Yokogawa EJA440E User Manual

User’s Manual
DPharp HART 5/HART 7 Communication Type (EJXA, EJAE)
IM 01C25T01-06EN
IM 01C25T01-06EN
4th Edition
DPharp HART 5/HART 7 Communication Type (EJXA, EJAE)
IM 01C25T01-06EN 4th Edition
Contents
1. Introduction ............................................................................................... 1-1
Regarding This Manual ....................................................................................1-1
1.1 Safe Use of This Product .................................................................................1-2
1.2 Warranty .............................................................................................................1-2
1.3 Abbreviation and Marking ................................................................................1-3
1.4 Applicable Conguration Files ........................................................................1-4
1.5 ATEX Documentation .......................................................................................1-5
2. Connection ................................................................................................ 2-1
2.1 Integral Indicator Display When Powering On ..............................................2-1
2.2 HART Protocol Revision ..................................................................................2-1
2.3 Device Description (DD) on a Conguration Tool and
Transmitter Device Revision............................................................................2-2
2.4 Set the parameters using DTM ........................................................................2-3
2.5 Interconnection Between DPharp and the HART Conguration Tool ........2-4
2.6 Power Supply Voltage and Load Resistance .................................................2-4
3. Parameter Setting ..................................................................................... 3-1
3.1 Menu Tree ..........................................................................................................3-1
3.1.1 Group I: DD and DTM (excluding EJX HART 5 DTM based on FDT1.2)
...........................................................................................................3-1
3.1.2 Group II: EJX HART 5 DTM based on FDT1.2 ..................................3-8
3.2 Basic Setup ......................................................................................................3-12
3.2.1 Tag and Device Information .............................................................3-12
3.2.2 Unit ...................................................................................................3-12
3.2.3 Range Change .................................................................................3-13
3.2.4 Output Mode ....................................................................................3-13
3.2.5 Damping Time Constant Setup ........................................................3-13
3.2.6 Output Signal Low Cut Mode Setup ................................................3-14
3.2.7 Impulse Line Connection Orientation Setup ....................................3-14
3.2.8 Static Pressure Setup ......................................................................3-15
3.3 Detailed Setup .................................................................................................3-15
3.3.1 Bi-directional Flow Measurement ....................................................3-15
3.3.2 Analog Output Signal Adjustable Range .........................................3-16
4th Edition: June 2013 (YK) All Rights Reserved, Copyright © 2010, Yokogawa Electric Corporation
IM 01C25T01-06EN
3.3.3 Integral Indicator Display Mode .......................................................3-16
3.3.4 Integral Indicator Scale Setup ..........................................................3-16
3.3.5 Unit for Displayed Temperature .......................................................3-18
3.3.6 Sensor Trim ......................................................................................3-18
3.3.7 Trim Analog Output ..........................................................................3-20
3.3.8 External Switch Mode ......................................................................3-20
3.3.9 CPU Failure Burnout Direction and Hardware Write Protect ..........3-21
3.3.10 Software Write Protection ................................................................3-21
3.3.11 Signal Characterizer ........................................................................3-22
3.3.12 Alarm ................................................................................................3-22
3.3.13 Status Output (only for EJX series: option code AL)
EJX
............3-23
3.3.14 Capillary Fill Fluid Density Compensation ......................................3-24
3.3.15 Test Output, Simulation, and Squawk ..............................................3-25
3.3.16 Burst Mode .......................................................................................3-27
3.3.16.1 In the case of using HART 5 ...........................................3-27
3.3.16.2 In the case of using HART 7 ...........................................3-27
3.3.17 Multidrop Mode ................................................................................3-32
3.3.17.1 Setting on HART 5 ..........................................................3-32
3.3.17.2 Setting on HART 7 ..........................................................3-33
3.3.18 Switching HART Protocol Revision .................................................3-33
ii
4. Diagnostics ............................................................................................... 4-1
4.1 Self-Diagnostics ................................................................................................4-1
4.1.1 Identify Problems by Using HART Conguration Tool .......................4-1
4.1.2 Checking with Integral Indicator .........................................................4-2
4.1.3 Status information available for HART 7
4.2 Advanced Diagnostics (Only for EJX series)
4.2.1 Multi-sensing Process Monitoring ......................................................4-3
4.2.2 Impulse Line Blockage Detection (ILBD) ...........................................4-3
4.2.2.1 Blockage Detection ...........................................................4-6
4.2.2.2 Combination of Reference Result and Blockage Detection
..........................................................................................4-8
4.2.2.3 Operation Parameters ......................................................4-9
4.2.2.4 Operating Procedure ...................................................... 4-11
4.2.2.5 Alarm and Alert Setting ...................................................4-12
4.2.2.6 Condition Check .............................................................4-14
4.2.2.7 Obtain Reference Values ................................................4-15
4.2.2.8 Capability Test of Blockage Detection Operation ...........4-16
4.2.2.9 Start ILBD Operation ......................................................4-16
4.2.2.10 Tuning .............................................................................4-17
4.2.2.11 Reset of Reference Value ...............................................4-18
4.2.2.12 ILBD Parameter List .......................................................4-19
HART 7
EJX
............................4-2
.....................................4-3
IM 01C25T01-06EN
4.2.3 Heat Trace Monitoring......................................................................4-21
4.2.3.1 Flg Temp Coef Setting ....................................................4-21
4.2.3.2 Out of Temperature Measurement Range ......................4-22
4.2.3.3 Parameter Lists for Heat Trace Monitoring .....................4-23
4.3 Alarms and Countermeasures ......................................................................4-24
5. Parameter Summary ................................................................................ 5-1
Appendix 1. Safety Instrumented Systems Installation ............................A1-1
A1.1 Scope and Purpose ....................................................................................... A1-1
A1.2 Using the transmitter for an SIS Application .............................................. A1-1
A1.2.1 Safety Accuracy ...............................................................................A1-1
A1.2.2 Diagnostic Response Time ..............................................................A1-1
A1.2.3 Setup ................................................................................................A1-1
A1.2.4 Required Parameter Settings ..........................................................A1-1
A1.2.5 Proof Testing ....................................................................................A1-1
A1.2.6 Repair and Replacement .................................................................A1-2
A1.2.7 Startup Time .....................................................................................A1-2
A1.2.8 Firmware Update .............................................................................A1-2
A1.2.9 Reliability Data .................................................................................A1-2
A1.2.10 Lifetime Limits ..................................................................................A1-2
A1.2.11 Environmental Limits .......................................................................A1-2
A1.2.12 Application Limits .............................................................................A1-2
A1.3 Denitions and Abbreviations ...................................................................... A1-3
A1.3.1 Denitions ........................................................................................A1-3
A1.3.2 Abbreviations ...................................................................................A1-3
iii
Appendix 2. ILBD Check List ........................................................................A2-1
Revision Information
IM 01C25T01-06EN
<1. Introduction>

1. Introduction

1-1
Thank you for purchasing the DPharp EJX series pressure transmitter/EJA series pressure transmitter(“transmitter”).
The transmitters are precisely calibrated at the factory before shipment. To ensure both safety and efciency, please read this manual carefully before operating the instrument. This manual describes the HART protocol communication functions of the transmitter and explains how to set the parameters for the transmitters using the HART conguration tool. For information on the installation, wiring, and maintenance of the transmitters, please refer to the user’s manual of each model.
WARNING
When using the transmitter in a Safety Instrumented Systems (SIS) application, refer to Appendix 1 in this manual. The instructions and procedures in the appendix must be strictly followed in order to maintain the designed safety integrity of the transmitter.
• Please note that changes in the specications, construction, or component parts of the instrument may not immediately be reected in this manual at the time of change, provided that postponement of revisions will not cause difculty to the user from a functional or performance standpoint.
• The following safety symbols are used in this manual:
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.

Regarding This Manual

• This manual should be provided to the end user.
• The contents of this manual are subject to change without prior notice.
• All rights reserved. No part of this manual may be reproduced in any form without Yokogawa’s written permission.
• Yokogawa makes no warranty of any kind with regard to this manual, including, but not limited to, implied warranty of merchantability and tness for a particular purpose.
• If any question arises or errors are found, or if any information is missing from this manual, please inform the nearest Yokogawa sales ofce.
• The specications covered by this manual are limited to those for the standard type under the specied model number break-down and do not cover custom-made instruments.
IMPORTANT
Indicates that operating the hardware or software in this manner may damage it or lead to system failure.
NOTE
Draws attention to information essential for understanding the operation and features.
IM 01C25T01-06EN
<1. Introduction>
1-2

1.1 Safe Use of This Product

For the safety of the operator and to protect the instrument and the system, please be sure to follow this manual’s safety instructions when handling this instrument. If these instructions are not heeded, the protection provided by this instrument may be impaired. In this case, Yokogawa cannot guarantee that the instrument can be safely operated. Please pay special attention to the following points:
(a) Installation
• This instrument may only be installed by an engineer or technician who has an expert knowledge of this device. Operators are not allowed to carry out installation unless they meet this condition.
• With high process temperatures, care must be taken not to burn yourself by touching the instrument or its casing.
• Never loosen the process connector nuts when the instrument is installed in a process. This can lead to a sudden, explosive release of process uids.
• When draining condensate from the pressure detector section, take appropriate precautions to prevent the inhalation of harmful vapors and the contact of toxic process uids with the skin or eyes.
• When removing the instrument from a hazardous process, avoid contact with the process uid and the interior of the meter.
• All installation shall comply with local installation requirements and the local electrical code.
(b) Wiring
• The instrument must be installed by an engineer or technician who has an expert knowledge of this instrument. Operators are not permitted to carry out wiring unless they meet this condition.
• Before connecting the power cables, please conrm that there is no current owing through the cables and that the power supply to the instrument is switched off.
(c) Operation
• Wait 10 min. after the power is turned off before opening the covers.
(d) Maintenance
• Please carry out only the maintenance procedures described in this manual. If you require further assistance, please contact the nearest Yokogawa ofce.
• Care should be taken to prevent the build up of dust or other materials on the display glass and the name plate. To clean these surfaces, use a soft, dry cloth.
(e) Modication
• Yokogawa will not be liable for malfunctions or damage resulting from any modication made to this instrument by the customer.

1.2 Warranty

• The warranty shall cover the period noted on the quotation presented to the purchaser at the time of purchase. Problems occurring during the warranty period shall basically be repaired free of charge.
• If any problems are experienced with this instrument, the customer should contact the Yokogawa representative from which this instrument was purchased or the nearest Yokogawa ofce.
• If a problem arises with this instrument, please inform us of the nature of the problem and the circumstances under which it developed, including the model specication and serial number. Any diagrams, data and other information you can include in your communication will also be helpful.
• The party responsible for the cost of xing the problem shall be determined by Yokogawa following an investigation conducted by Yokogawa.
• The purchaser shall bear the responsibility for repair costs, even during the warranty period, if the malfunction is due to:
- Improper and/or inadequate maintenance by
the purchaser.
- Malfunction or damage due to a failure
to handle, use, or store the instrument in accordance with the design specications.
- Use of the product in question in a location
not conforming to the standards specied by Yokogawa, or due to improper maintenance of the installation location.
- Failure or damage due to modication or
repair by any party except Yokogawa or an approved representative of Yokogawa.
- Malfunction or damage from improper
relocation of the product in question after delivery.
- Reason of force majeure such as res,
earthquakes, storms/oods, thunder/ lightening, or other natural disasters, or disturbances, riots, warfare, or radioactive contamination.
IM 01C25T01-06EN
<1. Introduction>
1-3

1.3 Abbreviation and Marking

The following models, HART protocol revisions and conguration les are applied in this manual.
HART
Model
EJAE
EJXA*
*: Not applicable for EJX9A
In order to classify multiple models, HART protocol revisions, or conguration les, abbreviated words or marks are used as below in this manual.
■ Applied models
• The following expression is used instead of model name.
[Model: EJAE] EJA series or EJA
[Model: EJXA (excluding EJX9A)] EJX series or EJX
EJX
• applied for EJX series only.
■ HART protocol revision
• Two HART protocol revisions are expressed for short as below.
Protocol
Revision
5 7 5 7
Conguration le
• DD (Device Description)
• DTM (FDT1.2)
• DTM (FDT2.0)
mark indicates specication or function
■ Conguration le
Three conguration les are applied in this manual.
• DD stands for Device Description (le).
• This manual covers two revision DTM (Device Type Manager) les based on FDT (Field Device Tool) standard. The difference of revisions is indicated as follows.
[DTM for FDT 1.2] DTM (FDT1.2) or [1.2] [DTM for FDT2.0] DTM (FDT2.0) or [2.0]
The root referring to a parameter is classied to Group I or II according to applied conguration le.
Conguration
le
DD
DTM (FDT2.0) I
Note: Only DTM (FDT1.2) for EJX with HART 5 is classied to
Group II.
EJA EJX
HART 5 HART 7 HART 5 HART 7
I
I
IDTM (FDT1.2) II
As the above, two roots referring to a parameter is shown in this manual.
Procedure to call up xxx parameter
DD and DTM (excluding EJX_HART 5[1.2])
EJX_HART 5[1.2] DTM …→…
[Root Menu] →…
HART protocol revision 5: HART 5 HART protocol revision 7: HART 7
HART 7
mark indicates specication or function applied for HART 7 only. Refer to section 2.2 for typical functions for HART 7.
HART 5
mark indicates specication or function applied for HART 5 only.
For parameter menu tree, refer to section 3.1.
IM 01C25T01-06EN
<1. Introduction>
1.4 Applicable Conguration Files
DD
File Applied device
File name
010 =2 or later 0a0 =1 or later 030 =3 or later 0a0 =2 or later
DD revision
()
Model
EJA series
EJX series
DTM
File Applied device
File name
EJA-NEXT
HART DTM
DTM
revision
3.3.0.140 or later
*2
EJA-NEXT
FDT2.0
5.0.0.0 or later
*3
HART DTM
EJA-NEXT
HART 7 DTM
3.3.0.140 or later
*2
EJA-NEXT
FDT2.0
5.0.0.0 or later
*3
HART 7 DTM
EJXV3.1 1.4.160.8 or later
EJX FDT2.0
HART DTM
EJX HART 7
DTM
EJX FDT2.0
HART 7 DTM
*1: The DTM is included in Yokogawa DTM Library HART 2012-2/Device Files R3.03.03 or later. *2: The DTM is included in Yokogawa Device DTM Library 2.3/Device Files R3.03.03 or later. *3: The DTM is included in Device DTM Library 4.0 or later.
5.0.0.0 or later
3.3.0.140 or later
5.0.0.0 or later
*1
*3
*2
*3
FDT
revision
FDT1.2
FDT2.0
FDT1.2
FDT2.0
FDT1.2
FDT2.0
FDT1.2
FDT2.0
HART protocol
revision
5 EJA-NEXT (0x5C) 1 7 EJA-NEXT(0x375C) 10 5 EJX (0x51) 3 7 EJX (0x3751) 10
Model
EJA series
EJX series
HART
protocol
revision
5
7
5
7
Device type
Device type
EJA-NEXT
(0x5C)
EJA-NEXT
(0x375C)
EJX
(0x51)
EJX
(0x3751)
1-4
Device
revision
Device
revision
1
10
3
10
Refer to section 2.2 to 2.4 for conrmation of each revision number.
IM 01C25T01-06EN
<1. Introduction>

1.5 ATEX Documentation

This is only applicable to the countries in European Union.
1-5
GB
DK
E
NL
SK
CZ
I
LT
LV
EST
PL
SF
D
SLO
P
H
F
BG
RO
S
M
GR
IM 01C25T01-06EN
<2. Connection>

2. Connection

2.1 Integral Indicator Display When Powering On

For models with the integral indicator code “D”, the display shows all segments in the LCD and then changes to the displays shown below sequentially.
All segments display
Model name (3 s)

2.2 HART Protocol Revision

NOTE
LCD display can be set to “All segments display” only.
• Procedure to call up the display
DD (HART 5/7) DTM (HART 7 /EJA:HART 5)
DTM
(EJX:HART 5)
ON
OFF
[Root Menu] (Refer to subsection
3.1.1) → Detailed setup → Display condition → Chg power on info
Conguration → Local Display → Chg power on info
Show all segments display, Model name, Communication Protocol, and Device Revision when powering on.
Show all segments display when powering on.
2-1
Communication Protocol (3 s)
Device Revision (3 s)
F0200.ai
Either “5” or “7” is displayed on the “Communication Protocol” display as HART protocol revision followed by device revision number on the “Device Revision” display.
NOTE
This function is available for software revision
2.02 or later. Software revision can be checked by the following procedure.
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu](Refer to subsection
3.1.1) → Review → Software rev
Conguration → Device information1 → Software rev
NOTE
In this User’s Manual, HART protocol revision 5 and 7 are described as HART 5 and HART 7 respectively.
For the models with the output signal code “-J”, HART protocol revision 5 or 7 is selectable. The protocol revision is set as specied in the order.
The typical function which is available by HART protocol revision 7 is listed as follows. Refer to HART 7 description in this document or
HART 7
mark
for detail.
• Long Tag Supporting Up to 32 Characters Long tag secures a better asset management
with abundant digits in its software.
• Enhanced Burst Mode and Event Notication Advanced burst mode includes the variety
of transmission setting by specifying burst variables, update period, and message trigger mode, and event notication function gives you alert signal based on the status change in preset values and self-diagnosis.
• Squawk Identifying the transmitter by displaying the
particular pattern on LCD
• Multidrop Communication Up to 63 transmitters can be connected. An
analog signal output available for one device in a loop.
How to conrm protocol revision is shown below.
There are three ways to conrm the protocol revision set to the transmitter.
IM 01C25T01-06EN
<2. Connection>
F0201.ai
: Refer to USER'S MANUAL.
Made in Japan TOKYO 180-8750 JAPAN
MODEL SUFFIX
SUPPLY OUTPUT MWP
mA DC
V DC
STYLE
CAL RNG
NO.
XXX - - - XX
Revision No.
(a) Conrmation on the name plate The last numerical number engraved after
Serial number and year of production shows HART protocol revision number at the shipment which is shown in Figure 2.1.
NOTE
HART 7 communication is supported by FieldMate R2.02 or later.
NOTE
When the output signal code of the transmitter is “-J”, HART protocol revision can be changed. Refer to subsection 3.3.18 about the procedure of the revision change of HART 5 and HART 7.
2-2
Output Signal
Code
Revision No.
HART Protocol
Revision
5 HART 5
J
7 HART 7
- HART 7
E - HART 5
Figure 2.1 Hart Protocol Revision Number on
Name Plate
(b) Conrmation on integral indicator
(A case of integral indicator code D is specied) Refer to section 2.1. (c) Conrmation by using HART conguration tool
1) Connect the conguration tool to the transmitter.
2) Conrm numerical number displayed on “Universal rev” column.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu (refer to 3.1.1) ] → Review → Universal rev
Conguration → HART →Universal rev
IMPORTANT
Protocol revision supported by HART conguration tool must be the same or higher than that of the transmitter.
Protcol revision supported by HART conguration tool
5 7
Protocol revision of the transmitter
 : Communication OK×: Communication NG
5
7 ×
2.3 Device Description (DD) on a Conguration Tool and Transmitter Device Revision
Before using a HART conguration tool, conrm that the DD for the transmitter is installed in the conguration tool.
About the DD, use the device type, device revision and DD Revision shown in the Table 2.1.
Table 2.1 HART Protocol Revision, Device
Revision and DD Revision
HART
Protocol
Revision
(*1)
5
7
*1: When the output signal code is “–E”, only “5” is available.
The device revision of the transmitter and DD can be conrmed as shown below.
If the correct DD is not installed in the conguration tool, download it from the ofcial web site of HART Communication Foundation.
(1) Conrmation of device revision for the
transmitter
● Conrmation on integral indicator (A case of integral indicator code D is specied)
Refer to the section 2.1
DPharp Pressure Transmitter
Model
EJX series
EJA series
EJX series
EJA series
Device
Type
EJX
(0x51)
EJA-NEXT
(0x5C)
EJX
(0x3751)
EJA-NEXT
(0x375C)
Device
RevisionDDRevision
3
1
10
10
3
or later
2
or later
2
or later
1
or later
IM 01C25T01-06EN
<2. Connection>
2-3
● Conrmation by using HART conguration tool
a) Connect the conguration tool to the
transmitter.
b) Conrm numerical number displayed on
“Fld dev rev” column.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu (refer to 3.1.1) ] → Review →Fld dev rev
Conguration → HART →Fld dev rev
(2) Conrmation of device revision for the
conguration tool
Conrm the device revision from the installed
DD le name according to the procedure provided for the conguration tool.
The rst two digits indicate the device revision
and the next two digits indicate the DD revision.
0 a 0 2. X X X
DD revision
Device revision

2.4 Set the parameters using DTM

When congure the parameters using FieldMate, use the DTM (Device Type Manager) shown in the Table 2.2.
NOTE
The DTM revision can be conrmed by “DTM setup”. Device Files is a Media included in FieldMate. The user registration site provides Device Files with the latest update programs. (URL: https://voc.yokogawa.co.jp/PMK/) In case update, following operation by “DTM setup” is required.
• Update DTM catalog
• Assign corresponding DTM to the device (refer to Table 2.2)
Refer to FieldMate Instruction Manual for detail.
NOTE
Device revision of DD le is given in hexadecimal
Table 2.2 Applicable DTM
File Applied device
File name
EJA-NEXT
HART DTM
EJA-NEXT
FDT2.0
HART DTM
EJA-NEXT
HART 7 DTM
EJA-NEXT
FDT2.0
HART 7 DTM
EJXV3.1 1.4.160.8 or later
EJX FDT2.0
HART DTM
EJX HART 7
DTM
EJX FDT2.0
HART 7 DTM
*1: The DTM is included in Yokogawa DTM Library HART 2012-2/Device Files R3.03.03 or later. *2: The DTM is included in Yokogawa Device DTM Library 2.3/Device Files R3.03.03 or later. *3: The DTM is included in Device DTM Library 4.0 or later.
DTM
revision
3.3.0.140 or later
5.0.0.0 or later
3.3.0.140 or later
5.0.0.0 or later
5.0.0.0 or later
3.3.0.140 or later
5.0.0.0 or later
*2
*3
*2
*3
*1
*3
*2
*3
FDT
revision
FDT1.2
FDT2.0
FDT1.2
FDT2.0
FDT1.2
FDT2.0
FDT1.2
FDT2.0
Model
EJA series
EJX series
HART
protocol
revision
5
7
5
7
Device type
EJA-NEXT
(0x5C)
EJA-NEXT
(0x375C)
EJX
(0x51)
EJX
(0x3751)
Device
revision
1
10
3
10
IM 01C25T01-06EN
<2. Connection>
F0203.ai
2-4
2.5 Interconnection Between DPharp and the HART Conguration Tool
The HART conguration tool can interface with the transmitter from the control room, the transmitter site, or any other wiring termination point in the loop, provided there is a minimum of 250 Ω between the connection and the power supply. To communicate, it must be connected in parallel with the transmitter; the connections are non-polarized. Figure 2.2 illustrates the wiring connections for direct interface at the transmitter site for the DPharp. The HART conguration tool can be used for remote access from any terminal strip as well.
Control room
Terminal
board
Distributor
DPharp
Relaying terminals
USB
FieldMate
Modem

2.6 Power Supply Voltage and Load Resistance

When conguring the loop, make sure that the external load resistance is within the range in the gure below.
(Note) With an intrinsically safe transmitter, external load
resistance includes safety barrier resistance.
600
External load resistance
R (Ω)
250
0 10.5 16.6 25.2 42
Figure 2.3 Relationship between Power Supply
E–10.5
R=
0.0244
Power supply voltage E (V DC)
Communication
applicable range
Voltage and External Load Resistance
PULSE
SUPPLY
CHECK ALARM
HART configuration tool
PC/FieldMate
USB
Figure 2.2 Connecting the HART Conguration
Tool
F0202.ai
IM 01C25T01-06EN
<3. Parameter Setting>

3. Parameter Setting

3.1 Menu Tree

The structure of menu tree varies according to conguration tool based on DD or DTM. The difference is classied into two groups (I and II) as shown in the below table.
3-1
Applied model
EJA series
EJX series
I: DD and DTM (excluding EJX HART 5 DTM based on FDT1.2) II: EJX HART 5 DTM based on FDT1.2
HART protocol
revision
DD
HART 5 HART 7 HART 5 II
I-1
HART 7 I-2
. . . . . . . . . . . . . . . . . . . . . . . . .
FDT1.2 FDT2.0
I-2
. . . . .
DTM
I-2
Refer to section 3.1.1. Refer to section 3.1.2.

3.1.1 Group I: DD and DTM (excluding EJX HART 5 DTM based on FDT1.2)

When FieldMate with DD and DTM (excluding EJX HART 5 DTM based on FDT1.2) is used in order to set or refer to parameters, there is difference on the initial root menu as below.
I-1 DD
Root Menu
• Device setup
• Pres
• AO
• LRV
• URV
I-2 DTM
Root Menu
• Device Configuration* - Configure/Setup
• Diagnostic*
• Process Variable*
• Process variables
• Diag/Service
• Basic setup
• Detailed setup
• Review
• Basic setup
• Detailed setup
• Review
• Diag/Service
• Process Variables
A B C D, E
C D, E
B A
*: The next parameter is displayed on the top menu when using the DTM based or FDT2.0.
A
Process variables
Pres
• Pres %
AO
• SP
• SP %
• Snsr temp
• Engr Disp
• Engr exp
• Engr Unit
• Device Variables and Status
HART 7
• Pres
• Pres Data Quality
• Pres Limit Status
• SP
• SP Data Quality
• SP Limit Status
• Snsr temp
• Temp Data Quality
• Temp Limit Status
• Pres %
• Percent Range Data Quality
• Percent Range Limit Status
• AO
• Loop Current Data Quality
• Loop Current Limit Status
DTM DD
• PV
• PV Data Quality
• PV Limit Status
• SV
• SV Data Quality
• SV Limit Status
• TV
• TV Data Quality
• TV Limit Status
• % rnge
• % rnge Data Quality
• % rnge Limit Status
• Loop current
• Loop current Data Quality
• Loop current Limit Status
HART 7
F0301-01.ai
: HART 7 only
F0301-02.ai
IM 01C25T01-06EN
<3. Parameter Setting>
HART 7
B
: HART 7 only
EJX
: EJX Series only
3-2
Diag/Service
• Test device (DD)
• Status (DTM)
• Loop Test(DD)
• Test (DTM)
• Calibration
• Status
• Self test
• Master test
• Squawk
• Simulate
HART 7
HART 7
• Loop test
• Self test
• Master test
• Squawk
• Simulate
HART 7
HART 7
• Test Auto Release
Time
• Re-range (DD)
• Keypad input (DTM)
• Analog output trim
• Status group 1
• Status group 2
• Status group 3
• Status group 4
• Status group 5
• Status group 6
• Status group 7
• Status group 8
• Status group 9
• Status group 10
• Device status
• Ext dev status
• Cfg chng count
HART 7
HART 7
HART 7
HART 7
• Reset Cfg chng flag
• Time Stamp
HART 7
• Keypad input
• Apply values
• D/A trim
• Scaled D/A trim
• Clear D/A trim
HART 7
• LRV
• URV
• Unit
• LSL
• USL
• Min span
• Diag Parameters
EJX
Error log
• Test Auto Release Time (DD)
• Pres sensor trim
• SP sensor trim
• Trim info.
See B1 (next page)
• Error log view
Error log Clear
• Pres Zero trim
• Pres trim
• P LTP
• P UTP
• Pres trim info.
• Static Pres trim
• SP LTP
• SP UTP
• SP trim info.
• Trim Who
• Trim Date
• Trim Loc
Trim Desc
• P LTD
• P UTD
• Clear P snsr trim
• SP LTD
• SP UTD
• Clear SP snsr trim
F0301-03.ai
IM 01C25T01-06EN
<3. Parameter Setting>
Diag Mode
Diag Applicable
Diag Variables
EJX
: EJX Series only
Ratio fDP Status
Ratio fDP
Ratio fSPl Status
Ratio fSPl
Ratio fSPh Status
Ratio fSPh
BlkF Status
BlkF
DP Avg Status
DP Avg
CRatio fDP Status
CRatio fDP
NRatio fDP Status
NRatio fDP
3-3
Diag Parameters
EJX
B1
Diag Error
Diag Option
ILBD Parameters
Status
Configuration
Diag Reference
Fluct Variables
Set Diag Mode
Diag Period
Diag Lim
Diag Description
Ref fDP Status
Ref fDP
Ref fSPl Status
Ref fSPl
Ref fSPh Status
Ref fSPh
Ref BlkF Status
Ref BlkF
Ref DP Avg Status
Ref DP Avg
fDP Status
fDP
fSPl Status
fSPl
fSPh Status
fSPh
Lim fDPmax
Lim fDPmin
Lim fSPlmax
Lim fSPlmin
Lim fSPhmax
Lim fSPhmin
Lim BlkFmax
Lim BlkFmin
Lim DPAvgmax
Lim DPAvgmin
HT Parameters
Diag Output
Status
Configuration
Diag Out Option
Diag Fixed Out Val
Diag Reference
Diag Supp Count
Diag Ref Lim
Diag DPComp
Snsr temp
Amp temp
Flg temp
Flg Temp Coef
Flg Temp Lim
Diag Description
Ref fDP
Ref fSPl
Ref fSPh
Ref BlkF
Ref DP Avg
Ref Lim fDPmin
Ref Lim fSPmin
Ref Lim BlkFmax
Flg Temp Hi Alert Val
Flg Temp Lo Alert Val
F0301-04.ai
IM 01C25T01-06EN
<3. Parameter Setting>
C
• Basic setup
Tag
HART 7
3-4
: HART 7 only
• Long tag
HART 7
• Unit
• Re-range
• Device infomation
• Xfer fnctn
• Pres Damp
• Low cut
• Low cut mode
• H/L Swap
• SP setup
• Keypad input
• Apply values
• Date
• Descriptor
• Message
• Write protect
• Model
HART 7
• SP Range
• SP Unit
• SP Damp
• SP A/G Setup
• SP H/L Select
• LRV
• URV
• Unit
• LSL
• USL
• Min span
• Keypad input
• SP Apply values
• A/G Select
• Atm. Pres Value
• SP LRV
• SP URV
• SP Unit
• SP LSL
• SP USL
• SP Min span
F0301-05.ai
IM 01C25T01-06EN
<3. Parameter Setting>
3-5
D
• Detailed setup
Review
• Sensors
• Signal condition
• Pressure sensor
• SP sensor
• Temp sensor
• Snsr temp
• Amp temp
• Temp Unit
• Process variables
• Pres
• Pres %
• Unit
• Pres sensor trim
• SP
• SP %
• SP Unit
• A/G Select
• SP H/L Select
• SP sensor trim
• SP setup
• Pres
• Pres %
• SP
• Snsr temp
• Pres Zero trim
• Pres trim
• P LTP
• P UTP
• Pres trim info.
• Static Pres trim
• SP LTP
• SP UTP
• SP trim info.
• SP Range
• SP Unit
• SP Damp
• SP A/G Setup
• SP H/L Select
HART 7
: HART 7 only
EJX
: EJX Series only
• P LTD
• P UTD
• Clear P snsr trim
• SP LTD
• SP UTD
• Clear SP snsr trim
• SP LRV
• SP URV
• SP Unit
• SP LSL
• SP USL
• SP Min Span
• Keypad input
• SP Apply values
• A/G Select
• Atm. Pres Value
• Output condition
• Display condition
• Device information
• Test Key
• Re-range
• Unit
• Xfer fnctn
• Pres Damp
• Low cut
• Low cut mode
• H/L Swap
• Bi-dir mode
• Quick resp
• T.Z. Cmp menu
• S.C. menu
• Process variables
• Analog output
See D1 (next page)
See E
• Keypad input
• Apply values
• S.C.
• Num of points
• Point setting
• X Start
• Y Start
• X End
• Y End
• Loop test
• Loop current mode
HART 7
• D/A trim
• Scaled D/A trim
• Clear D/A trim
• AO alm typ
• Channel flags
HART 7
• Auto recover
• AO lower limit
• AO upper limit
• LRV
• URV
• Unit
• LSL
• USL
• Min span
• T.Z. Cmp mode
• Temp Zero
• Pres
• Pres %
• AO
• SP
• SP %
• Snsr temp
• Engr Disp
• Engr exp
• Engr Unit
• Digital Output
EJX
F0301-06.ai
IM 01C25T01-06EN
<3. Parameter Setting>
D1
• HART output
• Poll addr
• Loop current mode
HART 7
• Num req preams
• Num resp preams
HART 7
• Burst Condition
HART 7
• Burst mode
• Burst option
HART 5
HART 5
• Burst Message 1
• Burst mode
• Burst Command
• Burst Device Variables
• Set Burst Trigger
• Set Burst Period
• Burst Msg Trigger Mode
• Burst Trigger Level
• Update Period
• Max Update Period
HART 5
HART 7
3-6
: HART 5 only : HART 7 only
EJX
: EJX Series only
• Burst Variable Code
(DD)
• Device Variable Code (DTM)
• Process Alerts (DD)
• Process Alerts (DTM)
• Pres Alert mode
• Config Pres Alerts
• SP Alert mode
• Config SP Alerts
• Temp Alert mode
• Config Temp Alerts
• DO Config
EJX
• Pres Alert
• SP Alert
• Temp Alert
• DO Config
EJX
• Burst Message 2
• Burst Message 3
• Event Notification
• PV Update time period (DD)
• SV Update time period (DD)
• TV Update time period (DD)
• Update time period (DTM)
• SP update time (DTM)
• Temp update time (DTM)
• Hi Alert Val
• Lo Alert Val
• LSL
• USL
• Temp Hi Alert Val
• Temp Lo Alert Val
• Digital Output
• DO Select
• DO Signal type
• DO Test
• Pres Alert mode
• Config Pres Alerts
• SP Alert mode
• Config SP Alerts
• Temp Alert mode
• Config Temp Alerts
• Digital Output
• DO Select
• DO Signal type
• DO Test
Same as above Same as above
• Event Notification Control
• Event Mask
• Set Event Notification Timing
• Event Notification Retry Time
• Max Update Time
• Event Debounce Interval
• Knowledge (DD)
• Knowledge (DTM)
• SP Hi Alert Val
• SP Lo Alert Val
• SP LSL
• SP USL
• Hi Alert Val
• Lo Alert Val
• LSL
• USL
• SP Hi Alert Val
• SP Lo Alert Val
• SP LSL
• SP USL
• Temp Hi Alert Val
• Temp Lo Alert Val
• Device Status Mask
• Status group 1 Mask to 10 Mask
• Ext dev status Mask
• Device Diagnostic Status 0 Mask
• Device Diagnostic Status 1 Mask
• AO saturated Mask
• AO fixed Mask
• Event Status
• Time First Unack Event Triggered
• Acknowledge Event Notificatoin
• Event Status
• Event Number
• Time First Unack Event Triggered
• Latched Cfg chng count
• Latched Device Status
• Latched Status group 1 to 10
• Latched Ext dev status
• Latched Device Diagnostic Status 0
• Latched Device Diagnostic Status 1
• Latched AO saturated
• Latched AO fixed
F0301-07.ai
IM 01C25T01-06EN
<3. Parameter Setting>
E
• Detailed setup
Review
• Sensors
• Signal condition
• Output condition
• Display condition
• Disp select
• P disp condition
• Disp Out1
• Disp Out2
• Disp Out3
• Disp Out4
• Disp Pres % fnctn
• Disp Pres % Reso
• Pres disp point
HART 7
3-7
: HART 7 only
• Device information
• Test Key
• SP disp condition
• Engr disp range
• Bar indicator
• Chg power on info
• Field device info
• Sensor infomation
• Self test (DD)
• SP disp point
• Engr LRV
• Engr URV
• Engr exp
• Engr Unit
• Engr point
• Set Engr Unit
• Modify Engr Unit
Tag
• Long tag
HART 7
Date
• Descriptor
• Message
• Model 1
• Model 2
• Model 3
• Write protect
• Wrt protect menu
• Ext SW
• Revision #’s
• Additional Info
• Option Password
• Isoltr matl
• Fill fluid
• Gasket matl
• Process Conn matl
• Drain vent matl
• Process Conn type
• RS isoltr matl
• Process Conn size
• Num of RS
• RS fill fluid
• RS type
• Write protect
• Enable wrt 10min
• New password
• Software seal
• Universal rev
• Fld dev rev
• Software rev
• Chg universal rev
• Style No.
• Serial No.
• Mftr Date
• Extra No.
• Final asmbly num
• Dev id
• Distributor
• Country
• Max dev vars
HART 7
• Device Profile
HART 7
HART 7
F0301-08.ai
IM 01C25T01-06EN
<3. Parameter Setting>

3.1.2 Group II: EJX HART 5 DTM based on FDT1.2

Root Menu
• Process Variables
• Device Status
• Diag and Service
• Easy Setup
• Configuration
• Calibration
• Write Protect
P
• Process Variables
• Pres %
• AO
• URV
• LRV
• Xfer fnctn
• Pres Damp
• Pres
• SP
• A/G Select
• Snsr temp
• Engr Disp
• Engr exp
• Engr Unit
• USL
• LSL
• P UTP
• P LTP
P Q R S T U V
3-8
Q
• Device Status
• Process Variable
• Diagnostic List
• Pres %
• Pres
• SP
• Snsr Temp
• Device Status
• Hardware Failure
• Transducer Status
• Diag Status
• Configuration
F0301-21.ai
IM 01C25T01-06EN
<3. Parameter Setting>
R
• Diag and Service
• Service
• Advanced Diag Variables
• Loop test
• Master test
• DO Test
• Error log view
• Error log Clear
• Test Key
• Test Auto Release Time
• Diag Description
• BlkF
• fDP
• fSPh
• fSPl
• DPAvg
• Ref BlkF
• Ref fDP
• Ref fSPh
• Ref fSPl
• Ref DPAvg
• CRatio fDP
• NRatio fDP
• Ratio fDP
• Ratio fSPh
• Ratio fSPl
• Cap Temp
• Amp Temp
• Flg Temp
3-9
• Advanced Diag Configurations
• Advanced Diag Alerts
• Impulse Line Blockage Detection
• Heat Trace
• Diag Out Option
• Diag Fixed Out Val
• Diag Error
• Diag Mode
• Diag Period
• Diag DPComp
• Diag Description
• Ref BlkF
• Ref fDP
• Ref fSPh
• Ref fSPl
• Ref DPAvg
• Alarm Notification
• Threshold
• Alarm Notification
• Threshold
• Flg Temp Coefficient
• Tuning
• Flg Temp
• Related to high side alarm
• Related to both side alarm
• Related to low side alarm
• Related to Flg temp alarm
• Diag Option
• Diag Suppress Count
• Sensitivity
• Fig Temp High Limit
• Fig Temp Low Limit
S
• Easy Setup
• Tag
• USL
• LSL
• Unit
• URV
• LRV
• Xfer fnctn
• Pres Damp
• Low cut
• Low cut mode
F0301-22.ai
IM 01C25T01-06EN
<3. Parameter Setting>
T
• Configuration
• Pressure Sensor
• Static Pressure Sensor
• Physical Information
• Process Input
• Analog Output
• Local Display
• Signal Characterizer Menu
• Process Alerts
• Device Information1
• Process Conn type
• Process Conn matl
• Process Conn size
• Gasket matl
• Isoltr matl
• Drain vent matl
• Fill fluid
• RS type
• RS isoltr matl
• RS fill fluid
• Num of RS
• Disp Out1
• Disp Out2
• Disp Out3
• Disp Out4
• Disp Pres % fnctn
• Disp Pres % Reso
• Pres disp point
• Engr URV
• Engr LRV
• Engr Unit
• Engr exp
• Engr point
• SP disp point
• Bar Indicator
• Chg power on info
• Model
• Manufacturer
• Hardware rev
• Software rev
• Date
• Descriptor
• Message
• Final asmbly num
• Auto recover
• Ext SW
• SP USL
• SP LSL
• SP Min Span
• SP Unit
• SP URV
• SP LRV
• SP Damp
• SP H/L Select
• A/G Select
• Atm. Pres Value
• Pres %
• AO
• Unit
• URV
• LRV
• Apply values
• Xfer fnetn
• Pres Damp
• Low cut
• Low cut mode
• AO alm typ
• AO upper limit
• AO lower limit
• Quick resp
• Bi-dir mode
• Pres Alert mode
• Hi Alert Val
• Lo Alert Val
• SP Alert mode
• SP Hi Alert Val
• SP Lo Alert Val
• Temp Alert mode
• Temp Hi Alert Val
• Temp Lo Alert Val
• Digital Output
• DO Select
• DO Signal type
3-10
• USL
• LSL
• Min span
• H/L Swap
• T.Z. Cmp mode
• Temp Zero
• Pres
• Unit
• Pres %
• SP
• SP Unit
• SP %
• Snsr temp
• Temp Unit
• S.C.
• Num of points
• X Start
• X End
• Y Start
• Y End
• X1
• X2
• X3
• X4
• X5
• X6
• X7
• X8
• X9
• Y1
• Y2
• Y3
• Y4
• Y5
• Y6
• Y7
• Y8
• Y9
• Device Information2
• HART
• Tag
• Poll addr
• Dev id
• Universal rev
• Fld dev rev
• Chg universal rev
• Num req preams
• Physical signal code
• Burst mode
• Burst option
• Model 1
• Model 2
• Model 3
• Style No.
• Serial No.
• Mftr Date
• Extra No.
F0301-23.ai
IM 01C25T01-06EN
<3. Parameter Setting>
U
• Calibration
• Trim Who
• Trim Date
• Trim Loc
• Trim Desc
• Pres Zero trim
• P UTP
• P LTP
• P UTD
• P LTD
• Pres trim
• Clear P snsr trim
• SP UTP
• SP LTP
• SP UTD
• SP LTD
• Static Pres trim
• Clear SP snsr trim
• D/A trim
• Scaled D/A trim
• Clear D/A trim
3-11
V
• Write Protect
• Write Protect
• Enter new password
F0301-24.ai
IM 01C25T01-06EN
<3. Parameter Setting>
3-12

3.2 Basic Setup

IMPORTANT
After setting and sending data with the HART conguration tool, wait 30 seconds before turning off the transmitter. If it is turned off too soon, the settings will not be stored in the transmitter.

3.2.1 Tag and Device Information

If there are specied when ordering, the desired Tag No. and device information are set and shipped. Tag No. and device information can be checked as follows.
• Procedure to call up the display using by DD and DTM (excluding EJX HART 5 DTM based on FDT1.2)
Item Procedure
Tag [Root Menu] → Basic setup → Tag Long tag
(HART 7 only) Descriptor [Root Menu] → Basic setup → Device
Message [Root Menu] → Basic setup → Device
Date [Root Menu] → Basic setup → Device
• Procedure to call up the display by EJX HART 5 DTM based on FDT1.2
Item Procedure
Tag Easy Setup → Tag
Descriptor Conguration → Device information 1
Message Conguration → Device information 1
Date Conguration → Device information 1
When the Tag No. and device information are changed, input them based on the following limitations.
[Root Menu] → Basic setup → Long Tag
information → Descriptor
information → Message
information → Date
or Conguration → HART → Tag
→ Descriptor
→ Message
→ Date
Item Limitations
Tag Up to 8 characters or numbers*
Long tag (HART 7 only)
Descriptor Up to 16 characters or numbers*
Message Up to 32 characters or numbers*
Date mm/dd/yyyy
*1: The characters bounded by the thick line in the following
table can be used.
*2: All characters in the following table can be used.
SP ! " # $ % & ' ( ) * + , - . /
0 1 2 3 4 5 6 7 8 9 : ; < = > ?
@ A B C D E F G H I J K L M N O
P Q R S T U V W X Y Z [ \ ] ^ _
` a b c d e f g h i j k l m n o
p q r s t u v w x y z { | } ~
*: SP shows one-byte space
Up to 32 characters or numbers*
- mm: month (2 digits)
- dd: days (2 digits)
- yyyy: years (4 digits)
1
2
1
1

3.2.2 Unit

The unit parameter is set at the factory before shipment if specied at the time of order. Follow the procedure below to change the unit parameter.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
Note that the Yokogawa default setting for the standard temperature is 4°C (39.2°F). For the units of mmH2O, inH2O, and ftH2O, the pressure varies according to the standard temperature denition. Select the appropriate unit with @68degF when a standard temperature of 20°C (68°F) is required.
Available pressure units are shown below.
inH2O@68degF inHg ftH2O@68degF mmH2O@68degF mmHg psi bar
[Root Menu] → Basic setup → Unit
Easy Setup → Unit or Conguration → Analog Output → Unit
mbar g/cm kg/cm Pa kPa torr atm
2
2
MPa inH2O mmH2O ftH2O hPa
IM 01C25T01-06EN
<3. Parameter Setting>
3-13

3.2.3 Range Change

The range values are factory-set as specied by the customer. To change the range, follow the steps below.
(1) Keypad input — LRV and URV
The measurement span is determined by the upper and lower range values. In this method, the upper and lower range values can be set independently, and the span changes according to the range limit values sent to the transmitter.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ LRV Lower range value → URV Upper range value
[Root Menu] → Basic setup → Re-range → Keypad input
Easy Setup → or Conguration → Analog Output →
NOTE
The measurement span is determined by the upper and lower range values. Changing the lower range value causes the upper range value to change automatically, keeping the span constant. If a change in the lower range value causes the upper range value to exceed the measuring limit of the transmitter, an error message appears and the transmitter holds the output signal right before the error occurred. Enter the correct values within the range of the sensor limits. Note that changing the upper range value does not cause the lower range value to change. Thus, changing the upper range value also changes the span.

3.2.4 Output Mode

The mode setting for the output signal and the integral indicator can be performed independently.
The output mode for the output signal is set as specied in the order when the instrument is shipped. Follow the procedure below to change the mode.
The calibration range can be set as LRV > URV under the following conditions, reversing the 4 to 20 mA output signal. When using the integral indicator, change the user set scale values accordingly.
Conditions: LSL ≤ LRV ≤ USL LSL ≤ URV ≤ USL |URV – LRV| ≥ Min Span
LSL: Lower sensor limit of range setting
USL: Upper sensor limit of range setting
(2) Apply values — changing the ranges while
applying an actual Input
This feature allows the lower and upper range values to be setup automatically with the actual input applied. If the upper and lower range values are set, URV and LRV are changed at the same time.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu] → Basic setup → Re-range → Apply values →
Conguration → Analog Output → Apply values →
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ Xfer fnctn Select “Linear” or “Sq root”
[Root Menu] → Basic setup →
Easy Setup → or Conguration → Analog Output →

3.2.5 Damping Time Constant Setup

The damping time constant is set as specied in the order when the instrument is shipped. Follow the procedure below to change the damping time constant. The damping time constant for the amplier assembly can be set here. The damping time constant for the entire transmitter is the sum of the values for the amplier assembly and the capsule assembly.
Any number from 0.00 to 100.00 can be set for the damping time constant. Note that setting the quick response parameter ON enables you to set the time constant between 0.00 and 0.49 seconds.
• Procedure to call up the Pres Damp display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
[Root Menu] → Basic setup → Pres Damp
Easy Setup → Pres Damp or Conguration → Analog Output → Pres Damp
IM 01C25T01-06EN
<3. Parameter Setting>
3-14
• Procedure to call up the Quick resp display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ Off Set from 0.50 to 100.00 → On Set from 0.00 to 100.00
[Root Menu] → Detailed setup → Signal condition → Quick resp →
Conguration → Analog Output → Quick resp →

3.2.6 Output Signal Low Cut Mode Setup

Low cut mode can be used to stabilize the output signal near the zero point.
The low cut point can be set in a range from 0 to 20%, the direct ratio corresponding to the output signal of 4 to 20 mA. (Hysteresis for the cut point: ±10% of the cut point)
Either “Linear” or “Zero” can be selected as the low cut mode. Unless otherwise specied, the cut mode is set to “Linear” at the factory.
The default value of Low cut is set according to the combination of the Output mode (Xfer fnctn) and Integral indicator display mode (Disp Pres % fnctn). See below table.
Example: Low cut at 20%
(%)
50
Output
20
0
Input
For low cut in linear mode
50
(%)
(%)
50
Output
20
0
Input
For low cut in zero mode
F0302.ai
50
(%)
Figure 3.1 Low Cut Mode
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ Low cut Set from 0 to 20% of output → Low cut mode Select “Linear” or “Zero”
[Root Menu] → Basic setup →
Easy Setup → or Conguration → Analog Output →
The low cut point has hysteresis so that the output around the point is behaved as below gure.
Relationship of default value of Low cut and Low cut point
Combination of
output mode and
display mode
#
Output
mode
Display
mode
Default value of Low cut
1) Linear Linear 10% 10% / 10%
2) Sq Root Sq Root 10% 10% / 10%
3) Linear Sq Root 1%* 1% / 10%
4) Sq Root Linear 10% 10% / NA
*: It is applied for software revision 2.02 or later. For
In the case 3) above, Low cut point for the display is
(Example: Low cut value; 2%, Low cut point; 14%)
previous software version, it is set in 10%.
square root of Low cut value.
Low cut
point for
the output
signal/
display
Note that when the output modes of the output signal and the display are selected as “Sq root” and “Linear” accordingly, the low cut function is not available for the display value.
<Example> Output mode: Linear Low cut mode: Zero Low cut: 20.00%
Output Low cut point
7.2mA (20%)
4mA
Setting range: 0 to 20%
Input
2% 2%
Hysteresis fixed at 10% of the cut point
F0303.ai

3.2.7 Impulse Line Connection Orientation Setup

This function reverses the impulse line orientation.
Follow the procedure below to assign the high pressure impulse line connection to the L side of the transmitter.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ H/L Swap Select “Normal” or “Reverse”
[Root Menu] → Basic setup →
Conguration → Pressure Sensor →
IM 01C25T01-06EN
<3. Parameter Setting>
3-15

3.2.8 Static Pressure Setup

The differential pressure transmitter can display the static pressure also.
(1) Setting of the unit for static pressure
Follow the procedure below to change the static pressure unit.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ SP Unit Select the unit for static pressure
(2) Setting of the measuring range for static
pressure
Follow the procedure below to change the lower range value (LRV) and upper range value (URV).
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ SP LRV Set the lower range value (0 %) of
→ SP URV Set the upper range value (100 %)
(3) Selection of Gauge pressure and Absolute
pressure
Either the gauge pressure or absolute pressure can be selected to display on the LCD display.
[Root Menu] → Basic setup → SP setup →
Conguration → Process Input (or Static Pressure Sensor) →
(Refer to subsection 3.2.2 Unit)
[Root Menu] → Basic setup → SP setup → SP Range → Keypad input →
Conguration → Static Pressure Sensor →
static pressure
of static pressure
(4) Selection of pressure side
Either the high or low pressure side of capsule can be selected to monitor the static pressure.
High pressure side is selected when the transmitter is shipped.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ SP H/L Select Select “High” or “Low”
[Root Menu] → Basic setup → SP setup →
Conguration → Static Pressure Sensor →

3.3 Detailed Setup

3.3.1 Bi-directional Flow Measurement

(a) Bi-dir mode enables selection of 50% output at
an input of 0 mmH2O.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ Bi-dir mode Select “On” or “Off”
(b) Combining Bi-dir mode with Xfer fnctn
provides a square root output computed independently for 0% to 50% output and for 50% to 100% output.
Output mode “LINEAR”
20 mA (100% display)
[Root Menu] → Detailed setup → Signal condition →
Conguration → Analog output →
Absolute pressure is selected when the transmitter is shipped.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ A/G Select Select “Gauge” or “Absolute”
→ Atm. Pres Value 0.1013 MPa when the transmitter
[Root Menu] → Basic setup → SP setup → SP A/G Setup →
Conguration → Static Pressure Sensor →
is shipped
LRV HRV
4 mA (−100% display)
Output mode “SQUARE ROOT”
20 mA (100% display)
Low Cut
LRV HRV
4 mA (−100% display)
F0304.ai
IM 01C25T01-06EN
<3. Parameter Setting>
3-16

3.3.2 Analog Output Signal Adjustable Range

Output signal adjustable range at normal operating condition are set as shown below at the factory when the instrument is shipped, and output signal are limited by these value.
Lower limit Upper limit
Standard Option code /C1
Option code /C2 and /C3 3.8 mA 20.5 mA
Output signal range can be changed between
3.6mA and 21.6mA to match it to the equipment on
the receiving side. Lower value is set at AO lower limit and upper value is set at AO upper limit respectively. Follow the procedure below to change the upper and lower values.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ AO lower limit Set the lower value (mA) → AO upper limit Set the upper value (mA)
[Root Menu] → Detailed setup → Output condition → Analog output →
Conguration → Analog output →
Set the values as below. Lower value < Upper value
3.6 mA 21.6 mA

3.3.4 Integral Indicator Scale Setup

The following ve displays are available for integral indicators: input pressure, % of range, user set scale, input static pressure*1, and % of static pressure range*1. A cycle of up to four displays can be shown by assigning variables to the parameters at Disp select.
Available displays
Input pressure
(PRES)
% of range
(PRES %)
User set scale
(ENGR. PRES)
Indicates values of input pressure with the indication limits –99999 to
99999.
PRES 456 kPa
Indicates input pressure in 110% range depending on the set range (LRV and URV).
PRES % 45.6 %
Indicates values depending on the engineering range (Engr LRV and Engr URV) with the unit (Engr Unit).
Engr LRV 0.0 Engr URV 45.0 Engr exp ×100 Engr Unit m3/min Engr point 1
Description
and related parameters
2.5 to

3.3.3 Integral Indicator Display Mode

The mode setting for the output signal and the integral indicator can be performed independently.
The output mode for the integral indicator is set as specied in the order when the instrument is shipped. Follow the procedure below to change the mode.
• Procedure to call up the display
DD and DTM (excluding EJX_ HART 5[1.2])
EJX_HART 5[1.2] DTM
→ Disp Pres % fnctn Select “Linear” or “Sq root”
If the instrument is equipped with an integral indicator and the transfer function is sq root, “ ” is displayed on the integral indicator.
[Root Menu] → Detailed setup → Display condition → P disp condition →
Conguration → Local Display →
Input static pressure
% of static pressure range
*1: Available for differential pressure transmitter.
(SP)*
(SP %)*
1
1
Indicates input static pressure with the indication limits –99999 to 99999. Reference pressure is factory-set in absolute.
SP 4.000 MPa
Indicates input static pressure in –10 to 110% range depending on the set range (SP LRV and SP URV).
SP % 52.6 %
See (a.) through (d.) shown below for the setting procedures.
F0305.ai
IM 01C25T01-06EN
Loading...
+ 67 hidden pages