The information contained in this book is intended
to assist operating personnel by providing
information on the characteristics of the purchased
equipment.
It does not relieve the user of their responsibility of
using accepted engineering practices in the
installation, operation, and maintenance of this
equipment.
Any further questions, contact AC Fire Pump,
(847) 966-3700.
2
INTRODUCTION
We welcome you as a user of AC Fire Pump. Your
pump is a product of careful engineering and
skilled workmanship. We believe you have the
best pump possible for the service intended. With
care and preventative maintenance, our AC
Fire Pump will deliver efficient, trouble-free service.
This manual is furnished to acquaint you with
some of the practical ways to install, operate, and
maintain this pump. Read it completely before
doing any work on your unit and keep it handy for
future reference.
To maintain this unit at maximum efficiency, follow
the recommended installation and servicing
procedures outlined in this manual. To guide in the
installation of the pump for maximum operating
time and minimum downtime, you may contact
the AC Fire Pump Network of Sales and Service
Representative.
Experienced, factory-trained service personnel
offer prompt, efficient service at reasonable rates.
These service personnel can find and correct
costly errors such as poor grouting, misalignment,
pipe stresses transmitted to the pump casing, or
improperly sized piping. A service person may be
requested through your nearest AC Fire Pump
Sales Representatives.
Replacement and spare parts, including special
attention to your individual problems, may also be
obtained through the AC Fire Pump Representative.
For warranty coverages, refer to your sales
contract.
PUMP IDENTIFICATION
There are two identification plates on each pump.
The pump rating plate gives identification and
rating information. Figure 1 shows an example of a
typical Rating Plate.
rating plate to identify the pump in his operation.
(e.g. CWP-11 stands for Chilled Water Pump No.
11)
Size Type
8X8X17 8100
Serial Number
1-21937-1-1
GPM Head (ft.) RPM
1500 200 1780
Model Number Imp. Dia. (in.)
150 14.80
Max. Field Hydrotest Pressure
262 PSI
Identification No. Year
CWP-112000
MORTON GROVE, IL USA AC0687
FIGURE 1 – RATING PLATE
The frame plate, shown below, gives information
concerning the bearings and their lubrication. The
inboard and outboard bearing numbers refer to the
bearing manufacturer’s numbers.
Frame Inb. Brg.
F-20-E4 6039
Lubrication Out. Brg.
GREASE 5308
Part No.
AC0685
FIGURE 2 – FRAME PLATE
Permanent records for this pump are referenced
by the Serial Number and it must, therefore, be
used to order all spare and replacement parts. The
last digit indicates the specific pump on orders for
more than one pump. For example, if an order
called for six pumps, all pumps would have the
same first three sets of digits and the last digit will
change to identify each of the six. (e.g. 1-21937-1-
, 1-21937-1-2, etc.)
1
The identification number is a number which the
end user of the pump requests to be put on the
3
SAFETY INSTRUCTION
The warning and caution decals located on the
pump are there for the safety of anyone involved
with the installation, operation, and maintenance
of the pump. PLEASE READ THE DECALS
CAREFULLY.
SAFETY
INSTRUCTION
This safety alert symbol will be used in this manual
and on the pump safety instruction decals to draw
attention to safety related instructions. When used
the safety alert symbol means ATTENTION!
BECOME ALERT! YOUR SAFETY IS INVOLVED!
FAILURE TO FOLLOW THE INSTRUCTIONS
MAY RESULT IN A SAFETY HAZARD.
WARNING:
Do not operate pump at or near zero flow
(closed discharge shutoff valve). Explosion could
result due to large temperature rise in the fluid
being pumped. Failure to follow these instructions
could result in property damage, severe personal
injury, or death.
WARNING:
If pump is to be used on process fluids
above 120°F, pump surface temperatures could
be warm enough to cause burns. We
recommended pump surfaces be insulated or
appropriately guarded. Failure to follow these
instructions could result in severe personal injury.
4
INSTALLATION
RECEIVING THE PUMP
Check the pump for damage immediately upon
arrival. (An absolute must!) Prompt reporting of
any damage to the carrier’s agent, with notations
made on the freight bill, will expedite satisfactory
adjustment by the carrier.
Pumps and drivers are normally shipped from the
factory mounted on a baseplate. Couplings may
either be completely assembled or have the
coupling hubs mounted on the shafts and the
connecting members removed. When the
connecting members are removed, they will be
packaged in a separate container and shipped
with the pump or attached to the baseplate.
LIFTING THE PUMP
The following instructions are for the safe lifting of
the Series 8100 pump.
The pump unit should be unloaded and handled
by lifting equally at four or more points on the
baseplate. The lugs on the upper half casing are
designed for lifting the upper half casing only.
Horizontal
1. Bare Pump (Model 100)
WARNING: Falling Objects Hazard
Eyebolts or lifting lugs, if provided, are for
lifting only the components to which they are
attached. Failure to follow these instructions could
result in serious personal injury or death, or
property damage.
Using a nylon sling, chain, or wire rope,
hitch around both bearing supports (See
Figure 3).
2. Pump, Base, and Driver (Model 150)
NYLON SLING,
CHAIN OR WIRE
ROPE
CHOKER HITCH
AROUND
BEARING
FRAME
FIGURE 3 – MODEL 100
Pump, base, and driver assemblies where
the base length exceeds 100 inches may
not be safe to lift as a complete assembly.
Damage to the baseplate may occur. If the
driver has been mounted on the baseplate
at the factory, it is safe to lift the entire
assembly. If driver has not been mounted
at the factory and the overall baseplate
lengths exceeds 100 inches, do not lift the
entire assembly consisting of pump, base,
and driver. Instead lift the pump and
baseplate to its final location without the
driver. Then mount the driver.
Bases supplied with lifting holes:
Large bases are supplied with lifting holes
in the sides or the ends of the base (See
Figure 4).
Care must be taken to size equipment for
unbalanced loads which may exist if the
motor is not mounted on the base at the
time of lifting. Motor may or may not be
mounted at the factory.
45º MAX
FIGURE 4 – MODEL 150
5
Using ANSI/OSHA Standard “S” hooks,
place the “S” hooks in the holes provided
in the four corners of the base. Be sure
the points of the hooks do not touch the
bottom of the pump base. Attach nylon
slings, chains, or wire rope to the “S”
hooks. Size the equipment for the load,
and so the lift angle will be less than 45°
from the vertical.
Bases supplied without lifting holes:
Place one sling around the outboard
bearing housing. Place the remaining sling
around the back end of the motor as close
to the mounting feet as possible. Make
sure the sling does not damage the
housing cover or conduit box.
Join the free ends of the slings together
and place over the lifting hook. Use
extreme care when positioning sling under
the motor so it cannot slip off (See
Figure 5).
or wire rope using latch hook or standard
shackle and end loop.
NYLON SLING,
CHAIN, OR
WIRE ROPE
30º
MAX
45º
MAX
FIGURE 5 – MODEL 150
Vertical
1. Half Pedestal (Model 200)
WARNING: Falling Objects Hazard
Eyebolts or lifting lugs, if provided, are for
lifting only the components to which they are
attached. Failure to follow these instructions could
result in serious personal injury or death, or
property damage.
Place nylon sling, chain or wire rope
around both flanges. Use a latch hook or
standard shackle and end loops.
FIGURE 6 – MODEL 200
Be sure to use shoulder eyebolts that are
manufactured per ANSI B18.15 and sized
to fit the holes provided.
Be sure lifting equipment is of sufficient
length to keep the lift angle less than 30°
from the vertical (See Figure 7).
Be sure the lifting equipment is of
sufficient length to keep the lift angle less
than 30° from the vertical (See Figure 6).
2. Full Pedestal (Model 300)
Install eyebolts in the three holes provided
at the top of the support, being sure to
tighten securely. Attach nylon sling, chain
6
NYLON SLING,
30º
MAX
CHAIN, OR
WIRE ROPE
FIGURE 7 – MODEL 300
STORAGE
The following storage procedures apply to the
Series 8100 pump only. Other accessories such
as motors, steam turbines, gears, etc., must be
handled per the respective manufacturer’s
recommendations.
Temporary
Temporary storage is considered one month
or less. If the pump is not installed and
operated soon after arrival, store it in a clean,
dry place that has slow, moderate changes in
ambient temperature. Rotate the shaft
periodically to coat the bearings with lubricant
and to retard oxidation, corrosion, and to
reduce the possibility of false brinelling of the
bearings. Shaft extensions and other
exposed machine surfaces should be coated
with an easily removable rust preventative
such as Ashland Oil Tectyl No. 502C.
For oil lubricated bearings, fill the frame
completely with oil. Before putting equipment
into operation, drain the oil and refill to proper
level.
Cortec Corp. VCI-329 (for both grease and oil
lubricated bearings). Seal all vents and apply
a water proof tape around the oil seals in the
bearing frame. Remember for pumps with oil
lubricated bearings to drain the oil from the
frame and refill to the proper level before
running the pump.
LOCATION
The pump should be installed as near to the
suction supply as possible, with the shortest and
most direct suction pipe practical. The total
dynamic suction lift (static lift plus friction losses in
suction line) should not exceed the limits for which
the pump was sold.
When installing the pump, consider its location in
relation to the system to assure that sufficient Net
Positive Suction Head (NPSHA) is available at the
pump inlet connection. Available NPSH (NPSHA)
must always equal or exceed the required NPSH
(NPSHR) of the pump.
The pump must be primed before starting.
Whenever possible, the pump should be located
below the fluid level to assure priming. This
condition provides a positive suction head on the
pump. It is also possible to prime the pump by
pressurizing the suction vessel.
The pump should be installed with sufficient
accessibility for inspection and maintenance. A
clear space with ample head room should be
allowed for the use of an overhead crane or hoist
to lift the unit.
NOTE: Allow a sufficient amount of space to
dismantle pump without disturbing the pump
suction and discharge piping.
Select a dry place above the floor level wherever
possible. Take care to prevent pump from freezing
during cold weather when not in operation. Should
the possibility of freezing exist during a shut-down
period, the pump should be completely drained,
and all passages and pockets where liquid might
collect should be blown out with compressed air.
Make sure there is a suitable power source
available for the pump driver. If motor driven, the
electrical characteristics of the power source
should be identical to those shown on motor data
plate.
Long Term
Storage longer than one month is considered
long term storage. Follow the same
procedure for temporary storage with the
following addition. Add one half ounce of a
corrosion inhibiting concentrated oil such as
FOUNDATION
The pump is built to provide years of service if
installed properly and attached to a suitable
foundation. A base of concrete weighing 2 ½ to 5
times the weight of the pump is recommended.
7
The foundation should be poured without
interruption to within 1/2 to 1 ½ inches of the
finished height. The top surface of the foundation
should be well scored and grooved before the
concrete sets; this provides a bonding surface for
the grout.
FIGURE 9A – SETTING BASE PLATE AND
GROUTING YEAR 2000 STYLE BASE FOR
BOTH MOTOR AND ENGINE DRIVEN UNITS
BASEPLATE
Foundation bolts should be set in concrete as
shown in Figure 8. An optional 4-inch long tube
around the bolts at the top of the concrete will
allow some flexibility in bolt alignment to match the
holes in the base plate. Allow enough bolt length
for grout, shims, lower base plate flange, nuts and
washers. The foundation should be allowed to
cure for several days before the base plate is
shimmed and grouted.
FOUNDATION
PIPE SLEEVE
BOLT
(OPTIONAL)
WASHER
BUILT-UP
CONCRETE FOUNDATION
FIGURE 8 – FOUNDATION
SHIMS
GROUT
FORM
BOLT
SLEEVE
ANCHOR BOLT
CONCRETE
FIGURE 9B – GROUTING PRE-YEAR 2000
STYLE BASE FOR MOTOR DRIVEN UNITS
a. Use blocks and shims under base for
support at anchor bolts and midway
between bolts, to position base
approximately 1" above the concrete
foundation, with studs extending through
holes in the base plate.
b. By adding or removing shims under the
base, level and plumb the pump shaft and
flanges. The base plate does not have to
be level.
BASE PLATE SETTING (BEFORE PIPING)
NOTE: This procedure assumes that a concrete
foundation has been prepared with anchor or hold
down bolts extending up ready to receive unit. It
must be understood that pump and motor have
been mounted and rough aligned at the factory. If
motor is to be field mounted, consult factory for
recommendations. AC Fire Pump CANNOT assume
responsibility for final alignment.
NOTE:
TO KEEP SHIMS IN
ALLOW 1” FOR SHIMS.
PLACE ON BOTH SIDES
OF ANCHOR BOLTS.
LEVELING OF PUMP BASE ON
CONCRETE FOUNDATION.
PLACE ALLOW GROUT
TO FLOW AROUND
HOLD DOWN LUGS.
GROUT
GROUT ONLY
TO TOP OF
BASE RAIL.
PUMP
BASE RAIL
CONCRETE
FOUNDATION
c. Draw anchor nuts tight against base, and
observe pump and motor shafts or
coupling hubs for alignment. (Temporarily
remove coupling guard for checking
alignment.)
d. If alignment needs improvement, add
shims or wedges at appropriate positions
under base, so that retightening of anchor
nuts will shift shafts into closer alignment.
Repeat this procedure until a reasonable
alignment is reached.
NOTE: Reasonable alignment is defined as
that which is mutually agree upon by pump
contractor and the accepting facility (final
operator). Final alignment procedures are
covered under “Alignment Procedures.”
e. Check to make sure the piping can be
aligned to the pump flanges without
placing pipe strain on either flange.
f. Pour grout in the base plate completely
(See “Grouting Procedure”) and allow
grout to dry thoroughly before attaching
8
piping to pump. (24 hours is sufficient time
with approved grouting procedure.)
GROUTING PROCEDURE
Grout compensates for uneven foundation,
distributes weight of unit, and prevents shifting.
Use an approved, non-shrinking grout, after
setting and leveling unit (See Figure 9).
a. Build strong form around the foundation to
contain grout.
b. Soak top of concrete foundation
thoroughly, then remove surface water.
c. Base plate should be completely filled with
grout.
d. After the grout has thoroughly hardened,
check the foundation bolts and tighten if
necessary.
e. Check the alignment after the foundation
bolts are tightened.
f. Approximately 14 days after the grout has
been poured or when the grout has
thoroughly dried, apply an oil base paint to
the exposed edges of the grout to prevent
air and moisture from coming in contact
with the grout.
dried thoroughly according to instructions. Final
alignment should be made by shimming driver
only. Alignment should be made at operating
temperatures.
WARNING: Unexpected Start-up Hazard
Disconnect and lock out power before
servicing. Failure to follow these instructions could
result in serious personal injury or death and
property damage.
ANSI/OSHA COUPLER GUARD
REMOVAL/INSTALLATION
WARNING: Unexpected Start-up Hazard
Disconnect and lock out power before
servicing. Failure to follow these instructions could
result in serious personal injury or death and
property damage.
NOTE: Do not spread the inner and outer guards
more than necessary for guard removal or
installation. Over spreading the guards may alter
their fit and appearance.
Removal
a. Remove the two capscrews that hold the
outer (motor side) coupler guard to the
support bracket(s).
ALIGNMENT PROCEDURE
NOTE: A flexible coupling will only compensate for
small amounts of misalignment. Permissible
misalignment will vary with the make of coupling.
Consult coupling manufacturer’s data when in
doubt.
Allowances are to be made for thermal expansion
during cold alignment, so that the coupling will be
aligned at operating temperature. In all cases, a
coupling must be in alignment for continuous
operation. Even though the coupling may be
lubricated, misalignment causes excessive wear,
vibration, and bearing loads that result in
premature bearing failure and ultimate seizing of
the pump. Misalignment can be angular, parallel,
or a combination of these, and in the horizontal
and vertical planes. Final alignment should be
made by moving and shimming the motor on the
base plate, until the coupling hubs are within the
recommended tolerances measured in total runout. All measurements should be taken with the
pump and motor foot bolts tightened. The shaft of
sleeve bearing motors should be in the center of
its mechanical float.
NOTE: Proper alignment is essential for correct
pump operation. This should be performed after
base plate has been properly set and grout has
b. Spread the outer guard and pull it off the
inner guard.
c. Remove the capscrew that holds the inner
guard to the support bracket.
d. Spread the inner guard and pull it over the
coupler.
Installation
a. Check coupler alignment before
proceeding. Correct if necessary.
b. Spread the inner guard and place it over
the coupler.
c. With the inner guard straddling the
support bracket, install a capscrew
through the hole (or slot) in the support
bracket and guard located closest to the
pump. Do not tighten the capscrew.
d. Spread the outer guard and place it over
the inner guard.
e. Install the outer guard capscrews by
following the step stated below which
pertains to your particular pump:
i. For pumps with a motor saddle support
bracket: Ensure the outer guard is
9
straddling the support arm, and install
but do not tighten the two remaining
capscrews.
ii. For pumps without a motor saddle
support bracket: Insert the spacer
washer between the holes located
closest to the motor in the outer guard,
and install, but do not tighten, the two
remaining capscrews.
ANSI/OSHA Coupling Guard Exploded View
For Typical 8100 Series Fire Pump Installation
OUTER GUARD
LOCATE SUPPORT ARM
BETWEEN OUTER GUARD ENDS.
ALIGN THE ARM WITH HOLES IN
THE OUTER GUARD AND HOLES
IN THE SADDLE BRACKET.
f. Position the outer guard so it is centered
around the shaft, and so there is less than
a 1/4" of the motor shaft exposed. On
guards that utilize a slotted support
bracket, the inner guard will have to be
positioned so there is only a 1/4" of the
pump shaft exposed.
g. Holding the guard in this position, tighten
the three capscrews.
INNER GUARD
ATTACH SUPPORT BRACKET
TO BEARING HOUSING
SUPPORT
BRACKET
NUT
LOCKWASHER
MOTOR SADDLE
BRACKET ATTACH
TO MOTOR SADDLE
CAPSCREW
FLAT WASHER
SPACER WASHER
THIS OPTION USED IN PLACE OF
SPACER WHERE OVERALL LENGTH
OF GUARD EXCEEDS 12 INCHESOR
GUARD WITH IS OVER 10 INCHES
ACROSSTHE FLATS.
Method 1 – Straight Edge Alignment for
Standard Sleeve Type Coupler with Black
Rubber Insert
(See Figure 10A)
Proceed with this method only if satisfied that
face and outside diameters of the coupling
halves are square and concentric with the
coupling borers. If this condition does not
exist or elastomeric couplings do not make
this method convenient, use Method 2.
1. Check angular misalignment using a
micrometer or caliper. Measure from the
outside of one flange to the outside of the
opposite flange at four points 90° apart.
DO NOT ROTATE COUPLER.
BRACKET SUPPORT
ATTACHED INSIDE HERE
IN LINE WITH BOLT
BRACKET
SUPPORT
Misalignment up to 1/64" per inch of
coupler radius is permissible.
2. At four points 90° apart (DO NOT
ROTATE COUPLER), measure the
parallel coupler misalignment by laying a
straight edge across one coupler half and
measuring the gap between the straight
edge and opposite coupler half. Up to a
1/64" gap is permissible.
10
STRAIGHT EDGE
FEELER GAGE
ANGULAR ALIGNMENT PARALLEL ALIGNMENT
INCORRECT ALIGNMENT
i. For single element couplings, a
satisfactory parallel misalignment is
.004"T.I.R., while a satisfactory angular
misalignment is .004"T.I.R. per inch of
radius R (See Figure 10B).
PARALLEL
ALIGNMENT
DIAL
INDICATOR
STRAIGHT EDGE
FEELER GAGE
CORRECT ALIGNMENT
FIGURE 10A – CHECKING ALIGNMENT
(METHOD 1)
Method 2 – For Orange Hytrel Insert, 3500
RPM Operation, or All Other Coupler
Types Except as Noted Below
(See Figure 10B)
a. Make sure each hub is secured to its
respective shaft and that all connecting
and/or spacing elements are removed at
this time.
b. The gap between the coupling hubs is set
by the manufacturer before the units are
shipped. However, this dimension should
be checked. (Refer to the coupling
manufacturer’s specifications supplied
with the unit.)
c. Scribe index lines on coupling halves as
shown in Figure 10B.
d. Mount dial indicator on one hub as shown
for parallel alignment. Set dial to zero.
e. Turn both coupling halves so that index
lines remain matched. Observe dial
reading to see whether driver needs
adjustment (See paragraph i below).
f. Mount dial indicator on one hub as shown
for angular alignment. Set dial to zero.
g. Turn both coupling halves so that index
lines remain matched. Observe dial
reading to see whether driver needs
adjustment (See paragraph i below).
h. Assemble coupling. Tighten all bolts and
set screw(s). It may be necessary to
repeat steps c through f for a final check.
INDEX LINE
RESILIENT
SEPARATOR
ANGULAR
ALIGNMENT
DIAL
INDICATOR
FIGURE 10B – CHECKING ALIGNMENT
(METHOD 2)
Grid Couplings
NOTE: The following procedure is intended
for mounting and alignment of Rexnord
Industries, LLC. and Clarke Fire Protection
Products, Inc., Tapered Grid Couplings.
Adequate lubrication is essential for
satisfactory operation. Grease supplied by
the coupling manufacturer is highly
recommended. Other greases to be used
should be approved by the coupling
manufacturer.
Alignment is shown using a spacer bar and
straight edge. Rexnord Industries, LLC. and
Clarke Fire Protection Products, Inc. state
this practice has been proven for many
industrial applications. Superior alignment
can be achieved through the use of dial
indicators as shown above.
1. Clean all metal parts using non-flammable
solvent.
2. Lightly coat seals with coupling vendor
supplied grease and place on shafts
before mounting shaft hubs.
3. Install keys and mount hubs with flange
faces flush with shaft ends or as otherwise
specified.
4. Reposition hubs on shafts as required to
achieve the required hub gap shown in
Figure 10H or otherwise specified. The
length of engagement on each shaft
11
should be roughly equal to the shaft
diameter.
5. Tighten setscrews.
6. Bring the pump and motor halves of the
coupler into approximate height alignment,
by placing equal amounts of shims under
all the motor feet.
7. Tighten the motor bolts.
8. Use a spacer bar equal in thickness to the
gap specified in Figure 10C. Insert bar, as
shown below, to same depth at 90°
intervals and measure clearance between
bar and hub face with feeler gauges. The
difference in minimum and maximum
measurements must not exceed the
angular installation limits shown in Figure
10H.
misalignment, strike the side of the motor
foot with a mallet.
11. Tighten the motor bolts and check again.
If a correction is made, re-check alignment
directions. Repeat this process until
in all
the desired result is obtained.
12. Pack gap and grooves with coupling
vendor supplied grease before inserting
grid. When grids are furnished in two or
more segments, install them so that all cut
ends extend in the same direction as
shown below. This will ensure correct grid
contact with non-rotating pin in cover
halves.
13. Spread the grid slightly to pass over the
coupling teeth and seat with a soft mallet.
FIGURE 10C – USING SPACER BAR
9. Align so that a straight edge rests (as
shown in Figure 10D) on both hubs and
also at 90° intervals without rotating the
coupling. Check with feelers. The
clearance must not exceed the
PARALLEL OFFSET installation limits
specified in Figure 10H.
FIGURE 10D – USING STRAIGHT EDGE
10. If adjustment is needed, loosen the motor
bolts and add (or remove) an equal
amount of shims under each motor foot to
align the height. To correct side
FIGURE 10E – SEATING THE GRID
14. Pack the spaces between and around the
grid with as much as coupling vendor
supplied grease as possible and wipe off
the excess until flush with the top of the
grid.
15. Position seals on hubs to line-up with
grooves in cover. Position gaskets on
flange of lower cover half and assemble
covers so that the match marks are on the
same side.
12
gaskets stay in position during fastener
tightening.
FIGURE 10G – COVER INSTALLATION,
VERTICAL POSITION
17. Ensure the lube plugs are installed in the
cover.
WARNING: Coupling Failure
FIGURE 10F – COVER INSTALLATION
16. If the shafts are not horizontal, or coupling
is to be used vertically, assemble cover
halves with the lug and match mark UP or
Do not operate coupling without proper lubrication
Failure to follow these instructions could result in
serious personal injury or death and property
damage.
on the high side. Push gaskets in until
they stop against the seals and secure
cover halves with fasteners, tightening to
torque specified in Figure 10H. Ensure
Final alignment cannot be accomplished until
the pump has been operated initially for a
sufficient length of time to attain operating
temperature. When normal operating
temperature has been attained, secure the
pump to re-check alignment and compensate
for temperature accordingly. See Alignment
Section.
WARNING: Rotating Components
Hazard
Do not operate pump without all guards in place.
Failure to follow these instructions could result in
serious personal injury or death and property
damage.
WARNING: Coupling Failure
Do not operate pump with coupling out of
alignment. Ensure final coupling alignment is
within the values stated above or according to the
coupling manufacturer’s instructions. Coupling,
pump, or driver failure may occur.
OPTIONAL Alignment Procedure
If desired, the pump and motor feet can be
doweled to the base after final alignment is
complete. This should not be done until the
unit has been run for a sufficient length of
time and alignment is within the tolerance.
See Doweling Section.
CAUTION: Extreme Temperature and/or
Flying Debris Hazard
Eye protection and gloves required. Failure to
follow these instructions could result in property
damage and/or moderate personal injury.
NOTE: Pump may have been doweled to
base at factory.
DOWELING
Pump units may, if desired, be dowelled on
diagonally opposite feet. This should not be done
until the unit has been run for a sufficient length of
time and alignment is within the above alignment
tolerance.
Failure to follow these instructions could result in
serious personal injury or death and property
damage.
DIAL INDICATOR
SEPARATORS TO
TAKE UP BEARING
PARALLEL ALIGNMENT ANGULAR ALIGNMENT
FIGURE 11 – CHECKING ALIGNMENT (METHOD 2)
REFERENCE
MAR
SLACK
14
SUCTION AND DISCHARGE PIPING
The introduction of a pump into a piping system
which is not well designed or adjusted may cause
strain on the pump, leading to misalignment or
even impeller rubbing. Since slight strain may go
unnoticed, final alignment should be done with the
system full.
Pipe flanges should not impose any strain on the
pump. This can be checked by a dial indicator.
Any strain must be corrected by adjustments in the
piping system.
Make sure that all piping joints are air-tight.
Where flanged joints are used, assure that inside
diameters match properly.
Remove burrs and sharp edges when making up
joints.
Do not “spring” piping when making any
connections.
Provide for pipe expansion when hot fluids are to
be pumped.
When installing the pump piping, be sure to
observe the following precautions:
Piping should always be run to the pump.
Do not move pump to pipe. This could make final
alignment impossible.
Both the suction and discharge piping should be
independently anchored near the pump and
properly aligned so that no strain is transmitted to
the pump when the flange bolts are tightened. Use
pipe hangers or other supports at necessary
intervals to provide support. When expansion
joints are used in the piping system they must be
installed beyond the piping supports closest to the
pump. Tie bolts and spacer sleeves should be
used with expansion joints to prevent pipe strain.
Do not install expansion joints next to the pump or
in any way that would cause a strain on the pump
resulting from system pressure changes. When
using rubber expansion joints, follow the
recommendations of the Technical Handbook on
Rubber Expansion Joints and Flexible Pipe
Connectors. It is usually advisable to increase the
size of both suction and discharge pipes at the
pump connections to decrease the loss of head
from friction.
Install piping as straight as possible, avoiding
unnecessary bends. Where necessary, use 45° or
long radius 90° fittings to decrease friction losses.
Suction Piping
When installing the suction piping, observe
the following precautions (See Figure 13).
The sizing and installation of the suction
piping is extremely important. It must be
selected and installed so that pressure losses
are minimized and sufficient liquid will flow
into the pump when started and operated.
Many NPSH (Net Positive Suction Head)
problems can be directly attributed to
improper suction piping systems.
Suction piping should be short in length, as
direct as possible, and never smaller in
diameter than the pump suction opening. A
minimum of ten (10) pipe diameters between
any elbow or tee and the pump should be
allowed. If a long suction pipe is required, it
should be one or two sizes larger than the
suction opening, depending on its length.
CAUTION:
An elbow should not be used directly
before the suction of a double suction pump if its
plane is parallel to the pump shaft. This can cause
an excessive axial load or NPSH problems in the
pump due to an uneven flow distribution (See
Figure 12). If there is no other choice, the elbow
should have straightening vanes to help evenly
distribute the flow.
15
WATER VELOCITY INCREASES
HERE, CAUSING A GREATER
FLOW TO ONE SIDE OF THE
IMPELLER
CASING
PUMP CASING
SUCTION
ELBOW
FIGURE 12 – UNBALANCED LOADING OF A DOUBLE SUCTION IMPELLER
DUE TO UNEVEN FLOW AROUND AN ELBOW ADJACENT TO THE PUMP
Eccentric reducers should be limited to one
pipe size reduction each to avoid excessive
turbulence and noise. They should be of the
conical type. Contour reducers are not
recommended.
When operating on a suction lift, the suction
pipe should slope upward to the pump
nozzle. A horizontal suction line must have a
gradual rise to the pump. Any high point in
the pipe can become filled with air and
prevent proper operation of the pump. When
reducing the piping to the suction opening
diameter, use an eccentric reducer with the
eccentric side down to avoid air pockets.
NOTE: When operating on suction lift never
use a concentric reducer in a horizontal
suction line, as it tends to form an air pocket
in the top of the reducer and the pipe.
Figure 13 shows some correct and incorrect
suction piping arrangements.
PUMP SUCTION
FLANGE
2. When foot valves are used, or where there
are other possibilities of “water hammer,”
close the discharge valve slowly before
shutting down the pump.
3. Where two or more pumps are connected
to the same suction line, install gate
valves so that any pump can be isolated
from the line. Gate valves should be
installed on the suction side of all pumps
with a positive pressure for maintenance
purposes. Install gate valves with stems
horizontal to avoid air pockets. Globe
valves should not be used, particularly
where NPSH is critical.
4. The pump must never be throttled by the
use of a valve on the suction side of the
pump. Suction valves should be used only
to isolate the pump for maintenance
purposes, and should always be installed
in positions to avoid air pockets.
IMPELLER
When installing valves in the suction piping,
observe the following precautions:
1. If the pump is operating under static
suction lift conditions, a foot valve may be
installed in the suction line to avoid the
necessity of priming each time the pump
is started. This valve should be of the
flapper type, rather than the multiple
spring type, sized to avoid excessive
friction in the suction line. (Under all other
conditions, a check valve, if used, should
be installed in the discharge line. See
Discharge Piping)
16
SUCTION PIPE INSTALLED
WITH A GRADUAL RISE TO PUMP
LEVEL
CENTER LINE
OF PIPE
AIR POCKET
GRADUAL RISE
TO PUMP
NO AIR
POCKETS
CORRECT
AIR POCKET
INCORRECT
AIR POCKET
INCORRECT
INCORRECT
NO AIR
POCKETS
CORRECT
GRADUAL RISE
TO PUMP
CHECK VALVE
GATE VALVE
INCREASER
Discharge Piping
If the discharge piping is short, the pipe
diameter can be the same as the discharge
opening. If the piping is long, the pipe
diameter should be one or two sizes larger
than the discharge opening. On long
horizontal runs, it is desirable to maintain an
even a grade as possible. Avoid high spots,
such as loops, which will collect air and
throttle the system or lead to erratic pumping.
A slow closing check valve and an isolating
gate valve should be installed in the
discharge line. The check valve (triple duty
valve), placed between pump and gate valve,
protects the pump from excessive back
pressure, and prevents liquid from running
back through the pump in case of power
failure. The gate valve is used in priming and
starting, and when shutting the pump down.
Pressure Gauges
Properly sized pressure gauges should be
installed in both the suction and discharge
nozzles in the gauge taps provided. The
gauges will enable the operator to easily
observe the operation of the pump, and also
determine if the pump is operating in
conformance with the performance curve. If
cavitation, vapor binding, or other unstable
operation should occur, widely fluctuating
discharge pressure will be noted.
ECCENTRIC
REDUCER
CORRECT
DISTANCE PLUS
ECCENTRIC REDUCER
STRAIGNTENS FLOW
CORRECT
PATH OF WATER
INCORRECT
FIGURE 13 – SUCTION PIPING
ARRANGMENTS
STUFFING BOX LUBRICATION
Contaminants in the pumped liquid must not enter
the stuffing box. These contaminants may cause
severe abrasion or corrosion of the shaft, or shaft
sleeve, and rapid packing or mechanical seal
deterioration; they can even plug the stuffing box
flushing and lubrication system. The stuffing box
must be supplied at all times with a source of
clean, clear liquid to flush and lubricate the
packing or seal. It is important to establish the
optimum flushing pressure that will keep
contaminants from the stuffing box cavity. If this
pressure is too low, fluid being pumped may enter
the stuffing box. If the pressure is too high,
excessive packing or seal wear may result; and
extreme heat may develop in the shaft causing
higher bearing temperatures. The most desirable
condition, therefore, is to use a seal water
pressure 15-20 psig above the maximum stuffing
box pressure.
If the pump system pressure conditions vary
during the day, packing adjustment becomes
17
difficult. Consideration should be given to using a
mechanical seal. (See Mechanical Seals.)
Packing
Standard pumps are normally packed before
shipment. If the pump is installed within 60
days after shipment, the packing will be in
good condition with a sufficient supply of
lubrication. If the pump is stored for a longer
period, it may be necessary to repack the
stuffing box. In all cases, however, inspect
the packing before the pump is started.
NOTE: Packing adjustment is covered in the
Maintenance section of this manual.
On some applications, it is possible to use
internal liquid lubrication (pumped liquid) to
lubricate packing. Only when all of the
following conditions prevail, can this be done:
1. Liquid is clean, free from sediment and
chemical precipitation and is compatible
with seal materials.
2. Temperature is above 32°F and below
160°F.
3. Suction pressure is below 75 psig.
4. Lubrication (pumped liquid) has lubricating
qualities.
5. Liquid is non-toxic and non-volatile.
When the liquid being pumped contains
solids or is otherwise not compatible with
packing materials, an outside supply of seal
liquid should be furnished. In general,
external-injection liquid (from an outside
source) is required when any of the above
conditions cannot be met.
The standard stuffing box consists of rings of
packing (see assembly section for number of
rings), a seal cage (optional), and a gland. A
shaft sleeve which extends through the box
and under the gland is normally provided to
protect the shaft.
A tapped hole is supplied in the stuffing box
directly over the seal cage to introduce a
clean, clear sealing medium. The stuffing box
must, at all times, be supplied with sealing
liquid at a high enough pressure to keep the
box free from foreign matter, which would
quickly destroy the packing and score the
shaft sleeve.
Only a sufficient volume of sealing liquid to create
a definite direction of flow from the stuffing box
inward to the pump casing is required, but the
pressure is important. Apply seal water at a rate of
approximately .25 GPM at a pressure
approximately 15 to 20 psig above the suction
pressure. (Approximately one (1) drop per
second.)
One recommended method to minimize error in
regulating flushing water is a “Controlled Pressure
System” (Figure 14). It is important to set the
pressure reducing valve adjusted to a value
slightly exceeding the maximum stuffing box
operating pressure (assuming it is reasonably
constant). A flow indicating device will detect a
failing of the bottom packing rings allowing
leakage in the pump.
External sealing liquid should be adjusted to the
point where the packing runs only slightly warm,
with a very slow drip from the stuffing box. Excess
pressure from an external source can be very
destructive to packing. More pressure is required,
however, for abrasive slurries than for clear
liquids. Examination of the leakage will indicate
whether to increase or decrease external
pressure. If slurry is present in the leakage,
increase the pressure until only clear liquid drips
from the box. If the drippage is corrosive or
harmful to personnel, it should be collected and
piped away.
A common error is to open the external piping
valve wide and then control the drippage by
tightening the packing gland. A combination of
both adjustments is essential to arrive at the
optimum condition. The life of packing and sleeve
depends on careful control more than any other
factor.
FLOWMETER
PRESSURE
GUAGE
STUFFING BOX
PRESSURE
REDUCING
VALAVE
FIGURE 14 – CONTROLLED PRESSURE
SYSTEM
18
Mechanical Seals
Mechanical seals are preferred over packing on
some applications because of better sealing
qualities and longer serviceability. When a seal is
properly installed, it will last longer than packing
on similar applications. A mechanical shaft seal is
supplied in place of a packed stuffing box when
specifically requested. The change from packing
to an alternate arrangement may be made in the
field by competent service personnel. Conversion
parts may be order from your AC Fire Pump Sales
Representative.
Just as with packing, the mechanical seal
chamber must be supplied, at all times, with a
source of clean, clear liquid to flush and lubricate
the seal. The most important consideration is to
establish the optimum flushing pressure that will
keep contaminants from the seal cavity. If this
pressure is too low, fluid being pumped may enter
the stuffing box. If the pressure is too high,
excessive seal wear may result.
When contaminants are present in the system
fluid, an external source of clean seal water must
be supplied. Supply approximately .25 GPM at a
pressure approximately 15 to 20 psig above the
suction pressure.
Figure 14 shows the recommended flush system
for mechanical seal. Water enters the seal
chamber, lubricates the seal face, and exits into
the pump itself. Positive flow in the seal water line
indicates adequate seal water pressure.
Cartridge Seals
Follow the appropriate lubrication directions for
mechanical seals given in this section. Most
cartridge seals provide flushing connections on
their glands. Use the cartridge seal gland flushing
taps (if provided) for your seal water connections
instead of the stuffing box tap. The quench taps on
the glands (if present) are normally only used in
chemical applications. Consult seal manufacturer’s
literature for more detailed information.
Cyclone Sediment Separators
If the fluid being pumped contains sediment and
there is no external, clean water source available
to flush the mechanical seals, a cyclone sediment
separator can be used to remove most of the
sediment from the liquid being pumped so it can
be used to flush the seals. The separator is placed
in the seal water piping line and removes the
sediment to an external drain (normally back to the
pump suction line).
19
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.