Thank you for purchasing the DPharp electronic
pressure transmitter.
The DPharp Pressure Transmitters are precisely
calibrated at the factory before shipment. To ensure
correct and efficient use of the instrument, please read
this manual thoroughly and fully understand how to
operate the instrument before operating it.
j Regarding This Manual
• This manual should be passed on to the end user.
• The contents of this manual are subject to change
without prior notice.
• All rights reserved. No part of this manual may be
reproduced in any form without Yokogawa’s written
permission.
• Yokogawa makes no warranty of any kind with
regard to this manual, including, but not limited to,
implied warranty of merchantability and fitness for a
particular purpose.
• If any question arises or errors are found, or if any
information is missing from this manual, please
inform the nearest Yokogawa sales office.
• The specifications covered by this manual are
limited to those for the standard type under the
specified model number break-down and do not
cover custom-made instruments.
• Please note that changes in the specifications,
construction, or component parts of the instrument
may not immediately be reflected in this manual at
the time of change, provided that postponement of
revisions will not cause difficulty to the user from a
functional or performance standpoint.
j Safety Precautions
• For the protection and safety of the operator and the
instrument or the system including the instrument,
please be sure to follow the instructions on safety
described in this manual when handling this instrument. In case the instrument is handled in contradiction to these instructions, Yokogawa does not
guarantee safety.
• For the intrinsically safe equipment and
explosionproof equipment, in case the instrument is
not restored to its original condition after any repair
or modification undertaken by the customer,
intrinsically safe construction or explosionproof
construction is damaged and may cause dangerous
condition. Please contact Yokogawa for any repair
or modification required to the instrument.
• The following safety symbol marks are used in this
Manual:
WARNING
Indicates a potentially hazardous situation which,
if not avoided,
injury.
CAUTION
Indicates a potentially hazardous situation which,
if not avoided, may result in minor or moderate
injury. It may also be used to alert against
unsafe practices
could
result in death or serious
.
NOTE
For FOUNDATION Fieldbus and HART protocol
versions, please refer to IM 1C22T2-01E and IM
1C22T1-01E respectively, in addition to this IM.
IMPORTANT
Indicates that operating the hardware or software
in this manner may damage it or lead to system
failure.
Draws attention to information essential for
understanding the operation and features.
1-1
IM 1C22J1-01E
1. INTRODUCTION
WARRANTY
• The warranty shall cover the period noted on the
quotation presented to the purchaser at the time of
purchase. Problems occurred during the warranty
period shall basically be repaired free of charge.
• In case of problems, the customer should contact the
Yokogawa representative from which the instrument
was purchased, or the nearest Yokogawa office.
• If a problem arises with this instrument, please
inform us of the nature of the problem and the
circumstances under which it developed, including
the model specification and serial number. Any
diagrams, data and other information you can
include in your communication will also be helpful.
• Responsible party for repair cost for the problems
shall be determined by Yokogawa based on our
investigation.
• The Purchaser shall bear the responsibility for repair
costs, even during the warranty period, if the
malfunction is due to:
- Improper and/or inadequate maintenance by the
purchaser.
- Failure or damage due to improper handling, use or
storage which is out of design conditions.
- Use of the product in question in a location not
conforming to the standards specified by
Yokogawa, or due to improper maintenance of the
installation location.
- Failure or damage due to modification or repair by
any party except Yokogawa or an approved
representative of Yokogawa.
- Malfunction or damage from improper relocation
of the product in question after delivery.
- Reason of force majeure such as fires, earthquakes,
storms/floods, thunder/lightening, or other natural
disasters, or disturbances, riots, warfare, or
radioactive contamination.
WARNING
• Instrument installed in the process is under
pressure. Never loosen or tighten the flange
bolts as it may cause dangerous spouting of
process fluid.
• Since the accumulated process fluid may be
toxic or otherwise harmful, take appropriate
care to avoid contact with the body, or inhalation of vapors even after dismounting the
instrument from the process line for maintenance.
CAUTION
This instrument is tested and certified as intrinsically safe type or explosionproof type. Please
note that the construction of the instrument,
installation, external wiring, maintenance or
repair is strictly restricted, and non-observance
or negligence of this restriction would result in
dangerous condition.
1-2
IM 1C22J1-01E
2.HANDLING CAUTIONS
2. HANDLING CAUTIONS
This chapter describes important cautions regarding
how to handle the transmitter. Read carefully before
using the transmitter.
The EJA Series pressure transmitters are thoroughly
tested at the factory before shipment. When the
transmitter is delivered, visually check them to make
sure that no damage occurred during shipment.
Also check that all transmitter mounting hardware
shown in Figure 2.1 is included. If the transmitter was
ordered without the mounting bracket, the transmitter
mounting hardware is not included. After checking the
transmitter, repack it in the way it was delivered until
installation.
Transmitter
mounting bolt
U-bolt
2.2 Unpacking
When moving the transmitter to the installation site,
keep it in its original packaging. Then, unpack the
transmitter there to avoid damage on the way.
2.3 Storage
The following precautions must be observed when
storing the instrument, especially for a long period.
(a) Select a storage area which meets the following
conditions:
• It is not exposed to rain or water.
• It suffers minimum vibration and shock.
• It has an ambient temperature and relative
humidity within the following ranges.
Ambient temperature:
–40 to 85°C without integral indicator
–30 to 80°C with integral indicator
Relative humidity:
5% to 100% R.H. (at 40°C)
Preferred temperature and humidity:
approx. 25°C and 65% R.H.
U-bolt nut
Figure 2.1 Transmitter Mounting Hardware
Mounting bracket
F0201.EPS
2.1 Model and Specifications
Check
The model name and specifications are indicated on the
name plate attached to the case. If the reverse operating mode was ordered (reverse signal), ‘REVERSE’
will be inscribed in field *1.
Figure 2.2 Name Plate Example of JIS Flameproof Type
(b) When storing the transmitter, repack it as nearly
as possible to the way it was packed when
delivered from the factory.
(c) If storing a transmitter that has been used,
thoroughly clean the diaphragm surface of the
diaphragm seal (pressure-detector section), so that
no measured fluid remains on them. Also make
sure before storing that the pressure-detector and
transmitter assemblies are securely mounted.
2.4 Selecting the Installation
Location
The transmitter is designed to withstand severe
environmental conditions. However, to ensure stable
and accurate operation for years, observe the following precautions when selecting an installation location.
(a) Ambient Temperature
Avoid locations subject to wide temperature
variations or a significant temperature gradient. If
the location is exposed to radiant heat from plant
equipments, provide adequate thermal insulation
and/or ventilation.
2-1
IM 1C22J1-01E
2. HANDLING CAUTIONS
(b) Ambient Atmosphere
Avoid installing the transmitter in a corrosive
atmosphere. If the transmitter must be installed in a
corrosive atmosphere, there must be adequate
ventilation as well as measures to prevent intrusion
or stagnation of rain water in conduits.
(c) Shock and Vibration
Select an installation site suffering minimum shock
and vibration (although the transmitter is designed
to be relatively resistant to shock and vibration).
(d) Installation of Explosion-protected Transmitters
Explosion-protected transmitters can be installed in
hazardous areas according to the types of gases for
which they are certified. See Subsection 2.9
“Installation of Explosion Protected Type Transmitters.”
2.5 Pressure Connection
WARNING
• Instrument installed in the process is under
pressure. Never loosen or tighten the flange
bolts to avoid the dangerous spouting of
process fluid.
• Since the accumulated process fluid may be
toxic or otherwise harmful, take appropriate
care to avoid contact with the skin, eyes or
body, or inhalation of vapors even after dismounting the instrument from process line for
maintenance.
The following precautions must be observed in order to
safely operate the transmitter under pressure.
(a) Never apply a pressure higher than the specified
maximum working pressure.
(b) Never loosen or tighten the bolts securing the
diaphragm seal flanges when the assembly is under
pressure. Do it after releasing the process pressure
if required.
2.6 Waterproofing of Cable
Conduit Connections
Apply a non-hardening sealant to the threads to
waterproof the transmitter cable conduit connections.
(See Figure 5.4.2a, 5.4.2b and 5.4.2d.)
2.7 Restrictions on Use of Radio
Transceiver
IMPORTANT
Although the transmitter has been designed to
resist high frequency electrical noise, if a radio
transceiver is used near the transmitter or its
external wiring, the transmitter may be affected
by high frequency noise pickup. To test for such
effects, bring the transceiver in use slowly from a
distance of several meters from the transmitter,
and observe the measurement loop for noise
effects. Thereafter, always use the transceiver
outside the area affected by noise.
2.8 Insulation Resistance and
Dielectric Strength Test
Since the transmitter has undergone insulation resistance and dielectric strength tests at the factory before
shipment, normally these tests are not required.
However, if required, observe the following precautions in the test procedures.
(a) Do not perform such tests more frequently than is
absolutely necessary. Even test voltages that do not
cause visible damage to the insulation may degrade
the insulation and reduce safety margins.
(b) Never apply a voltage exceeding 500 V DC (100 V
DC with an internal lightning protector) for the
insulation resistance test, nor a voltage exceeding
500 V AC (100 V AC with an internal lightning
protector) for the dielectric strength test.
(c) Before conducting these tests, disconnect all signal
lines from the transmitter terminals. Perform the
tests in the following procedure:
• Insulation Resistance Test
1) Short-circuit the + and – SUPPLY terminals in the
terminal box.
2) Turn OFF the insulation tester. Then connect the
insulation tester plus (+) lead wire to the shorted
SUPPLY terminals and the minus (–) leadwire to
the grounding terminal.
3) Turn ON the insulation tester power and measure
the insulation resistance. The voltage should be
applied short as possible to verify that the insulation resistance is at least 20 MΩ.
2-2
IM 1C22J1-01E
2. HANDLING CAUTIONS
4) After completing the test and being very careful not
to touch exposed conductors disconnect the
insulation tester and connect a 100 kΩ resistor
between the grounding terminal and the shortcircuiting SUPPLY terminals. Leave this resistor
connected at least one second to discharge any
static potential. Do not touch the terminals while it
is discharging.
• Dielectric Strength Test
1) Short-circuit the + and – SUPPLY terminals in the
terminal box.
2) Turn OFF the dielectric strength tester. Then
connect the tester between the shorted SUPPLY
terminals and the grounding terminal. Be sure to
connect the grounding lead of the dielectric strength
tester to the ground terminal.
3) Set the current limit on the dielectric strength tester
to 10 mA, then turn ON the power and gradually
increase the test voltage from ‘0’ to the specified
voltage.
4) When the specified voltage is reached, hold it for
one minute.
5) After completing this test, slowly decrease the
voltage to avoid any voltage surges.
2.9 Installation of Explosion
Protected Type
NOTE
For FOUNDATION Fieldbus explosion protected
type, please refer to IM 1C22T2-01E.
WARNING
To pressure the safety of explosionproof equipment requires great care during mounting,
wiring, and piping. Safety requirements also
place restrictions on maintenance and repair
activities. Please read the following sections very
carefully.
2.9.1 FM Approval
a. FM Intrinsically Safe Type
Caution for FM intrinsically safe type. (Following
contents refer “DOC. No. IFM012-A12 P.1 and 2.”)
Note 1. Model EJA Series pressure transmitters
with optional code /FS1 are applicable for
use in hazardous locations.
• Intrinsically Safe for Class I, Division 1, Groups A,
B, C & D. Class II, Division 1, Groups E, F & G
and Class III, Division 1 Hazardous Locations.
• Nonincendive for Class I, Division 2, Groups A, B,
C & D. Class II, Division 2, Groups E, F & G and
Class III, Division 1 Hazardous Locations.
• Outdoor hazardous locations, NEMA 4X.
• Temperature Class: T4
• Ambient temperature: –40 to 60°C
Note 2. Entity Parameters
• Intrinsically Safe Apparatus Parameters
[Groups A, B, C, D, E, F and G]
Vmax = 30 VCi = 22.5 nF
Imax = 165 mALi = 730 µH
Pmax = 0.9 W
• Entity Installation Requirements
Vmax ≥ Voc or Vt, Imax ≥ Isc or It,
Pmax (IS Apparatus) ≥ Pmax (Barrier)
Ca ≥ Ci + Ccable, La ≥ Li + Lcable
Note 3. Installation
• Barrier must be installed in an enclosure that meets
the requirements of ANSI/ISA S82.01.
• Control equipment connected to barrier must not
use or generate more than 250 V rms or V dc.
• Installation should be in accordance with ANSI/
ISA RP12.6 “Installation of Intrinsically Safe
Systems for Hazardous (Classified) Locations” and
the National Electric Code (ANSI/NFPA 70).
• The configuration of associated apparatus must be
FMRC Approved.
2-3
IM 1C22J1-01E
2. HANDLING CAUTIONS
• Dust-tight conduit seal must be used when installed
in a Class II, III, Group E, F and G environments.
• Associated apparatus manufacturer’s installation
drawing must be followed when installing this
apparatus.
• The maximum power delivered from the barrier
must not exceed 0.9 W.
• Note a warning label worded “SUBSTITUTION OF
COMPONENTS MAY IMPAIR INTRINSIC
SAFETY,” and “INSTALL IN ACCORDANCE
WITH DOC. No. IFM012-A12 P.1 and 2.”
Note 4. Maintenance and Repair
• The instrument modification or parts replacement by
other than authorized representative of Yokogawa
Electric Corporation is prohibited and will void
Factory Mutual Intrinsically safe and Nonincendive
Approval.
[Intrinsically Safe]
Hazardous LocationNonhazardous Location
Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G
EJA Series Pressure
Transmitters
+
Supply
Hazardous LocationNonhazardous Location
Class I, II, Division 2,
Groups A, B, C, D, E, F, G
Class III, Division 1.
EJA Series Pressure
Transmitters
Supply
–
[Nonincendive]
+
–
Safety Barrier
+
–
Not Use
Safety Barrier
+
–
General
Purpose
Equipment
+
–
General
Purpose
Equipment
+
–
F0203.EPS
b. FM Explosionproof Type
Caution for FM explosionproof type.
Note 1. Model EJA Series differential, gauge, and
absolute pressure transmitters with
optional code /FF1 are applicable for use
in hazardous locations.
• Explosionproof for Class I, Division 1, Groups B, C
and D.
• Dust-ignitionproof for Class II/III, Division 1,
Groups E, F and G.
• Outdoor hazardous locations, NEMA 4X.
• Temperature Class: T6
• Ambient Temperature: –40 to 60°C
• Supply Voltage: 42 V dc max.
• Output signal: 4 to 20 mA
Note 2. Wiring
• All wiring shall comply with National Electrical
Code ANSI/NEPA70 and Local Electrical Codes.
• When installed in Division 1, “FACTORY
SEALED, CONDUIT SEAL NOT REQUIRED.”
Note 3. Operation
• Keep the “CAUTION” nameplate attached to the
transmitter.
CAUTION: OPEN CIRCUIT BEFORE REMOVING COVER. SEAL ALL CONDUITS WITHIN
18 INCHES. WHEN INSTALLED IN DIV.1,
“FACTORY SEALED, CONDUIT SEAL NOT
REQUIRED.” INSTALL IN ACCORDANCE
WITH THE INSTRUCTION MANUAL IM 1C22.
• Take care not to generate mechanical sparking
when accessing to the instrument and peripheral
devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement
by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void Factory Mutual Explosionproof Approval.
c. FM Intrinsically Safe Type/FM
Explosionproof Type
Model EJA Series pressure transmitters with
optional code /FU1 can be selected the type
of protection (FM Intrinsically Safe or FM
Explosionproof) for use in hazardous locations.
Note 1. For the installation of this transmitter,
once a particular type of protection is
selected, any other type of protection
cannot be used. The installation must
be in accordance with the description
about the type of protection in this
instruction manual.
Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label
other than the selected type of protection when the transmitter is installed.
2.9.2 CSA Certification
a. CSA Intrinsically Safe Type
Caution for CSA Intrinsically safe type. (Following contents refer to “DOC No. ICS003-A12 P.1-1
and P.1-2.”)
Note 1. Model EJA Series differential, gauge,
and absolute pressure transmitters with
optional code /CS1 are applicable for
use in hazardous locations
2-4
IM 1C22J1-01E
2. HANDLING CAUTIONS
• Intrinsically Safe for Class I, Division 1, Groups A,
B, C & D. Class II, Division 1, Groups E, F & G
and Class III, Division 1 Hazardous Locations.
• Nonincendive for Class I, Division 2, Groups A, B,
C & D, Class II, Division 2, Groups F & G, and
Class III, Hazardous Locations. (not use Safety
Barrier)
• Encl. “Type 4X”
• Temperature Class: T4
• Ambient temperature: –40 to 60°C
• Process Temperature: 120°C max.
Note 2. Entity Parameters
• Intrinsically safe ratings are as follows:
Maximum Input Voltage (Vmax) = 30 V
Maximum Input Current (Imax) = 165 mA
Maximum Input Power (Pmax) = 0.9 W
Maximum Internal Capacitance (Ci) = 22.5 nF
Maximum Internal Inductance (Li) = 730 µH
* Associated apparatus (CSA certified barriers)
Maximum output voltage (Voc) ≤ 30 V
Maximum output current (Isc) ≤ 165 mA
Maximum output power (Pmax) ≤ 0.9 W
Note 3. Installation
• All wiring shall comply with Canadian Electrical
Code Part I and Local Electrical Codes.
• The instrument modification or parts replacement
by other than authorized representative of
Yokogawa Electric Corporation and Yokogawa
Corporation of America is prohibited and will void
Canadian Standards Intrinsically safe and
nonincendive Certification.
[Intrinsically Safe]
Hazardous LocationNonhazardous Location
Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G
EJA Series Pressure
Transmitters
+
Supply
Hazardous LocationNonhazardous Location
Class I, II, Division 2,
Groups A, B, C, D, E, F, G
Class III
EJA Series Pressure
Transmitters
Supply
–
[Nonincendive]
+
–
Safety Barrier
+
+
–
–
Not Use
Safety Barrier
General
Purpose
Equipment
General
Purpose
Equipment
+
–
+
–
F0204.EPS
b. CSA Explosionproof Type
Caution for CSA explosionproof type.
Note 1. Model EJA Series differential, gauge, and
absolute pressure transmitters with
optional code /CF1 are applicable for use
in hazardous locations:
• Explosionproof for Class I, Division 1, Groups B,
C and D.
• Dust-ignitionproof for Class II/III, Division 1,
Groups E, F and G.
• Encl “Type 4X”
• Temperature Class: T6, T5, and T4
• Process Temperature: 85°C (T6), 100°C (T5), and
120°C (T4)
• Ambient Temperature: –40 to 80°C
• Supply Voltage: 42 V dc max.
• Output Signal: 4 to 20 mA
Note 2. Wiring
• All wiring shall comply with Canadian Electrical
Code Part I and Local Electrical Codes.
• In hazardous location, wiring shall be in conduit as
shown in the figure.
CAUTION: SEAL ALL CONDUITS
WITHIN 50 cm OF THE ENCLOSURE.
UN SCELLEMENT DOIT ÊTRE
INSTALLÉ À MOINS DE 50 cm DU
BÎTIER.
• When installed in Division 2, “SEALS NOT
REQUIRED.”
Note 3. Operation
• Keep the “CAUTION” label attached to the
transmitter.
CAUTION: OPEN CIRCUIT BEFORE
REMOVING COVER.
OUVRIR LE CIRCUIT AVANT
D´NLEVER LE COUVERCLE.
• Take care not to generate mechanical sparking
when accessing to the instrument and peripheral
devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement
by other than authorized representative of
Yokogawa Electric Corporation and Yokogawa
Corporation of America is prohibited and will void
Canadian Standards Explosionproof Certification.
2-5
IM 1C22J1-01E
2. HANDLING CAUTIONS
Non-Hazardous
Locations
Non-hazardous
Location
Equipment
42 V DC Max.
4 to 20 mA DC
Signal
Non-Hazardous
Locations
Non-hazardous
Location
Equipment
42 V DC Max.
4 to 20 mA DC
Signal
Hazardous Locations Division 1
50 cm Max.
Sealing Fitting
Hazardous Locations Division 2
Sealing Fitting
Conduit
EJA Series
EJA Series
F0205.EPS
c. CSA Intrinsically Safe Type/CSA
Explosionproof Type
Model EJA Series pressure transmitters with
optional code /CU1 can be selected the type of
protection (CSA Intrinsically Safe or CSA
Explosionproof) for use in hazardous locations.
Note 1. For the installation of this transmitter,
once a particular type of protection is
selected, any other type of protection
cannot be used. The installation must be
in accordance with the description about
the type of protection in this instruction
manual.
Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label other
than the selected type of protection when
the transmitter is installed.
Note 2. Entity Parameters
• Intrinsically safe rating of the transmitters are as
follows.
Maximum Input Voltage (Ui) = 30 V
Maximum Input Current (Ii) = 165 mA
Maximum Input Power (Pi) = 0.9 W
Maximum Internal Capacitance (Ci) = 0.02 µF
Maximum Internal Inductance (Li) = 0.73 mH
Note 3. Wiring
• All Wiring shall comply with the Australian
Standard.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement
by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void Standards Association of Australia
Intrinsically safe and Type n Certification.
[Intrinsic Safety]
Hazardous LocationNonhazardous Location
(Zone 0)
EJA Series
Pressure
Transmitter
*1: Any safety barriers used for the output current must be
limited by a resistor “R” such that Imaxout-Uz/R.
Hazardous Location
EJA Series
Pressure
Transmitter
+
–
[Type n]
(Zone 2)
+
–
+
Safety Barrier
–
+
Power Supply
–
*1
F0206.EPS
*2
2.9.3 SAA Certification
a. SAA Intrinsically Safe Type
Caution for SAA Intrinsically safe type and Type n.
Note 1. Model EJA Series differential, gauge, and
absolute pressure transmitters with
optional code /SU1 are applicable for use
in hazardous locations.
• Type of Protection and Marking Code:
Ex ia IIC T4 (Tamb = 60°C) IP67 Class I Zone 0
• Type of Protection and Marking Code:
Ex n IIC T4 (Tamb = 60°C) IP67 Class I Zone 2
• Ambient Temperature: –40 to 60°C
*2: The voltage of the power supply is not exceed 30V dc.
b. SAA Flameproof Type
Caution for SAA flameproof type.
Note 1. Model EJA Series differential, gauge, and
absolute pressure transmitters with
optional code /SU1 are applicable for use
in hazardous locations:
• Type of Protection and marking Code:
Ex d II C T* IP67 Class I Zone 1 (T* see schedule)
• Temperature Class: T6, T5, and T4
• Process Temperature:
85°C (T6), 100°C (T5), and 120°C (T4)
2-6
IM 1C22J1-01E
F0207.EPS
2. HANDLING CAUTIONS
• Supply voltage: 42 V dc max.
• Output Signal: 4 to 20 mA
• Ambient Temperature: –40 to 80°C
Note 2. Wiring
• All wiring shall comply with the Australian
Standard.
Note 3. Operation
• Keep the “CAUTION” label attached to the
transmitter.
CAUTION: AMBIENT TEMPERATURE
ABOVE 75 DEG C SELECT SUITABLE
CABLE. DISCONNECT POWER AND
WAIT 1 MINUTE BEFORE REMAKING
COVER.
• Take care not to generate mechanical sparking
when accessing to the instrument and peripheral
devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement
by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void Standards Association of Australia
Flameproof Certification.
2.9.4 CENELEC (KEMA)/IEC (KEMA)
Certification
a. CENELEC (KEMA) Intrinsically Safe Type
Caution for CENELEC (KEMA) intrinsically safe
type.
Note 1. Model EJA Series differential, gauge, and
absolute pressure transmitters with
optional code /KS1 for potentially explosive atmospheres:
• Type of Protection and Marking code:
EEx ia IIC T4
• Temperature Class: T4
• Process Temperature: 120°C max.
• Ambient Temperature: –40 to 60°C
Note 2. Electrical Data
• In type of explosion protection intrinsic safety EEx
ia IIC only for connection to a certified intrinsically
safe circuit with following maximum values:
Ui = 30 V
Ii = 165 mA
Pi = 0.9 W
Effective internal capacitance; Ci = 22.5 nF
Effective internal inductance; Li = 730 µH
Note 3. Installation
• All wiring shall comply with local installation
requirements. (Refer to the installation diagram)
Note 4. Maintenance and Repair
• The instrument modification or parts replacement
by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void KEMA Intrinsically safe Certification.
[Installation Diagram]
Hazardous Location
Transmitter
+
Supply
–
*1: In any safety barriers used the output current must be limited
by a resistor “R” such that Imaxout-Uz/R.
Nonhazardous Location
+
Safety Barrier
–
F0208.EPS
*1
b. CENELEC (KEMA) Flameproof Type
Caution for CENELEC (KEMA) flameproof type.
Note 1. Model EJA Series differential, gauge, and
absolute pressure transmitters with
optional code /KF1 for potentially explosive atmospheres:
• Type of Protection and Marking Code: EEx d IIC
T6···T4
• Temperature Class: T6, T5, and T4
• Maximum Process Temperature:
85°C (T6), 100°C (T5), and 120°C
• Ambient Temperature: –40 to 80°C
Note 2. Electrical Data
• Supply voltage: 42 V dc max.
• Output signal: 4 to 20 mA
Note 3. Installation
• All wiring shall comply with local installation
requirement.
• The cable entry devices shall be of a certified
flameproof type, suitable for the conditions of use.
Note 4. Operation
• Keep the “CAUTION” label to the transmitter.
CAUTION: WAIT 1 MIN. AFTER
POWER-DISCONNECTION, BEFORE
OPENING THE ENCLOSURE.
• Take care not to generate mechanical sparking
when accessing to the instrument and peripheral
devices in a hazardous location.
Note 5. Maintenance and Repair
• The instrument modification or parts replacement
by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void KEMA Flameproof Certification.
2-7
IM 1C22J1-01E
2. HANDLING CAUTIONS
c. IEC (KEMA) Type of Protection “n”
Caution for IEC (KEMA) Type of Protection “n.”
Note 1. Model EJA Series pressure transmitters
with optional code /KU1 for potentially
explosive atmospheres.
• Type of Protection and Marking Code:
Ex nA IIC T4
• Temperature Class: T4
• Process Temperature: 120°C max.
• Ambient Temperature: –40 to 60°C
Note 2. Electrical Data
• Supply and output circuit ≤ 30 V dc, 165 mA
(terminals + and –)
Note 3. Installation
• All wiring shall comply with local installation
requirements. (refer to the installation diagram)
Note 4. Maintenance and Repair
• The instrument modification or parts replacement
by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void KEMA Type of Protection “n” Certification.
[Installation Diagram]
Hazardous Location
(Zone 2 only)
Transmitter
+
Supply
–
Nonhazardous Location
+
Power Supply
–
Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label other
than the selected type of protection when
the transmitter is installed.
2.9.5 JIS Certification
JIS Flameproof and Intrinsically Safe Type
The model EJA Series pressure transmitters with
optional code /JF1 and /JS1, which have obtained
certification according to technical criteria for explosion-protected construction of electric machinery and
equipment(Standards Notification No. 556 from the
Japanese Ministry of Labor) conforming to IEC
standards, are designed for hazardous areas where
explosive gases and/or inflammable vapors may be
present. [JIS Flameproof Type(optional code /JF1)
allows installation in Division 1 and 2 areas, and JIS
Intrinsically Safe Type(optional code /JS1) allows
installation in Division 0, 1, and 2 areas.]
To observe the safety of flameproof equipment requires
great care during mounting, wiring, and piping. Safety
requirements also place restrictions on maintenance
and repair activities. Users absolutely must read
“Installation and Operating Precautions for JIS Intrinsically Safe Equipment and Flameproof Equipment” at
the end of this manual.
CAUTION
(For JIS flameproof type without integral indicator)
F0209.EPS
Ratings of the Power Supply as follows;
Maximum Voltage: 30 V
Maximum Current: 165 mA
d. CENELEC (KEMA) Intrinsically Safe Type/
CENELEC (KEMA) Flameproof Type/IEC
(KEMA) Type of Protection “n”
Model EJA Series pressure transmitters with
optional code /KU1 can be selected the type of
protection (CENELEC (KEMA) Intrinsically
Safe or CENELEC (KEMA) Flameproof or IEC
(KEMA) Type of Protection “n”) for use in
hazardous locations.
Note 1. For the installation of this transmitter,
once a particular type of protection is
selected, any other type of protection
cannot be used. The installation must be
in accordance with the description about
the type of protection in this instruction
manual.
When the fill fluid near the sensor part moves
from within, the instrument outputs a failure
signal either high or low of the specific signal. In
that case, generate the alarm to identify that the
failure signal is output since the event may
invalidate the flameproof approval.
If the optional integral indicator is equipped, the
indicator identifies the alarm on its display.
Therefore, no other alarm generation is necessary.
Hazardous LocationNonhazardous Location
4 to 20 mA DC1 to 5 V DC
Transmitter
Figure 2.3 Example of using DCS (Distributed Control
System)
Power
Supply
DCS
Display
F0210.EPS
2-8
IM 1C22J1-01E
2.10 EMC Conformity Standards
For EMI (Emission): EN55011, AS/NZS 2064 1/2
For EMS (Immunity): EN50082–2
NOTE
YOKOGAWA recommends customer to apply
the Metal Conduit Wiring or to use the twisted
pair Shield Cable for signal wiring to conform the
requirement of EMC Regulation, when customer
installs the EJA Series Transmitters to the plant.
Note 1: Options depend on your order specifications. For details, see Subsection 9.2, “Model and Suffix Codes.”
Note 2: • Insert the pin (CN4) as shown in the above figure into the H or L side. The pin is set to the H side for delivery (unless
option code /C1 is otherwise specified in the order).
• The setting can be confirmed by calling up parameter D52 using the BRAIN TERMINAL. Refer to Subsection. 7.3.2 (8).
Display Symbol
Meaning of Display Symbol
The output signal being zero-adjusted is increasing.
The output signal being zero-adjusted is decreasing.
2
%, Pa, hPa, kPa, MPa, kgf/cm
atm, mmHg, mmH
O, inH2O, inHg, ftH2O, psi, Torr
2
, gf/cm2, mbar, bar,
Select one of these seventeen available engineering units for the display.
j Before installing the transmitter, read the cautionary
notes in Section 2.4, “Selecting the Installation
Location.” For additional information on the
ambient conditions allowed at the installation
location, refer to Subsection 9.1 “Standard Specifications.”
IMPORTANT
• When welding piping during construction, take
care not to allow welding currents to flow
through the transmitter.
• Do not step on this instrument after installation.
4.2 Mounting the Diaphragm
Seals
Mount the diaphragm seals using the flanges as shown
in Figure 4.2.1. Figure 4.2.2 shows how to mount the
diaphragm seals on a tank. The customer should
prepare the mating flange, gasket, bolts and nuts.
IMPORTANT
• During the diaphragm seal installation, ensure
as far as possible that no seal liquid head is
applied to the diaphragm seal.
• Exercise care so as not to damage diaphragm
surface. Since the diaphragm protrudes approx.
1mm from the flange surface, placing the
diaphragm seals with its diaphragm surface
facing downward may damage the diaphragm
surface.
• Do not sharply bend or twist capillary tube or
apply excessive stress to it.
IMPORTANT
Install the sealed diaphragm
so that the shank positions
downward.
Capillary tube
Diaphragm seal
Flange
Bolt
The product is shipped with
these parts assembled.
Correctly install the diaphragm seals on
the high and low pressure sides of the
process, checking the label on each seal.
Figure 4.2.1 Mounting the Diaphragm Seals
Diaphragm
ød
Gasket
Nut
IMPORTANT
Please use a gasket which has a bigger inside
diameter than that of gasket facing (ød) on
diaphragm seal. In case a gasket which has a
smaller inside diameter than that of gasket
facing is used, it may cause an error as the
gasket prevents diaphragm from working correctly. (Refer to Subsection 9.4 ‘Dimensions’)
F0401.EPS
F0402.EPS
Figure 4.2.2 Installing the Diaphragm Seals to a Tank
4.3 Transmitter Mounting
j The transmitter can be mounted on a nominal 50
mm (2-inch) pipe using the mounting bracket
supplied, as shown in Figure 4.3.1 The transmitter
can be mounted on either a horizontal or a vertical
pipe.
j When mounting the bracket on the transmitter,
tighten the (four) bolts that hold the transmitter to a
torque of approximately 39 N·m {4 kgf·m}.
IMPORTANT
Never loosen the four screws securing the cover
flange or the screws at the joints between the
capillary tube and cover flanges (if the seal liquid
leaks, the transmitter cannot be used).
4-1
IM 1C22J1-01E
Vertical pipe mounting
Horizontal pipe mounting
U-bolt nut
Transmitter
mounting bolt
4. INSTALLATION
IMPORTANT
The transmitter should be installed at least 700
mm (when the model code of the material of the
wetted part is H, at least 1300 mm) below the
process connection to ensure a positive head
pressure of fill fluid. If it can not be installed at
least 700 mm below the process connection,
please use the equation below:
(P–P0)3dHg
h=37.5310–3 [mm]
ds
h:Vertical height between the process
connection and the transmitter (mm)
h≤0: Install the transmitter at least h (mm)
below the process connection
h>0: Install the transmitter at most h (mm)
above the process connection
P:Pressure in the tank (Pa abs)
P0: Minimum working pressure limit of the
transmitter (Pa abs)
If the ambient temperature range is
–10 to 50°C.
5254 (Wetted parts material code S)
6980 (Wetted parts material code T)
13019 (Wetted parts material code H)
6980 (Wetted parts material code U)
ds: Specific gravity of fill fluid (at 25°C), refer
to GS 1C22J3-E.
dHg:Specific gravity of the Mercury 13.6 (at
25°C)
Mounting bracket
50mm (2-inch) pipe
Figure 4.3.1 Transmitter Mounting
U-bolt
F0403.EPS
h
(+)
0
P
(–)
F0404.EPS
Figure 4.3.2 Example of Installation to Tank (Caution on
Installation)
4-2
IM 1C22J1-01E
4. INSTALLATION
4.4 Affixing the Teflon Film
The FEP Teflon option includes a teflon film and
fluorinated oil.
Before mounting the diaphragm seal to the process
flange, affix the teflon film as follows :
IMPORTANT
(1) Position the diaphragm seal so that the
diaphragm is in a upward position.
(2) Pour the fluorinated oil on the diaphragm and
gasket area covering it completely and
evenly. Be careful not to scratch the diaphragm or change the its shape.
(3) Affix the teflon film over the diaphragm and
gasket area.
(4) Next, carefully inspect the cover and try to
identify any entrapped air between the
diaphragm and the teflon film. The air must
be removed to ensure accuracy. If air
pockets are present, use your fingers to
remove the air by starting at the center of the
diaphragm and work your way out.
(5) Place the gasket with the teflon film and affix
to the process flange.
Teflon film
PART No.
F9347XA
F9347YA
Process flange size
For 3inch (80 mm)
For 2inch (50 mm)
4.5 Rotating Transmitter Section
The DPharp transmitter section can be rotated in 90°
segments.
(1) Remove the two Allen screws that fasten the
transmitter section and pressure-detector section,
using the Allen wrench supplied with the transmitter.
(2) Rotate the transmitter section slowly in 90°
segments.
(3) Tighten the two Allen screws.
IMPORTANT
Do not rotate the transmitter section more than
180°.
Transmitter section
Rotate 90° or 180°
segments
Rotate 90° or 180°
segments
Conduit
connection
Zero-adjustment
screw
Fluorinated oil
[PART No.: F9145YN]
Diaphragm
Gasket area
Diaphragm seal
Figure 4.4.1 Affixing the Teflon Film
F0405.EPS
Pressure-detector section
Figure 4.5.1 Rotating Transmitter Section
4-3
F0406.EPS
IM 1C22J1-01E
5.WIRING
5. WIRING
5.1 Wiring Precautions
IMPORTANT
• Lay wiring as far as possible from electrical
noise sources such as large capacity transformers, motors, and power supplies.
• Remove electrical connection dust cap before
wiring.
• All threaded parts must be treated with waterproofing sealant. (A non-hardening silicone
group sealant is recommended.)
• To prevent noise pickup, do not pass signal
and power cables through the same ducts.
• Explosion-protected instruments must be wired
in accordance with specific requirements (and,
in certain countries, legal regulations) in order
to preserve the effectiveness of their explosionprotected features.
• The terminal box cover is locked by an Allen
head bolt (a shrouding bolt) on CENELEC,
SAA, and JIS flameproof type transmitters.
When the shrouding bolt is driven clockwise by
an Allen wrench, it is going in and cover lock is
released, and then the cover can be opened.
See Subsection 8.4 “Disassembly and Reassembly” for details.
Refer to The “Installation and Operating
Precautions for JIS Flameproof Equipment”
and “Installation and Operating Precautions
for JIS Intrinsically Safe Equipment” at the
end of this manual for correct wiring.
CAUTION
If the transmitter is flameproof and the ambient
temperature is 50°C or more, use cables having
a maximum allowable heat resistance of at least
75°C in consideration of the instrument's generation of heat or the cables' self-heating.
(d) In environment where oils, solvents, corrosive gases
or liquids may be present, use wires or cables that
are resistant to such substances.
(e) It is recommended that crimp-on solderless terminal
lugs (for 4 mm screws) with insulating sleeves be
used for leadwire ends.
5.3 Connections of External
Wiring to Terminal Box
5.3.1 Power Supply Wiring Connection
Connect the power supply wiring to the SUPPLY +
and – terminals.
Transmitter terminal box
+
Power supply
–
F0501.EPS
Figure 5.3.1 Power Supply Wiring Connection
5.2 Selecting the Wiring Materials
(a) Use stranded leadwires or cables which are the
same as or better than 600 V grade PVC insulated
wire (JIS C3307) or equivalent.
(b) Use shielded wires in areas that are susceptible to
electrical noise.
(c) In areas with higher or lower ambient temperatures,
use appropriate wires or cables.
5.3.2 External Indicator Connection
Connect wiring for external indicators to the CHECK +
and – terminals.
(Note) Use a external indicator whose internal resistance is 10 Ω or
less.
Power supply
+
–
Transmitter terminal box
Figure 5.3.2 External Indicator Connection
5-1
External indicator
IM 1C22J1-01E
F0502.EPS
Loading...
+ 50 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.