Xylem 795 User Manual

Manual
MJK Data Transmitter 795
Valid from software version 830434
COMLI PROTOCOL
MJK Automation A/S
Byageren 7 DK-2850 Nærum Denmark Tel: +45 45 56 06 56 Fax: +45 45 56 06 46 www.mjk.com
Station ID:
795 Type:
795 Serial no:
M795GB0503
Data Transmitter 795
Konformitetserklæring
Vi, MJK Automation A/S, DK-2850 Nærum, påtager os det fulde ansvar for at produktet
som denne erklæring angår, er i overensstemmelse med følgende standard(er) eller andre normdokument(er).
EN 50081-1:1995 EN 50082-1:1995
efter bestemmelserne i direktiv
89/336/EØF; 93/68/EØF
Declaration of Conformity
We, MJK Automation A/S, DK-2850 Nærum, declare under our sole responsibility that the product
MJK Data Transmitter 795
to which this declaration relates is in conformity with the following standard(s) or other normative document(s).
EN 50081-1:1995 EN 50082-1:1995
following the provisions of Directive
89/336/EWG; 93/68/EWG
Konformitätserklärung
Wir, MJK Automation A/S, DK-2850 Nærum, erklären in alleiniger Verantwortung, dass das Produkt
auf das sich diese Erklärung bezieht mit der/den folgenden Nor me(en) oder normativen Dokument(en) übereinstimmt.
EN 50081-1:1995 EN 50082-1:1995
Gemäss den Bestimmungen der Richtlinie
89/336/EWG; 93/68/EWG
Declaration de conformite
Nous, MJK Automation A/S, DK-2850 Nærum, déclarons sous notre seule responsabilité que le produit
auquel se réfère cette déclaration est conforme á la (aux) norme(s) ou autre(s) document(s) normatif(s)
EN 50081-1:1995 EN 50082-1:1995
conformément aux dispositions de Directive
89/336/EWG; 93/68/EWG
Dichiarazione di conformità
Noi, MJK Automation A/S, DK-2850 Nærum, dichiariamo sotto la nostra esclusiva responsabilità che l’apparecchio
MJK Data Transmitter 795
al quale questa dichiarazione si riferisce, è conforme alla seguente normativa(e) stand­ard o ad altri documenti di normativa(e)
EN 50081-1:1995 EN 50082-1:1995
conformemente alla disposizioni della Direzione
89/336/EWG; 93/68/EWG
Declaración de Conformidad
Nosotros, MJK Automation A/S, DK-2850 Nærum, declaramos bajo nuestra única responsabilidad que el producto
al cual se refiere esta declaración, está en conformidad con la(s) siguente(e) norma(s) u otros documentos normativos
EN 50081-1:1995 EN 50082-1:1995
según las disposiciones de la(s) directiva(s)
89/336/EWG; 93/68/EWG
M795GB0503
2
SW ver. 830434
Data Transmitter 795
Contents
1 Introduction .......................................... 5
1.1 Versions........................................................5
1.2 Communications protocols ........................... 5
1.3 MJK-Link™ .................................................. 6
1.4 About this manual ........................................ 6
1.5 Safety instructions ........................................6
1.6 Product identification .................................... 6
1.6.1 Standard versions 7
1.6.2 Versions with built-in options 7
2 Mechanical mounting ..........................8
2.1 Mounting on a wall ....................................... 8
3 Electrical mounting .............................. 9
3.1 Power supply................................................ 9
3.2 In- and output signals 9
3.2.1 I/O terminals, 8 DI/8 DO/4 AI 9
3.2.2 I/O terminals, 12 DI/4 DO/4 AI 10
3.2.3 I/O terminals, 16 DI/4 AI 10
3.3 Connection examples ................................. 11
3.3.1 Digital inputs 11
3.3.2 Digital outputs 11
3.3.3 Analogue inputs 11
3.3 Connection of Pump Controller 704 ...........12
3.4 Connection of communications ports ......... 12
3.4.1 Communications port 12
3.4.2 Built-in modem 12
4 The front panel ................................... 13
4.1 Display and keys 13
4.2 Menu structure ...........................................13
5 Functional menus ............................... 14
5.1.1 F0 - Program version, time and date 14
5.1.2 F0 - Interlock, operation or alarm signal 14
5.1.3 F0 - Internal flag, operation or alarm signal 14
5.1.4 F0 - Limits, high/low 14
5.1.5 F0 - Digital inputs, operation or alarm signal 14
5.2 F1 - Digital inputs on/off ............................. 14
5.3.1 F2 - Digital outputs on/off 14
5.3.2 F2 - Internal flag on/off 14
5.4 F3 - Limits - High/Low ................................ 15
5.5 F4 - Analogue input value # ........................ 15
5.5.1 F5 - Analogue input scaling 15
5.5.2 F5 - Analogue input on Pump Controller 704 15
5.6 F6 - Counter for inputs ...............................15
5.7 F7 - Counter for time ..................................15
5.8 F8 - Alarm / Alarm number ........................16
5.9.1 F9.1 - Stormflow volume 16
5.9.2 F9.2 - Stormflow calculation 16
5.10 F# - Modem/Line status .............................16
5.11 F* - Communication status ......................... 16
6 Programming of main functions........ 17
6.1 Select language ..........................................17
6.2 Set time and date ....................................... 17
6.3 Automatic change between
summer time and winter time .....................17
6.4 Access code enabled/disabled ................... 17
6.4.1 Enter password 17
6.5 Calculation of average values on
analogue inputs .......................................... 17
6.6 Data logging interval ...................................17
6.7 Tone / pulse dialing ..................................... 17
6.8 Alarm call on power failure.......................... 17
6.9 Number of incoming rings before answer ... 18
6.10 ID. no. for the Data Transmitter ................... 18
6.11 Automatic reset of alarms ...........................18
6.11.1 Call on automatic alarm reset 18
6.12 Start time for operational reports ................18
6.13 795 telephone number ...............................18
6.14 SMSC telephone number ...........................18
6.15 RS485 function........................................... 18
6.15.1 Master ID number 18
7 Programming of analogue inputs ..... 19
7.1 Select analogue input ................................. 19
7.2 0 - 20 or 4 - 20 mA input ............................ 19
7.3 Scaling at 0 / 4 mA ..................................... 19
7.4 Scaling at 20 mA ........................................19
7.5 Monitoring of high limit ............................... 19
7.5.1 Set high limit 19
7.5.2 High limit operation / alarm 19
7.5.3 Dialout on high limit 19
7.5.4 Signal delay for exceeding high limit 19
7.6 Monitoring of low limit ................................. 19
7.6.1 Set low limit 20
7.6.2 Low limit operation / alarm 20
7.6.3 Dialout on high limit 20
7.6.4 Signal delay for exceeding low limit 20
7.7 Divisor ........................................................20
8 Programming of digital inputs ........... 20
8.1 Select a digital input ................................... 20
8.2 NO or NC ................................................... 20
8.3 Operational or alarm input ..........................20
8.3.1 Dialout on alarm 20
8.4 Signal delay ................................................20
9 Programming of digital outputs ........21
9.1 Select a digital output ................................. 21
9.2 NO or NC ................................................... 21
9.3 Time controlled output................................ 21
9.4 ON time ...................................................... 21
9.4.1 Time before start 21
M795GB0503
3
SW ver. 830434
Data Transmitter 795
10 Programming of logical functions ..... 21
10.1 Select the output to receive the result
of the logical function.................................. 21
10.2 Select logical function .................................21
10.2.1 Select signals for the logical function 21
10.2.2 Operational or alarm signal on
internal flag 22
10.2.3 Dialout when alarm signal on
internal flag 22
10.2.4 Signal delay on internal flag 22
11 Programming of interlock .................. 22
11.1 Interlock of this station ................................ 22
11.2 Interlock interval.......................................... 22
11.3 Selection of substation ...............................22
11.4 Interlock active / inactive ............................ 23
11.4.1 Start of interlock 23
11.4.2 Stop interlock 23
11.4.3 Receivers telephone / ID number 23
11.4.4 Receiver's output 24
12 Programming of Pump Controller(s) . 25
12.1 704 connected ...........................................25
12.2 Call on alarm or system error on 704 .......... 25
12.2 Programming of the
internal Pump Controller .............................25
12.2.1 Select level signal 25
12.2.2 Start level for pump no. 1 25
12.2.2 Stop level for pump no. 1 25
12.2.3 Levels in use in 795 25
12.2.4 Start level for pump no. 2 25
12.3.2 Stop level for pump no. 2 25
12.3.3 Alternation of pumps 25
13 Telephone list for alarms ................... 26
13.1 Telephone number 1-9 ............................... 26
13.2 Number type .............................................. 26
13.2.1 Telephone number 26
13.2.2 Enter pager message 26
13.2.3 Enter SMS message 27
13.2.4 Pause between calls 27
15 Programming of 702 ComTroller ....... 29
15.1 Select 702 ..................................................29
16 Alarms ................................................. 30
16.1 Operational or alarm signal ......................... 30
16.2 Alarm calls .................................................. 30
16.3 Reset of alarms .......................................... 30
15.3.1 Automatic reset of alarms 30
17 Factory settings ................................. 31
18 Signal lists .......................................... 33
19 Register list ......................................... 37
20 Menu structure ................................... 44
20.1 Functional menus .......................................44
20.2 Programming menus ..................................45
A Appendix............................................. 50
A1 Technical specifications .............................. 50
A2 Number of signals available ........................50
A3 Inputs and outputs ..................................... 50
A4 Dimensions ................................................. 50
B Appendix............................................. 51
B1 Maintenance ............................................... 51
B2 Service codes ............................................. 51
B2.2 Forced setup
without reset of datalogger 51
B2.3 Forced setup
including reset of datalogger 51 B2.4 Baud rate and communication method 51 B2.5 Activation of SIM card for GSM/GPRS
modem 51 B2.6 Total reset 51
B3 Software upgrade .......................................51
B4 SMSC telephone numbers .........................52
B5 Spare parts................................................. 52
14 Programming of stormflow calculation .. 27
14.1 Stormflow calculation .................................27
14.2 Stormflow calculation in use ....................... 28
14.2.1 Zero point input no. 28
14.2.2 Level signal for flow calculation 28
14.2.3 Number of Q(h) points 28
14.2.4 Height value [h] for level point 28
14.2.5 Flow value [Q] for level point 28
M795GB0503
4
SW ver. 830434
Data Transmitter 795
1 Introduction
Thank you for choosing an MJK Data Transmitter
795. A great effort has been put into developing a product, which complies with all demands.
MJK Data Transmitter 795 is mounted in the field and with its digital in- and output and analogue input it is capable to receive and transmit most types of digital and analogue signals. From a built-in RS232 serial port, the MJK Data Trans­mitter 795 can communicate directly with other equipment i.e. a pc, PLC or a Scada system.
MJK Data Transmitter 795 can with one click on the mouse or from a telephone call activate digital output and/or read in- and outputs, alarm signal type for the latest 9 alarms and all logged data.
All settings, alarms and logged data can be read in the display, from easy to use functionnal menus.
MJK Data Transmitter 795 can be supplied in versions that communicates via a built-in GSM modem or telephone modem, or in versions for radio modem.
MJK Data Transmitter 795 is easy to install and operate, but read the instruction manual carefully in order to make optimum use of the unit.
You can allways contact your sales reprsentative or the MJK Automation Hotline in case of doubt or for guidance. Try also to log onto http:// www.mjk.com.
1.1 Versions
MJK Data Transmitter 795 is as standard supplied in the following hardware versions:
- 8, 12 or 16 digital inputs
- 0,4 or 8 digital outputs
- 4 analogue inputs
- 1 or 2 RS232 ports
Display of a pumping station from a pc with the
monitoring program MJK-Link™.
MJK Data Transmitter 795 can also be program­med to make a telephone call when there is an alarm and transmit the alarm as text to a pc or SCADA system and to a cell phone as SMS text. The Data Transmitter 795 has a bult in battery for telephone calls at power failure.
The RS 232 ports is used as connection to MJK Pump Controller 704 and to connection of a PC for configuration or reading of data in the field for i.e. a portable PC or for configuration or reading of data, when the Data Transmitter 795 is used as data logger.
1.2 Communications protocols
MJK Data Transmitter 795 can be connected to a distribution station either through a serial connection (RS232-RS 485), a built-in Hayes compatible telephone modem, a data radio or a GSM modem.
Communication complies with one protocol which must be followed by master and slave. Data Transmitter 795 is always the slave, i.e. the Data Transmitter must receive a command before it can reply. MJK Data Transmitter 795 is supplied with Comli PLC-protocol as standard. The following historical data are available in this protocol:
- Time counter on digital inputs, total, total today, total yesterday and the latest 24 hours, all with 1 hour interval.
An MJK Data Transmitter 795 with built-in modem
can transmit alarms as SMS messages directly to
the cell phone of employee on duty.
M795GB0503
- Analogue values stored with 5 min. interval 24 hours back, and in the extended log with a user defined logging interval.
5
SW ver. 830434
1.3 MJK-Link™
The Windows based program MJK-Link™ can be applied to monitor one or several MJK Data Transmitter 795. Via a PC with modem it is possible with MJK-Link™ to read values, modify setpoints and read datalogger for e.g. storm flow values. All settings in Data Transmitter 795 can be implemented via MJK-Link™.
Furthermore, MJK Link™ can be used to control the MJK Pump Comtroller 704. This facitily is used when e.g. MJK Data Transmitter 795 and MJK Pump Controller 704 is used together.
This manual covers MJK Data Transmitter 795 in Comli versions for communication via telephone modem, GSM modem or closed radio networks.
1.4 About this manual
The manual is divided into 4 main sections:
1: Introduction
Presentation of Data Transmitter 795 and this manual.
Data Transmitter 795
Explosion hazardous areas
MJK Data Transmitter 795 is not approved for
use in explosion hazardous areas.
All current local and national standards and regulations regarding installation and use of Ex approved material, certifications and safety instructions for Ex equipment that have been used in connection with installation of Data Trans­mitter 795 must be strictly observed.
1.6 Product identification
Check that the item(s) delivered corresponds to the ordered item(s). The item number is printed on a label that is sticked onto the packing.
2: Mounting
Information for performing mechanical and electrical mounting.
3: Basic settings
A look through the most common settings.
4: Field operation
A look through all settings for special applications of Data Transmitter 795.
1.5 Safety instructions
1: Read this manual carefully.
2: Be aware of the environment on the installa-
tion site. Wear necessary protective equipment and follow all current safety regulations.
3: MJK Data Transmitter 795 can give out start
signals to dangerous machinery. Therefore, it must be ensured that eventually connected machinery and other equipment are effectively being put out of service by i.e. removal of main fuses, lock main- and/or security switches in off position before commencing setting, fault finding, service and maintenance work etc.
➀➀
➀➀ ➁➁
➁➁
➂➂
➂➂
➃➃
➃➃
➀➀
Item number
➀➀ ➁➁
Item description
➁➁
➂➂
Serial number
➂➂ ➃➃
Communications program
➃➃
An identical marking can be found on the right hand side of the cabinet:
4: There is a risk of lethal electrical shock from
some of the terminals on Data Transmitter
795. Be careful not touch these while the unit is in operation.
Repair
1: Repair must only be made by MJK or a
representative approved by MJK.
M795GB0503
6
SW ver. 830434
Data Transmitter 795
1.6.1 Standard versions
This manual covers the following standard vers­ions with Comli protocol:
Item no.: In- and outputs: Communication:
204510 204511 204512 204520 204521 204522
MJK Data Transmitter 795 with 2 X RS232 and
4 AI / 8 DI / 8 DO 4 AI / 12 DI / 4 DO 4 AI / 16 DI / 0 DO
4 AI / 8 DI / 8 DO 4 AI / 12 DI / 4 DO 4 AI / 16 DI / 0 DO
built-in telephone modem.
(Item no. 204510/204511/204512)
2 × RS232 w. modem 2 × RS232 w. modem 2 × RS232 w. modem 1 × RS232 wo. modem 1 × RS232 wo. modem 1 × RS232 wo. modem
1.6.2 Versions with built-in options
The following type options can be built into Data Transmitter 795:
Varenr.: Betegnelse:
204570 Galvanically insulated RS232 port 204571 Galvanically insulated RS485 port 204572 Galvanically insulated port for TP 6000 204573 Galvanically insulated port for Niros UHF 204574 205105 GSM modem complete w. aerial 205106 GPRS modem complete w. aerial
Galvanically insulated port for external modem
The factory mounted options can be determined read on the terminal box lid:
MJK Data Transmitter 795 delivered from factory
with galvanically insulated communications port.
MJK Data Transmitter 795 with 1 X RS232 and 1 x
communications option port.
(Item no. 204520/204521/204522)
MJK Data Transmitter 795 delivered from factory
with built-in GSM-modem.
For both types of option applies that the data transmitter is mounted and connected like a stan­dard data transmitter.
Please see separate documentation for the built­in options.
M795GB0503
7
SW ver. 830434
2 Mechanical mounting
Data Transmitter 795
explosion hazardous areas!
Data Transmitter 795 is IP65 enclosed, and can be mounted outdoors directly on a wall or a railing, eventually by means of MJK rain roof 200115 and MJK universal fitting 200205.
must not be mounted in
Data Transmitter 795
Dimensional drawing for mounting screws.
See also page 51.
MJK rain roof 200115 mounted on pole with MJK
universal bracket 200205.
Data Transmitter 795 can also be mounted in a panel by means of MJK panel mounting kit
200105.
Data Transmitter 795 mounted in a panel with MJK
panel mounting kit 200105.
2.1 Mounting on a wall
The cabinet is mounted using three screws. The upper screw is used for the suspension and the two lower screws is used to fix the cabinet.
Remove the terminal box lid to gain access to the
two lower mounting holes.
The cabinet is suspended by the upper screw and.
fastened with the two lower screws.
The distance between the mounting screws is shown on the dimensional drawing.
Please observe minimum distance if more than
one cabinet is mounted.
You will find a jig in full size at the back of this manual.
MJK Data Transmitter 795 must be mou
ted vertically in order to comply with the IP68
standard.
M795GB0503
X
Do not use a screw machine!
8
SW ver. 830434
Data Transmitter 795
3 Electrical mounting
Data Transmitter 795
explosion hazardous areas!
Data Transmitter 795 must not be connected to
the power supply before all connections are
Remove the terminal lid and the front panel to gain acces to all terminals.
3.1 Power supply
Data Transmitter 795 can be supplied from both 230 V AC and 24 V DC.
must not be mounted in
made.
Terminal: Designation:
Protective ground
N 230 V AC neutral
L 230 V AC live
- 24 V DC negative
+ 24 V DC positive
Please note, that 24 V DC will not be available on the terminals marked '24 V DC forsyning' unless the Data Transmitter is fed from the mains.
3.2 In- and output signals
Data Transmitter 795 is delivered in 3 different I/O variants; 4AI / 8DI / 8DO, 4AI / 12DI / 4DO and 4AI / 16DI respectively.
Specifications:
DI: Passive with common negative, max. 24 V DC.
(Optocoupler med 10 k serial resistor)
Trig voltage: < 1 V DC = Off, > 10 V DC = On, pulse length > 100 ms.
DO: Voltage free relay contacts,
max. 1 A @ 24 V DC / 0,5 A @ 48 V AC.
AI: 0/4 - 20 mA or 0 - 1 V DC.
Input impedance = 50 Ω.
3.2.1 I/O terminals, 8 DI/8 DO/4 AI
DO 1 DO 2 DO 3 DO 4
DO 1/2/3/4 common -
DO 5 DO 6 DO 7 DO 8
DO 5/6/7/8 common -
Shield for RS232 to 704
Signal ground for RS232 to 704
24 V DC out +
24 V DC out -
DI 1 + DI 2 + DI 3 + DI 4 + DI 1/2/3/4 common ­DI 5 + DI 6 + DI 7 + DI 8 + DI 5/6/7/8 common ­AI 1 + AI 1 ­AI 2 + AI 2 ­AI 3 + AI 3 ­AI 4 + AI 4 ­Rx for RS232 to 704 Tx for RS232 to 704
M795GB0503
9
SW ver. 830434
3.2.2 I/O terminals, 12 DI/4 DO/4 AI
Data Transmitter 795
DI 9 + DI 10 + DI 11 + DI 12 +
DI 9/10/11/12 common -
DO 1 DO 2 DO 3 DO 4
DO 1/2/3/4 common -
Screen for RS232 to 704
Signal ground for RS232 to 704
24 V DC out +
24 V DC out -
DI 1 + DI 2 + DI 3 + DI 4 + DI 1/2/3/4 common ­DI 5 + DI 6 + DI 7 + DI 8 + DI 5/6/7/8 common ­AI 1 + AI 1 ­AI 2 + AI 2 ­AI 3 + AI 3 ­AI 4 + AI 4 ­Rx for RS232 to 704 Tx for RS232 to 704
3.2.3 I/O terminals, 16 DI/4 AI
DI 9 + DI 10 + DI 11 + DI 12 +
DI 9/10/11/12 common -
DI 13 + DI 14 + DI 15 + DI 16 +
DI 13/14/15/16 common -
Screen for RS232 to 704
Signal ground for RS232 to 704
24 V DC out +
24 V DC out -
DI 1 + DI 2 + DI 3 + DI 4 + DI 1/2/3/4 common ­DI 5 + DI 6 + DI 7 + DI 8 + DI 5/6/7/8 common ­AI 1 + AI 1 ­AI 2 + AI 2 ­AI 3 + AI 3 ­AI 4 + AI 4 ­Rx for RS232 to 704 Tx for RS232 to 704
M795GB0503
10
SW ver. 830434
Data Transmitter 795
3.3 Connection examples
3.3.1 Digital inputs
The digital inputs are passive, i.e. they need to be supplied from an external power source or from the terminals marked '24 V'.
Note, that the inputs has common negative in groups of 4 inputs.
A common installation error is that an input is
not connected to the correct negative terminal!
The inputs can be individually configured to be normally open (NO) or normally closed (NC).
3.3.3 Analogue inputs
The analog inputs are passive. i.e. they must be supplied from an external power source or from the terminals marked '24 V'.
Every input have its own plus and negative termi­nal.
A common installation fault is that an input is
not connected to the correct negative terminal!
The input range can be individually configured to 0-20 mA or 4-20 mA.
Above diagram show an example of connecting two
switches to DI1 and DI2. Note the common
negative terminal!
3.3.2 Digital outputs
The digital outputs are voltage-free relay contacts with a capacity of max. 24 V DC / 1 A or max. 48 V AC / 0,5 A resistive load.
The outputs can be individually configured to be normally open (NO) or normally closed (NC).
M795GB0503
A passive mA signal
from a pressure
transmitter.
11
An active mA signal from
a level transmitter.
SW ver. 830434
3.3 Connection of Pump Controller 704
Only the RS232 port on the plug-in terminals of the Data Transmitter can be used for connecting a MJK Pump Controller 704. A screened, twisted pair cable must be used, and it should be connected as shown below:
Data Transmitter 795
The shield must not be connected to the Pump Controller 704.
Max. cable length is 15 metres.
DO NOT CONNECT
3.4 Connection of communications ports
(Only item no. 204520 / 21 / 22.)
3.4.1 Communications port
All options listed in section 1.6.2 is supplied with a flat cable, that just need to be mounted in the communications port socket on the lower PCB.
See also separate documentation for the option in question.
THE SHIELD IN
THIS END!
3.4.2 Built-in modem
The built-in modem can be connected to a telephone outlet with the enclosed RJ11 cable. If the modem should be connected to a terminal, the cable should be stripped and only the red og blue wire need to be connected. The two other wires are not used.
M795GB0503
12
SW ver. 830434
Data Transmitter 795
4 The front panel
Display
2 x 24 digit backlit alphanumerical display for indication of user menus and measuring values.
4.1 Display and keys
Numerical keys
The keys 0-9, #, used to enter
are
*
telephone numbers, delays, analogue scaling etc.
ESC. key
This key is used to go back to the previous menu, or to cancel a selection. Press this key 2 or 3 times to revert to functional indication.
Functional key F
The function key are used for selecting the different functional menus to be displayed. The illustration show the function menu F0 for program version, time and date.
MENU key
This key is used to switch between main menus and submenus.
ENTER key
The ENTER kry is used to change between the main menu and submenus and to go through the submenus. The ENTER kay is always used to confirm a selection in a submenu.
Arrow keys
The arrow keys are sed for altering the current setting. In a sub-menu the current selection is always shown in the upper line, and the alternative selection is shown in brackets in the lower line. The arrow keys are used to select an alternative setting. The arrow keys are also used to select input and output number.
The key increase and the key
decrease a value.
4.2 Menu structure
Above figure is an overview of the general function of the functional keys.
INDICATION
MENUS
MAIN
MENU
SUBMENU W.
SELECTION
SUBMENU W.
SELECTION
See also page 42.
MAIN
MENU
M795GB0503
13
SW ver. 830434
5 Functional menus
Data Transmitter 795
5.1.1 F0 - Program version, time and date
Menu F0 displays date og and time. Moreover, it will display the current communications protocol and program version.
5.1.2 F0 - Interlock, operation or alarm signal
Menu F0 followed by 1 x 'down arrow' will display which signals that initiate the 9 programmable in­terlock sequences:
'A': alarm signal, '+': operation signal, '-': not in use.
5.1.3 F0 - Internal flag, operation or alarm signal
Menu F0 followed by 2 x 'down arrow' will display which signals that are linked to the internal flags:
5.2 F1 - Digital inputs on/off
Menu F1 indicates if the digital inputs are set ON or OFF. Up to 8 inputs are shown simultaneously.
If there are more than 8 inputs, the remaining inputs will be displayed by pressing one of the arrow keys:
Note, that a delay period can be set for every di­gital input so that the digital input can go ON for a short period without triggering an eventual alarm.
When the input is OFF, an empty field is shown. When the input goes ON, a flashing field is shown during the delay time, after which a field is shown constantly.
5.3.1 F2 - Digital outputs on/off
Menu F2 displays whether the digital outputs are set ON or OFF:
'A': alarm signal, '+': operation signal, '-': not in use.
5.1.4 F0 - Limits, high/low
Menu F0 followed by 2 x 'down arrow' will indicate which analogue inputs that are linked to a high/low alarm limit, and also if the limit will release an operational or alarm signal:
'A': alarm signal, '+': operation signal, '-': not in use.
5.1.5 F0 - Digital inputs, operation or alarm signal
Menu F0 followed by 4 (and 5) x 'down arrow' display which digital inputs, that releases an ope­ration or alarm signal:
'A': alarm signal, '+': operation signal, '-': not in use.
A delay period can be set for every digital output. This delay period must run out before the output are activated.
When the output is OFF, an empty field is shown. When the output goes ON, a flashing field are shown during the delay time, after which a field are shown constantly.
5.3.2 F2 - Internal flag on/off
Menu F2 followed by 1 x 'down arrow' will display the status for the internal flags.
M795GB0503
14
SW ver. 830434
Data Transmitter 795
5.4 F3 - Limits - High/Low
Menu F3 indicates if high and low limit is ON or OFF for the analogue inputs. The first four digits indicate if the high limit setting is exceeded and the last four digits indicate if the low limit setting is exceeded:
A delay time can be set individually for each analogue input in that the the input can exceed the limit for a short period without activating an alarm.
An empty square is displayed when the limit is not exceeded. When the limit is exceeded, a solid square  is displayed. If a delay period is set, the square will flash during the delay period.
5.5 F4 - Analogue input value #
Menu F4 indicates the value of the analogue inputs as a bargraph:
Select the desired input with the arrow keys or the numeric keys.
5.5.1 F5 - Analogue input scaling
Menu F5 indicates the value of an analogue input as a percentage and the mA signal and as a scaled value:
Select the desired input with the arrow keys or the numeric keys.
5.5.2 F5 - Analogue input on Pump Controller 704
Menu F2 followed by 1 x 'down arrow' display the value of the analogue input on the Pump Controller 704 (if connected):
Please observe that the value is collected directly from the Pump Controller 704 and is not scaled.
5.6 F6 - Counter for inputs
Whenever a digital input or an analogue high/low limit is active, it will be recorded by a counter. The number is displayed in menu F6:
Use the arrow keys to change between:
- digital input 1 - 8/12/16
- analogue high limit 1 - 4
- analogue low limit 1 - 4
In addition, the numerical keys 1 - 8 can be used to select the desired input.
The selected counter can be reset by pressing the ENTER key.
5.7 F7 - Counter for time
Menu F7 indicate for how long the digital input and the analogue high and low limits have been active. Time counters is running continuously such as if the input is set to OFF for some time and then is set to ON, the counter will count from the last value. The time is displayed in hours and minutes:
The scaled value is determined by the programming of the analogue input.
If the value represents e.g. a level measurement in a tank, and the level normally varies between 2 m and 3 m, the analogue input will normally be programmed so 2 m corresponds with '200' (low value) and 3 m corresponds with '300' (high value).
A level of 2,5 m will then give a scaled readout of 250 and 50 %.
If the scaled value should be shown as '2,5', it is possible to set a divisor for each input. In this example the divisor should have the value 100.
See also section 7.
M795GB0503
Use the arrow keys to change between:
- digital input 1 - 8/12/16
- analogue high limit 1 - 4
- analogue low limit 1 - 4
In addition, the numerical keys 1 - 8 can be used to select the desired input.
The selected counter can be reset by pressing the ENTER key.
15
SW ver. 830434
Data Transmitter 795
5.8 F8 - Alarm / Alarm number
Menu F8 indicate if the last 9 alarms are ON or OFF:
Each time a new alarm is activated, it will be recorded as alarm no. 1 and all other recorded alarms will move down one place and alarm 9 will be deleted. When the alarm for one input has been ON one time it must be set to OFF before a new alarm from the same input is accepted as an alarm.
If the alarm has not been reset and another 9 alarms occur, i.e. the first alarm become no. 10 and therefore will become invisible in the alarm list, this alarm will be reset automatically.
A flashing square is shown when an alarm goes ON.
If the alarm are being reset but is still active, a so­lid square is shown constantly. When the alarm goes OFF again, a square is shown constantly.
By means of the arrow keys or by entering the alarm number, the status, type and timestamps for on and off time can be displayed. Whenever an alarm goes ON, the input number and start time will be recorded. Similarly, when the alarm is reset, the reset time is recorded, and when the alarm goes OFF, the end time will be recorded:
5.9.2 F9.2 - Stormflow calculation
Whenever a stormflow occur, the flow is
3
displayed as m
/h in menu F9-2:
5.10 F# - Modem/Line status
(Only for versions with built-in telephone modem or GSM modem.)
Menu F# displays the status of outgoing alarm calls or incoming calls:
The following is displayed during an incoming call:
The following is displayed during an outgoing alarm call to one of the telephone numbers in the telephone number list:
When Data Transmitter 795 interlocks another Data Transmitter 795 i.e. in order to perform a remote start or stop of a pump, the following is displayed:
'ID' indicates the ID number of the Data Transmit­ter itself.
If the Data Transmitter are configured as a Master in a multidrop system, the 'ID' can also be the ID number of a connected Slave unit.
Return to normal operating display with the arrow keys or by prssing the '0' key.
5.9.1 F9.1 - Stormflow volume
Menu F9 displays the recorded stormflow volume.
The counter can be reset with the ENTER key.
M795GB0503
5.11 F* - Communication status
Menu F* indicate the communication status on the serial port, the port to Pump Controller 704, and the built-in telephone modem:
795 serial: R = Rx, T = Tx, CD = Carrier Detect, RTS = Request to send og CTS = Clear to send.
704: R = Rx, T = Tx and = Pump Controller 704 not interlocked / Pump Controller 704 interlocked. The Pump Controller 704 signal to the Data Transmitter that the Pump Controller 704 will not activate any control outputs, because the Pump Controller are interlocked.
16
SW ver. 830434
Data Transmitter 795
6 Programming of main functions
6.1 Select language
Select the desired language with the arrow keys and confirm with ENTER.
6.2 Set time and date
Enter time and date with the numerical keys or the arrow keys. Confirm with ENTER:
Just press ENTER at all entries if changes are not needed in order to proceed to the next menu.
6.3 Automatic change between summer time and winter time
Select if the clock should change automatically between summer time and winter time:
6.5 Calculation of average values on analogue inputs
The value of an analogue input is recorded every second, and every 5 minutes the values is log­ged. If averaging of the analogue values are selected, an average of the analogue value over the last 5 minutes will be calculated and logged.
If averaging is not selected, the analogue value at the actual time will be logged.
Use the arrow keys to select and confirm with ENTER.
6.6 Data logging interval
The data logging interval is used for the extended logging function, where the value for the analogue input and the level from MJK Pump Controller 704 is stored.
Use the arrow keys to select and confirm with ENTER.
Just press ENTER at all entries if changes are not needed in order to proceed to the next menu:
6.4 Access code enabled/disabled
Select if an access code is required to gain ac­cess to the remaining system menus. This function make it possible to protect the system configuration from unauthorized changes:
Use the arrow keys to select and confirm with ENTER.
6.4.1 Enter password
If access code protection is selected, a 4-digit access code is required in order to gain access to the remaining system menus.
The interval between loggings can be chosen amongst the following values: 30 sec. (00:30), 1 min. (01:00), 5 min. (05:00), 10 min. (10:00), 30 min. (30:00) and 1 hour (60:00).
Use the arrow keys to select and confirm with ENTER.
6.7 Tone / pulse dialing
Select between pulse or tone dialing from a telephone modem:
Use the arrow keys to select and confirm with ENTER.
6.8 Alarm call on power failure
If alarm call at power failure is selected, the Data Transmitter will call the first telephone number in the telephone list when the power supply fail. A power failure will not be detected before the supply has been gone for minimum 30 sec. Hereby alarm calls on short power surges are avoided.
M795GB0503
Use the arrow keys to select and confirm with ENTER.
17
SW ver. 830434
Data Transmitter 795
6.9 Number of incoming rings before answer
Set the number of rings (1 to 5) before Data Transmitter 795 answer the call.
Use the arrow keys or numerical keys 1 to 5 to select and confirm with ENTER.
6.10 ID. no. for the Data Transmitter
The ID number is used for identification of the individual data transmitters.
Use the arrow keys or numerical keys and confirm with ENTER.
6.11 Automatic reset of alarms
Select if incoming alarms should be automatically reset when the alarm condition disappears.
6.13 795 telephone number
Enter the telephone number that the Data Trans­mitter is connected to. The number is used as ID no. in connection with transmission of SMS alarms through landlines.
Use the numerical keys and confirm with ENTER.
6.14 SMSC telephone number
SMS messages need to be dialed to a specific SMS gateway, that will handle the further trans­mission through the cellphone network.
Use the numerical keys and confirm with ENTER.
Telephone numbers to SMSC gateway can be found in Appendix B.
6.15 RS485 function
This function is only available on Data Transmitter 795 with RS485 port.
If 'NO' are selected, all incoming alarms need to be reset manually.
Use the arrow keys and confirm with ENTER.
6.11.1 Call on automatic alarm reset
If 'Automatic reset of alarms' have been selected as described in the previous section, there will be an option to select if the Data Transmitter should perform a call, if an alarm condition disappear and therefore releases an automatic reset of an alarm.
Use the arrow keys and confirm with ENTER.
6.12 Start time for operational reports
Many plant managers want to have the operational reports displaced so they will elapse between i. e. 07:00 to 06:59. Enter the desired displacement counted from midnight:
Select if this Data Transmitter 795 should be a Master (the unit sending out alarms), or if this Data Transmitter 795 should be a Slave which is interconnected to another Master via the RS485 port:
Use the arrow keys and confirm with ENTER.
6.15.1 Master ID number
Select the Master ID for this Data Transmitter 795 if it is set to Master, or select the Slave ID for the unit in the multidrop cluster which should receive alarms and relay them via modem or radio:
Use the arrow keys and confirm with ENTER.
Use the arrow keys or numerical keys and confirm with ENTER.
M795GB0503
18
SW ver. 830434
Data Transmitter 795
7 Programming of analogue inputs
7.1 Select analogue input
Select the desired analogue input with the arrow keys and confirm with ENTER.
7.2 0 - 20 or 4 - 20 mA input
Select input type with the arrow keys and confirm with ENTER.
7.3 Scaling at 0 / 4 mA
Set the scaling of the low (0/4) mA value.
NB! The setting for the low mA value must be lower than the setting for the high mA value! (See next section.)
Use the numerical keys and confirm with ENTER.
7.4 Scaling at 20 mA
Set the scaling of the high mA value.
7.5.1 Set high limit
Set the upper limit value that should cause a recording in the operational or alarm log - see also section 13, "Operational or alarm signal".
In case the input are not scaled, 20 mA on the analogue input will correspond to 9999.
Use the arrow keys or numerical keys and confirm with ENTER.
7.5.2 High limit operation / alarm
Select if a high limit excession should be recorded in the alarm log or the operational log ­see also section 15, "Operational or alarm signal".
Use the arrow keys and confirm with ENTER.
7.5.3 Dialout on high limit
Select if a high limit activation should cause a dialout attempt.
NB! The setting for the high mA value must be higher than the setting for the low mA value! (See previous section.)
Use the numerical keys and confirm with ENTER.
7.5 Monitoring of high limit
Select if exceeding a high limit should be recorded or not.
Use the arrow keys and confirm with ENTER.
Use the arrow keys and confirm with ENTER.
7.5.4 Signal delay for exceeding high limit
Select the period in which the analogue value can exceed the high limit without activating an alarm:
Use the arrow keys (double arrow for minutes and single arrow for seconds) and confirm with ENTER.
7.6 Monitoring of low limit
Select if exceeding a low limit should be recorded or not.
Use the arrow keys and confirm with ENTER.
M795GB0503
19
SW ver. 830434
Data Transmitter 795
8 Programming of digital inputs
7.6.1 Set low limit
Set the lower limit value that should cause a recording in the operational or alarm log - see also section 13, "Operational or alarm signal".
In case the input are not scaled, 0 / 4 mA on the analogue input will correspond to 0.
Use the arrow keys or numerical keys and confirm with ENTER.
7.6.2 Low limit operation / alarm
Select if a low limit excession should be recorded in the alarm log or the operational log - see also section 15, "Operational or alarm signal".
Use the arrow keys or numerical keys and confirm with ENTER.
7.6.3 Dialout on high limit
Select if a low limit activation should cause a dialout attempt.
(Maximum period is 8 hours.)
8.1 Select a digital input
Select the desired digital input with the arrow keys and confirm with ENTER.
8.2 NO or NC
Select if the input should be active (ON) when there is a signal on the input or passive (OFF) when there is no signal on the input.
Use the arrow keys and confirm with ENTER.
8.3 Operational or alarm input
Select if an activation of the input should be recorded in the alarm log or in the operational log
- see also section 15, "Operational or alarm sig­nal".
Use the arrow keys and confirm with ENTER.
8.3.1 Dialout on alarm
Select if an activation of the digital input should cause a dialout attempt:
Use the arrow keys and confirm with ENTER.
7.6.4 Signal delay for exceeding low limit
Select the period in which the analogue value can exceed the low limit without activating an alarm:
Use the arrow keys (double arrow for hours/ minutes and single arrow for seconds) and confirm with ENTER.
7.7 Divisor
Set the desired divisor value for the analogue in­put. The divisor has only significance for displaying of analogue values in function menu F5, and not to the values that are transmitted to other data transmitters or SCADA systems.
The divisor has no significance for the setting of high or low limits.
Use the arrow keys and confirm with ENTER.
8.4 Signal delay
Select the period in which the digital input can be active without causing an alarm or a recording of an operational signal: (Maximum period is 8 hours.)
Use the arrow keys (double arrow for hours/ minutes and single arrow for seconds) and confirm with ENTER.
Use the arrow keys or numerical keys and confirm with ENTER.
M795GB0503
20
SW ver. 830434
Data Transmitter 795
9 Programming of digital outputs
9.1 Select a digital output
Select the desired digital output with the arrow keys and confirm with ENTER.
9.2 NO or NC
Select if the relay contact should be open (NO) or closed (NC), when the output is not active.
Use the arrow keys and confirm with ENTER.
9.3 Time controlled output
Select if the output should go ON and stay ON when the Data Transmitter receive a start signal ('FIXED'), or if the output should go ON when the Data Transmitter receive a start signal and stay ON for a pre-set period of time ('TIME').
If 'FIXED' are selected, the Data Transmitter need a stop signal in order to deactivate the output.
10 Programming of logical functions
This menu gives the possibility to program simple logical functions like AND, OR, and SET/RESET based on different digital signals in both Data Transmitter 795 and the Pump Controller 704 (if connected).
Since it is also possible to set internal flags in Data Transmitter 795, it will be possible to make combina-tions of several logical function and thus obtain PLC-like logical functions in the Data Trans­mitter 795.
10.1 Select the output to receive the result of the logical function
The result of a logical function can be sent to an internal flag or directly to a digital output.
Select the desired signal with the arrow keys and confirm with ENTER.
10.2 Select logical function
Select the desired logical function for the signal.
Use the arrow keys and confirm with ENTER.
9.4 ON time
Select the period in which the output should be active, if the output is set to be 'TIME' controlled.
Use the arrow keys (double arrow for minutes and single arrow for seconds) and confirm with ENTER.
9.4.1 Time before start
Select the delay time for activation of the output relay. The delay time is from the moment the Data Transmitter receive an ON command and until the relay output will be activated.
Use the arrow keys (double arrow for minutes and single arrow for seconds) and confirm with ENTER.
Use the arrow keys and confirm with ENTER.
10.2.1 Select signals for the logical function
Select the signals to be used for the logical function.
In the left hand side of the display is shown the previous selected signal type to receive the result of the logical function together with the selected logical function.
In the right hand side of the display is shown the input signals for the selected logical function.
M795GB0503
21
SW ver. 830434
1: Select the upper input signal with the arrow
keys and confirm with ENTER.
2: After that, select the lower input signal and
confirm with ENTER. Please note, that DO1 and DO2 may be used by the pump controller function - see also section 12.
10.2.2 Operational or alarm signal on internal flag
If the signal type is selected as internal flag it is possible to select if an internal flag should be an operational signal or alarm signal.
Data Transmitter 795
11 Programming of interlock
With this function it will be possible for two Data Transmitters to send command to each other. E.g. one Data Transmitter can control a digital output on another Data Transmitter.
Furthermore, if a Pump Controller 704 is connected to a Data Transmitter, the output relays on the Pump Controller 704 can be controlled by another Data Transmitter 795.
11.1 Interlock of this station
This menu makes it possible to block remote commands from other Data Transmitters (substations).
Use the arrow keys and confirm with ENTER.
10.2.3 Dialout when alarm signal on internal flag
Selct if the internal flag should release an alarm call attempt on an alarm.
Use the arrow keys and confirm with ENTER.
10.2.4 Signal delay on internal flag
This menu is used to set the period in which both input signals should be active in order to set the internal flag.
Use the arrow keys and confirm with ENTER.
Note, that interlock of a connected Pump Controller 795 also will be blocked.
Use arrow keys and confirm with ENTER.
11.2 Interlock interval
This menu is used to set the interval for how often other Data Transmitters should be dialed for remote control.
The actual application and communication method is decisive for setting the interlock inter­val. As an example, in case communication are taking place through a dialed line, it would be expensive to exchange interlock commands between two Data Transmitters every 5 minutes, if it is about stopping a waste water pump in connection with an overrun.
Use arrow keys and confirm with ENTER.
The setting will be valid for all Data Transmitters (substations) that are being set to interlock in the following menus.
M795GB0503
11.3 Selection of substation
Select the Data Transmitter (substation) to be interlocked.
Use arrow keys and confirm with ENTER..
22
SW ver. 830434
Data Transmitter 795
11.4 Interlock active / inactive
Select if the previously chosen Data Transmitter (substation) should be interlocked.
Use arrow keys and confirm with ENTER.
11.4.1 Start of interlock
Select the signal initiating an interlock on the selected Data Transmitter (substation):
The following signals are available:
- internal flag 1-8
- digital input 1-8/12/16
- analogue limit HIGH 1-4
- analogue limit LOW 1-4
- 704 system error
- power failure
- 704 output 1-2
The following signals are available:
- internal flag 1-8
- digital input 1-8/12/16
- analogue limit HIGH 1-4
- analogue limit LOW 1-4
- 704 system error
- power failure
- 704 output 1-2
As long as the signal is ON, all calls will take place in the interlock interval previously chosen.
If the interlock interval is set to 10 minutes or more, the remote controlled output should be configured as time controlled with an ON-time set to more than 10 minutes (e.g. 15 minutes) to avoid a situation where the remote output is ON constantly caused by a communications error. (E.g. a broken telephone cable.) In this way it is ensured, that the output is switched OFF, if communications fail.
On error-free communication the ON-timer on the remote controlled output will be initialized on every call, and with that the output will stay ON as long as the controlling signal is active.
Only one call attemt will be made. In case the same signal are selected as both start condition and stop condition, the stop condition will be when the digital signal goes OFF.
Use the arrow keys and confirm with ENTER.
11.4.3 Receivers telephone / ID number
Enter the telephone number / ID number of the Data Transmitter to be interlocked.
Enter the ID number if radio modems are used.
If the receiver is another Data Transmitter which is directly connected to the same multidrop line via the RS485 port, the ID number of the Data Trans-
preceeded with a minus. (The F key is used
mitter to enter the minus character.)
Use arrow keys and confirm with ENTER.
11.4.2 Stop interlock
Select the digital signal that - when switched OFF
- will cause the Data Transmitter to call the other Data Transmitter and set an output OFF:
M795GB0503
Ex.: Data Transmitter ID 001 is supposed to
remote control Data Transmitter ID 003: Enter the ID number "- 003" into Data Transmitter 001.
If the receiver is another Data Transmitter which is communicating via data radio, the Data Trans­mitter's ID-nummer should be entered
without a
preceeding minus.
23
SW ver. 830434
Eks.: Data Transmitter ID 001 is supposed to
remote control Data Transmitter ID 003: Enter the ID number "003" into Data Transmitter 001.
If the receiving unit is another Data Transmitter which is communicating via telephone/GSM mo­dem, the telephone number to the Data Trans­mitter is entered here.
Data Transmitter 795
Please note, that only a Master Data Transmitter can directly remote control other Data Transmit­ters belonging to other clusters.
Use the numeric keys and confirm with ENTER.
11.4.4 Receiver's output
Select the desired digital output on the interlocked Data Transmitter:
Use the arrow keys and confirm with ENTER.
Ex.: Data Transmitter no. 1 is supposed to
remote control the Data Transmitter no. 3: Enter the telephone number "45560656" into Data Transmitter no. 1.
If the receiving unit is a Data Transmitter belonging to another cluster of Data Transmitters, the ID number / telephone number belonging to the Master in the cluster should be entered followed by the ID number of the desired Data Transmitter in the cluster.
Eks.: Data Transmitter 001 in the lower cluster is
remote controlling Data Transmitter 003 in the upper cluster: Enter telephone / ID­number "45560656-003" into Data Trans­mitter no. 001.
M795GB0503
24
SW ver. 830434
Data Transmitter 795
12 Programming of Pump Controller(s)
12.1 704 connected
Select if a MJK Pump Controller 704 are connected to the Data Transmitter:
Use the arrow keys and confirm with ENTER.
12.2 Call on alarm or system error on 704
Select if the Data Transmitter should perform a call caused by an alarm signal, a control signal or a system error signal from Pump Controller 704.
Calls will be made to the telphone numbers ente­red in the telephone number list in Data Transmit­ter 795.
Use the arrow keys and confirm with ENTER.
12.2 Programming of the internal Pump Controller
Select the number of pumps connected to Data Transmitter 795:
12.2.2 Start level for pump no. 1
Select the desired start level for pump no. 1:
Use the arrow keys and confirm with ENTER.
12.2.2 Stop level for pump no. 1
Select the desired stop level for the pump(s).
Use the arrow keys and confirm with ENTER.
12.2.3 Levels in use in 795
If 2 pumps are connected to Data Transmitter 795, two different start and stop levels are available.
Use the arrow keys and confirm with ENTER.
12.2.4 Start level for pump no. 2
Select the desired start level for pump no. 2:
Note, that DO1 and DO2 will be assigned to the internal pump controller. If '1' is selected, DO1 will be assigned as control relay for pump no. 1, and if '2' is selected, DO2 will also be assssigned as control relay (for pump no. 2).
Use the arrow keys and confirm with ENTER.
12.2.1 Select level signal
Select the desired level signal:
Select between one of the analogue inputs on Data Transmitter 795 or the analogu input on Pump Controller 704.
Use the arrow keys and confirm with ENTER.
Use the arrow keys and confirm with ENTER.
12.3.2 Stop level for pump no. 2
Select the desired stop level for pump no. 2:
Use the arrow keys and confirm with ENTER.
12.3.3 Alternation of pumps
Select if the pumps should be alternated.
Use the arrow keys and confirm with ENTER.
M795GB0503
25
SW ver. 830434
13 Telephone list for alarms
(Not valid for versions with radio modem.)
13.1 Telephone number 1-9
This menu contain a list where up to 9 telephone numbers can be entered.
The numbers in the list will be called in the same order they are entered.
Data Transmitter 795
The message can be different for the individual telephone numbers. Pager messages will be displayed in the pager together with a code for the alarm type that have caused the call.
An example: When digital input no. 5 on a Data Transmitter with telephone number 45560656 receives an alarm input, the code 05-45560656 will be sent to the pager.
The alarm codes are:
Use the numerical keys and confirm with ENTER.
13.2 Number type
Select the telephone number type for the current entry.
Select between SMS, ordinary telephone, pager or PC.
Note, that 'PAGER' will only be available on versions with built-in modem.
Use the arrow keys and confirm with ENTER.
13.2.1 Telephone number
Enter the telephone number.
The '#' key can be used to wait for dialing tone for calls from a local exchange. The '#' key can also give a 2 second break. E.g. 0#45 56 06 56**39: Dial 0, wait for dialing tone from city line, call 45560656, wait 4 seconds, and then call 39.
Use the numerical keys and confirm with ENTER. Max. number of digits is 17.
13.2.2 Enter pager message
If a telephone number is selected as a pager number, a pager message/code (e.g. the Data Transmitter's own telephone number) of maximum 17 digits can be entered here.
01 : Digital input no. 1 02 : Digital input no. 2 03 : Digital input no. 3 04 : Digital input no. 4 05 : Digital input no. 5 06 : Digital input no. 6 07 : Digital input no. 7 08 : Digital input no. 8 09 : Digital input no. 9 (option) 10 : Digital input no. 10 (option) 11 : Digital input no. 11 (option) 12 : Digital input no. 12 (option) 13 : Digital input no. 13 (option) 14 : Digital input no. 14 (option) 15 : Digital input no. 15 (option) 16 : Digital input no. 16 (option)
21 : Analogue limit no. 1 LOW 22 : Analogue limit no. 2 LOW 23 : Analogue limit no. 3 LOW 24 : Analogue limit no. 4 LOW
31 : Analogue limit no. 1 HIGH 32 : Analogue limit no. 2 HIGH 33 : Analogue limit no. 3 HIGH 34 : Analogue limit no. 4 HIGH
40 : MJK 704 system error 41 : MJK 704 output no. 1 42 : MJK 704 output no. 2 43 : MJK 704 output no. 3 44 : MJK 704 output no. 4
51: Internal flag no. 1 52: Internal flag no. 2 53: Internal flag no. 3 54: Internal flag no. 4 55: Internal flag no. 5 56: Internal flag no. 6 57: Internal flag no. 7 58: Internal flag no. 8
Use the numerical keys and confirm with ENTER.
M795GB0503
26
90 : MJK 795 power failure
SW ver. 830434
Data Transmitter 795
14 Programming of stormflow calculation
13.2.3 Enter SMS message
If the current telephone number type is selected as an SMS type, enter an SMS message/code of up to 8 digits:
Use the numerical keys and confirm with ENTER.
If the message is entered via the keypad of the Data Transmitter, the message can only consist of numbers, but with MJK-Link™ it will be possible to enter text messages.
The SMS message will be displayed on the cell phone with 'MJK 795' as headline followed by location and cause of the alarm and the SMS message.
Test the SIM card in a cell phone if the SMS messages are not received. Also, check if the telephone number to the receiving SMS gateway is correct.
Pager messages and SMS messages are delivered as telegraphic alarm to an external ser­ver, which implies that Data Transmitter 795 has no option to test that the telegraphic alarm has been received by the recipient.
13.2.4 Pause between calls
Enter a pause between the call attempts to the telephone numbers on the telephone list:
Use the numerical keys and confirm with ENTER.
14.1 Stormflow calculation
Data Transmitter 795 can calculate the flow of an overrun via a digital input an an analogue input.
MJK 795
MJK 501
MJK 7062
In above example, MJK Pressure Transmitter 7062 provides the level signal to the Data Trans­mitter, and an MJK Level Electrode 501 is mounted where the stormflow starts. By this, the level measurement is set to zero and flow is calculated by means of the level signal.
Usually, the Data Transmitter is connected to a Pump Controller 704 with a level transmitter with its measuring range adopted to the pump controller. The measuring range is normally higher than necessary for flow measurement, typically 10 m for the pump control and 10-20 cm for flow calculation. The accuracy on the level measurement of the pump controller is as the to­tal measuring range of the flow measurement.
M795GB0503
The Q/h curve of the weir must be entered in this menu such as the data transmitter can calculate the stormflow. Include as many Q(h) points as possible in order to obtain the highest possible calculation accuracy.
Below is demonstrated Q(h) curve and Q(h) table for a rectangular weir with side contraction:
Q(h) point no.: h[m] Q[m3]
1 0,00 0,00 2 0,01 48,71 3 0,02 137,78 4 0,03 253,12 5 0,04 389,70 6 0,05 544,62 7 0,06 715,92 8 0,07 902,17
27
SW ver. 830434
Data Transmitter 795
If these Q(h) values are entered in this menu, the resulting Q(h) curve will be as shown below, and the Data Transmitter will calculate the flow according to this curve:
Note, that Q
must be no more than
MAX
59.999 m3/
h.
14.2 Stormflow calculation in use
Select if stormflow calculation should be used:
Use the arow keys and confirm with ENTER.
14.2.3 Number of Q(h) points
In this menu the number of Q(h) points that are desired for the piece by piece linearization of the flow calculation.
The number of Q(h) points can be set from 1 and 9, as the zero point value will be provided to be 0
3
/h.
m
Use the arow keys and confirm with ENTER.
14.2.4 Height value [h] for level point
Enter the height [h] for the Q(h) point.
The entered value MUST be higher than that for the previous Q(h) point.
Use the numerical keys and confirm with ENTER.
14.2.5 Flow value [Q] for level point
Enter the volume [Q] for the Q(h) point.
14.2.1 Zero point input no.
Select the input that the level electrode are connedted to. This input will activate the storm­flow calculation.
The following inputs can be selected:
- 795: DI 1 - 8 / 12 / 16
- 795: High/low limit 1 - 4
- 704: Output 1 - 4
- Combi alarm 1 - 8
Use the arow keys and confirm with ENTER.
14.2.2 Level signal for flow calculation
Select the input that provide the level signal for the stormflow calculation:
The following inputs can be selected:
- 795: Al 1-4
- 704: Level
Use the numerical keys and confirm with ENTER.
The current flow value and the total stormflow value can be read in functional menu F9. See also section 5.10.
Use the arow keys and confirm with ENTER.
M795GB0503
28
SW ver. 830434
Data Transmitter 795
15 Programming of 702 ComTroller
If one or more 702 ComTrollers is connected to the Data Transmitter as multidrop units on the RS485 port, they can all be programmed via the Data Transmitter's keyboard and display. (The Data Transmitter must be the Master in the cluster.)
15.1 Select 702
Enter the ID number for the desired 702 ComTroller:
Use the arow keys and confirm with ENTER.
The Data Transmitter will now attempt to establish a connection with the selected 702 ComTroller:
If the selected 702 ComTroller does not respond, the connection attempt can be interrupted by pressing the ComTroller can be selected.
When the selected 702 ComTroller responds, svarer, the Data Transmitter's display and key­board can now be used for remote programming of the ComTroller:
The function will be interrupted by pressing the key.
key, whereafter another
*
*
M795GB0503
29
SW ver. 830434
16 Alarms
Data Transmitter 795
16.1 Operational or alarm signal
The digital inputs can be set to be either a operational or alarm signals.
An operational signal defines a non-critical con­dition, e.g. a signal that only need to be recorded in the operational log. It would typically be a sig­nal indicating whether a pump is running or not.
An alarm signal is a signal, which normally is not active and only becomes active when critical con­ditions occur, e.g. a thermal overload signal from a pump. Furthermore, an alarm signal has me­mory and reset, i.e. when the alarm signal becomes no-active, the previous active condition are remembered. This previous active condition must be reset by the user before a new change to active condition will be accepted as an alarm signal.
For both types of signals are applied that both the number of changes to active condition and the period of time where the signal has been active will be recorded in the alarm record.
16.2 Alarm calls
If 'Call on alarm' is selected, the Data Transmitter will call all the numbers in the telephone list star­ting with the first entry. Proceeding to the next number in the list will take place after a preset period of time -'Pause between calls'. See also section 13.
If a call is made to a modem on a SCADA main station, it will be the main station's task to reset the alarm and stop the dialout routine. If call are made to a pager or telephone, the dialout routine is stopped by making a call to the Data Transmit­ter. A tone will be heard in the handset. This will not reset the alarms, but only stop the dialout routine. See also section 15.3.1.
If another alarm occur during the dialout routine, the dialout routine will continue, and the new alarm will be reported in to the next number in the telephone list.
16.3 Reset of alarms
When an alarm signal becomes active, it will be visible in menu F8 (see section 5.8).
Whenever a digital alarm signal becomes active, the alarm will be present in menu F8.1. This menu will show the alarm type and start time together with a flashing symbol ''. The symbol will flash as long as the alarm has not been reset, and the symbol will appear solid when the alarm has been reset but still active.
The symbol disappear when the alarm has been reset and the alarm signal is inactive. When the symbol disappear, the stop time for the alarm is displayed instead of the start time.
In order to reset an alarm from the front panel of MJK Data Transmitter 795, the menu F8 must be shown. Then use the arrow keys to select the alarm to be reset. Reset the selected alarm by pressing ENTER. The symbol '' will then appear solid if the alarm signal is still active or disappear, if the alarm signal is no longer active. An alarm can also be reset from a SCADA system.
An alarm signal must have been reset and change from non-active to active condition in order to be visible in the alarm list again. This means that if you do not want to receive the same alarm call several times on the SCADA sta­tion, the alarm should not be reset. The Data Transmitter will then stop further alarm calls concerning that particular alarm even if the alarm signal change from non-active to active condition.
15.3.1 Automatic reset of alarms
If an alarm has not been reset, and another 9 alarms occur, meaning that the not yet reset alarm becomes no. 10 and therefore no longer will be visible in the alarm list, the alarm will be reset automatically, if the function 'Automatic reset of alarms' has been activated. See also section 6.11.
Versions with radio modem transmit all alarms to the main station (ID no. 0).
M795GB0503
30
SW ver. 830434
Data Transmitter 795
17 Factory settings
Main functions: Settings: Main functions: Settings:
Language English No. of rings before answer 1 Autochange summer/winter time No ID no. for data transmitter 1 Access code No Automatic alarm reset No Averaging of analog inputs No Call on auto alarm reset No Datalogging interval 00:30 (30 sek.) Start time for operational report 00:00 Tone/Pulse dialing Tone 795 telephone number ­Alarm call on power failure No SMSC telephone number -
Analogue inputs: AI1: AI2: AI3: AI4:
0-20mA/4-20mA 4-20 mA 4-20 mA 4-20 mA 4-20 mA Scaling @ 0/4 mA 0 0 0 0 Scaling @ 20 mA 9999 9999 9999 9999 High limit yes/no No No No No High limit value 999 999 999 999 High limit operational/alarm Operational Operational Operational Operational Signal delay (sec.) 0 0 0 0 Dialout on high limit No No No No Low limit yes/no No No No No Low limit value 0 0 0 0 Low limit operational/alarm Operational Operational Operational Operational Signal delay (sec.) 0 0 0 0 Dialout on high limit No No No No Divisor 0 0 0 0
Digital inputs: NO/NC: Operational/Alarm Alarm call Signal delay:
Digital indgang nr. 1-8/12/16 NO Operational No 0
Digital outputs: NO/NC: Time/Fixed: On time: Time before start:
DO no. 1-4/8 NO Time 10 sec. 5 sec.
Interlock: Setting: (Station 1-9)
Interlock of this station No Interlock interval 5 min + 0 Start of interlock DI 1 Stop of interlock DI 1 Receivers tel/ID no. 0 Receivers output DO 1
Pump control: Setting:
704 connected No 704 output alarm call No 704 system errror alarm call No 795 no. of pumps 0 795 start level 1 0 795 stop level 1 0 795 level 2 in use No 795 start level 2 0 795 stop level 2 0 795 alternation No
Telephone list:
Telephone no. 1-9 Available 0 0
M795GB0503
Type (PC/pager/ Telephone Pager/SMS
Tel/SMS): number: message:
31
Pause in min.:
SW ver. 830434
Storm flow calculation: Setting:
In use Yes/No No Zero point DI1 Level signal 704 level No of Q(h) points 9 Q(h) point no. 1 Level: 10 ; Flow (m Q(h) point no. 2 Level: 10 ; Flow (m Q(h) point no. 3 Level: 10 ; Flow (m Q(h) point no. 4 Level: 10 ; Flow (m Q(h) point no. 5 Level: 10 ; Flow (m Q(h) point no. 6 Level: 10 ; Flow (m Q(h) point no. 7 Level: 10 ; Flow (m Q(h) point no. 8 Level: 10 ; Flow (m Q(h) point no. 9 Level: 10 ; Flow (m
3
/h) : 1.11
3
/h) : 2.22
3
/h) : 3.33
3
/h) : 4.44
3
/h) : 5.55
3
/h) : 6.66
3
/h) : 7.77
3
/h) : 8.88
3
/h) : 9.99
Data Transmitter 795
M795GB0503
32
SW ver. 830434
Data Transmitter 795
g
18 Signal lists
PUMP STATION NO: MJK 795 ID NO: PUMP CONTROLLER TYPE:
NAME: SERIAL NO. MJK 795: CONTROLLER SERIAL NO.:
TELEPHONE NO.: DATE: SENSOR SERIAL NO.:
DATA TRANSMITTER MJK 795
MAIN FUNCTIONS
CODE: ANALOG
AVERAGING
YES NO TONE PULSE YES NO
ANALOG INPUT:
AI 1-4 SIGNAL NAME: 0-20 mA 4-20 mA Zero Span
AI 1
AI 2
AI 3
AI 4
ANALOG LIMITS:
DIAL METHOD DIALOUT ON
VOLTAGE ERROR
HIGH/LOW
LIMIT
0-9999
SIGNAL ALARM
DATA LOGGING INTERVAL
MM:SS
NO. OF RINGS BEFORE ANSWER
1-5
SIGNAL
DELAY
MIN:SEK
LOW LIMIT ANALOG INPUT 1
HIGH LIMIT ANALOG INPUT 1
M795GB0503
2
3
4
2
3
4
33
SW ver. 830434
DIGITAL INPUTS
Data Transmitter 795
DI 1-8 DI 1-12 DI 1-16
DI 1
DI 2
DI 3
DI 4
DI 5
DI 6
DI 7
DI 8
DI 9
DI 10
DI 11
DI 12
SIGNAL NAME: SIG-
NAL
ALARM NO NC
SIGNAL
DELAYED
MIN:SEC
DIAL VIA
TEL.:
DI 13
DI 14
DI 15
DI 16
DIGITAL OUTPUTS (@ 8 or 12 DI)
SIGNAL NAME: TIME FIXED NO NC
DO 1
DO 2
DO 3
DO 4
DO 5
DO 6
DO 7
DO 8
DELAY
BEFORE
START
MIN:SEC
ON-TIME
MIN:SEC
DO 9
DO 10
DO 11
DO 12
M795GB0503
34
SW ver. 830434
Data Transmitter 795
INTERLOCK
START INTERLOCK
PUMP CONTROLLER MJK 704 YES NO
STOP INTERLOCK
RECEIVERS OUTPUT NO.
RECEIVERS TEL NO.:
CONNECTED
ALARM CALL OUTPUT 1
ALARM CALL OUTPUT 2
ALARM CALL OUTPUT 3
ALARM CALL OUTPUT 4
ALARM CALL ON SYSTEM ERROR
TELEPHONE NUMBERS FOR ALARM CALLS
TELEPHONE NUMBER PC: TEL.: PAGER: SMS: PAGE / SMS MESSAGE:
NO. 1:
NO. 2:
NO. 3:
NO. 4:
NO. 5:
NO. 6:
NO. 7:
NO. 8:
NO. 9:
M795GB0503
35
SW ver. 830434
Data Transmitter 795
STORM FLOW CALCULATION
IN USE: YES: NO:
ZERO POINT:
LEVEL MEASUREMENT:
NO. OF Q(h) POINTS:
LEVEL: FLOW: (M3/h)
HEIGHT VALUE NO. 1:
HEIGHT VALUE NO. 2:
HEIGHT VALUE NO. 3:
HEIGHT VALUE NO. 4:
HEIGHT VALUE NO. 5:
HEIGHT VALUE NO. 6:
HEIGHT VALUE NO. 7:
HEIGHT VALUE NO. 8:
HEIGHT VALUE NO. 9:
COMBI ALARMS
IN USE:
YES / NO
COMBI ALARM 1: AND
COMBI ALARM 2: AND
COMBI ALARM 3: AND
COMBI ALARM 4: AND
COMBI ALARM 5: AND
COMBI ALARM 6: AND
COMBI ALARM 7: AND
COMBI ALARM 8: AND
ALARM
SIGNALS:
DELAY:
(MM:SS)
ALARM CALL:
YES / NO
M795GB0503
36
SW ver. 830434
Data Transmitter 795
19 Register list
ONLINE VALUES: I/O NO.: VALUE: DESCRIPTION:
Digital output 1 0 read/write Digital outputs are READ and WRITE signals Digital output 2 1 read/write Digital output 3 2 read/write Digital output 4 3 read/write Digital output 5 4 read/write Digital output 6 5 read/write Digital output 7 6 read/write Digital output 8 7 read/write Digital input 1 10 read Digital inputs are READ ONLY signals. Digital input 2 11 read Digital input 3 12 read Digital input 4 13 read Digital input 5 14 read Digital input 6 15 read Digital input 7 16 read Digital input 8 17 read Digital input 9 20 read Digital input 10 21 read Digital input 11 22 read Digital input 12 23 read Digital input 13 24 read Digital input 14 25 read Digital input 15 26 read Digital input 16 27 read Alarm input 1 30 read/reset Alarms are READ and RESET signals. Alarm input 2 31 read/reset Alarm input 3 32 read/reset Alarm input 4 33 read/reset Alarm input 5 34 read/reset Alarm input 6 35 read/reset Alarm input 7 36 read/reset Alarm input 8 37 read/reset Alarm input 9 40 read/reset Alarm input 10 41 read/reset Alarm input 11 42 read/reset Alarm input 12 43 read/reset Alarm input 13 44 read/reset Alarm input 14 45 read/reset Alarm input 15 46 read/reset Alarm input 16 47 read/reset Limit relay (high)1 50 read The condition of the limit relays can be read. Limit relay (high)2 51 read Limit relay (high)3 52 read Limit relay (high)4 53 read Limit relay (low)1 54 read Limit relay (low)2 55 read Limit relay (low)3 56 read Limit relay (low)4 57 read Limit relay (high)1 60 read/reset Alarms can be set and reset (cancelled). Limit relay (high)2 61 read/reset (0-255) Limit relay (high)3 62 read/reset Limit relay (high)4 63 read/reset Limit relay (low)1 64 read/reset Limit relay (low)2 65 read/reset Limit relay (low)3 66 read/reset Limit relay (low)4 67 read/reset 704 output 1 70 read/write An output (pump) can be activated if the level is higher 704 output 2 71 read/write than the stop level, or an output can be deactivated 704 output 3 72 read/write if the level is lower than the start level. 704 output 4 73 read/write 704 alarm 1 74 read/reset Read or reset alarm 704 alarm 2 75 read/reset Læs eller afstil alarm 704 alarm 3 76 read/reset Læs eller afstil alarm 704 alarm 4 77 read/reset Reset
Communication flag 102 read/write Bit 102 is set by the 795 on alarm transmission ans must be reset
Power failure 103 read/reset Reset 704 system error 104 read/reset Reset
704 Flow calculation possible 106 read/write Alarm bit for test alarm 107 read/reset Test alarm bit is set and reset on I/O107
100 read/write 101 read/write
by the main station when the alarm has been received.
105 read/write
110 read/write 111 read/write 112 read/write 113 read/write 114 read/write 115 read/write 704 Interlock status bit ( Read / Write bit)
M795GB0503
37
SW ver. 830434
Data Transmitter 795
ONLINE VALUES: I/O NO.: DESCRIPTION:
116 read/write
Internal flag 1 140 read/reset The Combi alarms are a combination of 2 signals ANDed together. The programming of the
Internal flag 2 141 read/reset The programming of the Combi alarms is made on the MJK Data transmitter 795. Internal flag 3 142 read/reset All the Combi Alarms are READ or RESET bits Internal flag 4 143 read/reset Internal flag 5 144 read/reset Internal flag 6 145 read/reset Internal flag 7 146 read/reset Internal flag 8 147 read/reset Test alarm 150 read/reset I/O150 activates a 2 min. timer which activates I/O 107
ONLINE VALUES: REG. NO.: VALUE: DESCRIPTION:
Digital outputs 1-8 0 0-255 The outputs can be read and set (0-255) Digital inputs 1-8 1 0-255 Inputs can be read (0-255) Digital inputs 9-16 2 0-255 Option Alarm inputs 1-8 3 0-255 Read an reset (0-255) Alarm inputs 9-16 4 0-255 Option Limit Switches 1-4 5 0-255 Read (0-255) Alarm limits 1-4 6 0-255 Read and reset (cancelled) (0-255) 704 output/alarm 1-4 7 0-255 (Outputs can only be controlled bit-wise !) Control signals 8 Read and reset (795 voltage failure and 704 system error)
Cluster and ID no. 10 0-255 Read Status for internal flags 11 Read Alarms from internal flags 12 Read and reset Test register 13 Writing 1 to this register activates a test procedure.
Password 15 Enter 1795 to enable change in the setup page (page 2) Analogue indgang 1 16 0-9999 Analogue indgang 2 17 0-9999 Analogue indgang 3 18 0-9999 Analogue indgang 4 19 0-9999 795 ID no. 20 1-247 704 level 21 0-1000 (0-255) 795 stormflow m³/h 22 0-65535 Extended log interval 23 0=30 sec. 1=1 min. 2=5 min. 3=10 min. 4=30 min. 5=1 hour 704 P1 start level 24 0-1000 704 P2 start level 25 0-1000 704 P3 start level 26 0-1000 704 P4 start level 27 0-1000 704 P1 stop level 28 0-1000 704 P2 stop level 29 0-1000 704 P3 stop level 30 0-1000 704 P4 stop level 31 0-1000 Al1 high limit value 32 0-9999 Analog limits can be read and set Al2 high limit value 33 0-9999 Al3 high limit value 34 0-9999 Al4 high limit value 35 0-9999 Al1 low limit value 36 0-9999 Al2 low limit value 37 0-9999 Al3 low limit value 38 0-9999 Al4 low limit value 39 0-9999 ID number from Inter, Master 40 Interlock output 41
795 P1 start level 44 0-9999 795 P2 start level 45 0-9999 795 P1 stop level 46 0-9999 795 P2 stop level 47 0-9999
117 read/write
Combi alarms is made on the MJK Data transmitter 795.
9
14
42 43
M795GB0503
38
SW ver. 830434
Data Transmitter 795
COUNTERS, 'TOTAL' REG. NO.: VALUE: DESCRIPTION:
DI 1 pulse counter 48 0-65535 Pulse counter can be read and set. DI 2 pulse counter 49 0-65535 DI 3 pulse counter 50 0-65535 DI 4 pulse counter 51 0-65535 DI 5 pulse counter 52 0-65535 DI 6 pulse counter 53 0-65535 DI 7 pulse counter 54 0-65535 DI 8 pulse counter 55 0-65535 DI 9 pulse counter 56 0-65535 DI 10 pulse counter 57 0-65535 DI 11 pulse counter 58 0-65535 DI 12 pulse counter 59 0-65535 DI 13 pulse counter 60 0-65535 DI 14 pulse counter 61 0-65535 DI 15 pulse counter 62 0-65535 DI 16 pulse counter 63 0-65535 DI 1 time counter 64 0-65535 Time counters can be read and set. DI 2 time counter 65 0-65535 Time counters counts in whole hours. DI 3 time counter 66 0-65535 DI 4 time counter 67 0-65535 DI 5 time counter 68 0-65535 DI 6 time counter 69 0-65535 DI 7 time counter 70 0-65535 Di 8 time counter 71 0-65535 DI 9 time counter 72 0-65535 DI 10 time counter 73 0-65535 DI 11 time counter 74 0-65535 DI 12 time counter 75 0-65535 DI 13 time counter 76 0-65535 DI 14 time counter 77 0-65535 DI 15 time counter 78 0-65535 DI 16 time counter 79 0-65535 Limit 1 (high) pulse 80 0-65535 Pulse counters can be read and set. Limit 2 (high) pulse 81 0-65535 Limit 3 (high) pulse 82 0-65535 Limit 4 (high) pulse 83 0-65535 Limit 1 (low) pulse 84 0-65535 Limit 2 (low) pulse 85 0-65535 Limit 3 (low) pulse 86 0-65535 Limit 4 (low) pulse 87 0-65535 Limit 1 (high) time 88 0-65535 Time counters can be read and set. (0-65535) Limit 2 (high) time 89 0-65535 Time counters counts in whole hours. Limit 3 (high) time 90 0-65535 Limit 4 (high) time 91 0-65535 Limit 1 (low) time 92 0-65535 Limit 2 (low) time 93 0-65535 Limit 3 (low) time 94 0-65535 Limit 4 (low) time 95 0-65535 704 output 1 pulse 96 0-65535 Pulse counters can be read and set. 704 output 2 pulse 97 0-65535 704 output 3 pulse 98 0-65535 704 output 4 pulse 99 0-65535 704 output 1 time 100 0-59999 Time counters can be read and set. (0-65535) 704 output 2 time 101 0-59999 Time counters counts in whole hours. 704 output 3 time 102 0-59999 704 output 4 time 103 0-59999 795 stormflow counter m³ 104 0-65535 704 pumped value P1 105 0-65535 704 pumped value P2 106 0-65535 704 pumped value P3 107 0-65535 704 pumped value P4 108 0-65535 704 value total 109 0-65535 704 capacity P1 112 0-65535 704 capacity P2 113 0-65535 704 capacity P3 114 0-65535 704 capacity P4 115 0-65535 Analogue 1 max value total 120 0-9999 Analogue 2 max value total 121 0-9999 Analogue 3 max value total 122 0-9999 Analogue 4 max value total 123 0-9999 704 level max value total 124 0-9999
M795GB0503
39
SW ver. 830434
COUNTERS, 'TODAY' REG. NO.: VALUE: DESCRIPTION:
DI 1 pulse counter 128 0-65535 DI 2 pulse counter 129 0-65535 DI 3 pulse counter 130 0-65535 DI 4 pulse counter 131 0-65535 DI 5 pulse counter 132 0-65535 DI 6 pulse counter 133 0-65535 DI 7 pulse counter 134 0-65535 DI 8 pulse counter 135 0-65535 DI 9 pulse counter 136 0-65535 DI 10 pulse counter 137 0-65535 DI 11 pulse counter 138 0-65535 DI 12 pulse counter 139 0-65535 DI 13 pulse counter 140 0-65535 DI 14 pulse counter 141 0-65535 DI 15 pulse counter 142 0-65535 DI 16 pulse counter 143 0-65535 DI 1 time counter 144 0-1440 Time counters count in whole minutes. DI 2 time counter 145 0-1440 DI 3 time counter 146 0-1440 DI 4 time counter 147 0-1440 DI 5 time counter 148 0-1440 DI 6 time counter 149 0-1440 DI 7 time counter 150 0-1440 DI 8 time counter 151 0-1440 DI 9 time counter 152 0-1440 DI 10 time counter 153 0-1440 DI 11 time counter 154 0-1440 DI 12 time counter 155 0-1440 DI 13 time counter 156 0-1440 DI 14 time counter 157 0-1440 DI 15 time counter 158 0-1440 DI 16 time counter 159 0-1440 Limit 1 (high) pulse 160 0-65535 Limit 2 (high) pulse 161 0-65535 Limit 3 (high) pulse 162 0-65535 Limit 4 (high) pulse 163 0-65535 Limit 1 (low) pulse 164 0-65535 Limit 2 (low) pulse 165 0-65535 Limit 3 (low) pulse 166 0-65535 Limit 4 (low) pulse 167 0-65535 Limit 1 (high) time 168 0-1440 Time counters count in whole minutes. Limit 2 (high) time 169 0-1440 Limit 3 (high) time 170 0-1440 Limit 4 (high) time 171 0-1440 Limit 1 (low) time 172 0-1440 Limit 2 (low) time 173 0-1440 Limit 3 (low) time 174 0-1440 Limit 4 (low) time 175 0-1440 704 output 1 pulse 176 0-65535 704 output 2 pulse 177 0-65535 704 output 3 pulse 178 0-65535 704 output 4 pulse 179 0-65535 704 output 1 time 180 0-1440 Time counters count in whole minutes. 704 output 2 time 181 0-1440 704 output 3 time 182 0-1440 704 output 4 time 183 0-1440 795 stormflow counter m³ 184 0-65535 704 pumped value P1 185 0-65535 704 pumped value P2 186 0-65535 704 pumped value P3 187 0-65535 704 pumped value P4 188 0-65535 704 value total 189 0-65535
Data Transmitter 795
M795GB0503
40
SW ver. 830434
Data Transmitter 795
COUNTERS, 'YESTERDAY' REG. NO.: VALUE: DESCRIPTION:
D1 1 pulse counter 208 0-65535 D1 2 pulse counter 209 0-65535 D1 3 pulse counter 210 0-65535 D1 4 pulse counter 211 0-65535 D1 5 pulse counter 212 0-65535 D1 6 pulse counter 213 0-65535 D1 7 pulse counter 214 0-65535 D1 8 pulse counter 215 0-65535 D1 9 pulse counter 216 0-65535 D1 10 pulse counter 217 0-65535 D1 11 pulse counter 218 0-65535 D1 12 pulse counter 219 0-65535 D1 13 pulse counter 220 0-65535 D1 14 pulse counter 221 0-65535 D1 15 pulse counter 222 0-65535 D1 16 pulse counter 223 0-65535 D1 1 time counter 224 0-1440 Time counters count in whole minutes. D1 2 time counter 225 0-1440 D1 3 time counter 226 0-1440 D1 4 time counter 227 0-1440 D1 5 time counter 228 0-1440 D1 6 time counter 229 0-1440 D1 7 time counter 230 0-1440 D1 8 time counter 231 0-1440 D1 9 time counter 232 0-1440 D1 10 time counter 233 0-1440 D1 11 time counter 234 0-1440 D1 12 time counter 235 0-1440 D1 13 time counter 236 0-1440 D1 14 time counter 237 0-1440 D1 15 time counter 238 0-1440 D1 16 time counter 239 0-1440 Limit 1 (high) pulse 240 0-65535 Limit 2 (high) pulse 241 0-65535 Limit 3 (high) pulse 242 0-65535 Limit 4 (high) pulse 243 0-65535 Limit 1 (low) pulse 244 0-65535 Limit 2 (low) pulse 245 0-65535 Limit 3 (low) pulse 246 0-65535 Limit 4(low) pulse 247 0-65535 Limit 1 (high) pulse 248 0-59999 Time counters count in whole minutes Limit 2 (high) pulse 249 0-59999 Limit 3 (high) pulse 250 0-59999 Limit 4 (high) pulse 251 0-59999 Limit 1 (low) pulse 252 0-59999 Limit 2 (low) pulse 253 0-59999 Limit 3 (low) pulse 254 0-59999 Limit 4 (low) pulse 255 0-59999 704 output 1 pulse 256 0-65535 704 output 2 pulse 257 0-65535 704 output 3 pulse 258 0-65535 704 output 4 pulse 259 0-65535 704 output 1 time 260 0-1440 Time counters count in whole minutes 704 output 2 time 261 0-1440 704 output 3 time 262 0-1440 704 output 4 time 263 0-1440 795 stormflow counter m³ 264 0-65535 704 pumped value P1 265 0-65535 704 pumped value P2 266 0-65535 704 pumped value P3 267 0-65535 704 pumped value P4 268 0-65535 704 value total 269 0-65535
M795GB0503
41
SW ver. 830434
Data Transmitter 795
LOG, 24 h á 5 min: REG. NO.: VALUE: DESCRIPTION:
Analogue input 1 288 The lowest logged value. Analogue input 1 575 The oldest logged value. Analogue input 2 576 The lowest logged value. Analogue input 2 863 The oldest logged value. Analogue input 3 864 The lowest logged value. Analogue input 3 1151 The oldest logged value. Analogue input 4 1152 The lowest logged value. Analogue input 4 1439 The oldest logged value. 704 level 1440 The lowest logged value. 704 level 1727 The oldest logged value.
LOG, 24 h á 1 h: REG. NO.: VALUE: DESCRIPTION:
D1 1 pulse counter 1728-1751 24 x time difference counters. D1 2 pulse counter 1752-1775 24 x time difference counters. D1 3 pulse counter 1776-1799 24 x time difference counters. D1 4 pulse counter 1800-1823 24 x time difference counters. D1 5 pulse counter 1824-1847 24 x time difference counters. D1 6 pulse counter 1848-1871 24 x time difference counters. D1 7 pulse counter 1872-1895 24 x time difference counters. D1 8 pulse counter 1896-1919 24 x time difference counters. D1 9 pulse counter 1920-1943 24 x time difference counters. D1 10 pulse counter 1944-1967 24 x time difference counters. D1 11 pulse counter 1968-1991 24 x time difference counters. D1 12 pulse counter 1992-2015 24 x time difference counters. D1 1 time counter 2016-2039 24 x time difference counters in minutes. D1 2 time counter 2040-2063 24 x time difference counters in minutes. D1 3 time counter 2064-2087 24 x time difference counters in minutes. D1 4 time counter 2088-2111 24 x time difference counters in minutes. D1 5 time counter 2112-2135 24 x time difference counters in minutes. D1 6 time counter 2136-2159 24 x time difference counters in minutes. D1 7 time counter 2160-2183 24 x time difference counters in minutes. D1 8 time counter 2184-2207 24 x time difference counters in minutes. D1 9 time counter 2208-2231 24 x time difference counters in minutes. D1 10 time counter 2232-2255 24 x time difference counters in minutes. D1 11 time counter 2256-2278 24 x time difference counters in minutes. D1 12 time counter 2280-2303 24 x time difference counters in minutes. Limit 1 (high) pulse 2304-2327 24 x time difference counters. Limit 2 (high) pulse 2328-2351 24 x time difference counters. Limit 3 (high) pulse 2352-2375 24 x time difference counters. Limit 4 (high) pulse 2376-2399 24 x time difference counters. Limit 1 (low) pulse 2400-2423 24 x time difference counters. Limit 2 (low) pulse 2424-2447 24 x time difference counters. Limit 3 (low) pulse 2448-2471 24 x time difference counters. Limit 4 (low) pulse 2472-2495 24 x time difference counters. Limit 1 (high) time 2496-2519 24 x time difference counters in minutes. Limit 2 (high) time 2520-2543 24 x time difference counters in minutes. Limit 3 (high) time 2544-2567 24 x time difference counters in minutes. Limit 4 (high) time 2568-2591 24 x time difference counters in minutes. Limit 1 (low) time 2592-2615 24 x time difference counters in minutes. Limit 2 (low) time 2616-2639 24 x time difference counters in minutes. Limit 3 (low) time 2640-2663 24 x time difference counters in minutes. Limit 4 (low) time 2664-2687 24 x time difference counters in minutes. 704 output 1 pulse 2688-2711 24 x time difference counters. 704 output 2 pulse 2712-2735 24 x time difference counters. 704 output 3 pulse 2736-2759 24 x time difference counters. 704 output 4 pulse 2760-2783 24 x time difference counters. 704 output 1 time 2784-2807 24 x time difference counters in minutes. 704 output 2 time 2808-2831 24 x time difference counters in minutes. 704 output 3 time 2832-2855 24 x time difference counters in minutes. 704 output 4 time 2856-2879 24 x time difference counters in minutes. 795 stormflow pulse 2880-2903 24 x time difference counters in minutes. 704 pumped value P1 2904-2927 24 x time difference counters in minutes. 704 pumped value P2 2928-2951 24 x time difference counters in minutes. 704 pumped value P3 2952-2975 24 x time difference counters in minutes. 704 pumped value P4 2976-2999 24 x time difference counters in minutes. 704 pumped value total 3000-3023 24 x time difference counters in minutes.
SPECIAL REGISTERS: REG. NO.: VALUE: DESCRIPTION:
795 Log interval in sec. 3068 Read only 795 Log Pointer 3069 Read only Software Release 3070 Read only Data Page 3071 READ and WRITE Register. 0=standard Comli 1= 704 COMLI, 2=795 Setup parameters,
3=Datalogger for 704 level, 4-7=Datalogger for Analogue 1-4
M795GB0503
42
SW ver. 830434
Data Transmitter 795
M795GB0503
43
SW ver. 830434
20 Menu structure
20.1 Functional menus
Data Transmitter 795
M795GB0503
44
SW ver. 830434
Data Transmitter 795
20.2 Programming menus
M795GB0503
45
SW ver. 830434
Data Transmitter 795
M795GB0503
46
SW ver. 830434
Data Transmitter 795
M795GB0503
47
SW ver. 830434
Data Transmitter 795
M795GB0503
48
SW ver. 830434
Data Transmitter 795
M795GB0503
49
SW ver. 830434
Appendix
Data Transmitter 795
A Appendix
A1 Technical specifications
Dimensions: 185 x 240 x 115 mm (h × w × d) Power supply: 230 / 115 V AC or 12 / 24 V DC Emergency power: Built-in accumulator for monitoring of power supply and emergency communication.
Power consumption: 15 VA (Approx.) Temperature range: - 20 … + 60 °C Material, housing: Polystyrol Material, lid: Makrolon Enclosure: IP 65 Ur: Real time clock with built-in battery backup
Kommunikation
Telephone / fax: Hayes compatible, auto dial, auto answer, 2400 / 4800 baud GSM / GPRS: 900 / 1800 MHz GSM / GPRS modem UHF: Data radio via RS 232 port APL / owned lines: RS 485 for owned lines (multidrop)
Accuracy: < ± ½ % for analogue inputs CE: EN50081-1, EN50082-1
Kapacitet for ca. 3 nødopkald pr. opladning á 12 timer.
A2 Number of signals available
Number of possible signals on a standard Data Transmitter 795
I/O Limit relays Counters Time counters Alarms
Analoge indgange 4 8 8 8 8 Digitale indgange 8/12/16 8/12/16 8/12/16 8/12/16 Digitale udgange 8/4/0
Antal i alt 20 8 16/20/24 16/20/24 16/20/24
Alle værdier overføres som i dag, i går og totalværdier.
A3 Inputs and outputs
Analogue inputs: 0/4 - 20 mA or 0 - 1 V DC. Input voltage = 50 Ω. Digital inputs: 8 / 12 / 16 DI, passive with common negative pole, max. 24 V DC. (Optocoupler with 10 k serial resistor)
Digital outputs: 0 / 4 / 8 DO, voltage free relay contacts, max. 1 A v. 24 V DC / 0,5 A v. 48 V AC. Digital I/O: Total 16 DI + DO Data communication: 2 x ports (RS 485 with item no. 204570 built-in)
Trig voltage: < 1 V DC = Off, > 10 V DC = On, pulse length > 100 ms.
A4 Dimensions
M795GB0503
50
SW ver. 830434
Data Transmitter 795
B Appendix
Appendix
B1 Maintenance
In case the function 'Alarm call at power failure' is acticvated, it is recommended to exchange the built-in accumulator yearly. Beyond this, MJK Data Transmitter 795 require no particular maintenance.
Check the accumulator by disconnecting the power and check if the Data Transmitter is able to perform a dialup sequence in order to transmit a power failure alarm.
When the power is disconnected, the display backlight will disappear immediately.
If 'Alarm call at power failure' is deacticvated, the display will be turned off completely after 20 - 40 sec. If 'Alarm call at power failure' is acticvated, the Data Transmitteren will start to dial the phone numbers in the telephone list in a period of max. 5 minutes, and then the Data Transmitter will shut down.
B2 Service codes
Data Transmitter 795 are equipped with functions that should not be operated by the end user.
Always contact MJK Hotline before the ser­vice codes are used!
B2.1 Universal access code
If the access code is unavailable, the acces code 1 1 1 1 can always be used.
See also separate documentation for GSM/GPRS option.
B2.6 Total reset
This code give access to a TOTAL RESET.
Enter
F 0 and 2 0 4 5.
B3 Software upgrade
The software is stored in EPROM, that just need to be exchanged for upgrading.
When the EPROM is exchanged, all basic settings and all logdata will be preserved, if the old software are version 800400 and onwards. All basic settings and logdata will be lost when upgrading software versions before 800400.
1: Read first the instruction that came with the
new EPROM.
2: Disable the function 'Alarm call at power
failure'. See section 6.8.
3: Disconnect the power supply to the Data
Transmitteren.
4: Remove the front panel by unscrewing the 4
retaining screws in each corner and flip it out of the cabinet. Note: DO NOT withdraw the
flat cable to the lower PCB!
B2.2 Forced setup without reset of datalogger
If this code is used, the user will be forced to go through all settings. The logged data will not be erased.
F 0 followed by 1 2 3 4.
Enter
B2.3 Forced setup including reset of
datalogger
If this code is used, the user will be forced to go through all settings. All logdata will also be
erased!
F 0 followed by 4 3 2 1.
Enter
B2.4 Baud rate and communication method
This code give access to menus for setting the baud rate for the serial port and to select communication method (GSM/GPRS/Pager/ internal modem etc.).
F * followed by 2 0 4 5.
Enter
B2.5 Activation of SIM card for GSM/GPRS
modem
Enter
F # followed by * * 0 5 *.
Note the notch in
the EPROM!
5: Remove the old EPROM.
Mount the new EPROM in the socket marked 'IC4' (see illustration above). Make sure the EPROM is mounted in the correct orientation!
6: Reassemble the front and connect the power
source to the Data Transmitter.
7: All basic setting must be confirmed.
It is very important that the hardware setup settings are correct!
Data Transmitter 795 is now ready for operation.
M795GB0503
51
SW ver. 830434
B4 SMSC telephone numbers
The SMS messages from Datatransmitter 795 must be dialed to an SMS central server on one of the following numbers:
Denmark: (+45) 90 13 12 01
The Netherlands: (+31) 653 14 14 14
Norway: (+47) 90 00 21 98
Portugal: (+35) 19 62 11 3000
Sveden: (+46) 7 40 93 00 00
Germany: (+49) 172 227 80 20
B5 Spare parts
Item no.: Description:
550235 Back-up battery 820015 Cabinet, complete 200025 Lid for cabinet 200020 Cover frame for cabinet 200105 Panel mounting kit 200115 Local mounting kit w. rain / sun roof 200205 Universal bracket 200210 Bracket for wall mounting of
universal bracket
200215 Extension for universal bracket
Data Transmitter 795
Options:
204575 External 12 V DC power supply 691040 RS232 cable + 9 pole D-connector
Programs
EPROM with other protocols and language vers­ions are available on request.
M795GB0503
52
SW ver. 830434
M795DK0303 SW ver. 830430
53
Data Transmitter 795
M795GB0503
54
SW ver. 830434
Loading...