14.2 Stormflow calculation in use ....................... 28
14.2.1Zero point input no.28
14.2.2Level signal for flow calculation28
14.2.3 Number of Q(h) points28
14.2.4Height value [h] for level point28
14.2.5Flow value [Q] for level point28
M795GB0503
4
SW ver. 830434
Data Transmitter 795
1Introduction
Thank you for choosing an MJK Data Transmitter
795. A great effort has been put into developing a
product, which complies with all demands.
MJK Data Transmitter 795 is mounted in the field
and with its digital in- and output and analogue
input it is capable to receive and transmit most
types of digital and analogue signals. From a
built-in RS232 serial port, the MJK Data Transmitter 795 can communicate directly with other
equipment i.e. a pc, PLC or a Scada system.
MJK Data Transmitter 795 can with one click on
the mouse or from a telephone call activate digital
output and/or read in- and outputs, alarm signal
type for the latest 9 alarms and all logged data.
All settings, alarms and logged data can be read
in the display, from easy to use functionnal
menus.
MJK Data Transmitter 795 can be supplied in
versions that communicates via a built-in GSM
modem or telephone modem, or in versions for
radio modem.
MJK Data Transmitter 795 is easy to install and
operate, but read the instruction manual carefully
in order to make optimum use of the unit.
You can allways contact your sales reprsentative
or the MJK Automation Hotline in case of doubt
or for guidance. Try also to log onto http://
www.mjk.com.
1.1Versions
MJK Data Transmitter 795 is as standard
supplied in the following hardware versions:
-8, 12 or 16 digital inputs
-0,4 or 8 digital outputs
-4 analogue inputs
-1 or 2 RS232 ports
Display of a pumping station from a pc with the
monitoring program MJK-Link™.
MJK Data Transmitter 795 can also be programmed to make a telephone call when there is an
alarm and transmit the alarm as text to a pc or
SCADA system and to a cell phone as SMS text.
The Data Transmitter 795 has a bult in battery for
telephone calls at power failure.
The RS 232 ports is used as connection to MJK
Pump Controller 704 and to connection of a PC
for configuration or reading of data in the field for
i.e. a portable PC or for configuration or reading
of data, when the Data Transmitter 795 is used
as data
logger.
1.2Communications protocols
MJK Data Transmitter 795 can be connected to a
distribution station either through a serial
connection (RS232-RS 485), a built-in Hayes
compatible telephone modem, a data radio or a
GSM modem.
Communication complies with one protocol
which must be followed by master and slave.
Data Transmitter 795 is always the slave, i.e. the
Data Transmitter must receive a command before
it can reply. MJK Data Transmitter 795 is supplied
with Comli PLC-protocol as standard. The
following historical data are available in this
protocol:
-Time counter on digital inputs, total, total
today, total yesterday and the latest 24 hours,
all with 1 hour interval.
An MJK Data Transmitter 795 with built-in modem
can transmit alarms as SMS messages directly to
the cell phone of employee on duty.
M795GB0503
-Analogue values stored with 5 min. interval 24
hours back, and in the extended log with a
user defined logging interval.
5
SW ver. 830434
1.3MJK-Link™
The Windows based program MJK-Link™ can be
applied to monitor one or several MJK Data
Transmitter 795. Via a PC with modem it is
possible with MJK-Link™ to read values, modify
setpoints and read datalogger for e.g. storm flow
values. All settings in Data Transmitter 795 can
be implemented via MJK-Link™.
Furthermore, MJK Link™ can be used to control
the MJK Pump Comtroller 704. This facitily is
used when e.g. MJK Data Transmitter 795 and
MJK Pump Controller 704 is used together.
This manual covers MJK Data Transmitter 795 in
Comli versions for communication via telephone
modem, GSM modem or closed radio networks.
1.4About this manual
The manual is divided into 4 main sections:
1: Introduction
Presentation of Data Transmitter 795 and this
manual.
Data Transmitter 795
Explosion hazardous areas
MJK Data Transmitter 795 is not approved for
use in explosion hazardous areas.
All current local and national standards and
regulations regarding installation and use of Ex
approved material, certifications and safety
instructions for Ex equipment that have been
used in connection with installation of Data Transmitter 795 must be strictly observed.
1.6Product identification
Check that the item(s) delivered corresponds to
the ordered item(s). The item number is printed
on a label that is sticked onto the packing.
2: Mounting
Information for performing mechanical and
electrical mounting.
3: Basic settings
A look through the most common settings.
4: Field operation
A look through all settings for special
applications of Data Transmitter 795.
1.5Safety instructions
1: Read this manual carefully.
2: Be aware of the environment on the installa-
tion site. Wear necessary protective
equipment and follow all current safety
regulations.
3: MJK Data Transmitter 795 can give out start
signals to dangerous machinery. Therefore, it
must be ensured that eventually connected
machinery and other equipment areeffectively being put out of service by i.e.
removal of main fuses, lock main- and/or
security switches in off position before
commencing setting, fault finding, service and
maintenance work etc.
➀➀
➀
➀➀
➁➁
➁
➁➁
➂➂
➂
➂➂
➃➃
➃
➃➃
➀➀
➀ Item number
➀➀
➁➁
➁ Item description
➁➁
➂➂
➂ Serial number
➂➂
➃➃
➃ Communications program
➃➃
An identical marking can be found on the right
hand side of the cabinet:
4: There is a risk of lethal electrical shock from
some of the terminals on Data Transmitter
795. Be careful not touch these while the unit
is in operation.
Repair
1: Repair must only be made by MJK or a
representative approved by MJK.
M795GB0503
6
SW ver. 830434
Data Transmitter 795
1.6.1 Standard versions
This manual covers the following standard versions with Comli protocol:
Item no.: In- and outputs:Communication:
204510
204511
204512
204520
204521
204522
MJK Data Transmitter 795 with 2 X RS232 and
4 AI / 8 DI / 8 DO
4 AI / 12 DI / 4 DO
4 AI / 16 DI / 0 DO
4 AI / 8 DI / 8 DO
4 AI / 12 DI / 4 DO
4 AI / 16 DI / 0 DO
built-in telephone modem.
(Item no. 204510/204511/204512)
2 × RS232 w. modem
2 × RS232 w. modem
2 × RS232 w. modem
1 × RS232 wo. modem
1 × RS232 wo. modem
1 × RS232 wo. modem
1.6.2 Versions with built-in options
The following type options can be built into Data
Transmitter 795:
Varenr.:Betegnelse:
204570Galvanically insulated RS232 port
204571Galvanically insulated RS485 port
204572Galvanically insulated port for TP 6000
204573Galvanically insulated port for Niros UHF
204574
205105GSM modem complete w. aerial
205106GPRS modem complete w. aerial
Galvanically insulated port for external modem
The factory mounted options can be determined
read on the terminal box lid:
MJK Data Transmitter 795 delivered from factory
with galvanically insulated communications port.
MJK Data Transmitter 795 with 1 X RS232 and 1 x
communications option port.
(Item no. 204520/204521/204522)
MJK Data Transmitter 795 delivered from factory
with built-in GSM-modem.
For both types of option applies that the data
transmitter is mounted and connected like a standard data transmitter.
Please see separate documentation for the builtin options.
M795GB0503
7
SW ver. 830434
2Mechanical mounting
Data Transmitter 795
explosion hazardous areas!
Data Transmitter 795 is IP65 enclosed, and can
be mounted outdoors directly on a wall or a
railing, eventually by means of MJK rain roof
200115 and MJK universal fitting 200205.
must not be mounted in
Data Transmitter 795
Dimensional drawing for mounting screws.
See also page 51.
MJK rain roof 200115 mounted on pole with MJK
universal bracket 200205.
Data Transmitter 795 can also be mounted in a
panel by means of MJK panel mounting kit
200105.
Data Transmitter 795 mounted in a panel with MJK
panel mounting kit 200105.
2.1Mounting on a wall
The cabinet is mounted using three screws. The
upper screw is used for the suspension and the
two lower screws is used to fix the cabinet.
Remove the terminal box lid to gain access to the
two lower mounting holes.
The cabinet is suspended by the upper screw and.
fastened with the two lower screws.
The distance between the mounting screws is
shown on the dimensional drawing.
Please observe minimum distance if more than
one cabinet is mounted.
You will find a jig in full size at the back of this
manual.
MJK Data Transmitter 795 must be mou
ted vertically in order to comply with the IP68
standard.
M795GB0503
X
Do not use a screw machine!
8
SW ver. 830434
Data Transmitter 795
3Electrical mounting
Data Transmitter 795
explosion hazardous areas!
Data Transmitter 795 must not be connected to
the power supply before all connections are
Remove the terminal lid and the front panel to
gain acces to all terminals.
3.1Power supply
Data Transmitter 795 can be supplied from both
230 V AC and 24 V DC.
must not be mounted in
made.
Terminal:Designation:
Protective ground
N230 V AC neutral
L230 V AC live
-24 V DC negative
+24 V DC positive
Please note, that 24 V DC will not be available on
the terminals marked '24 V DC forsyning' unless
the Data Transmitter is fed from the mains.
3.2In- and output signals
Data Transmitter 795 is delivered in 3 different I/O
variants; 4AI / 8DI / 8DO, 4AI / 12DI / 4DO and
4AI / 16DI respectively.
Specifications:
DI:Passive with common negative, max. 24 V DC.
(Optocoupler med 10 kΩ serial resistor)
Trig voltage: < 1 V DC = Off, > 10 V DC = On,
pulse length > 100 ms.
DO: Voltage free relay contacts,
max. 1 A @ 24 V DC / 0,5 A @ 48 V AC.
AI:0/4 - 20 mA or 0 - 1 V DC.
Input impedance = 50 Ω.
3.2.1 I/O terminals, 8 DI/8 DO/4 AI
DO 1
DO 2
DO 3
DO 4
DO 1/2/3/4 common -
DO 5
DO 6
DO 7
DO 8
DO 5/6/7/8 common -
Shield for RS232 to 704
Signal ground for RS232 to 704
24 V DC out +
24 V DC out -
DI 1 +
DI 2 +
DI 3 +
DI 4 +
DI 1/2/3/4 common DI 5 +
DI 6 +
DI 7 +
DI 8 +
DI 5/6/7/8 common AI 1 +
AI 1 AI 2 +
AI 2 AI 3 +
AI 3 AI 4 +
AI 4 Rx for RS232 to 704
Tx for RS232 to 704
M795GB0503
9
SW ver. 830434
3.2.2 I/O terminals, 12 DI/4 DO/4 AI
Data Transmitter 795
DI 9 +
DI 10 +
DI 11 +
DI 12 +
DI 9/10/11/12 common -
DO 1
DO 2
DO 3
DO 4
DO 1/2/3/4 common -
Screen for RS232 to 704
Signal ground for RS232 to 704
24 V DC out +
24 V DC out -
DI 1 +
DI 2 +
DI 3 +
DI 4 +
DI 1/2/3/4 common DI 5 +
DI 6 +
DI 7 +
DI 8 +
DI 5/6/7/8 common AI 1 +
AI 1 AI 2 +
AI 2 AI 3 +
AI 3 AI 4 +
AI 4 Rx for RS232 to 704
Tx for RS232 to 704
3.2.3 I/O terminals, 16 DI/4 AI
DI 9 +
DI 10 +
DI 11 +
DI 12 +
DI 9/10/11/12 common -
DI 13 +
DI 14 +
DI 15 +
DI 16 +
DI 13/14/15/16 common -
Screen for RS232 to 704
Signal ground for RS232 to 704
24 V DC out +
24 V DC out -
DI 1 +
DI 2 +
DI 3 +
DI 4 +
DI 1/2/3/4 common DI 5 +
DI 6 +
DI 7 +
DI 8 +
DI 5/6/7/8 common AI 1 +
AI 1 AI 2 +
AI 2 AI 3 +
AI 3 AI 4 +
AI 4 Rx for RS232 to 704
Tx for RS232 to 704
M795GB0503
10
SW ver. 830434
Data Transmitter 795
3.3Connection examples
3.3.1 Digital inputs
The digital inputs are passive, i.e. they need to be
supplied from an external power source or from
the terminals marked '24 V'.
Note, that the inputs has common negative in
groups of 4 inputs.
A common installation error is that an input is
not connected to the correct negative terminal!
The inputs can be individually configured to be
normally open (NO) or normally closed (NC).
3.3.3 Analogue inputs
The analog inputs are passive. i.e. they must be
supplied from an external power source or from
the terminals marked '24 V'.
Every input have its own plus and negative terminal.
A common installation fault is that an input is
not connected to the correct negative terminal!
The input range can be individually configured to
0-20 mA or 4-20 mA.
Above diagram show an example of connecting two
switches to DI1 and DI2. Note the common
negative terminal!
3.3.2 Digital outputs
The digital outputs are voltage-free relay contacts
with a capacity of max. 24 V DC / 1 A or max. 48
V AC / 0,5 A resistive load.
The outputs can be individually configured to be
normally open (NO) or normally closed (NC).
M795GB0503
A passive mA signal
from a pressure
transmitter.
11
An active mA signal from
a level transmitter.
SW ver. 830434
3.3Connection of Pump Controller 704
Only the RS232 port on the plug-in terminals of
the Data Transmitter can be used for connecting
a MJK Pump Controller 704. A screened, twisted
pair cable must be used, and it should be
connected as shown below:
Data Transmitter 795
The shield must not be connected to the Pump
Controller 704.
Max. cable length is 15 metres.
DO NOT CONNECT
3.4Connection of communications ports
(Only item no. 204520 / 21 / 22.)
3.4.1 Communications port
All options listed in section 1.6.2 is supplied with
a flat cable, that just need to be mounted in the
communications port socket on the lower PCB.
See also separate documentation for the option
in question.
THE SHIELD IN
THIS END!
3.4.2 Built-in modem
The built-in modem can be connected to a
telephone outlet with the enclosed RJ11 cable. If
the modem should be connected to a terminal,
the cable should be stripped and only the red og
blue wire need to be connected. The two other
wires are not used.
M795GB0503
12
SW ver. 830434
Data Transmitter 795
4The front panel
Display
2 x 24 digit backlit
alphanumerical display
for indication of user
menus and measuring
values.
4.1Display and keys
Numerical keys
The keys 0-9, #,
used to enter
are
*
telephone numbers,
delays, analogue
scaling etc.
ESC. key
This key is used to go
back to the previous
menu, or to cancel a
selection. Press this
key 2 or 3 times to
revert to functional
indication.
Functional key F
The function key are
used for selecting the
different functional
menus to be displayed.
The illustration show
the function menu F0
for program version,
time and date.
MENU key
This key is used to
switch between main
menus and submenus.
ENTER key
The ENTER kry is used
to change between the
main menu and
submenus and to go
through the submenus.
The ENTER kay is
always used to confirm
a selection in a
submenu.
Arrow keys
The arrow keys are
sed for altering the
current setting. In a
sub-menu the current
selection is always
shown in the upper
line, and the alternative
selection is shown in
brackets in the lower
line. The arrow keys
are used to select an
alternative setting. The
arrow keys are also
used to select input
and output number.
The ↑ key increase
and the ↓ key
decrease a value.
4.2Menu structure
Above figure is an overview of the general function of the functional keys.
INDICATION
MENUS
MAIN
MENU
SUBMENU W.
SELECTION
SUBMENU W.
SELECTION
See also page 42.
MAIN
MENU
M795GB0503
13
SW ver. 830434
5Functional menus
Data Transmitter 795
5.1.1 F0 - Program version, time and date
Menu F0 displays date og and time. Moreover, it
will display the current communications protocol
and program version.
5.1.2 F0 - Interlock, operation or alarm signal
Menu F0 followed by 1 x 'down arrow' will display
which signals that initiate the 9 programmable interlock sequences:
'A': alarm signal, '+': operation signal,
'-': not in use.
5.1.3 F0 - Internal flag, operation or alarm signal
Menu F0 followed by 2 x 'down arrow' will display
which signals that are linked to the internal flags:
5.2F1 - Digital inputs on/off
Menu F1 indicates if the digital inputs are set ON
or OFF. Up to 8 inputs are shown simultaneously.
If there are more than 8 inputs, the remaining
inputs will be displayed by pressing one of the
arrow keys:
Note, that a delay period can be set for every digital input so that the digital input can go ON for a
short period without triggering an eventual alarm.
When the input is OFF, an empty field is
shown. When the input goes ON, a flashing field
is shown during the delay time, after which a field
is shown constantly.
5.3.1 F2 - Digital outputs on/off
Menu F2 displays whether the digital outputs are
set ON or OFF:
'A': alarm signal, '+': operation signal, '-':
not in use.
5.1.4 F0 - Limits, high/low
Menu F0 followed by 2 x 'down arrow' will
indicate which analogue inputs that are linked to
a high/low alarm limit, and also if the limit will
release an operational or alarm signal:
'A': alarm signal, '+': operation signal, '-':
not in use.
5.1.5 F0 - Digital inputs, operation or alarm signal
Menu F0 followed by 4 (and 5) x 'down arrow'
display which digital inputs, that releases an operation or alarm signal:
'A': alarm signal, '+': operation signal, '-':
not in use.
A delay period can be set for every digital output.
This delay period must run out before the output
are activated.
When the output is OFF, an empty field is
shown. When the output goes ON, a flashing field
are shown during the delay time, after which a
field are shown constantly.
5.3.2 F2 - Internal flag on/off
Menu F2 followed by 1 x 'down arrow' will display
the status for the internal flags.
M795GB0503
14
SW ver. 830434
Data Transmitter 795
5.4F3 - Limits - High/Low
Menu F3 indicates if high and low limit is ON or
OFF for the analogue inputs. The first four digits
indicate if the high limit setting is exceeded and
the last four digits indicate if the low limit setting is
exceeded:
A delay time can be set individually for each
analogue input in that the the input can exceed the
limit for a short period without activating an alarm.
An empty square is displayed when the limit is
not exceeded. When the limit is exceeded, a solid
square is displayed. If a delay period is set, the
square will flash during the delay period.
5.5F4 - Analogue input value #
Menu F4 indicates the value of the analogue inputs
as a bargraph:
Select the desired input with the arrow keys or
the numeric keys.
5.5.1 F5 - Analogue input scaling
Menu F5 indicates the value of an analogue input
as a percentage and the mA signal and as a
scaled value:
Select the desired input with the arrow keys or
the numeric keys.
5.5.2 F5 - Analogue input on Pump Controller 704
Menu F2 followed by 1 x 'down arrow' display
the value of the analogue input on the Pump
Controller 704 (if connected):
Please observe that the value is collected directly
from the Pump Controller 704 and is not scaled.
5.6F6 - Counter for inputs
Whenever a digital input or an analogue high/low
limit is active, it will be recorded by a counter. The
number is displayed in menu F6:
Use the arrow keys to change between:
-digital input 1 - 8/12/16
-analogue high limit 1 - 4
-analogue low limit 1 - 4
In addition, the numerical keys 1 - 8 can be used
to select the desired input.
The selected counter can be reset by pressing
the ENTER key.
5.7F7 - Counter for time
Menu F7 indicate for how long the digital input
and the analogue high and low limits have been
active. Time counters is running continuously
such as if the input is set to OFF for some time
and then is set to ON, the counter will count from
the last value. The time is displayed in hours and
minutes:
The scaled value is determined by the
programming of the analogue input.
If the value represents e.g. a level measurement
in a tank, and the level normally varies between 2
m and 3 m, the analogue input will normally be
programmed so 2 m corresponds with '200' (low
value) and 3 m corresponds with '300' (high
value).
A level of 2,5 m will then give a scaled readout of
250 and 50 %.
If the scaled value should be shown as '2,5', it is
possible to set a divisor for each input. In this
example the divisor should have the value 100.
See also section 7.
M795GB0503
Use the arrow keys to change between:
-digital input 1 - 8/12/16
-analogue high limit 1 - 4
-analogue low limit 1 - 4
In addition, the numerical keys 1 - 8 can be used
to select the desired input.
The selected counter can be reset by pressing
the ENTER key.
15
SW ver. 830434
Data Transmitter 795
5.8F8 - Alarm / Alarm number
Menu F8 indicate if the last 9 alarms are ON or
OFF:
Each time a new alarm is activated, it will be
recorded as alarm no. 1 and all other recorded
alarms will move down one place and alarm 9 will
be deleted. When the alarm for one input has
been ON one time it must be set to OFF before a
new alarm from the same input is accepted as an
alarm.
If the alarm has not been reset and another 9
alarms occur, i.e. the first alarm become no. 10
and therefore will become invisible in the alarm
list, this alarm will be reset automatically.
A flashing square is shown when an alarm
goes ON.
If the alarm are being reset but is still active, a solid square is shown constantly. When the alarm
goes OFF again, a square is shown constantly.
By means of the arrow keys or by entering the
alarm number, the status, type and timestamps
for on and off time can be displayed. Whenever
an alarm goes ON, the input number and start
time will be recorded. Similarly, when the alarm is
reset, the reset time is recorded, and when the
alarm goes OFF, the end time will be recorded:
5.9.2 F9.2 - Stormflow calculation
Whenever a stormflow occur, the flow is
3
displayed as m
/h in menu F9-2:
5.10 F# - Modem/Line status
(Only for versions with built-in telephone modem
or GSM modem.)
Menu F# displays the status of outgoing alarm
calls or incoming calls:
The following is displayed during an incoming
call:
The following is displayed during an outgoing
alarm call to one of the telephone numbers in the
telephone number list:
When Data Transmitter 795 interlocks another
Data Transmitter 795 i.e. in order to perform a
remote start or stop of a pump, the following is
displayed:
'ID' indicates the ID number of the Data Transmitter itself.
If the Data Transmitter are configured as a Master
in a multidrop system, the 'ID' can also be the ID
number of a connected Slave unit.
Return to normal operating display with the arrow
keys or by prssing the '0' key.
5.9.1 F9.1 - Stormflow volume
Menu F9 displays the recorded stormflow
volume.
The counter can be reset with the ENTER key.
M795GB0503
5.11 F* - Communication status
Menu F* indicate the communication status on
the serial port, the port to Pump Controller 704,
and the built-in telephone modem:
795 serial:R = Rx, T = Tx, CD = Carrier Detect,
RTS = Request to send og CTS = Clear to send.
704: R = Rx, T = Tx and = Pump Controller
704 not interlocked / Pump Controller 704
interlocked. The Pump Controller 704 signal to
the Data Transmitter that the Pump Controller
704 will not activate any control outputs, because
the Pump Controller are interlocked.
16
SW ver. 830434
Data Transmitter 795
6Programming of main functions
6.1Select language
Select the desired language with the arrow keys
and confirm with ENTER.
6.2Set time and date
Enter time and date with the numerical keys or
the arrow keys. Confirm with ENTER:
Just press ENTER at all entries if changes are not
needed in order to proceed to the next menu.
6.3Automatic change between summer
time and winter time
Select if the clock should change automatically
between summer time and winter time:
6.5Calculation of average values on
analogue inputs
The value of an analogue input is recorded every
second, and every 5 minutes the values is logged. If averaging of the analogue values are
selected, an average of the analogue value over
the last 5 minutes will be calculated and logged.
If averaging is not selected, the analogue value at
the actual time will be logged.
Use the arrow keys to select and confirm with
ENTER.
6.6Data logging interval
The data logging interval is used for the extended
logging function, where the value for the analogue
input and the level from MJK Pump Controller
704 is stored.
Use the arrow keys to select and confirm with
ENTER.
Just press ENTER at all entries if changes are not
needed in order to proceed to the next menu:
6.4Access code enabled/disabled
Select if an access code is required to gain access to the remaining system menus. This
function make it possible to protect the system
configuration from unauthorized changes:
Use the arrow keys to select and confirm with
ENTER.
6.4.1 Enter password
If access code protection is selected, a 4-digit
access code is required in order to gain access
to the remaining system menus.
The interval between loggings can be chosen
amongst the following values: 30 sec. (00:30), 1
min. (01:00), 5 min. (05:00), 10 min. (10:00), 30
min. (30:00) and 1 hour (60:00).
Use the arrow keys to select and confirm with
ENTER.
6.7Tone / pulse dialing
Select between pulse or tone dialing from a
telephone modem:
Use the arrow keys to select and confirm with
ENTER.
6.8Alarm call on power failure
If alarm call at power failure is selected, the Data
Transmitter will call the first telephone number in
the telephone list when the power supply fail. A
power failure will not be detected before the
supply has been gone for minimum 30 sec.
Hereby alarm calls on short power surges are
avoided.
M795GB0503
Use the arrow keys to select and confirm with
ENTER.
17
SW ver. 830434
Loading...
+ 37 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.