Xylem 9100 User Manual

INSTRUCTION MANUAL
AC8585
REVISION C
INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.
9100 Series Base Mounted Centrifugal Fire Pumps
TABLE OF CONTENTS
DESCRIPTION......................................................3
OPERATIONAL LIMITS .......................................3
MAXIMUM WORKING PRESSURE .....................3
SEAL OPERATING LIMITS .................................3
PACKING ......................................................3
1. GENERAL MAINTENANCE.................... 25
2. MAINTENANCE OF PUMP DUE TO
FLOOD DAMAGE ............................... 25
3. BEARING LUBRICATION – GREASE ... 25
4. PACKING SEAL...................................... 26
5. CLEANING WITHOUT DISMANTLING
PUMP .................................................. 26
MAINTENANCE TIME TABLE........................... 27
PUMP IDENTIFICATION ......................................3
SAFETY INSTRUCTIONS ....................................4
ADDITIONAL SAFETY REQUIREMENTS...........5
ELECTRICAL SAFETY .................................5
THERMAL SAFETY ......................................5
MECHANICAL SAFETY................................5
PUMP LOCATION ................................................6
INTRODUCTION...................................................7
1. PURPOSE OF MANUAL...........................7
2. WARRANTY ..............................................7
3. PUMP IDENTIFICATION ..........................7
4. INSTALLATION.........................................7
5. RECEIVING PUMP ...................................7
6. TEMPORARY STORAGE .........................7
7. LOCATION ................................................7
8. FOUNDATION...........................................8
9. BASE PLATE SETTING (BEFORE
PIPING) .................................................8
10. GROUTING PROCEDURE .....................9
11. SEE ANSI/OSHA COUPLER GUARD
REMOVAL/INSTALLATION ..................9
12. ALIGNMENT PROCEDURE ...................9
13. ANSI/OSHA COUPLER GUARD
REMOVAL/INSTALLATION ..................9
14. DOWELING...........................................15
15. SUCTION AND DISCHARGE PIPING..15
16. STUFFING BOX LUBRICATION...........18
17. PACKING ..............................................18
SERVICE INSTRUCTIONS ................................ 28
DISASSEMBLY AND REASSEMBLY
PROCEDURES................................... 28
DISMANTLING (PUMP WITH PACKING) .. 28
ASSEMBLY (PUMP WITH PACKING) ....... 30
APPENDIX “A” ..................................................33
EXPLODED VIEW ......................................33
REPLACEMENT PARTS LIST ...................34
LIMITED END FLOAT COUPLINGS .......... 35
ORDERING PARTS.................................... 35
DEALER SERVICING ........................................36
NOTE
The information contained in this book is intended to assist operating personnel by providing information on the characteristics of the purchased equipment.
It does not relieve the user of their responsibility of using accepted engineering practices in the installation, operation, and maintenance of this equipment.
Any further questions, contact AC Fire Pump, (847) 966-3700.
OPERATION .......................................................20
1. PRE-START CHECKS ............................20
2. PRIMING .................................................20
3. STARTING ..............................................20
4. OPERATING CHECKS ...........................20
5. FREEZING PROTECTION......................21
CHANGING ROTATION.....................................22
MAINTENANCE..................................................25
DESCRIPTION
The 9100 Series Centrifugal Fire Pumps are frame mounted pumps which feature – high efficiency, rugged construction, compact design, foot mounted volute and regreasable bearings. These features, along with the horizontal split case, make installation, operation and service easy to perform.
OPERATIONAL LIMITS
Unless special provisions have been made for your pump by AC Fire Pump Systems, the operational limits for 9100 Series Centrifugal Fire Pumps are as follows:
MAXIMUM WORKING PRESSURE
Listed on pump nameplate.
SEAL OPERATING LIMITS
PACKING
PH Limitations 7-9; Temperature Range 0 to +200°F
For use on open or closed systems which require a large amount of makeup water, as well as systems which are subjected to widely varying chemical conditions and solids buildup.
PUMP IDENTIFICATION
Permanent records for this pump are referenced by the Serial Number and it must, therefore, be used with all correspondence to order all spare and replacement parts. The fourth digit indicates the specific pump on orders for more than one pump. For example, if an order called for six pumps, all pumps would have the same first three sets of digits and the last digit will change to
, 03-
identify each of the six. (e.g. 03-123456-01­123456-01-02
, etc.)
01
FIGURE 1 – RATING PLATE
3
SAFETY INSTRUCTIONS
SAFETY INSTRUCTIONS
This safety alert symbol will be used in this manual and on the pump safety instruction decals to draw attention to safety related instructions. When used the safety alert symbol means ATTENTION! BECOME ALERT! YOUR SAFETY IS INVOLVED! FAILURE TO FOLLOW THE INSTRUCTIONS MAY RESULT IN A SAFETY HAZARD.
Your 9100 Series Centrifugal Fire Pump should have the following safety instruction decals displayed. If the decals are missing or illegible contact your local AC Fire Pump Systems representative for a replacement.
WARNING
ROTATING COMPONENTS
DISCONNECT AND LOCKOUT POWER BEFORE SERVICING.
DO NOT OPERATE WITHOUT ALL GUARDS IN PLACE.
CONSULT INSTALLATION AND SERVICE INSTRUCTION SHEET BEFORE OPERATING OR SERVICING.
FAILURE TO FOLLOW INSTRUCTIONS COULD RESULT IN INJURY OR DEATH.
Additional Safety Requirements:
1. Electrical connections to be made by
qualified Electrician in accordance with all national, state and local codes.
2. Motor must have properly sized starter
with properly sized heaters to provide overload and undervoltage protection.
3. If pump, motor or piping are operating at
extremely high or low temperatures, guarding or insulation is required.
4. The maximum working pressure of the
pump is listed on the pump nameplate, do not exceed this pressure.
RATING PLATE
WARNING
EYEBOLTS OR LIFTING LUGS IF PROVIDED ARE FOR LIFTING ONLY THE COMPONENTS TO WHICH THEY ARE ATTACHED. FAILURE TO FOLLOW INSTRUCTIONS COULD RESULT IN INJURY OR DEATH.
CAUTION CAUTION
COUPLER ALIGNMENT IS REQUIRED! LEVEL AND GROUT PUMP BEFORE USE!
CHECK ALIGNMENT BEFORE GROUTING, AFTER SYSTEM IS FILLED, AFTER SERVICING PUMP, AND AS REQUIRED. CONSULT THE SERVICE INSTRUCTIONS FOR DETAILS.
FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN INJURY OR PROPERTY DAMAGE.
FIGURE 2 – SAFETY INSTRUCTION DECALS
DO NOT RUN PUMP DRY, SEAL DAMAGE MAY OCCUR.
INSPECT PUMP SEAL REGULARKY FOR LEAKS, REPLACE AS REQUIRED.
FOR LUBRICATION REQUIREMENTS, CONSULT SERVICE INSTRUCTIONS.
FAILURE TO FOLLOW INSTRUCTIONS COULD RESULT IN INJURY OR PROPERTY DAMAGE.
ADDITIONAL SAFETY REQUIREMENTS
ELECTRICAL SAFETY
WARNING: Electrical Shock Hazard
Electrical connections to be made by a qualified electrician in accordance with all applicable codes, ordinances, and good practices. Failure to follow these instructions could result in serious personal injury or death, and property damage.
WARNING: Electrical Overload Hazard
Three phase motors must have properly sized heaters to provide overload and under voltage protection. Single-phase motors have built-in overload protectors. Failure to follow these instructions could result in serious personal injury or death, and property damage.
THERMAL SAFETY
WARNING: Extreme Temperature
Hazard
If pump, motor, or piping is operating at extremely high or low temperature, guarding or insulation is required. Failure to follow these instructions could result in serious personal injury or death, and property damage.
MECHANICAL SAFETY
WARNING: Unexpected Startup Hazard
Disconnect and lockout power before servicing. Failure to follow these instructions could result in serious personal injury or death, and property damage.
WARNING: Excessive System Pressure
Hazard
The maximum working pressure of the pump is listed on the nameplate, do not exceed this pressure. Failure to follow these instructions could result in serious personal injury or death, and property damage.
WARNING: Excessive Pressure Hazard
Volumetric Expansion
WARNING
The heating of water and other fluids causes volumetric expansion. The associated forces may cause failure of system components and release of high temperature fluids. Installing properly sized and located compression tanks and pressure relief valves will prevent this. Failure to follow these instructions could result in serious personal injury or death, and property damage.
CAUTION
WARNING
PUMP LOCATION
Locate the pump so there is sufficient room for inspection, main-tenance and service. If the use of a hoist or tackle is needed, allow ample head room.
WARNING: Falling Objects Hazard
Eyebolts or lifting lugs, if provided, are for lifting only the components to which they are attached. Failure to follow these instructions could result in serious personal injury or death, or property damage.
If lifting base pump is required, use a nylon string, chain, or wire rope, hitch around both bearing supports. If lifting of the entire pump is required, do so with slings placed under the base rails as shown.
CHOKER HITCH AROUND BEARING FRAME
NYLON SLING, CHAIN OR WIRE ROPE
Care must be taken to size equipment for unbalanced loads which may exist if the motor is not mounted on the base at the time of lifting. Motor may or may not be mounted at the factory.
Pump, base, and driver assemblies where the base length exceeds 100 inches may not be safe to lift as a complete assembly. Damage to the baseplate may occur. If the driver has been mounted on the baseplate at the factory, it is safe to lift the entire assembly. If the driver has not been mounted at the factory, and the overall baseplate length exceeds 100 inches, do not lift the entire assembly consisting of pump, base, and driver. Instead, lift the pump and baseplate to its final location without the driver. Then mount the driver.
The best pump location for sound and vibration absorption is on a concrete floor with subsoil underneath. If the pump location is overhead, special precautions should be undertaken to reduce possible sound transmission. Consult a sound specialist.
FIGURE 3
If the pump is not on a closed system, it should be placed as near as possible to the source of the liquid supply, and located to permit installation with the fewest number of bends or elbows in the suction pipe.
The installation must be evaluated to determine that the Net Positive Suction Head Available (NPSHA) meets or exceeds the Net Positive Suction Head Required (NPSHR), as stated by the pump performance curve. See page 15 for more details on proper suction piping installation.
INTRODUCTION
1. PURPOSE OF MANUAL
This manual is furnished to acquaint you with some of the practical ways to install, operate, and maintain this pump. Read it completely before doing any work on your unit and keep it handy for future reference.
Equipment cannot operate well without proper care. To keep this unit at top efficiency, follow the recommended installation and servicing procedures outlined in this manual.
2. WARRANTY
Refer to your local representative for warranty coverage.
3. PUMP IDENTIFICATION
All pumps are designated by Serial Number, Model Number, and Size. This information is stamped on an identification plate which is mounted on the pump.
4. INSTALLATION
5. RECEIVING PUMP
Check pump for shortages and damage immediately upon arrival. (An absolute must.) Prompt reporting to the carrier’s agent with notations made on the freight bill, will expedite satisfactory adjustment by the carrier.
Pumps and drivers normally are shipped from the factory mounted and painted with primer and one finish coat. Couplings may be either completely assembled or have the coupling hubs mounted on the shafts and the connecting members removed. When the connecting members are removed, they will be packaged in a separate container and shipped with the pump or attached to the base plate.
Shafts are in alignment when the unit is shipped; however, due to shipping, the pumps may arrive misaligned and, therefore, alignment must be established during installation. AC Fire Pump Systems has determined that proper and correct alignment can only be made by accepted erection practices. Refer to the following paragraphs on “Foundation,” “Base Plate Setting,” “Grouting Procedure,” “Alignment Procedure” and “Doweling.”
6. TEMPORARY STORAGE
If the pump is not to be installed and operated soon after arrival, store it in a clean, dry place having slow, moderate changes in ambient temperature. Rotate the shaft periodically to coat the bearings with lubricant and to retard oxidation, corrosion, and to reduce the possibility of false brinelling of the bearings.
7. LOCATION
The pump should be installed as near the suction supply as possible, but no less than five suction diameters (refer to page 15, suction and discharge piping section) with the shortest and most direct suction pipe practical. The total dynamic suction lift (static lift plus friction losses in suction line) should not exceed the limits for which the pump was sold.
The pump must be primed before starting. Whenever possible, the pump should be located below the fluid level to facilitate priming and assure a steady flow of liquid. This condition provides a positive suction head on the pump. It is also possible to prime the pump by pressurizing the suction vessel.
When installing the pump, consider its location in relation to the system to assure that sufficient Net Positive Suction Head (NPSH) at pump suction is provided. Available NPSH must always equal or exceed the required NPSH of the pump.
The pump should be installed with sufficient accessibility for inspection and maintenance. A clear space with ample head room should be allowed for the use of an overhead crane or hoist sufficiently strong to lift the unit.
NOTE: Allow sufficient space to be able to dismantle pump without disturbing the pump inlet and discharge piping.
Select a dry place above the floor level wherever possible. Take care to prevent pump from freezing during cold weather when not in operation. Should the possibility of freezing exist during a shut-down period, the pump should be completely drained, and all passages and pockets where liquid might collect should be blown out with compressed air.
Make sure there is a suitable power source available for the pump driver. If motor driven, electrical characteristics should be identical to those shown on motor data plate.
8. FOUNDATION
A substantial foundation and footing should be built to suit local conditions. The foundation must be substantial enough to absorb vibration. (Hydraulic Institute Standards recommends the foundation weigh at least five (5) times the weight of the pump unit.) It must form a permanent and rigid support for the baseplate. This is important in maintaining the alignment of the flexibly coupled unit.
ALLOW 1" FOR SHIMS. PLACE ON BOTH SIDES OF ANCHOR BOLTS.
APPROX. 1" GAP
NOTE: TO KEEP SHIMS IN PLACE ALLOW GROUT TO FLOW AROUND HOLD DOWN LUGS.
GROUT ONLY TO TOP OF BASE RAIL.
PUMP BASE RAIL
GROUT
The foundation should be poured without interruption to within 1/2 to 1-1/2 inches of the finished height. The top surface of the foundation should be well scored and grooved before the concrete sets; this provides a bonding surface for the grout.
Foundation bolts should be set in concrete as shown in Figure 4. An optional 4-inch long tube around the bolts at the top of the concrete will allow some flexibility in bolt alignment to match the holes in the base plate. Allow enough bolt length for grout, shims, lower base plate flange, nuts and washers. The foundation should be allowed to cure for several days before the base plate is shimmed and grouted.
FOUNDATION BOLT
WASHER
(OPTIONAL)
PIPE SLEEVE
BUILT-UP CONCRETE FOUNDATION
FIGURE 4 – FOUNDATION
9. BASE PLATE SETTING (BEFORE PIPING)
NOTE: This procedure assumes that a
concrete foundation has been prepared with anchor or hold down bolts extending up ready to receive unit. It must be understood that pump and motor have been mounted and rough aligned at the factory. If motor is to be field mounted, consult factory for recommendations. AC Fire Pump Systems cannot assume responsibility for final alignment.
CONCRETE
LEVELING OF PUMP BASE ON CONCRETE FOUNDATION.
FOUNDATION
FIGURE 5 – SETTING BASE PLATE AND
GROUTING
a. Use blocks and shims under base for
support at anchor bolts and midway between bolts, to position base approximately 1" above the concrete foundation, with studs extending through holes in the base plate.
b. By adding or removing shims under the
base, level and plumb the pump shaft and flanges. The base plate does not have to be level.
c. Draw anchor nuts tight against base, and
observe pump and motor shafts or coupling hubs for alignment. (Temporarily remove coupling guard for checking alignment.)
d. If alignment needs improvement, add
shims or wedges at appropriate positions under base, so that retightening of anchor nuts will shift shafts into closer alignment. Repeat this procedure until a reasonable alignment is reached.
NOTE: Reasonable alignment is defined as that which is mutually agreed upon by pump contractor and the accepting facility (final operator). Final alignment procedures are covered under “Alignment Procedures.”
e. Check to make sure the piping can be
aligned to the pump flanges without placing pipe strain on either flange.
f. Grout in base plate completely (See
“Grouting Procedure”) and allow grout to dry thoroughly before attaching piping to pump. (24 hours is sufficient time with approved grouting procedure.)
10. GROUTING PROCEDURE
Grout compensates for uneven foundation, distributes weight of unit, and prevents shifting. Use an approved, non-shrinking grout, after setting and leveling unit (See Figure 5).
a. Build strong form around the foundation to
contain grout.
b. Soak top of concrete foundation
thoroughly, then remove surface water.
c. Base plate should be completely filled with
grout.
d. After the grout has thoroughly hardened,
check the foundation bolts and tighten if necessary.
e. Check the alignment after the foundation
bolts are tightened.
f. Approximately 14 days after the grout has
been poured or when the grout has thoroughly dried, apply an oil base paint to the exposed edges of the grout to prevent air and moisture from coming in contact with the grout.
11. SEE ANSI/OSHA COUPLER GUARD REMOVAL/INSTALLATION
(page 9)
12. ALIGNMENT PROCEDURE
NOTE: A flexible coupling will only
compensate for small amounts of misalignment. Permissible misalignment will vary with the make of coupling. Consult coupling manufacturer’s data when in doubt.
Allowances are to be made for thermal expansion during cold alignment, so that the coupling will be aligned at operating temperature. In all cases, a coupling must be in alignment for continuous operation. Even though the coupling may be lubricated, misalignment causes excessive wear, vibration, and bearing loads that result in premature bearing failure and ultimate seizing of the pump. Misalignment can be angular, parallel, or a combination of these, and in the horizontal and vertical planes. Final alignment should be made by moving and shimming the motor on the base plate, until the coupling hubs are within the recommended tolerances measured in total run-out. All measurements should be taken with the pump and motor foot bolts tightened. The shaft of sleeve bearing
motors should be in the center of its mechanical float.
NOTE: Proper alignment is essential for correct pump operation. This should be performed after base plate has been properly set and grout has dried thoroughly according to instructions. Final alignment should be made by shimming driver only. Alignment should be made at operating temperatures.
WARNING: Unexpected Start-up Hazard
Disconnect and lock out power before servicing. Failure to follow these instructions could result in serious personal injury or death and property damage.
13. ANSI/OSHA COUPLER GUARD REMOVAL/INSTALLATION
WARNING: Unexpected Start-up Hazard
Disconnect and lock out power before servicing. Failure to follow these instructions could result in serious personal injury or death and property damage.
NOTE: Do not spread the inner and outer guards more than necessary for guard removal or installation. Over spreading the guards may alter their fit and appearance.
Removal
a. Remove the two capscrews that hold the
outer (motor side) coupler guard to the support bracket(s).
b. Spread the outer guard and pull it off the
inner guard.
c. Remove the capscrew that holds the inner
guard to the support bracket.
d. Spread the inner guard and pull it over the
coupler.
Installation
a. Check coupler alignment before
proceeding. Correct if necessary.
b. Spread the inner guard and place it over
the coupler.
c. With the inner guard straddling the
support bracket, install a capscrew through the hole (or slot) in the support bracket and guard located closest to the pump. Do not tighten the capscrew.
d. Spread the outer guard and place it over
the inner guard.
e. Install the outer guard capscrews by
following the step stated below which pertains to your particular pump:
i. For pumps with a motor saddle support
bracket: Ensure the outer guard is straddling the support arm, and install but do not tighten the two remaining capscrews.
ii. For pumps without a motor saddle
support bracket: Insert the spacer washer between the holes located closest to the motor in the outer guard,
ANSI/OSHA Coupling Guard Exploded View For Typical 9100 Series Fire Pump Installation
OUTER GUARD
and install, but do not tighten, the two remaining capscrews.
f. Position the outer guard so it is centered
around the shaft, and so there is less than a 1/4" of the motor shaft exposed. On guards that utilize a slotted support bracket, the inner guard will have to be positioned so there is only a 1/4" of the pump shaft exposed.
g. Holding the guard in this position, tighten
the three capscrews.
INNER GUARD
ATTACH SUPPORT BRACKET TO BEARING HOUSING
LOCATE SUPPORT ARM BETWEEN OUTER GUARD ENDS. ALIGN THE ARM WITH HOLES IN THE OUTER GUARD AND HOLES IN THE SADDLE BRACKET.
NUT
LOCKWASHER
MOTOR SADDLE BRACKET ATTACH TO MOTOR SADDLE
BRACKET SUPPORT
CAPSCREW
FLAT WASHER
SPACER WASHER
THIS OPTION USED IN PLACE OF SPACER WHERE OVERALL LENGTH OF GUARD EXCEEDS 12 INCHES OR GUARD WITH IS OVER 10 INCHES ACROSS THE FLATS.
ATTACHES INSIDE HERE IN LINE WITH BOLT
BRACKET SUPPORT
SUPPORT BRACKET
10
Method 1 – Straight Edge Alignment for Standard Sleeve Type Coupler with Black Rubber Insert
(See Figure 6A)
Proceed with this method only if satisfied that face and outside diameters of the coupling halves are square and concentric with the coupling borers. If this condition does not exist or elastomeric couplings do not make this method convenient, use Method 2.
1. Check angular misalignment using a micrometer or caliper. Measure from the outside of one flange to the outside of the opposite flange at four points 90° apart. DO NOT ROTATE COUPLER. Misalignment up to 1/64" per inch of coupler radius is permissible.
2. At four points 90° apart (DO NOT ROTATE COUPLER), measure the parallel coupler misalignment by laying a straight edge across one coupler half and measuring the gap between the straight edge and opposite coupler half. Up to a 1/64" gap is permissible.
STRAIGHT EDGE
DIAL
PARALLEL
INDICATOR
ALIGNMENT
INDEX LINE
RESILIENT SEPARATOR
ANGULAR ALIGNMENT
DIAL INDICATOR
FIGURE 6B - CHECKING ALIGNMENT
(Method 2)
Method 2 – For Orange Hytrel Insert, 3500 RPM Operation, or All Other Coupler Types Except as Noted Below
(See Figure 6B)
a. Make sure each hub is secured to its
respective shaft and that all connecting and/or spacing elements are removed at this time.
b. The gap between the coupling hubs is set
by the manufacturer before the units are shipped. However, this dimension should be checked. (Refer to the coupling manufacturer’s specifications supplied with the unit.)
FEELER GAGE
ANGULAR ALIGNMENT PARALLEL ALIGNMENT
INCORRECT ALIGNMENT
STRAIGHT EDGE
FEELER GAGE
CORRECT ALIGNMENT
FIGURE 6A – CHECKING ALIGNMENT
(Method 1)
c. Scribe index lines on coupling halves as
shown in Figure 6B.
d. Mount dial indicator on one hub as shown
for parallel alignment. Set dial to zero.
e. Turn both coupling halves so that index
lines remain matched. Observe dial reading to see whether driver needs adjustment (See paragraph i below).
f. Mount dial indicator on one hub as shown
for angular alignment. Set dial to zero.
g. Turn both coupling halves so that index
lines remain matched. Observe dial reading to see whether driver needs adjustment (See paragraph i below).
h. Assemble coupling. Tighten all bolts and
set screw(s). It may be necessary to repeat steps c through f for a final check.
i. For single element couplings, a
satisfactory parallel misalignment is .004"T.I.R., while a satisfactory angular
11
misalignment is .004"T.I.R. per inch of radius R (See Figure 6B).
Grid Couplings NOTE: The following procedure is intended
for mounting and alignment of Rexnord Industries, LLC. and Clarke Fire Protection Products, Inc., Tapered Grid Couplings.
Adequate lubrication is essential for satisfactory operation. Grease supplied by the coupling manufacturer is highly recommended. Other greases to be used should be approved by the coupling manufacturer.
Alignment is shown using a spacer bar and straight edge. Rexnord Industries, LLC. and Clarke Fire Protection Products, Inc. state this practice has been proven for many industrial applications. Superior alignment can be achieved through the use of dial indicators as shown above.
1. Clean all metal parts using non-flammable solvent.
2. Lightly coat seals with coupling vendor supplied grease and place on shafts before mounting shaft hubs.
3. Install keys and mount hubs with flange faces flush with shaft ends or as otherwise specified.
4. Reposition hubs on shafts as required to achieve the required hub gap shown in Figure 6H or otherwise specified. The length of engagement on each shaft should be roughly equal to the shaft diameter.
5. Tighten setscrews.
6. Bring the pump and motor halves of the coupler into approximate height alignment, by placing equal amounts of shims under all the motor feet.
7. Tighten the motor bolts.
8. Use a spacer bar equal in thickness to the gap specified in Figure 6C. Insert bar, as shown below, to same depth at 90° intervals and measure clearance between bar and hub face with feeler gauges. The difference in minimum and maximum measurements must not exceed the angular installation limits shown in Figure 6H.
FIGURE 6C – USING SPACER BAR
9. Align so that a straight edge rests within the limits shown in Figure 6D on both hubs as shown below and also at 90° intervals without rotating the coupling. Check with feelers. The clearance must not exceed the PARALLEL OFFSET installation limits specified in Figure 6H.
FIGURE 6D – USING STRAIGHT EDGE
10. If adjustment is needed, loosen the motor bolts and add (or remove) an equal amount of shims under each motor foot to align the height. To correct side misalignment, strike the side of the motor foot with a mallet.
11. Tighten the motor bolts and check again. If a correction is made, re-check alignment in all
directions. Repeat this process until
the desired result is obtained.
12. Pack gap and grooves with coupling vendor supplied grease before inserting grid. When grids are furnished in two or more segments, install them so that all cut ends extend in the same direction as shown below. This will ensure correct grid contact with non-rotating pin in cover halves.
13. Spread the grid slightly to pass over the coupling teeth and seat with a soft mallet.
12
Loading...
+ 25 hidden pages