YASKAWA SI-EP3/V Installation Manual

Page 1
YASKAWA AC Drive-V1000 Option
PROFINET
Installation Manual
Type SI-EP3/V
To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance. Ensure the end user receives this manual.
MANUAL NO. TOEP YEACOM 06A
Page 2
Page 3
Table of Contents
1 PREFACE AND SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2 PRODUCT OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
3 RECEIVING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
4 OPTION COMPONENTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5 INSTALLATION PREPARATION . . . . . . . . . . . . . . . . . . . . . 17
6 PROCEDURE A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
7 PROCEDURE B. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
8 NETWORK TOPOLOGY AND CONNECTIONS . . . . . . . . . .41
9 OPTION DRIVE PARAMETERS . . . . . . . . . . . . . . . . . . . . . .43
10 WEB INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
11 TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
12 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
Copyright © 2011 YASKAWA AMERICA, INC.
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of Yaskawa. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because Yaskawa is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Yaskawa assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 3
Page 4
This Page Intentionally Blank
4 YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 5

1 Preface and Safety

STOP
(Hz)
(Hz) (A) (V)
V1000
1 Preface and Safety
Yaskawa manufactures products used as components in a wide variety of industrial systems and equipment. The selection and application of Yaskawa products remain the responsibility of the equipment manufacturer or end user. Yaskawa accepts no responsibility for the way its products are incorporated into the final system design. Under no circumstances should any Yaskawa product be incorporated into any product or design as the exclusive or sole safety control. Without exception, all controls should be designed to detect faults dynamically and fail safely under all circumstances. All systems or equipment designed to incorporate a product manufactured by Yaskawa must be supplied to the end user with appropriate warnings and instructions as to the safe use and operation of that part. Any warnings provided by Yaskawa must be promptly provided to the end user. Yaskawa offers an express warranty only as to the quality of its products in conforming to standards and specifications published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS OFFERED. Yaskawa assumes no liability for any personal injury, property damage, losses, or claims arising from misapplication of its products.

Applicable Documentation

The following manuals are available for the PROFINET option:
PROFINET Option
Yaskawa AC Drive V1000-Series Option SI-EP3/V PROFINET Installation Manual Manual No.: TOEP YEACOM 06
Yaskawa AC Drive V1000-Series Option SI-EP3/V PROFINET Technical Manual Manual No.: SIEP YEACOM 06
Read this manual first. The installation manual is packaged with the option and contains information required to install the option, verify operation, and set up related drive parameters.
The technical manual contains detailed information about the option pertaining to communication protocols, and supported features and messaging. In the U.S., access; http://www.yaskawa.com to obtain the Technical Manual. Customers in other areas should contact a Yaskawa representative.
Yaskawa Drive
Yaskawa AC Drive V1000 Quick Start Guide Manual:TOEP C710606 47
Yaskawa AC Drive V1000 Technical Manual Manual No.: SIEP C710606 18
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 5
The drive manuals cover basic installation, wiring, operation procedures, functions, troubleshooting, and maintenance information. The manuals also include important information about parameter settings and drive tuning. Access these sites to obtain Yaskawa instruction manuals; U.S.: http://www.yaskawa.com Europe: http://www.yaskawa.eu.com Japan: http://www.e-mechatronics.com Other areas: contact a Yaskawa representative.
Page 6
1 Preface and Safety
Yaskawa AC Drive V1000 NEMA Type 4X/IP66 Installation Manual Manual No.: TOBP C710606 35
This manual contains basic information required to install the V1000 NEMA Type 4X/IP66 drive. Carefully review this manual along with the Quick Start Guide accompanying the NEMA Type 4X/IP66.

Terms

Note: Indicates supplemental information that is not related to safety messages
Drive: Yaskawa AC Drive V1000-Series
Option: Yaskawa AC Drive V1000-Series SI-EP3/V PROFINET option
H: Indicates an engineering unit for hexadecimal number format
1012: Indicates a drive feature or function that is only available in drive software version 1012 or greater

Registered Trademarks

• All trademarks are the property of their respective owners.
6 YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 7
1 Preface and Safety
DANGER
W ARNING
CAUTION
NOTICE

Supplemental Safety Information

Read and understand this manual before installing, operating, or servicing this option. The option must be installed according to this manual and local codes.
The following conventions are used to indicate safety messages in this manual. Failure to heed these messages could result in serious or possibly even fatal injury or damage to the products or to related equipment and systems.
Indicates a hazardous situation, which, if not avoided, will result in death or serious injury.
Indicates a hazardous situation, which, if not avoided, could result in death or serious injury.
Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury.
Indicates an equipment damage message.
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 7
Page 8
1 Preface and Safety
DANGER
NOTICE
General Safety
General Precautions
• The diagrams in this section may include options and drives without covers or safety shields to illustrate details. Be sure to reinstall covers or shields before operating any devices. The option should be used according to the instructions described in this manual.
• Any illustrations, photographs, or examples used in this manual are provided as examples only and may not apply to all products to which this manual is applicable.
• The products and specifications described in this manual or the content and presentation of the manual may be changed without notice to improve the product and/or the manual.
• When ordering new copies of the manual, contact a Yaskawa representative or the nearest Yaskawa sales office and provide the manual number shown on the front cover.
Heed the safety messages in this manual.
Failure to comply will result in death or serious injury.
The operator is responsible for injuries or equipment damage caused from failure to heed the warnings in the manual.
Do not expose the drive or option to halogen group disinfectants.
Failure to comply may cause damage to the electrical components in the option.
Do not pack the drive in wooden materials that have been fumigated or sterilized.
Do not sterilize the entire package after the product is packed.
Do not modify the drive or option circuitry.
Failure to comply could result in damage to the drive or option and will void warranty.
Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified.
8 YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 9
1 Preface and Safety
Lire le manuel avant l'installation. Attendre 5 minutes apres la coupure de l'alimentation, pour permettre la decharge des condensateurs. Pour repondre aux exigences , s assurer que le neutre soit relie a la terre, pour la serie 400V.
Option Unit Warning Labels
Warning information is displayed on the option unit as shown in the figure below. Follow all warnings and safety instructions when using the product.
Warning Contents
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 9
Page 10

2 Product Overview

2 Product Overview

About This Product

The SI-EP3/V option connects the V1000 drive to a PROFINET network and facilitates the exchange of data.
This manual explains the handling, installation and specifications of this product.
The SI-EP3/V option is a simple, networking solution that reduces the cost and time to wire and install factory automation devices, while providing interchangeability of like components from multiple vendors.
By installing the option to a drive, it is possible to do the following from a PROFINET master device:
• Operate the drive
• Monitor the operation status of the drive
• Change parameter settings.
SI-EP3/V is PROFINET Conformance Class A certified.

Applicable Models

This option can be used with the drive models in Table 1.
Table 1 Applicable Models
Drive Software Version <1>
CIMR-VAAA CIMR-VABA
CIMR-VAFA CIMR-VAJA
CIMR-VALA
CIMR-VAGA CIMR-VAHA
<1> See “PRG” on the drive nameplate for the software version number.
1012
508
10 YASKAWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 11

3 Receiving

3 Receiving
Please perform the following tasks after receiving the option.
• Inspect the option for damage. Contact the shipper immediately if the option appears damaged upon receipt.
• Verify receipt of the correct model by checking the model number printed on the option nameplate (Refer to Top Views of Option on page 12 for nameplate positioning).
• Contact your supplier if you have received the wrong model or the option does not function properly.

Option Package Contents

Description: Option Unit Ground Wires Installation Manual
MANUAL
_
Quantity: 141
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 11
Page 12

4 Option Components

A
B
C
H
E
D
H
G
I
J
R
F
Q
00000000000000
SI-EP3/V
1XXX
P
N
K
M
OL
S
Option with cover removed
CN5 connector port
Option with cover attached
Option Underside
4 Option Components

SI-EP3/V PROFINET Option

Figure 1
A–LED (MS)
<1> K – Port 2 LED (10/100) <1>
B–LED (NS)<1> L–Port 2 C – Option cover M – Port 2 LED (LINK/ACT) D – PROFINET PCB N – Port 1 LED (10/100)
<1> Refer to Option LED Display on page 14 for details on the LEDs. <2> Ground wires are packaged loose inside the option packaging and must be connected during installation.
E – Screw hole (attaching option cover) O – Port 1 F – Nameplate P – Port 1 LED (LINK ACT) G – Functional Earth cable connection (FE) Q – PROFINET cable connection H – Mounting tabs R – Option connector (CN5)
I – Ground wire
<2> S – Option Firmware Label
J – Pass-through hole for ground wire
Figure 1 Top Views of Option
(VST)
12 YASKAWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
<1>
<1>
<1>
Page 13
4 Option Components
Dimensions with Option Added- IP00/IP20 Open Chassis and
IP20/NEMA Type 1
The installed option adds 27 mm (1.06 in.) to the total depth of the drive.
Figure 2
27 mm (1.06 in.)
Figure 2 Dimensions

Terminal CN1

The communication connector on the option is a modular, dual port, RJ45 female communication connector designated CN1. CN1 is the connection point for a customer supplied male Ethernet network RJ45 CAT5e (STP) communication cable.
Figure 3
RJ45 CAT5e Female Communication Cable Ports 1 and 2
RJ45 CAT5e Network Communication Cable
Figure 3 RJ45 Connections
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 13
Page 14
4 Option Components
Table 2 Male 8-way Ethernet Modular Connector (Customer-Supplied)
Male EtherNet 8-Way Modular Connector Pin Description
1 (Pair 2) Transmit data (TXD) +
2 (Pair 2) Transmit data (TXD) -
3 (Pair 3) Receive data (RXD) +
4 (Pair 1) Not used
5 (Pair 1) Not used
6 (Pair 3) Receive data (RXD) -
7 (Pair 4) Not used
8 (Pair 4) Not used <1>
<1> Not used for 10 Mbps and 100 Mbps networks.
<1>
<1>
<1>

Option LED Display

The option has six LEDs:
Bi-color Status LEDs:
• Module status (MS) red/green
• Network status (NS) red/green
Ethernet LEDs (2 each):
• Network speed-10/100 yellow
• Link status and network activity-Link/Act green
The operational states of the option LEDs after the power-up diagnostic LED sequence is completed are described in Table 3. The states with a number in parenthesis are the number of pulses of 250 ms on, 250 ms off cycles, followed by 500 ms off, then repeating the cycle. Wait at least 2 seconds for the power-up diagnostic process to complete before verifying LED states.
14 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 15
Name
MS (visible through drive cover)
NS (visible through drive cover)
10/100 (visible at RJ45 cable ports)
LINK/ACT (visible at RJ45 cable ports)
4 Option Components
Table 3 Option LED States
Indication
Color Status
OFF Power supply OFF
Green ON Option operating
Green Flashing (1) Diagnostics Diagnostic data available.
Green Flashing (2) Configuration tool Identified by a configuration tool.
Red ON
Red Flashing (1) Configuration error (non-fatal) Configuration error.
Red Flashing (2) No IP (non-fatal) No IP address assigned.
Red Flashing (3) No station name (non-fatal) No station name assigned.
Red Flashing (4) Init failure (non-fatal) Failed to initialize module.
Green/ Red
OFF Offline or Power supply OFF
Green ON Connected
Green Flashing Connected and stopped
Red ON BUS fault Unrecoverable BUS fault.
Red Flashing (1) Lost communication
Red Flashing (2) Lost link No link detected to network.
Yellow OFF 10 Mbps is established
Yellow ON 100 Mbps is established
Green OFF Link is not established
Green ON Link is established
Green Flashing
Flashing Option self-test The option is in self-test mode.
Operating Status Remarks
Power is not being supplied to the drive.
The option is operating normally and initialization is complete.
Default MAC or fatal error occurred.
Link is established and there is network activity
Default MAC address has been programmed or the option has detected an unrecoverable error.
Connection established with I/O controller and in RUN mode.
Connection established with I/O controller and in STOP mode.
Host communication is temporarily lost.
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 15
Page 16
4 Option Components
Power-Up Diagnostics
An LED test is performed each time the drive is powered up. The initial boot sequence may take several seconds. After the LEDs have completed the diagnostic LED sequence, the option is successfully initialized. The LEDs then assume operational conditions as shown in
Table 3.
Table 4 Power-Up Diagnostic LED Sequence
Sequence Module Status (MS) Network Status (NS) Time (ms)
1 Green OFF 250
2 Red OFF 250
3GreenOFF -
4 Green Green 250
5 Green Red 250
6GreenOFF -
16 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 17

5 Installation Preparation

W ARNING
5 Installation Preparation

Section Safety

DANGER
Electrical Shock Hazard
Do not connect or disconnect wiring while the power is on.
Failure to comply will result in death or serious injury.
Disconnect all power to the drive, wait at least five minutes after all indicators are off, measure the DC bus voltage to confirm safe level, and check for unsafe voltages before servicing. The internal capacitor remains charged after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc.
Electrical Shock Hazard
Do not remove the option cover while the power is on.
Failure to comply could result in death or serious injury.
The diagrams in this section may include options and drives without covers or safety shields to show details. Be sure to reinstall covers or shields before operating any devices. Use the option according to the instructions described in this manual.
Do not allow unqualified personnel to use equipment.
Failure to comply could result in death or serious injury.
Maintenance, inspection, and replacement of parts must be performed only by authorized personnel familiar with installation, adjustment, and maintenance of this product.
Do not touch circuit boards while the power to the drive is on.
Failure to comply could result in death or serious injury.
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 17
Page 18
5 Installation Preparation
NOTICE
W ARNING
Do not use damaged wires, stress the wiring, or damage the wire insulation.
Failure to comply could result in death or serious injury.
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
Damage to Equipment
Observe proper electrostatic discharge (ESD) procedures when handling the option, drive, and circuit boards.
Failure to comply may result in ESD damage to circuitry.
Never shut the power off while the drive is running or outputting voltage.
Failure to comply may cause the application to operate incorrectly or damage the drive.
Do not operate damaged equipment.
Failure to comply may cause further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance.
Use shielded twisted-pair wires and ground the shield to the ground terminal of the drive.
Properly connect all pins and connectors.
Failure to comply may prevent proper operation and possibly damage equipment.
Check wiring to ensure that all connections are correct after installing the option and connecting any other devices.
Failure to comply may result in damage to the option.
18 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 19
5 Installation Preparation
Model Number Location
CIMR-VUBA00012GAA 200V 1PHASE 12 0A/11.0A
S/N J013ZB797110004
Model Number Location

Prior to Installing the Option

Prior to installing the option, wire the drive, make necessary connections to the drive terminals, and verify that the drive functions normally without the option installed. Refer to the product manual packaged with the drive for information on wiring and connecting the drive.

Choosing the Correct Installation Procedure

The installation procedure differs between NEMA 4X and IP00/IP20 enclosure types. The enclosure type is identified within the drive model number. Refer to STEP 1. and Figure 6 on page 20 to identify the drive enclosure type.
1. Locate the drive model number using Figure 4 and Figure 5. Record the model
Figure 4
Figure 5
number for use in STEP 2.
Figure 4 Model Number Location: IP00/IP20 Open Chassis and IP20/NEMA Type 1 Enclosure
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 19
Figure 5 Model Number Location: NEMA 4X Enclosures
Page 20
5 Installation Preparation
2. Use Figure 6 to find the digit within the model number that identifies the enclosure
Figure 6
type. Record the enclosure type for use in STEP 3.
CIMR - V U 2 A 0001 F A A
Drive
<1> Refer to manual TOBPC71060635 for more information on these models. <2> Refer to manual TOBPC71060621 for more information on these models. <3> Drives with these specifications do not guarantee complete protection for the specified environmental condition.
V1000 Series
Region
No.
Code
A Japan
B China
C Europe
T Asia
U USA
No. Voltage Class
B
2
4
Customized
No.
Specifications
A Standard model
1-phase, 200-240 Vac
3-phase, 200-240 Vac
3-phase, 380-480 Vac
Drive capacity
F
Enclosure Type
No.
IP00/Open-Chassis
A
IP20/Open-Chassis
B
F IP20/NEMA Type 1
NEMA 4X/IP66 <1>G
J
IP20/Finless <2>
L IP00/Finless <2>
Design Revision Order
Environmental
No.
Specification <3> Standard
A
Humidity- and
M
dust-resistant Oil-resistant
N
Vibration-resistant
S
Figure 6 Drive Enclosure Type Identification
3. Use the enclosure type digit recorded from STEP 2. and Tab le 5 to select the
correct installation Procedure A on page 22 or Procedure B on page 33.
Table 5 Installation Procedure by Enclosure Type
Model Number-Enclosure Type Digit Drive Enclosure Type Installation Procedure
A, B IP20/Open-Chassis Procedure A on page 22
F IP20/NEMA Type 1
<1>
G NEMA Type 4X/IP66 Procedure B on page 33
<1> Installing the option on an IP20/NEMA Type 1 enclosure drive voids NEMA Type 1 protection while maintaining
IP20 conformity.
Procedure A on page 22
20 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 21
5 Installation Preparation
4. Tool requirements. Select tools for your enclosure type and model, refer to
Table 6. Next, go to the chosen installation Procedure A on page 22 or Procedure B on page 33 from STEP 3.
Note: Tools required to prepare the option cables for wiring are not listed in this manual.
Table 6 Tool Requirements
Model Number
Enclosure Type Digit
A, B IP20/Open-Chassis
F IP20/NEMA Type 1
G NEMA Type 4X/IP66
<1> Screw sizes vary by drive capacity. Select a screwdriver appropriate for the drive capacity.
Drive Enclosure Type Drive Capacity Tools
All
2A0030G/H 2A0040G/H 2A0056G/H 2A0069G/H 4A0018G/H 4A0023G/H 4A0031G/H 4A0038G/H
Other capacities
Phillips screwdriver ­M3 metric/#1, #2 U.S. standard
<1>
size
10 mm socket wrench Phillips screwdriver ­M3 metric/#1, #2 U.S. standard
<1>
size
8 mm socket wrench Phillips screwdriver ­M3 metric/#1, #2 U.S. standard
<1>
size
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 21
Page 22

6 Procedure A

6 Procedure A
Use Procedure A steps to install the option on drives with IP00/IP20 Open Chassis & IP20/NEMA Type 1 enclosures or enclosure type digits A, B or F within the model number.

Procedure A Steps

DANGER! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury. Before installing the option, disconnect all power to the drive. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are off and measure the DC bus voltage level to confirm safe level.
NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling the option, drive, and circuit boards. Failure to comply may result in ESD damage to circuitry.
1. Shut off power to the drive, wait at least five minutes after confirming the DC bus
voltage is safe, then loosen the screw that fastens the front cover in place and remove the front cover. This drive front cover will be replaced by the option cover.
Figure 7
Cover removal varies depending on drive size.
Figure 7 Remove the Front Cover
2. The remaining installation steps differ by drive model. Find the drive model number
and identify the Enclosure Type Digit on the drive nameplate and refer to the appropriate Table 7 row and “Proceed to STEP” column.
Table 7 Procedure A- Steps by Drive Model
Enclosure Type Digit within
Model Number
A, B IP20/Open-Chassis CIMR-VAB STEP 3. on page 23
F IP20/NEMA Type 1
<1> Installing the option on an IP20/NEMA Type 1 enclosure drive voids NEMA Type 1 protection while maintaining
IP20 conformity.
22 YASKAWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Enclosure Type Drive Model Proceed to STEP
CIMR-VAF STEP 7. on page 25
<1>
Page 23
3. IP20/Open-Chassis models CIMR-VAB.
Remove the bottom cover of the drive. Apply pressure using fingers to the tabs on each side of the bottom cover. Pull the bottom cover away from the drive while pushing in on the tabs to release the cover from the drive. Refer to Figure 8 for details. Refer to Figure 9 for drive models CIMR-VBA0006B to BA0018B, 2A0010B to 2A0069B, and 4A0001B to 4A0038B, which require removing the terminal cover
Figure 8
Figure 9
prior to removing the bottom cover.
Figure 8 Remove the Bottom Cover on an IP20/Open-Chassis Drive
(Models CIMR-VBA0001B to BA0003B and 2A0001B to 2A0006B)
6 Procedure A
Figure 9 Remove the Terminal Cover and Bottom Cover on an IP20/Open-Chassis Drive
(Models CIMR-VBA0006B to BA0018B; 2A0010B to 2A0069B; 4A0001B to 4A0038B)
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 23
Page 24
6 Procedure A
To Option ground screw FE Screw size: M3
To drive ground terminal Screw size: M3.5 to M6
4. Select one of the four different length ground wires packaged with the option.
Choose the proper ground wire by first removing the ground terminal screw from the drive, Figure 11. Test fit the screw (size M3.5 to M6) into each of the four ground
Figure 10
drive-side ring lugs prior to installation. Ground wire selection varies by drive model.
Figure 10 Ground Wire Selection
5. On IP20/Open-Chassis models, connect the drive side of the ground wire to the
Figure11
drive ground terminal.
Ground terminal
Ring lug for Option ground FE Size: M3
Drive-side ground terminal ring lug (size varies): M3.5 to M6
Ground wire
Ground wire
Figure 11 Ground Wire Connection on IP20/Open-Chassis
6. Proceed to STEP 12. on page 28 to continue the option installation procedure for
IP20/Open-Chassis models.
24 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 25
6 Procedure A
7. From STEP 2. for IP20/NEMA Type 1 enclosure models CIMR-VAF,
loosen the screw on the front of the NEMA Type 1 terminal cover and remove it from the drive. Refer to Figure 12 for details. Refer to Figure 13 for drive models CIMR-VBA0006F to BA0018F, 2A0010F to 2A0069F, and 4A0001F to 4A0038F, which require removing the plastic terminal cover prior to removing the NEMA Type 1 terminal cover.
Figure 12
Figure 13
(Models CIMR-VBA0006F to BA0018F; 2A0010F to 2A0069F; 4A0001F to 4A0038F)
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 25
Figure 12 Remove the NEMA Type 1 Terminal Cover
Figure 13 Remove the Terminal Cover on an IP20/NEMA Type 1 Drive
Page 26
6 Procedure A
8. Loosen the screws attaching the NEMA Type 1 conduit bracket to the drive to
Figure 14
remove the NEMA Type 1 conduit bracket.
Figure 14 Remove the NEMA Type 1 Conduit Bracket
9. Select one of the four different length ground wires packaged with the option,
Figure 15. Choose the proper ground wire by first removing the ground terminal
screw from the drive Figure 16. Test fit the screw (size M3.5 to M6) into each of the four ground drive-side ring lugs prior to installation. Ground wire selection varies by
Figure 15
drive model.
To drive ground terminal Screw size: M3.5 to M6
To Option ground screw FE Screw size: M3
Figure 15 Ground Wire Selection
26 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 27
6 Procedure A
Ground terminal
Ground wire
Drive ground terminal/ located on NEMA Type 1 conduit bracket screw
Ground wire
Drive-side ground terminal ring lug (size varies): M3.5 to M6
Ring lug for Option ground FE Size: M3
IP20/NEMA Type 1 Enclosure
10. On IP20/NEMA Type 1 enclosure drives, the screw for the drive ground terminal
also acts as one of the screws that attaches the NEMA Type 1 conduit bracket to the drive. Reattach the NEMA Type 1 conduit bracket according to Figure 16 and connect the drive-side of the ground wire to the drive ground terminal.
Figure 16
Figure 16 Reattach the NEMA Type 1 Conduit Bracket and Connect the Ground Wire
11. Reattach the IP20/NEMA Type 1 bottom terminal cover according to Figure 17.
Figure 17
Proceed to STEP 13.
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 27
Figure 17 Reattach the Bottom Cover IP20/NEMA Type 1
Page 28
6 Procedure A
IP20/Open-Type
12. Reattach the IP20/Open Type bottom cover. Keep the ground wire inside of the
Figure 18
bottom cover when reattaching.
Figure 18 Reattach the Bottom Cover IP20/Open Type
13. Reinstall the terminal cover on these models.
Refer to Figure 19. CIMR-VBA0006 to BA0018, V2A0010 to 2A0069, and V4A0001 to 4A0038. These models require routing the ground wire through the notch on the bottom of the terminal cover. Refer to Figure 20. CIMR-VBA0006 to BA0018, V2A0010 to 2A0020, and
Figure 19
V4A0001 to 4A0011.
(Models CIMR-VBA0006 to BA0018; 2A0010 to 2A0069; 4A0001 to 4A0038)
28 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Figure 19 Reattach the Terminal Cover
Page 29
Figure 20
Route ground wire through inside of drive bottom cover
Option unit ground terminal (FE)
Ground wire
Option through-hole for ground wire
Terminal cover Ground wire routing notch (model specific)
(Models CIMR-VBA0006 to BA0018; 2A0010 to 2A0020; 4A0001 to 4A0011)
14. Refer to Figure 21 for ground wire routing.
Figure 21
Figure 20 Terminal Cover Ground Wire Notch
6 Procedure A
Figure 21 Ground Wire Routing
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 29
Page 30
6 Procedure A
Line up tabs
CN5 Connector
Ta b
Ta b
15. Attach the option to the drive. Properly seat the tabs on the left and right sides of the
Figure 22
option to the drive case.
Figure 22 Connect the Option
30 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 31
6 Procedure A
Option ground terminal FE
Ground wire to drive ground terminal screw
RJ45 8-pin Shielded Twisted Pair Cat5e cable(s)
16. Connect the ground wire at the option ground terminal FE. Tighten the screw to 0.5
Figure 23
~ 0.6 Nm or (4.4 ~ 5.3 in lbs) using an M3 Phillips screwdriver.
Figure 23 Connect the Ground Wire to the Option
17. To connect the option to a network, firmly connect RJ45 8-pin Shielded Twisted Pair
Cat5e cable(s) into the modular connector ports. Refer to Network Topology and
Connections on page 41.
NOTICE: Do not connect or disconnect the communication cable while the drive is powered up or while the drive is in operation. Failure to comply may cause a static discharge, which will cause the option card to stop working properly. Cycle power on the drive and option card to attempt to reestablish functionality.
Figure 24
Figure 24 CN1 RJ45 CAT5e Communication Cable Ports
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 31
Page 32
6 Procedure A
Line up tabs
18. Attach the option cover by aligning the tabs with the mounting holes, seat the front
Figure 25
NOTICE: Damage to Equipment. Take proper precautions when wiring the option so that the front covers will easily fit back onto the drive. Make sure no cables are pinched between the front covers and the drive when replacing the cover. Failure to comply may result in damage to circuitry and equipment.
cover into place, and tighten the screw on the front.
Figure 25 Attach the Option Cover
19. Set drive parameters in Table 10 on page 43 for proper option performance.
20. End of installation Procedure A.
32 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 33

7 Procedure B

Remove LED operator cable
Connector release tab
Front cover
Front cover bolt
Drive
CN1 port
7 Procedure B
Use Procedure B steps to install the option on drives with a NEMA Type 4X/IP66 enclosures or with the enclosure type digit G within the model number.

Procedure B Steps

DANGER! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply will result in death or serious injury. Before installing the option, disconnect all power to the drive. The internal capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least five minutes after all indicators are off and measure the DC bus voltage level to confirm safe level.
NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling the option, drive, and circuit boards. Failure to comply may result in ESD damage to circuitry.
1. Shut off power to the drive, wait at least five minutes after confirming the DC bus
voltage is safe, then loosen the bolts that fasten the front cover in place and remove the front cover.
2. Press firmly on the connector release tab holding the LED operator cable (CN1) in
Figure 26
place and disconnect the cable.
Figure 26 Remove the Drive Front Cover
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 33
Page 34
7 Procedure B
3. Remove the lower terminal cover from the drive, if provided.
Apply pressure using fingers on the left and right tabs. Lift and pull the cover forward to release. IMPORTANT! The lower terminal cover is required for secure mounting of the option on certain models. Use Table 8 to find the lower terminal cover part number by model. Contact your Yaskawa representative for ordering, if this part is not available in your drive.
Table 8 Lower Terminal Cover Part Number by Model
Drive Model CIMR-V Terminal Cover Part Number
BA0006G/H and BA0010G/H 2A0010G/H and 2A0012G/H 4A0001G/H to 4A0009G/H
BA0012G/H 2A0020G/H 4A0011G/H
Other models Not required
Figure 27
CVST31300
CVST31301
Figure 27 Remove the Lower Terminal Cover
34 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 35
7 Procedure B
Option Cover
Mounting Tab
Mounting Slot
Mounting Slot
Mounting Tab
Drive
Ground terminal screw
Option Unit
Drive ground terminal screw
FE
4. Remove the option cover.
Figure 28
Figure 28 Remove the Option Cover
5. Remove the lower right drive ground terminal screw that fastens the drive to the
case, Figure 29. This screw will be used to connect the ground wire from the option unit to the drive. Tool tip: Use a long-shaft Phillips screwdriver. A magnetic tip screwdriver will aid in keeping the screw captive during removal and installation.
Figure 29
Remove the option unit ground terminal (FE) screw.
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 35
Figure 29 Remove Ground Terminal Screws
Page 36
7 Procedure B
6. Select one of the four different length ground wires packaged with the option,
Figure 30. Choose the proper ground wire by test fitting the screw (size M3.5 to M6)
into each of the four drive-side ground ring lugs prior to installation. Ground wire
Figure 30
selection varies by drive model.
To drive ground terminal Screw size: M3.5 to M6
To Option ground screw FE Screw size: M3
Figure 30 Ground Wire Selection
7. Connect the ground wire to the drive using the lower right screw that fastens the
drive to the case. Tool tip: Use a long-shaft Phillips screwdriver. A magnetic tip screwdriver will aid in
Figure 31
keeping the screw captive during removal and installation.
NEMA 4X Drive
Option ground screw FE Screw size: M3
Drive-side ground terminal Screw size: M3.5 to M6
Lower-right screw
Ground wire
Long-shaft magnetic tip screwdriver
Ground Wire
Figure 31 Drive-side Ground Wire Connection
36 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 37
7 Procedure B
Option uni
t
ground
terminal (FE)
Ground terminal screw
Ground wire Option through-hole for ground wire
Option back side
8. Pass the ground wire into the through-hole for ground wire, in the back of the option,
and connect the ground wire at the option ground terminal (FE). Tighten the screw
Figure 32
to 0.5 ~ 0.6 Nm or (4.4 ~ 5.3 in lbs) using an M3 Phillips screwdriver.
Figure 32 Ground Wire Connection Option Unit Side
9. Firmly connect RJ45 8-pin Shielded Twisted Pair Cat5e cable(s) into the modular
connector ports to connect the option to a network, Figure 33. Refer to Network
Topology and Connections on page 41.
NOTICE: Do not connect or disconnect the communication cable while the drive is powered up or while the drive is in operation. Failure to comply may cause a static discharge, which will cause the option card to stop working properly. Cycle power on the drive and option card to attempt to reestablish functionality.
Figure 33
Ground wire to drive ground terminal screw
RJ45 8-pin Shielded Twisted Pair Cat5e cable(s)
Figure 33 Communication Cable Ports
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 37
Page 38
7 Procedure B
10. Attach the option cover by aligning the tabs with the mounting slots. Figure 34.
Figure 34
Cover mounting slot
Ground wire to drive ground screw
Mounting tab
Cover mounting slot
Option cover
Cat5E cables
Mounting tab
Figure 34 Attach the Option Cover
11. Reattach the lower terminal cover, (on certain models), to the drive by aligning the
Figure 35
left and right tabs and snap into place. Figure 35.
Figure 35 Reattach the Lower Terminal Cover
38 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 39
7 Procedure B
CN5 Connector port on drive
CN5 Connector
(underside of option)
Mounting Tab
Drive
CN1 Port
Inside front cover
Insert LED operator cable
12. Attach the option unit to the drive by aligning the two mounting tabs on left and right
side of the option with slots on the drive. Plug-in the CN5 connector on the back of the option unit into the CN5 connector on the drive. Tighten the screw in the front of
Figure 36
the option unit. Figure 36.
Figure 36 Attach Option Unit to Drive
13. Insert the LED operator cable from the front cover into port CN1 on the drive.
Figure 37
Figure 37
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 39
Figure 37 Insert LED Operator Cable to Drive CN1 Port
Page 40
7 Procedure B
14. Reattach the front cover of the drive using four bolts, Figure 38. Refer to Table 9 on
page 40 for tightening torque specifications.
NOTICE: Damage to Equipment. Take proper precautions when wiring the option so that the front covers will easily fit back onto the drive. Make sure no cables are pinched between the front covers and the drive when replacing the cover. Failure to comply may result in damage to circuitry and equipment.
Figure 38
Table 9 Front Cover Installation Bolt Size and Tightening Torque
Voltage Class Model No. CIMR-V
Single Phase 200 V Class BA0001 to BA0012 M5 2.0 to 2.5 (17.7 to 22.1)
Three Phase 200 V Class
Three Phase 400 V Class
Drive
Front cover screw
Front cover
Figure 38 Attach Cover to Drive
Installation Screw Size
2A0001 to 2A0020 M5 2.0 to 2.5 (17.7 to 22.1)
2A0030 to 2A0069 M6 5.4 to 6.0 (47.8 to 53)
4A0001 to 4A0011 M5 2.0 to 2.5 (17.7 to 22.1)
4A0018 to 4A0038 M6 5.4 to 6.0 (47.8 to 53)
Tightening Torque
Nm
(lb-in)
15. Set drive parameters in Table 10 for proper option performance.
16. End of Procedure B.
40 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 41

8 Network Topology and Connections

STOP
(Hz)
(Hz) (A) (V)
V1000
STOP
(Hz)
(Hz) (A) (V)
V1000
STOP
(Hz)
(Hz) (A) (V)
V1000
STOP
(Hz)
(Hz) (A) (V)
V1000
STOP
(Hz)
(Hz) (A) (V)
V1000
STOP
(Hz)
(Hz) (A) (V)
V1000
Traditional Star Network Daisy Chain Network
Cable Topology A
Cable Topology B
8 Network Topology and Connections
The dual RJ45 network ports on the option board act as a switch to allow for flexibility in cabling topology. For example, a traditional star network topology (Cable Topology A), may be employed by using a single port on the option board. Alternatively, a daisy-chained approach may be employed by using both RJ45 ports. The daisy chain approach (Cable Topology B), reduces the requirements of central switch ports. Refer to Figure 39.
Use the second communications cable port to daisy chain a series of drives where applicable (Cable Topology B). Refer to Figure 39.
Figure 39
Figure 39 Topology Options

Communication Cable Wiring

Communication Cable Specifications
Only use cables recommended for PROFINET. Using a cable not specifically recommended may cause the option or drive to malfunction.
The use of CAT5e or equivalent Shielded Twisted Pair (STP) cable is recommended.
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 41
Page 42
8 Network Topology and Connections

Connection Diagram

Figure 40
PROFINET Master
Power
PROFINET Cable
PROFINET Cable
Figure 40 Wiring Diagram
R/L1 S/L2 T/L3
PROFINET
V1000
SI-EP3/V
Option
U/T1
V/T2
W/T3
<1>
M
Motor
Drive Ground Terminal
FE
<1> The ground wire (FE to drive ground) packaged with the option, must be connected during installation.

GSDML Files

For easy network implementation of drives equipped with the SI-EP3/V option, a GSDML file can be obtained from: U.S.: http://www.yaskawa.com Other areas: Contact a Yaskawa representative.
42 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 43

9 Option Drive Parameters

9 Option Drive Parameters
Before starting network communications, verify proper setting of drive parameters in
Ta bl e 1 0 using the drive digital operator.
Table 10 Parameter Settings
No. Name Description Default
Selects the frequency reference input source.
b1-01
<1>
b1-02
<1>
F6-01
F6-02
F6-03
F6-07
<3>
F6-08
<3>
Frequency Reference Selection
Run Command Selection
Operation Selection after Communications Error
External Fault Detection Conditions (EF0)
Stopping Method for External Fault from Communication Option Board
NetRef/ComRef Selection Function
Reset Communication Relat ed Parameters
0: Operator - Digital preset speed d1-01 to d1-17 1: Terminals - Analog input terminal A1 or A2 2: MEMOBUS/Modbus communications 3: Option PCB 4: Pulse Input (Terminal RP)
Selects the run command input source. 0: Digital Operator - RUN and STOP keys 1: Digital input terminals S1 to S7 2: MEMOBUS/Modbus communications 3: Option PCB
Determines drive response when a bUS error is detected during communications with the option. 0: Ramp to Stop 1: Coast to Stop 2: Fast-Stop 3: Alarm Only 4: Alarm (d1-04) <5> 5: Alarm Ramp to Stop
Sets the condition for external fault detection (EF0). 0: Always detected 1: Detected only during operation
Determines drive response for external fault input (EF0) detection during communication. 0: Ramp to Stop 1: Coast to Stop 2: Fast-Stop 3: Alarm Only
0: Multi-step speed reference disabled 1: Multi-step speed reference allowed
Determines if communication-related parameters F6­ and F7- are set back to original default values when the drive is initialized using parameter A1-03. 0: Do not reset F6- and F7- parameters 1: Reset F6- and F7- parameters Note: Setting this parameter does not affect communication-related parameters.
<2>
<5>
<2>
(Set to 3 for
PROFINET)
(Set to 3 for
PROFINET)
1
1
1
0
1
1
0
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 43
Page 44
9 Option Drive Parameters
No. Name Description Default
F6-14 <6> bUS Error Auto Reset
F7-01 to F7-04 IP Address
F7-05 to F7-08 Subnet Mask
F7-09 to F7-12 Gateway Address
F7-13 Address Mode at Startup
F7-14
F7-15
F7-16 <6> Communication Loss Timeout
F7-23 to F7-27
Duplex Mode Selection
Communication Speed Selection
Option Firmware Version VST800250 Dynamic Output Assembly Parameters
Option Firmware Version VST800251 Dynamic Output Assembly Parameters
0: Disabled 1: Enabled
Sets static IP address of the SI-EP3/V option when parameter F7-13=0. Note: Parameter F7-01 sets the most significant octet.
Sets static Subnet Mask of network connection. Note: Parameter F7-05 sets the most significant octet
Sets static Gateway address of network connection. Note: Parameter F7-09 sets the most significant octet.
Selects how the option address is set. 0: Static 2: DCP
Selects duplex mode setting. 0: Half duplex forced 1: Auto-negotiate duplex mode and communication speed 2: Full duplex forced 3: Half (port 1)/Auto (port 2) 4: Half (port 1)/Full (port 2) <5> 5: Auto (port 1)/Half (port 2) <5> 6: Auto (port 1)/Full (port 2) <5> 7: Full (port 1)/Half (port 2) <5> 8: Full (port 1)/Auto (port 2) <5>
Sets the communication speed. 10: 10 Mbps 100: 100 Mbps 101: 10 (port 1)/100 Mbps (port 2) 102: 100 (port 1)/10 Mbps (port 2) <5>
Sets the timeout value for communication loss detection in tenths of a second. A value of 0 disables the connection timeout. Example: An entered value of 100 represents 10.0 seconds.
Configurable outputs 1 to 5. If a value other than 0 is assigned to parameters F7-23 to F7-27 and F7-33 to F7-37 by the drive, that value will take precedent over a value set by the configuration software. If the value in the drive is 0 (default), the value from the configuration software will be used.
Configurable outputs 1 to 5. If a value other than 0 is assigned in the configuration software, those values will be used, otherwise, the values of the drive parameters set in parameters F7-23 to F7-27 and F7-33 to F7-37 will be used.
<5>
<5>
0
192 168 1 20
255 255 255
0
192 168 1 1
2
1 <4>
10
0.0
0
44 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 45
9 Option Drive Parameters
No. Name Description Default
Configurable inputs 1 to 5.
Option Firmware Version VST800250 Dynamic Input Assembly
F7-33 to F7-37
H5-11
<1> To start and stop the drive with the option master device using serial communications, set b1-02 to 3. To control
the drive frequency reference via the master device, set b1-01 to 3.
<2> If F6-01 is set to 3, then the drive will continue to operate when a bUS error or an EF0 fault is detected. Take
proper safety measures, such as installing an emergency stop switch. <3> Drive software versions 1012 and later have F6-07 and F6-08 both set to 1. <4> Drive software versions 1014 and earlier have F7-14 default of 0. <5> Available in drive software versions PRG:1024 and later when combined with option firmware version
VST800251 and later. Not available in drive software versions PRG:508. <6> Available in option firmware version VST800251 and later.
U6-80 to U6-83 Online IP Address
U6-84 to U6-87 Online Subnet Subnet, U6-94 is the most significant octet. 0 to 255
U6-88 to U6-91 Online Gateway Gateway, U6-88 is the most significant octet. 0 to 255
Parameters
Option Firmware Version VST800251 Dynamic Input Assembly Parameters
Communications ENTER Function Selection
No. Name Description Value Range
U6-92 Online Speed Port 1 Link Speed 10, 100
U6-93 Online Duplex Port 1 Duplex Setting 0: Half, 1: Full
U6-94 Online Duplex Port 2 Link Speed 0: Half, 1: Full
U6-95 Online Duplex Port 2 Duplex Setting 0: Half, 1: Full
U6-98 First Fault First Option Board Fault -
U6-99 Current Fault Current Option Board Fault -
If a value other than 0 is assigned to parameters F7-23 to F7-27 and F7-33 to F7-37 by the drive, that value will take precedent over a value set by the configuration software. If the value in the drive is 0 (default), the value from the configuration software will be used.
Configurable outputs 1 to 5. If a value other than 0 is assigned in the configuration software, those values will be used, otherwise, the values of the drive parameters set in parameters F7-23 to F7-27 and F7-33 to F7-37 will be used.
Select the function for the ENTER command that saves parameter data to the drive. 0: Parameter changes are activated when ENTER command is written 1: Parameter changes are activated immediately without use of ENTER command
Table 11 Option Monitors
SI-EP3/V IP Address, U6-80 is the most significant octet.
0
1
0 to 255
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 45
Page 46

10 Web Interface

10 Web Interface
The web server interface to the drive option through port 80 allows management of diagnostic information through a standard web browser. The web page is a Java applet that creates a tabbed web page. Refer to Table 12 for a list of available web page tabs.
Note: PCs must have Java SE 6 Update 14 or later installed to view the web pages. PCs without Java
will display web pages with limited features.
SI-EP3/V firmware version VST800251 provides different web page interface tabs. Web page interface examples are shown for systems using SI-EP3/V option firmware version VST800250 and prior and for systems using version VST800251 and later.
Refer to SI-EP3/V Firmware Update on page 58 to update SI-EP3/V option firmware, if
the web interface pages associated with firmware VST800251 are needed.
Table 12 Web Server Interface Web Page Tabs
Tab Name
HTML Home Page (Main) - - 47
Main 49 49
Drive Status 50 50
Network 51 51
Email Alerts 52 52
Doc Links 53 --
Parameter Access
Configuration
Custom Tab 57 58
<1> The Parameter Access Tab and Configuration Tab are only accessible after entering a valid password.
<1>
<1>
Option Firmware Version Web Page Tab Availability
VST800250 and Prior Page No. VST800251 and Later Page No.
54 54
55 55
46 YASKAWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 47
10 Web Interface

Web Server Interface

Access the web server interface by typing the IP address of the SI-EP3/V option in a web browser address.
Example: "http://192.168.1.20"
The SI-EP3/V IP Address is available using V1000 drive digital operator to access Option Monitors U6-80 to U6-83. Refer to Option Monitors on page 45.
HTML Home Page (option firmware version VST800251 and later)
The main HTML home page provides basic drive and option data and a link to an enhanced web page.
Figure 41
Figure 41 Main Tab View
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 47
Page 48
10 Web Interface
Main Tab (option firmware version VST800250 and prior)
The Main tab shows basic option information such as IP address, MAC address, and firmware version.
Figure 42
Figure 42 Main Tab View
48 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 49
10 Web Interface
Main Tab (option firmware version VST800251 and later)
The Main tab shows basic option information such as IP address, MAC address, and firmware version.
Figure 43
Figure 43 Main Tab View
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 49
Page 50
10 Web Interface
Drive Status Tab
The Drive Status tab shows basic I/O information and drive state information.
Figure 44
Figure 44 Drive Status Tab View
50 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 51
10 Web Interface
Network Tab
The Network tab shows the status of the option network traffic and the status of open I/O connections.
Figure 45
Figure 45 Network Tab View
Table 13 Network Monitor Descriptions
Network Monitor Explanation
Msg Tx OK Cumulative number of messages transmit successfully from SI-EP3/V.
Msg Rx OK Cumulative number of messages received successfully to SI-EP3/V.
Current Connections Current number of open connections.
Control Connection Delta Time
Msg Tx Dropped
Msg Rx Dropped
Collisions
Msg Tx Errors
Msg Rx Errors
Tx Retry
Note: Cumulative counters are reset when the power supply is cycled.
The time between the last two writes to the Control register, MEMOBUS/Modbus address 0001H.
Cumulative number of messages dropped due to output network buffer being full and unable to hold the new message.
Cumulative number of messages dropped due to input network buffer being full and unable to hold the new message.
Cumulative number of collisions (half duplex only) reported by the MAC/PHY (Media Access Control/Physical Connection).
Cumulative number of transmit underruns and transmit stops reported by the MAC/PHY.
Cumulative number of receive overruns, receive stops, and receive error frames reported by the MAC/PHY.
Cumulative number of transmits in which the 1st attempt was delayed due to busy medium reported by the MAC/PHY.
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 51
Page 52
10 Web Interface
Email Alerts Tab
The Email Alerts tab allows the user to configure four Email Fault/Alarm conditions. When the condition is true, one email will be sent to the provided email address. Another email will not be sent until the condition becomes false and then true again. A 30-second timer prevents emails from being sent when conditions reoccur immediately after being removed. The timer helps limit the amount of emails sent regarding the same intermittent condition and helps to reduce network traffic by reducing emails about reoccurring errors.
Figure 46
Figure 46 Email Alerts Tab View
52 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 53
10 Web Interface
SI-EP3
Procedure: Conditional Email Set-up
1. Define the condition that will trigger the email by selecting a monitor parameter, a
comparator, and a value. Set up comparator values for the range of values to check in the chosen condition. If choosing only one condition and no OR or AND are needed, set the “OR/AND” drop-down selection to “NotUsed”.
2. Enter the email address where the alert will be sent.
3. Enter the message that will appear in the email contents.
4. Enter the email subject.
5. Click the “Email Active” check box to enable the alert.
Clicking “Save to device” will save the entered information into the option memory.
Clicking “Cancel and reload” will cancel any pending edits and display the most recently saved settings from the option board.
Doc Links Tab (option firmware version VST800250 and prior)
The Doc links tab contains links to the option documentation on the Yaskawa website.
Figure 47
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 53
Figure 47 Doc Links Tab View
Page 54
10 Web Interface
Parameter Access Tab
The Parameter Access tab allows the user to read and write parameters from the drive. Write access is restricted until a valid password is entered.
Figure 48
Figure 48 Parameter Access Tab View
The Modbus address for the drive parameter being accessed must be entered in hexadecimal. The number must begin with “0x” to signify hexadecimal.
Clicking “Read” will load and display the current value of the given Modbus Address. Clicking “Set” will save the given value to the given Modbus address.
After a “Read” or “Set” command is given, Status will display “Waiting” while the action is being carried out, then “Complete” is displayed when finished.
54 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 55
10 Web Interface
sample@sample.
Configuration Tab
The Configuration tab sets web page behavior parameters. Access is restricted unless a valid password is entered.
Figure 49
Figure 49 Configuration Tab View
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 55
Page 56
10 Web Interface
Security Login
Enter a valid password and click “Log in”. The button text will change to “Log out” and the status will change to “Logged in”.
Note: The default security password is “yaskawa”.
This password can be changed in the “Change Password” section of the tab. Entering a valid password allows access to the settings in the Configuration tab, Email Alerts tab, and the Parameter Access tab.
Change Password
To change the password, enter the new password in the “New Password:” and “Confirm Password:” text boxes then click “Change password”. The Status display will change to “Idle” then “Changing Password” then “Password Changed”. If the passwords in the two text boxes do not match, the Status will display “Passwords don’t match”.
Option Card
The values displayed in the various tabs are refreshed at the rate defined in the “Applet Refresh Rate (ms)” text box. Enter values in the range of 1000 ms to 65.535 seconds.
Parameter Security can be enabled or disabled by clicking one of the radio buttons. When “Disabled” is selected, no password is necessary and all functions in the web pages will be available. When “Enabled” is selected, a valid password must be entered to edit email settings and to write parameters.
Email Settings
The “Email Server IP” text box must contain the IP address of the email server. The subnet address is configured in drive parameters F7-05 through F7-08. The configured email alerts will use the server at this address when sending emails.
Enter the email server port in the “Email Port” text box.
The value in the “From’ Email Address” text box identifies the origin of the email alerts to the recipient.
Click “Submit Email Parameters” to save the email settings to the option.
Click “Save Configuration Parameters to Flash” to save the entered values from this tab into non-volatile memory. These values will then be remembered after cycling power.
General Settings
Click “Save Options Card Parameters” to save the Applet Refresh Rate and the Parameter Security settings to the option.
56 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 57
10 Web Interface
Custom Tab (option firmware version VST800250 and prior)
The Custom tab displays a selection of quick setting parameters.
Figure 50
Figure 50 Custom Tab View
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 57
Page 58
10 Web Interface
Custom Tab (option firmware version VST800251 and later)
The Custom tab displays a selection of quick setting parameters.
Figure 51
Figure 51 Custom Tab View

SI-EP3/V Firmware Update

The Profinet SI-EP3/V firmware can be updated to obtain the most recent version.
1. Navigate to this URL: https://www.yaskawa.com/pycprd/partner/fmw-network­communications
2. Enter your Partner Login credentials.
3. Download the Communication Option Flash Write Procedure manual no.TOEPYAICOM14 for instructions on how to update the SI-EP3/V firmware.
4. Download the *.YFlash file for your specific communication option to your PC.
58 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 59

11 Troubleshooting

11 Troubleshooting

Drive-Side Error Codes

Drive-side error codes appear on the drive digital operator. Causes of the errors and corrective actions are listed in Table 14. For additional error codes that may appear on the drive digital operator, refer to the drive Technical Manual available at http://www.yaskawa.com.
Faults
Both bUS (Option Communication Error) and EF0 (External Fault Input from the option) can appear as an alarm or as a fault. When a fault occurs, the digital operator ALM LED remains lit. When an alarm occurs, the ALM LED flashes.
If communication stops while the drive is running, use the following questions as a guide to help remedy the fault:
• Is the option properly installed?
• Is the communication line properly connected to the option? Is it loose?
• Is the controller program working? Has the controller/PLC CPU stopped?
• Did a momentary power loss interrupt communications?
Table 14 Fault Display and Possible Solutions
LED Operator Display Fault Name
Option Communication Error.
bUS
Cause Possible Solution
Master controller (PLC) has stopped communicating.
Communication cable is not connected properly.
A data error occurred due to noise.
Option is damaged.
After establishing initial communication, the connection was lost. Only detected when the run command or frequency reference is assigned to the option (b1-01 = 3 or b1-02 = 3).
Check that power is supplied to the PLC Check that PLC is not in program mode
Check for faulty wiring Correct any wiring problems
Check the various options available to minimize the effects of noise Counteract noise in the control circuit, main circuit, and ground wiring If a magnetic contactor is identified as a source of noise, install a surge absorber to the contactor coil Make sure the cable used meets the option requirements Make sure the option ground wire is connected between option FE terminal and the drive ground terminal connected to earth ground
If there are no problems with the wiring and the error continues to occur, replace the option.
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 59
Page 60
11 Troubleshooting
LED Operator Display Fault Name
EF0
Cause Corrective Action
An external fault is being sent from the upper controller (PLC).
Problem with the PLC program. Check the program used by the PLC and make the appropriate corrections.
LED Operator Display Fault Name
oFA00
Cause Possible Solution
Non-compatible option connected to the drive.
LED Operator Display Fault Name
oFA01
Cause Possible Solution
Problem with the connectors between the drive and option.
LED Operator Display Fault Name
oFA03
Cause Possible Solution
Option hardware fault. Replace the option.
External Fault Input from the option.
The alarm function for an external device is triggered.
Remove the cause of the external fault Reset the external fault input from the PLC device
Option Fault.
Option is not properly connected.
Connect an option that is compatible with the drive.
Option Fault.
Option is not properly connected.
Turn the power off and check the connectors between the drive and option.
Option Fault.
Option self-diagnostics error.
LED Operator Display Fault Name
oFA04
Cause Possible Solution
Option hardware fault. Replace the option.
60 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Option Fault.
Option Flash write mode.
Page 61
LED Operator Display Fault Name
to
oFA30 to oFA43
Cause Possible Solution
Option hardware fault. Replace the option.
Option Fault (Port A).
Communication ID error.
Minor Faults and Alarms
LED Operator Display Minor Fault Name
CALL
Cause Possible Solution
Communication wiring is faulty, there is a short circuit, or improper connection.
Programming error on the master side.
Communication circuitry is damaged.
Serial Communication Transmission Error.
Communication is not established.
Check for wiring errors Correct the wiring Remove ground shorts and reconnect loose wires
Check communications at start-up and correct programming errors.
Perform a self-diagnostics check Replace the drive if the fault continues to occur
11 Troubleshooting
Minor Fault
(H2- = 10)
YES
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 61
Page 62
11 Troubleshooting







!"##$%%&*
+;=  
+;=

%

?!%

?!%

?!%
bUS Error Auto-Reset
bUS Error Auto-Reset Function Description
bUS Error Auto-Reset when configured, allows the drive to automatically recover from a bUS error as a result of a communication loss with the host.
A bUS Error will automatically reset under the following conditions.
• Network communication between the host and the drive is restored. (bUS error removed)
• bUS Error Auto-Reset is enabled as described in this section.
Enabling bUS Error Auto-Reset
Parameter F6-14 14 becomes available when the option is installed on the drive.
1. Set parameter F6-14 = 1:Enabled
2. Set parameter F6-01 = 0:Ramp to Stop, 1:Coast to Stop, 2:Fast-Stop
3. Set parameter F7-16 = 0.1 to 10.0 seconds (optional)
Enabling bUS Error Auto-Restart (After a Time Delay)
Parameter F7-16 Communication Loss Timeout will delay the occurance of a bUS error condition by the amount of time set in this parameter. F7-16 is set in tenths of seconds. The status LEDs on the option will indicate the bUS error condition immediately upon detection and during the F7-16 delay time. Refer to Figure 52.
• Set parameter F7-16 = 0.1 to 10.0 seconds (0.0 setting disables F7-16) to enable timeout delay.
Figure 52
<1>
bUS Error Auto Reset enables the bUS Error Auto-Reset function. F6-
Figure 52 bUS Error Delay Timing Example
<1>
Available in SI-EP3/V firmware version VST800251 and later when used with V1000 drive software versions
PRG:1024 and later.
62 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 63
11 Troubleshooting
Related Parameters
Table 15 Parameters related to bUS Error Auto-Reset Functionality
No.
(Addr. Hex)
F6-01
(03A2)
F6-14 <6>
(03BB)
F7-16 <6>
(03F4)
<2> If F6-01 is set to 3, then the drive will continue to operate when a bUS error is detected. Use caution and proper
safety measures, when installing an emergency stop switch.
<5> Available in drive software versions PRG:1024 and later when combined with option firmware version
VST800251 and later. Not available in drive software versions PRG:508.
<6> Available in option firmware version VST800251 and later.
Option Fault Monitors U6-98 and U6-99
Operation Selection after Communications Error
bUS Error Auto Reset
Communication Loss Timeout
The option can declare error/warning conditions via drive monitor parameters on the drive digital operator as shown in Table 16.
Fault Condition Fault Declared
No Fault n/a 0 No faults.
Force Fault EF0 3
Network Link Down
Network Failure BUS ERROR 1301 Connection with PLC Timeout.
Default MAC Address
No IP Address None 1304 No IP Address has been programmed into the option.
No Station Name None 1305 No Station Name has been programmed into the option.
Name Description Default
Determines drive response when a bUS error is detected during communications with the option. 0: Ramp to Stop 1: Coast to Stop 2: Fast-Stop 3: Alarm Only 4: Alarm (d1-04) <5> 5: Alarm Ramp to Stop
0: Disabled 1: Enabled
Sets the timeout value for communication loss detection in tenths of a second. A value of 0 disables the connection timeout. Example: An entered value of 100 represents 10.0 seconds. Note: A change to this parameter setting is not effective until main power to the drive is cycled.
<2>
<5>
Table 16 Option Fault Monitor Descriptions
Status Value
(U6-98/U6-99)
Network sent a message to force this node to the fault state.
BUS ERROR 1300 No network link to option board.
None 1303
Factory default MAC Address programmed into the option. Return for reprogramming.
Description
1
0
0.0
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 63
Page 64
11 Troubleshooting
Fault Condition Fault Declared
Config Error None 1306 Configuration error on power-up.
Init. Failure None 1307 Initialize error on power-up.
Permanent Communication Loss
BUS ERROR 1308
Status Value
(U6-98/U6-99)
Description
Fatal error in MAC/PHY hardware, requires power cycle to recover.
Two drive monitor parameters, U6-98 and U6-99 assist in network troubleshooting:
• U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared upon drive power-up.
• U6-99 displays the present option SI-EP3/V status. U6-99 is cleared upon a network­issued fault reset and upon power-up.
If another fault occurs while the original fault is still active, parameter U6-98 retains the original fault value and U6-99 stores the new fault status value.
64 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 65

12 Specifications

12 Specifications
Table 17 Option Specifications
Item Specification
Model SI-EP3/V option
Option Conformance Passed PROFINET Conformance Class A
Connector Type Dual RJ45 8-pin Shielded Twisted Pair Cat 5e cable
Physical Layer Type Isolated Physical Layer
IP Address Setting Programmable from drive keypad or network
Communication Speed
Number of Connections 1 PLC connection, 1 supervisor connection, 2 web page connections
Duplex Mode Half-forced, Auto-negotiate, Full-forced
Address Startup Mode Static, DCP
Ambient Temperature -10 C to +50 C
Humidity Up to 95% RH (no condensation)
Storage Temperature -20 C to +60 C (allowed for short-term transport of the product)
Area of Use Indoor (free of corrosive gas, airborne particles, etc.)
Altitude Up to 1000 m
PROFINET Functions
IEC Overvoltage Category Intended for use in “Overvoltage Category II” as specified in IEC 60664-1
Programmable from drive keypad or network: 10/100 Mbps, auto-negotiate.
PROFINET IO Configurable I/O in cyclic messages Drive diagnostic alarms I&M0
YAS KA WA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual 65
Page 66
12 Specifications
Published in U.S.A. January 2011 11-01
Date of publication
Date of original publication
MANUAL NO. SIEP YEACOM 06

Revision History

The revision dates and the numbers of the revised manuals appear on the bottom of the back cover.
Date of Publication
September 2014 1 Various
January 2011 First edition
Revision
Number
Section Revised Content
Updated contents to support SI-EP3 firmware VST800251 and NEMA 4X installation procedure. Bus tolerance parameters added. New GSDML file.
66 YA SK AWA TOEP YEACOM 06A V1000 Option PROFINET SI-EP3/V Installation Manual
Page 67
Page 68
YASKAWA AC Drive-V1000 Option
PROFINET
Installation Manual
YASKAWA AMERICA, INC.
2121 Norman Drive South, Waukegan, IL 60085, U.S.A. Phone: 1-847-887-7000 or (800)YASKAWA (800-927-5292) Fax: 1-847-887-7310 Internet: http://www.yaskawa.com
YASKAWA ELETRICO DO BRASIL LTDA.
Avenida Fagundes Filho, 620 Sao Paulo-SP CEP 04304-000, Brazil Phone 55-11-3585-1100 Fax 55-11-5581-8795 Internet: http://www.yaskawa.com.br
YASKAWA AMERICA, INC.
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations. Therefore, be sure to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.
© 2010 YASKAWA AMERICA INC. All rights reserved.
MANUAL NO. TOEP YEACOM 06A