All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or
transmitted, in any form or by any means, mechanical, electronic, photocopying, recording, or otherwise,
without the prior written permission of Y askawa. No p atent liab ility is assumed with respect to the use of the
information contained herein. Moreover, because Yaskawa is constantly striving to improve its high-quality
products, the information contained in th is manual is subject to chan ge without not ice. Every precau tion has
been taken in the preparation of this manual. Yaskawa assumes no responsibility for errors or omissions.
Neither is any liability assumed for damages resulting from the use of the information contained in this
publication.
YASKAWA ELECTRIC TOBP C730600 56A 1000-Series Option SI-W3 Installation Guide3
1 Preface and Safety
1Preface and Safety
Yaskawa manufactures products used as components in a wide variety of industrial systems
and equipment. The selection and application of Yaskawa products remain the responsibility
of the equipment manufacturer or end user. Yaskawa accepts no responsibility for the way its
products are incorporated into the final system design. Under no circumstances should any
Yaskawa product be incorporated into any product or design as the exclusive or sole safety
control. Without exception, all controls should be designed to detect faults dynamically and
fail safely under all circumstances. All systems or equipment designed to incorporate a
product manufactured by Yaskawa must be supplied to the end user with appropriate
warnings and instructions as to the safe use and operation of that part. Any warnings
provided by Yaskawa must be promptly provided to the end user. Yaskawa offers an express
warranty only as to the quality of its products in conforming to standards and specifications
published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, I S
OFFERED. Yaskawa assumes no liability for any personal injury, property damage, losses,
or claims arising from misapplication of its products.
◆ Applicable Documentation
The following manuals are available for the option:
Read this manual first.
The installation manual is packaged with
the option and contains information
required to install the option and set up
related drive parameters.
The technical manual contains detailed
information about the option. Access the
following sites to obtain the technical
manual:
U.S.: http://www.yaskawa.com
Europe: http://www.yaskawa.eu.com
Japan: http://www.e-mechatronics.com
For questions, contact your local
Yaskawa sales office or the nearest
Yaskawa representative.
4YASKAWA ELECTRIC TOBP C730600 56A 1000-Series Option SI-W3 Installation Guide
1 Preface and Safety
Yaskawa Drive
The drive manuals cover basic
installation, wiring, operation procedures,
Yaskawa AC Drive
1000-Series
Quick Start Guide
Yaskawa AC Drive
1000-Series
Technical Manual
functions, troubleshooting, and
maintenance information.
The manuals also include important
information about parameter settings and
drive tuning.
Access these sites to obtain Yaskawa
instruction manuals:
U.S.: http://www.yaskawa.com
Europe: http://www.yaskawa.eu.com
Japan: http://www.e-mechatronics.com
For questions, contact your local
Yaskawa sales office or the nearest
Yaskawa representative.
◆ Terms and Abbreviations
Note:Indicates supplemental information that is not related to safety messages.
Drive:Yaskawa AC Drive 1000-Series
Option:Yaskawa AC Drive 1000-Series Option LONWORKS SI-W3
• Trademarks are the property of their respective owners.
◆ Supplemental Safety Information
Read and understand this manual before installing, operating, or servicing this option. Install
the option according to this manual and local codes.
The following conventions indicate safety messages in this manual. Failure to heed these
messages could cause fatal injury or damage products and related equipment and systems.
Indicates a hazardous situation, which, if not avoided, will result in death or serious
injury.
Indicates a hazardous situation, which, if not avoided, could r esult in death or
serious injury.
Indicates a hazardous situation, which, if not avoided, could r esult in minor or
moderate injury.
• The diagrams in this book may include options and drives without covers or safety shields to
illustrate details. Be sure to reinstall covers or shields before operating any devices. Use the option
according to the instructions described in this manual.
• Any illustrations, photographs, or examples used in this manual are provided as examples only and
may not apply to all products to which this manual is applicable.
• The products and specifications described in this manual or the content and presentation of the
manual may be changed without notice to improve the product and/or the manual.
• When ordering new copies of the manual, contact a Yaskawa representative or the nearest Yaskawa
sales office and provide the manual number shown on the front cover.
Heed the safety messages in this manual.
Failure to comply will result in death or serious injury.
The operating company is responsible for any injuries or equipment damage resulting
from failure to heed the warnings in this manual.
Do not modify the drive or option circuitry.
Failure to comply could result in damage to the drive or option and will void warranty.
Yaskawa is not responsible for any modification of the product made by the user. This
product must not be modified.
Do not expose the drive or option to halogen group disinfectants.
Failure to comply may cause damage to the electrical components in the drive or option.
Do not pack the drive in wooden materials that have been fumigated or sterilized.
Do not sterilize the entire package after the product is packed.
The LONWORKS Communication Option Card (Model SI-W3) is based on LonT alk. It acts
as an interface for connecting an AC drive to a LONWORKS network using the LonTalk
protocol.
With the option card insta lled to the drive, the following operations are possible with devices
using the LonTalk protocol.
• operate the drive
• monitor the operation status of the drive
• change parameter settings.
◆ Applicable Models
The option can be used with the models in Table 1.
Table 1 Applicable Models
Drive Series
A1000≥ PRG 1017
<1> See “PRG” on the drive nameplate for the software version number.
Software Version <1>
8YASKAWA ELECTRIC TOBP C730600 56A 1000-Series Option SI-W3 Installation Guide
3 Receiving
ERRRUN
RXTX
*123456789ABC*
*123456789ABC*
*123456789ABC*
MANUAL
3Receiving
Please perform the following tasks upon receiving the option:
• Inspect the option for damage. Contact the shipper immediately if the option appears
damaged upon receipt.
• Verify receipt of the correct model by checking the model number printed on the option
nameplate
(Refer to Figure 1 on page 10 for more information).
• Contact your supplier if you have received the wrong model or the option does not
function properly.
◆ Option Package Contents
Descri
ption:
Quant
ity:
◆ Tools Required for Installation
• A Phillips screwdriver (M3 metric / #1, #2 U.S. standard size) is required to install the
• A straight-edge screwdriver (blade depth: 0.4 mm, width: 2.5 mm) is required to wire the
YASKAWA ELECTRIC TOBP C730600 56A 1000-Series Option SI-W3 Installation Guide9
Option
_
1131 11
Ground
Wire
Screws
(M3)
LED LabelBar Code
option.
option terminal block.
Note: Tools required to prepare option cables for wiring are not listed in this manual.
Installation
Manual
4 Option Components
4Option Components
◆ LONWORKS Option
Figure 1
M
A
B
C
D
E
F
LKJIHG
A – Connector (CN5)H – LED (SERVICE)
B – Installation holeI – Service Switch
C–LED (ERR)
D – LED (RUN)
E–LED (TX)
F–LED (RX)<1>M – Terminal block CN1
G – Neuron ID
<1> Refer to Option LED Display on page 12 for details on the LEDs.
<2> The ground wire provided in the option shipping package must be connected during installation .
<1>J – Digital operator connector (CN3)
<1>K – Model number
<1>L – Gr ound terminal and installation hole <2>
Figure 1 LONWORKS Option Components
Underside
10YASKAWA ELECTRIC TOBP C730600 56A 1000-Series Option SI-W3 Installation Guide
4 Option Components
◆ Terminal Block CN1
The communication terminal is a pluggable terminal block that serves as the connection
point of the LONWORKS network communication cable to the option.
Table 2 Terminal Descriptions
TerminalTerminal No.NameDescription
1
2
3
1ASignal Line A
2SLDShield
3BSignal Line B
◆ Connector CN3 for Digital Operator
DANGER! Electric Shock Hazard. Do not touch drive main terminals and control terminals. Failure to
comply will result in death or serious injury.
Connecting the CN3 and the digital operator (model: JVOP-182) lets the user set the DDC
function parameters.
◆ Service Switch
This is a neuron ID output switch. Pressing this switch outputs the neuron ID to the netwo rk.
■Initializing Bind Data
Cycling power to the drive while holding down the service switch will clear the bind data,
and reset the configuration properties back to the factory sett ings.
Note: Do not turn off the power to the drive while initializing the bind data. The RUN, RX, TX, and
ERR LEDs are lit (ON) during initialization of the bind data.
Do not connect or disconnect wiring while the power is on.
Failure to comply will result in death or serious injury.
Disconnect all power to the drive and wait at least the amount of time specified on the
drive front cover safety label. After all indicators are off, measure the DC bus voltage to
confirm safe level, and check for unsafe voltages before servicing. The internal capacitor
remains charged after the power supply is turned off.
Electrical Shock Hazard
Do not remove the front covers of the drive while the power is on.
Failure to comply could result in death or serious injury.
The diagrams in this section may include options and drives without covers or safety
shields to show details. Be sure to reinstal l covers or shields before operating any devices.
Use the option according to the instructions described in this manual.
Do not allow unqualified personnel to use equipment.
Failure to comply could result in death or serious injury.
Maintenance, inspection, and replacement of parts must be performed only by authorized
personnel familiar with installation, adjustment, and maintenance of this product.
Do not touch the option card while the power to the drive is on.
Do not touch the drive’s main terminals and control circuit terminals when using the
service switch and digital operator connector on the option unit. Failure to comply could
result in death or serious injury.
YASKAWA ELECTRIC TOBP C730600 56A 1000-Series Option SI-W3 Installation Guide13
5 Installation Procedure
NOTICE
W ARNING
Do not use damaged wires, stress the wiring, or damage the wire insulation.
Failure to comply could result in death or serious injury.
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to
overheating of electrical connections.
Damage to Equipment
Observe proper electrostatic discharge (ESD) procedures when handling the option,
drive, and circuit boards.
Failure to comply may result in ESD damage to circuitry.
Never shut the power off while the drive is running or outputting voltage.
Failure to comply may cause the application to operate incorrectly or damage the drive.
Do not operate damaged equipment.
Failure to comply may cause further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance.
Use shielded twisted-pair wires and ground the shield to the ground terminal of the drive.
Properly connect all pins and connectors.
Failure to comply may prevent proper operation and possibly damage equipment.
Check wiring to ensure that all connections are correct after installing the option
and connecting any other devices.
Failure to comply may result in damage to the option.
Prior to installing the option, wire the drive, make the necessary connections to the drive
terminals, and verify that the drive functions normally. Refer to the Quick Start Guide
packaged with the drive for information on wiring and connecting the drive.
Figure 2 shows an exploded view of the drive with the option and related components for
reference.
Figure 2
N
M
L
K
J
I
H
G
A – Insertion point for CN5H – Included screws
B – Option cardI – Ground wire
C – Front coverJ – Option terminal block
D – Digital operatorK – Drive grounding terminal (FE)
E – LED labelL – Connector CN5-A
F – Terminal coverM – Connector CN5-B
G – Removable tabs for wire routingN – Connector CN5-C
Refer to the instructions below to install the option.
1. Shut off power to the drive, wait the appropriate amount of time for voltage to
dissipate, then remove the digital operator (D) and front covers (C, F). Refer to the
Quick Start Guide packaged with the drive for directions on removing the front
covers. Cover removal varies depending on drive size.
DANGER! Electrical Shock Hazard. Disconnect all power to the drive and wait at least the amount of time
specified on the drive front cover safety label. After all indicators are off , measure the DC bus voltage to
confirm safe level, and check for unsafe voltages before servicing to prevent electric shock. The internal
capacitor remains charged even after the power supply is turned off.
NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling
the option, drive, and circuit boards. Failure to comply may result in ESD damage to circuitry.
Figure 3
Figure 3 Remove the Front Covers and Digital Operator
2. With the front covers and digital operator removed, apply the LED label (E) in the
Figure 4
appropriate position on the drive top front cover (C).
C
ERRRUN
RXTX
E
Figure 4 Apply the LED Label
3. Make sure the screws on the left and right sides of the option terminal block (J) are
xm) or 4.4 to 5.43 (inch-lbs), then
B
H
NS MS
Figure 5
tightened with a tightening torque of 0.5 to 0.6 (N
insert the option card (B) into the CN5-A connector (L) located on the drive and
fasten it using one of the included screws (H).
4. Connect the ground wire (I) to the ground terminal (K) using one of the remaining
provided screws (H). Connect the other end of the ground wire (I) to the remaining
ground terminal and installation hole on the option using the last remaining provided
Figure 6
screw (H).
Figure 6 Connect the Ground Wire
Note: There are two screw holes on the drive for use as ground terminals. When connecting more than
two options, two ground wires will need to share the same drive ground terminal.
5. Select the proper type and length of communication cables.
Refer to Wiring Specifications on page 22 for details on selecting cables.
about 5.5 mm (7/32”)
When not using
crimped insulated
sleeves
Pull back the shielding and lightly
twist the end with fingers, keeping
the ends from fraying.
LONWORKS drop line
(do not solder ends)
Blade depth of
0.4 mm or less
Blade width of
2.5 mm or less
Tightening torque:
0.22 to 0.25 N m
or 4.4 to 5.3 in-lbs
Terminal block CN1
Loosen the screws and
insert the wire into the
opening on the terminal block.
6. Prepare and connect the communication cables to the terminal block as shown in
Figure 7 and Figure 8. Take particular precaution to ensure that each wire is
properly connected and wire insulation is not accidentally pinched into electrical
terminals.
WARNING! Fire Hazard. Tighten all terminal screws according to the specified tightening torque. Loose
electrical connections could result in death or serious injury by fire du e to overheating e lectrical connections.
Tightening screws beyond the specified tightening torque may result in erroneo us opera tion, d amage to the
terminal block, or cause a fire.
NOTICE: Heat shrink tubing or electrical tape may be required to ensure that cable shielding does not come
into contact with other wiring. Insufficient insulation may cause a sh ort circuit that can damage the opt ion or
the drive.
Figure 7
Insulation
Shield
Shield
Figure 7 Preparing Ends of Shielded Cable
Note: Separate communication cables from main circuit wiring and other electrical lines.
Figure 8
Shield sheath
(Insulate with electrical tape
or shrink tubing)
Depending on the drive model, some drives may require routing wire through the
side of the front cover to the outside. In these cases, cut out the perforated openings
in the left side of the drive front cover as shown in Figure 10-A, and leave no sharp
edges to damage wiring.
Route the wiring inside the enclosure as show in Figure 10-B for drives that do not
require routing through the front cover. Refer to the Peripheral Devices & Options
Figure 10
section of the drive Technical Manual for more information.
5 Installation Procedure
A – Route wires through the openings
provided on the left side of the
front cover.
<1> The drive will not meet NEMA Type 1 requirements if wiring is exposed outside the enclosure.
A free topology segment must be terminated. The segment can be terminated anywhere.
Figure 12
Twisted pair terminator
Ra
Ca
100 µF
50 V (min)
Figure 12 RC Network (Ra = 52.3 Ω ±1%, 1/8 W)
Cb
100 µF
50 V (min)
Shielded twisted pair
◆ XIF Files, Resource Files
XIF files and the resource files for this option card are not included. For more information,
either contact Yaskawa's sales department directly or your nearest Yask awa repre se ntative.
The following parameters are used to set up the drive for operation with the option.
Confirm proper setting of the parameters in Table 4 before starting network
communications.
Table 4 Related Parameters
No.
(Addr.
Hex)
b1-01
(180)
b1-02
(181)
F6-01
(3A2)
F6-02
(3A3)
F6-03
(3A4)
F6-06
(3A7)
<2>
F6-07
(3A8)
NameDescriptionValues
Selects the frequency reference input source
Frequency Reference
Selection 1
Run Command
Selection 1
Communications Error
Operation Selection
External Fault from
Comm. Option
Detection Selection
External Fault from
Comm. Option
Operation Selection
Torque Reference/
Torque Limit Selection
from Comm. Option
Multi-Step Speed
Enable/Disable
Selection when
NefRef/ComRef is
Selected
0: Digital Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus communications
3: Option
4: Pulse Input (Terminal RP)
Selects the run command input source
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S
2: MEMOBUS/Modbus communications
3: Option
Determines drive response after a bUS error during
communications with the option
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
Sets the condition for external fault detection (EF0)
0: Always detected
1: Detected only during operation
Determines drive response for external fault input (EF0)
detection during LONWORKS communication
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
0: Torque reference / torque limit via network
communications are disabled.
1: Torque reference / torque limit via network
communications are enabled.
Default: 1
Range: 0 to 4
(Set to 3 for
LONWORKS
only)
Default: 1
Range: 0 to 3
(Set to 3 for
LONWORKS
only)
Default: 1
Range: 0 to 3
Default: 0
Range: 0, 1
Default: 1
Range: 0 to 3
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
24YASKAWA ELECTRIC TOBP C730600 56A 1000-Series Option SI-W3 Installation Guide
6 Related Parameters
No.
(Addr.
Hex)
F6-08
(36A)
<1> Setting F6-01 or F6-03 to 3 will allow the drive to continue to operate after detecting a fault. When allowing the
drive to continue operation after fault detection, be sure to take proper safety measures such as installing an
emergency stop switch.
<2> Enabled in CLV, AOLV/PM, and CLV/PM control modes (A1-02 = 3, 6, or 7). When enabled, d5-01 determines
whether the value is read as the torque limit value (d5-01 = 0) or read as the torque reference value (d5-01 = 1).
This value is read as the torque limit in CLV/PM.
<3> Setting specifies that the torque reference or the torque limit is to be provided with Torque Reference/Torque
Limit Selection from Comm. Option (F6-06 = 1). The motor might not rotate if a torque reference or a torque limit
is not received from the network.
NameDescriptionValues
Reset Communication
Parameters
Determines which F6- and F7- parameters are reset to
default values when initializing the drive using A1-03.
0: Do not reset parameters
1: Reset parameters
Output: FSNVT_obj_status nvoStatus
Displays the status of objects in a node.
Member NameDescription
object_idObject ID (refer to the object request)
bit 31invalid_idTurns ON if the object_id specified by nviRequest is invalid.
bit 30invalid_requestTurns ON if the object_request specified by nviRequest is invalid.
bit 29disabled
bit 28out_of_limitsNot supported. (Always 0.)
bit 27open_circuitNot supported. (Always 0.)
bit 26out_of_serviceNot supported. (Always 0.)
bit 25mechanical_faultNot supported. (Always 0.)
bit 24feedback_failureNot supported. (Always 0.)
bit 23over_rangeNot supported. (Always 0.)
bit 22under_rangeNot supported. (Always 0.)
bit 21electrical_faultNot supported. (Always 0.)
bit 20unable_to_measureNot supported. (Always 0.)
bit 19comm_failureNot supported. (Always 0.)
bit 18fail_self_testNot supported. (Always 0.)
bit 17self_test_in_progressNot supported. (Always 0.)
bit 16locked_outNot supported. (Always 0.)
bit 15manual_controlNot supported. (Always 0.)
bit 14in_alarmNot supported. (Always 0.)
bit 13in_overrideNot supported. (Always 0.)
bit 12report_maskNot supported. (Always 0.)
bit 11programming_modeNot supported. (Always 0.)
bit 10programming_failNot supported. (Always 0.)
bit 9alarm_notify_disabledNot supported. (Always 0.)
bit 8 to 0reservedAlways 0.
Indicates whether or not a given object is enabled for operation.
Turns ON when an object is disabled.
Nominal Motor Speed in RPM
(Motor Rated Rotation Frequency)
Minimum Ramp Down Time
(Minimum Deceleration Time)
Output Frequency Monitor Minimum Change Range
Setting 1 (nciFreqMinDelta1)
Output Frequency Monitor Minimum Change Range
Setting 2 (nciFreqMinDelta2)
Cumulative Power Monitor Upper Limit:
nciDrvEngylimit
Cumulative Power Monitor Minimum Change Range
Setting
YASKAWA ELECTRIC TOBP C730600 56A 1000-Series Option SI-W3 Installation Guide33
9 Troubleshooting
9Troubleshooting
◆ Drive-Side Error Codes
Table 6 lists the various option-related fault codes. Refer to the drive Technical Manual for
further information about fault codes.
■Faults
Both bUS (Option Communication Error) and EF0 (External Fault Input from the option)
can appear as either an alarm or as a fault. When a fault occurs, the digital operator ALM
LED remains lit. When an alarm occurs, the digital operator ALM LED flashes.
Check the following items first when an error code occurs on the drive:
• Communication cable connections
• Make sure the option is properly installed to the drive
• Did a momentary power loss interrupt communications?
Table 6 Fault Displays, Causes, and Possible Solutions
Digital Operator DisplayFault Name
Option Communication Error
bUS
CausePossible Solution
Network has stopped communicating
Communication cable is not connected
properly
A data error occurred due to noise
Option is damaged
Connection timeout
The connection was lost after establishing initial communication.
Only detected when the run command frequency reference is assigned to
the option
(bl-01 = 3 or bl-02 = 3).
Check for faulty wiring.
Correct any wiring problems.
• Counteract noise in the control circuit wiring, main circuit lines, and
ground wiring.
• If a magnetic contactor is the noise source, install a surge absorber to the
contactor coil.
• Use only the LONWORKS network cables.
Ground the shield on the controller side and on the option side.
If there are no wiring problems and the fault continues to occur, replace
the option.
The option Receive Heart Beat timer timed out.
Make sure that Receive Heart Beat time is set properly.
Check the option connection and communication signal.
34YASKAWA ELECTRIC TOBP C730600 56A 1000-Series Option SI-W3 Installation Guide
9 Troubleshooting
Digital Operator DisplayFault Name
EF0
CausePossible Solution
An external fault is being sent from the
network
Problem with the network program
Digital Operator DisplayFault Name
oFA00
CausePossible Solution
Non-compatible option connected to
drive port CN5-A
Digital Operator DisplayFault Name
oFA01
CausePossible Solution
Problem with the connector between the
drive and option
Digital Operator DisplayFault Name
to
oFA30 to oFA43
CausePossible Solution
Option hardware faultReplace the option. Contact Yaskawa for assistance.
Digital Operator DisplayFault Name
oFb00
CausePossible Solution
Non-compatible option connected to
drive port CN5-B
External Fault Input from the option
The alarm function for an external device has been triggered.
• Remove the cause of the external fault
• Reset the external fault input from the network
Check the program used by the network and make the appropriate
corrections.
Non-Compatible Option connected to drive port CN5-A
Option is not properly connected.
Use only compatible options. Connect the SI-W3 to CN5-A. For other
option connections refer to the Installation Manual for those options.
Option Fault (CN5-A)
Option is not properly connected.
Turn the power off and check the connectors between the drive and option.
Option Fault (CN5-A)
Communication ID error.
Non-Compatible Option connected to drive port CN5-B
Non-compatible option is connected.
Use only compatible options. Connect the SI-W3 to CN5-A. For other
option connections refer to the Installation Manual for those options.
ModelSI-W3
Note TypeHost Application Node
Communication Speed78 kbps
Communication ICNeuron chip FT3120
Communication DriverFT-X1 (free topology)
ProtocolLonTalk protocol node
Network Variables
Network Variable Alias Maximum: 50
Maximum Number of
Connections
Total Wiring LengthMax 500 m
Ambient Temperature-10°C to +50°C (14°F to 122°F)
Humidity95% RH or lower with no condensation
Storage Temperature-20°C to +60°C (-4°F to 140°F) allowed for short-term transport of the product
Area of UseIndoor (free of corrosive gas, airborne particles, etc.)
Altitude1000 m (3280 ft.) or lower
Total: 236
Standard Network Variable Types (SNVT): Variable Speed Motor Drive function profile
Ver1.1
64 (in one segment)
YASKAWA ELECTRIC TOBP C730600 56A 1000-Series Option SI-W3 Installation Guide37
10 Specifications
QSG_only
◆ Revision History
Revision dates and manual numbers appear on the bottom of the back cover.
MANUAL NO.ޓTOBP C730600 56A
Published in Japan November 2011 11-11
151 Lorong Chuan, #04-01, New Tech Park, 556741, Singapore
Phone: 65-6282-3003
http://www.yaskawa.com.sg
YASKAWA ELECTRIC (SHANGHAI) CO., LTD.
No. 18 Xizang Zhong Road, 17F, Harbour Ring Plaza, Shanghai, 200001, China
Phone: 86-21-5385-2200
http://www.yaskawa.com.cn
YASKAWA ELECTRIC (SHANGHAI) CO., LTD. BEIJING OFFICE
Room 1011, Tower W3 Oriental Plaza, No. 1 East Chang An Ave.,
Dong Cheng District, Beijing, 100738, China
Phone: 86-10-8518-4086
YASKAWA ELECTRIC TAIWAN CORPORATION
9F, 16, Nanking E. Rd., Sec. 3, Taipei, 104, Taiwan
Phone: 886-2-2502-5003
Fax: 55-11-5581-8795
Fax: 44-1236-458182
Fax: 82-2-784-8495
Fax: 65-6289-3003
Fax: 86-21-5385-3299
Fax: 86-10-8518-4082
Fax: 886-2-2505-1280
YASKAWA ELECTRIC CORPORATION
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture
thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations. Therefore, be sure
to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.
bit 27open_circuit
bit 26out_of_service
bit 25mechanical_fault
bit 24feedback_failure
bit 23over_range
bit 22under_range
bit 21electrical_fault
bit 20unable_to_measure
bit 19comm_failure
bit 18fail_self_test
bit 17self_test_in_progress
bit 16locked_out
bit 15manual_control
bit 14in_alarm
bit 13in_override
bit 12report_mask
bit 11programming_mode
bit 10programming_fail
bit 9alarm_notify_disabled
bit 8 〜 0