YASKAWA 400 V Class: 414 A to 2000 A Heavy Duty. 466 A to 2250 A Normal Duty Programming Manual

YASKAWA AC Drive-A1000 HHP
High Performance Vector Control Drive
Programming Manual
Type: CIMR-AU Model: 400 V Class: 414 A to 2000 A Heavy Duty, 466 A to 2250 A Normal Duty
575 V Class: 414 A to 2000 A Heavy Duty, 466 A to 2250 A Normal Duty 690 V Class: 414 A to 2000 A Heavy Duty, 466 A to 2250 A Normal Duty
To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance. Ensure the end user receives this manual.
MANUAL NO. SIEP YEAHHP 01B
Parameter Details
Troubleshooting
Parameter List
MEMOBUS/MODBUS Communications
1
2
E
Copyright © 2011 YASKAWA AMERICA, INC. All rights reserved.
No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of Yaskawa. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because Yaskawa is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Yaskawa assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
Table of Contents
1. PARAMETER DETAILS ................................................................................... 9
1.1 A: Initialization........................................................................................................... 10
A1: Initialization ....................................................................................................................... 10
A2: User Parameters............................................................................................................... 17
1.2 b: Application............................................................................................................. 18
b1: Operation Mode Selection................................................................................................. 18
b2: DC Injection Braking and Short Circuit Braking................................................................. 25
b3: Speed Search.................................................................................................................... 27
b4: Timer Function .................................................................................................................. 33
b5: PID Control........................................................................................................................ 33
b6: Dwell Function................................................................................................................... 43
b7: Droop Control (CLV, CLV/PM) .......................................................................................... 43
b9: Zero Servo......................................................................................................................... 44
1.3 C: Tuning.................................................................................................................... 46
C1: Acceleration and Deceleration Times ............................................................................... 46
C2: S-Curve Characteristics.................................................................................................... 48
C3: Slip Compensation............................................................................................................ 48
C4: Torque Compensation ...................................................................................................... 51
C5: Automatic Speed Regulator (ASR) ................................................................................... 53
C6: Carrier Frequency............................................................................................................. 57
1.4 d: Reference Settings ............................................................................................... 59
d1: Frequency Reference........................................................................................................ 59
d2: Frequency Upper/Lower Limits ......................................................................................... 61
d3: Jump Frequency................................................................................................................ 62
d4: Frequency Reference Hold and Up/Down 2 Function....................................................... 63
d5: Torque Control .................................................................................................................. 67
d6: Field Weakening and Field Forcing................................................................................... 72
d7: Offset Frequency............................................................................................................... 73
1.5 E: Motor Parameters ................................................................................................. 74
E1: V/f Pattern for Motor 1....................................................................................................... 74
E2: Motor 1 Parameters .......................................................................................................... 77
E3: V/f Pattern for Motor 2....................................................................................................... 80
E4: Motor 2 Parameters .......................................................................................................... 81
1.6 F: Option Settings ..................................................................................................... 84
F1: PG Speed Control Card Settings ...................................................................................... 84
F2: Analog Input Card Settings ............................................................................................... 86
F3: Digital Input Card Settings ................................................................................................ 87
F4: Analog Monitor Card Settings ........................................................................................... 88
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
3
Table of Contents
F5: Digital Output Card Settings........................................................................................................ 89
F6 and F7: Communication Option Card........................................................................................... 89
CC-Link Parameters.......................................................................................................................... 91
PROFIBUS-DP Parameters .............................................................................................................. 91
CANopen Parameters ....................................................................................................................... 92
DeviceNet Parameters ...................................................................................................................... 92
1.7 H: Terminal Functions.........................................................................................................95
H1: Multi-Function Digital Inputs ....................................................................................................... 95
H2: Multi-Function Digital Outputs................................................................................................... 105
H3: Multi-Function Analog Inputs .................................................................................................... 115
H4: Multi-Function Analog Outputs ................................................................................................. 121
H5: MEMOBUS/Modbus Serial Communication ............................................................................. 122
H6: Pulse Train Input/Output........................................................................................................... 125
1.8 L: Protection Functions ....................................................................................................128
L1: Motor Protection ........................................................................................................................ 128
L2: Momentary Power Loss Ride-Thru............................................................................................ 134
L3: Stall Prevention ......................................................................................................................... 140
L4: Speed Detection........................................................................................................................ 145
L5: Fault Restart.............................................................................................................................. 146
L6: Torque Detection....................................................................................................................... 148
L7: Torque Limit .............................................................................................................................. 151
L8: Drive Protection......................................................................................................................... 152
1.9 n: Special Adjustments.....................................................................................................158
n1: Hunting Prevention.................................................................................................................... 158
n2: Speed Feedback Detection Control (AFR) Tuning.................................................................... 158
n3: High Slip Braking (HSB) and Overexcitation Braking................................................................ 159
1.10 o: Operator Related Settings............................................................................................161
o1: Digital Operator Display Selection............................................................................................. 161
o2: Digital Operator Keypad Functions ........................................................................................... 162
o3: Copy Function ........................................................................................................................... 164
o4: Maintenance Monitor Settings................................................................................................... 165
q: DriveWorksEZ Parameters.......................................................................................................... 166
r: DriveWorksEZ Connection Parameters ....................................................................................... 166
1.11 T: Motor Tuning .................................................................................................................168
T1: Parameter Settings during Induction Motor Auto-Tuning .......................................................... 168
1.12 U: Monitor Parameters......................................................................................................171
U1: Operation Status Monitors ........................................................................................................ 171
U2: Fault Trace................................................................................................................................ 171
U3: Fault History.............................................................................................................................. 171
U4: Maintenance Monitors .............................................................................................................. 171
U5: PID Monitors ............................................................................................................................. 171
U6: Operation Status Monitors ........................................................................................................ 171
U8: DriveWorksEZ Monitors............................................................................................................ 172
2. TROUBLESHOOTING.......................................................................................... 173
2.1 Section Safety....................................................................................................................174
2.2 Motor Performance Fine-Tuning......................................................................................176
Fine-Tuning V/f Control and V/f Control with PG............................................................................. 176
Fine-Tuning Open Loop Vector Control .......................................................................................... 176
Parameters to Minimize Motor Hunting and Oscillation .................................................................. 177
4
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Table of Contents
2.3 Drive Alarms, Faults, and Errors .....................................................................................179
Types of Alarms, Faults, and Errors................................................................................................ 179
Alarm and Error Displays ................................................................................................................ 179
2.4 Fault Detection ..................................................................................................................184
Fault Displays, Causes, and Possible Solutions ............................................................................. 184
2.5 Alarm Detection.................................................................................................................203
Alarm Codes, Causes, and Possible Solutions ............................................................................... 203
2.6 Operator Programming Errors .........................................................................................213
Operator Programming Error Codes, Causes, and Possible Solutions........................................... 213
2.7 Auto-Tuning Fault Detection ............................................................................................217
Auto-Tuning Codes, Causes, and Possible Solutions..................................................................... 217
2.8 Copy Function Related Displays .....................................................................................222
Tasks, Errors, and Troubleshooting ................................................................................................ 222
2.9 Diagnosing and Resetting Faults.....................................................................................224
Fault Occurs Simultaneously with Power Loss ............................................................................... 224
If the Drive Still has Power After a Fault Occurs ............................................................................. 224
Viewing Fault Trace Data After Fault .............................................................................................. 224
Fault Reset Methods ....................................................................................................................... 225
2.10 Troubleshooting without Fault Display...........................................................................226
Common Problems.......................................................................................................................... 226
Cannot Change Parameter Settings ............................................................................................... 226
Motor Does Not Rotate Properly after Pressing RUN Button or after Entering External Run
Command ...................................................................................................................................... 227
Motor is Too Hot.............................................................................................................................. 228
Drive Does Not Allow Selection of the Desired Auto-Tuning Mode................................................. 229
oPE02 Error Occurs When Lowering the Motor Rated Current Setting .......................................... 229
Motor Stalls during Acceleration or Acceleration Time is Too Long................................................ 229
Drive Frequency Reference Differs from the Controller Frequency Reference Command ............. 230
Excessive Motor Oscillation and Erratic Rotation............................................................................ 230
Deceleration Takes Longer Than Expected with Dynamic Braking Enabled .................................. 230
Noise From Drive or Motor Cables When the Drive is Powered On ............................................... 231
Ground Fault Circuit Interrupter (GFCI) Trips During Run .............................................................. 231
Connected Machinery Vibrates When Motor Rotates ..................................................................... 231
PID Output Fault.............................................................................................................................. 232
Insufficient Starting Torque ............................................................................................................. 232
Motor Rotates after the Drive Output is Shut Off (Motor Rotates During DC Injection Braking) ..... 232
Output Frequency is Not as High as Frequency Reference............................................................ 232
Sound from Motor............................................................................................................................ 233
Motor Does Not Restart after Power Loss....................................................................................... 233
A. PARAMETER LIST............................................................................................... 235
A.1 Understanding Parameter Descriptions..........................................................................236
A1-02 Control Modes, Symbols, and Terms ................................................................................... 236
A.2 Parameter Groups .............................................................................................................237
A.3 A: Initialization Parameters ..............................................................................................238
A1: Initialization ............................................................................................................................... 238
A2: User Parameters....................................................................................................................... 239
A.4 b: Application.....................................................................................................................240
b1: Operation Mode Selection......................................................................................................... 240
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
5
Table of Contents
b2: DC Injection Braking and Short Circuit Braking......................................................................... 241
b3: Speed Search............................................................................................................................ 242
b4: Timer Function .......................................................................................................................... 243
b5: PID Control................................................................................................................................ 243
b6: Dwell Function........................................................................................................................... 245
b7: Droop Control ............................................................................................................................ 245
b9: Zero Servo................................................................................................................................. 246
A.5 C: Tuning............................................................................................................................247
C1: Acceleration and Deceleration Times ....................................................................................... 247
C2: S-Curve Characteristics............................................................................................................ 248
C3: Slip Compensation.................................................................................................................... 248
C4: Torque Compensation .............................................................................................................. 249
C5: Automatic Speed Regulator (ASR) ........................................................................................... 250
C6: Carrier Frequency..................................................................................................................... 251
A.6 d: References.....................................................................................................................252
d1: Frequency Reference................................................................................................................ 252
d2: Frequency Upper/Lower Limits ................................................................................................. 253
d3: Jump Frequency........................................................................................................................ 253
d4: Frequency Reference Hold and Up/Down 2 Function............................................................... 254
d5: Torque Control .......................................................................................................................... 255
d6: Field Weakening and Field Forcing........................................................................................... 255
d7: Offset Frequency....................................................................................................................... 256
A.7 E: Motor Parameters .........................................................................................................257
E1: V/f Pattern for Motor 1............................................................................................................... 257
E2: Motor 1 Parameters .................................................................................................................. 258
E3: V/f Pattern for Motor 2............................................................................................................... 259
E4: Motor 2 Parameters .................................................................................................................. 260
A.8 F: Options...........................................................................................................................261
F1: PG Speed Control Card (PG-X3/PG-B3) .................................................................................. 261
F2: Analog Input Card (AI-A3)......................................................................................................... 263
F3: Digital Input Card (DI-A3).......................................................................................................... 263
F4: Analog Monitor Card (AO-A3) ................................................................................................... 263
F5: Digital Output Card (DO-A3) ..................................................................................................... 264
F6, F7: Communication Option Card............................................................................................... 264
A.9 H Parameters: Multi-Function Terminals ........................................................................269
H1: Multi-Function Digital Inputs ..................................................................................................... 269
H2: Multi-Function Digital Outputs................................................................................................... 273
H3: Multi-Function Analog Inputs .................................................................................................... 276
H4: Analog Outputs ......................................................................................................................... 279
H5: MEMOBUS/Modbus Serial Communication ............................................................................. 279
H6: Pulse Train Input/Output........................................................................................................... 280
A.10 L: Protection Function ......................................................................................................282
L1: Motor Protection ........................................................................................................................ 282
L2: Momentary Power Loss Ride-Thru............................................................................................ 283
L3: Stall Prevention ......................................................................................................................... 284
L4: Speed Detection........................................................................................................................ 285
L5: Fault Restart.............................................................................................................................. 286
L6: Torque Detection....................................................................................................................... 286
L7: Torque Limit .............................................................................................................................. 287
L8: Drive Protection......................................................................................................................... 288
A.11 n: Special Adjustment.......................................................................................................290
6
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Table of Contents
n1: Hunting Prevention.................................................................................................................... 290
n2: Speed Feedback Detection Control (AFR) Tuning.................................................................... 290
n3: High Slip Braking (HSB) and Overexcitation Braking................................................................ 290
A.12 o: Operator-Related Settings ...........................................................................................292
o1: Digital Operator Display Selection............................................................................................. 292
o2: Digital Operator Keypad Functions ........................................................................................... 292
o3: Copy Function ........................................................................................................................... 293
o4: Maintenance Monitor Settings................................................................................................... 293
A.13 DriveWorksEZ Parameters ...............................................................................................295
q: DriveWorksEZ Parameters.......................................................................................................... 295
r: DriveWorksEZ Connection Parameters ....................................................................................... 295
A.14 T: Motor Tuning .................................................................................................................296
T1: Induction Motor Auto-Tuning..................................................................................................... 296
A.15 U: Monitors.........................................................................................................................298
U1: Operation Status Monitors ........................................................................................................ 298
U2: Fault Trace................................................................................................................................ 300
U3: Fault History.............................................................................................................................. 302
U4: Maintenance Monitors .............................................................................................................. 302
U5: PID Monitors ............................................................................................................................. 305
U6: Operation Status Monitors ........................................................................................................ 305
U8: DriveWorksEZ Monitors............................................................................................................ 306
A.16 Control Mode Dependent Parameter Default Values .....................................................307
A1-02 (Motor 1 Control Mode) Dependent Parameters .................................................................. 307
E3-01 (Motor 2 Control Mode) Dependent Parameters .................................................................. 308
A.17 V/f Pattern Default Values.................................................................................................309
A.18 Defaults by Drive Model and Duty Rating ND/HD...........................................................310
B. MEMOBUS/MODBUS COMMUNICATIONS........................................................ 313
B.1 MEMOBUS/Modbus Configuration ..................................................................................314
B.2 Communication Specifications........................................................................................315
B.3 Connecting to a Network ..................................................................................................316
Network Cable Connection.............................................................................................................. 316
Wiring Diagram for Multiple Connections ........................................................................................ 316
Network Termination ....................................................................................................................... 317
B.4 MEMOBUS/Modbus Setup Parameters ...........................................................................319
MEMOBUS/Modbus Serial Communication.................................................................................... 319
B.5 Drive Operations by MEMOBUS/Modbus........................................................................322
Observing the Drive Operation........................................................................................................ 322
Controlling the Drive........................................................................................................................ 322
B.6 Communications Timing...................................................................................................323
Command Messages from Master to Drive..................................................................................... 323
Response Messages from Drive to Master ..................................................................................... 323
B.7 Message Format ................................................................................................................324
Message Content ............................................................................................................................ 324
Slave Address ................................................................................................................................. 324
Function Code ................................................................................................................................. 324
Data................................................................................................................................................. 324
Error Check ..................................................................................................................................... 324
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
7
Table of Contents
B.8 Message Examples ...........................................................................................................326
Reading Drive MEMOBUS/Modbus Register Contents .................................................................. 326
Loopback Test................................................................................................................................. 326
Writing to Multiple Registers............................................................................................................ 326
B.9 MEMOBUS/Modbus Data Table........................................................................................328
Command Data ............................................................................................................................... 328
Monitor Data.................................................................................................................................... 329
Broadcast Messages....................................................................................................................... 340
Fault Trace Contents....................................................................................................................... 341
Alarm Register Contents ................................................................................................................. 343
B.10 Enter Command.................................................................................................................344
Enter Command Types ................................................................................................................... 344
Enter Command Settings when Upgrading the Drive...................................................................... 344
B.11 Communication Errors .....................................................................................................345
MEMOBUS/Modbus Error Codes.................................................................................................... 345
Slave Not Responding..................................................................................................................... 345
B.12 Self-Diagnostics ................................................................................................................346
INDEX ................................................................................................................... 347
8
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
1

Parameter Details

1.1 A: INITIALIZATION................................................................................................10
1.2 B: APPLICATION...................................................................................................18
1.3 C: TUNING..............................................................................................................46
1.4 D: REFERENCE SETTINGS..................................................................................59
1.5 E: MOTOR PARAMETERS....................................................................................74
1.6 F: OPTION SETTINGS...........................................................................................84
1.7 H: TERMINAL FUNCTIONS...................................................................................95
1.8 L: PROTECTION FUNCTIONS............................................................................128
1.9 N: SPECIAL ADJUSTMENTS..............................................................................158
1.10 O: OPERATOR RELATED SETTINGS................................................................161
1.11 T: MOTOR TUNING..............................................................................................168
1.12 U: MONITOR PARAMETERS..............................................................................171
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
9
1.1 A: Initialization

1.1 A: Initialization

The initialization group contains parameters associated with initial drive setup, including parameters involving the display language, access levels, initialization, and password.
u

A1: Initialization

A1-00: Language Selection
n
Selects the display language for the digital operator.
Note: This parameter is not reset when the drive is initialized using parameter A1-03.
No. Parameter Name Setting Range Default
A1-00 Language Selection 0,1 0
Setting 0: English
Setting 1: Japanese
A1-01: Access Level Selection
n
Allows or restricts access to drive parameters.
No. Parameter Name Setting Range Default
A1-01 Access Level Selection 0 to 2 2
Setting 0: Operation only
Allows access and programming of parameters A1-01, A1-04, and Drive Mode.
Allows access to all U monitor parameters.
Does not allow access to Verify Mode, Setup Mode, or Auto-Tuning Mode.
Setting 1: User Parameters
Allows access and programming of parameters A1-00, A1-01, A1-04, and Drive Mode.
Allows access to all U monitor parameters.
Allows access to parameters set in A2-01 to A2-32 in Setup Mode.
Does not allow access to Verify Mode or Auto-Tuning Mode.
Setting 2: Advanced Access Level (A) and Setup Access Level (S)
Allows access and programming of all parameters.
Notes on Parameter Access
• If the drive parameters are password protected by A1-04 and A1-05, parameters A1-01 through A1-03, A1-06, A1-07, and A2-01 through A2-32 cannot be modified.
If a digital input terminal programmed for “Program lockout” (H1-oo = 1B) is enabled, parameter values cannot be modified, even if A1-01 is set to 1 or 2.
• If parameters are changed via serial communication, it will not be possible to edit or change parameter settings with the digital operator until an Enter command is issued to the drive from the serial communication.
A1-02: Control Method Selection
n
Selects the Control Method (also referred to as the control mode) that the drive uses to operate the motor. Parameter A1-02 determines the control mode for motor 1 when the drive is set up to run two motors.
Note: When changing control modes, all parameter settings depending upon the setting of A1-02 will be reset to the default.
No. Parameter Name Setting Range Default
A1-02 Control Method Selection 0, 1, 2, 3 2
Control Modes for Induction Motors (IM)
10
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
1.1 A: Initialization
Setting 0: V/f Control for Induction Motors
Use this mode for simple speed control and for multiple motor applications with low demands to dynamic response or speed accuracy. This control mode is also used when the motor parameters are unknown and Auto-Tuning cannot be performed. The speed control range is 1:40.
Setting 1: V/f Control with PG Speed Feedback
Use this mode for general-purpose applications that require high speed accuracy but do not require high dynamic response. This control mode is also used when the motor parameters are unknown and Auto-Tuning cannot be performed. The speed control range is 1:40.
Setting 2: Open Loop Vector Control
Use this mode for general, variable-speed applications with a speed control range of 1:200 that require precise speed control, quick torque response, and high torque at low speed without using a speed feedback signal from the motor.
Setting 3: Closed Loop Vector Control
Use this mode for general, variable-speed applications that require precise speed control down to zero speed, quick torque response or precise torque control, and a speed feedback signal from the motor. The speed control range is up to 1:1500.
A1-03: Initialize Parameters
n
Resets parameters to default values. After initialization, the setting for A1-03 automatically returns to 0.
No. Parameter Name Setting Range Default
A1-03 Initialize Parameters 0, 1110, 2220, 3330, 5550 0
Setting 1110: User Initialize
Resets parameters to the values selected by the user as User Settings. User Settings are stored when parameter o2-03 is set to “1: Set defaults”.
Note: User Initialization resets all parameters to a user-defined set of default values previously saved to the drive. Set parameter o2-03 to 2 to
Setting 2220: 2-Wire Initialization
clear the user-defined default values.
Resets parameters to default settings with digital inputs S1 and S2 configured as Forward run and Reverse run, respectively.
Refer to Setting 40, 41: Forward Run, Reverse Run Command for 2-Wire Sequence on page 102 for more information on
digital input functions.
Setting 3330: 3-Wire Initialization
Resets parameters to default settings with digital inputs S1, S2, and S5 configured as Run, Stop, and Forward/Reverse respectively. Refer to Setting 0: 3-Wire Sequence on page 96 for more information on digital input functions.
Setting 5550: oPE04 Reset
An oPE04 error appears on the digital operator when a terminal block with settings saved to its built-in memory is installed in a drive that has edited parameters. Set A1-03 to 5550 to use the parameter settings saved to the terminal block memory.
Notes on Parameter Initialization
The parameters shown in Table 1.1 will not be reset when the drive is initialized by setting A1-03 = 2220 or 3330. Although the control mode in A1-02 is not reset when A1-03 is set to 2220 or 3330, it may change when an application preset is selected.
Table 1.1 Parameters Not Changed by Drive Initialization
No. Parameter Name
A1-00 Language Selection
A1-02 Control Method Selection
C6-01 Duty Selection
E1-03 V/f Pattern Selection
F6-08 Communication Parameter Reset
o2-04 Drive/kVA Selection
A1-04, A1-05: Password and Password Setting
n
Parameter A1-04 enters the password when the drive is locked; parameter A1-05 is a hidden parameter that sets the password.
Parameter Details
1
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
11
- MODE -
U1-01= 0.00Hz
U1-02= 0.00Hz U1-03= 0.00 A
DRV
Freq Ref (AI)
Rdy
FWD
LSEQ LREF
-PRMSET­Initialization
Select Language
PRG
A1-00= 0
FWD
-PRMSET­Select Language
English
PRG
FWD
A1-00= 0 *0*
-PRMSET-
A1- 04 = 0
(0~9999)
“0”
PRG
Enter Password
FWD
OFF
-PRMSET-
A1- 05 = 0
(0~9999)
“0”
PRG
Select Password
FWD
-PRMSET-
A1- 05 = 0000
(0~9999)
“0”
PRG
Select Password
FWD
0
-PRMSET-
A1- 05 = 1234
(0~9999)
“0”
PRG
Select Password
FWD
4
-PRMSET-
A1- 05 = 0
(0~9999)
“0”
PRG
Select Password
FWD
1.1 A: Initialization
No. Parameter Name Setting Range Default
A1-04 Password
A1-05 Password Setting
0000 to 9999 0000
How to Use the Password
The user can set a password in parameter A1-05 to restrict access to the drive. The password must be entered to A1-04 to unlock parameter access (i.e., parameter setting A1-04 must match the value programmed into A1-05). The following parameters cannot be viewed or edited until the value entered to A1-04 correctly matches the value set to A1-05: A1-01, A1-02, A1-03, A1-06, A1-07, and A2-01 through A2-32.
The instructions below demonstrate how to set password “1234”. An explanation follows on how to enter that password to unlock the parameters.
Table 1.2 Setting the Password for Parameter Lock
Step Display/Result
1. Turn on the power to the drive. The initial display appears.
- MODE - PRG
Programming
2.
Press or until the Parameter Setting Mode screen appears.
FWD
HELP
DATA
3.
Press to enter the parameter menu tree.
4.
Select the flashing digits by pressing
5.
Select A1-04 by pressing .
Press while holding down
6.
7.
Press .
8.
Use
Note:
A1-05 is hidden and will not display by pressing only .
F1
F2
,
, , and to enter the password.
F1
F2
,
, or .
at the same time. A1-05 will appear.
9.
10. The display automatically returns to the display shown in step 6.
12
Press to save what was entered.
Entry Accepted
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
1.
-PRMSET- PRG Control Method
FWD
A1-02= 2 2
Open Loop Vector
-PRMSET­Initialization
Select Language
PRG
A1-00= 0
FWD
-PRMSET­Select Language
English
PRG
FWD
A1-00= 0 *0*
-PRMSET-
A1- 04 = 0
(0~9999)
“0”
PRG
Enter Password
FWD
-PRMSET- PRG
Enter Password
FWD
A1-04= 1234
V/f Control
4
-PRMSET-
A1- 04 = 0
(0~9999)
“0”
PRG
Enter Password
FWD
-PRMSET- PRG
Control Method
FWD
A1-02= 2 2
Open Loop Vector
-PRMSET- PRG
Control Method
FWD
A1-02= 2
Open Loop Vector
2
-PRMSET- PRG
Control Method
FWD
A1-02= 2
V/F Control
0
“2”
Press to display A1-02.
1.1 A: Initialization
Table 1.3 Check if A1-02 is Locked (continuing from step 10 above)
Step Display/Result
2.
Press , making sure that the setting values cannot be changed.
3.
Press to return to the first display.
Table 1.4 Enter the Password to Unlock Parameters (continuing from step 3 above)
Step Display/Result
1.
Press to enter the parameter setup display.
2.
Press
3.
Press to scroll to A1-04 and .
F1
F2
,
, to select the flashing digits as shown.
4. Enter the password “1234”.
- MODE - PRG
Programming
FWD
HELP
DATA
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
5.
Press to save the new password.
6. Drive returns to the parameter display.
7.
Press and scroll to A1-02.
8.
Press to display the value set to A1-02. If the first “0” blinks, parameter settings are unlocked.
Use and to change the value if desired (though changing the control mode at this point is
9.
not typically done).
Entry Accepted
Parameter Details
1
13
-PRMSET- PRG Control Method
FWD
A1-02= 0 0
V/F Control
1.1 A: Initialization
Step Display/Result
10.
Press to save the setting, or press to return to the previous display without saving changes.
11. The display automatically returns to the parameter display.
Note: 1. Parameter settings can be edited after entering the correct password.
2. Performing a 2-Wire or 3-Wire initialization resets the password to “0000”.
3. Enter a setting other than the password (e.g., 0000) in A1-04 to use the set password to release the lock and restore the lock with the
same password after changing parameter settings.
A1-06: Application Preset
n
Entry Accepted
Several Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these Application Presets automatically assigns functions to the input and output terminals and sets a predefined group of parameters to values appropriate for the selected application.
In addition, the parameters most likely to be changed are assigned to the group of User Parameters, A2-01 through A2-16. User Parameters are part of the Setup Group, which provides quicker access by eliminating the need to scroll through multiple menus.
Setting 1: Water Supply Pump Application
Table 1.5 Water Supply Pump: Parameter Settings
No. Name Default Setting
A1-02 Control Method Selection 0: V/f Control
b1-04 Reverse Operation Selection 1: Reverse Prohibited
C1-01 Acceleration Time 1 1.0 s
C1-02 Deceleration Time 1 1.0 s
C6-01 Duty Rating 1: Normal Duty
E1-03 V/f Pattern Selection 0FH
E1-07 Mid Output Frequency 30.0 Hz
E1-08 Mid Output Frequency Voltage 50.0 V
L2-01 Momentary Power Loss Operation Selection 1: Enabled
L3-04 Stall Prevention Selection during Deceleration 1: Enabled
b1-01 Frequency Reference Selection E1-08 Mid Output Frequency Voltage
b1-02 Run Command Selection E2-01 Motor Rated Current
b1-04 Reverse Operation Selection H1-05
C1-01 Acceleration Time 1 H1-06
C1-02 Deceleration Time 1 H1-07
E1-03 V/f Pattern Selection L5-01 Number of Auto Restart Attempts
E1-07 Mid Output Frequency
14
Table 1.6 Water Supply Pump: User Parameters (A2-01 to A2-16)
No. Parameter Name No. Parameter Name
Multi-Function Digital Input Terminal S5 Function Selection
Multi-Function Digital Input Terminal S6 Function Selection
Multi-Function Digital Input Terminal S7 Function Selection
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
1.1 A: Initialization
Setting 2: Conveyor Application
Table 1.7 Conveyor: Parameter Settings
No. Parameter Name Default Setting
A1-02 Control Method Selection 0: V/f Control
C1-01 Acceleration Time 1 3.0 s
C1-02 Deceleration Time 1 3.0 s
C6-01 Duty Rating 0: Heavy Duty
L3-04 Stall Prevention Selection during Deceleration 1: Enabled
Table 1.8 Conveyor: User Parameters (A2-01 to A2-16)
No. Parameter Name No. Parameter Name
A1-02 Control Method Selection C1-02 Deceleration Time 1
b1-01 Frequency Reference Selection E2-01 Motor Rated Current
b1-02 Run Command Selection L3-04 Stall Prevention Selection during Deceleration
C1-01 Acceleration Time 1
Setting 3: Exhaust Fan Application
Table 1.9 Exhaust Fan: Parameter Settings
No. Parameter Name Default Setting
A1-02 Control Method Selection 0: V/f Control
b1-04 Reverse Operation Selection 1: Reverse Prohibited
C6-01 Duty Selection 1: Normal Duty
E1-03 V/f Pattern Selection 0FH
E1-07 Mid Output Frequency 30.0 Hz
E1-08 Mid Output Frequency Voltage 50.0 V
L2-01 Momentary Power Loss Operation Selection 1: Enabled
L3-04 Stall Prevention Selection during Deceleration 1: Enabled
Table 1.10 Exhaust Fan: User Parameters (A2-01 to A2-16)
No. Parameter Name No. Parameter Name
b1-01 Frequency Reference Selection E1-07 Mid Output Frequency
b1-02 Run Command Selection E1-08 Mid Output Frequency Voltage
b1-04 Reverse Operation Selection E2-01 Motor Rated Current
b3-01 Speed Search Selection at Start H1-05
C1-01 Acceleration Time 1 H1-06
C1-02 Deceleration Time 1 H1-07
Multi-Function Digital Input Terminal S5 Function Selection
Multi-Function Digital Input Terminal S6 Function Selection
Multi-Function Digital Input Terminal S7 Function Selection
E1-03 V/f Pattern Selection L5-01 Number of Auto Restart Attempts
Setting 4: HVAC Fan Application
Table 1.11 HVAC Fan: Parameter Settings
No. Parameter Name Default Setting
A1-02 Control Method Selection 0: V/f Control
b1-04 Reverse Operation Selection 1: Reverse Prohibited
b1-17 Run Command at Power Up 1: Run command issued, motor operation start
C6-01 Duty Rating 1: Normal Duty
C6-02 Carrier Frequency Selection 1: 2.0 kHz
H2-03 Terminals P2 Function Selection 39: Watt Hour Pulse Output
Parameter Details
1
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
15
1.1 A: Initialization
No. Parameter Name Default Setting
L2-01 Momentary Power Loss Operation Selection
L8-03 Overheat Pre-Alarm Operation Selection 4: Operation at lower speed
L8-38 Carrier Frequency Reduction 2: Enabled across entire frequency range.
Table 1.12 HVAC Fan: User Parameters (A2-01 to A2-16)
No. Parameter Name No. Parameter Name
b1-01 Frequency Reference Selection d2-02 Frequency Reference Lower Limit
b1-02 Run Command Selection E1-03 V/f Pattern Selection
b1-03 Stopping Method Selection E1-04 Max Output Frequency
b1-04 Reverse Operation Selection E2-01 Motor Rated Current
C1-01 Acceleration Time 1 H3-11 Terminal A2 Gain Setting
C1-02 Deceleration Time 1 H3-12 Terminal A2 Input Bias
C6-02 Carrier Frequency Selection L2-01 Momentary Power Loss Operation Selection
d2-01 Frequency Reference Upper Limit o4-12 kWh Monitor Initial Value Selection
Setting 5: Compressor Application
Table 1.13 Compressor: Parameter Settings
No. Parameter Name Default Setting
A1-02 Control Method Selection 0: V/f Control
b1-04 Reverse Operation Selection 1: Reverse Prohibited
C1-01 Acceleration Time 1 5.0 s
C1-02 Deceleration Time 1 5.0 s
C6-01 Duty Rating 0: Heavy Duty
E1-03 V/f Pattern Selection 0F Hex
L2-01 Momentary Power Loss Operation Selection 1: Enabled
L3-04 Stall Prevention Selection during Deceleration 1: Enabled
2: CPU Power Active - Drive will restart if power returns prior to control power supply shut down.
Table 1.14 Compressor: User Parameters (A2-01 to A2-16):
No. Parameter Name No. Parameter Name
b1-01 Frequency Reference Selection E1-03 V/f Pattern Selection
b1-02 Run Command Selection E1-07 Mid Output Frequency
b1-04 Reverse Operation Selection E1-08 Mid Output Frequency Voltage
C1-01 Acceleration Time 1 E2-01 Motor Rated Current
C1-02 Deceleration Time 1
A1-07: DriveWorksEZ Function Selection
n
Enables and disables the DriveWorksEZ program inside the drive.
DriveWorksEZ is a software package for customizing drive functionality or adding PLC functionality by the interconnection and configuration of basic software function blocks. The drive performs user-created programs in 1 ms cycles.
Note: 1. If DriveWorksEZ has assigned functions to any of the multi-function output terminals, those functions will remain set to those terminals
No. Parameter Name Setting Range Default
A1-07 DriveWorksEZ Function Selection 0 to 2 0
Setting 0: DWEZ disabled
Setting 1: DWEZ enabled
Setting 2: Digital input
even after disabling DriveWorksEZ.
2. For more information on DriveWorksEZ, contact a Yaskawa representative.
If a digital input is programmed for DWEZ enable/disable (H1-oo = 9F), DWEZ will be enabled when the input is opened.
16
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
1.1 A: Initialization
u

A2: User Parameters

A2-01 to A2-32: User Parameters 1 to 32
n
The user can select up to 32 parameters and assign them to parameters A2-01 through A2-32 to provide quicker access by eliminating the need to scroll through multiple menus. The User Parameter list can also save the most recently edited parameters.
No. Parameter Name Setting Range Default
A2-01 to A2-32 User Parameters 1 to 32 b1-01 to o4-13
<1> A1-06 determines how parameters edited by the user are saved to the list of User Parameters, A2-01 through A2-32.
Saving User Parameters
Determined by
A1-06
<1>
To save specific parameters to A2-01 through A2-32, set parameter A1-01 to 2 to allow access to all parameters, then enter the parameter number to one of the A2-oo parameters to assign it to the list of User Parameters. Finally, set A1-01 to 1 to restrict access so users can only set and refer to the parameters saved as User Parameters.
A2-33: User Parameter Automatic Selection
n
Determines whether recently edited parameters are saved to the second half of the User Parameters (A2-17 to A2-32) for quicker access.
No. Parameter Name Setting Range Default
A2-33 User Parameter Automatic Selection 0, 1
Determined by
A1-06
Setting 0: Do not save list of recently edited parameters
Set A2-33 to 0 to manually select the parameters listed in the User Parameter group.
Setting 1: Save list of recently edited parameters
Set A2-33 to 1 to automatically save recently edited parameters to A2-17 through A2-32. A total of 16 parameters are saved with the most recently edited parameter set to A2-17, the second most recently to A2-18, and so on. Access the User Parameters using the Setup Mode of the digital operator.
Note: User parameters are listed from A2-27 to A2-32. Parameters A2-01 to A2-26 are already listed as defined by default when in Setup Mode.
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Parameter Details
1
17
1.2 b: Application

1.2 b: Application

u

b1: Operation Mode Selection

b1-01: Frequency Reference Selection 1
n
Selects the frequency reference source 1 for the REMOTE mode.
Note: 1. If a Run command is input to the drive but the frequency reference entered is 0 or below the minimum frequency, the RUN indicator
No. Parameter Name Setting Range Default
b1-01 Frequency Reference Selection 1 0 to 4 1
Setting 0: Operator keypad
Using this setting, the frequency reference can be input by:
switching between the multi-speed references in the d1-oo parameters.
• entering the frequency reference on the operator keypad.
Setting 1: Terminals (analog input terminals)
Using this setting, an analog frequency reference can be entered as a voltage or current signal from terminals A1, A2, or A3.
Voltage Input
Voltage input can be used at any of the three analog input terminals. Make the settings as described in Table 1.15 for the input used.
LED on the digital operator will light and the STOP indicator will flash.
2. Press the LO/RE key to set the drive to LOCAL and use the operator keypad to enter the frequency reference.
Terminal Signal Level
A1
A2
A3
0 to 10 Vdc H3-01 = 0
-10 to +10 Vdc H3-01 = 1
0 to 10 Vdc H3-09 = 0
-10 to +10 Vdc H3-09 = 1
0 to 10 Vdc H3-05 = 0
-10 to +10 Vdc H3-05 = 1
2 k
Table 1.15 Analog Input Settings for Frequency Reference Using Voltage Signals
Parameter Settings
Signal Level
Selection
Drive
10.5 V, 20 mA power supply
+V
0 to 10 V
Figure 1.1 Setting the Frequency Reference as a Voltage Signal at Terminal A1
A1 Analog Input 1
A2 Analog Input 2
A3 Analog Input 3
AC Analog input common
-V
-10.5 V, 20 mA power supply
Function Selection Gain Bias
(Frequency Reference Bias)
H3-02 = 0
H3-10 = 0
(Frequency Reference Bias)
H3-06 = 0
(Frequency Reference Bias)
4 k
OR
H3-03 H3-04
H3-11 H3-12
H3-07 H3-08
10.5 V, 20 mA power supply
+V
-10 to 10 V
A1 Analog Input 1
A2 Analog Input 2
A3 Analog Input 3
AC Analog input common
-V
-10.5 V, 20 mA power supply
Set DIP switch S1 on the terminal board to “V” for voltage input.
Set DIP switch S4 on the terminal board to “AI”.
Drive
Notes
Use the wiring example shown in Figure 1.1 for any other analog input terminals. When using input A2 make sure DIP switch S1 is set for voltage input.
Current Input
Input terminal A2 can accept a current input signal. Refer to Table 1.16 to set terminal A2 for current input.
18
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Terminal
A2
Table 1.16 Analog Input Settings for Frequency Reference Using a Current Signal
Signal
Level
4 to 20 mA H3-09 = 2
0 to 20 mA H3-09 = 3
Signal Level
Selection
Figure 1.2 Setting the Frequency Reference as a Current Signal to Terminal A2
Parameter Settings
Function
Selection
H3-10 = 0
(Frequency Bias)
DIP switch S1
V I
0 or 4 to 20 mA
Gain Bias
H3-11 H3-12
Drive
10.5 V, 20 mA power supply
+V
A1 Analog Input 1
A2 Analog Input 2
A3 Analog Input 3
AC Analog input common
-V
-10.5 V, 20 mA power supply
1.2 b: Application
Notes
Make sure to set DIP switch S1 on the terminal board to “I” for current input.
Switching between Main/Auxiliary Frequency References
The frequency reference input can be switched between the analog terminals A1, A2, and A3 using multi-speed inputs. Refer
to Multi-Step Speed Selection on page 59 for details on using this function.
Setting 2: MEMOBUS/Modbus Communications
This setting requires entering the frequency reference via the RS-485/422 serial communications port (control terminals R+, R-, S+, S-).
Setting 3: Option card
This setting requires entering the frequency reference via an option board plugged into connector CN5-A on the drive control board. Consult the option board manual for instructions on integrating the drive with the communication system.
Note: If the frequency reference source is set for Option PCB (b1-01 = 3), but an option board is not installed, an oPE05 Operator Programming
Setting 4: Pulse Train Input
Error will be displayed on the digital operator and the drive will not run.
This setting requires a pulse train signal to terminal RP to provide the frequency reference. Follow the directions below to verify that the pulse signal is working properly.
Verifying the Pulse Train is Working Properly
• Set b1-04 to 4 and set H6-01 to 0.
• Set the H6-02 to the pulse train frequency value that equals 100% of the frequency reference.
• Enter a pulse train signal to terminal RP and check for the correct frequency reference on the display.
b1-02: Run Command Selection 1
n
Determines the Run command source 1 in the REMOTE mode.
No. Parameter Name Setting Range Default
b1-02 Run Command Selection 1 0 to 3 1
Setting 0: Operator
This setting requires entering the Run command via the digital operator RUN key and also illuminates the LO/RE indicator on the digital operator.
Setting 1: Control Circuit Terminal
This setting requires entering the Run command via the digital input terminals using one of following sequences:
• 2-Wire sequence 1:
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Parameter Details
1
19
1.2 b: Application
Two inputs (FWD/Stop-REV/Stop). Set A1-03 to 2220 to initialize the drive and preset terminals S1 and S2 to these functions. This is the default setting of the drive. Refer to Setting 40, 41: Forward Run, Reverse Run Command for 2-
Wire Sequence on page 102.
• 2-Wire sequence 2:
Two inputs (Start/Stop-FWD/REV). Refer to Setting 42, 43: Run and Direction Command for 2-Wire Sequence 2 on
page 103.
• 3-Wire sequence:
Three inputs (Start-Stop-FWD/REV). Set A1-03 to 3330 to initialize the drive and preset terminals S1, S2, and S5 to these functions. Refer to Setting 0: 3-Wire Sequence on page 96.
Setting 2: MEMOBUS/Modbus Communications
This setting requires entering the frequency reference via the RS-485/422 serial communications port (control terminals R+, R-, S+, S-).
Setting 3: Option Card
This setting requires entering the Run command via the communication option board by plugging a communication option board into the CN5-A port on the control PCB. Refer to the option board manual for instructions on integrating the drive into the communication system.
Note: If b1-02 is set to 3, but an option board is not installed in CN5-A, an oPE05 operator programming error will be displayed on the digital
b1-03: Stopping Method Selection
n
operator and the drive will not run.
Selects how the drive stops the motor when the Run command is removed or when a Stop command is entered.
No. Parameter Name Setting Range Default
b1-03 Stopping Method Selection 0 to 3 0
Setting 0: Ramp to Stop
When the Run command is removed, the drive will decelerate the motor to stop. The deceleration rate is determined by the active deceleration time. The default deceleration time is set to parameter C1-02.
When the output frequency falls below the level set in parameter b2-01, the drive will start DC injection, Zero Speed Control, or Short Circuit Braking, depending on the selected control mode. Refer to b2-01: DC Injection Braking Start Frequency
on page 25 for details.
Setting 1: Coast to Stop
When the Run command is removed, the drive will shut off its output and the motor will coast (uncontrolled deceleration) to stop. The stopping time is determined by the inertia and the friction in the driven system.
Run
command
Output
frequency
Motor speed
ON OFF
Drive output is shut off
Figure 1.3 Coast to Stop
Note: After a stop is initiated, any subsequent Run command entered will be ignored until the minimum baseblock time (L2-03) has expired. Do
Setting 2: DC Injection Braking to Stop
not enter Run command until it has come to a complete stop. Use DC Injection at Start (Refer to b2-03: DC Injection Braking Time at
Start on page 26) or Speed Search (Refer to b3: Speed Search on page 27) to restart the motor before it has completely stopped.
When the Run command is removed, the drive will enter baseblock (turn off its output) for the minimum baseblock time (L2-03). When the minimum baseblock time has expired, the drive will inject the amount DC current set in parameter b2-02 into the motor windings to brake the motor. The stopping time in DC Injection Braking to Stop is significantly faster compared to Coast to Stop.
Note: This function is not available in the control modes for PM motors (A1-02 = 5, 6, 7).
Note: PM motor control modes are not available in A1000 HHP drive models.
20
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
DC Injection brake time
(b2-04) x 10 x Output frequency
Max. output frequency (E1-04)
=
1.2 b: Application
Run
command
Output
frequency
Motor speed
ON OFF
DC Injection Braking
with the current set in
Motor coasts
Minimum Baseblock
Time (
L2-03)
b2-02
Figure 1.4 DC Injection Braking to Stop
DC Injection Braking time is determined by the value set to b2-04 and the output frequency at the time the Run command is removed. It can be calculated by:
DC Injection braking time
b2-04×10
b2-04
10%
Output frequency when
Stop command was entered
100%
(Maximum output
frequency)
Figure 1.5 DC Injection Braking Time Depending on Output Frequency
Note: If an overcurrent (oC) fault occurs during DC Injection Braking to Stop, lengthen the minimum baseblock time (L2-03) until the fault no
longer occurs.
Setting 3: Coast to Stop with Timer
When the Run command is removed, the drive will turn off its output and the motor will coast to stop. The drive will not start if a Run command is input before the time t (C1-02) has expired. Cycle the Run command that was activated during time t after t has expired to start the drive.
Run command
Output
frequency
ON ON ONOFF OFF
Drive output shut off
Run wait time t
Figure 1.6 Coast to Stop with Timer
The wait time t is determined by the output frequency when the Run command is removed and by the active deceleration time.
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Parameter Details
1
21
Min output frequency
100%
(Max output
frequency)
Output frequency
when Stop command
was entered
Run wait time t
Active deceleration time
Momentary Power Loss Minimum Baseblock Time (L2-03)
Zero Speed
Control
b2-01 DC Injection
Speed Level
Run
Command
Frequency
reference
Motor
Speed
OFF ON
Zero Speed
Control
E1-09 Min.
Frequency
b2-04
Zero Speed
Time at Stop
E1-09
b2-03
Zero Speed Time at Start
IM: Initial Excitation
PM: Zero Spd. Contr.
1.2 b: Application
Figure 1.7 Run Wait Time Depending on Output Frequency
b1-04: Reverse Operation Selection
n
Enables and disables Reverse operation. For some applications, reverse motor rotation is not appropriate and may cause problems (e.g., air handling units, pumps, etc.).
No. Parameter Name Setting Range Default
b1-04 Reverse Operation Selection 0, 1 0
Setting 0: Reverse operation enabled
Possible to operate the motor in both forward and reverse directions.
Setting 1: Reverse operation disabled
Drive disregards a Reverse run command or a negative frequency reference.
b1-05: Action Selection below Minimum Output Frequency (CLV and CLV/PM)
n
Sets the operation when the frequency reference is lower than the minimum output frequency set in parameter E1-09.
No. Parameter Name Setting Range Default
b1-05 Action Selection below Minimum Output Frequency 0 to 3 0
Setting 0: Follow the Frequency Reference
The drive adjusts the motor speed following the speed reference, even if the frequency reference is below the setting of parameter E1-09. When the Run command is removed and the motor speed is smaller than the setting of b2-01, Zero Speed Control (not position lock) is performed for the time set in parameter b2-04 before the drive output shuts off.
Figure 1.8 Run at the Frequency Reference
Setting 1: Coast to Stop
The motor starts when the frequency reference exceeds the parameter E1-09 setting. When the motor is running and the frequency reference falls below E1-09, the drive output shuts off and the motor coasts. When the motor speed falls below the zero speed level set in b2-01, Zero Speed Control is activated for the time set in b2-04.
22
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
b2-03
Zero Speed Time at Start
IM: Initial Excitation
PM: Zero Spd. Contr.
Run
Command
Frequency
reference
Motor
Speed
OFF ON
Zero Speed
Control
E1-09 Min.
Frequency
b2-04
Zero Speed Time at Stop
Motor
Coasts
b2-01 Zero
Speed Level
Run
Command
Frequency
reference
Motor
Speed
OFF ON
Zero Speed
Control
E1-09 Min.
b2-04
Run at E1-09
Run at
E1-09
b2-03
IM: Initial Excitation
PM: Zero Spd. Contr.
Frequency
Zero Speed Time at Start
Zero Speed
Time at Stop
b2-01 Zero Speed Level
Zero
Speed
Control
Run
Command
Frequency
reference
Motor
Speed
OFF ON
Zero Speed
Control
E1-09 Min. Frequency
b2-04
E1-09
b2-03
IM: Initial Excitation
PM: Zero Spd. Contr.
Zero Speed Time at Start
Zero Speed Time at Stop
b2-01 Zero
Speed Level
1.2 b: Application
Figure 1.9 Coast to Stop
Setting 2: Run at the Minimum Frequency
When a Run command is active and the frequency reference is smaller than the parameter E1-09 setting, the drive runs the motor at the speed set in E1-09. When the Run command is removed, the drive decelerates the motor. As soon as the motor speed reaches the zero speed level set in b2-01, Zero Speed Control is activated for the time set in b2-04.
Figure 1.10 Run at the Minimum Frequency
Setting 3: Zero Speed Control
The drive applies Zero Speed Control whenever the frequency reference setting is below the value of parameter E1-09.
Remove the Run command when the drive is operating at or above the frequency set in E1-09 to activate Zero Speed Control for the time set in b2-04, regardless of whether Zero Speed Control was already active.
Figure 1.11 Zero Speed Control
b1-06: Digital Input Reading
n
Defines how the digital inputs are read. The inputs are acted upon every 1 ms or 2 ms depending upon the setting.
No. Name Setting Range Default
b1-06 Digital Input Reading 0, 1 1
Parameter Details
Setting 0: Read once (1 ms scan)
The state of a digital input is read once. If the state has changed, the input command is immediately processed. With this setting the drive responds more quickly to digital inputs, but a noisy signal could cause erroneous operation.
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
1
23
1.2 b: Application
Setting 1: Read twice (2 ms scan)
The state of a digital input is read twice. The input command is processed only if the state does not change during the double reading. This reading process is slower than the “Read once” process, but it is more resistant to noisy signals.
b1-07: LOCAL/REMOTE Run Selection
n
The drive has three separate control sources that can be switched using digital inputs (H1-oo = 1 (LOCAL/REMOTE Selection) or 2 (External reference 1/2)) or the LO/RE key on the digital operator. Refer to Setting 1: LOCAL/REMOTE
Selection on page 96, Refer to Setting 2: External Reference 1/2 Selection on page 97 and Refer to o2-01: LO/RE (LOCAL/REMOTE) Key Function Selection on page 162 for details.
• LOCAL: Digital operator. The digital operator sets the frequency reference and Run command.
• REMOTE: External reference 1. The frequency reference and Run command source are set by b1-01 and b1-02.
• REMOTE: External reference 2. The frequency reference and Run command source are set by b1-15 and b1-16. When switching from LOCAL to REMOTE, or between External reference 1 and External reference 2, the Run command
may already be present at the location at which the source is being switched. In this case, use parameter b1-07 to determine how the Run command is treated.
No. Parameter Name Setting Range Default
b1-07 LOCAL/REMOTE Run Selection 0, 1 0
Setting 0: Run command must be cycled
When the Run command source differs between the old source and the new source (e.g., the old source was the terminals and the new source is serial communication), and the Run command is active at the new source as the switchover occurs, the drive will not start or the drive will stop operation if it was previously running. The Run command must be cycled at the new source to restart the drive.
Setting 1: Accept Run command at the new source
When the Run command is active at the new source, the drive starts or continues operation if it was previously running.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly if switching control sources when b1-07 = 1. Clear all personnel from rotating machinery and electrical connections prior to switching control sources. Failure to comply may cause death or serious injury.
b1-08: Run Command Selection while in Programming Mode
n
As a safety precaution, the drive will not normally respond to a Run command input when the digital operator is being used to adjust parameters in Programming Mode (Verify Menu, Setup Mode, Parameter Settings Mode, and Auto-Tuning Mode). If required by the application, set b1-08 to allow the drive to run while in Programming Mode.
No. Parameter Name Setting Range Default
b1-08 Run Command Selection while in Programming Mode 0 to 2 0
Setting 0: Disabled
A Run command is not accepted while the digital operator is in Programming Mode.
Setting 1: Enabled
A Run command is accepted in any digital operator mode.
Setting 2: Prohibit programming during run
It is not possible to enter the Programming Mode as long as the drive output is active. The Programming Mode cannot be displayed during Run.
b1-14: Phase Order Selection
n
Sets the phase order for drive output terminals U/T1, V/T2, and W/T3.
Switching motor phases will reverse the direction of the motor.
No. Parameter Name Setting Range Default
b1-14 Phase Order Selection 0, 1 0
Setting 0: Standard Phase Order Setting 1: Switched Phase Order
b1-15: Frequency Reference Selection 2
n
Enabled when H1-oo = 2 and the terminal is closed. Refer to Setting 2: External Reference 1/2 Selection on page 97 and
Refer to b1-02: Run Command Selection 1 on page 19 for details.
24
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
1.2 b: Application
No. Parameter Name Setting Range Default
b1-15 Frequency Reference Selection 2 0 to 4 0
b1-16: Run Command Selection 2
n
Enabled when H1-oo = 2 and the terminal is closed. Refer to Setting 2: External Reference 1/2 Selection on page 97 and
Refer to b1-01: Frequency Reference Selection 1 on page 18 for details.
No. Parameter Name Setting Range Default
b1-16 Run Command Selection 2 0 to 3 0
b1-17: Run Command at Power Up
n
Determines whether an external Run command that is active during power up will start the drive.
No. Parameter Name Setting Range Default
b1-17 Run Command at Power Up 0, 1 0
Setting 0: Run Command at Power Up Is Not Issued
Cycle the Run command to start the drive.
Note: For safety reasons, the drive is initially programmed not to accept a Run command at power up (b1-17 = 0). If a Run command is issued at
Setting 1: Run Command at Power Up Is Issued
power up, the RUN indicator LED will flash quickly.
If an external Run command is active when the drive is powered up, the drive will begin operating the motor once the internal start up process is complete.
WARNING! Sudden Movement Hazard. If b1-17 is set to 1 and an external Run command is active during power up, the motor will begin rotating as soon as the power is switched on. Proper precautions must be taken to ensure that the area around the motor is safe prior to powering up the drive. Failure to comply may cause serious injury.
u

b2: DC Injection Braking and Short Circuit Braking

These parameters determine operation of the DC Injection Braking, Zero Speed Control, and Short Circuit Braking features.
b2-01: DC Injection Braking Start Frequency
n
Active when “Ramp to Stop” is selected as the stopping method (b1-03 = 0).
No. Name Setting Range Default
b2-01 DC Injection Braking Start Frequency 0.0 to 10.0 Hz
Determined by
A1-02
The function triggered by parameter b2-01 depends on the control mode that has been selected.
V/f, V/f w/PG, and OLV (A1-02 = 0, 1, 2)
For these control modes, parameter b2-01 sets the starting frequency for DC Injection Braking at Stop. When the output frequency falls below the setting of b2-01, DC Injection Braking is enabled for the time set in parameter b2-04.
DC Injection
E1-09 Min. Frequency b2-01 Zero Speed Level
Output
frequency
Figure 1.12 DC Injection Braking at Stop for V/f, V/f w/PG and OLV
Note: If b2-01 is set to a smaller value than parameter E1-09 (minimum frequency), then DC Injection Braking will begin as soon as the frequency
falls to the value set to E1-09.
Braking
Time
b2-04
Parameter Details
CLV (A1-02 = 3)
Note: PM motor control modes are not available in A1000 HHP drive models.
For these control modes, parameter b2-01 sets the starting frequency for Zero Speed Control (not position lock) at stop. When the output frequency falls below the setting of b2-01, Zero Speed Control is enabled for the time set in parameter b2-04 provided b1-05 is set to 0.
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
25
1
1.2 b: Application
Zero Speed
E1-09 Min. Frequency b2-01 Zero Speed Level
Output
frequency
Figure 1.13 Zero Speed Control at Stop in CLV and CLV/PM
Note: If b2-01 is set lower than the minimum frequency (E1-09), then Zero Speed Control begins at the frequency set to E1-09.
b2-02: DC Injection Braking Current
n
Control
Time
b2-04
Sets the DC Injection Braking current as a percentage of the drive rated current. The carrier frequency is automatically reduced to 1 kHz when this parameter is set to more than 50%.
No. Name Setting Range Default
b2-02 DC Injection Braking Current 0 to 100% 50%
The level of DC Injection Braking current affects the strength of the magnetic field attempting to lock the motor shaft. Increasing the current level will increase the amount of heat generated by the motor windings. Do not set this parameter higher than the level necessary to hold the motor shaft.
b2-03: DC Injection Braking Time at Start
n
Sets the time of DC Injection Braking (Zero Speed Control in CLV and CLV/PM) at start. Used to stop a coasting motor before restarting it or to apply braking torque at start. Disabled when set to 0.00 s.
No. Name Setting Range Default
b2-03 DC Injection Braking Time at Start 0.00 to 10.00 s 0.00 s
Note: Before starting an uncontrolled rotating motor (e.g., a fan motor driven by windmill effect), use DC Injection or Speed Search to stop the
b2-04: DC Injection Braking Time at Stop
n
motor or detect motor speed before starting it. Otherwise, motor stalling and other faults can occur.
Sets the time of DC Injection Braking (Zero Speed Control in CLV and CLV/PM) at stop. Used to completely stop a motor with high inertia load after ramp down. Increase the value if the motor still coasts by inertia after it should have stopped. Disabled when set to 0.00 s.
No. Name Setting Range Default
b2-04 DC Injection Braking Time at Stop 0.00 to 10.00 s
Determined by
A1-02
26
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
1.2 b: Application
b2-08: Magnetic Flux Compensation Value
n
Sets the magnetic flux compensation at start as a percentage of the no-load current value (E2-03). This function allows for the development of more flux to facilitate starting machines that require high starting torque or motors with a large rotor time constant.
No. Name Setting Range Default
b2-08 Magnetic Flux Compensation Value 0 to 1000% 0%
When a Run command is issued, the DC current level injected into the motor changes linearly from the level set to b2-08 to the level set to E2-03 within the time set to b2-03.
Output frequency
b2-08
E2-03
Magnetizing Current
Reference
Figure 1.14 Magnetic Flux Compensation
b2-03
Time
When b2-08 0%, the current will flow for the time set in b2-03 (DC Injection Braking Time at Start) when DC Injection Braking starts. The current will change linearly from the setting of b2-08 to the setting of E2-03.
The level of the DC current injected to the motor is limited to 80% of the drive rated current or to the motor rated current, whichever value is smaller.
Note: 1. If b2-08 is set below 100%, it can take a relatively long time for flux to develop.
2. If b2-08 is set to 0%, the DC current level will be the DC Injection current set to b2-02.
3. As DC Injection can generate a fair amount of noise, b2-08 may need to be adjusted to keep noise levels acceptable.
u

b3: Speed Search

The Speed Search function allows the drive to detect the speed of a rotating motor shaft that is driven by external forces and start the motor operation directly from the detected speed without first stopping the machine.
Example: When a momentary loss of power occurs, the drive output shuts off and the motor coasts. When power returns, the drive can find the speed of the coasting motor and restart it directly.
Enabling Speed Search for PM motors only requires setting parameter b3-01 to 1.
The drive offers current detection and speed estimation Speed Search for induction motors. Parameter b3-24 selects the speed search method for induction motors. Both methods and relevant parameters are explained below.
Current Detection Speed Search (b3-24 = 0)
n
Current Detection Speed Search detects the motor speed by looking at motor current in IM motors. When Speed Search is started it reduces the output frequency starting from either the maximum output frequency or the frequency reference while increasing the output voltage using the time set in parameter L2-04. As long as the current is higher than the level set to b3-02, the output frequency is lowered using the time constant set to b3-03. If the output current falls below b3-02, the drive assumes that the output frequency and motor speed are the same and accelerates or decelerates to the frequency reference.
Be aware that sudden acceleration may occur when using this method of Speed Search with relatively light loads.
Figure 1.15 illustrates Current Detection Speed Search operation after a momentary power loss (L2-01 must be set to 1 or 2):
Parameter Details
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
1
27
Run command
Output
frequency
Output current
OFF ON
b3-02 (Speed search operation current)
Decel time set
set to b3-03
Waits for twice as long as L2-04
Selected frequency reference
Minimum Baseblock Time (L2-03)
Max. output frequency or the specified frequency reference
1.2 b: Application
AC power
supply
Output frequency
Output current
Output frequency before momentary power loss
OFFON
Min. Baseblock Time (L2-03)
Decel time set to b3-03
b3-05
Waits for twice as long as L2-04
Selected frequency reference
Speed Search operation current set to b3-02
Figure 1.15 Current Detection Speed Search after Power Loss
Note: After power is restored, the drive waits until the time set to b3-05 has passed before performing Speed Search. Thereby the Speed Search
may start not at the end of L2-03 but even later.
When Speed Search is applied automatically with the Run command, the drive waits for the minimum baseblock time set to L2-03 before starting Speed Search. If L2-03 is lower than the time set to parameter b3-05, then b3-05 is used as the wait time.
Figure 1.16 Current Detection Speed Search at Start or Speed Search Command by Digital Input
Notes on Using Current Detection Type Speed Search
• Shorten the Speed Search deceleration time set to b3-03 if an oL1 fault occurs while performing Current Detection Speed Search.
• Current Detection Speed Search is not available when using OLV Control for PM motors.
• Increase the minimum baseblock time set to L2-03 if an overcurrent or overvoltage fault occurs when performing Speed Search after power is restored following a momentary power loss.
Speed Estimation Type Speed Search (b3-24 = 1)
n
This method can be used for a single induction motor connected to a drive. Do not use this method if the motor is one or more frame size smaller than the drive, at motor speeds above 200 Hz, or when using a single drive to operate more than one motor.
Speed Estimation is executed in the two steps described below:
Step 1: Back EMF Voltage Estimation
This method is used by Speed Search after baseblock (e.g., a power loss where the drive CPU continued to run and the Run command was kept active). Here, the drive estimates the motor speed by analyzing the back EMF voltage and outputs the estimated frequency and increases the voltage using the time constant set in parameter L2-04. After that, the motor is accelerated or decelerated to the frequency reference starting from the detected speed. If there is not enough residual voltage in the motor windings to perform the calculations described above, the drive will automatically proceed to step 2.
28
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
AC power
Run command
Output
frequency
Output
current
OFF
ON
b3-02 (Speed search operation current)
Starts at the speed speed that was detected
Waits twice as long as L2-04
Frequency reference set to the drive
Decelerates at the Speed
Search decel time set to b3-03
1.0 s
Min. Baseblock Time (L2-03) <1>
supply
Output
frequency
Output
current
1.2 b: Application
OFFON
Starts at the speed that was detected
Several miliseconds
Selected frequency reference
Min. Baseblock Time
(L2-03)
b3 -05
<1>
Figure 1.17 Speed Search after Baseblock
<1> After AC power is restored, the drive will wait for at least the time set to b3-05. If the power interruption is longer than
the minimum baseblock time set to L2-03, the drive will wait until the time set to b3-05 has passed after power is restored before starting Speed Search.
Step 2: Current Injection
Current Injection is performed when there is insufficient residual voltage in the motor after extended power losses, when Speed Search is applied with the Run command (b3-01 = 1), or when an External search command is used.
This feature injects the amount of DC current set to b3-06 to the motor and detects the speed by measuring the current feedback. The drive then outputs the detected frequency and increases the voltage using the time constant set to parameter L2-04 while looking at the motor current.
The output frequency is reduced if the current is higher than the level in b3-02. When the current falls below b3-02, the motor speed is assumed to be found and the drive starts to accelerate or decelerate to the frequency reference.
<1> The wait time for Speed Search (b3-05) determines the lower limit.
Notes on Using Speed Estimation Speed Search
• Perform Stationary Auto-Tuning for Line-to-Line Resistance (T1-01 = 2). If the there is a change in the cable length between
the drive and motor.
• Use Current Detection to search for speeds beyond 200 Hz if the application is running multiple motors from the same drive
or if the motor is considerably smaller than the capacity of the drive.
• Speed Estimation may have trouble finding the actual speed if the motor cable is very long. Use Current Detection in these
instances.
n
Speed Search Activation
Speed Search can be activated using any of the methods 1 through 5 described below. Select the Speed Search type in parameter b3-24 independent of the activation method.
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Figure 1.18 Speed Search at Start
Parameter Details
1
29
1.2 b: Application
Method 1. Automatically activate Speed Search with every Run command. Set b3-01, Speed Search Selection at Start, to 1 (Enabled). External Speed Search commands are ignored.
Method 2. Activate Speed Search using the multi-function input terminal. Use the input functions for H1-oo in Table 1.17.
Table 1.17 Speed Search Activation by Multi-Function Input Terminal
b3-24 = 1
Setting Description
61
62
External Search Command 1
External Search Command 2
(Current Injection
Method of Speed
Estimation)
Activate Speed Estimation Speed Search
Activate Speed Estimation Speed Search
(Current Detection Speed Search)
Closed: Activate Current Detection Speed Search from the maximum output frequency (E1-04).
Closed: Activate Current Detection Speed Search from the frequency reference.
b3-24 = 0
To activate Speed Search by the multi-function input terminal, the input must be set together with the Run command or the Run command must be entered after giving the Speed Search command.
30
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Loading...
+ 330 hidden pages