List of Dangerous Substances .................................................................................... 63
•
Page 5
Explanation
Illustrated Symbols
Various symbols are used in this safety manual in order to use the unit without
danger of injury and damage of the unit. A list of problems caused by ignoring
the warnings and improper handling is divided as shown below.Be sure that you
understand the warnings and cautions in this manual before operating the unit.
Cautions in Using with Safety
MEANING OF ILLUSTRATED SYMBOLS
WARNING!
CAUTION!
If the warning is ignored, there is the danger of a problem that
may cause a serious accident or even fatality.
If the caution is ignored, there is the danger of a problem that may
cause injury/damage to property or the unit itself.
Meaning of Symbols
This symbol indicates items that urge the warning (including the caution).
A detailed warning message is shown adjacent to the symbol.
This symbol indicates items that are strictly prohibited.
A detailed message is shown adjacent to the symbol with specific actions not to
perform.
This symbol indicates items that should be always performed.
A detailed message with instructions is shown adjacent to the symbol.
1
Page 6
Table of Illustrated Symbols
Warning
Cautions in Using with Safety
Warning,
generally
Caution
Caution,
generally
Caution,
water only
Warning,
high voltage
Caution,
electrical shock
Caution,
deadly poison
Warning,
high temperature
Caution,
Warning,
drive train
Caution,
scald
no road heating
Warning,
explosive
Caution,
not to drench
Prohibit
Prohibit,
generally
Compulsion
Compulsion,
generally
inflammable
Compulsion,
connect to the
Prohibit,
grounding
terminal
to disassemble
Compulsion,
install on a flat
Prohibit,
surface
Prohibit,
to touch
Compulsion,
disconnect the
power plug
Compulsion,
periodical
inspection
2
Page 7
Cautions in Using with Safety
Fundamental Matters of "WARNING!" and "CAUTION!"
WARNING!
Do not use this unit in an area where there is flammable or explosive gas
Never use this unit in an area where there is flammable or explosive gas. This unit is not
explosion-proof. An arc may be generated when the power switch is turned on or off, and
fire/explosion may result. (Refer to page 63 "List of Dangerous Substances".)
Always ground this unit
Always ground this unit on the power equipment side in order to avoid electrical shock due to a power
surge.
If a problem occurs
If smoke or strange odor should come out of this unit for some reason, turn off the power key right
away, and then turn off the circuit breaker and the main power. Immediately contact a service
technician for inspection. If this procedure is not followed, fire or electrical shock may result. Never
perform repair work yourself, since it is dangerous and not recommended.
Do not use the power cord if it is bundled or tangled
Do not use the power cord if it is bundled or tangled. If it is used in this manner, it can overheat and
fire may be caused.
Do not process, bend, wring, or stretch the power cord forcibly
Do not process, bend, wring, or stretch the power cord forcibly. Fire or electrical shock may result.
Substances that can not be used
Never use explosive substances, flammable substances and substances that include explosive or
flammable ingredients in this unit. Explosion or fire may occur. (Refer to page 63 "List of Dangerous
Substances".)
Do not touch high-temperature parts
The inside of the body or the door may become hot during and just after operation. It may cause burns.
CAUTION!
During a thunder storm
During a thunderstorm, turn off the power key immediately, then turn off the circuit breaker and the main
power. If this procedure is not followed, fire or electrical shock may be caused.
3
Page 8
Requirements for Installation
Before Using this unit
WARNING!
1. Always ground this unit
• Be sure to connect the earth wire (the green cable of power cord) to the grounding conductor
or ground terminal to prevent accidents caused by electric leakage.
• Do not connect the earth wire to gas or water pipes. If not, fire disaster may be caused.
• Do not connect the earth wire to the ground for telephone wire or lightning conductor. If not,
fire disaster or electric shock may be caused.
• Do not use a branching receptacle, which may cause the heat generation.
2. Choose a proper place for installation
• Do not install this unit in a place where:
♦ Rough or dirty surface.
♦ Flammable gas or corrosive gas is generated.
♦ Ambient temperature exceeds 35°C.
♦ Ambient temperature fluctuates violently.
♦ There is direct sunlight.
♦ There is excessive humidity and dust.
♦ There is a constant vibration.
• Install this unit on a stable place with the space as shown below.
More than
15cm
More than 15cm
More than
15cm
3. Caution at defrost
• Catch drain from drain hose with a tray at defrost.
Note: The tray is not included in the attachments of unit.
More than 1m
Front side
Drain hose
ドレインホース
水受容器
Tray
4
Page 9
Before Using this unit
Requirements for Installation
4. Do not use this unit in an area where there is flammable or explosive gas
• Never use this unit in an area where there is flammable or explosive gas. This unit is not
explosion-proof. An arc may be generated when the power switch is turned ON or OFF, and
fire/explosion may result. (Refer to page 63 "List of Dangerous Substances".)
改造
5. Do not modify 6. Installation on horizontal surface
• Modification of this unit is strictly
prohibited. This could cause a failure.
• Set this unit to the flattest place. Setting
this unit on rough or slope place could
cause the vibration or noise, or cause the
unexpectible trouble or malfunction.
改造
5
Page 10
Before Using this unit
Requirements for Installation
7. Choose a correct power distribution board or receptacle
• Choose a correct power distribution board or receptacle that meets the unit’s rated electric
capacity.
Electric capacity: IN603: 100V AC 10A, IN803: 100V AC 12A
NOTE)
Starburst connection with a branching receptacle or extended wiring with a cord reel lowers
electrical power voltage, which may cause the degradation of the refrigeration capability or
temperature control performance.
8. Handling of power code
• Do not entangle the power cord. This will cause overheating and possibly a fire.
• Do not bend or twist the power cord, or apply excessive tension to it. This may cause a fire
and electrical shock.
• Do not lay the power cord under a desk or chair, and do not allow it to be pinched in order to
prevent it from being damaged and to avoid a fire or electrical shock.
• Keep the power cord away from any heating equipment such as a room heater. The cord's
insulation may melt and cause a fire or electrical shock.
• If the power cord becomes damaged (wiring exposed, breakage, etc.), immediately turn off the
power at the rear of this unit and shut off the main supply power. Then contact your nearest
dealer for replacement of the power cord. Leaving it may cause a fire or electrical shock.
• Connect the power plug to the receptacle which is supplied appropriate power and voltage.
9. Before/after installing
• It may cause injure to a person if this unit falls down or moves by the earthquake and the
impact. etc..To prevent, take measures that the unit cannot fall down, and not install to busy
place.
6
Page 11
When Using the Unit
Before Using this unit
CAUTION!
1. Do not use explosive or flammable substance
• Never use explosive substances, flammable substances and substances that include
explosive or flammable ingredients in this unit. Explosion or fire may occur.
Flammable
or explosive
substance
2. Do not make an overload 3. Do not set samples in close formation
• The withstand load of shelf is 15kg
(uniform load)Set the samples apart
each other.
• The temperature in furnace cannot be
controlled if too much samples are set
there. Make sure to use the shelf and
set samples apart each other so as to
make the free space of 30% or more to
the furnace to acquire accuracy of
temperature.
Samples
15Kg
Shelf
4. Notes for some kind of sample
• Stainless steel SUS304 is used for interior; however, it may be corroded by strong acid etc.
And the door packing made of rubber may be corroded by some kind of solvent, e.g. alkaline,
oil, halogen etc.
• Much frost on the evaporator degrades the refrigeration capability, which may cause
uncontrollability of setting temperature. Be careful, especially, to treat samples with large
water content that generate much frost. Perform the defrost operation if frost is observed
through the frost inspection window.
• The equipment with large heat load cannot be used because the temperature in furnace
increases.
Make the free space of 30% or more
7
Page 12
Before Using this unit
Defrost in Refrigerator
Much frost on the evaporator degrades the refrigeration capability, which may cause
uncontrollability of setting temperature. In the IN602 or IN802, the condition of frost on the
evaporator can be checked through the frost inspection window inside furnace. The frosting speed
varies depending on the following conditions.
1) Temperature used・・・・・・・・・・・・・・Easily frosted when using the unit in low temperature
2) External temperature/humidity・・・Easily frosted when external temperature/humidity is higher
3) Sample in furnace・・・・・・・・・・・・・・Easily frosted when sample contains much water
The following operations can be set to take measure against frosting in the IN603 or IN803. Set
either of them depending on the situation. The fixed temperature and program operation are
available there by pressing the DEFROST key on the operation panel, in addition to the program
operation.
① Manual defrost operation (manual start/automatic stop):
Perform the defrost operation if much frost is in the evaporator. Temperature control is suspended in
addition to stop of heater and blast fan during operation. The operation is started manually and
stopped automatically with the built-in timer after 5-minute operation.
→Refer to the page 46 for the operating instructions.
② Cycle defrost operation (Automatic start/stop):
Set the cycle defrost operation to operate the unit effectively for long term. The unit can repeat the
defrost operation and operation stop automatically at specified interval specified previously. Frost
can be usually removed to perform the cycle defrost operation for ten minutes in a day. The amount
of frost varies depending on the conditions. Set it appropriately. Temperature control is suspended in
addition to stop of heater and blast fan during operation.
→Refer to the page 47 for the operating instructions.
CAUTION!
• The temperature in furnace increases about 3℃ at the defrost operation. Be careful if it affects the
samples. The indicated temperature may increase more than 10℃ at that time.
③ Setting of refrigeration operation mode in refrigerator (continuous/cycle):
Generation of frost can be reduced by setting the cycle operation where the refrigerator repeats
operation and halt. The refrigerator operation mode has a function to set the refrigerator to
continuous operation, cycle operation or halt condition. The refrigerator repeats 12-minute operation
and 12-minute halt condition in the cycle operation. If the setting temperature is 10℃ or below, it
switches automatically to the continuous operation related to the refrigeration capacity. The
refrigerator does not work regardless of setting temperature if it is set to be stopped. Set the
continuous operation when considering the accuracy of temperature control important, and set the
cycle operation when reducing the mount of frost at long term operation (the accuracy of temperature
control lower than that in the continuous operation). The cycle operation can also prevent the
samples from drying. Set the refrigerator stop if it is not necessary to be operated (it automatically
stops if the setting temperature is 44℃ or above).
→Refer to the page 49 for the operating instructions.
CAUTION!
• The frosting amount varies depending on the conditions in use even the cycle operation is set. It may
be larger when operating the refrigerator for long term. In this case, defrost the refrigerator by
performing the defrost operation or cycle defrost operation.
8
Page 13
Main Unit
IN603
Magnetic packing
Front view
Inner door
Description and Function of Each Part
Production plate
Shelf
Shelf bracket
Cable port
Specification plate
Independent overheating
prevention device
Rear view
Control panel
Power switch
(Earth leakage breaker)
Power cord
Power plug
9
Page 14
Main Unit
IN803
Front view
Magnetic packing
Description and Function of Each Part
Independent overheating
prevention device
Control panel
Power switch
(Earth leakage breaker)
Shelf bracket
Production plate
Cable port
Inner door
Shelf
Specification plate
Power plug
Rear view
Power cord
10
Page 15
Structure Chart
IN603
棚板
Shelf
Door packing
扉パッキン
Inner door
内扉
Description and Function of Each Part
ファン
Fan
Temperature
温 度
sensor
センサ
Heater
ヒータ
Evaporator
蒸発器
Frost checking
霜観測窓
window
Condenser
コンデンサ
Control panel
コントローラ操作パネル
Compressor
コンプレッサ
11
Page 16
Structure Chart
IN803
Shelf
棚板
コントローラ
Control panel
操作パネル
Door packing
扉パッキン
Inner door
内扉
Description and Function of Each Part
ファン
Fan
温度センサ
Temperature sensor
(Pt&K ダブルセンサ)
(Pt&K double sensor)
Heater
ヒータ
Frost checking
霜観測窓
window
Evaporator
蒸発器
コンデンサ
Condenser
Compressor
コンプレッサ
12
Page 17
Y
Control Panel
5
FIXED TEMP
6
7
8
9
10
11
12
AUTO STOP
AUTO START
PROGRAM
STANDB
END
HEATER
REFRIGE
1
FUNCTION PROGRAM
Description and Function of Each Part
3 4
DEFROST
POWER
℃
MENU
2
TROUBLE
ENTER
CANCEL
1
Main Display:
2
Sub Display:
3
TROUBLE Lamp:
4
DEFROST key:
5
FIXED TEMP lamp:
6
AUTO STOP Lamp:
7
AUTO START Lamp:
8
PROGRAM Lamp:
9
STANDBY Lamp:
10
END Lamp:
11
HEATER Lamp:
12
REFRIGE Lamp:
13
14 15
16
17
18
19
20
Displays the measured temperature and error code.
Displays the operation and setting information.
Blinks when a trouble occurs.
Starts/stops the defrost operation.
Lights while the fixed temperature operation is running.
Blinks while the choosing operation mode.
Lights while the auto stop operation is running.
Blinks while choosing the operation mode.
Lights while the auto start operation is running.
Blinks while choosing the operation mode.
Lights while the program operation is running.
Blinks while choosing the operation mode.
Lights while the device is in standby state.
Blinks while the device is in startup wait state.
Blinks at end of the autostop or program operation.
Lights while the heater works.
Lights while the refrigerator works.
13
FUNCTION Key:
14
PROGRAM Key:
15
MENU Key:
16
▼(Down) Key:
17
▲(Up) Key:
18
ENTER Key:
19
CANCEL Key:
20
POWER Key:
Starts the function menu.
Starts the program menu.
Starts the operation menu.
Lowers down the setting value.
Rises up the setting value.
Settles the inputted value/item.
Cancels the current inputting.
Turns ON/OFF the power.
13
Page 18
Operation Method
Key Operation Chart of Mode Setting and Program Registering
14
Page 19
Operation Method
Operation Mode and Function List
The operation mode consists of the following four modes.
No. Name Description Page
1. Fixed Temperature Operation
2. Auto Stop Operation
3. Auto Start Operation
4. Program Operation
The function menus are listed below.
Name Function Page
Date/Time
Timer Mode
Operation Start Signal Input Mode
Operation Stop Signal Input Mode
Key Lock Mode
Buzzer Mode
Calibration Offset
Integrating Operation Time
Controls temperature with fixed temperature. 16
Stops operation at specified time. 19
Starts operation at specified time. 22
Starts program operation at specified time. 24
Sets date and time. 38
Sets timer mode. 39
Sets operation start signal input mode. 40
Sets operation stop signal input mode. 41
Sets key lock mode. 42
Sets buzzer mode. 43
Sets calibration offset temperature. 45
Displays integrating operation time. 46
Defrost Operation Mode
Cycle Defrost Operation Time
Refrigerator Operation Mode
Communication Lockout Mode
Operation start signal input mode:
When it is set to on, the unit starts operation after it receives the operation start signal in each mode.
Operation stop signal input mode:
When it is set to on, the unit stops operation after it receives the operation stop signal during operation in
each mode.
Sets defrost operation mode of refrigerator. 47
Sets cycle defrost operation time of refrigerator. 48
Sets operation mode of refrigerator. 49
Sets communication lockout mode. 50
15
Page 20
Operation Method
Fixed Temperature Operation
Start the operation from turning on the power shown in the figure, and continue the operation
under the setting temperature unless turning off the power.
SV
Setting of the Fixed Temperature Operation
Turn on the power
1
FIXED TEMP
AUTO STOP
AUTO START
PROGRAM
STANDBY
END
HEATER
REFRIGE
FUNCTION PROGRAM
▲
START
t
▲
STOP
• Turn on the power switch of the unit (earth leakage
breaker). Pressing the POWER key turns on the
POWER
power. The Main Display indicates the
temperature in furnace. The Sub Display
indicates "Standby" and the STANDBY lamp lights
on. (Hereafter, this state is called the "standby
state".)
℃
MENU ENTER
Standby
2002/01/01 12:00
TROUBLE
CANCEL
DEFROST
POWER
SV: Setting temperature
t: Time
Select operation mode
2
FIXED TEMP
AUTO STOP
AUTO START
PROGRAM
STANDBY
END
HEATER
FUNCTION PROGRAM
REFRIGE
MENU
Fixed TEMP OPR
Select OPR mode
℃
MENU ENTER
① Pressing the MENU key displays the operation
mode selection screen.
② The Sub Display on the operation mode selection
screen displays the name of operation mode
currently selected with blinking. The
corresponding operation mode lamp blinks at the
same time.
TROUBLE
CANCEL
DEFROST
③ Keep pressing the MENU key until the fixed
temperature operation mode is displayed.
POWER
④ Press the ENTER key. The fixed temperature
operation mode is decided.
The fixed temperature operation is selected at the
initial setting of unit. The operation mode carried
out last is selected in case other than it.
16
Page 21
Fixed Temperature Operation
Set temperature
3
FIXED TEMP
AUTO STOP
AUTO START
PROGRAM
STANDBY
END
HEATER
REFRIGE
FIXED TEMP
AUTO STOP
AUTO START
PROGRAM
STANDBY
END
HEATER
REFRIGE
4
Start operation
FIXED TEMP
AUTO STOP
AUTO START
PROGRAM
STANDBY
END
HEATER
REFRIGE
FUNCTION PROGRAM
FUNCTION PROGRAM
FUNCTION PROGRAM
Set TEMP 0.0
Fixed TEMP OPR
℃
MENU ENTER
Set TEMP 37.0
Fixed TEMP OPR
℃
MENU ENTER
Set TEMP 37.0
Fixed TEMP OPR
℃
MENU ENTER
℃↑
℃
TROUBLE
CANCEL
℃
TROUBLE
CANCEL
TROUBLE
CANCEL
Operation Method
① The setting temperature input screen is
displayed. The Sub Display indicates "Set
DEFROST
POWER
DEFROST
POWER
DEFROST
POWER
TEMP" and the numeric character that indicates
temperature blinks.
② Set the temperature using the "▲▼".
③ Press the ENTER key to decide the temperature
and start the fixed temperature operation.
CAUTION!
The refrigerator operation can not be performed
again for five minutes just after an operation stop.
The refrigerator has been in the standby state and
the REFRIGE lamp blinks during the period.
① The blinking FIXED TEMP lamp lights on when
the fixed temperature operation starts. The unit
starts to control temperature according to the
setting temperature. The HEATER lamp lights
on when the heater is on and The REFRIGE lamp
lights on when the refrigerator is on.
② The Sub Display displays the setting temperature.
The arrow which indicates the state of
temperature control is also displayed with
blinking. The direction of arrow shows as
follows depending on the relation between the
setting temperature at operation start and that in
furnace.
POWER
Set TEMP
2002/01/01 12:00
37.0℃↑
(When setting temperature is
higher than temperature in
furnace)
Set TEMP
2002/01/01 12:00
37.0℃↓
(When setting temperature is
lower than temperature in
furnace)
③ The direction of arrow shows as shown below
when the temperature in furnace reaches to
within ±1.0℃ of setting temperature.
Set TEMP
2002/01/01 12:00
(When temperature in furnace
reaches to around setting
temperature)
37.0℃→
④ Press the POWER key to stop operation.
17
Page 22
Fixed Temperature Operation
Operation Method
Vary the temperature
5
FIXED TEMP
AUTO STOP
AUTO START
PROGRAM
STANDBY
END
HEATER
FUNCTION PROGRAM
FUNCTION PROGRAM
FUNCTION PROGRAM
AUTO START
AUTO START
REFRIGE
FIXED TEMP
AUTO STOP
PROGRAM
STANDBY
HEATER
REFRIGE
FIXED TEMP
AUTO STOP
PROGRAM
STANDBY
HEATER
REFRIGE
END
END
Set TEMP 37.0
Fixed TEMP OPR
℃
MENU ENTER
Set TEMP 30.0
Fixed TEMP OPR
℃
MENU ENTER
Set TEMP 30.0
2002/01/01 12:00
℃
MENU ENTER
℃↑
① Make the setting temperature blinking using the "
℃
TROUBLE
CANCEL
DEFROST
POWER
▲▼" during the fixed temperature operation.
② Vary the temperature using the "▲▼".
℃
TROUBLE
DEFROST
CANCEL
POWER
③ Press the ENTER key to decide the temperature.
CANCEL
TROUBLE
DEFROST
POWER
The fixed temperature operation continues under
the new setting temperature.
18
Page 23
r
r
Operation Method
Auto Stop Operation
As shown in the following figure, the device stops operating automatically by setting the timer.
Set time
▼
SV: Setting temperature
t: Time
SV
Waiting
Operation
Activate time
Start operation (manual) Stop operation (auto)
Setting of the Auto Stop Operation
Turn on the power
1
POWER
FIXED TEMP
AUTO STOP
AUTO START
PROGRAM
STANDBY
END
HEATER
FUNCTION PROGRAM
REFRIGE
Select operation mode
2
FIXED TEMP
AUTO STOP
AUTO START
PROGRAM
STANDBY
END
HEATER
FUNCTION PROGRAM
REFRIGE
Standby
2002/01/01 12:00
℃
MENU ENTER
MENU
Auto-stop OPR
Select OPR mode
℃
MENU ENTER
TROUBLE
CANCEL
TROUBLE
CANCEL
period
DEFROST
POWER
DEFROST
POWER
t
• Turn on the power switch of the unit (earth leakage
breaker). Pressing the POWER key turns on the
power. The Main Display indicates the
temperature in furnace. The Sub Display
indicates "Standby" and the STANDBY lamp lights
on.
① Pressing the MENU key displays the operation
mode selection screen.
② The Sub Display on the operation mode selection
screen displays the name of operation mode
currently selected with blinking. The
corresponding operation mode lamp blinks at the
same time.
③ Keep pressing the MENU key until the auto stop
operation mode is displayed.
④ Press the ENTER key. The auto stop operation
mode is decided.
The fixed temperature operation is selected at the
initial setting of unit. The operation mode carried
out last is selected in case other than it.
19
Page 24
Auto Stop Operation
Operation Method
Set temperature and operation period/stop
3
time.
AUTO START
AUTO START
FIXED TEMP
AUTO STOP
PROGRAM
STANDBY
HEATER
REFRIGE
FIXED TEMP
AUTO STOP
PROGRAM
STANDBY
HEATER
REFRIGE
END
END
FUNCTION PROGRAM
FUNCTION PROGRAM
Set TEMP 0.0
Auto-stop OPR
℃
MENU ENTER
Set TEMP 37.0
Auto-stop OPR
℃
MENU ENTER
℃
TROUBLE
CANCEL
℃
TROUBLE
CANCEL
① The setting temperature input screen is
DEFROST
displayed. The Sub Display indicates "Set
TEMP" and the numeric character that indicates
POWER
temperature blinks.
② Set the temperature using the "▲▼".
③ Press the ENTER key to decide the temperature.
DEFROST
④ The operation period/stop time input screen is
POWER
displayed after the setting temperature is
decided.
Display the period/time using the "▲▼".
Input the operation period when the setting of
timer mode shows "Time". Input the operation
stop time when it shows "Clock".
OPR time30min
Auto-stop OPR
(Operation period
edition screen)
Stop time 13:00
Auto-stop OPR
(Operation stop time
edition screen)
• The display style of operation period varies
depending on the range of time to be displayed.
Time Range Indication
0minute to 59minutes
1hour to
99hours59minutes
0min to 59min
1h00m to 99h59m
• The input range of operation stop time is always
from 0:00 to 23:59.
Pressing the CANCEL key quit the setting of auto
stop operation.
20
Page 25
Auto Stop Operation
4
Start operation
FIXED TEMP
AUTO STOP
AUTO START
PROGRAM
STANDBY
HEATER
REFRIGE
END
FUNCTION PROGRAM
Set TEMP 37.0
Stop in
℃
MENU ENTER
Operation Method
℃↑
30min
CANCEL
TROUBLE
① Press the ENTER key to decide the setting and
DEFROST
the auto stop operation starts. The blinking
AUTO STOP lamp lights on and the Sub Display
POWER
displays the setting temperature and residual time
to operation stop.
② The countdown of timer is suspended when the
temperature in furnace is out of the range of
"within ± 1℃ to the setting temperature". In
this case, the Sub Display displays "Wait" with
blinking. The time display on the right side of
"Wait" shows the total waiting time in operation.
AUTO START
FIXED TEMP
AUTO STOP
PROGRAM
STANDBY
HEATER
REFRIGE
END
FUNCTION PROGRAM
Stop time
2002/01/01 12:30
℃
MENU ENTER
Set TEMP
Wait 1min
(Waiting screen)
37.0℃↑
③ The operation stops when the residual time
TROUBLE
CANCEL
DEFROST
POWER
counts zero. The END lamp blinks and the Sub
Display displays the operation finish time when
the operation stops.
The wait function is not activated when the auto stop
operation is carried out with "Clock" mode. The
operation stops at specified time.
④ Press the POWER key to quit operation.
21
Page 26
r
S
Operation Method
Auto Start Operation
As shown in the following figure, this mode is applied to the device for starting the operation after
the specified time (hours) automatically. Note that the device does not stop the operation
automatically. Stop the operation by manual without fail.
V
Activate controller (Manual)
Setting of the Auto Start Operation
Set time
▼
Activate Timer
Start operation (Auto)
SV: Setting temperature
t: Time
t
Turn on the power
1
FIXED TEMP
AUTO STOP
AUTO START
PROGRAM
STANDBY
END
HEATER
FUNCTION PROGRAM
REFRIGE
Select operation mode
2
FIXED TEMP
AUTO STOP
AUTO START
PROGRAM
STANDBY
END
HEATER
FUNCTION PROGRAM
REFRIGE
POWER
Standby
2002/01/01 12:00
℃
MENU ENTER
MENU
Auto-start OPR
Select OPR mode
℃
MENU ENTER
• Turn on the power switch of the unit (earth leakage
breaker). Pressing the POWER key turns on the
power. The Main Display indicates the
temperature in furnace. The Sub Display
indicates "Standby" and the STANDBY lamp lights
TROUBLE
CANCEL
DEFROST
POWER
on.
① Pressing the MENU key displays the operation
mode selection screen.
② The Sub Display on the operation mode selection
screen displays the name of operation mode
currently selected with blinking. The
corresponding operation mode lamp blinks at the
same time.
③ Keep pressing the MENU key until the auto start
operation mode is displayed.
TROUBLE
CANCEL
④ Press the ENTER key. The auto start operation
DEFROST
mode is decided.
The fixed temperature operation is selected at the
POWER
initial setting of unit. The operation mode carried
out last is selected in case other than it.
22
Page 27
Auto Start Operation
Operation Method
Set temperature and start wait period/time
3
AUTO START
AUTO START
FIXED TEMP
AUTO STOP
PROGRAM
STANDBY
HEATER
REFRIGE
FIXED TEMP
AUTO STOP
PROGRAM
STANDBY
HEATER
REFRIGE
END
END
FUNCTION PROGRAM
FUNCTION PROGRAM
Set TEMP 0.0
Auto-start OPR
℃
MENU ENTER
Set TEMP 37.0
Auto-start OPR
℃
MENU ENTER
℃
TROUBLE
CANCEL
℃
TROUBLE
CANCEL
① The setting temperature input screen is
DEFROST
displayed. The Sub Display indicates "Set
TEMP" and the numeric character that indicates
POWER
temperature blinks.
② Set the temperature using the "▲▼".
③ Press the ENTER key to decide the temperature.
DEFROST
④ The operation start wait period/time input screen
POWER
is displayed after the setting temperature is
decided.
Display the operation start wait period/time using
the "▲▼".
Input the operation start wait period when the
setting of timer mode shows "Time". Input the
operation start time when it shows "Clock".
Wait ST 30min
Auto-start OPR
(Operation start wait
period edition screen)
Start Time 13:00
Auto-start OPR
(Operation start time
edition screen)
• The display style of operation start wait period
varies depending on the range of time to be
displayed.
Time Range Indication
Start operation
4
FIXED TEMP
AUTO STOP
AUTO START
PROGRAM
STANDBY
END
HEATER
REFRIGE
FIXED TEMP
AUTO STOP
AUTO START
PROGRAM
STANDBY
END
HEATER
REFRIGE
FUNCTION PROGRAM
FUNCTION PROGRAM
Set TEMP 100
Start in
℃
MENU ENTER
Set TEMP 37.0
2002/01/01 12:30
℃
MENU ENTER
30min
℃↑
0minute to 59minutes
1hour to
99hours59minutes
0min to 59min
1h00m to 99h59m
• The input range of operation start time is always
from 0:00 to 23:59.
Pressing the CANCEL key quit the setting of auto
start operation.
① Press the ENTER key to decide the operation
℃
TROUBLE
CANCEL
DEFROST
POWER
start wait period/time. The unit enters to auto
start operation wait state. The blinking AUTO
START lamp lights on and the STANDBY lamp
blinks instead in this state. The Sub Display
displays the setting temperature and residual
time to operation start.
② The operation starts when the residual time
CANCEL
TROUBLE
DEFROST
POWER
counts zero. The STANDBY lamp lights off and
the Sub Display displays the same subject as in
the fixed temperature operation after the
operation starts.
③ Press the POWER key to cancel or quit the wait
state.
23
Page 28
Operation Method
Program Operation
As shown in the figure, this mode is used for running the device under the setting program.
(Temperature)
Start pv
Step1Step2 Step3 Step4Step5Step6 Step7 Step8
Setting of the Program Operation
Turn on the power
1
POWER
AUTO START
FIXED TEMP
AUTO STOP
PROGRAM
STANDBY
HEATER
REFRIGE
END
FUNCTION PROGRAM
Standby
2002/01/01 12:00
℃
MENU ENTER
TROUBLE
CANCEL
Setting
temperature
End program Start program
• Turn on the power switch of the unit (earth leakage
breaker). Pressing the POWER key turns on the
power. The Main Display indicates the
temperature in furnace. The Sub Display
indicates "Standby" and the STANDBY lamp lights
on.
DEFROST
POWER
(Time)
Program registration using PROGRAM key is necessary before starting program operation.
Select operation mode
2
MENU
① Pressing the MENU key displays the operation
mode selection screen.
② The Sub Display on the operation mode selection
screen displays the name of operation mode
currently selected with blinking. The
corresponding operation mode lamp blinks at the
same time.
③ Keep pressing the MENU key until the program
operation mode is displayed.
④ Press the ENTER key. The program operation
mode is decided.
The fixed temperature operation is selected at the
initial setting of unit. The operation mode carried
AUTO START
FIXED TEMP
AUTO STOP
PROGRAM
STANDBY
HEATER
REFRIGE
END
FUNCTION PROGRAM
Program OPR
Select OPR mode
℃
MENU ENTER
TROUBLE
CANCEL
DEFROST
POWER
out last is selected in case other than it.
24
Page 29
Program Operation
Operation Method
Set step number and start wait period/
3
time
FIXED TEMP
AUTO STOP
AUTO START
PROGRAM
STANDBY
HEATER
REFRIGE
END
FUNCTION PROGRAM
First step S01
Program OPR
℃
MENU ENTER
TROUBLE
CANCEL
① The initiating step input screen is displayed.
DEFROST
The Sub Display displays "First step" and the
step number blinks.
POWER
② Select the step number using the"▼▲" and then
check it using the ENTER key.
The "steps that are not set" and "step within repeat"
are not displayed. If no program is registered (no
steps are used), the buzzer sounds with a message
on the Sub Display. In this case, register program
using the PROGRAM key and start the step again.
NO program
Registered
(Display in case no program
is registered)
③ The operation start wait period/time input screen
is displayed after the step number is decided.
Display the operation start wait period/time using
the "▲▼".
Input the operation start wait period when the
setting of timer mode shows "Time". Input the
operation start time when it shows "Clock".
Wait ST 30min
Program OPR
(Operation start wait
period edition screen)
Start Time 13:00
Program OPR
(Operation start time
edition screen)
Pressing the CANCEL key quit the setting of auto
start operation.
25
Page 30
Program Operation
Operation Method
Start operation
4
FIXED TEMP
AUTO STOP
AUTO START
PROGRAM
STANDBY
END
HEATER
REFRIGE
FIXED TEMP
AUTO STOP
AUTO START
PROGRAM
STANDBY
END
HEATER
REFRIGE
FUNCTION PROGRAM
FUNCTION PROGRAM
Step
Start in
℃
MENU ENTER
Set TEMP 37.0
Step
℃
MENU ENTER
S01
30min
℃↑
S01
CANCEL
CANCEL
TROUBLE
TROUBLE
① Press the ENTER key to decide the operation
DEFROST
start wait period/time. The unit enters to
program operation wait state. The blinking
POWER
PROGRAM lamp lights on and the STANDBY
lamp blinks instead in this state. The Sub
Display displays the step number and residual
time to operation start.
② The operation starts when the residual time
DEFROST
counts zero. The STANDBY lamp lights off and
the Sub Display displays the executing step
POWER
number and the setting temperature after the
operation starts.
③ The following screens are displayed in sequence
during operation.
Set TEMP
Step S01
(Executing step number)
Set TEMP
37.0℃↑
↓
37.0℃↑
Remain 15min
(Remaining time)
↓
Set TEMP
Rep. count 10
37.0℃↑
(Residual count of repeat:
displayed during repeat only)
↓
Set TEMP
Wait 5min
37.0℃↑
(Waiting state: displayed
FIXED TEMP
AUTO STOP
AUTO START
PROGRAM
STANDBY
END
HEATER
FUNCTION PROGRAM
REFRIGE
Stop time
2002/01/01 12:30
℃
MENU ENTER
④ The END lamp blinks and the Sub Display
TROUBLE
CANCEL
DEFROST
POWER
displays the operation finish time when the
operation stops.
⑤ Press the POWER key to cancel the operation or
quit the wait state.
during wait only)
26
Page 31
Input Program
Select program function
1
• Check that the power in turned on.
PROGRAM
Select step S01
Program OPR
ENTER
TROUBLE
CANCEL
Operation Method
① Press the PROGRAM key. The program menu
starts and step number selection screen is
displayed.
Press the "▼▲". The registered step numbers
and the smallest number of un-used step are
displayed in sequence. Select the step number
among them.
The "S01" is displayed when no program is
registered. In this case, the "▼▲" are invalid.
② Press the ENTER key. The selected step
number is decided and the setting item selection
screen is displayed. The "Set TEMP" is
displayed first.
③ Press the CANCEL key to cancel the program
menu.
Edit step
2
• The following four setting items are included in a step.
Setting item Setting range
Setting temperature
Setting time
Repeat initiating step
Repeat count
Setting temperature range by product type
0 minute to 999 hour and 59 minutes, End
None, Registered step numbers 1 to 32
1 to 9999, Infinity
• The unit operates with fixed rate inclination if the "START TEMP" and the "Set Temp" are different.
It enters into "Wait" if the temperature does not reach to the setting temperature within a setting
time.
TEMP
.
Set Temp.
START
.
TEMP
.
Set Time
(Operation with fixed rate inclination)
TIME
27
Page 32
Operation Method
Input Program
2
• The temperature is kept constant till the end of setting time when the "START TEMP" and the "Set
Temp" are the same. The unit enters into "Wait" and measurement of residual time is suspended
when the temperature in furnace is within ±1℃ to the setting temperature.
TEMP.
START
TEMP
.
.
Set Time
Set Temp.
TIME
• The unit operates with full-power from the "START TEMP" to the "Set Temp" when the period is set
to 0 minute. It keeps the "Wait" state until the temperature in furnace is within ±1℃ to the
setting temperature.
START
TEMP
TEMP.
Reached time to the set temp.
.
.
Waiting
Set Temp.
TIME
• The conception of repeat is shown in the figure below. The first operation of repeat interval is not
counted as a repeat count.
Step No. S01
No rep eat
instruction
Step N o. S02
No repeat
instru cti on
Step N o. S03
No repeat
instru cti on
5 repe ati ng
of in ter val
Step No. S04
Start step: S02
Repeat times : 5
Step N o. S05
No repeat
instru cti on
28
Page 33
Operation Method
Input Program
2
① After the step number is decided, the setting item selection screen is displayed. Select the
items on the Sub Display using the PROGRAM key.
No. Item Sub Display Notes
1
Setting
temperature
Set TEMP
S01
Set time 0min
2 Setting time
S01
3
initiating step
Repeat
Rep. start S01
S01
Rep. count5
4 Repeat count
S01
Insert step
5 Step insertion
S01
Delete step
6 Step deletion
S01
Program End
7 Program end
S01
The step number currently edited is displayed on the lower column of Sub Display. The details for all
registered steps in use are displayed followed by all un-used steps.
The "Set TEMP" for the next step follows the "Program End". The screen, in this way, displays the
details of respective steps in sequence. The unused steps are displayed at the end if other steps are
used. The display "un-used" is added at the end of step number displayed in the lower column of
Sub Display for un-used steps. All steps subsequent to the step with "un-used" are un-used steps.
37.0℃
Add a new step at the position of step
currently referred to. The sequence number
of each step hereafter increases by one.
Delete the step currently referred to. The
sequence number of each step hereafter
decreases by one.
Complete program registration/edition.
• The setting items are not displayed on the screen depending on the setting conditions shown
below.
Setting item Not displayed in the following condition
Setting temperature
Repeat initiating step
Repeat count
Step insertion
It is impossible to change the content of program currently operated. Checking it is possible.
Not displayed when the setting time is set to "End".
Not displayed when the period is set to "End" or when the
other step is inserted in the specified repeat interval.
Not displayed when the repeat initiating step is not
displayed, or "No" is set.
Not displayed when steps are left.
29
Page 34
Operation Method
Input Program
2
② Select the "Set TEMP" and press the ENTER key. The temperature setting edition screen is
displayed. The blinking "
" (cursor) goes out and the setting value blinks instead.
ENTER
Set TEMP
S01
(Selection screen)
► 30.0℃
→
Set TEMP
S01
(Edition screen)
30.0℃
③ Select the temperature using "▼▲" and press the ENTER key. The setting is decided and the
screen returns to the setting item selection screen.
Set TEMP 37.0℃
S01
TROUBLE
Set TEMP 37.0℃
S01
TROUBLE
→
CANCEL
ENTER
(Decide the input) (Selection screen)
④ Press the CANCEL key to cancel the input. The value is cancelled and the screen returns to the
setting item selection screen.
ENTER
CANCEL
Set time 45min
S01
TROUBLE
Set time 30min
S01
TROUBLE
→
CANCEL
ENTER
(Cancel the input) (Selection screen)
ENTER
CANCEL
30
Page 35
Operation Method
Input Program
Insert step into the position currently displayed
3
① Display the "Insert step" on the setting item selection screen and then press the ENTER key.
The screen returns to the setting item selection screen and the setting temperature of inserted
step is displayed.
The "Insert step" is not displayed if no steps are left.
S01
Insert step
TROUBLE
Set TEMP 0.0℃
S01
TROUBLE
→
CANCEL
ENTER
(Decide the input) (Selection screen)
The initial settings below are set in the newly inserted step. The settings of "un-used" steps displayed
at the end of "Select step" are the same as that listed below.
Item Initial setting
Setting temperature
0℃
Setting time 0 minute
Add step at the end of program
4
Repeat initiating stepNo
① Display the setting of un-used step on the setting item selection screen and then press the
ENTER key.
ENTER
CANCEL
Set TEMP 0.0℃
S23(un-used)
ENTER
CANCEL
TROUBLE
The "SO1" (the first step) indicates "un-used" at the first registration of program.
The items other than "Insert step", "Delete step" and "End program" can be set.
The "un-used" steps are not displayed if no steps are left.
② Change the setting value and press the ENTER key.
③ The indication "un-used" on the lower column of Sub Display goes out.
Set TEMP
S23
► 0.0℃
31
Page 36
Operation Method
Input Program
Delete step currently displayed
5
• Check that any program is registered.
① Select the "Delete step" and press the ENTER key.
Delete step
S01
ENTER
Pressing the "CANCEL key before pressing the ENTER quit the deletion.
End program edition
6
① Select the "Program End" on the setting item selection screen and press the ENTER key. The
edited program is saved and the edition is completed.
CANCEL
TROUBLE
Program End
S01
ENTER
CANCEL
TROUBLE
Cancel edited program
7
• Press the CANCEL key on the step number selection screen to cancel the edited program,
including insertion, deletion and addition of step.
• Press the CANCEL key on the setting item selection screen to return to the step number selection
screen. Press it again to cancel the edited program.
32
Page 37
Program Creation Example
• The program pattern below is explained as an example.
Press the PROGRAM key to display the step number selection
1
S04 - End - -
screen.
50.0℃
20.0℃
℃-10.0
30min No -
0min No -
15min S02 1
Operation Method
Select step S01
Program OPR
TROUBLE
Display "SO1" using the "▼▲".
2
Press the ENTER key to display the "Set TEMP".
3
Press the ENTER key to display the setting temperature edition
4
screen. The cursor goes out and the setting temperature blinks.
Set the temperature to 50℃ using the "▼▲".
5
Press the ENTER key to decide the temperature.
6
Press the PROGRAM key to display the "Set time" selection
7
screen.
CANCEL
ENTER
Select step S01
Program OPR
Set TEMP
S01
Set TEMP
S01
Set TEMP
S01
Set TEMP
S01
Set time ► 0min
S01
► 0.0℃
0.0℃
50.0℃
► 50.0℃
Press the ENTER key to display the setting period edition screen.
8
The cursor goes out and the setting period blinks.
Set the period to 30 min using the "▼▲".
9
Press the ENTER key to decide the period.
10
33
Set time 0min
S01
Set time 30min
S01
Set time ► 30min
S01
Page 38
Program Creation Example
Press the PROGRAM key to display the "Rep. start".
11
Operation Method
Rep. start ► No
Press the ENTER key to display the repeat initiating step edition
12
screen. The cursor goes out and the setting for repeat initiating
step blinks.
Set the "No" using the "▼▲".
13
Press the ENTER key to decide the setting.
14
Press the PROGRAM key until the "Set TEMP" in the Step 2 is
15
displayed. The display on the lower column changes from "S01"
to "S02"or to "SO2 (un-used)".
Press the ENTER key to display the setting temperature edition
16
screen. The cursor goes out and the setting temperature blinks.
Set the temperature to 20℃ using the "▼▲"
17
S01
Rep. start No
S01
Rep. start ► No
S01
Rep. start ► No
S01
Set TEMP
S02
Set TEMP
S02
Set TEMP
S02
► 0.0℃
0.0℃
20.0℃
Press the ENTER key to decide the temperature.
18
Press the PROGRAM key to display the "Set time" selection
19
screen.
Press the ENTER key to display the setting period edition screen.
20
The cursor goes out and the setting period blinks.
Set the period to 0 min using the "▼▲".
21
Press the ENTER key to decide the period.
22
Press the PROGRAM key to display the "Rep. start".
23
Press the ENTER key to display the repeat initiating step edition
24
screen. The cursor goes out and the setting for repeat initiating
step blinks.
Set TEMP
S02
Set time ► 0min
S02
Set time 0min
S02
Set time 0min
S02
Set time ► 0min
S02
Rep. start ► No
S02
Rep. start No
S02
► 20.0℃
34
Page 39
Program Creation Example
Set the "No" using the "▼▲".
25
Operation Method
Rep. start ► No
Press the ENTER key to decide the setting.
26
Press the PROGRAM key until the "Set TEMP" in the Step 3 is
27
displayed. The display on the lower column changes from "S02"
to "S03"or to "SO3 (un-used)".
Press the ENTER key to display the setting temperature edition
28
screen. The cursor goes out and the setting temperature blinks.
Set the temperature to -10℃ using the "▼▲".
29
Press the ENTER key to decide the temperature.
30
Press the PROGRAM key to display the "Set time" selection
31
screen.
S02
Rep. start ► No
S02
Set TEMP
S03
Set TEMP
S03
Set TEMP
S03
Set TEMP
S03
Set time ► 0min
S03
► 0.0℃
0.0℃
-10.0℃
► -10.0℃
Press the ENTER key to display the setting period edition screen.
32
The cursor goes out and the setting period blinks.
Set the period to 15 min using the "▼▲".
33
Press the ENTER key to decide the period.
34
Press the PROGRAM key to display the "Rep. start".
35
Press the ENTER key to display the repeat initiating step edition
36
screen. The cursor goes out and the setting for repeat initiating
step blinks.
Set "S02" using the "▼▲".
37
Press the ENTER key to decide the setting.
38
Set time 0min
S03
Set time 15min
S03
Set time ► 15min
S03
Rep. start ► No
S03
Rep. start No
S03
Rep. start S02
S03
Rep. start ► S02
S03
35
Page 40
Program Creation Example
Press the PROGRAM key to display the "Rep. count".
39
Operation Method
Rep.count ►Endless
Press the ENTER key to display the setting for repeat count
40
edition screen. The cursor goes out and the repeat count blinks.
Set "1" using the "▼▲".
41
Press the ENTER key to decide the setting.
42
Press the PROGRAM key until the "Set time" in the Step 4 is
43
displayed. The display on the lower column changes from "S03"
to "S04"or to "SO4 (un-used)".
Press the ENTER key to display the setting period edition screen.
44
The cursor goes out and the setting period blinks.
Display the "End" using the "▼▲".
45
S03
Rep. count Endless
S03
Rep. count 1
S03
Rep.count ► 1
S03
Set time ► 0min
S04
Set time 0min
S04
Set time End
S04
Press the ENTER key to decide the setting.
46
Press the PROGRAM key until the "Program End" in the Step 4 is
47
displayed.
Press the ENTER key to register the program and return to the
48
standby state.
Set time ► End
S04
S04
2002/01/01 12:00
Program End
Standby
36
Page 41
Operation Method
Set Clock
The clock is not set at factory shipment. Set it with your watch or time tone before using the unit.
The setting for clock can not be changed at the operation start waiting state in the auto start mode/program
mode, or during operation. Press the POWER key and stop operation to change it.
Select the item in function menu
1
• Check that the power in turned on.
FUNCTION
Select the setting item
2
Date 2001/09/22
Time 23:59
CANCEL
ENTER
Date ►2001/09/22
Time 17:30
↓
Date 2001►09/22
TROUBLE
① Press the FUNCTION key. The function menu
starts and the Sub Display displays the items.
Select the item using the FUNCTION key.
① Display the "Date" and "Time" using the
FUNCTION key. The date and time currently set
are displayed.
② The "
" (cursor) moves to "year", "month",
"date", "hour" and "minute" in this order when the
FUNCTION key is pressed. Select the item to
be set and press the ENTER key.
Time 17:30
↓
Date 2001/09►22
Time 17:30
↓
Date 2001/09/22
Time ►17:30
↓
Date 2001/09/22
Time 17►30
37
Page 42
Set Clock
Operation Method
Input value
3
Set clock
4
Date 2001/09/22
Time 17:30
↓
Date 2002/09/22
Time 17:30
Date 2002/09/22
Time 23:59
ENTER
TROUBLE
CANCEL
① The "
" (cursor) goes out and the current value
blinks instead. Display the desired value using
the "▼▲".
① Press the ENTER key. The setting is decided
and the function menu selection screen is
displayed.
38
Page 43
Operation Method
Set the Timer Mode
Changes in timer mode are not reflected in the operation currently carried out in the following state of unit;
operation start waiting state in the auto start mode, during auto stop mode operation, and operation start
waiting state in the program operation mode. The changes are reflected on and after the next operation.
Select the item in function menu
1
• Check that the power in turned on.
FUNCTION
Timer mode Time
CANCEL
ENTER
Select mode
2
Timer mode Time
↓
Timer mode Clock
TROUBLE
① Press the FUNCTION key. The function menu
starts and the Sub Display displays the items.
Select the item using the FUNCTION key.
② Display the "Timer mode" and press the ENTER
key.
Press the CANCEL key to cancel the function menu.
① The "
" (cursor) goes out and the mode currently
selected blinks instead. Display the "Time" or
"Clock" using the "▼▲".
Set timer mode
3
Timer mode Clock
ENTER
CANCEL
TROUBLE
① Press the ENTER key. The timer mode is
decided and the function menu selection screen
is displayed.
39
Page 44
Set the Operation Start Signal Input Mode
Operation Method
Select the item in function menu
1
• Check that the power in turned on.
FUNCTION
OPR signal OFF
CANCEL
ENTER
Select mode
2
OPR signal OFF
↓
OPR signal ON
TROUBLE
① Press the FUNCTION key. The function menu
starts and the Sub Display displays the items.
Select the item using the FUNCTION key.
② Display the "OPR signal" and press the ENTER
key.
Press the CANCEL key to cancel the function menu.
① The "
" (cursor) goes out and the mode currently
selected blinks instead. Display the "ON" or
"OFF" using the "▼▲".
Set operation start signal input mode
3
OPR signal ON
AUTO START
FIXED TEMP
AUTO STOP
PROGRAM
STANDBY
HEATER
REFRIGE
ENTER
Set TEMP 37.0
℃
END
FUNCTION PROGRAM
MENU ENTER
TROUBLE
CANCEL
Wait: OPR signal
Start operation
4
① Press the ENTER key. The operation start
signal input mode is decided and the function
menu selection screen is displayed.
• The unit is in the operation start signal input wait
state at the operation start in each mode when the
operation start signal input mode is set to on.
• In the state above, the lamp of current operation
lights on and the STANDBY lamp blinks. The
℃
TROUBLE
CANCEL
DEFROST
POWER
lower column of the Sub Display indicates "Wait:
OPR signal".
① The unit starts operation when operation start
signal is input or the operation start signal input
mode is set to "OFF".
40
Page 45
Set the Operation Stop Signal Input Mode
Operation Method
Select the item in function menu
1
• Check that the power in turned on.
FUNCTION
Stop signal OFF
CANCEL
ENTER
Select mode
2
Stop signal OFF
↓
Stop signal ON
TROUBLE
① Press the FUNCTION key. The function menu
starts and the Sub Display displays the items.
Select the item using the FUNCTION key.
② Display the "Stop signal" and press the ENTER
key.
Press the CANCEL key to cancel the function menu.
① The "
" (cursor) goes out and the mode currently
selected blinks instead. Display the "ON" or
"OFF" using the "▼▲".
Set operation stop signal input mode
3
Stop signal ON
ENTER
CANCEL
TROUBLE
① Press the ENTER key. The operation stop
signal input mode is decided and the function
menu selection screen is displayed.
• The unit monitors the input of operation stop signal
during operation in each mode and automatically
stops operation if it is input when the operation
stop signal input mode is set to "ON". The unit
enters to the standby state.
41
Page 46
Set the Key Lock Mode
Operation Method
Select the item in function menu
1
• Check that the power in turned on.
FUNCTION
Key lock OFF
CANCEL
ENTER
Select mode
2
Key lock OFF
↓
Key lock ON
TROUBLE
① Press the FUNCTION key. The function menu
starts and the Sub Display displays the items.
Select the item using the FUNCTION key.
② Display the "Key lock" and press the ENTER key.
Press the CANCEL key to cancel the function menu.
① The "
" (cursor) goes out and the mode currently
selected blinks instead. Display the "ON" or
"OFF" using the "▼▲".
Set key lock mode
3
Key lock ON
ENTER
TROUBLE
CANCEL
① Press the ENTER key. The key lock mode is
decided and the function menu selection screen
is displayed.
Only the POWER key and change of key lock mode
are available in key lock state. If any operation
except that is done, the Sub Display displays the
"Key lock" with the alarm sound.
Set TEMP
37.0℃→
Key lock
(Screen of under the fixed temperature operation)
42
Page 47
Set the Buzzer Mode
Operation Method
Select the item in function menu
1
• Check that the power in turned on.
FUNCTION
Buzzer mode OFF
CANCEL
ENTER
Select mode
2
Buzzer mode OFF
↓
Buzzer mode ON
TROUBLE
① Press the FUNCTION key. The function menu
starts and the Sub Display displays the items.
Select the item using the FUNCTION key.
② Display the "Buzzer mode" and press the ENTER
key.
Press the CANCEL key to cancel the function menu.
① The "
" (cursor) goes out and the mode currently
selected blinks instead. Display the "ON" or
"OFF" using the "▼▲".
Set buzzer mode
3
Buzzer mode ON
① Press the ENTER key. The buzzer mode is
decided and the function menu selection screen
is displayed.
TROUBLE
The buzzer at auto stop and at the end of program
operation does not sound when the buzzer mode is
turned to "OFF". It sounds when the safety device
ENTER
CANCEL
works because a trouble occurs on the unit.
43
Page 48
Operation Method
Calibration Offset Function
Calibration offset is a function which corrects the difference between the temperature in furnace and that of
controller (sensor temperature) if arises. The function parallel corrects the difference either to the plus or
minus side within the whole temperature range of unit.
starts and the Sub Display displays the items.
Select the item using the FUNCTION key.
② Display the "Calibrate" and press the ENTER key.
Press the CANCEL key to cancel the function menu.
① The "
" (cursor) goes out and the current offset
temperature blinks instead. Select the "-" to
lower the temperature (to rise that in furnace),
or "+" to rise it (to lower that in furnace) to display
the offset temperature using the "▼▲".
44
Page 49
Calibration Offset Function
Operation Method
Set calibration offset
3
Calibrate +2.5℃
ENTER
CANCEL
TROUBLE
(Ex.)
Indicated temperature on controller: 37℃
Measured temperature: 36℃
↓
Calibration offset: -1
① Press the ENTER key. The setting is decided
and the function menu selection screen is
displayed.
Offset is adjustable within the range from +3.0℃ to
-3.0℃.
Temperature correction in
overheating prevention device:
The temperature of overheating prevention device is
automatically corrected by the same amount when
that of controller is collected.
45
Page 50
Operation Method
Integrating Operation Time
The integrating operation time is a function to check the operation hours of unit. Its content can not be
changed.
Select the item in function menu
1
• Check that the power in turned on.
FUNCTION
Check integrating operation time
2
Acc. time 100hr
CANCEL
Manual Defrost Operation
① Press the FUNCTION key. The function menu
starts and the Sub Display displays the items.
Select the item using the FUNCTION key.
① The integrating operation time from factory
shipment to now is displayed.
The integrating operation time indicates the total
sum of lapsed time in standby, operation start wait,
operation and operation end state.
② Press the CANCEL key to cancel the function
menu after checking the time.
Select the item in function menu
1
DEFROST
Set TEMP
DEF Processing
37.0℃↑
① Press the DEFROST key to start the defrost
operation.
• The unit ends the defrost operation when the
defrost time (parameter) is up. The STANDBY
lamp blinks and "DEF Processing" is displayed
during the defrost operation.
• Press the DEFROST key again to suspend
defrosting.
Defrost operation is not available in the standby
state.
The default value of defrost operation is five
minutes.
46
Page 51
Set the Defrost Operation Mode
Operation Method
Select the item in function menu
1
• Check that the power in turned on.
FUNCTION
DEF mode OFF
CANCEL
ENTER
Select mode
2
DEF mode OFF
↓
DEF mode Cycle
TROUBLE
① Press the FUNCTION key. The function menu
starts and the Sub Display displays the items.
Select the item using the FUNCTION key.
② Display the "DEF mode" and press the ENTER
key.
Press the CANCEL key to cancel the function menu.
① The "
" (cursor) goes out and the mode currently
selected blinks instead. Display the "OFF" or
"Cycle" using the "▼▲".
Set defrost operation mode
3
DEF mode Cycle
ENTER
TROUBLE
CANCEL
① Press the ENTER key. The defrost operation
mode is decided and the function menu selection
screen is displayed.
47
Page 52
Set the Cycle Defrost Operation Time
Operation Method
Select the item in function menu
1
• Check that the power in turned on.
FUNCTION
Cycle ►5min ON
Select setting item
2
DEF 23h55m OFF
Cycle 5min ON
DEF 23h55m OFF
CANCEL
ENTER
TROUBLE
① Press the FUNCTION key. The function menu
starts and the Sub Display displays the items.
Select the item using the FUNCTION key.
② Display the "Cycle/DEF" using the FUNCTION
key.
• The Sub Display displays the current setting of
cycle defrost operation time for "ON" and "OFF".
Press the CANCEL key to cancel the function menu.
① Select the setting item using the FUNCTION key
and press the ENTER key.
Cycle►5min ON
DEF 23h55m OFF
↓
Cycle5min ON
Input value
3
Set cycle defrost operation time
4
Cycle 10min ON
DEF 23h55m OFF
ENTER
TROUBLE
CANCEL
① The "
DEF ►23h55m OFF
" (cursor) goes out and the current value
blinks instead. Edit the value using the "▼▲".
Cycle5min ON
DEF 23h55m OFF
↓
Cycle10min ON
DEF 23h55m OFF
① Press the ENTER key. The cycle defrost
operation time is decided and the function menu
selection screen is displayed.
48
Page 53
Set the Refrigerator Operation Mode
Operation Method
Select the item in function menu
1
• Check that the power in turned on.
FUNCTION
REF mode Cont
CANCEL
ENTER
Select mode
2
REF mode Cont
↓
REF mode Cycle
TROUBLE
① Press the FUNCTION key. The function menu
starts and the Sub Display displays the items.
Select the item using the FUNCTION key.
② Display the "REF mode" and press the ENTER
key.
Press the CANCEL key to cancel the function menu.
① The "
" (cursor) goes out and the mode currently
selected blinks instead. Display the "Cont",
"Cycle" or "Stop" using the "▼▲".
↓
REF mode Stop
Set refrigerator operation mode
3
REF mode Cycle
ENTER
TROUBLE
CANCEL
① Press the ENTER key. The refrigerator
operation mode is decided and the function menu
selection screen is displayed.
The refrigerator continues to operate if the setting
temperature is set to 44.0 ℃ or below in the
continuous operation.
It repeats 12-minute operation and 12-minute halt
condition in the cycle operation.
49
Page 54
Operation Method
Set the Communication Lockout Mode (Optional accessory)
Select the item in function menu
1
• Check that the power in turned on.
FUNCTION
Comm. Lockout OFF
CANCEL
ENTER
Select mode
2
Comm. Lockout OFF
↓
Comm. Lockout ON
TROUBLE
① Press the FUNCTION key. The function menu
starts and the Sub Display displays the items.
Select the item using the FUNCTION key.
② Display the "Comm. Lockout" and press the
ENTER key.
① The "
" (cursor) goes out and the mode currently
selected blinks instead. Display the "ON" or
"OFF" using the "▼▲".
Set communication lockout mode
3
Comm. Lockout ON
ENTER
TROUBLE
CANCEL
① Press the ENTER key. The communication
lockout mode is decided and the function menu
selection screen is displayed.
50
Page 55
The Independent Overheating Prevention Device
Operation Method
Select the item in function menu
1
① Set the temperature using the "▼▲".
60℃
Notes for the independent overheating prevention device
• In case there is a small difference between the set values of temperature for the independent
overheating prevention device and that of controller, the independent overheating prevention
device may be activated and stops the operation. Set the temperature of the device so it be
at least 10℃ or more higher than that of controller.
• The default value of the independent overheating prevention device at factory shipment is
60℃. The setting temperature range is 0 to 65℃.
• The independent overheating prevention device is not intended to protect the sample from
overheating.
• For the independent overheating prevention device to start at the required temperature, first
establish a stable operation at such a required temperature, and lower gradually the setting
value of the independent overheating prevention device, and then check if the operation is
maintained with stable at the required temperature. (It takes about five soconds for the device
to activate. Check after waiting for five seconds.) When the device activates, the unit
indicates Er07 and stops the operation.
• Wait for about five seconds for the period to record it before turning off the power after the
setting temperature of independent overheating prevention device is changed.
51
Page 56
Handling Precautions
WARNING!
If a problem occurs
If smoke or strange odor should come out of this unit for some reason, turn off the power key
right away, and then turn off the circuit breaker and the main power. Immediately contact a
service technician for inspection. If this procedure is not followed, fire or electrical shock may
result. Never perform repair work yourself, since it is dangerous and not recommended.
Substances that cannot be used
Never use explosive substances, flammable substances and substances that include explosive
or flammable ingredients in this unit. Explosion or fire may occur. (Refer to page 63 "List of
Dangerous Substances".)
CAUTION!
Do not step on this unit
Do not step on this unit. It will cause injury if this unit fall down or break.
Do not put anything on this unit
Keep clear on the unit to prevent dropping and injury. Do not put flammable such as paper
around it.
During a thunder storm
During a thunderstorm, turn off the power key immediately, then turn off the circuit breaker and
the main power. If this procedure is not followed, fire or electrical shock may be caused.
About the amount of samples
If the excessive amount of sample is set, it could be impossible to control the temperature
normally. To keep the temperature control accuracy, do not use this unit in overload.
Recovering after power failure
When power is supplied after a power failure, the device automatically starts operation again with
the same state as just before the power failure.
When I used a backup power supply for blackout return, but a blackout occurred for need in less
than 30 minutes more than 30 minutes as for the charge time of the backup power supply since I
turned on electricity in a device, there is the thing that a blackout does not return temporarily. The
blackout return function operates normally after it was charged a backup power supply enough
because I am not abnormal.
52
Page 57
Daily Inspection and Maintenance
Maintenance Method
WARNING!
• Disconnect the power cable from the power source when doing an inspection or maintenance unless
needed.
• Perform the daily inspection and maintenance after returning the temperature of this unit to the
normal one.
• Do not disassemble this unit.
CAUTION!
• Use a well-drained soft cloth to wipe dirt on this unit.
Do not use benzene, thinner or cleanser for wiping.
Do not scrub this unit. Deformation, deterioration
or color change may result in.
Monthly maintenance
• Check the earth leakage breaker function.
1. Connect the power cord.
2. Turn the breaker on.
3. Push the red test switch by a ballpoint pen etc.
4. If there is no problem, the earth leakage breaker will be turned off.
• Check the movement of the independent overheating prevention device.
Perform the fixed temperature operation of device with certain preset temperature. Then set the
operation temperature of independent overheating prevention device to the value approximately 5℃
lower than the preset temperature of device.
In normal condition, the device shuts off the heating circuit in a few seconds, at the same time the
TROUBLE lamp lights on and the "Er07" is indicated accompanied with a warning buzzer.
• Clean the fin on condenser.
Remove the grill on the left face of the IN602,
or left side in front of the IN802, then remove
the dust on the surface of fin on condenser
with a vacuum cleaner.
Condenser
CAUTION!
Do not soak the fin for cleaning.
Make sure to check the movement of earth leakage breaker above and overheating prevention device
before long term operation or night-time unmanned operation.
For any questions, contact the dealer who you purchased this unit from, or the nearest sales
division in our company.
53
Page 58
Long storage and disposal
When not using this unit for long term / When disposing
CAUTION!
When not using this unit for long term…
• Turn off the power and disconnect the power cord.
WARNING!
When disposing…
• Keep out of reach of children.
• Remove the door and driving parts.
• Treat as large trash.
Environmental protection should be considered
We request you to disassemble this unit as possible and recycle the reusable parts considering to
the environmental protection. The feature components of this unit and materials used are
listed below.
Power cord Synthetic rubber coating, Copper, Nickel and other
Wiring material Glass fiber, Incombustible vinyl, Copper, Nickel and other
Seals Resin
Sensor Stainless steel SUS304 and other
54
Page 59
In the Event of Failure…
Error Indication
Error code Name Cause Solution
Er.00
Er.01
Er.02
Er.03
Er.07
Er.10
Er.13
Er.14
Er.15
Setting value
error
Sensor error Temperature sensor failure Contact to our service division.
SSR error SSR failure Contact to our service division.
Heater error
Independent
overheating
prevention
device activation
Main relay error Contact to our service division.
Refrigerator error Overload of refrigerator Contact to our service division.
RAM error Checksum abnormality in RAM Contact to our service division.
EEPROM error Checksum abnormality in EEPROMContact to our service division.
Setting value is out of usable range Set correct value.
Heater disconnection
(Detection is available only during
the heater is controlled.)
Independent overheating prevention
device is in operation
Contact to our service division.
Reset the power supply, and
then adjust the setting
temperature of the independent
overheating prevention device.
55
Page 60
Trouble Shooting
Problem Possible Cause Solution
The device does not start
when turning on the power
switch.
In the Event of Failure…
Earth leakage breaker failure Replace the part.
Power switch failure Replace the part.
Power source failure
Heater disconnection Replace the part.
Connect to the appropriate
power source
Temperature does not rise.
Temperature does not fall.
Heater does not stop working
when the temperature reaches
setting value.
SSR failure Replace the part.
Temperature controller failure Replace the part.
Temperature sensor failure Replace the part.
Temperature controller failure Replace the part.
Clogging of condenser with dust Clean the fin on condenser
Much frost on evaporator Defrost
Relay failure Replace the part.
Power source failure
Refrigerator failure Repair or replace the part.
SSR failure Replace the part.
Temperature controller failure Replace the part.
Connect to the appropriate
power source
If power failure occurs…
The unit returns automatically to start operation automatically with the same condition as just
before the failure when it occurs during operation and is recovered. When I used a backup
power supply for blackout return, but a blackout occurred for need in less than 30 minutes more
than 30 minutes as for the charge time of the backup power supply since I turned on electricity
in a device, there is the thing that a blackout does not return temporarily. The blackout return
function operates normally after it was charged a backup power supply enough because I am not
abnormal.
56
Page 61
After Service and Warranty
In Case of Request for Repair
If the failure occurs, stop the operation, turn OFF the power switch, and unplug the power plug.
Please contact the sales agency that this unit was purchased, or the Yamato Scientific's sales
office.
< Check following items before contact >
◆ Model Name of Product
◆ Production Number
◆ Purchase Date
◆ About Trouble (in detail as possible)
Minimum Retention Period of Performance Parts for Repair
The minimum retention period of performance parts for repair of this unit is 7 years after
discontinuance of this unit.
The "performance part for repair" is the part that is required to maintain this unit.
See the production plate attached to this unit.
57
Page 62
Specification
IN603 IN803
Method Forced circulation
Temperature control
range
Temperature
adjustment accuracy
Temperature
distribution accuracy
Time required to reach
highest temperature
Time required to reach
lowest temperature
Temperature control
system
Temperature
setting system
Temperature
display system
Timer display range 0min to 99h59min, 100 to 999.5h
Timer resolution 1 minute or 1 hour
Operation mode
Additional functions Timer, Clock, Total operating hours counter (max. of 49999h), Calibration offset
Never use explosive substances, flammable substances and substances that include explosive
or flammable ingredients in this unit.
EXPLOSIVE
Ethylene glycol dinitrate (nitro glycol), Glycerin trinitrate (nitroglycerine), Cellulose
nitrate (nitrocellulose), and other explosive nitrate esters
Reference
EXPLOSIVE:
FLAMMABLE
IGNITING:
OXIDIZING:
Trinitrobenzene, Trinitrotoluene, Trinitrophenol (picric acid), and other explosive
nitro compounds
Acetyl hidroperoxide (peracetic acid), Methyl ethyl ketone peroxide, Benzyl
peroxide, and other organic peroxides
Lithium (metal), Potassium (metal), Sodium (metal), Yellow phosphorus,
Phosphorus sulfide, Red phosphorus, Celluloid compounds, Calcium carbide,
Lime phosphate, Magnesium (powder), Aluminum (powder), Powder of metals
other than magnesium and aluminum, Sodium hydrosulfite
Potassium chlorate, Sodium chlorate, Ammonium chlorate, and other chlorate
Potassium perchlorate, Sodium perchlorate, Ammonium perchlorate, and other
perchlorate
Potassium peroxide, Sodium peroxide, Barium peroxide, and other inorganic
peroxide
Potassium nitrate, Sodium nitrate, Ammonium nitrate, and other nitrate
Sodium chlorite and other chlorites
Calcium hypochlorite and other hypochlorites
Ethyl ether, Gasoline, Acetaldehyde, Propylene chloride, Carbon disulfide, and
other flammable substances having a flash point of lower than -30℃
INFLAMMABLE
LIQUID:
FLAMMABLE
GAS:
Normal hexane, ethylene oxide, acetone, benzene, methyl ethyl ketone, and
other flammable substances having a flash point of -30℃ or higher but lower
than 0℃
Methanol, Ethanol, Xylene, Pentyl acetate (amyl acetate), and other flammable
substances having a flash point of 0℃ or higher but lower than 30℃
Kerosene, Light oil (gas oil), Oil of turpentine, Isopentyl alcohol (isoamyl alcohol),
Acetic acid, and other flammable substances having a flash point of 30℃ or
higher but lower than 65℃
Hydrogen, Acetylene, Ethylene, Methane, Propane, Butane, and other flammable
substances which assume a gaseous state at 15℃ and 1 atm
(Source: Appendix Table 1 of Article 6 of the Industrial Safety and Health Order in Japan)
63
Page 68
Responsibility
Please follow the instructions in this document when using this unit. Yamato Scientific has no
responsibility for the accidents or breakdown of device if it is used with a failure to comply.
Never conduct what this document forbids. Unexpected accidents or breakdown may result in.
Note
◆ The contents of this document may be changed in future without notice.
◆ Any books with missing pages or disorderly binding may be replaced.
Instruction Manual for
Programmable Low Temperature Incubator
Model IN603/803
Second Edition May. 28, 2009
Yamato Scientific Co., Ltd.
2-1-6 Nihonbashi Honcho, Chuo-ku,
Tokyo, 103-8432, Japan
http://www.yamato-net.co.jp
64
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.