To properly use the product, read this manual thoroughly and retain
for easy reference, inspection, and maintenance. Ensure the end user
receives this manual.
No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means,
mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of Yaskawa. No patent
liability is assumed with respect to the use of the information contained herein. Moreover, because Yaskawa is constantly
striving to improve its high-quality products, the information contained in this manual is subject to change without notice.
Every precaution has been taken in the preparation of this manual. Yaskawa assumes no responsibility for errors or omissions.
Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
Table of Contents
1PREFACE AND SAFETY.........................................................................................4
Yaskawa manufactures products used as components in a wide variety of industrial systems and equipment. The selection and
application of Yaskawa products remain the responsibility of the equipment manufacturer or end user. Yaskawa accepts no
responsibility for the way its products are incorporated into the final system design. Under no circumstances should any
Yaskawa product be incorporated into any product or design as the exclusive or sole safety control. Without exception, all
controls should be designed to detect faults dynamically and fail safely under all circumstances. All systems or equipment
designed to incorporate a product manufactured by Yaskawa must be supplied to the end user with appropriate warnings and
instructions as to the safe use and operation of that part. Any warnings provided by Yaskawa must be promptly provided to
the end user. Yaskawa offers an express warranty only as to the quality of its products in conforming to standards and
specifications published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS OFFERED.
Yaskawa assumes no liability for any personal injury, property damage, losses, or claims arising from misapplication of its
products.
u
Applicable Documentation
The following manuals are available for the SI-EN3D option:
The Technical Manual contains detailed information about the option. In the U.S., access http://www.yaskawa.com
to obtain the Technical Manual. Customers in other areas should contact a Yaskawa representative.
1000-Series AC Drive Safety Precautions
Read this manual first. This manual contains essential safety information and simplified information for the drive.
This document also provides basic instructions on mechanical installation, a connection diagram, main circuit and
control circuit connections, switch and jumper configuration, basic troubleshooting, standards compliance and
fusing, drive specifications, and an abbreviated parameter list.
1000-Series AC Drive Quick Start Guide
This guide contains basic information required to install and wire the drive. It also gives an overview of fault
diagnostics, maintenance, and parameter settings. The purpose of this guide is to prepare the drive for a trial run
with an application and for basic operation. This manual is available for download on our documentation website,
www.yaskawa.com.
1000-Series AC Drive Technical Manual
This manual provides detailed information on parameter settings, drive functions, and MEMOBUS/Modbus
specifications. Use this manual to expand drive functionality and to take advantage of higher performance features.
This manual is available for download on our documentation website, www.yaskawa.com.
u
Terms
Note: Indicates supplemental information that is not related to safety messages.
Drive: Yaskawa 1000-Series AC Drive
Option: Yaskawa AC Drive 1000-Series SI-EN3D Dual-Port EtherNet/IP Option
u
Registered Trademarks
• EtherNet/IP is a trademark of the ODVA.
• All trademarks are the property of their respective owners.
u
Supplemental Safety Information
Read and understand this manual before installing, operating, or servicing this option. The option must be installed according
to this manual and local codes.
The following conventions are used to indicate safety messages in this manual. Failure to heed these messages could result in
serious or possibly even fatal injury or damage to the products or to related equipment and systems.
DANGER
Indicates a hazardous situation, which, if not avoided, will result in death or serious injury.
Indicates a hazardous situation, which, if not avoided, could result in death or serious injury.
WARNING! may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
CAUTION
Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury.
CAUTION! may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
NOTICE
Indicates a property damage message.
NOTICE: may also be indicated by a bold key word embedded in the text followed by an italicized safety message.
General Safety
n
General Precautions
• The diagrams in this manual may be indicated without covers or safety shields to show details. Replace the covers or shields before
operating the drive and run the drive according to the instructions described in this manual.
• Any illustrations, photographs, or examples used in this manual are provided as examples only and may not apply to all products to
which this manual is applicable.
• The products and specifications described in this manual or the content and presentation of the manual may be changed without notice
to improve the product and/or the manual.
• When ordering a new copy of the manual due to damage or loss, contact your Yaskawa representative or the nearest Yaskawa sales
office and provide the manual number shown on the front cover.
• If nameplate becomes worn or damaged, order a replacement from your Yaskawa representative or the nearest Yaskawa sales office.
DANGER
Heed the safety messages in this manual.
Failure to comply will result in death or serious injury.
The operating company is responsible for any injuries or equipment damage resulting from failure to heed the warnings in
this manual.
Electrical Shock Hazard
Do not connect or disconnect wiring while the power is on.
Failure to comply will result in death or serious injury.
Failure to comply will result in death or serious injury. Before servicing, disconnect all power to the equipment. The internal
capacitor remains charged even after the power supply is turned off. The charge indicator LED will extinguish when the DC
bus voltage is below 50 Vdc. To prevent electric shock, wait for at least the time specified on the warning label once all
indicators are OFF, and then measure the DC bus voltage level to confirm it has reached a safe level.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Do not perform a withstand voltage test on any part of the drive.
Failure to comply could result in damage to the sensitive devices within the drive.
Do not operate damaged equipment.
Failure to comply could result in further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.
Do not expose the drive to halogen group disinfectants.
Failure to comply may cause damage to the electrical components in the drive.
Do not pack the drive in wooden materials that have been fumigated or sterilized.
Do not sterilize the entire package after the product is packed.
The option provides a communications connection between the drive and an ODVA EtherNet/IP network. The option connects
the drive to an EtherNet/IP network and facilitates the exchange of data.
This manual explains the handling, installation and specifications of this product.
EtherNet/IP is a communications link to connect industrial devices (such as smart motor controllers, operator interfaces, and
variable frequency drives) as well as control devices (such as programmable controllers and computers) to a network. EtherNet/
IP is a simple, networking solution that reduces the cost and time to wire and install factory automation devices, while providing
interchangeability of like components from multiple vendors.
EtherNet/IP is an open device network standard.
By installing the option to a drive, it is possible to do the following from an EtherNet/IP master device:
• Operate the drive
• Monitor drive status
• Change drive parameter settings.
u
Applicable Models
The option can be used with the drive models in Table 1.
Table 1 Applicable Models
Drive SeriesDrive Model Number
CIMR-Ao2Aoooo
A1000
<1> See “PRG” on the drive nameplate for the software version number.
CIMR-Ao4A0002o to 4A0675o
CIMR-Ao4A0930 and 4A1200301o
CIMR-Ao5Aoooo504o; 1017 and later
• A Phillips screwdriver (M3 metric or #1, #2 U.S. standard) is required to install the option and remove drive front covers.
Screw sizes vary by drive capacity. Select a screwdriver appropriate for the drive capacity.
• Diagonal cutting pliers. (required for some drive models)
• A small file or medium grit sandpaper. (required for some drive models)
Note:Tools required to prepare the option cables for wiring are not listed in this manual.
H – EtherNet/IP cable connector
I – Option connector
J – Installation hole
K –
LED (MS)
L –
LED (NS)
<2>
<2>
M – EtherNet/IP PCB
F – Port 1
G –
Port 1 LED (LINK/ACT)
<2>
Figure 1 Option Components
<1> The ground wire is packaged loose in the option shipping package. Connect this ground wire during installation.
<2> Refer to Option LED Display on page 10 for details on the LEDs.
u
Communication Connector CN1
The communication connector on the option is a modular RJ45 female connector designated CN1.
CN1 is the connection point for a customer-supplied male Ethernet network communication cable.
• Link status and network activity - LINK/ACT (NS) red/green
The operational states of the option LEDs after completion of the power-up diagnostic LED sequence are described in Table
3. Wait at least 2 seconds for the power-up diagnostic process to complete before verifying LED states.
Table 3 Option LED States
Name
MS
NS
<1>
10/100
LINK/ACT
<1> Remove the cover to check the status of the LED. Be careful not to touch the main circuit terminals or the control board in the drive.
<1>
ColorStatus
GreenONNormal operation
GreenFlashingStandby/Initializing
RedFlashingNon-fatal error occurred
RedONFatal error occurredThe option has detected an unrecoverable major fault.
Green/RedFlashingOption self-testThe option is in self-test mode.
GreenON
GreenFlashingNot connectedThe option is online without an established connection.
RedFlashingMinor faultA minor recoverable fault has occurred.
RedONMajor faultThe option detected a duplicate IP address.
Green/RedFlashingOption self-testThe option is in self-test mode.
GreenOFF10 Mbps is established
GreenON100 Mbps is established
GreenOFFLINK is not established
GreenONLINK is established
GreenFlashing
Display
–OFFPower supply OFFPower is not being supplied to the drive.
–OFFPower supply OFF–
Operating StatusRemarks
The option is operating normally and initialization is
complete.
The option is in process of configuring or waiting for
configuration information.
The option has detected a recoverable minor fault such
as incomplete configuration.
Online communications
established
LINK is established and there is
network activity.
The option is online and has established connections.
–
Power-Up Diagnostics
n
An LED test is performed each time the drive is powered up. The initial boot sequence may take several seconds. After the
LEDs have completed the diagnostic LED sequence, the option is successfully initialized. The LEDs then assume operational
conditions as shown in Table 3.
Table 4 Power-Up Diagnostic LED Sequence
SequenceModule Status (MS)Network Status (NS)Time (ms)
Do not connect or disconnect wiring while the power is on.
Failure to comply will result in death or serious injury.
Disconnect all power to the drive and wait at least the amount of time specified on the drive front cover safety label. After
all indicators are off, measure the DC bus voltage to confirm safe level, and check for unsafe voltages before servicing. The
internal capacitor remains charged after the power supply is turned off.
WARNING
Electrical Shock Hazard
Do not remove the front covers of the drive while the power is on.
Failure to comply could result in death or serious injury.
The diagrams in this section may include options and drives without covers or safety shields to show details. Be sure to
reinstall covers or shields before operating any devices. The option should be used according to the instructions described
in this manual.
Do not allow unqualified personnel to use equipment.
Failure to comply could result in death or serious injury.
Maintenance, inspection, and replacement of parts must be performed only by authorized personnel familiar with installation,
adjustment, and maintenance of this product.
Do not touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
Do not use damaged wires, stress the wiring, or damage the wire insulation.
Failure to comply could result in death or serious injury.
Do not use damaged wires, place excessive stress on wiring, or damage the wire insulation.
Failure to comply could result in death or serious injury.
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never shut the power off while the drive is outputting voltage.
Failure to comply may cause the application to operate incorrectly or damage the drive.
Do not operate damaged equipment.
Failure to comply may cause further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance.
Use shielded twisted-pair wires and ground the shield to the ground terminal of the drive.
Failure to comply may prevent proper operation and possibly damage equipment.
Check wiring to ensure that all connections are correct after installing the option and connecting any other devices.
Failure to comply could result in damage to the option.
u
Prior to Installing the Option
Prior to installing the option, wire the drive, make necessary connections to the drive terminals, and verify that the drive
functions normally without the option installed. Refer to the drive Quick Start Guide for information on wiring and connecting
the drive.
Figure 2 shows an exploded view of the drive with the option and related components for reference.
A – Drive front cover
B – Digital operator
C – LED label
D – Drive terminal cover
E – Removable tabs for wire routing
F – Included screws
G – Ground wire
Figure 2 Drive Components with Option
H – Drive grounding terminal (FE)
I – Connector CN5-C
J – Connector CN5-B
K – Connector CN5-A
L – Insertion point for CN5 connector
M – Option
Remove the front covers of the drive before installing the option. Refer to the drive Quick Start Guide for directions on
removing the front covers. Cover removal varies depending on drive size. This option can only be inserted into the CN5-A
connector located on the drive control board.
DANGER! DANGER! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply could result in
death or serious injury. Before installing the option, disconnect all power to the drive and wait at least the amount of time specified on the
drive front cover safety label. After all indicators are off, measure the DC bus voltage to confirm safe level, and check for unsafe voltages
before servicing. The internal capacitor remains charged after the power supply is turned off.
Shut off power to the drive, wait the appropriate amount of time for voltage to dissipate, then remove the digital operator
1.
(B) and front covers (A, D). Front cover removal varies by model.
NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling the option, drive, and
circuit boards. Failure to comply may result in ESD damage to circuitry.
Figure 3 Remove the Front Covers and Digital Operator
With the front covers and digital operator removed, apply the LED label (C) in the appropriate position on the drive
2.
top front cover (A).
Figure 4 Apply the LED Label
Make sure the screws on the left and right sides of the option terminal block (J) are tightened with a tightening torque
3.
of 0.5 to 0.6 Nm (4.4 to 5.3 in lbs), then insert the option (B) into the CN5-A connector (L) located on the drive and
fasten it using one of the included screws (H).
Connect the ground wire (I) to the ground terminal (K) using one of the remaining provided screws (H). Connect the
4.
other end of the ground wire (I) to the remaining ground terminal and installation hole on the option (B) using the last
remaining provided screw (H) and tighten both screws to 0.5 to 0.6 N•m (4.4 to 5.3 in lbs).
Figure 5 Insert the Option
Figure 6 Connect the Ground Wire
Note:
There are two screw holes on the drive for use as ground terminals. When connecting three options, two ground wires will need
to share the same drive ground terminal.
Route the option wiring.
5.
Depending on the drive model, some drives may require routing the wiring through the side of the front cover to the
outside to provide adequate space for the wiring. Refer to the Peripheral Devices & Options section of the drive Quick
Start Guide or Technical Manual for more information on wire routing of specific models.
Route the wiring through the side of the front cover to the outside. In these cases, using diagonal cutting pliers, cut
out the perforated openings on the left side of the drive front cover as shown in Figure 7-A. Use a file or sandpaper
to make the sharp edges along the cutout smoother to prevent any damage to the wires. Route the wiring inside the
enclosure as shown in Figure 7-B for drives that do not require routing through the front cover.
Note:Separate communication cables from main circuit wiring and other electrical lines.
<1> The drive will not meet NEMA Type 1 requirements if wiring is exposed outside the enclosure.
Connect the Ethernet communication cable to the option modular connector (CN1) port 1.
6.
To connect the option to a network, firmly connect RJ45 8-pin shielded twisted pair Cat5e cable(s) into the modular
connector ports (see Figure 7).
IGMP Snooping
Switches implementing IGMP Snooping are strongly recommended. When IGMP Snooping is used, devices will only
receive the multicast packets in which they are interested.
Communication Cable Specifications
Only use cable recommended for EtherNet/Industrial Protocol (EtherNet/IP™). Using a cable not specifically
recommended may cause the option or drive to malfunction. Refer to the ODVA website for more information on
network cabling (http://www.odva.org).
The dual RJ45 network ports on the option board act as a switch to allow for flexibility in cabling topology. For example,
a traditional star network topology may be employed by using a single port on the option board. Alternatively, a daisychained approach may be employed by using both RJ45 ports. The daisy-chained approach reduces the requirements
of central switch ports. A ring topology is also possible.
The following parameters are used to set up the drive for operation with the option. Parameter setting instructions can be found
in the drive manual.
Confirm proper setting of the parameters in Table 5 before starting network communications. After changing parameter
settings, cycle power to the drive for the new settings to take effect.
Table 5 Related Parameters
No.
(Addr.
Hex)
b1-01
(0180)
<1>
b1-02
(0181)
<1>
F6-01
(03A2)
F6-02
(03A3)
F6-03
(03A4)
F6-06
(03A7)
<3>
F6-07
(03A8)
F6-08
(036A)
<5>
F6-14
(03BB)
F7-01
(03E5)
<6>
F7-02
(03E6)
<6>
F7-03
(03E7)
<6>
F7-04
(03E8)
<6>
F7-05
(03E9)
F7-06
(03EA)
F7-07
(03EB)
F7-08
(03EC)
Frequency Reference Selection
1
Run Command
Selection 1
Communications Error
Operation Selection
External Fault from Comm.
Option Detection Selection
External Fault from Comm.
Option Operation Selection
Torque Reference/Torque
Limit Selection from Comm.
Option
Multi-Step Speed Enable/
Disable Selection when
NefRef/ComRef is Selected
Reset Communication
Parameters
bUS Error Auto Reset
IP Address 1Sets the most significant octet of network static IP address.
IP Address 2Sets the second most significant octet of network static IP address.
IP Address 3Sets the third most significant octet of network static IP address.
IP Address 4Sets the fourth most significant octet of network static IP address.
Subnet Mask 1Sets the most significant octet of network static Subnet Mask.
Subnet Mask 2Sets the second most significant octet of network static Subnet Mask.
Subnet Mask 3Sets the third most significant octet of network static Subnet Mask.
Subnet Mask 4Sets the fourth most significant octet of network static Subnet Mask.
NameDescriptionValues
0: Digital operator
1: Analog input terminals
2: MEMOBUS/Modbus communications
3: Option PCB
Default: 1
Range: 0 to 4
4: Pulse input (terminal RP)
0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
Default: 1
Range: 0 to 3
3: Option PCB
0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to stop
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only
<2>
1: Detection during run only
Default: 1
Range: 0 to 3
Default: 0
Range: 0, 1
0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to stop
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only
0: Disabled. Torque reference/limit from option board disabled.
1: Enabled. Torque reference/limit from option board enabled.
<2>
<4>
0: Multi-step reference disabled (same as F7)
1: Multi-step reference enabled (same as V7)
Default: 1
Range: 0 to 3
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
0: Communication-related parameters (F6-oo/F7-oo) are not reset when
the drive is initialized using A1-03.
1: Reset all communication-related parameters
Default: 0
Range: 0, 1
(F6-oo/F7-oo) when the drive is initialized using A1-03.
Gateway Address 1Sets the most significant octet of network Gateway address.
Gateway Address 2Sets the second most significant octet of network Gateway address.
Gateway Address 3Sets the third most significant octet of network Gateway address.
Gateway Address 4Sets the fourth most significant octet of network Gateway address.
Address Mode at Startup
Duplex Mode Selection
Communication Speed
Selection
Communication Loss Timeout
EtherNet/IP Speed Scaling
Factor
EtherNet/IP Current Scaling
Factor
EtherNet/IP Torque Scaling
Factor
EtherNet/IP Power Scaling
Factor
EtherNet/IP Voltage Scaling
Factor
EtherNet/IP Time Scaling
F7-23 to
F7-32
(03FB to
Dynamic Output Assembly
Parameters
0374)
F7-33 to
F7-42
(0375 to
Dynamic Input Assembly
Parameters
037E)
<1> To start and stop the drive with the EtherNet/IP master device using serial communications, set b1-02 to 3 or set the “Net Control” bit in the
assemblies or Control Supervisor Object. To control the drive frequency reference of the drive via the master device, set b1-01 to 3 or set the Net
Reference bit in the assemblies or AC/DC Object.
<2> When set to 3, the drive will continue to operate when a fault is detected. Take safety measures, such as installing an emergency stop switch.
5: Auto (port 1)/Half (port 2)
6: Auto (port 1)/Full (port 2)
7: Full (port 1)/Half (port 2)
8: Full (port 1)/Auto (port 2)
Sets the communication speed
10: 10 Mbps
100: 100 Mbps
101: 10 (Port 1)/100 Mbps (port 2)
Default: 10
Range: 10; 100 to 102
102: 100 (Port 1)/10 Mbps (port 2)
Sets the timeout value for communication loss detection in tenths of a second.
A value of 0 disables the connection timeout.
Example: An entered value of 100 represents 10.0 seconds.
Sets the scaling factor for the speed monitor in EtherNet/IP Class ID 2AH
Object.
Sets the scaling factor for the output current monitor in EtherNet/IP Class ID
2AH Object.
Sets the scaling factor for the torque monitor in EtherNet/IP Class ID 2AH
Object.
Sets the scaling factor for the power monitor in EtherNet/IP Class ID 2AH
Object.
Sets the scaling factor for the voltage monitor in EtherNet/IP Class ID 2AH
Object.
Sets the scaling factor for the time monitor in EtherNet/IP Class ID 2AH
Object.
Default: 0.0
Min.: 0.0
Max.: 30.0
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Default: 0
Min.: -15
Max.: 15
Parameters used in Output Assembly 116. Each parameter contains a
MEMOBUS/Modbus address. The value received for Output Assembly 116
will be written to this corresponding MEMOBUS/Modbus address. A
MEMOBUS/Modbus address value of 0 means that the value received for
Default: 0
Output Assembly 116 will not be written to any MEMOBUS/Modbus
register.
Parameters used in Input Assembly 166. Each parameter contains a
MEMOBUS/Modbus address. The value sent for Input Assembly 166 will
be read from this corresponding MEMOBUS/Modbus address. A
MEMOBUS/Modbus address value of 0 means that the value sent for Input
Default: 0
Assembly 166 is not defined by the user, therefore the option default register
value will be returned.
PLC and received by this node. This section details “Output Assemblies” that are “Consumed” by this drive.
0
20
1
NameDescription
Run Fwd
Fault Reset
Speed Reference
Forward Run Command
0: Stop
1: Forward Run
Fault Reset
(0 to 1 transition: Fault Reset)
Speed Command
Sets drive speed reference.
Speed reference data: Frequency reference/2SS (SS: Speed scale)
Setting range: 0 to 0xFFFF
Example: setting a reference of 4096 with a speed scale of 2:
Speed reference data = 4096/22 = 1024 = 0x0400 Hex or 10.24 Hz
Unit depends on o1-03.
Run command from Network
0: Depends on b1-02
1: Enables the run command from network
Speed reference from Network
0: Depends on b1-01
1: Enables the speed reference from network
Speed Command
Sets drive speed reference.
Speed reference data: Frequency reference/2SS (SS: Speed scale)
Setting range: 0 to 0xFFFF
Example: setting a reference of 4096 with a speed scale of 2:
Speed reference data = 4096/22 = 1024 = 0x0400 Hex
Unit depends on o1-03.
Speed Command
Sets drive speed reference.
Speed reference data: Frequency reference/2SS (SS: Speed scale)
Setting range: 0 to 0xFFFF
Example: setting a reference of 4096 with a speed scale of 2:
Speed reference data = 4096/22 = 1024 = 0x0400 Hex
Unit depends on o1-03.
Torque Reference/Torque Limit
Sets the Torque Reference/Torque Limit in units of 0.1%.
Sets the Torque Reference when using Torque Control (d5-01 = 1).
Sets the Torque Limit when using Speed Control (d5-01 = 0).
The Torque Reference and Torque Limit are disabled with F6-06 = 0.
u
Extended Speed and Torque Control Output - 23 (0x17)
Run command from Network
0: Depends on b1-02
1: Enables the run command from network
Speed reference from Network
0: Depends on b1-01
1: Enables the speed reference from network
Speed Command
Sets drive speed reference.
Speed reference data: Frequency reference/2SS (SS: Speed scale)
Setting range: 0 to 0xFFFF
Example: setting a reference of 4096 with a speed scale of 2:
Speed reference data = 4096/22 = 1024 = 0x0400 Hex
Unit depends on o1-03.
MEMOBUS/Modbus Message Output (Vendor Specific Yaskawa Electric (YE) Assy) -
Sets the Torque Reference/Torque Limit in units of 0.1%.
Sets the Torque Reference when using Torque Control (d5-01 = 1).
Sets the Torque Limit when using Speed Control (d5-01 = 0).
The Torque Reference and Torque Limit are disabled with F6-06 = 0.
Terminal M1/M2
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Terminal P1
0: P1 OFF
1: P1 ON
This function is enabled only when H2-02 is set to F.
Terminal P2
0: P2 OFF
1: P2 ON
This function is enabled only when H2-03 is set to F.
Speed Command
Sets drive speed reference.
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
Torque Reference/Torque Limit
Sets the Torque Reference/Torque Limit in units of 0.1%.
Sets the Torque Reference when using Torque Control (d5-01 = 1).
Sets the Torque Limit when using Speed Control (d5-01 = 0).
The Torque Reference and Torque Limit are disabled with F6-06 = 0.
Torque CompensationSets the amount of Torque Compensation Sets in units of 0.1%.
u
Limit
Analog Output 1MEMOBUS/Modbus (0x0007)
Analog Output 2MEMOBUS/Modbus (0x0008)
Digital OutputsMEMOBUS/Modbus (0x0009)
High Speed/Torque Control Output (Vendor Specific Yaskawa Electric (YE) Assy) - 116
Terminal P1
0: P1 OFF
1: P1 ON
This function is enabled only when H2-02 is set to F.
Terminal P2
0: P2 OFF
1: P2 ON
This function is enabled only when H2-03 is set to F.
Speed Command
Sets drive speed reference.
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
Torque Reference/Torque Limit
Sets the Torque Reference/Torque Limit in units of 0.1%.
Sets the Torque Reference when using Torque Control (d5-01 = 1).
Sets the Torque Limit when using Speed Control (d5-01 = 0).
The Torque Reference and Torque Limit are disabled with F6-06 = 0.
(0x74)
This assembly is dynamic and can be configured as to what parameters are used. The first 20 Bytes (0-19) are fixed and the
next 20 Bytes can be configured using parameters F7-23 to F7-32. If an error occurs while trying to write to the dynamic
parameters, the appropriate error bit in Assembly 166 will be set. If more information is needed as to the nature of the error,
the extended error status can be read explicitly through Class 4, Instance 0xA6, Attribute 0x64. This will return 20 Bytes with
each dynamic parameter in Assembly 116 having a Byte dedicated to its extended error status. Refer to Input Assemblies
Terminal M1/M2
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Terminal P1
0: P1 OFF
1: P1 ON
This function is enabled only when H2-02 is set to F.
Terminal P2
0: P2 OFF
1: P2 ON
This function is enabled only when H2-03 is set to F.
Speed Command
Sets drive speed reference.
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
Torque Reference/Torque Limit
Sets the Torque Reference/Torque Limit in units of 0.1%.
Sets the Torque Reference when using Torque Control (d5-01 = 1).
Sets the Torque Limit when using Speed Control (d5-01 = 0).
The Torque Reference and Torque Limit are disabled with F6-06 = 0.
Contains the data to be written to the MEMOBUS/Modbus address defined in the given parameter. A value of 0 in the given
parameter means it is not used, therefore the value received for this given parameter will not be written to any MEMOBUS/
Modbus register. If the PPA is Input Assembly 166, then any errors occurring during a write will be flagged. Refer to High
Speed/Torque Status Input (Vendor Specific Yaskawa Electric (YE) Assy) - 166 (0xA6) on page 36 for details.
section details “Input Assemblies” that are “Produced” by this drive.
0
70
1
NameDescription
Faulted
Speed Actual
Faulted
0: No Faults Occurred
1: Fault Occurred
Forward Running
0: Stop or Reverse Running
1: Forward Running
Actual Drive Speed
Monitors drive output frequency.
Speed actual data: Output frequency x 2SS (SS: Speed scale)
Setting range: 0 to 0xFFFF
For example, when output frequency of 1024 with a speed scale of 2:
Speed actual data = 1024 x 22 = 4096 = 0x1000
Unit depends on o1-03.
Speed actual data: Output frequency x 2SS (SS: Speed scale)
Setting range: 0 to 0xFFFF
For example, when output frequency of 1024 with a speed scale of 2:
Speed actual data = 1024 x 22 = 4096 = 0x1000
Unit depends on o1-03.
0
1
2
Faulted
0: No Faults Occurred
1: Fault Occurred
Forward Running
0: Stop or Reverse Running
1: Forward Running
Actual Drive Speed
Monitors drive output frequency.
Speed actual data: Output frequency x 2SS (SS: Speed scale)
Setting range: 0 to 0xFFFF
For example, when output frequency of 1024 with a speed scale of 2:
Speed actual data = 1024 x 22 = 4096 = 0x1000
Unit depends on o1-03.
Output Torque
Shows the Torque Reference.
Value displays in 0.1% units.
0–––––
1–
2Speed Actual (Low Byte)
3Speed Actual (High Byte)
4Torque Actual (Low Byte)
5Torque Actual (High Byte)
Running 1
(FWD)
–Faulted
u
Extended Speed and Torque Control Input - 73 (0x49)
Drive StateContains the value from the Control Supervisor (Class 0x29) Instance 1 Attribute 6.
Speed Actual
Torque Actual
Reverse Running
0: Stop or Forward Running
1: Reverse Running
Drive Ready
0: Not Ready
1: Ready
Status of Run command from Network
0: Run command is not from network
1: Run command is from network
Status of Speed reference from Network
0: Speed reference is not from network
1: Speed reference is from network
Speed Agree
0: No Speed Agree
1: Speed actual at speed reference
Actual Drive Speed
Monitors drive output frequency.
Speed actual data: Output frequency x 2SS (SS: Speed scale)
Setting range: 0 to 0xFFFF
For example, when output frequency of 1024 with a speed scale of 2:
Speed actual data = 1024 x 22 = 4096 = 0x1000
Unit depends on o1-03.
Output Torque
Shows the Torque Reference.
Value displays in 0.1% units.
u
MEMOBUS/Modbus Message Input (Vendor Specific Yaskawa Electric (YE) Assy) - 150
(0x96)
Option generated busy event. The MEMOBUS/Modbus requested operation is in the process loop but the drive is not done.
0x22
0x23Attempting to write during a drive undervoltage (Uv) event.
0x24Attempting to write while the drive is storing data.
Writing “Enter” when drive is running.
Attempt to write data that is read only.
Attempt to write a parameter when drive is running.
During a CPF03 event attempting to write to registers other than A1-00 to A1-05, E1-03, o2-04.
Note:Refer to the MEMOBUS/Modbus Data Table in the MEMOBUS/Modbus Communications chapter of the drive manual for a list of monitor
u
Speed/Torque Status Input (Vendor Specific Yaskawa Electric (YE) Assy) - 151 (0x97)
High Speed/Torque Status Input (Vendor Specific Yaskawa Electric (YE) Assy) - 166
(0xA6)
If an error occurs while trying to read from the dynamic parameters, the appropriate error bit in Assembly 166 will be set. If
more information about the nature of the error is needed, the extended error status can be read explicitly through Class 4,
Instance 0xA6, Attribute 0x64. This will return 20 Bytes with each dynamic parameter in Assembly 166 having a Byte
dedicated to its extended error status.
Possible extended error codes are listed in Table 11 and Table 12. If an error occurs, extended error code 0x02 (Register
number failure) is usually set.
Table 11 Extended Error Codes for Assembly 116/166
Error CodeDescription
0x00No error
0x01Sub function code failure
0x02Register number failure
0x21Limit check error failure
0x22Write failure
0x23Write failure at Uv
0x24Write failure at busy
Table 12 Extended Error Codes in Class 0x04 Instance 0xA6 Attribute 0x64
Differs depending on selected motor
control mode.
When set to OLV/PM (A1-02 = 5),
value becomes 3 (PM motor).
When set to V/f (A1-02 = 0) or OLV
(A1-02 = 2), value becomes 7 (squirrel
cage motor).
Motor rated current.
Displayed in 0.1 A units. Changes
according to the current scale (CS).
Motor rated voltage.
Displayed in 1 V units. Changes
according to the voltage scale (VS).
0EGet Attribute Single
10Set Attribute Single
05Reset
O–Byte–
OOByte–Depends on capacity
OOByte–Depends on capacity
Depends on A1-02,
.
Control Method
Selection
Attributes Supported
n
Instance
ID
01
13
14
15
16State
17
18
19Ready
110Faulted
AttributeNameDescriptionGetSetSizeRangeDefault
Object Software
Revision
Run 1 (Forward
Run Command)
Run 2 (Reverse
Run Command)
NetCtrl
(Command)
Running 1
(FWD)
Running 1
(REV)
Revision number of the Control
Supervisor Object.
Forward Running
0: Stop
1: Forward Running
Reverse Running
0: Stop
1: Reverse Running
Run command from Network
0: Depends on b1-02
1: Enables the run command from
network
Drive Status
2: Not Ready
3: Ready (Stopped)
4: Enabled (Run command present)
5: Deceleration to Stop
6: Fault Stop
7: Fault
Drive control mode.
0: OLV, OLV for PM (Read only),
Advanced OLV for PM (Read only)
1: V/f
2: V/f with PG
3: CLV, CLV for PM (Read only)
Actual drive speed.
Unit is not affected by Speed Scale
(SS).
Frequency Reference.
Monitors the drive frequency
reference.
Unit is not affected by Speed Scale
(SS).
Actual Output Current.
Display is in the following units:
2A0004 to 2A0040, 4A0002 to
4A0023, 5A0007 to 5A0017: 0.01 A
units.
2A0056 to 2A0415, 4A0031 to
4A0675, 5A0022 to 5A0242: 0.1 A
units.
4A0930 and 4A1200: 1 A units.
Unit is not affected by Current Scale
(CS).
Drive Output Torque Unit is affected
by Torque Scale (TS)
Torque Reference/Torque Limit
Sets the Torque Reference/Torque
Limit. The units are determined by the
Torque Scale.
Sets the Torque Reference when using
Torque Control (d5-01 = 1).
Sets the Torque Limit when using
Speed Control (d5-01 = 0)
The Torque Reference/Torque Limit
are disabled when F6-06 = 0.
Drive Output Power Unit is affected by
Power Scale (PS).
Drive Input Voltage
Unit is affected by Voltage Scale (VS).
Drive Output Voltage
Unit is affected by Voltage Scale (VS).
Acceleration Time 1 (C1-01)
Units set in parameter C1-10.
Unit is affected by Time Scale (TS).
Acceleration Time 1 (C1-02)
Units set in parameter C1-10.
Unit is affected by Time Scale (TS).
Frequency Reference Lower Limit
(d2-02)
Frequency Reference Upper Limit
(d2-01)
Setting for F7-17, scale of units for
speed related data.
Setting for F7-18, scale of units for
current related data.
Setting for F7-19, scale of units for
torque related data.
Setting for F7-20, scale of units for
power related data.
Setting for F7-21, scale of units for
voltage related data.
Setting for F7-22, scale of units for
speed related data.
Status of Reference Command
(1 = Network).
0: As set by the drive parameters
1: Network
OOByte-15 to 150
OOByte-15 to 150
O–Byte–0
Device Level Ring (DLR) is a layer 2 protocol allowing for redundancy in EtherNet/IP based ring topology networks. DLR
allows devices to be placed in a ring to reduce the need for switch hardware and cabling and allow for the detection and
recovery of faults in the ring. This option is a beacon based ring node implementation.
To set up a DLR network, configure a supervisor on the network prior to connecting and powering on all devices in the ring.
Establishing a ring without an active supervisor may cause a loss of communication to devices on the ring.
The supervisor precedence must be configured when setting up the supervisor. Typically, the default beacon rate is 400 ms to
allow for faster fault detection and recovery period and should be fast enough for devices to recover on the ring without losing
an I/O connection. The precedence value for the supervisor is used when more than one supervisor is present. When two
supervisors are on the network, the supervisor with the higher MAC address will become the supervisor and the other will
become a backup supervisor.
Yaskawa recommends that all devices in the ring be DLR capable. Add non-DLR devices to the ring through a DLR-capable
device, such as a 3-port ETAP.
Ensure that non-DLR devices placed in the ring meet the following requirements:
• Disable MAC address learning
• Do not use multicast filtering
• Preserve VLAN tags.
Make sure that all switches in the ring are DLR-aware. Switches in the ring that are not DLR-aware may cause undesired
behavior due to MAC address learning of the supervisor beacon packets being received on two different switch ports.
Be sure to set the RPI only as fast as needed to limit the network traffic. Yaskawa supports RPIs down to 10 ms. However, if
a slower level of control is acceptable, a slower RPI setting will reduce network traffic.
Yaskawa also recommends setting up and configuring all devices prior to completing the ring by leaving one cable
disconnected. Make the last connection after configuring the nodes and supervisor.
Note:DLR is supported in option software versions VST800341 and later.
Services Supported
n
Service Code No. (Hex)Service Name
Attributes Supported
n
Instance
ID
01
11
12Network Status
46
AttributeNameDescriptionGetSetSizeRangeDefault
Object Software
01Get Attribute All
10Set Attribute Single
Revision
Network
Topology
Revision number of the DLR ObjectO–Word–3
Current network topology mode
0: Linear
1: Ring
Current status of network
0: Normal
1: Ring fault
2: Unexpected loop detected
3: Partial network fault
4: Rapid fault/restore cycle
Struct of:
Supervisor IP Address = Long
Supervisor MAC Address = Array of
bytes
0EGet Attribute Single
10Set Attribute Single
Revision number of the QoS ObjectO–Word–1
DSCP value for CIP transport class 0/1
Urgent priority messages
DSCP value for CIP transport class 0/1
Scheduled priority messages
DSCP value for CIP transport class 0/1
High priority messages
DSCP value for CIP transport class 0/1
Low priority messages
DSCP value for CIP explicit messages
and all other EtherNet/IP encapsulation
messages
O–Struct––
OOByte0 to 6355
OOByte0 to 6347
OOByte0 to 6343
OOByte0 to 6331
OOByte0 to 6327
u
TCP/IP Object 245 (Class 0xF5)
Services Supported
n
Service Code No. (Hex)Service Name
01Get Attribute All
0EGet Attribute Single
10Set Attribute Single
Attributes Supported
n
Instance
ID
AttributeNameDescriptionGetSetSizeRangeDefault
01
11Status
Object Software
Revision
Revision number of the TCP/IP ObjectO–Word–1
Bits 0-3 = Interface Status
0: Interface has not been configured
1: Interface Configuration is valid,
obtained from BOOTP, DHCP, or
NVRAM
2: Interface Configuration is valid and
obtained from hardware settings
3: Reserved
Bit 4 = Multicast Pending
Bits 5-31 = Reserved
Bit 0 = Link Status
Bit 1 = Duplex (0: Half/1: Full)
Bits 2-4 = Negotiation Status
0: In progress
12Interface Flags
13
16
110Interface Label–O–Short String–Port 1
21Interface Speed Interface speed currently in useO–UDINT––
22Interface Flags
26
210Interface Label–O–Short String–Port 2
Physical
Address (MAC)
Interface
Control
Interface
Control
1: Auto-negotiate failed
2: Speed found, duplex not found
3: Successful
4: Not attempted
Bit 5 = Manual Setting requires restart
Bit 6 = Local hardware fault
Bits 7-31 = Reserved
MAC addressO–
Struct of:
Control Bits: Word
Bit 0 = Auto-negotiate
Bit 1 = Forced Duplex Mode
Bits 2-15 = Reserved
Forced Int Speed: Word
Bit 0 = Link Status
Bit 1 = Duplex (0: Half/1: Full)
Bits 2-4 = Negotiation Status
0: In progress
1: Auto-negotiate failed
2: Speed found, duplex not found
3: Successful
4: Not attempted
Bit 5 = Manual Setting requires restart
Bit 6 = Local hardware fault
Bits 7-31 = Reserved
Struct of:
Control Bits: Word
Bit 0 = Auto-negotiate
Bit 1 = Forced Duplex Mode
Bits 2-15 = Reserved
Forced Int Speed: Word
O–DWord––
–OStruct––
O–DWord––
–OStruct––
Array of 6
Bytes
––
Note:“Get Attributes All” Service shall report in attribute ascending order.
This is a dynamic explicit Class Object. With this Class object any drive parameter with a MEMOBUS/Modbus address greater
than 0x00FF can be accessed. The mapping of Class Object instance/attribute to MEMOBUS/Modbus address is as follows.
Given a typical MEMOBUS/Modbus Address of 0xXXYY
The EtherNet/IP Instance value is equal to XX
The EtherNet/IP Attribute value is equal to YY
As an example, to access parameter b5-12 (MEMOBUS/Modbus Address =0x01B0)
Class Object is 100 (0x64) (Always for this Class Object)
Instance = 0x01
Attribute = 0xB0
Storing Changed Parameters
n
Writing a zero to 0x0900 (Enter) stores changed parameters to the non-volatile memory of the drive. Writing a 0 to 0x0910
(Accept) allows the drive to use the changed parameters. Reading Enter Command 0x0900 or Accept Command 0x910 will
always return a value of 0x0001.
Performing a RAM-ENTER to Store Register Data
Parameter H5-11 is used to decide whether a RAM-ENTER will be done on the writes to registers in the drive. If H5-11 = 1
(default), the option will issue the RAM-ENTER with the parameter writes. If H5-11 = 0, no RAM-ENTER is issued and an
ENTER command must be explicitly sent by the user for the parameter to be activated after a write.
Explicit writes to RAM-ENTER (0x910) and ROM-ENTER (0x900) are handled as special cases. If a user writes a 0 to RAMENTER or ROM-ENTER, the command will be executed in the drive. If a user writes a 1 to those registers, the command will
not be executed but returns a success to the explicit write on the network. Writing a value other than 0 or 1 will result in an
error response of Invalid Attribute Value on the network.
Note:Performing the RAM-ENTER increases the processing time of the writes and increases the response time to explicit writes.
Note:1. Attempting to set a read-only parameter results in an EtherNet/IP error code of 0x0E, Attribute Not Settable.
u
Yaskawa Monitor/Control Object 125 (Class 0x7D)
Services Supported
n
AttributeNameDescriptionGetSetSizeRangeDefault
MEMOBUS/
Modbus
Registers
0xFF00 to
0xFFFF
2. Attempting to access an invalid parameter results in an EtherNet/IP error code of 0x09, Invalid Attribute Value.
3. Refer to the MEMOBUS/Modbus Data Table in the MEMOBUS/Modbus Communications chapter of the drive manual for a list of
monitor data using the MEMOBUS/Modbus message area.
Service Code No. (Hex)Service Name
MEMOBUS/Modbus Registers
0xFF00 to 0xFFFF
0EGet Attribute Single
10Set Attribute Single
OOWord––
This is a dynamic explicit Class Object. With this Class object any parameter with a MEMOBUS/Modbus address less than
0x0100 can be accessed. This class is similar to the Drive Parameters Object Class 100, Object Class 100 differs slightly from
Object Class 125. In Object Class 125 the most significant byte of MEMOBUS/Modbus address is always zero and the Instance
ID remains at 1.
Given a typical MEMOBUS/Modbus Address 0f 0x00YY
The EtherNet/IP Instance value is equal to 0x01
The EtherNet/IP Attribute value is equal to YY
As an example, to access Drive Status (MEMOBUS/Modbus Address = 0x002C)
Class Object is 125 (0x7D) (Always for this Class Object)
Instance = 0x01
Attribute = 0x2C
Attributes Supported
n
Instance
ID
Note:1. Attempting to set a read-only parameter results in an EtherNet/IP error code of 0x0E, Attribute Not Settable.
Attribute
01–Object Software RevisionO–Word–1
110x0001Drive Command BitsOOWord–0
120x0002Frequency InstructionOOWord–4
........OOWord––
12550x00FFUnusedOOWord––
2. Attempting to access an invalid parameter results in an EtherNet/IP error code of 0x09, Invalid Attribute Value.
3. Refer to the MEMOBUS/Modbus Data Table in the MEMOBUS/Modbus Communications chapter of the drive manual for a list of
monitor data using the MEMOBUS/Modbus message area.
The option contains a series of web pages that allow for viewing of status and diagnostic information through a standard web
browser.
The web page is accessed through a self-contained web server at port 80. Access the home page by typing the IP address of
the option in a web browser. Example: "http://192.168.1.20"
The IP address of the option can be read using monitors U6-80 to U6-83 on the digital operator if it is unknown. Refer to
• When no internet connection is available, disable the revocation check by changing a Java setting in the PC: All Programs /
Java / Configure Java / Advanced Tab. Set "Perform certificate checks on" to "Do not check".
Current ConnectionsCurrent number of open connections.
Control Connection Delta
u
Time
Msg Tx DroppedCumulative number of messages dropped due to output network buffer being full and unable to hold the new message.
Msg Rx DroppedCumulative number of messages dropped due to input network buffer being full and unable to hold the new message.
Collisions
Msg Tx ErrorsCumulative number of transmit underruns and transmit stops reported by the MAC/PHY.
Msg Rx ErrorsCumulative number of receive overruns, receive stops, and receive error frames reported by the MAC/PHY.
Tx RetryCumulative number of transmits in which the 1st attempt was delayed due to busy medium reported by the MAC/PHY.
Email Alerts Tab
The time between the last two writes to the Control register, MEMOBUS/Modbus address 0001H.
Cumulative number of collisions (half duplex only) reported by the MAC/PHY (Media Access Control/Physical
Connection).
The Email Alerts tab allows the user to configure four Email Fault/Alarm conditions. When the condition is true, one email
will be sent to the provided email address. Another email will not be sent until the condition becomes false and then true again.
A 30-second timer prevents emails from being sent when conditions reoccur immediately after being removed. The timer helps
limit the amount of emails sent regarding the same intermittent condition and helps to reduce network traffic by reducing
emails about reoccurring errors.
Figure 15 Email Alerts Tab View
Conditional Email Set-up
n
Define the condition that will trigger the email by selecting a monitor parameter, a comparator, and a value. Set up
1.
comparator values for the range of values to check in the chosen condition. If choosing only one condition and no OR
or AND are needed, set the “OR/AND” drop-down selection to “NotUsed”.
Enter the email address where the alert will be sent.
2.
Enter the message that will appear in the email contents.
3.
Enter the email subject.
4.
Click the “Email Active” check box to enable the alert.
5.
Clicking “Save to device” will save the entered information into the option memory.
Clicking “Cancel and reload” will cancel any pending edits and display the most recently saved settings from the option board.
The Parameter Access tab allows the user to read and write parameters from the drive. Write access is restricted until a valid
password is entered.
Figure 16 Parameter Access Tab View
The MEMOBUS/Modbus address for the drive parameter being accessed must be entered in hexadecimal. The number must
begin with “0x” to signify hexadecimal. Clicking “Read” will load and display the current value of the given MEMOBUS/
Modbus Address.
Clicking “Set” will save the given value to the given MEMOBUS/Modbus address.
After a “Read” or “Set” command is given, Status will display “Waiting” while the action is being carried out, then “Complete”
is displayed when finished.
The Configuration tab sets web page behavior parameters. Access is restricted unless a valid password is entered.
Figure 17 Configuration Tab View
Security Login
n
Enter a valid password and click “Log in”. The button text will change to “Log out” and the status will change to “Logged
in”.
Note:The default security password is “yaskawa”.
This password can be changed in the “Change Password” section of the tab. Entering a valid password allows access to the
settings in the Configuration tab, Email Alerts tab, and the Parameter Access tab.
Change Password
n
To change the password, enter the new password in the “New Password:” and “Confirm Password:” text boxes then click
“Change password”. The Status display will change to “Idle” then “Changing Password” then “Password Changed”. If the
passwords in the two text boxes do not match, the Status will display “Passwords don’t match”.
Option Card
n
The values displayed in the various tabs are refreshed at the rate defined in the “Applet Refresh Rate (ms)” text box. Enter
values in the range of 1000 ms to 65.535 seconds.
Parameter Security can be enabled or disabled by clicking one of the radio buttons. When “Disabled” is selected, no password
is necessary and all functions in the web pages will be available. When “Enabled” is selected, a valid password must be entered
to edit email settings and to write parameters.
Email Settings
n
The “Email Server IP” text box must contain the IP address of the email server. The subnet address is configured in drive
parameters F7-05 through F7-08. The configured email alerts will use the server at this address when sending emails.
Enter the email server port in the “Email Port” text box.
The value in the “From Email Address” text box identifies the origin of the email alerts to the recipient.
Click “Submit Email Parameters” to save the email settings to the option.
Click “Save Configuration Parameters to Flash” to save the entered values from this tab into non-volatile memory. These
values will then be remembered after cycling power.
Drive-side error codes appear on the drive digital operator. Causes of the errors and corrective actions are listed below. Refer
to the drive manual for additional error codes that may appear on the drive digital operator.
Faults
n
Both bUS (Option Communication Error) and EF0 (Option Card External Fault) can appear as an alarm or as a fault. When a
fault occurs, the digital operator ALM LED remains lit. When an alarm occurs, the ALM LED flashes.
If communication stops while the drive is running, use the following questions as a guide to help remedy the fault:
• Is the option properly installed?
• Are the communication lines properly connected to the option? Are the wires loose?
• Is the controller program working? Has the controller/PLC CPU stopped?
• Did a momentary power loss interrupt communications?
Digital Operator DisplayFault Name
Option Communication Error
bUS
CausePossible Solution
Master controller (PLC) has stopped
communicating
Communication cable is not connected
properly
A data error occurred due to noise
Option is damagedIf there are no problems with the wiring and the error continues to occur, replace the option.
• The connection was lost after establishing initial communication.
• Only detected when the Run command or frequency reference is assigned to the option (b1-01 = 3 or
b1-02 = 3).
• Check that power is supplied to the PLC
• Check that PLC is not in program mode
• Check for faulty wiring
• Correct any wiring problems
• Check the various options available to minimize the effects of noise
• Counteract noise in the control circuit, main circuit, and ground wiring
• If a magnetic contactor is identified as a source of noise, install a surge absorber to the contactor coil
• Make sure the cable used meets requirements
• Make sure the option ground wire is connected between option FE terminal and the drive ground
terminal connected to earth ground
Digital Operator DisplayFault Name
EF0
CausePossible Solutions
An external fault was received from the PLC
and F6-03 is set to a value other than 3.
Problem with the PLC programCheck the PLC program and correct problems.
Digital Operator DisplayFault Name
oFA00
CausePossible Solution
Digital Operator DisplayFault Name
oFA01
CausePossible Solution
The option card connection to port CN5-A is
faulty
Option Card External Fault
The alarm function for an external device has been triggered.
• Remove the cause of the external fault.
• Remove the external fault input from the PLC.
Option Card Connection Error at Option Port CN5-A
Option compatibility error
Option Card Fault at Option Port CN5-A
Option not properly connected
• Turn off the power and reconnect the option card.
• Check if the option card is properly plugged into the option port. Make sure the card is fixed properly.
• If the option is not a communication option card, try to use the card in a different option port. If the
option card works properly in a different option port, CN5-A is damaged, and the drive requires
replacement. If the error persists (oFb01 or oFC01 occur), replace the option card.
The option card installed into port CN5-B is
incompatible with the drive
A communication option card has been
installed in option port
CN5-B
Digital Operator DisplayFault Name
An option card of the same type is already
installed in option port CN5-A
An input option card is already installed in
option port CN5-A
oFA03 to oFA06
oFA10, oFA11
oFA12 to oFA17Option Card Connection Error (CN5-A)
oFA30 to oFA43Communication Option Card Connection Error (CN5-A)
CausePossible Solution
oFb00
CausePossible Solution
oFb02
CausePossible Solution
Option Card Error Occurred at Option Port CN5-A
• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Option Card Fault at Option Port CN5-B
Option compatibility error
Confirm that the drive supports the option card to be installed.
Refer to Option Compatibility on page 62 for details. Contact Yaskawa for assistance.
Communication option cards are only supported by option port CN5-A. It is not possible to install more
than one communication option.
Option Card Fault at Option Port CN5-B
Same type of option card is currently connected
Except for PG options, only one of each option card type can only be installed simultaneously. Make sure
only one type of option card is connected.
Refer to Option Compatibility on page 62 for details. Contact Yaskawa for assistance.
Install a communication option, a digital input option, or an analog input option. More than one of the
same type of card cannot be installed simultaneously.
Digital Operator DisplayFault Name
oFC00
CausePossible Solution
The option card installed into port CN5-C is
incompatible with the drive
A communication option card has been
installed in option port
CN5-C
Digital Operator DisplayFault Name
oFC02
CausePossible Solution
An option card of the same type is already
installed in option port CN5-A or CN5-B.
An input option card is already installed in
option port CN5-A or CN5-B.
Option Card Connection Error at Option Port CN5-C
Option compatibility error
Confirm that the drive supports the option card to be installed.
Refer to Option Compatibility on page 62 for details. Contact Yaskawa for assistance.
Communication option cards are only supported by option port CN5-A. It is not possible to install more
than one communication option.
Option Card Fault at Option Port CN5-C
Same type of option card is currently connected
Except for PG options, only one of each option card type can only be installed simultaneously. Make sure
only one type of option card is connected.
Install a communication option, a digital input option, or an analog input option. More than one of the
same type of card cannot be installed simultaneously.
Communications wiring is faulty, there is a
short circuit, the wiring is incorrect, or the
connections are poor.
Programming error on the master side.Check communications at start-up and correct programming errors.
Communications circuitry is damaged.
Termination resistor setting is incorrect.
bUS Fault Tolerance
n
Serial Communication Transmission Error
Communication has not yet been established.
• Check for wiring errors.
• Correct the wiring.
• Check for disconnected cables and short circuits. Repair as needed.
• Perform a self-diagnostics check.
• If the problem continues, replace the control board or the entire drive. Contact
Yaskawa for instructions on replacing the control board.
Install a termination resistor at both ends of a communication line. Set the internal
termination resistor switch correctly on slave drives. Place DIP switch S1 to the
ON position.
Minor Fault
(H2-oo = 10)
YES
bUS Fault Auto-Restart
Parameter F6-14, bUS Fault Auto Reset Select, will appear when the option is installed.
Setting F6-14 = 0 (Disabled) or F6-01 = 3 or greater (Alarm only) will not affect standard default drive behavior.
Setting F6-14 = 1 (Enabled) AND F6-01 ≠ 3 (Fault) will cause the following operation: The bUS fault occurs after the F7-16
delay and the Run command is removed from the drive. Then the option throws a bUS fault to the drive. When the condition
is removed, the option commands a fault reset and returns control of the drive to the EtherNet/IP network.
Note:The option will only read parameter F6-01 and F6-14 from the drive during power-up.
bUS Fault Delay
Parameter F7-16, Communications Loss Detection Time Delay, will appear when the option is installed.
The setting value of F7-16 is the length of time that the option will delay sending the bUS fault to the drive.
The status LEDs on the option are not affected by the delay time set in F7-16; the LEDs will indicate the bUS condition
immediately.
Note:The option will only read parameter F7-16 from the drive during power-up.
Explicit Message Communications Errors
n
When there is a problem with a request message sent from the master in explicit communications, the drive will return one of
the following error codes.
Table 14 Communications Errors and Solutions
Error
Code
(Hex)
08Service not supportedThe service code is incorrect.Correct the service code.
09Invalid attribute valueThe attribute is incorrect.Correct the attribute.
0CObject state conflict
0EAttribute not settableAttempted to change a read-only attribute.Correct the service code or attribute setting.
13Not enough dataThe data size is incorrect.Correct the data size.
14Attribute not supported
15Too much dataThe data size is incorrect.Correct the data size.
16Object does not existAn unsupported object was specified.Correct the class or instance setting.
1FVendor-specific error
DescriptionCausePossible Solution
Attempted to change a drive constant that cannot be
changed while the drive is running.
Attempted to execute a service not defined for the
attribute.
Attempted to change a drive constant that cannot be
changed while the drive is running.
Attempted to change a drive constant to a value outside
the setting range.
Stop the drive.
Correct the service code or attribute setting.
Stop the drive.
Specify a value within the setting range.
Network sent a message to force this node to the fault
state.
This node and at least one other node have the same IP
Address.
Factory default MAC Address programmed into the
option. Return for reprogramming.
Two drive monitor parameters, U6-98 and U6-99 assist the user in network troubleshooting.
• U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared upon drive power-up.
• U6-99 displays the present option status. U6-99 is cleared upon a network-issued fault reset and upon power-up.
If another fault occurs while the original fault is still active, parameter U6-98 retains the original fault value and U6-99 stores
the new fault status value.
u
Option Compatibility
A limited number of options may be simultaneously connected to the drive depending on the type of option.
Table 16 below lists the number of options that can be connected to the drive and the drive ports for connecting those options.
Table 16 Option Installation
OptionPort/ConnectorNumber of Options Possible
PG-B3, PG-X3CN5-C
<2> <3>
PG-F3
AO-A3, DO-A3CN5-A, B, C1
<3>
SI-B3
<3>
ES3
<4>
DI-A3
<1> When connecting two PG option cards, use both CN5-B and CN5-C. When connecting only one PG option card, use the CN5-C connector.
<2> Not available for the application with Motor 2 Selection.
<3> Not available with models 4A0930 and 4A1200.
<4> When using AI-A3 and DI-A3 as monitors, the card can be connected to any of CN5-A, CN5-B or CN5-C. The input status of AI-A3 can then be
viewed using U1-21, U1-22, and U1-23, and the input status of DI-A3 can then be viewed using U1-17.
Room 1011, Tower W3 Oriental Plaza, No. 1 East Chang An Ave.,
Dong Cheng District, Beijing, 100738, China
Phone: 86-10-8518-4086
YASKAWA ELECTRIC TAIWAN CORPORATION
9F, 16, Nanking E. Rd., Sec. 3, Taipei, 104, Taiwan
Phone: 886-2-2502-5003
YASKAWA INDIA PRIVATE LIMITED
#17/A Electronics City, Hosur Road Bangalore 560 100 (Karnataka), India
Phone: 91-80-4244-1900
http://www.yaskawaindia.in
Fax: 55-11-3585-1187
Fax: 82-2-784-8495
Fax: 65-6289-3003
Fax: 86-21-5385-3299
Fax: 86-10-8518-4082
Fax: 886-2-2505-1280
Fax: 91-80-4244-1901
YASKAWA AMERICA, INC.
In the event that the end user of this p roduct is to b e the military and said product is to be employed in any weapons systems or the manufa cture
thereof, the export will fall u nder th e relevant regulations as stipulated in the For eign Exchange and Foreign Trade Regulatio ns. Therefore, be sure
to follow all procedures and submit all relevant documentation accordin g to any a nd all rules, r egulations and laws th at may ap
Specifications are subject to change without notice for on going product modifica tions and improvements.