Yaskawa SI-EN3 Installation

Page 1
YASKAWA AC Drive 1000-Series Option
EtherNet/IP
Installation Manual
To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance. Ensure the end user receives this manual.
安川インバータ1000シリーズオプション
EtherNet/IP
通信
取扱説明書
形  式
SI-EN3
製品を安全にお使い頂くために,本書を必ずお読みください。 また,本書をお手元に保管していただくとともに,最終的に本製品をご使用になる ユーザー様のお手元に確実に届けられるよう,お取り計らい願います。
MANUAL NO. TOBP C730600 58B
Page 2
Copyright © 2012 YASKAWA ELECTRIC CORPORATION
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of Yaskawa. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because Yaskawa is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Yaskawa assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
2 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Page 3

Table of Contents

1 PREFACE AND SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 PRODUCT OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3 RECEIVING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
4 OPTION COMPONENTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5 INSTALLATION PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . 14
6 RELATED DRIVE PARAMETERS . . . . . . . . . . . . . . . . . . . .32
7 CONFIGURING MESSAGING. . . . . . . . . . . . . . . . . . . . . . . . 36
8 OUTPUT ASSEMBLIES (DRIVE CONSUMES) . . . . . . . . . . 37
9 INPUT ASSEMBLIES (DRIVE PRODUCES) . . . . . . . . . . . . 39
10 WEB INTERFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
11 TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
12 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 3
Page 4

1 Preface and Safety

1 Preface and Safety
Yaskawa manufactures products used as components in a wide variety of industrial systems and equipment. The selection and application of Yaskawa products remain the responsibility of the equipment manufacturer or end user. Yaskawa accepts no responsibility for the way its products are incorporated into the final system design. Under no circumstances should any Yaskawa product be incorporated into any product or design as the exclusive or sole safety control. Without exception, all controls should be designed to detect faults dynamically and fail safely under all circumstances. All systems or equipment designed to incorporate a product manufactured by Yaskawa must be supplied to the end user with appropriate warnings and instructions as to the safe use and operation of that part. Any warnings provided by Yaskawa must be promptly provided to the end user. Yaskawa offers an express warranty only as to the quality of its products in conforming to standards and specifications published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS OFFERED. Yaskawa assumes no liability for any personal injury, property damage, losses, or claims arising from misapplication of its products.

Applicable Documentation

The following manuals are available for the SI-EN3 option:
SI-EN3 Option
Yaskawa AC Drive 1000-Series Option SI-EN3 EtherNet/IP Installation Manual Manual No: TOBP C730600 58 (This book)
Yaskawa AC Drive 1000-Series Option SI-EN3 EtherNet/IP Technical Manual Manual No: SIEP C730600 58
4 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Read this manual first. The installation manual is packaged with the option and contains information required to install the option and set up related drive parameters.
The technical manual contains detailed information about the option. Access the following sites to obtain the technical manual: U.S.: http://www.yaskawa.com Europe: http://www.yaskawa.eu.com Japan: http://www.e-mechatronics.com For questions, contact your local Yaskawa sales office or the nearest Yaskawa representative.
Page 5
Yaskawa Drive
1 Preface and Safety
Yaskawa AC Drive 1000-Series Quick Start Guide
Yaskawa AC Drive 1000-Series Technical Manual
The drive manuals cover basic installation, wiring, operation procedures, functions, troubleshooting, and maintenance information. The manuals also include important information about parameter settings and drive tuning. Access these sites to obtain Yaskawa instruction manuals: U.S.: http://www.yaskawa.com Europe: http://www.yaskawa.eu.com Japan: http://www.e-mechatronics.com For questions, contact your local Yaskawa sales office or the nearest Yaskawa representative.

Terms

Note: Indicates supplemental information that is not related to safety messages.
Drive: Yaskawa AC Drive 1000-Series
Option: Yaskawa AC Drive 1000-Series Option SI-EN3 EtherNet/IP

Registered Trademarks

• EtherNet/IP is a trademark of the ODVA.
• All trademarks are the property of their respective owners.
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 5
Page 6
1 Preface and Safety
DANGER
W ARNING
CAUTION
NOTICE

Supplemental Safety Information

Read and understand this manual before installing, operating, or servicing this option. The option must be installed according to this manual and local codes.
The following conventions are used to indicate safety messages in this manual. Failure to heed these messages could result in serious or possibly even fatal injury or damage to the products or to related equipment and systems.
Indicates a hazardous situation, which, if not avoided, will result in death or serious injury.
Indicates a hazardous situation, which, if not avoided, could result in death or serious injury.
Indicates a hazardous situation, which, if not avoided, could result in minor or moderate injury.
Indicates an equipment damage message.
6 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Page 7
1 Preface and Safety
DANGER
NOTICE
General Safety
General Precautions
• The diagrams in this section may include options and drives without covers or safety shields to illustrate details. Be sure to reinstall covers or shields before operating any devices. The option should be used according to the instructions described in this manual.
• Any illustrations, photographs, or examples used in this manual are provided as examples only and may not apply to all products to which this manual is applicable.
• The products and specifications described in this manual or the content and presentation of the manual may be changed without notice to improve the product and/or the manual.
• When ordering new copies of the manual, contact a Yaskawa representative or the nearest Yaskawa sales office and provide the manual number shown on the front cover.
Heed the safety messages in this manual.
Failure to comply will result in death or serious injury.
The operator is responsible for injuries or equipment damage caused from failure to heed the warnings in the manual.
Do not expose the drive or the option to halogen group disinfectants.
Failure to comply may cause damage to the electrical components in the option.
Do not pack the drive in wooden materials that have been fumigated or sterilized.
Do not sterilize the entire package after the product is packed.
Do not modify the drive or option circuitry.
Failure to comply could result in damage to the drive or option and will void warranty.
Yaskawa is not responsible for any modification of the product made by the user. This product must not be modified.
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 7
Page 8

2 Product Overview

2 Product Overview

About This Product

The option provides a communications connection between the drive and an ODVA EtherNet/IP network. The option connects the drive to an EtherNet/IP network and facilitates the exchange of data.
This manual explains the handling, installation and specifications of this product.
EtherNet/IP is a communications link to connect industrial devices (such as smart motor controllers, operator interfaces, and variable frequency drives) as well as control devices (such as programmable controllers and computers) to a network. EtherNet/IP is a simple, networking solution that reduces the cost and time to wire and install factory automation devices, while providing interchangeability of like components from multiple vendors.
EtherNet/IP is an open device network standard.
By installing the option to a drive, it is possible to do the following from an EtherNet/IP master device:
• drive operation
• drive operation status monitoring
• changing parameter settings.

Applicable Models

The option can be used with the drive models in Tab le 1 .
Table 1 Applicable Models
Drive Series Drive Model Number Software Version <1>
CIMR-A2A ≥ 1010
A1000
Z1000 CIMR-ZA 1014
<1> See “PRG” on the drive nameplate for the software version number.
CIMR-A4A0002 to 4A0675 ≥ 1010
CIMR-A4A0930 and 4A1200 301
CIMR-A5A 504
8 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Page 9

3 Receiving

3 Receiving
Please perform the following tasks upon receipt of the option:
• Inspect the option for damage. Contact the shipper immediately if the option appears damaged upon receipt.
• Verify receipt of the correct model by checking the model number printed on the name plate of the option package.
• Contact your supplier if you have received the wrong model or the option does not function properly.

Option Package Components

Table 2 Option Package Contents
Description: Option
Ground
Wire
Screws (M3) LED Label Installation Manual
_
Quantity: 113 1 1
NS MS
MANUAL

Tools Required for Installation

• A Phillips screwdriver (M3 metric/#1, #2 U.S. standard size <1>) is required to install the option and remove drive front covers.
• Diagonal cutting pliers. (required for some drive models)
• A small file or medium grit sandpaper. (required for certain drive models)
<1> Screw sizes vary by drive capacity. Select a screwdriver appropriate for the drive capacity.
Note: Tools required to prepare option networking cables for wiring are not listed in this manual.
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 9
Page 10

4 Option Components

4 Option Components

SI-EN3 Option

Figure 1
H G
F
A
B
Underside
E
A – Connector (CN5) B – Installation hole F – Communication connector CN1 (RJ45) C – LED (MS) D–LED (NS)<2> H – LED (10/100) <2>
<1> The ground wire provided in the option shipping package must be connected during installation <2> Refer to Option LED Display on page 12 for details on the LEDs
10 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
<2> G – LED (LINK/ACT) <2>
Figure 1 SI-EN3 Option Components
E – Ground terminal and installation hole
D C
<1>
Page 11
4 Option Components

Communication Connector CN1

The communication connector on the option is a modular RJ45 female connector designated CN1. CN1 is the connection point for a customer supplied male Ethernet network communication cable.
Table 3 Male 8-way Ethernet Modular Connector (Customer Supplied)
Male EtherNet 8-Way Modular Connector Pin Description
1 (Pair 2) Transmit data (TXD) +
2 (Pair 2) Transmit data (TXD) -
3 (Pair 3) Receive data (RXD) +
4 (Pair 1) Not used
5 (Pair 1) Not used
6 (Pair 3) Receive data (RXD) -
7 (Pair 4) Not used
8 (Pair 4) Not used <1>
<1> Not used for 10 Mbps and 100 Mbps networks.
<1>
<1>
<1>
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 11
Page 12
4 Option Components

Option LED Display

The option has four LEDs:
Bi-color Status LEDs:
• Module status (MS) red/green
• Network status (NS) red/green
Green Ethernet LEDs:
• Network speed-10/100 (MS) green
• Link status and network activity-Link/Act (NS) red/green
The operational states of the option LEDs after the power-up diagnostic LED sequence is completed are described in Table 4. Wait at least 2 seconds for the power-up diagnostic process to complete before verifying the states of the LEDs.
Table 4 Option LED States
LED
Name
MS
NS
Indication
Color Status
OFF Power supply OFF Power is not being supplied to the drive
Green ON Option operating The option is operating normally
Green Flashing Option initializing The option is configuring an IP address
Red ON Fatal error occurred
Red Flashing Non-fatal error occurred
Green/Red Flashing Option self-test The option is in self-test mode
OFF Offline or Power supply OFF
Green ON
Green Flashing
Red ON Communications error (fatal) The option detected a duplicate IP address
Red Flashing
Green/Red Flashing Option self-test The option is in self-test mode
Operating Status Remarks
The option has detected a fatal (unrecoverable) error
The option has detected a non-fatal (recoverable) error
Online communications established
Online communications not established
Communications time-out (non­fatal)
The option is online and has established connections
The option is online without an established connection
A communications time-out occurred
12 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Page 13
4 Option Components
LED
Name
10/100
<1>
LINK/
ACT
<1>
<1> Remove the drive front cover to check the status of the LED. Be careful not to touch the main circuit terminals or
the control board in the drive.
Indication
Color Status
Green OFF 10 Mbps is established
Green ON 100 Mbps is established
Green OFF Link is not established
Green ON Link is established
Green Flashing
Operating Status Remarks
Link is established and there is network activity
Power-Up Diagnostics
An LED test is performed each time the drive is powered up. The initial boot sequence may take several seconds. After the LEDs have completed the diagnostic LED sequence, the option is successfully initialized. The LEDs then assume operational conditions as shown in
Ta bl e 4.
Table 5 Power-Up Diagnostic LED Sequence
Sequence Module Status (MS) Network Status (NS) Time (ms)
1 Green OFF 250
2 Red OFF 250
3GreenOFF –
4 Green Green 250
5 Green Red 250
6GreenOFF –
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 13
Page 14

5 Installation Procedure

DANGER
W ARNING
5 Installation Procedure

Section Safety

Electrical Shock Hazard
Do not connect or disconnect wiring while the power is on.
Failure to comply will result in death or serious injury.
Disconnect all power to the drive and wait at least the amount of time specified on the drive front cover safety label.
After all indicators are off, measure the DC bus voltage to confirm safe level, and check for unsafe voltages before servicing. The internal capacitor remains charged after the power supply is turned off.
Electrical Shock Hazard
Do not remove the front covers of the drive while the power is on.
Failure to comply could result in death or serious injury.
The diagrams in this section may include options and drives without covers or safety shields to show details. Be sure to reinstall covers or shields before operating any devices. The option should be used according to the instructions described in this manual.
Do not allow unqualified personnel to use equipment.
Failure to comply could result in death or serious injury.
Maintenance, inspection, and replacement of parts must be performed only by authorized personnel familiar with installation, adjustment, and maintenance of this product.
Do not touch circuit boards while the power to the drive is on.
Failure to comply could result in death or serious injury.
14 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Page 15
5 Installation Procedure
NOTICE
W ARNING
Do not use damaged wires, place excessive stress on wiring, or damage the wire insulation.
Failure to comply could result in death or serious injury.
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
Damage to Equipment
Observe proper electrostatic discharge (ESD) procedures when handling the option, drive, and circuit boards.
Failure to comply may result in ESD damage to circuitry.
Never shut the power off while the drive is outputting voltage.
Failure to comply may cause the application to operate incorrectly or damage the drive.
Do not operate damaged equipment.
Failure to comply may cause further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance.
Use shielded twisted-pair wires and ground the shield to the ground terminal of the drive.
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 15
Page 16
5 Installation Procedure
NOTICE
Properly connect all pins and connectors.
Failure to comply may prevent proper operation and possibly damage equipment.
Check wiring to ensure that all connections are correct after installing the option and connecting any other devices.
Failure to comply may result in damage to the option.
16 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Page 17
5 Installation Procedure
F
H
L
M
N
K
I
B
C
D
E
A
G
J
NS MS
A1000

Installing the Option to A1000 Drive

Prior to Installing the Option
Prior to installing the option, wire the drive, make necessary connections to the drive terminals, and verify that the drive functions normally without the option installed. Refer to the Quick Start Guide packaged with the drive for information on wiring and connecting the drive.
Figure 2 shows an exploded view of the drive with the option and related components for
reference.
Figure 2
A – Insertion point for CN5
connector B – SI-EN3 option I – Ground wire C – Drive front cover J – Option modular connector CN1 D – Digital operator K – Drive grounding terminal (FE)
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 17
E – LED label L – Connector CN5-A F – Drive terminal cover M – Connector CN5-B G – Removable tabs for wire
routing
Figure 2 Drive Components with Option
H – Included screws
N – Connector CN5-C
Page 18
5 Installation Procedure
A1000
Installing the Option
Remove the front covers of the drive before installing the option. Refer to the drive Quick Start Guide for directions on removing the front covers. Cover removal varies depending on drive size. This option can be inserted only into the CN5-A connector located on the drive control board.
DANGER! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply could result in death or serious injury. Before installing the option, disconnect all power to the drive and wait at least the amount of time specified on the drive front cover safety label. After all indicators are off, measure the DC bus voltage to confirm safe level, and check for unsafe voltages before servicing. The internal capacitor remains charged after the power supply is turned off.
1. Shut off power to the drive, wait the appropriate amount of time for voltage to
dissipate, then remove the digital operator (D) and front covers (C, F). Refer to the Quick Start Guide packaged with the drive for directions on removing the front covers. Cover removal varies depending on drive size.
NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling the option, drive, and circuit boards. Failure to comply may result in ESD damage to circuitry.
Figure 3
C
D
F
Figure 3 Remove the Front Covers and Digital Operator
18 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Page 19
5 Installation Procedure
A1000
2. With the front covers and digital operator removed, apply the LED label (E) in the
Figure 4
appropriate position on the drive top front cover (C).
C
NS MS
Figure 4 Apply the LED Label
E
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 19
Page 20
5 Installation Procedure
L
H
J
B
A1000
3. Make sure the screws on the left and right sides of the option terminal block (J) are
tightened with a tightening torque of 0.5 to 0.6 Nxm (4.4 to 5.3 in lbs), then insert the option (B) into the CN5-A connector (L) located on the drive and fasten it using one
Figure 5
of the included screws (H).
Figure 5 Insert the Option
20 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Page 21
5 Installation Procedure
A1000
4. Connect the ground wire (I) to the ground terminal (K) using one of the remaining
provided screws (H). Connect the other end of the ground wire (I) to the remaining ground terminal and installation hole on the option (B) using the last remaining
Figure 6
provided screw (H) and tighten both screws to 0.5 to 0.6 Nxm (4.4 to 5.3 in lbs).
B
K
I
H
Figure 6 Connect the Ground Wire
Note: There are two screw holes on the drive for use as ground terminals (K). When connecting three
options, two ground wires will need to share the same drive ground terminal.
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 21
Page 22
5 Installation Procedure
B
A
5. Route the option wiring.
Depending on the drive model, some drives may require routing the wiring through the side of the front cover to the outside to provide adequate space for the wiring. Refer to the Peripheral Devices & Options section of the drive Quick Start Guide or Technical Manual for more information on wire routing of specific models.
Route the wiring through the side of the front cover to the outside. In these cases, using diagonal cutting pliers, cut out the perforated openings on the left side of the drive front cover as shown in Figure 7-A. Sharp edges along the cut out should be smoothed down with a file or sand paper to prevent any damage to the wires. Route the wiring inside the enclosure as shown in Figure 7-B for drives that do not require routing through the front cover.
Note: Separate communication cables from main circuit wiring and other electrical lines.
Figure 7
A – Route wires through the openings
provided on the left side of the front cover.
<1> The drive will not meet NEMA Type 1 requirements if wiring is exposed outside the enclosure.
22 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
<1>
Figure 7 Wire Routing Examples
B – Use the open space provided
inside the drive to route option wiring.
Page 23
5 Installation Procedure
Drive
M
U V
W
R S T
CN5
FE
<1>
EtherNet/IP Master
EtherNet/IP Cable
MotorPower
SI-EN3
EtherNet/IP
Option
CN1
A1000
6. Connect the Ethernet communication cable to the option modular connector (CN1).
To connect the option to a network, insert the RJ45 connector of the Cat 5e patch cable into the option modular connector (CN1). Ensure the cable end is firmly connected (see Figure 7).
IGMP Snooping
Switches implementing IGMP Snooping are strongly recommended. When IGMP Snooping is used, devices will only receive the multicast packets in which they are interested.
Communication Cable Specifications
Only use cable recommended for EtherNet/Industrial Protocol (EtherNet/IP™). Using a cable not specifically recommended may cause the option or drive to malfunction. Refer to the ODVA website for more information on network cabling (http://www.odva.org).
Connection Diagram
<1> The ground wire provided in the option shipping package must be connected during installation.
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 23
Figure 8 Option Connection Diagram
Page 24
5 Installation Procedure
A1000
7. Replace and secure the front covers of the drive (C, F) and replace the digital
Figure 8
operator (D).
C
D
F
Figure 9 Replace the Front Covers and Digital Operator
Note: Take proper precautions when wiring the option so that the front covers will easily fit back onto
the drive. Make sure no cables are pinched between the front covers and the drive when replacing the covers.
8. Set drive parameters in Table 6 for proper option performance.
24 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Page 25
5 Installation Procedure
NS MS
F
J
I
G
A
B
D
E
C
H

Installing the Option to Z1000 Drive

Prior to Installing the Option
Prior to installing the option, wire the drive, make necessary connections to the drive terminals, and verify that the drive functions normally without the option installed. Refer to the User Manual packaged with the drive for information on wiring and connecting the drive.
Figure 10 shows an exploded view of the drive with the option and related components for
reference.
Figure 9
A – Drive grounding terminal (FE) F – LED label B – SI-EN3 option G – Ground wire C – Mounting screw H – Terminal block CN1 D – Drive front cover I – Insert connector CN5 here E – HOA keypad J – Connector CN5
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 25
Figure 10 Drive Components with Option
Page 26
5 Installation Procedure
A1000
Installing the Option
Remove the front cover of the drive before installing the option. Refer to the drive User Manual for directions on removing the front covers. Cover removal varies depending on drive size. This option can be inserted only into the CN5-A connector located on the drive control board.
DANGER! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to comply could result in death or serious injury. Before installing the option, disconnect all power to the drive and wait at least the amount of time specified on the drive front cover safety label. After all indicators are off, measure the DC bus voltage to confirm safe level, and check for unsafe voltages before servicing. The internal capacitor remains charged after the power supply is turned off.
1. Shut off power to the drive, wait the appropriate amount of time for voltage to
dissipate, then remove the HOA keypad (E) and front cover (D).
NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling the option, drive, and circuit boards. Failure to comply may result in ESD damage to circuitry.
Figure 10
D
E
Figure 11 Remove the Front Cover and HOA Keypad
26 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Page 27
5 Installation Procedure
A1000
2. With the front cover and HOA keypad removed, apply the LED label (F) in the
Figure 11
appropriate position on the drive front cover (D).
D
F
NS MS
Figure 12 Apply the LED Label
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 27
Page 28
5 Installation Procedure
J
B
C
H
A1000
3. Make sure the screws on the left and right sides of the option terminal block (H) are
tightened with a tightening torque of 0.5 to 0.6 Nxm (4.4 to 5.3 in lbs), then insert the option (B) into the CN5 connector (J) located on the drive and fasten it using one of
Figure 12
the included screws (C).
Figure 13 Insert the Option
28 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Page 29
5 Installation Procedure
G
C
A
A1000
4. Connect the ground wire (G) to the ground terminal (A) using one of the remaining
provided screws (C). Connect the other end of the ground wire (G) to the ground terminal and installation hole on the option using the last remaining provided screw
Figure 13
(C) and tighten both screws to 0.5 to 0.6 Nxm (4.4 to 5.3 in lbs).
Figure 14 Connect the Ground Wire
5. Wire the communication cables.
Note: Separate communication cables from main circuit wiring and other electrical lines.
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 29
Page 30
5 Installation Procedure
Drive
M
U V
W
R S T
CN5
FE
<1>
EtherNet/IP Master
EtherNet/IP Cable
MotorPower
SI-EN3
EtherNet/IP
Option
CN1
A1000
6. Connect the Ethernet communication cable to the option modular connector (CN1).
To connect the option to a network, insert the RJ45 connector of the Cat 5e patch cable into the option modular connector (CN1). Ensure the cable end is firmly connected (see Figure 15).
IGMP Snooping
Switches implementing IGMP Snooping are strongly recommended. When IGMP Snooping is used, devices will only receive the multicast packets in which they are interested.
Communication Cable Specifications
Only use cable recommended for EtherNet/Industrial Protocol (EtherNet/IP™). Using a cable not specifically recommended may cause the option or drive to malfunction. Refer to the ODVA website for more information on network cabling (http://www.odva.org).
Connection Diagram
<1> The ground wire provided in the option shipping package must be connected during installation.
Figure 15 Option Connection Diagram
30 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Page 31
5 Installation Procedure
D
E
A1000
7. Replace and secure the front cover of the drive (D) and replace the HOA Keypad
Figure 14
(E).
Figure 16 Replace the Front Cover and HOA Keypad
Note: Take proper precautions when wiring the option so that the front covers will easily fit back onto
the drive. Make sure no cables are pinched between the front covers and the drive when replacing the covers.
8. Set drive parameters in Table 6 for proper option performance.

EDS Files

For easy network implementation of drives equipped with the option, an EDS file can be obtained from:
U.S.: http://www.yaskawa.com Europe: http://www.yaskawa.eu.com Japan: http://www.e-mechatronics.com
Other areas: Contact a Yaskawa representative.
Note: Download the EDS file for SI-EN3 option. The SI-EN3 will not function as a slave in the
network without the appropriate EDS file.
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 31
Page 32

6 Related Drive Parameters

6 Related Drive Parameters
The following parameters are used to set up the drive for operation with the option. Parameter setting instructions can be found in the drive Quick Start Guide or Technical Manual.
Confirm proper setting of the all parameters in Table 6 using the digital operator, before starting network communications.
Table 6 Related Parameter Settings
No.
(Addr. Hex)
b1-01
(180)
<1>
b1-02
(181)
<1>
F6-01 (3A2)
F6-02 (3A3)
F6-03 (3A4)
F6-06 (3A7)
<3>
F6-07 (3A8)
Name Description Value s
Selects the frequency reference input source.
Frequency Reference Selection
Run Command Selection
Operation Selection after Communications Error
External Fault Detection Conditions (EF0)
Stopping Method for External Fault from the Communication Option
Torque Reference/ Torque Limit Selection from the Communication Option
NetRef/ComRef Selection Function
0: Operator - Digital preset speed d1-01 to d1-17 1: Terminals - Analog input terminal A1 or A2 2: MEMOBUS/Modbus communications 3: Option 4: Pulse Input (Terminal RP)
Selects the run command input source. 0: Digital Operator - RUN and STOP keys 1: Digital input terminals S1 to S8 2: MEMOBUS/Modbus communications 3: Option
Determines drive response when a bUS error is detected during communications with the option. 0: Ramp to Stop 1: Coast to Stop 2: Fast-Stop 3: Alarm Only
Sets the condition for external fault detection (EF0). 0: Always detected 1: Detected only during operation
Determines drive response for external fault input (EF0) detection during option communications. 0: Ramp to Stop 1: Coast to Stop 2: Fast-Stop 3: Alarm Only
0: Torque Reference/Torque Limit via network communications are disabled. 1: Torque Reference/Torque Limit via network communications are enabled.
0: Multi-step speed reference disabled, (F7 functionality) 1: Multi-step speed reference allowed (V7 functionality)
<2>
<2>
<4>
Default: 1 Range: 0 to 4 (Set to 3)
Default: 1 Range: 0 to 3 (Set to 3)
Default: 1 Range: 0 to 3
Default: 0 Range: 0, 1
Default: 1 Range: 0 to 3
Default: 0 Range: 0, 1
Default: 0 Range: 0, 1
32 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Page 33
6 Related Drive Parameters
No.
(Addr. Hex)
F6-08 (36A)
F7-01 (3E5)
<5> <6>
<7>
F7-02 (3E6)
<5> <6>
<7>
F7-03 (3E7)
<5> <6>
<7>
F7-04 (3E8)
<5> <6>
<7>
F7-05 (3E9)
<7>
F7-06 (3EA)
<7>
F7-07 (3EB)
<7>
F7-08 (3EC)
<7>
F7-09 (3ED)
<7>
F7-10 (3EE)
<7>
F7-11 (3EF)
<7>
Name Description Val ues
Determines if communication-related parameters F6-
Reset Communication Related Parameters
and F7- are set back to original default values when the drive is initialized using parameter A1-03. 0: Do not reset parameters 1: Reset parameters
IP Address 1
IP Address 2
IP Address 3
IP Address 4
Subnet Mask 1
Subnet Mask 2
Subnet Mask 3
Subnet Mask 4
Gateway Address 1
Gateway Address 2
Gateway Address 3
Sets the static/fixed IP address. Parameter F7-01 sets the most significant octet.
Sets the static/fixed IP address. Parameter F7-02 sets the second most significant octet.
Sets the static/fixed IP address. Parameter F7-03 sets the third most significant octet.
Sets the static/fixed IP address. Parameter F7-04 sets the fourth most significant octet.
Sets the static/fixed Subnet Mask. Parameter F7-05 sets the most significant octet.
Sets the static/fixed Subnet Mask. Parameter F7-06 sets the second most significant octet.
Sets the static/fixed Subnet Mask. Parameter F7-07 sets the third most significant octet.
Sets the static/fixed Subnet Mask. Parameter F7-08 sets the fourth most significant octet.
Sets the static/fixed Gateway address. Parameter F7-09 sets the most significant octet.
Sets the static/fixed Gateway address. Parameter F7-10 sets the second most significant octet.
Sets the static/fixed Gateway address. Parameter F7-11 sets the third most significant octet.
Default: 0 Range: 0, 1
Default: 192 Range: 0 to 255
Default: 168 Range: 0 to 255
Default: 1 Range: 0 to 255
Default: 20 Range: 0 to 255
Default: 255 Range: 0 to 255
Default: 255 Range: 0 to 255
Default: 255 Range: 0 to 255
Default: 0 Range: 0 to 255
Default: 192 Range: 0 to 255
Default: 168 Range: 0 to 255
Default: 1 Range: 0 to 255
<7>
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 33
Page 34
6 Related Drive Parameters
No.
(Addr. Hex)
F7-12
(3E0)
<7>
F7-13
(3F1)
F7-14
(3F2)
F7-15
(3F3)
<8>
F7-17
(3F5)
F7-18
(3F6)
F7-19
(3F7)
F7-20
(3F8)
F7-21
(3F9)
F7-22
(3FA)
F7-23 to
F7-32
(3FB to 404)
Name Description Value s
Gateway Address 4
Address Mode at Startup
Duplex Mode Selection
Communication Speed Selection
EtherNet/IP Speed Scaling Factor
EtherNet/IP Current Scaling Factor
EtherNet/IP Torque Scaling Factor
EtherNet/IP Power Scaling Factor
EtherNet/IP Voltage Scaling Factor
EtherNet/IP Time Scaling
Dynamic Output Assembly Parameters
Sets the static/fixed Gateway address. Parameter F7-12 sets the fourth most significant octet.
Selects how the option address is set. 0: Static <6> 1: BOOTP 2: DHCP
Selects duplex mode setting. 0: Half duplex forced 1: Auto-negotiate 2: Full duplex forced
Sets the communication speed 10: 10 Mbps 100: 100 Mbps
Sets the scaling factor for the speed monitor in EtherNet/IP Class ID 2AH Object.
Sets the scaling factor for the output current monitor in EtherNet/IP Class ID 2AH Object.
Sets the scaling factor for the torque monitor in EtherNet/IP Class ID 2AH Object.
Sets the scaling factor for the power monitor in EtherNet/IP Class ID 2AH Object.
Sets the scaling factor for the voltage monitor in EtherNet/IP Class ID 2AH Object.
Sets the scaling factor for the time monitor in EtherNet/IP Class ID 2AH Object.
Parameters used in Output Assembly 116. Each parameter contains a MEMOBUS/Modbus address. The value received for Output Assembly 116 will be written to this corresponding MEMOBUS/Modbus address. A MEMOBUS/Modbus address value of 0 means that the value received for Output Assembly 116 will not be written to any MEMOBUS/Modbus register.
Default: 1 Range: 0 to 255
Default: 2 Range: 0 to 2
Default: 1 Range: 0 to 2
Default: 10 Range: 10, 100
Default: 0 Min.: -15 Max.: 15
Default: 0 Min.: -15 Max.: 15
Default: 0 Min.: -15 Max.: 15
Default: 0 Min.: -15 Max.: 15
Default: 0 Min.: -15 Max.: 15
Default: 0 Min.: -15 Max.: 15
Default: 0
34 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Page 35
6 Related Drive Parameters
No.
(Addr. Hex)
F7-33 to
F7-42
(405 to 40E)
<1> To start and stop the drive with the EtherNet/IP master device using serial communications, set b1-02 to 3 or set
the “Net Control” bit in the assemblies or Control Supervisor Object. To control the drive frequency reference of the drive via the master device, set b1-01 to 3 or set the Net Reference bit in the assemblies or AC/DC Object.
<2> If F6-01 is set to 3, the drive will continue to operate when a fault is detected. Take safety measures, such as
installing an emergency stop switch.
<3> A1000: Enabled in CLV, AOLV/PM, and CLV/PM control modes (A1-02 = 3, 6, or 7). When enabled, d5-01
determines whether the value is read as the Torque Limit value (d5-01 = 0) or read as the Torque Reference value (d5-01 = 1). In CLV/PM, this value is read as the Torque Limit. Z1000: Enabled in OLV/PM control modes (A1-02 = 5). When enabled, d5-01 determines whether the value is read as the Torque Limit value (d5-01 = 0) or read as the Torque Reference value (d5-01 = 1). In V/f, this value is read as the Torque Limit.
<4> The setting specifies that the Torque Reference or Torque Limit is to be provided via network communications
(F6-06 = 1). The motor may rotate if no torque reference or Torque Limit is supplied from the PLC. <5> Cycle power for setting changes to take effect. <6> If F7-13 is set to 0, then all IP Addresses (F7-01 to F7-04) must be unique. <7> Set F7-01 to F7-12 when F7-13 is set to 0. <8> Set F7-15 when F7-14 is set to 0 or 2.
Name Description Val ues
Parameters used in Input Assembly 166. Each parameter contains a MEMOBUS/Modbus address. The value sent for Input Assembly 166 will be read from this corresponding
Dynamic Input Assembly Parameters
MEMOBUS/Modbus address. A MEMOBUS/Modbus address value of 0 means that the value sent for Input Assembly 166 is not defined by the user, therefore the option default register value will be returned.
Refer to Input Assemblies (Drive Produces) on page 39 for
definitions of the default MEMOBUS/Modbus registers.
Default: 0
Table 7 Option Monitors
No. Name Description Value Range
U6-80 to U6-83 Online IP Address
U6-84 to U6-87 Online Subnet
U6-88 to U6-91 Online Gateway
U6-92 Online Speed Link Speed
U6-93 Online Duplex Duplex Setting 0: Half, 1: Full
U6-98 First Fault First Option Fault
U6-99 Current Fault Current Option Fault
IP Address currently available; U6-80 is the most significant octet
Subnet currently available; U6-84 is the most significant octet
Gateway currently available; U6-88 is the most significant octet
0 to 255
0 to 255
0 to 255
10: 10 Mbps 100: 100 Mbps
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 35
Page 36

7 Configuring Messaging

7 Configuring Messaging
This section provides information on methods used to control the drive with the option installed.

Drive Polled Configuration

The assemblies in Table 8 are available for polled I/O:
Table 8 Supported Polled I/O Assemblies
Assembly
Number
(Hex)
20 (14) Basic Speed Control Output Output 4 37
21 (15) Extended Speed Control Output Output 4 38
22 (16) Speed and Torque Control Output Output 6
23 (17) Extended Speed and Torque Control Output Output 6
70 (46) Basic Speed Control Input Input 4 39
71 (47) Extended Speed Control Input Input 4 40
72 (48) Speed and Torque Control Input Input 6
73 (49) Extended Speed and Torque Control Input Input 6
100 (64)
101 (65)
116 (74)
150 (96)
151 (97)
166 (A6)
(Vendor Specific Yaskawa Electric (YE) Assy)­MEMOBUS/Modbus Message Output
(Vendor Specific Yaskawa Electric (YE) Assy)-Speed/ Torque Control Output
(Vendor Specific Yaskawa Electric (YE) Assy)-High Speed/Torque Control Output
(Vendor Specific Yaskawa Electric (YE) Assy)­MEMOBUS/Modbus Message Input
(Vendor Specific Yaskawa Electric (YE) Assy)-Speed/ Torque Status Input
(Vendor Specific Yaskawa Electric (YE) Assy)-High Speed/Torque Status Input
Description Typ e Bytes Page
Output 5
Output 8
Output 44
Input 5
Input 8
Input 44
36 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Page 37

8 Output Assemblies (Drive Consumes)

8 Output Assemblies (Drive Consumes)
Note: The convention in this manual is from the PLC perspective. As such, an assembly is called an
“Output Assembly” when outputted from the PLC and received by this node. This section details “Output Assemblies” that are “Consumed” by this drive.

Basic Speed Control Output - 20 (0x14)

Output
Instance
20
Speed Reference
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0–––––
1–
2 Speed Reference (Low Byte)
3 Speed Reference (High Byte)
Name Description
Run Fwd
Fault Reset
Forward Run Command 0: Stop 1: Forward Run
Fault Reset (0 to 1 transition: Fault Reset)
Speed Command Sets drive speed reference. Speed reference data: Frequency reference/2 Setting range: 0 to 0xFFFF Example: setting a reference of 4096 with a speed scale of 2: Speed reference data = 4096/2 Unit depends on o1-03.
SS
(SS: Speed scale)
2
= 1024 = 0x0400 Hex or 10.24 Hz
Fault Reset
Run
Fwd
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 37
Page 38
8 Output Assemblies (Drive Consumes)

Extended Speed Control Output - 21 (0x15)

Output
Instance
21
Fault Reset
Speed Reference
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 NetRef NetCtrl
1–
2 Speed Reference (Low Byte)
3 Speed Reference (High Byte)
Name Description
Run Fwd
Run Rev
NetCtrl
NetRef
Forward Run Command 0: Stop 1: Forward Run
Reverse Run Command 0: Stop 1: Reverse Run
Fault Reset (0 to 1 transition: Fault Reset)
Run command from Network 0: Depends on b1-02 1: Enables the run command from network
Speed reference from Network 0: Depends on b1-01 1: Enables the speed reference from network
Speed Command Sets drive speed reference. Speed reference data: Frequency reference/2 Setting range: 0 to 0xFFFF For example, when setting a reference of 4096 with a speed scale of 2: Speed reference data = 4096/2 Unit depends on o1-03.
SS
(SS: Speed scale)
2
= 1024 = 0x0400
Fault
Reset
Run Rev
Run Fwd
38 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Page 39

9 Input Assemblies (Drive Produces)

9 Input Assemblies (Drive Produces)
Note: The convention in this manual is from the PLC perspective. An “Input Assembly” is outputted
from this node and read by the PLC. This section details “Input Assemblies” that are “Produced” by this drive.

Basic Speed Control Input - 70 (0x46)

Input
Instance
70
Parameter Data
Running 1 (FWD)
Speed Actual
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0–––––
1–
2 Speed Actual (Low Byte)
3 Speed Actual (High Byte)
Faulted
Faulted 0: No Faults Occurred 1: Fault Occurred
Forward Running 0: Stop or Reverse Running 1: Forward Running
Actual Drive Speed Monitors drive output frequency. Speed actual data: Output frequency x 2 Range: 0 to 0xFFFF For example, when output frequency of 1024 with a speed scale of 2: Speed actual data = 1024 x 2 Unit depends on o1-03.
2
= 4096 = 0x1000
SS
(SS: Speed scale)
Running 1
(FWD)
–Faulted
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 39
Page 40
9 Input Assemblies (Drive Produces)

Extended Speed Control Input - 71 (0x47)

Input
Instance
71
Running 1 (FWD)
Running 2 (REV)
Ctrl from Net
Ref from Net
Drive State Contains the value from the Control Supervisor (Class 0x29) Instance 1 Attribute 6.
Speed Actual
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0At Speed
1 Drive State
2 Speed Actual (Low Byte)
3 Speed Actual (High Byte)
Name Description
Faulted
War ni ng
Ready
At Speed
Faulted 0: No Faults Occurred 1: Fault Occurred
War ni ng 0: No Warning Occurred 1: Warning Occurred
Forward Running 0: Stop or Reverse Running 1: Forward Running
Reverse Running 0: Stop or Forward Running 1: Reverse Running
Drive Ready 0: Not Ready 1: Ready
Status of Run command from Network 0: Run command is not from network 1: Run command is from network
Status of Speed reference from Network 0: Speed reference is not from network 1: Speed reference is from network
Speed Agree 0: No Speed Agree 1: Speed actual at speed reference
Actual Drive Speed Monitors drive output frequency. Speed actual data: Output frequency x 2 Range: 0 to 0xFFFF For example, when output frequency of 1024 with a speed scale of 2: Speed actual data = 1024 x 22 = 4096 = 0x1000 Unit depends on o1-03.
Ref from
Net
Ctrl from
Net
Running 2
Ready
(REV)
SS
(SS: Speed scale)
Running 1
(FWD)
Warning Faulted
40 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Page 41

10 Web Interface

10 Web Interface
The web server interface to the option allows management of diagnostic information through a standard web browser. The embedded web pages include:
• Main page (Information)
• Drive Status page (Status, Monitor and Fault History)
• Network Monitor page (Network Monitor)

Main Page (information)

The embedded main page shows basic option information such as vendor ID, serial number, MAC address, and firmware version. This page also shows the status of the option and provides links to the other embedded web pages.
Figure 15
Figure 17 Main Page View
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 41
Page 42
10 Web Interface

Drive Status Page (Status, Monitor and Fault History)

The embedded drive status page shows basic I/O information and drive state information.
Figure 16
Figure 18 Drive Status Page View
42 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Page 43
10 Web Interface

Network Monitor Page (Network Monitor)

The embedded network monitor page shows the status of the option network traffic and open I/O connections.
Figure 17
Figure 19 Network Monitor Page View
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 43
Page 44
10 Web Interface
Table 9 Network Monitor Explanations
Network Monitor Explanation
Msg Tx OK Cumulative number of messages transmit successfully from the option.
Msg Rx OK Cumulative number of messages received successfully to the option.
Current Connections Current number of open connections.
Msg Tx Dropped
Msg Rx Dropped
Collisions Cumulative number of collisions.
Msg Tx Errors Cumulative number of transmit errors.
Msg Rx Errors Cumulative number of receive errors.
Tx Retry Cumulative number of transmit errors.
Originator IP Address The IP address of the network node making this connection.
Time out Multiplier
O2T_RPI
O2T_API
Consume Msg Cnt
T20_RPI
T20_API
Produce Msg Cnt
Reset Statistics Connection1
Cumulative number of messages dropped due to output network buffer being full and unable to hold the new message.
Cumulative number of messages dropped due to input network buffer being full and unable to hold the new message.
The value here specifies the multiplier applied to the expected packet rate (API) to obtain the value used by the inactivity timer for this connection.
Originator to Target (ie, PLC to SI-EN3) Requested Packet Interval for I/O messaging, in milliseconds, for this connection.
Originator to Target (ie, PLC to SI-EN3) Actual Packet Interval for I/O messaging, in milliseconds, for this connection.
Number of I/O messages consumed (ie, received) from the SI-EN3 since the connection was established or statistics were reset for this connection.
Target to Originator (ie, SI-EN3 to PLC) Requested Packet Interval for I/O messaging, in milliseconds, for this connection.
Target to Originator (ie, SI-EN3 to PLC) Actual Packet Interval for I/O messages, in milliseconds, for this connection.
Number of IO messages produced (ie, transmit) from the SI-EN3 since the connection was established or statistics were reset for this connection.
Clicking this resets the Consume Msg Cnt and the Produce Msg Cnt for this connection to start counting from zero.
Note: Network monitors are reset when the power supply is cycled.
44 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Page 45

11 Troubleshooting

11 Troubleshooting

Drive-Side Error Codes

Drive-side error codes appear on the drive digital operator. Causes of the errors and corrective actions are listed in Table 10. For additional error codes that may appear on the drive digital operator, refer to the drive Technical Manual.
Faults
Both bUS (option communication error) and EF0 (External fault input from the option) can appear as an alarm or as a fault. When a fault occurs, the digital operator ALM LED remains lit. When an alarm occurs, the ALM LED flashes.
If communication stops while the drive is running, use the following questions as a guide to help remedy the fault:
• Is the option properly installed?
• Is the communication line properly connected to the option? Is it loose?
• Is the controller program working? Has the controller/PLC CPU stopped?
• Did a momentary power loss interrupt communications?
Table 10 Fault Displays, Causes, and Possible Solutions
LED Operator Display Fault Name
Option Communication Error
bUS
Cause Possible Solution
Master controller (PLC) has stopped communicating
Communication cable is not connected properly
A data error occurred due to noise
Option is damaged
Connection Time-out
• After establishing initial communication, the connection was lost
• Only detected when the run command or frequency reference is assigned to the option (b1-01 = 3 or b1-02 = 3)
• Check that power is supplied to the PLC
• Check that PLC is not in program mode
• Check for faulty wiring
• Correct any wiring problems
• Inspect items that can minimize the effects of electrical noise
• Counteract noise in the control circuit, main circuit, and ground wiring
• If a magnetic contactor is identified as a source of noise, install a surge absorber to
the contactor coil
• Make sure the cable used meets the EtherNet/IP requirements
• Make sure the option ground wire is connected between option FE terminal and the drive ground terminal connected to earth ground
If there are no problems with the wiring and the error continues to occur, replace the option.
• The option Requested Packet Interval (RPI) timer timed out
• Make sure that RPI time is set properly
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 45
Page 46
11 Troubleshooting
Duplicate IP Address
LED Operator Display Fault Name
EF0
Cause Corrective Action
An external fault is being sent from the upper controller (PLC)
Problem with the PLC program
PLC is in the Idle Mode.
LED Operator Display Fault Name
oFA00
Cause Possible Solution
Non-compatible option connected to the drive
LED Operator Display Fault Name
oFA01
Cause Possible Solution
Problem with the connectors between the drive and option
Check if the option shares IP Address with at least one other node. Check the setting values of F7-01 to F7-04.
Option Card External Fault
The alarm function for an external device has been triggered.
• Remove the cause of the external fault
• Reset the external fault input from the PLC device
Check the program used by the PLC and make the appropriate corrections.
• Set the PLC to the Run Mode.
• Set the drive parameter F6-54 to 0 (Enabled) not to detect errors while the PLC is in the Idle Mode.
Option Card Connection Error (CN5-A)
Option is not properly connected.
Connect an option that is compatible with the drive.
Option Card Fault (CN5-A)
Option is not properly connected.
Turn the power off and check the connectors between the drive and option.
LED Operator Display Fault Name
oFA03
Cause Possible Solution
Option hardware fault Replace the option.
46 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Option Card Error (CN5-A)
Option self-diagnostics error.
Page 47
LED Operator Display Fault Name
oFA04
Cause Possible Solution
Option hardware fault Replace the option.
LED Operator Display Fault Name
to
Option hardware fault Replace the option.
LED Operator Display Fault Name
Non-compatible option connected to the drive.
LED Operator Display Fault Name
Options AI-A3 or DI-A3 are connected to the CN5-B port with an option connected to CN5-A.
oFA30 to
oFA43
Cause Possible Solution
oFb00
Cause Possible Solution
oFb02
Cause Possible Solution
Option Card Error (CN5-A)
Option flash write mode.
Option Card Connection Error (CN5-A)
Communication ID error.
Option Fault (CN5-B)
Non-compatible option is connected.
Connect the correct option to CN5-A.
Option Fault (CN5-B)
Two identical options are connected at the same time.
• Only one type of AI-A3, DI-A3 or SI- option can be connected to the drive.
• The SI-EN3 option can only be connected to CN5-A
11 Troubleshooting
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 47
Page 48
11 Troubleshooting
LED Operator Display Fault Name
oFC00
Cause Possible Solution
Non-compatible option connected to the drive.
LED Operator Display Fault Name
oFC02
Cause Possible Solution
Options AI-A3 or DI-A3 are connected to the CN5-B port while an option connected to CN5-A.
Minor Faults and Alarms
LED Operator Display Minor Fault Name
CALL
Cause Possible Solution
Communication wiring is faulty, there is a short circuit, or improper connection.
master side.
Communication circuitry is damaged.
Option Fault (CN5-C)
Non-compatible option is connected.
Connect the correct option to CN5-A.
Option Fault
Option Flash write mode.
• Only one type of AI-A3, DI-A3 or SI- option can be connected to the drive.
• The SI-EN3 option can only be connected to CN5-A
Serial communication transmission error
Communication is not established.
Check for wiring errors:
• Correct the wiring
• Remove ground shorts and reconnect loose wires
Check communications at start-up and correct programming errors.
• Perform a self-diagnostics check
• Replace the drive if the fault continues to occur
Minor Fault
(H2- = 10)
YESProgramming error on the
48 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Page 49
11 Troubleshooting
Explicit Message Communications Errors
When there is a problem with a request message sent from the master in explicit communications, the drive will return one of the following error codes.
Error Code (hex)
08 Service not supported The service code is incorrect. Correct the service code.
09 Invalid attribute value The attribute is incorrect. Correct the attribute.
0C Object state conflict
0E Attribute not settable
13 Not enough data The data size is incorrect. Correct the data size.
14
15 Too much data The data size is incorrect. Correct the data size.
16 Object does not exist An unsupported object was specified. Correct the class or instance setting.
1F Vendor-specific error
20 Invalid parameter
Description Cause Possible Solution
Attempted to change an drive constant that cannot be changed while the drive is running.
Attempted to change a read-only attribute.
Attribute not supported
Note: Refer to the MEMOBUS/Modbus Data Table in the Technical Manual for a list of monitor data
using the MEMOBUS/Modbus message area.
Attempted to execute a service not defined for the attribute.
• Attempted to change a drive constant that cannot be changed while the drive is running.
• Attempted to change a drive constant to a value outside the setting range.
Attempted to change to a data value outside the setting range.
Stop the drive.
Correct the service code or attribute setting.
Correct the service code or attribute setting.
• Stop the drive.
• Specify a value within the setting range.
Specify a data value within the setting range.
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 49
Page 50
11 Troubleshooting

Option Error Codes

Option Fault Monitors U6-98 and U6-99
The option can declare error/warning conditions via drive monitor parameters on the drive digital operator as shown in Ta bl e 11.
Table 11 Option Fault Monitor Descriptions
Fault Condition
No Fault n/a 0 No faults.
Force Fault EF0 3
Network Link Down BUS ERROR 1100 No network link to option.
Connection Time-out BUS ERROR 1101 The node timer (Requested Packet Interval) timed out.
Duplicate IP Address BUS ERROR 1102
Default MAC Address None 1103
Fault
Declared
Two drive monitor parameters, U6-98 and U6-99 assist the user in network troubleshooting.
• U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared upon drive power-up.
• U6-99 displays the present option status. U6-99 is cleared upon a network-issued fault reset and upon power-up.
If another fault occurs while the original fault is still active, parameter U6-98 retains the original fault value and U6-99 stores the new fault status value.
Status Value
(U6-98/U6-99)
Description
Network sent a message to force this node to the fault state.
This node and at least one other node have the same IP Address.
Factory default MAC Address programmed into the option. Return for reprogramming.
50 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Page 51
11 Troubleshooting

Option Compatibility with A1000

A limited number of options may be simultaneously connected to the A1000 depending on the type of option. Refer to Table 12 for more information. More details can be found in the Options and Peripheral Devices chapter of the drive Technical Manual.
Table 12 Option Installation Compatibility
Option
SI-C3, SI-EM3, SI-EN3, SI-N3, SI-P3, SI-S3, SI-W3, etc. CN5-A 1
PG-B3, PG-X3, etc. CN5-B, C 2
AI-A3 <1>, AO-A3, DI-A3 <1>, DO-A3, etc. CN5-A, B, C 1
<1> When installed in CN5-A, the AI-A3 and DI-A3 options can be used to set the frequency reference or replace the
drive analog inputs with higher resolution. When installed in CN5-B or CN5-C, these options can only be used for monitoring; their input levels will be displayed in U1-17 or U1-21 to U1-23.
<2> Use the CN5-C connector when connecting only one option to the drive; use both CN5-B and CN5-C when
connecting two options.
Connector Number of Possible Options
<2>
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 51
Page 52

12 Specifications

12 Specifications

Specifications

Table 13 Option Specifications
Item Specification
Model SI-EN3
Supported Messages
I/O Assembly Instance
SI-EN3 Specification Conformance Level A6: Passed
SI-EN3 Profile AC Drive
Connector Type RJ45 8-pin Straight Connector STP Cat 5e cable
Physical Layer Type
IP Address Setting Programmable from drive keypad or network
Communication Speed
Number of Connections
Duplex Mode Half-forced, Auto-negotiate, Full-forced
Address Startup Mode Static, BOOTP, DHCP
Ambient Temperature -10°C to +50°C (14°F to 122°F)
Humidity 95% RH or lower with no condensation
Storage Temperature -20°C to +60°C (-4°F to 140°F) allowed for short-term transport of the product
Area of Use Indoor (free of corrosive gas, airborne particles, etc.)
Altitude 1000 m (3280 ft.) or lower
• Explicit: Explicit Class 3, Unconnected
• I/O: Class 1, Listen Only, Input Only
• Input: 7 types (4 to 44 Bytes)
• Output: 7 types (4 to 44 Bytes)
• Isolated Physical Layer
• TCP Protocol Transformer Isolated
Programmable from drive keypad or network: 10/100 Mbps, auto-negotiate
•I/O: 2
• Explicit: 6
52 YASKAWA ELECTRIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual
Page 53
12 Specifications
MANUAL NO.ޓTOBP C730600 58B
Published in Japan November 2012 12-3
Date of publication
Date of original publication
Revision number
1
A1000
1

Revision History

Revision dates and manual numbers appear on the bottom of the back cover.
Date of
Publication
November 2012 All Revision: Reviewed and corrected entire documentation.
March 2012 −−First edition
Revision
Number
Section Revised Content
Chapter 2, 3,
YASKAWA ELECT RIC TOBP C730600 58B 1000-Series Option SI-EN3 Installation Manual 53
and 5
Addition: Z1000 drive added along with corresponding data.
Page 54
YASKAWA AC Drive 1000-Series Option
EtherNet/IP
Installation Manual
DRIVE CENTER (INVERTER PLANT)
2-13-1, Nishimiyaichi, Yukuhashi, Fukuoka, 824-8511, Japan Phone: 81-930-25-3844 Fax: 81-930-25-4369 http://www.yaskawa.co.jp
YASKAWA ELECTRIC CORPORATION
New Pier Takeshiba South Tower, 1-16-1, Kaigan, Minatoku, Tokyo, 105-6891, Japan Phone: 81-3-5402-4502 Fax: 81-3-5402-4580 http://www.yaskawa.co.jp
YASKAWA AMERICA, INC.
2121 Norman Drive South, Waukegan, IL 60085, U.S.A. Phone: (800) YASKAWA (927-5292) or 1-847-887-7000 Fax: 1-847-887-7310 http://www.yaskawa.com
YASKAWA ELÉTRICO DO BRASIL LTDA.
Avenda Fagundes Filho, 620 Bairro Saude, São Paulo, SP04304-000, Brazil Phone: 55-11-3585-1100 http://www.yaskawa.com.br
YASKAWA EUROPE GmbH
Hauptstrasse 185, 65760 Eschborn, Germany Phone: 49-6196-569-300 Fax: 49-6196-569-398 http://www.yaskawa.eu.com
YASKAWA ELECTRIC UK LTD.
1 Hunt Hill Orchardton Woods, Cumbernauld, G68 9LF, United Kingdom Phone: 44-1236-735000 http://www.yaskawa.co.uk
YASKAWA ELECTRIC KOREA CORPORATION
9F, Kyobo Securities Bldg., 26-4, Yeouido-dong, Yeongdeungpo-gu, Seoul, 150-737, Korea Phone: 82-2-784-7844 http://www.yaskawa.co.kr
YASKAWA ELECTRIC (SINGAPORE) PTE. LTD.
151 Lorong Chuan, #04-01, New Tech Park, 556741, Singapore Phone: 65-6282-3003 http://www.yaskawa.com.sg
YASKAWA ELECTRIC (CHINA) CO., LTD.
12F, Carlton Bld., No.21 HuangHe Road, HuangPu Distr ict, Shanghai 200003, China Phone: 86-21-5385-2200 http://www.yaskawa.com.cn
YASKAWA ELECTRIC (CHINA) CO., LTD. BEIJING OFFICE
Room 1011, Tower W3 Oriental Plaza, No. 1 East Chang An Ave., Dong Cheng District, Beijing, 100738, China Phone: 86-10-8518-4086
YASKAWA ELECTRIC TAIWAN CORPORATION
9F, 16, Nanking E. Rd., Sec. 3, Taipei, 104, Taiwan Phone: 886-2-2502-5003
YASKAWA ELECTRIC INDIA PRIVATE LIMITED
#17/A Electronics City, Hosur Road Bangalore 560 100 (Karnataka), India Phone: 91-80-4244-1900 http://www.yaskawaindia.in
Fax: 55-11-5581-8795
Fax: 44-1236-458182
Fax: 82-2-784-8495
Fax: 65-6289-3003
Fax: 86-21-5385-3299
Fax: 86-10-8518-4082
Fax: 886-2-2505-1280
Fax: 91-80-4244-1901
YASKAWA ELECTRIC CORPORATION
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations. Therefore, be sure to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.
© 2012 YASKAWA ELECTRIC CORPORATION. All rights reserved.
MANUAL NO. TOBP C730600 58B
Published in Japan November 2012 12-3 12-7-9
1 -0
Loading...