
• Scaled D/A trim
• Clear D/A trim
• AO alm typ
• Channel flags
HART 7
• Auto recover
• AO lower limit
• AO upper limit
• LRV
• URV
• Unit
• LSL
• USL
• Min span
• T.Z. Cmp mode
• Temp Zero
• Pres
• Pres %
• AO
• SP
• SP %
• Snsr temp
• Engr Disp
• Engr exp
• Engr Unit
• Digital Output
EJX
F0301-06.ai
IM 01C25T01-06EN
<3. Parameter Setting>
D1
• HART output
• Poll addr
• Loop current mode
HART 7
• Num req preams
• Num resp preams
HART 7
• Burst Condition
HART 7
• Burst mode
• Burst option
HART 5
HART 5
• Burst Message 1
• Burst mode
• Burst Command
• Burst Device
Variables
• Set Burst Trigger
• Set Burst Period
• Burst Msg Trigger
Mode
• Burst Trigger Level
• Update Period
• Max Update Period
HART 5
HART 7
3-6
: HART 5 only
: HART 7 only
EJX
: EJX Series only
• Burst Variable Code
(DD)
• Device Variable
Code (DTM)
• Process Alerts (DD)
• Process Alerts
(DTM)
• Pres Alert mode
• Config Pres Alerts
• SP Alert mode
• Config SP Alerts
• Temp Alert mode
• Config Temp Alerts
• DO Config
EJX
• Pres Alert
• SP Alert
• Temp Alert
• DO Config
EJX
• Burst Message 2
• Burst Message 3
• Event Notification
• PV Update time
period (DD)
• SV Update time
period (DD)
• TV Update time
period (DD)
• Update time period
(DTM)
• SP update time
(DTM)
• Temp update time
(DTM)
• Hi Alert Val
• Lo Alert Val
• LSL
• USL
• Temp Hi Alert Val
• Temp Lo Alert Val
• Digital Output
• DO Select
• DO Signal type
• DO Test
• Pres Alert mode
• Config Pres Alerts
• SP Alert mode
• Config SP Alerts
• Temp Alert mode
• Config Temp Alerts
• Digital Output
• DO Select
• DO Signal type
• DO Test
Same as above
Same as above
• Event Notification
Control
• Event Mask
• Set Event
Notification Timing
• Event Notification
Retry Time
• Max Update Time
• Event Debounce
Interval
• Knowledge (DD)
• Knowledge (DTM)
• SP Hi Alert Val
• SP Lo Alert Val
• SP LSL
• SP USL
• Hi Alert Val
• Lo Alert Val
• LSL
• USL
• SP Hi Alert Val
• SP Lo Alert Val
• SP LSL
• SP USL
• Temp Hi Alert Val
• Temp Lo Alert Val
• Device Status Mask
• Status group 1 Mask
to 10 Mask
• Ext dev status Mask
• Device Diagnostic
Status 0 Mask
• Device Diagnostic
Status 1 Mask
• AO saturated Mask
• AO fixed Mask
• Event Status
• Time First Unack
Event Triggered
• Acknowledge Event
Notificatoin
• Event Status
• Event Number
• Time First Unack
Event Triggered
• Latched Cfg chng
count
• Latched Device
Status
• Latched Status
group 1 to 10
• Latched Ext dev
status
• Latched Device
Diagnostic Status 0
• Latched Device
Diagnostic Status 1
• Latched AO
saturated
• Latched AO fixed
F0301-07.ai
IM 01C25T01-06EN
<3. Parameter Setting>
E
• Detailed setup
• Review
• Sensors
• Signal condition
• Output condition
• Display condition
• Disp select
• P disp condition
• Disp Out1
• Disp Out2
• Disp Out3
• Disp Out4
• Disp Pres % fnctn
• Disp Pres % Reso
• Pres disp point
HART 7
3-7
: HART 7 only
• Device information
• Test Key
• SP disp condition
• Engr disp range
• Bar indicator
• Chg power on info
• Field device info
• Sensor infomation
• Self test (DD)
• SP disp point
• Engr LRV
• Engr URV
• Engr exp
• Engr Unit
• Engr point
• Set Engr Unit
• Modify Engr Unit
• Tag
• Long tag
HART 7
• Date
• Descriptor
• Message
• Model 1
• Model 2
• Model 3
• Write protect
• Wrt protect menu
• Ext SW
• Revision #’s
• Additional Info
• Option Password
• Isoltr matl
• Fill fluid
• Gasket matl
• Process Conn matl
• Drain vent matl
• Process Conn type
• RS isoltr matl
• Process Conn size
• Num of RS
• RS fill fluid
• RS type
• Write protect
• Enable wrt 10min
• New password
• Software seal
• Universal rev
• Fld dev rev
• Software rev
• Chg universal rev
• Style No.
• Serial No.
• Mftr Date
• Extra No.
• Final asmbly num
• Dev id
• Distributor
• Country
• Max dev vars
HART 7
• Device Profile
HART 7
HART 7
F0301-08.ai
IM 01C25T01-06EN
<3. Parameter Setting>
3.1.2 Group II: EJX HART 5 DTM based on FDT1.2
Root Menu
• Process Variables
• Device Status
• Diag and Service
• Easy Setup
• Configuration
• Calibration
• Write Protect
P
• Process Variables
• Pres %
• AO
• URV
• LRV
• Xfer fnctn
• Pres Damp
• Pres
• SP
• A/G Select
• Snsr temp
• Engr Disp
• Engr exp
• Engr Unit
• USL
• LSL
• P UTP
• P LTP
P
Q
R
S
T
U
V
3-8
Q
• Device Status
• Process Variable
• Diagnostic List
• Pres %
• Pres
• SP
• Snsr Temp
• Device Status
• Hardware Failure
• Transducer Status
• Diag Status
• Configuration
F0301-21.ai
IM 01C25T01-06EN
<3. Parameter Setting>
R
• Diag and Service
• Service
• Advanced Diag
Variables
• Loop test
• Master test
• DO Test
• Error log view
• Error log Clear
• Test Key
• Test Auto Release
Time
• Diag Description
• BlkF
• fDP
• fSPh
• fSPl
• DPAvg
• Ref BlkF
• Ref fDP
• Ref fSPh
• Ref fSPl
• Ref DPAvg
• CRatio fDP
• NRatio fDP
• Ratio fDP
• Ratio fSPh
• Ratio fSPl
• Cap Temp
• Amp Temp
• Flg Temp
3-9
• Advanced Diag
Configurations
• Advanced Diag
Alerts
• Impulse Line
Blockage Detection
• Heat Trace
• Diag Out Option
• Diag Fixed Out Val
• Diag Error
• Diag Mode
• Diag Period
• Diag DPComp
• Diag Description
• Ref BlkF
• Ref fDP
• Ref fSPh
• Ref fSPl
• Ref DPAvg
• Alarm Notification
• Threshold
• Alarm Notification
• Threshold
• Flg Temp
Coefficient
• Tuning
• Flg Temp
• Related to high side
alarm
• Related to both side
alarm
• Related to low side
alarm
• Related to Flg temp
alarm
• Diag Option
• Diag Suppress Count
• Sensitivity
• Fig Temp High Limit
• Fig Temp Low Limit
S
• Easy Setup
• Tag
• USL
• LSL
• Unit
• URV
• LRV
• Xfer fnctn
• Pres Damp
• Low cut
• Low cut mode
F0301-22.ai
IM 01C25T01-06EN
<3. Parameter Setting>
T
• Configuration
• Pressure Sensor
• Static Pressure
Sensor
• Physical Information
• Process Input
• Analog Output
• Local Display
• Signal Characterizer
Menu
• Process Alerts
• Device Information1
• Process Conn type
• Process Conn matl
• Process Conn size
• Gasket matl
• Isoltr matl
• Drain vent matl
• Fill fluid
• RS type
• RS isoltr matl
• RS fill fluid
• Num of RS
• Disp Out1
• Disp Out2
• Disp Out3
• Disp Out4
• Disp Pres % fnctn
• Disp Pres % Reso
• Pres disp point
• Engr URV
• Engr LRV
• Engr Unit
• Engr exp
• Engr point
• SP disp point
• Bar Indicator
• Chg power on info
• Model
• Manufacturer
• Hardware rev
• Software rev
• Date
• Descriptor
• Message
• Final asmbly num
• Auto recover
• Ext SW
• SP USL
• SP LSL
• SP Min Span
• SP Unit
• SP URV
• SP LRV
• SP Damp
• SP H/L Select
• A/G Select
• Atm. Pres Value
• Pres %
• AO
• Unit
• URV
• LRV
• Apply values
• Xfer fnetn
• Pres Damp
• Low cut
• Low cut mode
• AO alm typ
• AO upper limit
• AO lower limit
• Quick resp
• Bi-dir mode
• Pres Alert mode
• Hi Alert Val
• Lo Alert Val
• SP Alert mode
• SP Hi Alert Val
• SP Lo Alert Val
• Temp Alert mode
• Temp Hi Alert Val
• Temp Lo Alert Val
• Digital Output
• DO Select
• DO Signal type
3-10
• USL
• LSL
• Min span
• H/L Swap
• T.Z. Cmp mode
• Temp Zero
• Pres
• Unit
• Pres %
• SP
• SP Unit
• SP %
• Snsr temp
• Temp Unit
• S.C.
• Num of points
• X Start
• X End
• Y Start
• Y End
• X1
• X2
• X3
• X4
• X5
• X6
• X7
• X8
• X9
• Y1
• Y2
• Y3
• Y4
• Y5
• Y6
• Y7
• Y8
• Y9
• Device Information2
• HART
• Tag
• Poll addr
• Dev id
• Universal rev
• Fld dev rev
• Chg universal rev
• Num req preams
• Physical signal
code
• Burst mode
• Burst option
• Model 1
• Model 2
• Model 3
• Style No.
• Serial No.
• Mftr Date
• Extra No.
F0301-23.ai
IM 01C25T01-06EN
<3. Parameter Setting>
U
• Calibration
• Trim Who
• Trim Date
• Trim Loc
• Trim Desc
• Pres Zero trim
• P UTP
• P LTP
• P UTD
• P LTD
• Pres trim
• Clear P snsr trim
• SP UTP
• SP LTP
• SP UTD
• SP LTD
• Static Pres trim
• Clear SP snsr trim
• D/A trim
• Scaled D/A trim
• Clear D/A trim
3-11
V
• Write Protect
• Write Protect
• Enter new password
F0301-24.ai
IM 01C25T01-06EN
<3. Parameter Setting>
3-12
3.2 Basic Setup
IMPORTANT
After setting and sending data with the HART
conguration tool, wait 30 seconds before
turning off the transmitter. If it is turned off
too soon, the settings will not be stored in the
transmitter.
3.2.1 Tag and Device Information
If there are specied when ordering, the desired Tag
No. and device information are set and shipped.
Tag No. and device information can be checked as
follows.
• Procedure to call up the display using by DD
and DTM (excluding EJX HART 5 DTM based
on FDT1.2)
• Procedure to call up the display by EJX HART 5
DTM based on FDT1.2
ItemProcedure
TagEasy Setup → Tag
DescriptorConguration → Device information 1
MessageConguration → Device information 1
DateConguration → Device information 1
When the Tag No. and device information are
changed, input them based on the following
limitations.
[Root Menu] → Basic setup → Long
Tag
information → Descriptor
information → Message
information → Date
or Conguration → HART → Tag
→ Descriptor
→ Message
→ Date
ItemLimitations
TagUp to 8 characters or numbers*
Long tag
(HART 7 only)
DescriptorUp to 16 characters or numbers*
MessageUp to 32 characters or numbers*
Datemm/dd/yyyy
*1: The characters bounded by the thick line in the following
table can be used.
*2: All characters in the following table can be used.
SP !"# $ % &'()*+,-./
0123 456 78 9:;< => ?
@A B C D E F G HIJK L M N O
PQ R S T U V W X Y Z[\]^_
`a bcdefghijklm no
pqrstuv w xyz{|}~
*: SP shows one-byte space
Up to 32 characters or numbers*
- mm: month (2 digits)
- dd: days (2 digits)
- yyyy: years (4 digits)
1
2
1
1
3.2.2 Unit
The unit parameter is set at the factory before
shipment if specied at the time of order. Follow the
procedure below to change the unit parameter.
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
Note that the Yokogawa default setting for the
standard temperature is 4°C (39.2°F). For the units
of mmH2O, inH2O, and ftH2O, the pressure varies
according to the standard temperature denition.
Select the appropriate unit with @68degF when a
standard temperature of 20°C (68°F) is required.
Available pressure units are shown below.
inH2O@68degF
inHg
ftH2O@68degF
mmH2O@68degF
mmHg
psi
bar
[Root Menu] → Basic setup →
Unit
Easy Setup → Unit or
Conguration → Analog Output
→ Unit
mbar
g/cm
kg/cm
Pa
kPa
torr
atm
2
2
MPa
inH2O
mmH2O
ftH2O
hPa
IM 01C25T01-06EN
<3. Parameter Setting>
3-13
3.2.3 Range Change
The range values are factory-set as specied by
the customer. To change the range, follow the steps
below.
(1) Keypad input — LRV and URV
The measurement span is determined by the upper
and lower range values. In this method, the upper
and lower range values can be set independently,
and the span changes according to the range limit
values sent to the transmitter.
The measurement span is determined by the upper
and lower range values. Changing the lower range
value causes the upper range value to change
automatically, keeping the span constant. If a
change in the lower range value causes the upper
range value to exceed the measuring limit of the
transmitter, an error message appears and the
transmitter holds the output signal right before the
error occurred. Enter the correct values within the
range of the sensor limits.
Note that changing the upper range value does
not cause the lower range value to change. Thus,
changing the upper range value also changes the
span.
3.2.4 Output Mode
The mode setting for the output signal and the
integral indicator can be performed independently.
The output mode for the output signal is set as
specied in the order when the instrument is
shipped. Follow the procedure below to change the
mode.
The calibration range can be set as LRV > URV
under the following conditions, reversing the 4
to 20 mA output signal. When using the integral
indicator, change the user set scale values
accordingly.
This feature allows the lower and upper range
values to be setup automatically with the actual
input applied. If the upper and lower range values
are set, URV and LRV are changed at the same
time.
The damping time constant is set as specied in
the order when the instrument is shipped. Follow
the procedure below to change the damping
time constant. The damping time constant for the
amplier assembly can be set here. The damping
time constant for the entire transmitter is the sum
of the values for the amplier assembly and the
capsule assembly.
Any number from 0.00 to 100.00 can be set for the
damping time constant. Note that setting the quick
response parameter ON enables you to set the time
constant between 0.00 and 0.49 seconds.
• Procedure to call up the Pres Damp display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
[Root Menu] → Basic setup →
Pres Damp
Easy Setup → Pres Damp or
Conguration → Analog Output →
Pres Damp
IM 01C25T01-06EN
<3. Parameter Setting>
3-14
• Procedure to call up the Quick resp display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
→ OffSet from 0.50 to 100.00
→ OnSet from 0.00 to 100.00
Low cut mode can be used to stabilize the output
signal near the zero point.
The low cut point can be set in a range from 0 to
20%, the direct ratio corresponding to the output
signal of 4 to 20 mA. (Hysteresis for the cut point:
±10% of the cut point)
Either “Linear” or “Zero” can be selected as the low
cut mode. Unless otherwise specied, the cut mode
is set to “Linear” at the factory.
The default value of Low cut is set according to the
combination of the Output mode (Xfer fnctn) and
Integral indicator display mode (Disp Pres % fnctn).
See below table.
Example: Low cut at 20%
(%)
50
Output
20
0
Input
For low cut in linear mode
50
(%)
(%)
50
Output
20
0
Input
For low cut in zero mode
F0302.ai
50
(%)
Figure 3.1 Low Cut Mode
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
→ Low cutSet from 0 to 20% of output
→ Low cut modeSelect “Linear” or “Zero”
[Root Menu] → Basic setup →
Easy Setup → or Conguration →
Analog Output →
The low cut point has hysteresis so that the output
around the point is behaved as below gure.
Relationship of default value of Low cut and
Low cut point
Combination of
output mode and
display mode
#
Output
mode
Display
mode
Default
value of
Low cut
1)LinearLinear10%10% / 10%
2) Sq Root Sq Root10%10% / 10%
3)LinearSq Root1%*1% / 10%
4) Sq RootLinear10%10% / NA
*: It is applied for software revision 2.02 or later. For
In the case 3) above, Low cut point for the display is
(Example: Low cut value; 2%, Low cut point; 14%)
previous software version, it is set in 10%.
square root of Low cut value.
Low cut
point for
the output
signal/
display
Note that when the output modes of the output
signal and the display are selected as “Sq root”
and “Linear” accordingly, the low cut function is not
available for the display value.
<Example>
Output mode: Linear
Low cut mode: Zero
Low cut: 20.00%
OutputLow cut point
7.2mA
(20%)
4mA
Setting range: 0 to 20%
Input
2%2%
Hysteresis
fixed at 10%
of the cut point
F0303.ai
3.2.7 Impulse Line Connection Orientation
Setup
This function reverses the impulse line orientation.
Follow the procedure below to assign the high
pressure impulse line connection to the L side of the
transmitter.
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
→ H/L SwapSelect “Normal” or “Reverse”
[Root Menu] → Basic setup →
Conguration → Pressure Sensor
→
IM 01C25T01-06EN
<3. Parameter Setting>
3-15
3.2.8 Static Pressure Setup
The differential pressure transmitter can display the
static pressure also.
(1) Setting of the unit for static pressure
Follow the procedure below to change the static
pressure unit.
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
→ SP UnitSelect the unit for static pressure
(2) Setting of the measuring range for static
pressure
Follow the procedure below to change the lower
range value (LRV) and upper range value (URV).
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
→ SP LRVSet the lower range value (0 %) of
→ SP URVSet the upper range value (100 %)
(3) Selection of Gauge pressure and Absolute
pressure
Either the gauge pressure or absolute pressure can
be selected to display on the LCD display.
[Root Menu] → Basic setup →
SP setup →
Conguration → Process Input (or
Static Pressure Sensor) →
Output signal adjustable range at normal operating
condition are set as shown below at the factory
when the instrument is shipped, and output signal
are limited by these value.
Lower limitUpper limit
Standard
Option code /C1
Option code /C2 and /C33.8 mA20.5 mA
Output signal range can be changed between
3.6mA and 21.6mA to match it to the equipment on
the receiving side.
Lower value is set at AO lower limit and upper
value is set at AO upper limit respectively.
Follow the procedure below to change the upper
and lower values.
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
→ AO lower limitSet the lower value (mA)
→ AO upper limitSet the upper value (mA)
Set the values as below.
Lower value < Upper value
3.6 mA21.6 mA
3.3.4 Integral Indicator Scale Setup
The following ve displays are available for integral
indicators: input pressure, % of range, user set
scale, input static pressure*1, and % of static
pressure range*1. A cycle of up to four displays can
be shown by assigning variables to the parameters
at Disp select.
Available displays
Input pressure
(PRES)
% of range
(PRES %)
User set scale
(ENGR. PRES)
Indicates values of input pressure
with the indication limits –99999 to
99999.
PRES 456 kPa
Indicates input pressure in
110% range depending on the
set range (LRV and URV).
PRES % 45.6 %
Indicates values depending on the
engineering range (Engr LRV and
Engr URV) with the unit (Engr Unit).
Engr LRV 0.0
Engr URV 45.0
Engr exp ×100
Engr Unit m3/min
Engr point 1
Description
and related parameters
–
2.5 to
3.3.3 Integral Indicator Display Mode
The mode setting for the output signal and the
integral indicator can be performed independently.
The output mode for the integral indicator is set
as specied in the order when the instrument is
shipped. Follow the procedure below to change the
mode.
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
→ Disp Pres % fnctn Select “Linear” or “Sq root”
If the instrument is equipped with an integral
indicator and the transfer function is sq root, “” is
displayed on the integral indicator.
Set Disp Out 2, Disp Out 3 and Disp Out 4 in the
same way if necessary.
In addition to the above item, “Not used” is also
displayed as a selection item.
b. Cyclic Display
Up to four displays can be displayed cyclically in the
order of the parameter number.
c. Display Resolution
User can change the position of decimal point
which is shown on the integral indicator.
Select the decimal point position of
pressure
Normal: Display one digit below
the decimal point
High Resolution: Display two digits
below the decimal point
• Procedure to call up the display for Pres and SP
Select the decimal point position
of differential pressure (0, 1, 2,
3 or 4)
Select the decimal point position
of static pressure (0, 1, 2, 3 or 4)
d. User Setting of Engineering Unit and Scale
Setting by DD and DTM (EJX HART 5 DTM
based on FDT1.2)
Engr disp range parameters allow the engineering
unit and scale to be displayed. At Set Engr Unit,
the following engineering units can be selected from
a list.
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
→ Set Engr UnitSelect the engineering unit
→ Engr LRVLower range value
→ Engr URVUpper range value
→ Engr expExponents for user scale display
→ Engr pointDecimal point position for user scale
Nl/min
Nm3/h
Nm3/min
ACFH
ACFM
SCFH
SCFM
GPH
GPM
m
mm
in
ft
3
kg/m
3
g/cm
At Modify Engr Unit parameter, user can set your
own unit also.
Up to eight alphanumeric characters, spaces or one
slashe (/) can be input at Modify Engr Unit; only
the rst six are displayed on the integral indicator.
The integral indicator shows “-- -- -- -- -- --” when
these symbols or more than two slashes are
entered.
IM 01C25T01-06EN
<3. Parameter Setting>
3-18
Setting by EJX HART 5 DTM based on
FDT1.2
User can input the desired unit at Engr Unit.
• Procedure to call up the display
EJX HART 5 DTM
based on FDT1.2
→ Engr UnitSet the engineering unit
→ Engr LRVLower range value
→ Engr URVUpper range value
→ Engr expExponents for user scale display
→ Engr pointDecimal point position for user
Conguration →Local Display →
scale display
Available characters and symbols for Engr Unit are
the same as for Modify Engr Unit shown above.
3.3.5 Unit for Displayed Temperature
When the instrument is shipped, the temperature
units are set to “deg C” (Centigrade). Follow the
procedure below to change this setting.
When this parameter is set, it also changes the
temperature unit for Snsr temp at Process variables and Amp temp at Temp sensor.
The transmitter is factory characterized. Factory
characterization is the process of comparing a
known pressure input with the output of each
transmitter sensor module over the entire pressure
and temperature operating range. During the
characterization process, this comparison
information is stored in the transmitter EEPROM. In
operation, the transmitter uses this factory-stored
curve to produce a process variable output (PV), in
engineering units, dependent on the pressure input.
The sensor trim procedure allows you to adjust
for local conditions, changing how the transmitter
calculates process variables. There are two ways
to trim the sensor: a zero trim and a full sensor trim.
A zero trim is a one-point adjustment typically used
to compensate for mounting position effects or
zero shifts caused by static pressure. A full sensor
trim is a two-point process, in which two accurate
end-point pressures are applied (equal to or greater
than the range values), and all output is linearized
between them.
(1) Zero Trim
a. Zeroing—Pres Zero trim
Pres Zero trim carries out the zero adjustment and
automatically sets the applied “0” input values to the
output value of “0”, keeping the span constant. Use
this setting when the LRV is known to be 0 mmH2O.
This zero adjustment calibrates the transmitter
output corresponding to the actual tank level. To
perform this adjustment, rst use a glass gauge
or the like to determine the actual tank level, then
enter the correct data as shown below.
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
→ Auto, Lower PtAuto trim for 0% point
DPharp span: 0 to 25.00 kPa
Actual level: 13.50 kPa
Transmitter output: 13.83 kPa
DPharp
[Root Menu] → Diag/Service →
Calibration → Pres Sensor trim
→ Pres trim →
Calibration → Pres trim →
25.00 kPa
Actual level
13.50 kPa
0.00 kPa
F0306.ai
c. Using External Zero-adjustment Screw
This method permits zero adjustment without
the HART conguration tool. Use a slotted
screwdriver to turn the zero-adjustment screw.
See the hardware manual for details.
Note that the parameter of Ext SW must be
“Enabled” to perform this adjustment. See
section 3.3.8 for the setting procedure.
IM 01C25T01-06EN
<3. Parameter Setting>
3-19
(2) Full Sensor Trim—Auto Trim and Manual
Trim
Full sensor trim is carried out by performing Auto,
Lower Pt followed by Auto, Upper Pt.
Also, you can manually perform the trimming
procedure with Manual, Lower Pt and Manual, Upper Pt.
The full sensor trim is a two-point adjustment,
and the lower point adjustment should always be
performed before the upper point adjustment in
order to maintain the pitch between the zero and
100% points within the calibration range.
In the manual method, the reference pressure
should also be applied to the transmitter at both
the lower and upper points. Without the reference
pressure, Manual, Lower Pt and Manual, Upper Pt may not represent the correct value for each
adjustment point.
a. Auto Sensor Trim
Applying reference pressure of 0% and 100% of the
measurement range to the transmitter, adjust the
lower and upper points automatically.
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
→ Auto, Lower PtAuto trim for 0% point
→ Auto, Upper PtAuto trim for 100% point
[Root Menu] → Diag/Service →
Calibration → Pres sensor trim →
Pres trim →
Calibration → Pres trim →
b. Manual Sensor Trim
Using the example below, follow the steps to
perform the full sensor trim by manually. The Pres
LTD (Manual, Lower Pt) and Pres UTD (Manual,
Upper Pt) represent the previously adjusted values.
Example: For the range of 1000 to 3000 mmH2O
Pres LTD (Manual, Lower Pt) = −4.0 mmH2O
Pres UTD (Manual, Upper Pt) = −3.0 mmH2O
<1> Call up the Manual, Lower Pt.
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
→ Manual, Lower Pt Manual trim for 0% point
→ Manual, Upper Pt Manual trim for 100% point
[Root Menu] → Diag/Service →
Calibration → Pres sensor trim
→ Pres trim →
Calibration → Pres trim →
<2> Suppose that a standard pressure of 1000
mmH2O is applied and the value of the “Pres
for trim” is 994.0. Correct for this output error
of 6 mmH2O by adding 6 mmH2O to Pres LTD (Manual, Lower Pt).
−4.0+6.0=+2.0
<3> Enter the correction value of “2” to the Pres
LTD (Manual, Lower Pt).
<4> Call up the Pres UTD (Manual, Upper Pt).
<5> Suppose that a standard pressure of 3000
mmH2O is applied and the value of the Pres for
trim is 3015.0. Firstly, obtain the slope error for
the span as follows;
Slope Error = ×(URV−LRV)
Applied Pressure Value−Value of Pres for Trim
= × (3000−1000) = −10
Applied Pressure Value
3000−3015
3000
Then correct for this slope error of −10 by
adding −10 to Pres UTD (Manual, Upper Pt).
−3.0+(−10.0)=−13.0
<6> Enter the correction value of “−13” to the Pres
UTD (Manual, Upper Pt).
(3) Sensor Trim for Static Pressure
For the transmitter, full sensor trim of the static
pressure is performed in the same way as with the
differential pressure.
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
→ Auto, Lower PtAuto trim for 0% point
→ Auto, Upper PtAuto trim for 100% point
→ Manual, Lower PtManual trim for 0% point
→ Manual, Upper PtManual trim for 100% point
[Root Menu] → Diag/Service
→ Calibration → SP sensor
trim → Static Pres trim →
Calibration → Static Pres trim
→
(4) Reset Trim Adjistment to Factory Setting
The Clear P snsr trim and Clear SP snsr trim
commands can reset the trim adjustment to the
initial calibrated values that were set. The amount of
the adjustment performed with the external zeroadjustment screw is returned to the initial setting as
well.
IM 01C25T01-06EN
<3. Parameter Setting>
3-20
• Procedure to call up the display for pressure
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
[Root Menu] → Diag/Service →
Calibration → Pres sensor trim →
Pres trim info. → Clear P snsr trim
Calibration → Clear P snsr trim
• Procedure to call up the display for static
pressure
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
[Root Menu] → Diag/Service →
Calibration → SP sensor trim →
SP trim info. → Clear SP snsr trim
Calibration → Clear SP snsr trim
3.3.7 Trim Analog Output
Fine current output adjustment is carried out with
D/A trim or Scaled D/A trim.
(1) D/A Trim
D/A trim is to be carried out if the calibration digital
ammeter does not exactly read 4.000 mA and
20.000 mA with an output signal of 0% and 100%.
• Procedure to call up the D/A trim display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
(2) Scaled D/A Trim
Scaled D/A trim is to be carried out if the output is
adjusted using a voltmeter or a meter whose scale
is 0 to 100%.
[Root Menu] → Diag/Service →
Calibration
→ Analog output trim → D/A trim
Calibration → D/A trim
<Example>
Adjustment using a volt meter. (4mA → 1V, 20mA
→ 5V)
1) Select “Change”.
2) Enter the value read on the voltmeter when the out-
put signal is 4mA.
In this case, enter the value of the voltage across a
250Ω resistor (1V).
3) Enter the value read on the meter when the output
signal is 20mA (5V).
4) Select “Proceed”.
5) Connect the voltmeter.
6) Output the 0% output signal and read the output
value.
7) Enter the reading of the voltmeter to the conguration
tool. (The output of the transmitter changes).
8) Conrm the voltmeter reading is 1.000.
9) If the reading on the voltmeter is 1.000, select “Yes”.
If the reading is not 1.000, select “No” and repeat
steps 6 and 7 until the voltmeter reads 1.000V.
10) Output the 100% output signal and read the output
value.
11) Enter the reading of the voltmeter.
12) Conrm the voltmeter reading is 5.000.
13) If the reading of the voltmeter is 5.000, select “Yes”.
If the reading on the voltmeter is not 5.000, select
“No” and repeat steps 10 and 11 until the voltmeter
reads 5.000V.
• Procedure to call up the Scaled D/A trim
display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
[Root Menu] → Diag/Service →
Calibration
→ Analog output trim →Scaled
D/A trim
Calibration → Scaled D/A trim
3.3.8 External Switch Mode
Follow the procedure below to enable or inhibit zero
point adjustment by means of the zero-adjustment
screw on the transmitter.
This is set to “Enabled” when the instrument is
shipped.
To change the mode, follow the procedure below.
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
EnabledEnable the external zero point
DisabledDisable the external zero point
[Root Menu] → Detailed setup →
Device information → Field device
info → Ext SW
Conguration → Device
information1 → Ext SW
adjustment
adjustment
IM 01C25T01-06EN
<3. Parameter Setting>
3-21
3.3.9 CPU Failure Burnout Direction and
Hardware Write Protect
There are two slide switches on the CPU assembly
board. One sets the burnout direction at CPU
failure, and the other sets a write protection function
which disables parameter changes through
the use of a handheld terminal or some other
communication method.
CPU assembly
Burnout direction switch
BO HL
WR ED
Slide switch
Write protection switch
Burnout direction switch (BO)
Burnout Direction
Switch Position
Burnout Direction
Hardware write protection switch (WR)
Write Protection
Switch Position
Write Protection
The parameter of AO alm typ parameter displays
the status of 4-20 mA DC output if a CPU failure
occurs. In case of a failure, communication is
disabled.
Standard specications or with option code /C3
The burnout direction switch is set to “HIGH”. If a
failure occurs, the transmitter outputs a 110% or
higher signal.
With option code /C1 or /C2
The burnout direction switch is set to “LOW”. If a
failure occurs, a –5% or lower output is generated.
To conrm the burnout direction at the CPU failure,
follow the procedure below.
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
HighBurnout direction is set to High
LowBurnout direction is set to Low
HLHL
HIGHLOW
HL
ED
NO
(Write enabled)
[Root Menu] → Detailed setup
→Output condition → Analog
output → AO alm typ
Conguration → Analog output →
AO alm typ
HL
ED
YES
(Write disabled)
F0307.ai
3.3.10 Software Write Protection
The transmitter congured data is saved by using a
write protection function. The write protection status
is set to “Yes” when 8 alphanumeric characters are
entered in the New password eld and transferred
to the transmitter.
When write protection is set to ”Yes,” the transmitter
does not accept parameter changes. When the
same eight alphanumeric string entered in the New
password eld is also entered in the Enable wrt
10min eld and transferred to the transmitter, it
will be possible to change transmitter parameters
during a 10 minute period.
To change the transmitter from the write protection
”Yes” status back to write protection ”No” status,
use Enable wrt 10min to rst release the write
protection function and then enter eight spaces in
the New password eld.
• Procedure to call up the display using by DD
and DTM (excluding EJX HART 5 DTM based
on FDT1.2)
DD and DTM
(excluding EJX_
HART 5[1.2])
→ Write protectDisplay current protect mode
→ Enable wrt 10
min
→ New passwordSet the new password or change
• Procedure to call up the display by EJX HART 5
DTM based on FDT1.2
EJX HART 5
DTM based on
FDT1.2
→ Write Protect Display current protect mode
→ Enter new
password
→ Enable write Enter the password here to release
[Root Menu] → Detailed setup
→ Device information → Field
device info → Wrt protect menu
→
(Yes: protected, No: not
protected)
Release the protect function for
10 min.
the password
Write Protect →
(Yes: protected, No: not protected)
Enter the password here to enable
the protect function.
Enter eight spaces to disable the
protect function.
the protect function for 10 min.
IM 01C25T01-06EN
<3. Parameter Setting>
3-22
3.3.11 Signal Characterizer
This function is used to compensate the output
for non-linear applications. The characterized
values are applied to the 4-20 mA output. For
the measured pressure, a maximum of nine
coordinates can be specied between 0-100%.
Perform the coordinate settings while the S.C. at S.C. menu parameter is “Disabled”.
To apply the settings to the output, set the S.C.
parameter to “Enabled”.
Note that the transmitter rejects the activation of the
function by AL. 60 with the following transmitter’s
status:
• When the specied coordinates of x and y are
not incremental as the input increases.
• When the output mode of the output signal is
set as “Sq root”; at the same time, the low cut
mode is set to “Linear”.
Y
100%
<3> Apply the settings
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
→ S.C.Select “Enabled” or “Disabled”
[Root Menu] → Detailed setup →
Signal condition → S.C. menu →
Conguration → Signal
Characterizer Menu →
3.3.12 Alarm
The function is used to display the alarm codes
when the input pressure exceeds the specied
value within the calibration range. The same is
available for the input static pressure and the
capsule temperature on the pressure sensor.
Refer to table 4.5 Alarm Message Summary for the
specic alarm code to be generated.
(1) Alarm Setting
Select the process variable at Process Alert which
the alarm is set, then set the alert mode for that
value.
INPUT
Input pressure in %Characterized value
100%0%
X
OUTPUT
F0308.ai
Follow the steps below to perform the signal
characterizer.
<1> Set the desired number of coordinates on the
line graph
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
→ Num of pointsSet the number between 0 and 9
[Root Menu] → Detailed setup →
Signal condition → S.C. menu →
Conguration → Signal
Characterizer Menu →
<2> Set the coordinates
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
→ Point settingSet the coordinates (X-axis,
[Root Menu] → Detailed setup →
Signal condition → S.C. menu →
When option code /DG6 is specied, Diag can
be also assigned to Status. The Hi Alert Val or
Lo Alert Val for Diag is dened by the following
parameters.
[Impulse Line Blockage Detection]
Limit meters to detect the blockage and
Condition error for ILBD operation is dened.
Refer to 4.2.2.1.
[Heat Trace Monitoring]
Flg temp Hi Alert Val and Flg temp Lo Alert
Val parameters are used as the upper and
This feature is used for a transistor output (open
collector) of an on/off signal according to the
status of high and low alarm limits, which are
user-congurable values as shown in subsection
3.3.12 Alarm. The status output can be assigned
as any combination of the high or low limits of the
• Procedure to call up the display by EJX HART 5
DTM based on FDT1.2
EJX HART 5 DTM
based on FDT1.2
→ Hi Alert ValSet the threshold value of upper
→ Lo Alert ValSet the threshold value of lower
→ SP Hi Alert ValSet the threshold value of upper
→ SP Lo Alert ValSet the threshold value of lower
→ Temp Hi Alert ValSet the threshold value of upper
→ Temp Lo Alert ValSet the threshold value of lower
Conguration → Process Alerts
→
side for pressure
side for pressure
side for static pressure
side for static pressure
side for capsule temperature
side for capsule temperature
input pressure, input static pressure, or capsule
temperature.
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5
[1.2] DTM
Display ItemContents (Select a output variable
Off–
PresDifferential pressure
SPStatic pressure
TempTemperature
Pres/SPPressure and static pressure
Pres/TempPressure and temperature
SP/TempStatic pressure and temperature
Pres/SP/TempPressure, static pressure and
Diag AlarmAlarm for advanced diagnostics
AllAlarm for pressure, static pressure,
[Root Menu] → Detailed setup
→Output condition → Process
Alerts → DO cong → DO Select
Conguration → Process Alerts →
DO Select
from the list below)
temperature
(Refer to subsection 4.2.2.5)
temperature, and advanced
diagnostics
3-23
IM 01C25T01-06EN
<3. Parameter Setting>
3-24
NOTE
No status output signal has been dened for a
CPU failure or hardware error. Use a 4-20 mA
signal to indicate a transmitter’s failure.
Example: Status output operation of ON
WHEN AL. DETECT
Status output for higher alert value
Output
(%)
On
Status output
OnOff
Status output for lower alert value
Output
(%)
On
Status output
*: 5% of setting span for differential pressure / pressure
Figure 3.2 Status Output
On
(2) Selecting of output signal
Status output can be selected for the contact
output.
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5
[1.2] DTM
ON WHEN AL.
DETECT
OFF WHEN AL.
DETECT
[Root Menu] → Detailed setup
→Output condition → Process Alerts
→ DO cong → DO Signal type
Conguration → Process Alerts →
DO Signal type
Output is “ON” when alert is detected
Output is “OFF” when alert is
detected
5%* of hysteresis
Setting
Time (t)
Setting
5%* of hysteresis
Time (t)
Off
value
value
F0309.ai
CAUTION
Whenever turning on the transmitter or detecting
the short interruption, check if contact output
correctly reects the alarm status and test
the ON/OFF action of contact output by the
parameter DO test to conrm that the contact
output operates correctly.
3.3.14 Capillary Fill Fluid Density
Compensation
For transmitters with diaphragm seals, this function
is used to compensate the zero shift caused by the
ambient temperature effect on the capillary tubes.
The following equation indicates the relationship
between the calculated output value and the
compensating constant K (%/°C) with the measured
ambient temperature at the capsule module.
Compensated output = output + K × Temp
(1) Temperature Compensation Mode Setup
When using this function, set T.Z. Cmp mode
to “On” to enable or “Off” to disable. To set to “On”, follow the procedure below.
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
→ T.Z. Comp modeSelect “On” or “Off”
Select “On” at the T.Z. Cmp mode display
(2) Zero Shift Compensation Setup
Obtain the K compensating value from the
equation (a) below, and enter the value to Temp Zero.
– h×B
K= ×100.............. (a)
Span
where,
B: Constant value of ll uid (See Table A.)
Span: |URV – LRV|
h: Distance from high pressure side to low
pressure side (m)
EJX118A/EJA118E: Distance from high side
of diaphragm seal to low side of diaphragm
seal.
[Root Menu] → Detailed setup
→ Signal condition → T.Z.
Comp menu →
Conguration → Pressure
Sensor →
EJX438A/EJA438E: Distance from
diaphragm seal (high side) to position of
transmitter (low side).
IM 01C25T01-06EN
<3. Parameter Setting>
3-25
● EJX118A/EJA118E
L
h
(+)
Transmitter
● EJX438A/EJA438E
Transmitter
Transmitter
Note: When the transmitter is positioned lower than the
diaphragm seal part, the value of “h” must have a
negative sign (–).
Example: Enter K value obtained from the equation (a).
A value haivng up to 3 decimal places may be
specied.
When h=+3 m, Fill uid code A, span=15 kPa,
K=−(+3)×0.00745÷15×100=−0.149
0
H
L
L
(+)
(–)
h
0
H
h
F0310.ai
3.3.15 Test Output, Simulation, and Squawk
NOTE
Fixed current output, DO Test, and Device
Variable Simulation Function continue for a given
holding time, then is released automatically.
Even if the HART conguration tool power
supply is turned off or the communication cable
is disconnected, the test output will continue for
that time.
The holding time can be selected from 10 min*,
30 min, 60 min, 3 hour, 6 hour or 12 hour.
*: Default value.
• Procedure to call up the display
DD [Root Menu] → Diag/Service →
DTM (excluding
EJX_HART 5
[1.2])
EJX_HART 5[1.2]
DTM
(1) Fixed current output
Test Auto Release Time
[Root Menu] → Diag/Service →
Test → Test Auto Release Time
Diag and Service → Service
→ Test Auto Release Time
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
→ Temp ZeroSet the compensation value
[Root Menu] → Detailed setup
→ Signal condition → T.Z.
Comp menu →
Conguration → Pressure
Sensor →
Input “-0.149” to Temp Zero prameter.
Note 1: The function is performed using a built-in temperature
Note 2: When the span changes, reenter the newly obtained
Table A. Constant value [B] of ll uid
sensor in the transmitter body. The temperature
deviation between the transmitter body and capillaries
should be minimized to achieve optimal performance
of the function.
This feature can be used to output a xed current
for loop checks. The available range for test output
depend on the settings for the AO lower limit and AO upper limit parameters, whose limit is from
3.6mA (-2.5%) to 21.6mA (110%).
Refer to the subsection 3.3.2 about the setting of
AO lower limit and AO upper limit.
While this function works, “TEST” is displayed on
the integral indicator.
Setting by DD and DTM (EJX HART 5 DTM
based on FDT1.2)
Call up the test output parameter (Loop test) and
select the output signal.
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
Display ItemContents
4mAOutput a 4mA DC signal
20mAOutput a 20mA DC signal
OtherSet a desired output signal value
EndExit
[Root Menu] → Diag/Service →
Test (DTM only) → Loop test →
Note 3: Select the unit of constant value of [B] from the actual
unit used for the transmitter in operation.
IM 01C25T01-06EN
<3. Parameter Setting>
3-26
Setting by EJX HART 5 DTM based on
FDT1.2
Call up the test output parameter (Loop test) and
select either manual test or auto test, and set the
current value.
• Procedure to call up the display
EJX HART 5
DTM based on
FDT1.2
Display ItemContents
Manual TestSet the current value or % value at
Auto TestSet the interval and rate of change
(2) DO Test (only for EJX series)
Diag and Service → Service
→ Loop test →
Test output value, then click the
Start button.
of current output at Auto Test Setting, then click the Start button.
EJX
This function performs the contact output test.
(option code: /AL)
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
Display ItemContents
OffContact output: OFF
OnContact output: ON
ExitOutput test is canceled
[Root Menu] → Detailed setup
→Output condition → Process
Alerts → DO cong → DO Test →
Diag and Service → Service → DO
test →
(3) Device Variable Simulation Function
(Effective only when setting to HART 7)
HART 7
Using the simulation function, the output signal can
be conrmed by setting any value and status to the
selected device variable.
Call up the parameter and follow the message
shown.
After completing the step 5, the simulation starts.
Integral indicator shows output value and alarm
(AL.91) alternately.
• Procedure of device variable simulation
Step 1 Call up the
parameter
2Selection of
Device Variable
3Setting of ValueInput the simulate value
4Setting of Data
quality
5Setting of Limit
status
[Root Menu] → Diag/
Service → Test (DTM)/Test
device (DD) → Simulate
Select one parameter from
the list below
Off
PV
SV
TV
Percent Range
Loop Current
Select one parameter from
the list below
Bad
Poor accuracy
Manual / Fixed
Good
Select one parameter from
the list below
Not limited
Low limited
High limited
Constant
NOTE
• All the simulations for pressure, static
pressure, and capsule temperature are
reected to the output. Accordingly, the loop
current, LCD display, and communication
output are directly corresponded to the
simulate value.
The alarm output is also available according
to the simulate value.
• Damping is applicable for pressure,
static pressure, and capsule temperature
simulation.
(4) Squawk (Effective only when setting to
HART 7)
This feature can be used to identify the
communicating transmitter by remotely causing
LCD to display the particular pattern as shown in
the Figure 3.3.
“SQUAWK” continues for approximately 15
seconds, then is released automatically.
Enter the larger number to “Change number of
squawks to make” in order to prolong the duration
of squawk indication.
HART 7
IM 01C25T01-06EN
<3. Parameter Setting>
S P
3-27
• Procedure to call up the Squawk display
[Root Menu] → Diag/Service → Test (DTM)/Test device
(DD) → Squawk
P
Figure 3.3 LCD display for Squawk
TF
F0311.ai
3.3.16 Burst Mode
3.3.16.1 In the case of using HART 5
HART 5
When the Burst mode is enabled, the transmitter
continuously sends the stored data. The data is
sent approximately three times per second as a
digital signal when the transmitter is set in burst
mode. When data is being sent in burst mode,
other operations can be performed with the HART
conguration tool.
(1) Selection of the transmission data.
Call up the Burst option parameter and select the
data which is transferred.
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
Display ItemContents
PVProcess variable assigned to PV
%range/currentOutput in % and mA
Process vars/crnt Output in mA and process variables
When the Burst mode is enabled, the transmitter
continuously sends up to three data listed in Table
3.1.
Refer to the subsection 3.3.16.2.1 Burst Message
for details.
When the Burst mode is set to “Wired HART
Enabled”, transmitter continuously sends alarm
signal also.
Refer to subsection 3.3.16.2.2 Event Notication for
detail.
When changing the setting of Burst mode, set “Off”
to the Burst mode.
Default setting is “Off”.
3.3.16.2.1 Burst Message and Burst Mode
(1) Burst message
The transmitter can transmit three burst messages
at the maximum.
The parameters for Burst Message are as follows.
• Burst Command
• Update Period and Max Update Period
• Burst Msg Trigger Mode
IM 01C25T01-06EN
<3. Parameter Setting>
Table 3.1 Burst parameters
Command parameterBurst Command
PV
(Pressure • Differential
Pressure)
% range/current
(Percent of range, Loop
current)
Process vars/current
(Loop current, Pressure
• Differential Pressure
• Static Pressure •
Temperature)
Process vars/% range/
current
Mapping by user
Self diagnosis informationCmd48:Read
*1: Output the data with time and status.
Cmd1:PVContinuous------
Cmd2:% range/currentContinuous------
Cmd3:Dyn vars/currentContinuous------
Cmd9:Device vars w/status Continuous------
Additional Device Status
Burst Msg Trigger
Mode
WindowPVDepend on the
Rising
Falling
On-change
Window% range%
Rising
Falling
On-change
WindowPVDepend on the
Rising
Falling
On-change
WindowTop of Burst
Rising
Falling
On-change
Continuous-----On-changeAll status---
Display ItemContents
PVSelect the pressure
SVSelect the static pressure
TVSelect the capsule temperature
% rngeSelect the % output
Loop currentSelect the output current
Not Used–
c. Update period and Max Update Period
Set to Update Period and Max Update Period.
When the period that is earlier than the operation
period of each process value was set, it is set
automatically to become bigger than an operation
period of the transmitter.
For Update Period, set the value that is smaller
than Max Update Period.
• Procedure to call up the display
DD and DTM [Root Menu] → Detailed setup
→Output condition →HART
output → Burst condition → Burst
Message 1,2 or 3 → Set Burst
Period
→ Update Period
/ Max Update
Period
0.5 s
1 s
2 s
4 s
8 s
16 s
32 s
1 min
5 min
10 min
15 min
30 min
45 min
60 min
d. Burst Msg Trigger Mode
Set the Burst Msg Trigger Mode from the
parameters shown below.
When Burst Msg Trigger Mode is Window, Rising
or Falling, set the Burst Trigger Level.
• Procedure to call up the display
DD and DTM [Root Menu] → Detailed setup →
Output condition →HART output →
Burst condition → Burst Message 1,2
or 3 → Set Burst Trigger →
Display ItemContents
ContinuousBurst Message is transmitted
continuously.
WindowIn “Window” mode, the Trigger Value
must be a positive number and is the
symmetric window around the last
communicated value.
RisingIn “Rising” mode, the Burst Message
must be published when the source
value exceeds the threshold
established by the trigger value.
FallingIn “Falling” mode, the Burst Message
must be published when the source
value fall below the threshold
established by the trigger value.
On-changeIn “On-change” mode, the Burst
Message must be published when the
source value on change established
by the trigger value.
IM 01C25T01-06EN
<3. Parameter Setting>
3-31
e. Burst Mode
When the Burst mode is set to “Wired HART
Enabled”, the transmitter starts to send the data.
When a setting change and a change of the Selfdiagnostics occur, device detect it as an event and
can transmit an alarm signal continuously.
Up to four events that occurred can be stored.
When using this function, set to Burst mode as
“Wired HART Enabled”.
Event Notication →
→ Event MaskSet the status to detect
→ Set Event Notication Timing
→ Event
Notication
Retry Time
→ Max Update
Time
→ Event
Debounce
Interval
→ Event
Notication
Control
Set the retry time when the event
occur.
Set the retry time when the event
does not occur.
The setting of the minimum event
duration
Stop the event monitor: Off
Shift to the monitor state: Enable
event notication on token-
passing data link layer
Therefore, the conguration changes to the device
are always detected as an event regardless of the
setting of the Device Status.
b) Event Notication Retry Time/ Max Update
Time/ Event Debounce Interval
Set to Event Notication Retry Time, Max Update
Time and Event Debounce Interval.
For Event Notication Retry Time, set the value
that is smaller than Max Update Time.
Event Notication
Retry Time
/Max Update Time
---Off
0.5 s0.5 s
1 s1 s
2 s2 s
4 s4 s
8 s8 s
16 s16 s
32 s32 s
1 min1 min
5 min5 min
10 min10 min
15 min15 min
30 min30 min
45 min45 min
60 min60 min
Event Debounce Interval
c) Event Notication Control
Select “Enable event notication on token-passing
data link layer” in the Event Notication Control
parameter to shift to the monitor state:
(2) Acknowledge Event Notication
The transmission of the event message stops when
event is approved.
a) Event Mask
Set the status to detect in the Event Mask
parameter.
Device Status Mask
Status group 1 Mask to 10 Mask
Ext dev status Mask
Device Diagnostic Status 0 Mask
Device Diagnostic Status 1 Mask
AO saturated Mask
AO xed Mask
When changing the conguration of the device,
Conguration Changed (0x40) Flag (refer to Table
4.7) of Device Status is set, and Cfg chng count
(refer to subsection 4.1.3 (5)) is also incremented.
Conguration changed ag detection can be
masked by the Device Status Mask, but it is
impossible to mask the Cfg chng count.
Conrm the latest event number.
Execute Acknowledge Event Notication
method.
1) Enter Event Number is set to “0”.
2) OK.
3) Set “Trans 0: Read Event Noticaiton” to
Select Transaction.
4) OK.
5) Conrm Event Number.
b) Conrmation record of Event Notication
Conrm four events checked in a).
Execute Acknowledge Event Notication
method.
1) Enter the event number to Enter Event
Number which is conrmed in a)5.
2) OK.
3) Set “Trans 0: Read Event Noticaiton” to
Select Transaction.
4) OK.
5) Knowledge menu displays events record.
Ex.) When the conrmed event number is 123.
Event NumberExplanation
123The latest event
122An event before the once.
121An event before the twice.
120An event before three times.
3.3.17 Multidrop Mode
3.3.17.1 Setting on HART 5
HART 5
“Multidropping” transmitters refer to the connection
of several transmitters to a single communication
transmission line. Up to 15 transmitters can be
connected when set in the multidrop mode. To
activate multidrop communication, the transmitter
address must be changed to a number from 1 to
15. This change deactivates the 4 to 20 mA analog
output, sending it to 4 mA. The alarm current is also
disabled.
About the procedure to call up the Polling
display, please refer to the User’s Manual of each
conguration tool.
NOTE
When the same polling address is set for
two or more transmitters in multidrop mode,
communication with these transmitters is
disabled.
(3) Communication when set in multidrop
mode.
• The HART conguration tool searches for a
transmitter that is set in multidrop mode when
it is turned on. When the HART conguration
tool is connected to the transmitter, the polling
address and the tag will be displayed.
• Select the desired transmitter. After that, normal
communication to the selected transmitter is
possible. However, the communication speed
will be slow.
To release multidrop mode, call up the Poll addr
display and set the address to “0”.
IM 01C25T01-06EN
<3. Parameter Setting>
3-33
3.3.17.2 Setting on HART 7
HART 7
“Multidropping” transmitters refer to the connection
of several transmitters to a single communication
transmission line. Up to 63 transmitters can be
connected when set in the multidrop mode. To
activate multidrop communication, the transmitter
address must be changed to a number from 1 to 63.
If it sets to multidrop mode, in order to transmit all
the data in digital one, it is necessary to change a
setup of the analog output signal of 4 to 20 mA.
Setting of Multidrop Mode
(1) Polling address
• Procedure to call up the display
DD and DTM[Root Menu] → Detailed setup
→Output condition →HART
output →
→ Poll addrEnter the number from 1 to 63
NOTE
When the same polling address is set for
two or more transmitters in multidrop mode,
communication with these transmitters is
disabled.
(2) Analog Output Signal Setting
Set Disabled to Loop current mode and x
an analog output signal to 4mADC. It becomes
impossible in this case, to also use a burnout
output.
However, in the case of the application which
receives and operates an analog output signal, an
analog output signal can be used for one loop. In
this case, set Enabled to Loop current mode.
• Procedure to call up the display
DD and DTM[Root Menu] → Detailed setup
→Output condition →Analog output
→ Loop current mode →
EnabledLoop current mode is enabled.
DisabledLoop current mode is disabled.
(3) Enabling the Multidrop Mode of
Conguration Tool
(4) Communication when set in multidrop
mode.
• The HART conguration tool searches for a
transmitter that is set in multidrop mode when
it is turned on. When the HART conguration
tool is connected to the transmitter, the polling
address and the tag will be displayed.
• Select the desired transmitter. After that, normal
communication to the selected transmitter is
possible. However, the communication speed
will be slow.
To release multidrop mode, call up the Poll addr
display and set the address to “0”.
Return Loop current mode to Enabled.
3.3.18 Switching HART Protocol Revision
When the output signal code is “-J”, HART protocol
revision of the transmitter can be selectable from 5
or 7.
The HART protocol revision is set and shipped as
specied in the order.
To change the HART protocol revision after
shipment, follow the procedure shown below.
IMPORTANT
When changing the protocol revision, conrm the
items below.
• Protocol revision supported by HART
conguration tool must be the same or
higher than new protocol revision of the
transmitter. (Refer to Table 2.1)
• Conrm that the DD or DTM which is suitable
to new protocol revision of transmitter is
installed in the conguration tool. (Refer to
Section 2.3 or 2.4)
1) Call up the parameter for protocol revision
change
• Procedure to call up the Chg universal rev
display.
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
[Root Menu] → Detailed setup
→ Device information → Field
device info → Revision #’s → Chg
universal rev
Conguration → HART → Chg
universal rev
About the procedure to call up the Polling
display, please refer to the User’s Manual of each
conguration tool.
IM 01C25T01-06EN
<3. Parameter Setting>
3-34
2) Activate the “Chg universal rev” method
IMPORTANT
The message is displayed to separate the
transmitter from the automatic control loop.
Conrm that the transmitter is separated.
3) Input the new revision number
An input column for new protocol revision number is
displayed.
Input the new HART protocol revision number of “5”
for HART 5 or “7” for HART 7.
4) Applying the new protocol revision
a. Close the conguration tool
After completion of Chg universal rev
method, close the HART conguration tool.
NOTE
When using a FieldMate, close the main display
of FieldMate.
b. Conrm the new HART protocol revision
number
Call up the Universal rev parameter, and conrm
that the new HART revision number is displayed.
• Procedure to call up the Universal rev.
parameter.
[Root Menu] → Detailed setup
→ Device information → Field
device info → Revision #’s →
Universal rev →
Conguration → HART →
Universal rev. →
b. Restart the transmitter
Turn off the power to the transmitter, and turn
it on.
IMPORTANT
New protocol revision is applied only after having
performed restart of the transmitter.
NOTE
A new HART revision number is displayed on
the integral indicator for three (3) seconds after
restart the transmitter. (Refer to section 2.1)
5) Conrming the new protocol revision
a. Restart the HART conguration tool
NOTE
When execute the other parameter conrmation
or setting change, execute after restart the
conguration tool.
IM 01C25T01-06EN
<4. Diagnostics>
4. Diagnostics
4-1
4.1 Self-Diagnostics
4.1.1 Identify Problems by Using HART
Conguration Tool
The HART conguration tool can be used to run
self-diagnostics on a transmitter and check for
incorrect data settings.
(1) DD and DTM (excluding EJX HART 5 DTM
based on FDT1.2)
The Self test and Status commands are available
for self-diagnostics. When Self test is run, the
integral indicator shows an error code and alarm
message if the transmitter detects any illegal
parameter settings or functional faults. See Table
4.5 Alarm Message Summary for probable cause
and countermeasures.
• Procedure to call up the Self test display
[Root Menu] → Diag/Service →
Test (DTM)/Test device (DD) → Self test
If no error is detected, “Self test OK” is displayed on
the conguration tool.
If the specic diagnostic item is known for the
check, you can directly call up the item by using the
Status command.
The status is categorized from 1 to 9 for HART 5,
and from 1 to 10 for HART 7.
See Table 4.5 to determine the status group.
Show an example below to conrm the status of
Status group 1.
When an improper operation is performed, the error
message is displayed.
See Table 4.6 HART Conguration Tool Error
Message.
(2) EJX HART 5 DTM based on FDT1.2
The Device Status commands are used for self-
diagnostics. When Device Status is run, the
integral indicator shows an error code and alarm
message if the transmitter detects any illegal
parameter settings or functional faults. See Table
4.5 Alarm Message Summary for probable cause
and countermeasures.
• Procedure to call up the Device Status display
Device Status
If no error is detected, “Status: Normal” is displayed
on the conguration tool.
If the specic diagnostic item is known for the
check, you can directly call up the item by using the
Diagnostic List in the Device Status display.
The Diagnostic List is categorized to Device Status,
Hardware Failure, Transducer Status, Diag Status,
and Conguration.
See Table 4.5 Alarm Message Summary.
If no error is detected, color symbol which shows
Normal State is displayed on top of the error
message.
If color symbol which shows Error State is
displayed, there is an error and a countermeasure
for that error is necessary.
• Procedure to call up the Status display
[Root Menu] → Diag/Service → Test device (DD only)
→ Status → Status group 1
If no error is detected, “Off” is displayed on the
conguration tool.
If there is an error, “On” is displayed on the
conguration tool, and a countermeasure for that
error is necessary.
Example of display: Illegal P LRV On
Illegal P URV Off
Illegal P SPAN Off
P SPAN trim err Off
P ZERO trim err Off
The HART conguration tool diagnoses at each
communication.
The HART conguration tool diagnoses at each
communication.
When an improper operation is performed, the error
message is displayed.
See Table 4.6 HART Conguration Tool Error
Message.
IM 01C25T01-06EN
<4. Diagnostics>
4-2
4.1.2 Checking with Integral Indicator
NOTE
If an error is detected by running self-diagnostics,
an error number is displayed on the integral
indicator. If there is more than one error, the error
number changes at three-second intervals.
See table 4.3.1 regarding the alarm codes.
F0401.ai
Figure 4.1 Integral Indicator
4.1.3 Status information available for
HART 7
Status added to HART 7 is explained below.
(1) Device Status
Device Status indicates the current operating
status of the device. (Refer to Table 4.7)
Table 4.10 indicates the relationship between
alarm and Device Status.
HART 7
(3) Data quality and Limit status
The transmitter can handle PV (Pres), SV (SP),
TV (Snsr temp), % rnge (Percent Range), and
Loop current. Each variable contains data
quality and limit status for providing useful
status about the data value. The data quality
is normally “Good”. However, in the case of a
sensor failure or out of measurement range,
it turns to “Bad” or “Poor Accuracy”. The limit
status indicates whether the data value is
limited (i.e., not responding to the process).
When the limit status is “Constant”, the value
will not be changed. For detail, refer to Table 4.9
and 4.10.
• Procedure to call up the display
[Dynamic Variables]
DD and DTM[Root Menu] → Process variables
→ Device variables and Status →
→ PV (Pres)
Data Quality
→ PV (Pres) Limit
Status
It is the same about the SV (SP) and TV (Temp), %
rnge (Percent Range), and Loop current
Good, Poor Accuracy, Manual/
Fixed, or Bad is displayed.
Constant, Low Limit, High Limit, or
Not Limited is displayed.
(4) Time Stamp
Time Stamp displays the date and the time
information which the transmitter maintains
from the time of the power on.
It is used as the additional information of the
process value and the event.
• Procedure to call up the display
DD and DTM[Root Menu] → Diag/Service → Test
device (DD only) → Status → Device
status
(2) Extended Device Status
Ext dev status contains commonly used
device information. (Refer to Table 4.8)
Table 4.10 indicates the relationship between
alarm and Extended Device Status.
• Procedure to call up the display
DD and DTM[Root Menu] → Diag/Service → Test
device (DD only) → Status → Ext dev
status
• Procedure to call up the display
DD and DTM[Root Menu] → Diag/Service →
Test device (DD only) → Status →
Time Stamp
→ Current DateIt shows the number of operating
days.
→ Current TimeIt shows the running time.
NOTE
Time Stamp is reset when powering on.
IM 01C25T01-06EN
<4. Diagnostics>
4-3
(5) Conguration Change Counter
The Conguration Change Counter is
incremented once for every user action
that changes the device’s conguration or
calibration. This value is never reset or written
and maintained even if power is removed from
the device.
• Procedure to call up the display
DD and DTM[Root Menu] → Diag/Service →
Test device (DD only) → Status →
→ Cfg chng
count
(6) Reset Conguration Changed Flag
Conguration Changed Flag can be reset by
this method.
The conguration change times
are counted. The counted value
cannot be reset.
NOTE
Refer to Conguration Changed (0x40) in the
Table 4.7.
• Procedure to call up the display
DD and DTM[Root Menu] → Diag/Service → Test
device (DD only) → Status → Reset
Cfg Chng ag
4.2.2 Impulse Line Blockage Detection
(ILBD)
ILBD is carried out by using statistical analysis
based on the measured values of process
uctuations that exist in a uid. An alarm on the
transmitter LCD display or an analog alert is
generated if blockage reaches a certain level.
The transmitter provides the following results as
blockage detection.
(1) A Blocking and B Blocking
These are blockage detections based on
the uctuation value change of differential
pressure/pressure. With a differential pressure
transmitter, each result indicates that both or
single side is plugged.
(2) L Side Blocking
It is a low-pressure side blockage detection
based on the change of BlkF or low-pressure-
side uctuation value.
(3) H Side Blocking
It is a high-pressure side blockage detection
based on the change of BlkF or high-pressure-
side uctuation value.
*: BlkF indicates blockage degree characterized
by a comparison of the high- and low-pressureside uctuation values. For the details, refer to
Figure 4.2.2.
4.2 Advanced Diagnostics
(Only for EJX series)
4.2.1 Multi-sensing Process Monitoring
Multi-sensing process monitoring function (option
code: /DG6) provides the advanced diagnostics
to detect the abnormal conditions in process
environment such as an impulse line etc. by using
the EJX multisensing technology and its unique
algorithm. There are following two functions.
Impulse Line Blockage Detection (ILBD)
The uctuation change of differential pressure and
static pressure is monitored by a silicone resonant
sensor and detects a potential blockage condition.
The differential pressure transmitter gives also a
result of which pressure-side was plugged.
Heat Trace Monitoring
The two temperature sensors built in the transmitter
calculate the ange temperature, the change of
which enables to detect the heat trace breakage or
the abnormal temperature due to the failure.
EJX
IMPORTANT
• The pressure uctuation amplitude in uids
must be sufciently large for blockages to be
detected.
• If the pressure uctuation amplitude is too
low for a reference value to be obtained,
blockages detection operation cannot be
performed with an alarm that the reference
value is invalid.
• The pressure uctuation amplitude may
decrease due to other causes unrelated with
a blockage according to process condition. In
above case, a false alarm of an impulse line
blockage may be generated. Before taking
action in response to a blockage alarm,
consider the plant operating conditions.
Notes for Pressure or Level
Measurement
With pressure or level measurement, the pressure
uctuation amplitude may reduce especially for the
following cases.
IM 01C25T01-06EN
<4. Diagnostics>
Pressure Measurement
• Operational pressure is near outside of
diagnostic range.
• Even though pressure is constant, the ow
decreases than that under normal condition.
• A source of pressure uctuation (pump,
compressor, blower, etc.) is shut down. As
a result, the pressure uctuation amplitude
decreases.
Level Measurement
• A transmitter is used to measure tank level and
the ow of uid into or out of the tank comes to
a stop.
• The agitator in the tank is shut down.
• A source of pressure variation (a compressor,
etc.) that controls the internal pressure of a
sealed (closed) tank is shut down.
Before taking action in response to a blockage
alarm, consider the plant operating conditions.
4-4
IM 01C25T01-06EN
<4. Diagnostics>
Functional block diagram
The gure below shows the functional block diagram of ILBD.
Ratio fDP
Ratio fSPl
Ratio fSPh
BlkF, fDP
fSPl, fSPh
Diag Applicable
Diag Error
Response Code
(Device Status)
Status group 8,9
Display on LCD
Figure 4.2 Functional Block Diagram of ILBD
The following outputs are given for the ILBD results.
Table 4.1 List of Outputs for ILBD
#
OUTPUT
Parameter name
Parameters based on the fluctuation value and blockage degree.
[ Diag DPComp: Non-Compensation ]
:
Ratio fDP
[ Diag DPComp: Compensation ]:
fSPl
Ratio fSPl
(1)
Ratio fSPh
BlkF
fDP
fSPI
fSPh
Diag Applicable*
Response Code
(2)
Device Status
(3)
Status group 8, 9
(4)
Diag Error
(5)
Display on LCD
(6)
Analog Output
Digital Output
(7)
*1: Available only for DD and DTM (excluding EJX HART 5 DTM based on FDT1.2).
For EJX HART 5 DTM based on FDT1.2, the color of icon on the Diag Error display changes with the status.
1
Ratio fSPl
Ratio fSPh
Blockage degree characterized in comparison of high-pressure side and low-pressure
side pressure fluctuation value.
Average value of the sum of squares of differential pressure fluctuations.
Average value of the sum of squares of low-pressure side static pressure fluctuation.
Average value of the sum of squares of high-pressure side static pressure fluctuation.
After the reference value is obtained, the applicable blockage defection and the status of
abnormal fluctuation are displayed on this parameter.
When an impulse line blockage is detected, “More Status Avairable” is generated in
Response Code Device Status.
When an impulse line blockage is detected, the result of the blockage detection
(alarm status) is indicated.
When an impulse line blockage is detected, the results of the blockage detection
(alarm status) is indicated.
When impulse line blockage is detected, an alarm status is displayed on LCD.
When impulse line blockage is detected, an alarm status is output on 4 to 20mA.
When impulse line blockage is detected, an alarm status is output on Status output.
=
Ref fSPl
=
Ref fSPh
fSPh
Remarks
Ratio fDP
Ratio fDP
=
=
fDP
Ref fDP
fDP
Ref fDP
Ref DPAvg
×
-------(6)
-------(7)
-------(1)
*1
-------(4)
-------(2)
-------(3)
-------(5)
F0402.ai
DPAvg
F0403.ai
IM 01C25T01-06EN
<4. Diagnostics>
4.2.2.1 Blockage Detection
Limit parameter
When the parameter based on pressure uctuation
exceeds the preset value, EJX diagnoses an
impulse line as blockage and gives an alarm. The
threshold values are set to Limit parameter shown
in below table.
Diag and Service → Advanced Diag
Congurations → Impulse Line
Blockage Detection → Threshold
→ Sensitivity →
Blocking” by using Ratio fDP
Blocking” by using Ratio fDP
Fluct L” by using Ratio fSPl
Blocking” by using Ratio fSPl
Fluct H” by using Ratio fSPh
Blocking” by using Ratio fSPh
Blocking” by using BlkF
Blocking” by using BlkF
range” by using DPAvg and to
detect “Invalid Ref xx” by using
Ref DPAvg
range” by using DPAvg and to
detect “Invalid Ref xx” by using
Ref DPAvg
4-6
Table 4.3 shows the default values at the factory
setting.
NOTE
• When ILBD is performed for the rst time,
use the default value. If the pressure
uctuation amplitude is low or a false alarm
is often generated after ILBD is performed,
change the values of Limit parameters
according to the procedure described in
subsection 4.2.2.10. Tuning
Note 1: The default values are set for level measurement. If EJX118A is applied to ow measurement, enter the same value to Limit
Note 2: It indicates the threshold value for “ILBD over range” (refer to 4.2.2.5).
A/B Blocking Detection
“A Blocking” and “B Blocking” indicates the result
estimated from blockage degree based on the
difference of the high- and low-pressure-side
uctuation values. Ratio fDP, SQRT (fDP / Ref fDP) is used to detect A/B blocking. Ref fDP is the
average value of the sum of squares of differential
pressure uctuations under normal condition.
As the value of Ratio fDP exceeds the value of Lim fDPmax, EJX gives basically an alarm of “A
Blocking”. On the other hand, if this value is below
the value of Lim fDPmin, EJX gives an alarm of “B
parameter [1] to [10] as those of EJX110A.
H/L Blocking Detection
EJX differential pressure transmitter enables
to detect both-, a high-, or low-pressure-side
blockage. The blockage degree characterized
by a comparison of high-pressure side and lowpressure-side uctuation values, BlkF, is used to
detect it. The value changes within a range of –1
to +1. As BlkF approaches +1, the high-pressure-
side blockage progresses. On the other hand, if it
approaches –1, the low-pressure-side blockage
progresses.
1
1
Blocking.
As a high- or low-pressure-side blockage
progresses, fDP increases. Therefore, “A Blocking”
with a differential pressure transmitter indicates
that a single-side impulse line is plugged for a
differential pressure transmitter. As the both-side
blockages progress simultaneously, fDP decreases.
Therefore, “B Blocking” with a differential pressure
transmitter indicates that both-side impulse lines
are plugged.
Threshold
0
Blockage Progress
BlkF
Blockage detection for
high-pressure side
Figure 4.3 Relation between Blockage Progress
and BlkF
Blockage Progress
0
BlkF
Threshold
-1-1
Blockage detection for
low-pressure side
F0404.ai
NOTE
A single-side impulse line blockage may
generate “B blocking” under the condition where
the uctuation amplitude is much different
between high- and low-pressure sides.
The each threshold value to detect the high- or lowpressure-side blockage is set to Lim BlkFmax or Lim BlkFmin.
IM 01C25T01-06EN
<4. Diagnostics>
4-8
L Side Blocking Detection
BlkF is preferentially used to "L Side Blocking"
detection. If BlkF cannot be used, Ratio fSPl,
SQRT (fSPl / Ref fSPl) is used to "L Side Blocking"
detection. Ref fSPl is the average value of the sum
of squares of low-pressure-side static pressure
uctuations under normal condition.
As the value of Ratio fSPl is below the value of Lim fSPlmin, EJX gives an alarm of "L Side Blocking".
On the other hand, if this value exceeds the value of
Lim fSPlmax, EJX gives an alarm of “Large Fluct
L”.
H Side Blocking Detection
BlkF is preferentially used to "H Side Blocking"
detection. If BlkF cannot be used, Ratio fSPh,
SQRT (fSPh / Ref fSPh) is used to "H Side
Blocking" detection. Ref fSPh is the average value
of the sum of squares of high-pressure-side static
pressure uctuations under normal condition.
As the value of Ratio fSPh is below the value
of Lim fSPhmin, EJX gives an alarm of "H Side
Blocking".
4.2.2.2 Combination of Reference Result
and Blockage Detection
Diag Applicable
The transmitter can detect four modes of impulse
line blockage: both-sides, high-pressure side, lowpressure side, and/or single-side and abnormal
uctuation when all the reference values are
properly measured. However, the detectable alarm
mode combination is limited when some of the
reference values are invalid. Available Blockage
Detection are shown in the below gure.
NOTE
• Ref fDP must be larger than the specied
level shown in Table 4.4 (refer to subsection
4.2.2.6). No blockage can be detected when
Ref fDP is not large enough.
• The plausibility of blockage detection needs
to be conrmed by blockage simulation test.
The simulation test can be performed by
the appropriate manifold operation (refer to
subsection 4.2.2.8).
On the other hand, if this value exceeds the value of
Lim fSPhmax, EJX gives an alarm of “Large Fluct
H”.
Large Fluctuation Detection
When a pump or compressor starts, the large
uctuation is generated as process condition
changes rapidly. This phenomenon affects process
uctuation measurement; so correct blockage
detection is not performed.
If “Large Fluct L” or “Large Fluct H” is detected,
consider whether a blockage result is correct.
The threshold values to detect large uctuation are
set to Lim fSPlmax and Lim fSPhmax.
Since these values are enough to detect large
uctuation, it is not almost necessary to change
them.
Diag and Service → Advanced Diag
Congurations → Impulse Line
Blockage Detection → Diag Mode
→
• A Blocking detection
(by using Ratio fDP)
• H Side Blocking detection
(by using Ratio fSPh)
• B Blocking detection
(by using Ratio fDP)
Available Blockage Detection
• B Blocking detection
(by using Ratio fDP)
F0405.ai
Diag Mode
ModeFunction
StopThe blockage detection operation is
stopped.
Calculation The blockage detection operation is
performed.
Alarms are generated along with the
result.
ReferenceReference values for the blockage
detection are obtained and updated to the
latest. After sampling reference values,
this mode changes to "Calculation".
When the blockage detection operation is
performed, set “Calculation” to Diag Mode. “Stop”
must be set when you change a threshold value or
set an alarm. “Reference” is set in order to obtain
the reference uctuation values under the normal
conguration.
IM 01C25T01-06EN
<4. Diagnostics>
AAA
A
If Diag Supp Count is set to three times, an
NOTE
When setting ILBD parameters in the transmitter
via “Online Parameter” of the EJX HART 5
DTM based on FDT1.2 menu, Diag Mode
automatically changes to 0 (Stop). After the
setting, Diag Mode automatically returns to the
original value.
alarm is not generated at part ‘A’ in Figure 4.4.
Because the rst and second values only exceeded
consecutively the threshold.
When the value exceeds consecutively the
threshold value three times, an alarm is generated
(see part ‘B’ in Figure 4.4).
Diag Supp Count (Number of times: 3)
An alarm is generated.
4-10
NOTE
When setting ILBD parameters in the transmitter
via “Download to device” of the EJX HART 5
DTM based on FDT1.2 menu, Diag Mode
automatically changes to 0 (Stop).
Diag Period
The values such as Ratio fDP and BlkF are
averaged based on several hundreds of pressure
uctuation values in constant time. Diag Period
denes the sampling time is. The default value at
the shipment is set to 180 seconds.
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
For the information on how to change the sampling
period, refer to subsection 4.2.2.10.
Diag Supp Count
When the value as Ratio fDP or BlkF exceeds
the threshold value for several times in a row,
it is estimated that the impulse line is plugged.
Diag Supp Count denes the number of times to
estimate blockage detection.
Diag and Service → Advanced Diag
Congurations → Impulse Line
Blockage Detection → Threshold →
Diag Suppress Count →
BBB
Upper Threshold
(Ex.Lim fDPmax)
Diag Period
Time
Diag Period
Diag Supp Count (Number of times: 3)
Figure 4.4 Relationship of Diag Supp Count and
Alarm
Lower Threshold
(Ex.Lim fDPmin)
B
An alarm is generated.
Time
F0406.ai
The number of detection to give an alarm is set for
each blockage detection function. The default value
at the shipment is set to three times.
If uctuating around the threshold value, an alarm
may be often generated. In this case, change the
threshold value (Limit parameter) or the sampling
time (Diag Period) to enhance the accuracy of the
blockage detection. Refer to subsection 4.2.2.10.
IM 01C25T01-06EN
<4. Diagnostics>
F0407.ai
NG
1, 2
7
3
4
5, 6
10
1-1) Alert Setting
• Enable an alert to be generated by
Diag Out Option parameter.
1-2) Alarm Masking
• Select the alarm status to display on
LCD or to give an alert by Diag Option parameter.
2-1) Check Stability of pressure
• Check the stability of Pres value.
2-2) Check Fluctuation Values
• Check whether the fluctuation values
are available for ILBD.
3-1) Obtain Reference Values
• Obtain a reference fluctuation value of
differential pressure/pressure and
static pressure under normal condition.
3-2)
Check Detection
Capability
• Simulate the blockage detection
operation with a three-valve
manifold or stop valve.
Tuning
• Change the threshold value by
Limit parameter.
• Change the sampling time by
Diag Period parameter.
Reset Reference Values
• Reset a reference fluctuation
value of differential
pressure/pressure according to
process condition.
4) Perform ILBD algorithm
Refer to subsection 4.2.2.11
Refer to
subsection 4.2.2.10
Process condition is
changed by a
comparison of the
condition when the
reference values were
obtained.
Blockage Detection
Alarm is generated.
Refer to
subsection 4.2.2.9
Spurious alarm detection.
Refer to subsection 4.2.2.8
Refer to subsection 4.2.2.7
Refer to subsection 4.2.2.6
Refer to subsection 4.2.2.6
Refer to subsection 4.2.2.5
Refer to subsection 4.2.2.5
1) Initial Setting
2) Condition
Check
3) Start up
Items on
Check sheet
OK
4-11
4.2.2.4 Operating Procedure
The basic ow of the ILBD operation is as follows.
1) Initial setting
2) Condition check
3) Start up
4) Perform the ILBD algorithm.
If an alarm is often generated or the process
condition changed in the ILBD operation, do
tuning to change the alarm setting, or to reset the
reference values.
Fill out the information to the checklist, at the
process shown in below gure.
(Refer to the Appendix 1. ILBD Check List)
Figure 4.5 Flow Chart of ILBD Operation
IM 01C25T01-06EN
<4. Diagnostics>
4-12
4.2.2.5 Alarm and Alert Setting
The abnormal results as the blockage detection and
high/low ange temperature (heat trace monitoring)
are given through an analog alert or the LCD
display of alarm status. Before performing the ILBD
operation, it is necessary to set the alarm and alert
according to the following procedure.
Storage of Abnormal results
(Diag Error)
Alarm Masking
(Diag Option)
Outside Diagnosis Range/
Invalid Ref xx
Masking
Alarm on
Analog Output
Figure 4.6 Alarm and Alert Setting
Alarm on
Status Output
Field Device More Status Available
Device Status
Additional Device Status
(Status group 8 and 9)
Alarm Display
on LCD
F0408.ai
DD
Bit
(HART 5/HART 7)
DTM (HART 7)
Not usedNot used
0
Not usedNot used
1
A BlockingA Blocking
2
Large Fluct L
3
Large Fluct H
4
L Side BlockingLow Side Blocking
5
H Side Blocking
6
B BlockingB Blocking
7
Invalid Ref FInvalid Ref BlkF
8
Invalid Ref SPHInvalid Ref fSPh
9
Invalid Ref SPLInvalid Ref fSPl
10
Invalid Ref DPInvalid Ref fDP
11
12 ILBD over range
FT low alarm
13
FT high alarm
14
15 Not usedNot used
DTM (HART 5)Category
Large Fluctuation
of Low Side
Large Fluctuation
of High Side
High Side
Blocking
Outside Diagnosis
Range
Flg Temp Low
Alarm
Flg Temp High
Alarm
ILBD
Heat trace
monitoring
Alarm Status
When the algorithm of ILBD and Heat trace
monitoring detect the abnormality, the result is
stored in Diag Error. The alarm status based on the
detected abnormality is displayed to Diag Error.
(Displayed to Impulse Line Blockage Detection
and Heat Trace for DTM(HART 5))
Diag and Service → Advanced Diag
Alerts → Diag Error
Note: FT indicates the ange temperature.
ILBD over range (Outside Diagnosis
Range)
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
1) Lim DPAvgmaxLim DPAvgmax is the upper limit of the
diagnostic capability range. The limit value can
be changed when Diag Mode is “Stop”.
DPAvg indicates the ratio of the average of
differential pressure to the EJX maximum span
regarded as 1. When DPAvg exceeds this
limit, “ILBD over range” is generated so that the
blockage detection becomes impossible.
2) Lim DPAvgminLim DPAvgmin is the lower limit of the
diagnostic capability range. The limit value can
be changed when Diag Mode is “Stop”.
Diag and Service → Advanced Diag
Congurations → Impulse Line
Blockage Detection → Threshold →
When DPAvg is below this limit, “ILBD over
range” is generated so that the blockage
detection becomes impossible.
IM 01C25T01-06EN
<4. Diagnostics>
4-13
<Example>
When the level range that can be measured by the
transmitter with 100 kPa span is –80 to 80 kPa, the
limits are set as follows.
• Lim DPAvgmax: 0.80
• Lim DPAvgmax: –0.80
1.000
0.80
0.000
ILBD over range
Detectable
range
DPAvg
-0.80
-1.000
ILBD over range
F0409.ai
Invalid Ref F, SPH, SPL, or DP
This alarm indicates that the reference value under
normal condition is invalid. If Ref F is invalid, the
blockage detection excluding BlkF is carried out.
If blockage detection function based on BlkF is
required, obtain the reference value again.
Also when Ref DPAvg is below Lim DPAvgmin
or exceeds Lim DPAvgmax, all reference value
becomes invalid so that “Invalid Ref DP”, “Invalid
Ref SPL”, “Invalid Ref SPH”, and “Invalid Ref F” are
generated.
Alarm Masking
Diag Option
DD
(HART 5/HART 7)
DTM (HART 7)
A BlockingA Blocking
Large Fluct LLarge Fluctuation of Low Side
Large Fluct HLarge Fluctuation of High Side
L Side BlockingLow Side Blocking
H Side BlockingHigh Side Blocking
B BlockingB Blocking
Invalid Ref DPInvalid Ref fDP
DTM (HART 5)
To Link the alarm to an analog alert and LCD
display, follow the procedure below.
1) Set “Stop” to Diag Mode.
2) Check each checkbox of the alarm, which is
selectable from bit 2 to 14.
Note: Set to “Calculation” after setting the parameter.
Alert Setting
Diag Out Option
When an alert regarding the impulse line blockage
or high/low ange temperature is generated, the
output value of 4-20 mA analog signal can be
changed.
ModeFunction
Off
Burnout
Fall back
Keeping PV measurement. The alert is not
reected to 4-20 mA analog signal.
The analog signal is shifted to the value of
AO upper limit or AO lower limit when an
alert is generated.
The shifted direction follows Burnout switch
setting.
The analog signal is hold to the specic
value, Diag Fixed Out Val, when an alert is
generated.
The alarms linked to an analog alert and LCD
display are selected by Diag Option.
Diag and Service → Advanced Diag
Congurations → Impulse Line
Blockage Detection → Diag Option
→
The bit of Diag Option is corresponding to that
of Diag Error. The following alarms are set at
the factory setting, which is corresponding to
hexadecimal 0x08FC.
Diag and Service → Advanced Diag
Congurations → Diag Out Option →
Diag Fixed Out Val
This parameter is used when “Fall back” is selected
to Diag Output Option.
When an alert is generated, the 4-20 mA analog
signal is held on the value specied by this
parameter.
The value can be entered within 3.6 to 21.6 mA.
IM 01C25T01-06EN
<4. Diagnostics>
4-14
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
[Root Menu] → Diag/Service →
Diag Parameters → Diag Output →
Diag Fixed Out Val →
Diag and Service → Advanced Diag
Congurations → Diag Fixed Out
Val →
Status Output for Advanced diagnostic
The output of the abnormal results are applicable
for a transistor output (open collector) of an on/off
signal according to the status of high and low alarm
limits, which are values set to Limit parameters as
shown in subsection 4.2.2.1. About the Flg Temp Hi Alert Val, or Flg Temp Lo Alert Val for Heat
trace monitoring, refer to subsection 4.2.3.2.
DO Select
If the advanced diagnostic function is installed, the
following modes can be also assigned to the status
output in addition to Pres, SP and Temp.
ModeFunction
Diag Alarm
All
The status regarding advanced diagnostic
masked by Diag Option is output.
All status of Press, SP, Temp and advanced
diagnostic are output.
4.2.2.6 Condition Check
After the transmitter was installed, it is necessary to
conrm if Pres is stable under the normal operating
condition or if uctuation amplitude under the
normal operating condition is large enough to detect
the blockage.
Stability of Pressure Value
1) Observe the value change of Pres under the
normal operating condition for 10 minutes.
If the value change is more than 10%, the error
inuences pressure uctuation value so that the
blockage detection becomes impossible. Consider
the plant operating conditions.
Fluctuation Value
NOTE
Alarm Display on LCD
If the ILBD algorithm detects the abnormality, the
content of the detected result is displayed with
“AL.88” or “AL.89” on the LCD. “AL.88” indicates
that condition is not applicable for the abnormality
detection and “AL.89” indicates the abnormality is
detected.
F0410.ai
Figure 4.7 Display Example of H Side Blocking
The alarm display on LCD regarding the advanced
diagnostic is described in Table 4.5.
NOTE
The blockage detection may not be carried
out correctly when pressure uctuation
amplitude especially with the pressure and level
measurement, is small.
Conrm that each value of fDP, fSPl, fSPh, and BlkF is more than the value specied in the below
table.
• Procedure to call up the fDP, fSPl, fSPh display
The alarms of “Invalid Ref xx” and “ILBD over
range” do not link to the 4-20 mA analog signal
and Status output.
IM 01C25T01-06EN
<4. Diagnostics>
4-15
Table 4.4 Requirements to apply ILBD
Condition
fDP7×10
fSPI1×10
fSPh1×10
BlkF-0.5 to 0.5
-10
or more
-10
or more
-10
or more
fDP is not enough.
No blockage can be detected if fDP is not larger
than the specied value.
Only fDP is enough.
“A Blocking” or “B Blocking” can be detected
if fSPl and fSPh are not larger than specied
values.
fDP and fSPl are enough.
“H Side Blocking” and “Large Fluct H” can not
be detected if fSPh is not larger than specied
value.
fDP and fSPh are enough.
“L Side Blocking” and “Large Fluct L” can not
be detected if fSPl is not larger than specied
value.
Start of Sampling
The sampling of reference value is carried out for
180 seconds, which is the default value set to Diag Period.
1) Conrm that the sampling period (Diag Period)
is set to 180 seconds.
2) Set “Reference” to Diag Mode.
The sampling starts soon after the setting.
IMPORTANT
• For the each parameter, the one value is
given. If Reference is set to Diag Mode
again, the value is updated and overwritten.
• If the power supply is shut down during the
sampling, Diag Mode becomes “Stop”. Set
“Reference” to Diag Mode in order to carry
out the sampling again.
End of Sampling
After about 180 seconds, the sampling
automatically nishes. The “Reference” setting of
Diag Mode moves automatically to “Calculation”.
Conrm that the setting of Diag Mode moves to
“Calculation”.
fDP, fSPl and fSPh are enough.
All alarm modes can be detected even if BlkF is
not within the specied values.
4.2.2.7 Obtain Reference Values
The pressure uctuation values are reduced
when the impulse line is plugged. Therefore, the
reference value is required to determine the degree
of reduction.
IMPORTANT
• If the impulse line is about to be plugged at
the time when a reference value is obtained,
blockages cannot be detected accurately.
The impulse lines on both the high-pressure
and low-pressure sides need to be cleaned
before a reference value is obtained.
• All air bubbles need to be adequately purged
before a reference value is obtained.
• Reference values must be obtained under
operating condition.
Reference Values
Conrm the latest values are obtained into the
following parameters.
Diag and Service → Advanced
Diag Conguration → Impulse Line
Blockage Detection → Ref fDP/Ref
fSPl/Ref fSPh/Ref BlkF/Ref DPAvg
IM 01C25T01-06EN
<4. Diagnostics>
4-16
Invalid Ref F, SPH, SPL, or DP
When the enough reference uctuation value is
not obtained, an alarm of invalid reference value
for each parameter is generated and also the ILBD
operation is not carried out.
Conrm the alarm of Invalid Ref F, SPH, SPL, or DP is not displayed in Diag Error.
If an alarm of Invalid Ref F, SPH, SPL, or DP is
generated, consider the process condition or obtain
the reference uctuation values again.
NOTE
Even if an alarm of Invalid Ref F, SPH, SPL, or
DP is generated, “Calculation” in Diag Mode is
kept.
4.2.2.8 Capability Test of Blockage
Detection Operation
Before performing the ILBD operation, check the
capability of the blockage detection operation.
The simulation test is performed by closing motion
of a three-valve manifold or stop valve. When
simulated blockage occurs, conrm that an alarm is
generated.
NOTE
The uctuation amplitude of atmospheric
pressure is nearly zero with pressure or level
measurement. In such case, simulate the
blockage detection by closing the valve where
the uctuation existed.
Simulation of Low-pressure Side
Blockage
1) Close the low-pressure-side valve.
2) Conrm the value of Pres is stable. If not,
open the valve a little.
3) Set “Calculation” to Diag Mode so as to start
blockage detection operation.
4) Check that an alarm of “L Side Blocking” is
generated after the time that consists of Diag Period and Diag Supp Count passed.
5) Check also the operation of the analog alert if
an analog alert is set.
6) Open the valve completely and check that
there are no alarms.
Simulation of Both-pressure Side
Blockage
1) Close the both-pressure-side valves.
2) Conrm the value of Pres is stable. If not,
open the valve a little.
3) Set “Calculation” to Diag Mode so as to start
blockage detection operation.
4) Check that an alarm of “B Blocking” is
generated in the Diag Error after the time
that consists of Diag Period and Diag Supp Count passed.
5) Check also the operation of the analog alert if
an analog alert is set.
6) Open the valve completely and check that
there are no alarms.
4.2.2.9 Start ILBD Operation
If process condition and capability to detect a
blockage are conrmed, you can start the ILBD
operation according to the following procedure.
Simulation of High-pressure Side
Blockage
1) Close the high-pressure-side valve.
2) Conrm the value of Pres is stable. If not,
open the valve a little.
3) Set “Calculation” to Diag Mode so as to start
blockage detection operation.
4) Check that an alarm of “H Side Blocking” is
generated after the time that consists of Diag Period and Diag Supp Count passed.
5) Check also the operation of the analog alert if
an analog alert is set.
6) Open the valve completely and check that
there are no alarms.
1) Check the value of sampling period (Diag Period).
2) Check the number of times that detect the
blockage consecutively in order to give an
alarm (Diag Supp Count). The default value
at the shipment is set to 3 times.
3) Set “Calculation” to Diag Mode.
If the reference value has not yet been
obtained, set “Reference” to Diag Mode.
After obtained the reference values, the
ILBD starts automatically. At the same time,
Diag Mode changes automatically from
“Reference” to “Calculation”.
IM 01C25T01-06EN
<4. Diagnostics>
4-17
4.2.2.10 Tuning
When the pressure uctuation amplitude in uids is
not sufciently large or an alarm is often generated
according to the process condition, tune up by
changing the threshold for the blockage detection
(Limit parameters) or the sampling period (Diag Period) to enhance the accuracy of the blockage
detection The ILBD operation must be stopped to
tune up. Set “Stop” to Diag Mode.
Threshold Value
The gure below shows the image of tuning effect
with a monochrome bar.
(a) The tuning image of the threshold values for
(1) Ratio fDP: Sqrt (fDP/Ref fDP),
(2) Ratio fSPl: Sqrt (fSPl/Ref fSPl),
(3) Ratio fSPh: Sqrt (fSPh/Ref fSPh)
013
Threshold (lower side)Threshold (upper side)
(1) Lim fDPmin
(2) Lim fSPlmin
(3) Lim fSPhmin
(b) The tuning image of the threshold values for
(4) Sqrt (BlkF/Ref BlkF)
0-11
Threshold (lower side)Threshold (upper side)
(4) Lim BlkFmin(4) Lim BlkFmax
Figure 4.8 Tuning Image of Threshold Value
(1) Lim fDPmax
(2) Lim fSPlmax
(3) Lim fSPhmax
F0411-1.ai
F0411-2.ai
(1) Setting by DD and DTM (excluding EJX
HART 5 DTM based on FDT1.2)
• Procedure to call up the threshold related
display
The default values at the factory setting are the
values of Lim fDPmax to Lim BlkFmin shown in
Table 4.3.
Change the threshold value to solve your problem
according to the above image.
1) Set “Stop” to Set Diag Mode.
2) Change the unsuitable value of Diag Lim
parameters corresponding to the each
blockage detection.
Note: Set to “Calculation” after setting the parameter.
Limit parameter
#ParameterThreshold value
[1] Lim fDPmax
[2] Lim fDPmin
[3] Lim fSPlmax
[4] Lim fSPlmin
[5] Lim fSPhmax
[6] Lim fSPhmin
[7] Lim BlkFmax
[8] Lim BlkFmin
Threshold to detect “A
Blocking” by using Ratio fDP
Threshold to detect “B
Blocking” by using Ratio fDP
Threshold to detect “Large
Fluct L” by using Ratio fSPl
Threshold to detect “L Side
Blocking” by using Ratio fSPl
Threshold to detect “Large
Fluct H” by using Ratio fSPh
Threshold to detect “H Side
Blocking” by using Ratio fSPh
Threshold to detect “H Side
Blocking” by using BlkF
Threshold to detect “L Side
Blocking” by using BlkF
Move the threshold toward the white.
• It becomes increasingly likely to give a false
alarm due to the disturbance from environment
change.
• If ow/differential pressure is below Lim DPAvgmin or exceeds Lim DPAvgmax,
pressure uctuation is likely too small or too
large to detect the blockage.
Move the threshold toward the black.
• It enables to be insusceptible to disturbance
such as environment change and to detect the
blockage easier.
• It becomes giving an alarm of the blockage after
the blockage has been progressed.
(2) Setting by EJX HART 5 DTM based on
FDT1.2
Combination of threshold depend on the sensitivity
of blockage detection can be selected from High,
Medium, or Low in the Sensitivity parameter.
• Procedure to call up the display
EJX HART 5
DTM based on
FDT1.2
Diag and Service → Advanced
Diag Conguration → Impulse Line
Blockage Detection → Threshold →
sensitivity
When select “Custom” in the Sensitivity parameter,
you can set each threshold individually.
Set the Diag Mode to “Stop” before changing the
threshold.
IM 01C25T01-06EN
<4. Diagnostics>
4-18
Combination of threshold for sensitivity parameter
If uctuating around the threshold value, an
alarm maybe often generated. When the above
phenomenon happens, the sampling time (Diag Period) can be changed so as to enhance the
accuracy of the blockage detection.
The longer the sampling time, better the expected
accuracy.
(1) Set “Stop” to Diag Mode.
(2) Enter the value to Diag Period within the
range of 20 to 65535 (seconds).
Note: Set to “Calculation” after setting the parameter.
Also, the accuracy can be improved by increasing
the number of Diag Supp Count.
ILBD Range Setting
If ow/differential pressure is less than the default
threshold value of Lim DPAvgmin, pressure
uctuation is not large enough to detect the
blockage. To prevent the fault blockage detection,
the threshold should be changed to larger value.
(1) Set “Stop” to Diag Mode.
(2) Enter the value to Lim DPAvgmin or Lim
DPAvgmax.
Note Set to “Calculation” after setting the parameter.
Ratio fDP Compensation
When the ow change is too large or small, an
alarm maybe often generated. When the above
case happens, the Ratio fDP can be compensated
so as to enhance the accuracy of the blockage
detection.
Diag DPComp
When “Compensation” is selected in Diag
DPComp, Ratio fDP is compensated by following
formula and used as treatable monitoring value,
CRatio fDP.
CRatio fDPCRatio fDP
=
fDP
Ref fDP
Ref DPAvg
DPAvg
On the other hand, if the compensation is not
necessary, “Non-compensation” is selected in Diag DPComp and Ratio fDP is used as NRatio fDP.
NRatio fDP
=
fDP
Ref fDP
• Procedure to call up the display
DD and DTM
(excluding EJX_
HART 5[1.2])
EJX_HART 5[1.2]
DTM
[Root Menu] → Diag/Service
→ Diag Parameters → ILBD
parameters → Status → Diag
Vriables → CRatio fDP/NRatio fDP
Diag and Service → Advanced Diag
Variables → CRatio fDP/NRatio fDP
4.2.2.11 Reset of Reference Value
When there are large ow change or the change of
uid conditions, obtain the reference value again. If
ow change by a comparison of the reference value
is ±25% or more, obtain the reference value again.
Diag and Service → Advanced
Diag Conguration → Impulse Line
Blockage Detection → Threshold →
IM 01C25T01-06EN
<4. Diagnostics>
4-19
4.2.2.12 ILBD Parameter List
# Parameter name Default valueExplanation
1 Diag Error0x0000The results detected by ILBD or Heat trace monitoring are stored into this
parameter.
Also the condition abnormality in the diagnostic process is stored as an error.
2 Diag Option0x08FCThe masking in this parameter enable to display each error message and the
status to the output signal or LCD.
The error assigned to each bit is corresponding to that of Diag Error.
Writable only when Diag Mode is "Stop".
3 Diag Out OptionOffOutput mode of 4-20mA when an advanced diagnostic alarm is generated.
There are following three output modes; Off, Burnout, or Fall back.
4 Diag Fixed Out
Val
5 DO SelectOffThe variables for status output are specied to this parameter. When the
6 Diag ModeStopThe operation mode of ILBD is set.
7 Diag Period180 (s)The data acquisition period for ILBD is set within 20 to 65535 (s). If the process
8 Diag Supp Count 3Detection count to generate an alarm. When the statistical value as Ratio fDP
9 Diag DescriptionMemo eld. 32 alphanumerics
10 fDPAverage value of the sum of squares of differential pressure uctuation.
11 fDP StatusStatus of fDP
12 fSPlAverage value of the sum of squares of low-pressure-side static pressure
13 fSPl StatusStatus of fSPl
14 fSPhAverage value of the sum of squares of high-pressure-side static pressure
15 fSPh StatusStatus of fSPh
16 BlkFBlockage degree characterized in comparison of high- and low-pressure side
17 BlkF StatusStatus of BlkF
18 DPAvgRatio of the average of differential pressure/pressure to the maximum span of an
19 DPAvg StatusStatus of DPAvg
20 Ratio fDPCRatio fDP or NRatio fDP is used by Diag Comp setting.
21 Ratio fDP StatusStatus of Ratio fDP
22 Ratio fSPlSQRT (fSPl/Ref fSPl).
23 Ratio fSPl StatusStatus of Ratio fSPl
24 Ratio fSPhSQRT (fSPh/Ref fSPh).
25 Ratio fSPh
Status
26 Ref fDPValue of fDP obtained under normal condition.
27 Ref fDP StatusStatus of fDP obtained under normal condition.
21.6 mAParameter for "Fall back" function in the Diag Out option. The output value of
4-20 mA analog signal is specied when an alarm is generated. The value can be
entered within 3.6 to 21.6 mA.
advanced diagnostic function (option code /DG6) is installed, the parameters
monitoring in diagnostic process can be also assigned to the status output.
Stop: The blockage detection is stopped.
Calculate: The blockage detection is carried out.
The alarms are generated along with the detected result.
Reference: The reference values are obtained and the update values are
overwritten.
After setting, this mode moves automatically to "Calculation".
uctuation values are unsteady, this value is changed to the longer to enhance
the accuracy of the blockage detection.
Writable only when Diag Mode is "Stop".
and BlkF exceeds consecutively the threshold by number of times preset to this
parameter, it is estimated that the impulse line is plugged.
uctuation. For gauge/absolute pressure transmitter, 0 is set.
uctuation. For gauge/absolute pressure transmitter, 0 is set.
pressure uctuation value.
EJX transmitter.
fDP decreases and this parameter is used to determine whether one or both
sides are plugged.
fSPl decreases and this parameter is used to determine whether low-pressureside is plugged.
fSPh decreases and this parameter is used to determine whether high-pressureside is plugged.
Status of Ratio fSPh
IM 01C25T01-06EN
<4. Diagnostics>
# Parameter name Default valueExplanation
28 Ref fSPlValue of fSPl obtained under normal condition.
29 Ref fSPl StatusStatus of fSPl obtained under normal condition.
30 Ref fSPhValue of fSPh obtained under normal condition.
31 Ref fSPh StatusStatus of fSPh obtained under normal condition.
32 Ref BlkFValue of BlkF obtained under normal condition.
33 Ref BlkF StatusStatus of BlkF obtained under normal condition.
34 Ref DPAvgValue of DPAvg obtained under normal condition.
35 Ref DPAvg
Status
36 Lim fDPmaxRefer to
Table 4.3
37 Lim fDPminLower limit for Ratio fDP to detect the blockage.
38 Lim fSPlmaxUpper limit for Ratio fSPl to detect the blockage.
39 Lim fSPlminLower limit for Ratio fSPl to detect the blockage.
40 Lim fSPhmaxUpper limit for Ratio fSPh to detect the blockage.
41 Lim fSPhminLower limit for Ratio fSPh to detect the blockage.
42 Lim BlkFmaxUpper limit for BlkF to detect the blockage.
43 Lim BlkFminLower limit for BlkF to detect the blockage.
44 Lim DPAvgmaxUpper limit for DPAvg. Writable only when Diag Mode is "Stop".
45 Lim DPAvgminLower limit for DPAvg. Writable only when Diag Mode is "Stop".
46 Ref Lim fDPmin7.0E-10Lower limit to judge whether Ref fDP is available for ILBD operation.
47 Ref Lim fSPmin1.0E-10Lower limit to judge whether Ref fSPl and Ref fSPh are available for ILBD
48 Ref Lim BlkFmax 0.5Upper limit to judge whether Ref BlkF is available for ILBD operation.
49 Status group 8Refer to Table 4.5.
50 Status group 9Refer to Table 4.5.
51 CRatio fDPRatio fDP is compensated by following formula and used as treatable monitoring
52 CRatio fDP
Status
53 NRatio fDPWhen Non-compensation is selected in Diag DP Comp, NRatio fDP is used as
54 NRatio fDP
Status
55 Diag DPComp0:
Compensation
56 Diag ApplicableAfter the reference value is obtained, the applicable blockage detection is
Status of DPAvg obtained under normal condition.
Upper limit for Ratio fDP to detect the blockage.
Writable only when Diag Mode is "Stop".
Writable only when Diag Mode is "Stop".
Writable only when Diag Mode is "Stop".
Writable only when Diag Mode is "Stop".
Writable only when Diag Mode is "Stop".
Writable only when Diag Mode is "Stop".
Writable only when Diag Mode is "Stop".
Writable only when Diag Mode is "Stop".
Writable only when Diag Mode is "Stop".
operation.
Writable only when Diag Mode is "Stop".
Writable only when Diag Mode is "Stop".
value when the ow change is too large or small.
Sqrt (fDP / Ref fDP) X | Ref DPAvg / DPAvg |
When compensation is selected in Diag DP Comp, CRatio fDP is used as
monitoring value.
Status of CRatio fDP
monitoring value. NRatio fDP = Sqrt (fDP / Ref fDP)
Status of NRatio fDP
Whether fDP is referred by CRatio fDP or NRatio fDP is selected.
displayed on this parameter.
4-20
IM 01C25T01-06EN
<4. Diagnostics>
4-21
4.2.3 Heat Trace Monitoring
The transmitter with Heat trace monitoring function
calculates the ange temperature by using the two
temperature sensors built in the transmitter.
An analog alert is generated if the temperature
reached to the preset level.
The ange temperature is based on the following
parameters and calculation formula.
[Parameters]
Parameter nameExplanation
Snsr temp (CT)Measured capsule temperature
value
Amp temp (AT)Measured amplier temperature
value
Flg temp (FT)Flange temperature value
(Calculated value)
Flg Temp Coef (Cf)Coefcient to calculate ange
temperature
Flg Temp Hi Alert Val Threshold to generate FT high
alarm
Flg Temp Lo Alert Val Threshold to generate FT low
alarm
[Calculation formula]
Flg temp (FT) = CT + Cf X (CT-AT)
If the ange temperature exceeds the value preset
to Flg Temp Hi Alert Val or Flg Temp Lo Alert Val,
an alert is generated.
4.2.3.1 Flg Temp Coef Setting
The value calculated according to the following
procedure is set to Flg Temp Coef.
• To enhance the calculation accuracy of the
ange temperature, measure the actual ange
temperature by using the temperature sensor
etc.
• Calculate the ratio of the capsule temperature
to the capsule temperature minus the amplier
temperature from the two temperature values
measured by the transmitter.
• Derive the Flg Temp Coef from the measured
ange temperature and the ratio of the capsule
temperature to the amplier temperature in
accordance with the following calculation
formula.
Flg Temp Coef (Cf) =
(Actual measured value of Flange temperature) - CT
CT - AT
For DTM (HART 5), Flg Temp Coef parameter can
be set by using Tuning function.
By setting the measured value of ange
temperature, Flg Temp Coef is calculated by using
capsule temperature and amplier temperature.
• Procedure to call up the Tuning display.
Diag and Service → Advanced Diag Conguration →
Heat Trace → Tuning
NOTE
The ange temperature is calculated by the
calculation formula assumed that the capsule
part of the transmitter is heated up or kept warm
by an electrical heater or steam. In the case of an
atmosphere temperature or less, the difference
of temperature of approximately 3 to 4 °C,
may occur because the amplier temperature
becomes higher than the capsule temperature.
IM 01C25T01-06EN
<4. Diagnostics>
4-22
Sensor
Amplifier
Temperature
Capsule
Temperature
Sensor signals
Process Value
calculation
Amp temp
Snsr temp
Calculation of
Flg temp
HTM alarm
Diag Output
Option
Flg Temp Coef
CT+(CT-AT) x Cf
Flg temp
Execution HTM
Alarm Masking
Figure 4.9 Functional Block Diagram of Heat Trace Monitoring (HTM)
4.2.3.2 Out of Temperature Measurement
Range
When the ange temperature is out of
measurement range, the alarm or alert is
generated. For the detail of alarm and alert setting,
refer to subsection 4.2.2.5.
DO Config
Result of HTM detection
Result of HTM detection
HTM alarm
HTM alarm
4-20mA DC
(Analog Output)
Amp temp
Snsr temp
Contact Output
(Digital Output)
Flg temp
Diag Error
Response Code
(Device Status)
Status group 9
Display on LCD
F0412.ai
The measurement range is set to Flg Temp Hi
Alert Val and Flg Temp Lo Alert Val, which values
can be specied within -50 to 130 deg C.
An alarm is generated.
Flg Temp Hi Alert
Flg Temp Lo Alert
Flg temp
Flgtemp
An alarm is generated.
TimeTime
F0413.ai
IM 01C25T01-06EN
<4. Diagnostics>
4-23
4.2.3.3 Parameter Lists for Heat Trace Monitoring
#Parameter nameDefault valueExplanation
1 Diag Error0x0000The results detected by ILBD or Heat trace monitoring are stored into this
parameter. Also the condition abnormality in the diagnostic process is
stored as an error.
2 Diag Option0x08FCThe masking in this parameter enable to display each error message and
the status to the output signal or LCD.
The error assigned to each bit is corresponding to that of Diag Error.
Writable only when Diag Mode is "Stop".
3 Diag Out OptionOffThe error status can be output by 4-20 mA analog signal.
There are following three output modes; Off, Burnout, or Fall back.
4 Diag Fixed Out Val21.6mAParameter for "Fall back" function in the Diag Out option.
The output value in 4-20 mA analog signal is specied when an alarm is
generated.
The value must be entered within 3.6 to 21.6 mA.
5 Snsr temp (Cap temp*2)Measured capsule temperature value
6 Amp tempMeasured Amplier temperature value
7 Flg temp(*1)Calculated ange temperature value
8 Flg Temp Coef0Coefcient to calculate ange temperature (Cf: Rt1/Rt2)
Rt1: Thermal resistance between the ange and capsule.
Rt2 : Thermal resistance between the cupsule and amplier.
9 Flg Temp Hi Alart Val
(Flg Temp High Limit*2)
10 Flg Temp Lo Alart Val
(Flg Temp Low Limit*2)
11 DO SelectOffSee subsection 3.3.13 Status Output
12 DO Signal typeON WHEN
13 Digital OutputOffSee subsection 3.3.13 Status Output
120 deg CUpper limit of Flg temp
-40 deg CLower limit of Flg temp
See subsection 3.3.13 Status Output
AL DETECT
*1: The Flg Temp Coef is 0 at the shipment so that the Flg temp outputs the same value as that of Snsr temp.
*2: EJX HART 5 DTM based on FDT1.2.
IM 01C25T01-06EN
<4. Diagnostics>
4.3 Alarms and Countermeasures
Table 4.5 Alarm Message Summary
Integral
indicator
AL. 01
CAP.ERR
AL. 02
AMP.ERR
—
AL. 10
PRESS
AL. 11
ST. PRSS
AL. 12
CAP.TMP
AL. 13
AMP.TMP
AL. 30
PRS.RNG
AL. 31
SP. RNG
AL. 35
P.HI
AL. 36
P.LO
AL. 37
SP.HI
AL. 38
SP.LO
*1: DD and DTM (excluding EJX HART 5 DTM based on FDT1.2)
*2: EJX HART 5 DTM based on FDT1.2
*3: Available only for HART 7
HART conguration
tool display
P sensor error *
Pressure Sensor
2
Error *
CT sensor error *
Capsule Temperature
Sensor Error *
or Low) set with burnout
direction switch.
[status output: undened]
Capsule temperature
sensor problem.
1
Capsule EEPROM
(About the output signal,
refer to subsection 3.3.9)
problem.
Amplier temperature
sensor problem.
1
Amplier EEPROM
problem.
Amplier problem.
No device ID is found. Continues to operate and
output.
Differential pressure is
outside measurement
range limit of capsule.
When PV is Pres
Output AO upper limit or
AO Lower limit. (Refer to
subsection 3.3.1)
Static pressure exceeds
limit.
When PV is SP
Output AO upper limit or
AO Lower limit. (Refer to
subsection 3.3.1)
Capsule temperature is
outside range (–50 to
Continues to operate and
output.
130°C).
Amplier temperature
is outside range (–50 to
95°C).
Differential pressure
exceeds specied range.
When PV is Pres.
Output AO upper limit or
lower limit.
(Refer to subsection 3.3.1)
Static pressure exceeds
specied range.
When PV is SP
Output AO upper limit or
lower limit.
(Refer to subsection 3.3.1)
Input pressure exceeds
2
*
specied threshold.
2
*
Continues to operate and
output.
Input static pressure
exceeds specied
threshold.
Countermeasure
Replace capsule if
the error recurs after
the transmitter is
restarted.
Replace capsule.
Replace amplier.
Replace amplier.
Check input or
replace capsule
when necessary.
Use heat insulation
or make lagging to
keep temperature
within range.
Check input and
range setting, and
change them as
needed.
Check input.
Status
group
1
*
1
2
2
3
4
5
4-24
Diagnostic
List
group *
Hardware Failure
Transducer Status
2
IM 01C25T01-06EN
<4. Diagnostics>
Integral
indicator
AL. 50
P. LRV
AL. 51
P. URV
AL. 52
P. SPN
AL. 53
P. ADJ
AL. 54
SP. RNG
AL. 55
SP. ADJ
AL.60
SC.CFG
*1: DD and DTM (excluding EJX HART 5 DTM based on FDT1.2)
*2: EJX HART 5 DTM based on FDT1.2
*3: Available only for HART 7
HART conguration
tool display
Illegal P LRV *
Illegal Pressure LRV
2
*
Illegal P URV *
Illegal Pressure URV
2
*
Illegal P SPAN *
Illegal Pressure SPAN
2
*
P SPAN trim err *
Pressure SPAN Trim
Error *
P ZERO trim err *
Pressure ZERO Trim
Error *
Illegal SP LRV *
Illegal Static Pressure
2
LRV *
Illegal SP URV *
Illegal Static Pressure
URV *
Illegal SP SPAN *
Illegal Static Pressure
SPAN *
SP SPAN trim err *
Static Pressure SPAN
Trim Error *
SP ZERO trim err *
Static Pressure ZERO
Trim Error *
1
1
1
1
2
1
2
1
1
2
1
2
1
2
1
2
Specied value is outside
of setting range.
Specied value is outside
of setting range.
Cause
SC cong errorSpecied values or
settings to dene signal
characterizer function do
not satisfy the condition.
4-20mA Output
operation during error
Holds at the output value
that existed immediately
before the error occurred.
Continues to operate and
output.
Holds at the output value
that existed immediately
before the error occurred.
Continues to operate and
output.
Continue to operate and
output.
Countermeasure
Check settings and
change them as
needed.
Adjust settings and
change them as
needed.
Check settings and
change them as
needed.
Adjust settings and
change them as
needed.
Check setting and
change them as
needed.
Status
group
1
*
6
7
4-25
Diagnostic
List
group *
Conguration
2
IM 01C25T01-06EN
<4. Diagnostics>
Integral
indicator
AL. 79
OV. DISP
AL.87
FLG. HI
AL.87
FLG. LO
AL.88
INVR.DP
AL.88
INVR.SL
AL.88
INVR.SH
AL.88
INVR.F
AL.89
ILBD.OV
AL.89
B BLK
AL.89
H BLK
AL.89
L BLK
AL.89
H LRG
AL.89
L LRG
AL.89
A BLK
AL. 91 *
P. SIM
AL.91 *
SP. SIM
AL.91 *
T. SIM
*1: DD and DTM (excluding EJX HART 5 DTM based on FDT1.2)
*2: EJX HART 5 DTM based on FDT1.2
*3: Available only for HART 7
HART conguration
tool display
Cause
—Displayed value exceeds
limit.
FT high alarm *
Flg Temp High Alarm
2
*
FT low alarm *
Flg Temp Low Alarm
2
*
Invalid Ref DP *
Invalid Ref fDP *
1
Flange temperature
exceeds a preset upper
limit.
1
Flange temperature is
below a preset lower
limit.
1
Differential pressure/
2
pressure uctuation does
not reach the reference
level required to blockage
detection so that no
blockage detection is
carried out.
Invalid Ref SPL *
Invalid Ref fSPl *
1
Low-pressure-side
2
uctuation does not
reach the reference
uctuation level required
to blockage detection.
Invalid Ref SPH *
Invalid Ref fSPh *
1
High-
2
pressure-side
uctuation uctuation does
not reach the reference
uctuation level required to
blockage detection.
Invalid Ref F *
Invalid Ref BlkF *
1
BlkF can not be used for
2
blockage detection for
some reasons.
ILBD over range *
Outside Diagnosis
2
Range *
B Blocking *1, *
1
Appointed the diagnosis
range outside.
2
B Blocking (both-side
blockage) is detected.
H Side Blocking *
High Side Blocking *
L Side Blocking *
Low Side Blocking *
Large Fluct H *
Large Fluctuation of
High Side *
Large Fluct L *
Large Fluctuation of
Low Side *
A Blocking *1, *
1
High-pressure-side
2
blockage is detected.
1
Low-pressure-side
2
blockage is detected.
1
2
1
2
2
Pressure uctuation
amplitude of highpressure side is large.
Pressure uctuation
amplitude of lowpressure side is large.
A Blocking (single-side
blockage) is detected.
P Simulate ModeUnder Simulation Mode
3
for device variables.
SP Simulate Mode
3
T Simulate Mode
3
4-20mA Output
operation during error
Continues to operate and
output.
It depends on the Diag Out
Option setting.
Off: Continue to operate and
output.
Burnout:Outputs AO upper
limit or AO lower limit.
Fall back:Outputs Diag Out
Fixed Val.
Continue to operate and
output.
It depends on the Diag Out
Option setting.
Off: Continue to operate and
output.
Burnout: Outputs AO upper
limit or AO lower limit.
Fall back: Outputs Diag Out
Fixed Val.
Output the setting value of
Simulate-Value
Countermeasure
Check settings and
change them as
needed.
Check the heater
failure.
Check the capsule
temp. and Amplier
temp.
Adjust Flg Temp
Coef.
Check process
condition.
Check process
condition.
Check Simulation
Mode
Status
group
1
*
—
8
9
10
4-26
Diagnostic
List
group *
Diag Status
Diag Status
—
2
IM 01C25T01-06EN
<4. Diagnostics>
Table 4.6 HART Conguration Tool Error Messages
Error messageProbable causeCountermeasure
Invalid selection—Change the setting.
Value was too highSet value is too high.
Value was too lowSet value is too low.
Too few data bytes received——
In write protect modeOperation is set in the Write Protect mode. —
Lower range value too highLRV set point is too high.Change the range.
Lower range value too lowLRV set point is too low.
Upper range value too highURV set point is too high.
Upper range value too lowURV set point is too low.
Span too smallSet span is too small.
Applied process too highApplied pressure is too high.Adjust the applied pressure.
Applied process too lowApplied pressure is too low.
New lower range value pushed upper
range value over upper sensor limit
Excess correction attemtedAmount of correction is too much.Adjust the amount.
Lower conversion not succeededCharacters are not convertible. e.g. %Correct the setting.
Not in xed current modeThe xed current mode is desired but not
In multidrop modeOperation is set in the multi-drop mode.—
Not write protect modeOperation is set without a password.—
Lower range value and upper range
value out of limits
The shift of URV according to the new LRV
setting exceeds USL.
set in that mode.
URV and LRV are out of range limits.Change the setting.
Change the URV setting within the
range of USL.
Set in the xed current mode.
4-27
Table 4.7 Device Status
ItemDescription
Field Device Malfunction
(0x80)
Conguration Changed
(0x40)*
Cold Start
(0x20)
More Status Available
(0x10)
Loop Current Fixed
(0x08)
Loop Current Saturated
(0x04)
Non-Primary Variable Out
of Limits
(0x02)
Primary Variable Out of
Limits
(0x01)
*: This ag can be reset. Refer to subsection 4.1.3 (6) Reset
Conguration Changed Flag
Field device has
malfunctioned due to a
hardware error or failure.
A modication has been
made to the conguration
of the eld device.
A reset of the eld device
has occurred, or power
has been removed and
reapplied.
Field device has more
status available.
Analog output and its
digital representation
are in xed mode, and
not responsive to input
changes.
Analog output and its
digital representation are
outside the operating
range limits, and not
responding to input.
Process applied to the
non-primary variable is
outside the operating
limits of the eld device.
Process applied to the
primary variable is outside
the operating limits of the
eld device.
Table 4.8 Extended Device Status
ItemDescription
Maintenance Required
(0x01)
Device Variable Alert
(0x02)
Table 4.9 Data Quality and Limit Status
Data QualityDescription
GoodThe value may be used in
Poor AccuracyThe quality of the value is
Manual / FixedThe value is manually
BadThe value is not useful.
Limit StatusDescription
ConstantThe value cannot be
Low LimitedThe value is out of the
High Limited
Not LimitedThe value is free to
Device requires
maintenance.
Conguration is invalid or
device is under simulation
mode.
control.
less than normal, but the
value may still be useful.
xed.
changed, no matter what
the process does.
high or low limit.
change.
IM 01C25T01-06EN
<4. Diagnostics>
Table 4.10 Relationship between Alarm and Status available for HART 7
Integral
Indicator
AL.01
CAP.ERR
HART conguration
tool display
P sensor error *
Pressure Sensor
2
Error *
CT sensor error *
Capsule
Temperature
Sensor Error *
Cap EEPROM
1
error *
Capsule
EEPROM Error *
AL.02
AMP.ERR
AT sensor error *
Amp Temp
Sensor Error *
Amp EEPROM
1
error *
Amp EEPROM
2
Error *
CPU board error
1
*
CPU Board Error
2
*
---No device ID *
No Device ID *
AL.10
PRESS
P outside limit *
Pressure Outside
2
Limit *
Device Status
1
Device
Malfunction
(0x80)
1
Extended
Device Status
Maintenance
Required
(0x01)
Differential
Pressure
(DP)
Value: Hold value
Status: Bad and Constant
Value: Hold value
Status: Bad and Constant
2
Value: Hold value
Status: Bad and Constant
2
1
2
Value: Hold value
Status: Bad and Constant
Value: Hold value
Status: Bad and Constant
Value: Hold value
Status: Bad and Constant
1
------Value: Measured value
2
1
Primary
Variable Out of
Limits (0x01)
Device
Variable Alert
(0x02)
Status: Good and Not Limited
Value:
Measured value
Status:
Poor Accuracy and Not
Limited
Value and Status (Data Quality and Limit Status)
Static
Pressure
(SP)
Temperature
(T)
% rangeLoop current
Value:Hold value
Status:Bad and Low Limited/
High Limited
Value: Hold value
Status: Bad and Low
Limited/High Limited
Value: Measured value
Status: Good and Not Limited
Value: Measured value
Status: Good and Not Limited
*1: DD and DTM (excluding EJX HART 5 DTM based on FDT1.2)
*2: EJX HART 5 DTM based on FDT1.2
*3: Depend on the setting of hardware switch
*4: Depend on the direction of range over (high or low)
Value: Hold value
Status: Bad and Low
Limited/High Limited
Status: Good and Not
Limited
*4
IM 01C25T01-06EN
<4. Diagnostics>
4-29
Integral
Indicator
AL.35
P. HI
AL.36
P. LO
AL.37
SP. HI
AL.38
SP. LO
AL.50
P. LRV
AL.51
P. URV
AL.52
P. SPN
AL.53
P. ADJ
HART conguration
tool display
P high alarm *
Pressure High
Alarm
P low alarm *
Pressure Low
Alarm
SP high alarm *
Static Pressure
High Alarm *
SP low alarm *
Static Pressure
Low Alarm *
Illegal P LRV *
Illegal Pressure
LRV *
Illegal P URV *
Illegal Pressure
URV *
Illegal P SPAN *
Illegal Pressure
SPAN *
1
2
*
1
2
*
2
2
1
2
1
2
1
1
1
2
P SPAN trim err *
Pressure SPAN
Trim Error *
P ZERO trim
err *
Pressure ZERO
Trim Error *
2
1
2
Device Status
Device Status
---Device
Variable Alert
(0x02)
1
Extended
Value and Status (Data Quality and Limit Status)
Differential
Pressure
(DP)
Static
Pressure
(SP)
Value: Measured value
Status: Good and Not Limited
Value: Measured value
Status: Good and Not Limited
Value:
Measured
value
Status:
Value:
Measured value
Status:
Good and Not Limited
Poor
Accuracy and
Not Limited
Temperature
(T)
% rangeLoop current
Value: Hold value
Status: Bad and Constant
Value: Measured value
Status: Poor Accuracy and
Not Limited
AL.54
SP. RNG
AL.55
SP. ADJ
Illegal SP LRV *
Illegal Static
Pressure LRV *
Illegal SP URV *
Illegal Static
Pressure URV *
Illegal SP SPAN
1
*
Illegal Static
Pressure SPAN *
SP SPAN trim
1
err *
Static Pressure
SPAN Trim Error
2
*
1
2
1
2
2
Value: Measured value
Status: Good and Not Limited
Value:
Measured
value
Status:
Good and Not
Limited
SP ZERO trim
1
err *
Static Pressure
ZERO Trim Error
2
*
AL.60
SC.CFG
AL.79
OV.DISP
SC cong errorValue: Measured value
Status: Good and Not Limited
---------Value: Measured value
Status: Good and Not Limited
*1: DD and DTM (excluding EJX HART 5 DTM based on FDT1.2)
*2: EJX HART 5 DTM based on FDT1.2
*3: Depend on the setting of hardware switch
*4: Depend on the direction of range over (high or low)
Value:
Measured
value
Status:
Poor
Accuracy and
Not Limited
Value:
Measured
value
Status:
Good and Not
Limited
Value: Measured value
Status: Good and Not
Limited
Value: Measured value
Status: Good and Not
Limited
IM 01C25T01-06EN
<4. Diagnostics>
4-30
Integral
Indicator
AL.87
FLG. HI
AL.87
FLG. LO
AL.88
INVR.DP
AL.88
INVR.SL
AL.88
INVR.SH
AL.88
INVR.F
AL.89
ILBD.OV
AL.89
B BLK
AL.89
H BLK
AL.89
L BLK
AL.89
H LRG
AL.89
L LRG
AL.89
A BLK
HART conguration
tool display
FT high alarm *
Flg Temp High
Alarm *
FT low alarm *
Flg Temp Low
Alarm *
Invalid Ref DP *
Invalid Ref fDP *
1
2
1
2
1
2
Invalid Ref SPL *
Invalid Ref fSPl *
Invalid Ref SPH *
Invalid Ref fSPh
2
*
Invalid Ref F *
1
Invalid Ref BlkF *
ILBD over range
1
*
Outside
Diagnosis Range
2
*
B Blocking *1, *
2
H Side Blocking *
High Side
Blocking *
2
L Side Blocking *
Low Side
Blocking *
Large Fluct H *
Large Fluctuation
of High Side *
Large Fluct L *
Large Fluctuation
of Low Side *
A Blocking *1, *
2
1
2
1
2
2
Device Status
Extended
Device Status
---Maintenance
Required
(0x01)
1
2
1
2
1
1
Value and Status (Data Quality and Limit Status)
Differential
Pressure
(DP)
Static
Pressure
(SP)
Value: Measured value
Status: Good and Not Limited
Value: Measured value
Status: Good and Not Limited
Value: Measured value
Status: Good and Not Limited
Value: Measured value
Status: Good and Not Limited
Temperature
(T)
% rangeLoop current
In the case “Off” is set to
Diag Out Option
Value: Measured value
Status: Good and Not
Limited
In the case “Burnout” is set
to Diag Out Option
Value: Low Limited/High
Limited
Status: Bad and Low
Limited/High Limited
*3
In the case “Fall back” is set
to Diag Out Option
Value: Fixed value
Status: Bad and Constant
In the case “Off” is set to
Diag Out Option
Value: Measured value
Status: Good and Not
Limited
In the case “Burnout” is set
to Diag Out Option
Value: Low Limited/High
Limited
Status: Bad and Low
Limited/High Limited
*3
In the case “Fall back” is set
to Diag Out Option
Value: Fixed value
Status: Bad and Constant
*1: DD and DTM (excluding EJX HART 5 DTM based on FDT1.2)
*2: EJX HART 5 DTM based on FDT1.2
*3: Depend on the setting of hardware switch
*4: Depend on the direction of range over (high or low)
IM 01C25T01-06EN
<4. Diagnostics>
4-31
Integral
Indicator
AL.91
P. SIM
HART conguration
tool display
Device Status
Extended
Device Status
P Simulate Mode ---Device
Variable Alert
(0x02)
Differential
Pressure
Value and
Status:
Pressure
simulation
value
AL.91
SP.SIM
AL.91
T.SIM
SP Simulate
Mode
T Simulate ModeValue: Measured value
Status: Good and Not
Limited
*1: DD and DTM (excluding EJX HART 5 DTM based on FDT1.2)
*2: EJX HART 5 DTM based on FDT1.2
*3: Depend on the setting of hardware switch
*4: Depend on the direction of range over (high or low)
(DP)
Value and Status (Data Quality and Limit Status)
Static
Pressure
(SP)
Value: Measured value
Status: Good and Not
Temperature
(T)
% rangeLoop current
According to the setting of
simulation
Limited
Value and
Status:
Static
Value: Measured value
Status: Good and Not
Limited
Pressure
simulation
value
Value and
Status:
Temperature
simulation
value
IM 01C25T01-06EN
<5. Parameter Summary>
5. Parameter Summary
5-1
FunctionLabelItemContentsDefault value Handling *
Analog output AO alm typAnalog output alarm typeHigh or LowR
AO lower limitLower limit of analog output3.6000 to 21.6000 mA3.6000 mAW
AO upper limitUpper limit of analog output3.6000 to 21.6000 mA21.6000 mAW
Auto recoverAuto-recover from hardware errorOff or OnOnW
Analog output
trim
Clear D/A trimReset analog output trimM
D/A trimAnalog output trim with ammeterM
Scaled D/A trimAnalog output trim with voltmeterM
Channel agsAnalog channel ags0x00R
Cmd 9: Device vars w/status
Cmd 48: Read Additional
Device Status.
Burst Variable
Code (DD)
Device Variable for the Burst
Message *
2
Max 8 slots.W
Device Variable
Code (DTM)
HART 7
Burst Msg Trigger
Mode
HART 7
Set Burst Trigger
HART 7
Set Burst Period
HART 7
Burst Trigger Level
HART 7
Update Period
HART 7
Burst Trigger Mode Selection Code
2
*
(Continuous, Window, Rising,
Falling, On-change)
Congure burst triggerCongure Burst Msg Trigger
Mode and Burst Trigger Level
Congure burst periodCongure Update Period and
Max Update Period
Burst Trigger Level *
Update Period for Burst mode *
2
2
Update period for burst
message
ContinuousR
0.0R
Burst Message
1: 0.5s
2: 60s
M
M
R
3: 60s
Max Update Period
HART 7
Max Update Period for Burst mode
2
*
Maximum update period for
burst message
60 minR
DampingPres DampDamping time constant for DP0.00 to 100.00 sW
Quick respQuick responseOn or OffOffW
DateDateDate**/**/**W
DescriptorDescriptorDescriptor16 alphanumericsW
*1: Handling: R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,
D
=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters.
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)
*3: The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.
1
IM 01C25T01-06EN
<5. Parameter Summary>
5-2
FunctionLabelItemContentsDefault value Handling *
Device
information
Chg universal revChange the HART universal
revision
Country
HART 7
Country codeUS, JP, DE, FR, ES, RU, CN JPW
HART 5 or HART 7M
Dev idDevice IDR
DistributorYokogawaR
Drain vent matlDrain and vent plug materialW
Extra No.Customizaion numberR
Ext SWExternal zeroing permissionDisabled or EnabledEnabledW
Fill uidFill uidW
Final asmbly numFinal assembly numberW
Fld dev revField device revisionR
Gasket matlGasket materialW
Isoltr matlCapsule materialW
Mftr DateManufactured dateR
Model 1Memo eld for MS code 132 alphanumericsW
Model 2Memo eld for MS code 232 alphanumericsW
Model 3Memo eld for MS code 332 alphanumericsW
Num of RSNumber of remote sealW
Process Conn matl Process connection materialW
Process Conn size Process connection sizeW
Process Conn type Process connection typeW
RS ll uidFill uid of remote sealW
RS Isoltr matlRemote seal materialW
RS typeRemote seal typeW
Serial No.Serial numberR
Sofftware revSoftware revisionR
Style No.Style numberStyle number of productR
Universal revUniversal revision16 alphanumericsR
Cfg chng count
HART 7
Reset Cfg chng ag
HART 7
Device Prole
HART 7
Max dev vars
HART 7
ModelModelModel name + Measurement
Conguration change counter0R
Reset Conguration change agM
Device ProleProcess
automation
device
Max device variables3R
R
R
span in the Sufx Codes
Ex) “EJX110 M”
Device
Variable
Simulation
Diag
Simulate
HART 7
Execution of device variable
simulation
Execute the simulationM
Diag ApplicableAppicable blockage detectionDisabled or EnabledRG
Applicable
Diag DPComp Diag DPCompfDP compensation selectionCompensation or
CompensationWG
Non-compensation
Diag Error Diag ErrorResults detected by ILBD or Heat
RG
trace monitoring
*1: Handling: R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,
D
=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters.
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)
*3: The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.
1
IM 01C25T01-06EN
<5. Parameter Summary>
5-3
FunctionLabelItemContentsDefault value Handling *
Diag Lim Lim fDPmaxUpper limit for Ratio fDP
Lim fDPminLower limit for Ratio fDP
Lim fSPlmaxUpper limit for Ratio fSPl
Lim fSPlminLower limit for Ratio fSPl
Lim fSPhmaxUpper limit for Ratio fSPh
Lim fSPhminLower limit for Ratio fSPh
Lim BlkFmaxUpper limit for BlkF
Lim BlkFminLower limit for BlkF
Lim DPAvgmaxUpper limit for DPAvg
Lim DPAvgminLower limit for DPAvg
Diag ModeDiag ModeILBD operation modeStop, Calculation, or
Diag Option Diag OptionAlarm maskingWG
Diag Output Diag Out OptionOutput mode of 4-20mA when
Diag Fixed Out Val 4-20 mA output when an advanced
Diag Period Diag PeriodSampling period per one Diag count 180 secWG
Diag
Reference
Diag Ref Lim Ref Lim fDPminLower limit of fDP7.0E-10WG
Diag Supp
Count
Diag Variables Ratio fDPSQRT (fDP/Ref fDP).RG
*1: Handling: R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)
*3: The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.
Diag DescriptionMemo eld32 alphanumericsWG
Ref fDPReference value of fDPWG
Ref fDP StatusStatus of Reference fDPRG
Ref fSPlReference value of fSPlWG
Ref fSPl StatusStatus of Reference fSPlRG
Ref fSPhReference value of fSPhWG
Ref fSPh StatusStatus of Reference fSPhRG
Ref BlkFReference value of BlkFWG
Ref BlkF StatusStatus of Reference BlkFRG
Ref DPAvgReference value of DPAvgWG
Ref DPAvg StatusStatus of Reference DPAvgRG
Ref Lim fSPminLower limit of fSPl and fSPh1.0E-10WG
Ref Lim BlkFmaxUpper limit of BlkF0.5WG
Diag Supp CountDetection count to generate an
Ratio fDP StatusStatus of Ratio fDPRG
Ratio fSPlSQRT (fSPl/Ref fSPl).RG
Ratio fSPl StatusStatus of Ratio fSPlRG
Ratio fSPhSQRT (fSPh/Ref fSPh).RG
Ratio fSPh StatusStatus of Ratio fSPhRG
BlkF
BlkF StatusStatus of BlkFRG
DPAvgRatio of the average of differential
DPAvg StatusStatus of DPAvgRG
CRatio fDPCompensated fDPRG
CRatio fDP StatusStatus of CRatio fDPRG
NRatio fDPNon-compensated fDPRG
NRatio fDP StatusStatus of NRatio fDPRG
D
=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters.
an advanced diagnostic alarm is
generated
diagnostic alarm is generated
alarm
Blockage degree characterized in
comparison of high-pressure side
and low-pressure side pressure
uctuation values
pressure/pressure to the maximum
span of an EJX transmitter.
Reference
Off, Burnout, or Fall backOffWG
3.6000 to 21.6000 mA21.6 mAWG
Refer to Table 4.2.3
Refer to Table 4.2.3
Refer to Table 4.2.3
Refer to Table 4.2.3
Refer to Table 4.2.3
Refer to Table 4.2.3
Refer to Table 4.2.3
Refer to Table 4.2.3
Refer to Table 4.2.3
Refer to Table 4.2.3
WG
WG
WG
WG
WG
WG
WG
WG
WG
WG
WG
WG
RG
RG
1
IM 01C25T01-06EN
<5. Parameter Summary>
5-4
FunctionLabelItemContentsDefault value Handling *
Display setup Bar IndicatorBar indicatorOff or OnOnW
Chg power on infoChange the LCD display when
powering on
Disp Out 1LCD output 1PRES, PRES %,
On or Off
M
PRES %W
ENGR.PRES, SP, SP %
Disp Out 2LCD output 2PRES, PRES %,
Not usedW
ENGR.PRES, SP, SP % or
Not used
Disp Out 3LCD output 3(Ditto)Not usedW
Disp Out 4LCD output 4(Ditto)Not usedW
Disp Pres % fnctn% display modeLinear or Sq rootAs specied or
W
Linear
Disp Pres % Reso% display resolutionNormal or High resolutionNormalW
Engr expUser set exponent---, x10, x100, x1000--- or as
W
specied
Engr LRVUser set lower range valueUnit specied in Set Engr Unit As speciedW
Engr pointDecimal place for user set0 to 42W
Engr URVUser set upper range valueUnit specied in Set Engr Unit As speciedW
Modify Engr UnitUser set engineering unitM
Pres disp pointDecimal place for differential
0 to 42W
pressure
Set Engr UnitEngineering unit selectM
SP disp pointDecimal place for static pressure0 to 42WD
Squawk
Retry Time, Event Max
Update Time and Event
Debounce Interval
M
*1: Handling: R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,
D
=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters.
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)
*3: The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.
1
IM 01C25T01-06EN
<5. Parameter Summary>
5-5
FunctionLabelItemContentsDefault value Handling *
Event
Notication
Event Notication
Retry Time
HART 7
Max Update Time
HART 7
Event Debounce
Interval
HART 7
Acknowledge Event
Event Notication Retry TimeR
Max Update Time for Event
Notication
Event Debounce IntervalDebounce Interval to detect
an event.
Acknowledge Event NoticationW
R
R
Notication
HART 7
Event Status
HART 7
Event Status0x00 Approved event or no
event
0x10 Conguration changed
R
event pending
0x20 Device status event
pending
0x40 More status available
event pending
Event Number
HART 7
Time First Unack
Event NumberW
Time First Unack Event TriggeredW
Event Triggered
HART 7
Latched Cfg chng
Latched Cfg chng countW
count
HART 7
Latched Device
Device status when event occurredW
Status
HART 7
Latched Status
group 1 to 10
HART 7
Field device status when event
occured
W
Latched Ext dev
status
HART 7
Latched Device
Diagnostic Status 0
HART 7
Latched Device
Diagnostic Status 1
HART 7
Latched AO
saturated
HART 7
Latched AO xed
HART 7
Flg temp Flg tempCalculated ange temperature
RG
value
Flg Temp Coef Flg Temp Coef0WG
Flg Temp Lim Flg Temp Hi Alart
Upper limit of Flange temperature
120 °C (deg C)
WG
Val
Flg Temp Lo Alart
Lower limit of Flange temperature-40 °C (deg C)WG
Val
*1: Handling: R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,
D
=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters.
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)
*3: The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.
1
IM 01C25T01-06EN
<5. Parameter Summary>
5-6
FunctionLabelItemContentsDefault value Handling *
Fluct Variables fDPAverage value of the sum of
RG
squares of differential pressure/
pressure uctuations
fDP StatusStatus of fDPRG
fSPlAverage value of the sum of
RG
squares of low-pressure-sidestatic
pressure uctuations
fSPl StatusStatus of fSPlRG
fSPhAverage value of the sum of
RG
squares of high-pressure-side
static pressure uctuations
fSPh StatusStatus of fSPhRG
Loop testLoop testTest output settingWithin AO lower and upper
M
limits
Test Auto Release
Time
Auto release time for the test
function. Coverage is Loop test,
10min, 30min, 60min, 3h,
6h, 12h
10 minW
DO test and Device Variable
Simulation.
Low cutLow cutLow cut0.00 to 20.00%Refer to
W
subsection
3.2.6
Low cut modeLow cut modeLinear or ZeroLinearW
Master testMaster testSoftware reset and self testM
MessageMessageMessage32 alphanumericsAs speciedW
Number of
requested
preambles
Optional
function
Piping
Num req preamsNumber of requested preamblesR
Num resp preams
HART 7
Option Password
Number of response preambles5W
Optional function activation
password
W
H/L SwapImpulse piping accessing direction Normal or ReverseNormalWD
orientation
Poll addressPoll addrPoll address for multidrop use0 to 15(HART 5), 0 to
0W
63(HART 7)
Loop current mode
HART 7
Process Alerts Digital Output
EJX
DO Select
EJX
DO Signal type
EJX
DO Test
EJX
Pres Alert ModeAlert Mode for differential pressure Off, Hi Al Detect,Lo Al Detect,
Loop current mode in Multi Drop
(Disabled, Enabled)DisabledW
mode
Display of contact outputOff or OnOffRA
Contact output selectOff, Combination of Pres, SP
OffWA
and Temp
Signal type selectON WHEN AL. DETECT, OFF
WHEN AL. DETECT
ON WHEN AL.
DETECT
WA
Test output contactStatus High, Status Low, ExitMA
OffW
Hi/Lo Al Detect
Hi Alert ValHigh alert value for differential
pressure
Lo Alert ValLow alert value for differential
pressure
SP Alert ModeAlert Mode for static pressureOff, Hi Al Detect,Lo Al Detect,
Set the threshold value for
high side alarm
Set the threshold value for
low side alarm
W
W
OffWD
Hi/Lo Al Detect
SP Hi Alert ValHigh alert value for static pressureSet the threshold value for
WD
high side alarm
SP Lo Alert ValLow alert value for static pressureSet the threshold value for
WD
low side alarm
Temp Alert ModeAlert Mode for temperatureOff, Hi Al Detect,Lo Al Detect,
OffW
Hi/Lo Al Detect
*1: Handling: R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,
D
=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters.
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)
*3: The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.
1
IM 01C25T01-06EN
<5. Parameter Summary>
5-7
FunctionLabelItemContentsDefault value Handling *
Process Alerts Temp Hi Alert ValHigh alert value for temperatureSet the threshold value for
120°C (deg C)W
high side alarm
Temp Lo Alert ValLow alert value for temperatureSet the threshold value for
-40°C (deg C)W
low side alarm
Process
variables
Engr DispUser scaled valueR
Engr UnitUser set engineering unitUnit specied in Set Engr Unit
8 alphanumerics
Loop Current (DD)
AO (DTM)
HART 7
Loop Current Data
Quality
HART 7
Loop Current Limit
Status
HART 7
PV (DD)
Pres (DTM)
PV (Pres) Data
Quality
HART 7
PV (Pres) Limit
Status
HART 7
PV Update time
Loop current value
3.6 to 21.6 mAR
(Analog Output Current)
Device variable process data
quality
Device variable limit statusDevice variable limit status of
Device variable process data
quality of Loop Current (mA)
GoodR
Not limitedR
Loop Current (mA)
Pressure/Differential pressure
value
Device variable process data
quality
Device variable limit statusDevice variable limit status of
Device variable process data
quality of pressure
GoodR
Not limitedR
pressure
PV (Pres) Update time period45 msR
period (DD)
Update time period
(DTM)
HART 7
% range (DD)
Pressure value in %-2.50 to 110.00%R
Pres % (DTM)
HART 7
% rnge (Percent
Range) Data
Quality
HART 7
% rnge (Percent
Range) Limit Status
HART 7
Device variable process data
quality
Device variable process data
quality of % range (Percent
Range)
Device variable limit statusDevice variable limit status of
% range (Percent Range)
GoodR
Not limitedR
SV (DD), SP (DTM) Static pressure valueRD
SP %Static pressure value in %-10.0 to 100.00 %RD
SV (SP) Data
Quality
HART 7
SV (SP) Limit
Status
HART 7
SV Update time
Device variable process data
quality
Device variable limit statusDevice variable limit status of
Device variable process data
quality of SV (SP)
GoodR
Not limitedR
SV (SP)
SV (SP) Update time period360 msR
period (DD)
SP update time
(DTM)
HART 7
1
R
R
*1: Handling: R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,
D
=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters.
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)
*3: The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.
IM 01C25T01-06EN
<5. Parameter Summary>
5-8
FunctionLabelItemContentsDefault value Handling *
Process
variables
TV (DD)
Snsr temp (DTM)
TV (Temp) Data
Quality
HART 7
TV (Temp) Limit
Status
HART 7
TV Update time
Temperature valueCapsule temperatureR
Device variable process data
quality
Device variable limit statusDevice variable limit status of
Device variable process data
quality of TV (Temp)
GoodR
Not limitedR
TV (Temp)
TV (Temp) Update time period1sR
period (DD)
Temp update time
(DTM)
HART 7
Range change Apply valuesRe range for measured pressure4 mA, 20 mA, or ExitM
Min SpanMinimum span for pressureR
LRVLower range value for pressureAs speciedW
LSLLower sensor limit for pressureR
URVUpper range value for pressureAs speciedW
USLUpper sensor limit for pressureR
Self testSelf testSelf-diagnosticsM
Sensor trimClear P snsr trimReset pressure trim to factory
M
setting
Clear SP snsr trimReset SP trim to factory settingMD
P LTDLower pressure trim deviationR
P LTPLower temperature trim pointR
P UTDUpper pressure trim deviationR
P UTPUpper temperature trim pointR
Pres trimPressure trimM
Pres Zero trimZeroingM
SP LTDLower SP trim deviationRD
SP LTPLower SP trim pointRD
SP UTDUpper SP trim deviationRD
SP UTPUpper SP trim pointRD
Static Pres trimStatic pressure trimMD
Trim DateTrim date**/**/**W
Trim DescTrim description16 alphanumericsW
Trim LocTrim location8 alphanumericsW
Trim WhoTrim person8 alphanumericsW
Set Diag Mode Set Diag ModeILBD operation modeStop, Calculation, or
WG
Reference
Signal
characterizer
Num of pointsNumber of coordinates0 to 99W
Point settingCoordinates editorM
S.C. Signal characterizer permissionDisabled or EnabledDisabledW
X EndEnd point of X100.00%R
X StartStart point of X0.00%R
Y EndEnd point of Y100.00%R
Y StartStart point of Y0.00%R
*1: Handling: R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,
D
=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters.
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)
*3: The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.
1
IM 01C25T01-06EN
<5. Parameter Summary>
5-9
FunctionLabelItemContentsDefault value Handling *
SP setupA/G SelectGauge/Abs select for static
Gauge or AbsoluteAbsoluteWD
pressure
Atm. Pres ValueConversion coefcient101.3 kPaWD
SP Apply valuesRerange for static pressure“0%, 100%, or Exit”MD
SP DampDamping time constant for SP0.00 to 100.002.00 sWD
SP H/L SelectH/L select for static pressureHigh or LowHighWD
SP Min SpanMinimum span for static pressureRD
SP LRVLower range value for static
Within measurement range0.0 MPaWD
pressure
SP LSLLower sensor limit for static
RD
pressure
*3
SP URV
Upper range value for static
Within measurement rangeWD
pressure
SP USLUpper sensor limit for static
RD
pressure
StatusDevice StatusCurrent operating statusR
Status group 1Device status information for
Display the hardware errorR
hardware
Status group 2Device status information for
Display the hardware errorR
hardware
Status group 3Device status information for
process
Status group 4Device status information for
process
Status group 5Device status information for
process
Status group 6
Status group 7
Status group 8
Status group 9
Status group 10
HART 7
Ext dev status
HART 7
Device status information for data
Device status information for data
Device status information for data
Device status information for data
Device status information for data
Extended Device StatusR
Display the process error
(Out of specication)
Display the process error
(Out of setting range)
Display the process error
(Alarm)
Display the setting errorR
Display the setting errorR
Display the diagnostic alarmR
Display the diagnostic alarmR
Display the simulation modeR
R
R
R
Time StampTime Stamp00:00:00R
TagTagTag number8 alphanumericsAs speciedW
Long tag
HART 7
Temperature
compensation
Temperature
sensor
Transfer
T.Z. Cmp mode Temperature compensation modeOff or OnOff W
Temp Zero Zero shift compensation–99.999 to 99.999%/degC0.000%/degCW
Amp temp Amplier temperatureR
Snsr temp Capsule temperatureR
Xfer fnctnOutput modeLinear or Sq rootAs specied or
function
UnitsUnitPressure, Differential pressure unitAs specied or
Enable wrt 10minWrite protection release8 alphanumericsM
New passwordUser set password for write
8 alphanumericsM
protection
Write protectWrite protection indicatorYes or NoNoR
*1: Handling: R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, G=Applicable for option code DG6,
D
=Applicable for differential pressure transmitters. Do not change these parameters for pressure transmitters.
*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)
*3: The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specications section in each user’s manual.
1
IM 01C25T01-06EN
<Appendix1. Safety Instrumented Systems Installation>
A1-1
Appendix 1. Safety Instrumented Systems
Installation
The calibration of the transmitter must be performed
WARNING
after parameters are set.
The contents of this appendix are cited from
exida.com safety manual on the transmitters
specically observed for the safety transmitter
purpose. When using the transmitter for Safety
Instrumented Systems (SIS) application, the
instructions and procedures in this section must
be strictly followed in order to preserve the
transmitter for that safety level.
A1.1 Scope and Purpose
This section provides an overview of the user
responsibilities for installation and operation of
the transmitter in order to maintain the designed
safety level for Safety Instrumented Systems (SIS)
applications. Items that will be addressed are proof
testing, repair and replacement of the transmitter,
reliability data, lifetime, environmental and
application limits, and parameter settings.
A1.2 Using the transmitter for an
SIS Application
A1.2.1 Safety Accuracy
The transmitter has a specied safety accuracy
of 2%. This means that the internal component
failures are listed in the device failure rate if they will
cause an error of 2% or greater.
A1.2.2 Diagnostic Response Time
The transmitter will report an internal failure within 5
seconds of the fault occurrence.
A1.2.4 Required Parameter Settings
The following parameters need to be set in order to
maintain the designed safety integrity.
Table A1.1 Required Parameter Settings
ItemDescription
Burnout direction
switch
Write protection
switch
To specify if the output should go
21.6 mA or higher or 3.6 mA or lower
upon detection of an internal failure.
The write function should be
disabled.
A1.2.5 Proof Testing
The objective of proof testing is to detect failures
within the transmitter that are not detected by the
diagnostics of the transmitter. Of main concern
are undetected failures that prevent the safety
instrumented function from performing its intended
function. See table A1.2 for proof testing method.
The frequency of the proof tests (or the proof
test interval) is to be determined in the reliability
calculations for the safety instrumented functions
for which the transmitter is applied. The actual
proof tests must be performed more frequently or
as frequently as specied in the calculation in order
to maintain required safety integrity of the safety
instrumented function.
The following tests need to be specically executed
when a proof test is performed. The results of
the proof test need to be documented and this
documentation should be part of a plant safety
management system. Failures that are detected
should be reported to Yokogawa.
A1.2.3 Setup
During installation the transmitter must be setup
with engineering units parameters. This is typically
done with a handheld terminal. These parameters
must be veried during the installation to insure
that the correct parameters are in the transmitter.
Engineering range parameters can be veried by
reading these parameters from the optional local
display or by checking actual calibration of the
transmitter.
The personnel performing the proof test of the
transmitter should be trained in SIS operations
including bypass procedures, transmitter
maintenance, and company management of
change procedures.
IM 01C25T01-06EN
<Appendix1. Safety Instrumented Systems Installation>
1. Follow all Management of Change
procedures to bypass logic solvers if
necessary.
2. Execute HART/BRAIN command to
send value to high alarm (21.5 mA) and
verify that current has reached this level.
3. Execute HART/BRAIN command to
send value to low alarm (3.6 mA) and
verify that current has reached this level.
4. Restore logic solvers operation and
verify.
Perform three point calibration along with
the functional test listed above.
• Handheld terminalProof Test Coverage
=52%
• Handheld terminal
• Calibrated pressure
source
Proof Test Coverage
=99%
The output needs to be
monitored to assure that the
transmitter communicates
the correct signal.
A1-2
A1.2.6 Repair and Replacement
If repair is to be performed with the process online
the transmitter will need to be bypassed during the
repair. The user should setup appropriate bypass
procedures.
In the unlikely event that the transmitter has a
failure, the failures that are detected should be
reported to Yokogawa.
When replacing the transmitter, the procedure in the
installation manual should be followed.
The personnel performing the repair or replacement
of the transmitter should have a sufcient skill level.
A1.2.7 Startup Time
The transmitter generates a valid signal within 1
second of power-on startup.
A1.2.8 Firmware Update
In case rmware updates are required, they
will be performed at factory. The replacement
responsibilities are then in place. The user will not
be required to perform any rmware updates.
A1.2.9 Reliability Data
A detailed Failure Mode, Effects, and Diagnostics
Analysis (FMEDA) report is available from
Yokogawa with all failure rates and failure modes.
The development process of the transmitter is
certied up to SIL3, allowing redundant use of
the transmitter up to this Safety Integrity Level,
depending the PFDavg calculation of the entire
Safety Instrumented Function.
When using the transmitter in a redundant
conguration, the use of a common cause factor
(β-factor) of 2% is suggested. (However, if the
redundant transmitters share an impulse line or if
clogging of the separate impulse lines is likely, a
common cause factor of 10% is suggested.)
Note that the failure rates of the impulse lines need
to be accounted for in the PFDavg calculation.
A1.2.10 Lifetime Limits
The expected lifetime of the transmitter is 50
years. The reliability data listed the FMEDA report
is only valid for this period. The failure rates of the
transmitter may increase sometime after this period.
Reliability calculations based on the data listed in
the FMEDA report for transmitter lifetimes beyond
50 years may yield results that are too optimistic,
i.e. the calculated Safety Integrity Level will not be
achieved.
A1.2.11 Environmental Limits
The environmental limits of the transmitter are
specied in the user’s manual IM 01C25.
The transmitter is certied up to SIL2 for use
in a simplex (1oo1) conguration, depending
on the PFDavg calculation of the entire Safety
Instrumented Function.
A1.2.12 Application Limits
The application limits of the transmitter are specied
in the user’s manual IM 01C25. If the transmitter is
used outside of the application limits, the reliability
data listed in A1.2.9 becomes invalid.
IM 01C25T01-06EN
<Appendix1. Safety Instrumented Systems Installation>
A1-3
A1.3 Denitions and
Abbreviations
A1.3.1 Denitions
Safety Freedom from unacceptable
risk of harm
Functional Safety The ability of a system to carry
out the actions necessary
to achieve or to maintain a
dened safe state for the
equipment/machinery/plant/
apparatus under control of the
system
Basic Safety The equipment must be
designed and manufactured
such that it protects against
risk of damage to persons
by electrical shock and other
hazards and against resulting
re and explosion. The
protection must be effective
under all conditions of the
nominal operation and under
single fault condition
A1.3.2 Abbreviations
FMEDA Failure Mode, Effects and Diagnostic
Analysis
SIF Safety Instrumented Function
SIL Safety Integrity Level
SIS Safety Instrumented System
SLC Safety Lifecycle
Verication The demonstration for each
phase of the life-cycle that the
(output) deliverables of the
phase meet the objectives
and requirements specied by
the inputs to the phase. The
verication is usually executed
by analysis and/or testing
Validation The demonstration that the
safety-related system(s) or
the combination of safetyrelated system(s) and external
risk reduction facilities meet,
in all respects, the Safety
Requirements Specication.
The validation is usually
executed by testing
Safety Assessment The investigation to arrive at a
judgment -based on evidenceof the safety achieved by
safety-related systems
Further denitions of terms used for safety
techniques and measures and the description of
safety related systems are given in IEC 61508-4.
IM 01C25T01-06EN
<Appendix2. ILBD Check List>
Appendix 2. ILBD Check List
Fill out the below checklist according to the operation ow of the ILBD in order to keep the important
information for the blockage detection.
Checklist (1/5)
No.ItemsParametersResultExample
14-20 mA Analog Signal Setting
• Select the output mode when an alarm is
generaed.
2Status Output
3Stability of Pres
(differential pressure/pressure)
under normal condition
Diag Out Option
Diag Fixed Out ValmA21.6 mA
DO Select
StatusGood
Off:
Burnout:
Fall back:
Pres: SP: Temp: Diag: All:
A2-1
• Check that the status of Pres is “GOOD”.
• Check the maximum and minimum values of
Pres.
4fDP under normal condition
• Check that the value of fDP is more than
-10
7x10
.
5Start to obtain Reference values
• Set "Reference" to Diag Mode.
6End of Reference Value Sampling
• Check that Diag Mode is “Calculation” after
the time set to "Diag Period" passed.
7Alarm setting
• Record the status of Checkbox in Diag Option.
Pres
fDP
Diag Mode
Diag Mode
Diag Option
A Blocking
Large Fluct L
Large Fluct H
L Side Blocking
H Side Blocking
B Blocking
Invalid Ref F
Invalid Ref SPH
Invalid Ref SPL
Invalid Ref DP
ILBD over range
Max.:
Min.:
Max.: 12.3 kPa
Min.: 12.1 kPa
IM 01C25T01-06EN
<Appendix2. ILBD Check List>
Checklist (2/5)
No.ItemsParametersResultExample
Alarm status
8
• Check the alarm status shown in Diag Error.
• Check that the alarm status of “ILBD over
range” is not shown in Diag Error.
ILBD parameters
9
• Record the values of parameters for ILBD
operation.
• Check the status of parameters for ILBD
operation.