Yaskawa SigmaLogic User Manual

OVERVIEW
DANGER!
Improper wiring can and will cause
bodily harm as well as damage to the equipment.
Please read this document and other documentation provided with the V1000 thoroughly before attemptin
g any
installation.
U/T1 V/T2 W/T3
3Ø Induction
motor
1Ø Input Power
Connect frame to
ground
Input
Protection
(Fuse or C.B.)
two
three
L1
L2
Fig. 1:
Input Power and Output Motor Electrical
Connections for Single Phase Input V1000
WARNING! DO NOT CONNECT ANY OF THE
FOLLOWING TERMINALS TO EARTH GROUND
SINGLE PHASE
INPUT V1000
(R/L1) (S/L2)
(U/T1)
(V/T2)
Connect to
chassis
ground
Fig.1 & 2
(see Step 1)
WITH POWER OFF, Make sure to follow good wiring practices and all applicable codes. Ensure that the equipment is grou
nded properly as
shown.
DANGER:
LETHAL VOLTAGES ARE PRESENT. Before applying power to the V1000, ensure that all protective covers ar
e fastened and all wiring connections are secure.
After the power has been turned OFF, wait at least
five
minutes
until the charge indicator extinguishes completely
before touching any wiring, circuit boards or components.
!
R/L1 S/L2
U/T1 V/T2 W/T3
3Ø Induction
motor
3Ø Input Power
Connect frame to
ground
Input
Protection
(Fuse or C.B.)
two
three
L1
L2
L3
Fig. 2:
Input Power and Output Motor Electrical
Connections for Three Phase Input V1000
(R/L1) (S/L2)
(T/L3)
(U/T1)
(V/T2)
(W/T3)
Connect to
chassis ground
R/L1 S/L2
T/L3
B1 B2
-
+ +1 +2
(W/T3)
THREE PHASE
INPUT V1000
Step
2
Step
1
Step3Step
4
OFF
Fig. 3 Digital Operator
Fig.1 or 2,
two
three
Step 3
After the power has been turned OFF, wait at least five minutes until the charge indicator extinguishes completely
before
touching any wiring, circuit boards or components.
DANGER
If motor rotation is not correct, then power down the V1000 Drive.
!
DO NOT RUN
THE MOTOR
Fig. 3
Digit Flashing
Enter Motor Power in kW (Kilowatt)
For standard AC motors use
the default setting for motor
base frequency (60Hz), motor
poles (4) and m
otor rated
speed.
Warning! Sudden movement hazard. The V1000 and motor may start unexpectedly during Auto-Tuning.
Warnin
g! Electric Shock Hazard. High voltage will be supplied to the motor when
stationary Auto-Tuning is p
erformed. Do not touch the motor during auto-tuning.
Notice: Auto-Tuning will not function properly wh
en a brake is engaged on the
load. Ensure the motor shaft can freely rotate. Never perform an Auto-Tu
ne with
motor connected to a load.
!
DO NOT RUN THE MOTOR
Motor HP to kW = HP x 0.746 Example: 10HP = 10 x 0.746 = 7.46 kW
YAI Document Number: TM.V1000.01 03/25/2013 © Yaskawa America, Inc. - (800) YASKAWA (927-5292) Fax (847) 887-7310 DrivesHelpDesk@yaskawa.com www.yaskawa.com
V1000 AC Drive Quick Start Procedure
Page 1 of 2
Page 1 of 2
V1000 Model Identification and
The following procedure is a supplement to other documentation supplied with this equipment and will guide the user in properly wiring the V1000 and motor. It will also allow the installer to check motor direction, correct if necessary and perform a motor Auto-Tune.
When installing the system be sure to follow good wiring practices and all applicable codes. Ensure that the mounting of the various components are secure and that the environment, such as extreme dampness, poor ventilation etc. will not cause system degradation.
To make sure you received the correct model it is essential to verify the V1000 nameplate with your order; and make sure that the drive has the correct rating so it
can be used with your motor. Please check the nameplate
information as shown in the example below.
x Check that the available power meets the input power
requirements.
x Ensure that the output power from the VFD is
compatible with the motor requirements.
x In the case of systems with multiple VFDs, follow the
above procedure for each VFD and motor.
Mounting the V1000
The mounting of the V1000 is extremely important regarding environment and accessibility. Depending on your system, there are various models available and the mounting dimensions (footprint) may be different. Because the mounting procedure is fairly extensive, it is beyond the scope of this document, the user is referred to the V1000 Quick Start Guide (Manual No. TOEPC71060614) received with the V1000, Section 1 Physical Installation. Match the model that you received and follow the procedure described in the manual to ensure a safe and functional installation. In cases where the system has more than one V1000, refer to the proper clearances required for adequate ventilation. Please pay particular attention to:
x The clearances to be maintained around the enclosure
x The environmental specifications such as avoiding
for adequate ventilation.
excessive dampness, extreme temperatures, chemical exposure, corrosive areas etc. to avoid damage to the equipment and to maintain safety.
Removing Protective Covers
Improper removal of the V1000 protective covers, as well as the conduit bracket (NEMA 1) can cause extensive damage to the V1000. To avoid damage to these items, please pay particular attention to the V1000 Quick Start Guide, Section 3, Protective Covers.
Open Chassis
Mounting
1012(13)
NEMA 1
Connect Motor and
Line Power
below show the electrical connections for the
input power and motor terminals for various V1000 Drive
Select the proper diagram for the single or three
Models. phase model you are installing
make the appropriate connections.
To change direction of
motor rotation, swap any
of the
leads (See Step 2)
To change direction of
motor rotation, swap any
of the
leads (See Step 2)
motor
motor
and
Check Motor Direction
In this step the motor is checked for proper direction and operation. This test is to be performed solely from the digital operator. Apply power to the V1000 after all the electrical connections have been made and protective covers have been re-attached. At this point, D
shown below in
Next, press
should turn on.
First Digit Flashing
Next, press
First Digit Flashing
Next, press
should now be operating at low speed running in the correct forward (clockwise) direction.
Next, press on the Digital Operator.
Digital Operator
Use precaution, and refer to output leads to the motor (U/T1, V/T2 and W/T3). After the wiring change, repeat
, the Digital Operator should display as
.
on the Digital Operator; the green LED
on the Digital Operator once, then press
.
on the Digital Operator. The motor
turned off.
swap any
and recheck motor direction.
REV LED
of the
Auto-tuning
In this step the V1000 is setup for use with the motor. Make sure all protective covers have been re-attached then apply power to the V1000.
Press three times until the Digital Operator
shows the Auto-Tuning menu (A.Tun) then press
.
Press
parameter T1-02 then press .
Press
Press
same procedure described above to adjust its value.
After setting parameter T1-07 press
the Auto-Tuning start command.
Next, press
Auto-Tuning procedure.
The display will show when the Auto-Tuning procedure has been successfully
completed. Please reference the V1000 Quick Start Guide or repeat the Auto-Tuning procedure
again if the display shows an error message.
two times until the Digital Operator shows
to select the digit you would like to change and use the
and to adjust the value, then press the to save the value.
to go to select the next parameter and follow the
Motor Rated Voltage (e.g. 230 V, 460 V)
Motor Rated current (e.g. 11.0 A, 22.0 A)
Motor Base Frequency (e.g. 60.0 Hz)
Motor Poles (e.g. 4 Poles)
Motor Rated Speed (e.g. 1750 rpm)
.
to select
on the Digital Operator; The V1000 will now start the
Step
5
DO NOT RUN THE MOTO
Access Parameter Menu and Change Parameter Value
Monitor Motor Frequency and Motor Current
FOUT
Please refer to the technical manual on how to access other drive monitors.
Motor Current
Output Frequency
Change Parameter Value
Select Parameter
Select Parameter Menu
DO NOT RUN THE MOTOR
This section may require you to change one or more V1000 parameters. Please refer to Step 5 for a det
ailed explanation on how to change parameters.
SELECT START / STOP CONTROL METHOD
1.
Start / Stop Control from Digital Operator
Set Value to
b1-02
2.
Start / Stop Control from external terminals (switch or relay contact)
Set Value to
( Factory Default)
Wiring Diagram: 2-Wire Control
Wiring Diagram: 3-Wire Control
Use for momentary contacts
Use for maintained contacts
NOTE: It is beyond the scope of this document to program the V1000 drive for network communication control. Please refer to the Technical Manual
for this selection.
SELECT SPEED METHOD
b1-01
(Factory Default)
1.
Adjust motor speed / frequency from the Digital Operator
Set Value to
2.
Speed reference from external terminals (Potentiometer or Analog Signal)
Set Value to
(Factory Default)
Potentiometer
2K Ohm
0 ~ 10Vdc
4 ~ 20mA
+
Located inside the drive on
the control card
(Set Parameter A1-03 to 3330)
Step
6
This section may require you to change one or more V1000 parameters. Please refer to Step 5 for a detailed explanation on how to change parameters.
FREQUENTLY ASKED QUESTIONS
GENERAL PURPOSE APPLICATION PARAMETERS
Question:
Answer:
2220
3330
Question:
Answer:
Question:
OV
Answer:
Question:
OL1
Answer:
Question:
Answer:
WARNING!
Yaskawa America, Inc.
2121 Norman Drive South
Waukegan, IL 60085
(800) YASKAWA (927-5292) Fax (847
) 887-7310
DrivesHelpDesk@yaskawa.com www.yaskawa.com
YAI Document Number: TM.V1000.01 03/25/2013
© Yaskawa Electric America, Inc.
Step
7
V1000 AC Drive Quick Start Procedure
Page 2 of 2
Changing Parameters and
Monitoring the V1000
This step shows how to access and modify a V1000 parameter as well as how to monitor V1000 signals such as output frequency and motor current.
Make sure all protective covers have been re-attached and power is turned on. D
R.
V1000 Digital Operator power-up state
Press
the digital operator shows the parameter
menu (PAr) then press
Press to select the digit
you would like to change. Next use
and to select the
two times until
.
parameter group, sub-group or number.
Modify the parameter value using
and and press
to save the new value.
V1000 Digital Operator power-up state
Press until the F
LED turns on. The display now shows
the actual drive output frequency in Hz.
Pressing again will
show the motor output current. The ‘A’
behind the value means ‘Amps’.
This step shows how to setup the sequence and reference method of the V1000. The sequence method determines how the V1000 drive receives its start and stop command and the reference method determines how the speed of the motor is controlled. Make sure all protective covers have been re-attached and power is turned on. D
Go to parameter b1-01,
To adjust frequency use / and press .
Go to parameter b1-01,
User Terminals User Terminals
P1 P2PCA1
A2 +V AC AM AC MP
Go to parameter b1-02,
Go to parameter b1-02,
S3 S5 S6 S7 HC SC H1 RPS2 S4S1
Forward
Reverse
Selecting Start/Stop and Speed Method
.
P1 P2PCA1
User Terminals User Terminals
A2 +V AC AM AC MP
Start
Switch
Stop
Switch
S3 S5 S6 S7 HC SC H1 RPS2 S4S1
Normally
Open
Normally
Closed
Reverse
Quick Start Parameters
The following table lists the general purpose application parameters as well as frequently asked questions.
Parameter
b1-01
b1-02
b1-03
b1-04
C1-01
C1-02
C6-01
d1-01
d2-01
d2-02
E2-01
L1-01
L1-02
Default Value
1
1
1 Stop Method Selection
0 Reverse Operation
10.0 sec. Acceleration Time The time it takes to ramp up from 0 to maximum motor speed.
10.0 sec. Deceleration Time The time it takes to ramp down from maximum motor speed to 0.
1 Normal / Heavy Duty
0.00 Hz Frequency Reference Frequency setting when speed is set from the keypad.
100.0 % Frequency Upper Limit Maximum motor speed allowed (e.g. 100 % = Max rpm)
0.0 % Frequency Lower Limit Minimum motor speed allowed (e.g. 100 % = Max rpm)
* Motor Rated Current Motor nameplate current
1 Motor Overload Selection
1.0 min Motor Overload Time Sets the motor thermal overload protection time.
Reference Source Speed Control Method
Run Source / Start/Stop Control Method
How do I reset the drive back to factory default settings?
Go to parameter A1-03 and set value 2
(Please refer to Step 6 for wiring diagram)
How do I adjust the time it takes the motor to speed up or slow down?
Adjust the acceleration time parameter C1-01 and deceleration time C1-02.
How do I prevent my drive from tripping on an O
Increase deceleration time parameter C1-02.
How do I prevent my drive from tripping on an O
Verify motor rated current parameter E2-01 and motor overload parameter settings
L1-01 Motor overload selection, L1-02 Motor overload protection time.
W
I want to run my motor above the nominal motor speed?
Increase the value of parameter E1-04 Maximum Frequency
Verify that the motor and system allow for this.
Description
0 = Digital Operator (Adjust Motor Speed from keypad) 1 = Terminals (Speed Pot. / 0 – 10V / 4—20mA)
0 = Digital Operator (Start/Stop motor from keypad) 1 = Terminals (Start/Stop using external contact / switch)
0 = Ramp to stop (Motor ramps down at stop command) 1 = Coast to stop (Motor freewheels at stop command)
0 = Allow motor to run in reverse direction 1 = Reverse direction prohibited
0 = Normal Duty (Use for fan and pump applications) 1 = Heavy Duty (Use for conveyor, mixer, applications)
0 = Disabled 1 = Standard Fan Cooled Motor 2 = Standard Blower Cooled Motor 3 = Vector Duty Motor
for 2 wire control or 3
fault (overvoltage) while my motor is ramping down?
fault (overload) while my motor is ramping down?
Comments
for 3 wire control
Loading...