Xylem 795 User Manual

Manual
MJK Data Transmitter 795
Valid from software version 830434
COMLI PROTOCOL
MJK Automation A/S
Byageren 7 DK-2850 Nærum Denmark Tel: +45 45 56 06 56 Fax: +45 45 56 06 46 www.mjk.com
Station ID:
795 Type:
795 Serial no:
M795GB0503
Data Transmitter 795
Konformitetserklæring
Vi, MJK Automation A/S, DK-2850 Nærum, påtager os det fulde ansvar for at produktet
som denne erklæring angår, er i overensstemmelse med følgende standard(er) eller andre normdokument(er).
EN 50081-1:1995 EN 50082-1:1995
efter bestemmelserne i direktiv
89/336/EØF; 93/68/EØF
Declaration of Conformity
We, MJK Automation A/S, DK-2850 Nærum, declare under our sole responsibility that the product
MJK Data Transmitter 795
to which this declaration relates is in conformity with the following standard(s) or other normative document(s).
EN 50081-1:1995 EN 50082-1:1995
following the provisions of Directive
89/336/EWG; 93/68/EWG
Konformitätserklärung
Wir, MJK Automation A/S, DK-2850 Nærum, erklären in alleiniger Verantwortung, dass das Produkt
auf das sich diese Erklärung bezieht mit der/den folgenden Nor me(en) oder normativen Dokument(en) übereinstimmt.
EN 50081-1:1995 EN 50082-1:1995
Gemäss den Bestimmungen der Richtlinie
89/336/EWG; 93/68/EWG
Declaration de conformite
Nous, MJK Automation A/S, DK-2850 Nærum, déclarons sous notre seule responsabilité que le produit
auquel se réfère cette déclaration est conforme á la (aux) norme(s) ou autre(s) document(s) normatif(s)
EN 50081-1:1995 EN 50082-1:1995
conformément aux dispositions de Directive
89/336/EWG; 93/68/EWG
Dichiarazione di conformità
Noi, MJK Automation A/S, DK-2850 Nærum, dichiariamo sotto la nostra esclusiva responsabilità che l’apparecchio
MJK Data Transmitter 795
al quale questa dichiarazione si riferisce, è conforme alla seguente normativa(e) stand­ard o ad altri documenti di normativa(e)
EN 50081-1:1995 EN 50082-1:1995
conformemente alla disposizioni della Direzione
89/336/EWG; 93/68/EWG
Declaración de Conformidad
Nosotros, MJK Automation A/S, DK-2850 Nærum, declaramos bajo nuestra única responsabilidad que el producto
al cual se refiere esta declaración, está en conformidad con la(s) siguente(e) norma(s) u otros documentos normativos
EN 50081-1:1995 EN 50082-1:1995
según las disposiciones de la(s) directiva(s)
89/336/EWG; 93/68/EWG
M795GB0503
2
SW ver. 830434
Data Transmitter 795
Contents
1 Introduction .......................................... 5
1.1 Versions........................................................5
1.2 Communications protocols ........................... 5
1.3 MJK-Link™ .................................................. 6
1.4 About this manual ........................................ 6
1.5 Safety instructions ........................................6
1.6 Product identification .................................... 6
1.6.1 Standard versions 7
1.6.2 Versions with built-in options 7
2 Mechanical mounting ..........................8
2.1 Mounting on a wall ....................................... 8
3 Electrical mounting .............................. 9
3.1 Power supply................................................ 9
3.2 In- and output signals 9
3.2.1 I/O terminals, 8 DI/8 DO/4 AI 9
3.2.2 I/O terminals, 12 DI/4 DO/4 AI 10
3.2.3 I/O terminals, 16 DI/4 AI 10
3.3 Connection examples ................................. 11
3.3.1 Digital inputs 11
3.3.2 Digital outputs 11
3.3.3 Analogue inputs 11
3.3 Connection of Pump Controller 704 ...........12
3.4 Connection of communications ports ......... 12
3.4.1 Communications port 12
3.4.2 Built-in modem 12
4 The front panel ................................... 13
4.1 Display and keys 13
4.2 Menu structure ...........................................13
5 Functional menus ............................... 14
5.1.1 F0 - Program version, time and date 14
5.1.2 F0 - Interlock, operation or alarm signal 14
5.1.3 F0 - Internal flag, operation or alarm signal 14
5.1.4 F0 - Limits, high/low 14
5.1.5 F0 - Digital inputs, operation or alarm signal 14
5.2 F1 - Digital inputs on/off ............................. 14
5.3.1 F2 - Digital outputs on/off 14
5.3.2 F2 - Internal flag on/off 14
5.4 F3 - Limits - High/Low ................................ 15
5.5 F4 - Analogue input value # ........................ 15
5.5.1 F5 - Analogue input scaling 15
5.5.2 F5 - Analogue input on Pump Controller 704 15
5.6 F6 - Counter for inputs ...............................15
5.7 F7 - Counter for time ..................................15
5.8 F8 - Alarm / Alarm number ........................16
5.9.1 F9.1 - Stormflow volume 16
5.9.2 F9.2 - Stormflow calculation 16
5.10 F# - Modem/Line status .............................16
5.11 F* - Communication status ......................... 16
6 Programming of main functions........ 17
6.1 Select language ..........................................17
6.2 Set time and date ....................................... 17
6.3 Automatic change between
summer time and winter time .....................17
6.4 Access code enabled/disabled ................... 17
6.4.1 Enter password 17
6.5 Calculation of average values on
analogue inputs .......................................... 17
6.6 Data logging interval ...................................17
6.7 Tone / pulse dialing ..................................... 17
6.8 Alarm call on power failure.......................... 17
6.9 Number of incoming rings before answer ... 18
6.10 ID. no. for the Data Transmitter ................... 18
6.11 Automatic reset of alarms ...........................18
6.11.1 Call on automatic alarm reset 18
6.12 Start time for operational reports ................18
6.13 795 telephone number ...............................18
6.14 SMSC telephone number ...........................18
6.15 RS485 function........................................... 18
6.15.1 Master ID number 18
7 Programming of analogue inputs ..... 19
7.1 Select analogue input ................................. 19
7.2 0 - 20 or 4 - 20 mA input ............................ 19
7.3 Scaling at 0 / 4 mA ..................................... 19
7.4 Scaling at 20 mA ........................................19
7.5 Monitoring of high limit ............................... 19
7.5.1 Set high limit 19
7.5.2 High limit operation / alarm 19
7.5.3 Dialout on high limit 19
7.5.4 Signal delay for exceeding high limit 19
7.6 Monitoring of low limit ................................. 19
7.6.1 Set low limit 20
7.6.2 Low limit operation / alarm 20
7.6.3 Dialout on high limit 20
7.6.4 Signal delay for exceeding low limit 20
7.7 Divisor ........................................................20
8 Programming of digital inputs ........... 20
8.1 Select a digital input ................................... 20
8.2 NO or NC ................................................... 20
8.3 Operational or alarm input ..........................20
8.3.1 Dialout on alarm 20
8.4 Signal delay ................................................20
9 Programming of digital outputs ........21
9.1 Select a digital output ................................. 21
9.2 NO or NC ................................................... 21
9.3 Time controlled output................................ 21
9.4 ON time ...................................................... 21
9.4.1 Time before start 21
M795GB0503
3
SW ver. 830434
Data Transmitter 795
10 Programming of logical functions ..... 21
10.1 Select the output to receive the result
of the logical function.................................. 21
10.2 Select logical function .................................21
10.2.1 Select signals for the logical function 21
10.2.2 Operational or alarm signal on
internal flag 22
10.2.3 Dialout when alarm signal on
internal flag 22
10.2.4 Signal delay on internal flag 22
11 Programming of interlock .................. 22
11.1 Interlock of this station ................................ 22
11.2 Interlock interval.......................................... 22
11.3 Selection of substation ...............................22
11.4 Interlock active / inactive ............................ 23
11.4.1 Start of interlock 23
11.4.2 Stop interlock 23
11.4.3 Receivers telephone / ID number 23
11.4.4 Receiver's output 24
12 Programming of Pump Controller(s) . 25
12.1 704 connected ...........................................25
12.2 Call on alarm or system error on 704 .......... 25
12.2 Programming of the
internal Pump Controller .............................25
12.2.1 Select level signal 25
12.2.2 Start level for pump no. 1 25
12.2.2 Stop level for pump no. 1 25
12.2.3 Levels in use in 795 25
12.2.4 Start level for pump no. 2 25
12.3.2 Stop level for pump no. 2 25
12.3.3 Alternation of pumps 25
13 Telephone list for alarms ................... 26
13.1 Telephone number 1-9 ............................... 26
13.2 Number type .............................................. 26
13.2.1 Telephone number 26
13.2.2 Enter pager message 26
13.2.3 Enter SMS message 27
13.2.4 Pause between calls 27
15 Programming of 702 ComTroller ....... 29
15.1 Select 702 ..................................................29
16 Alarms ................................................. 30
16.1 Operational or alarm signal ......................... 30
16.2 Alarm calls .................................................. 30
16.3 Reset of alarms .......................................... 30
15.3.1 Automatic reset of alarms 30
17 Factory settings ................................. 31
18 Signal lists .......................................... 33
19 Register list ......................................... 37
20 Menu structure ................................... 44
20.1 Functional menus .......................................44
20.2 Programming menus ..................................45
A Appendix............................................. 50
A1 Technical specifications .............................. 50
A2 Number of signals available ........................50
A3 Inputs and outputs ..................................... 50
A4 Dimensions ................................................. 50
B Appendix............................................. 51
B1 Maintenance ............................................... 51
B2 Service codes ............................................. 51
B2.2 Forced setup
without reset of datalogger 51
B2.3 Forced setup
including reset of datalogger 51 B2.4 Baud rate and communication method 51 B2.5 Activation of SIM card for GSM/GPRS
modem 51 B2.6 Total reset 51
B3 Software upgrade .......................................51
B4 SMSC telephone numbers .........................52
B5 Spare parts................................................. 52
14 Programming of stormflow calculation .. 27
14.1 Stormflow calculation .................................27
14.2 Stormflow calculation in use ....................... 28
14.2.1 Zero point input no. 28
14.2.2 Level signal for flow calculation 28
14.2.3 Number of Q(h) points 28
14.2.4 Height value [h] for level point 28
14.2.5 Flow value [Q] for level point 28
M795GB0503
4
SW ver. 830434
Data Transmitter 795
1 Introduction
Thank you for choosing an MJK Data Transmitter
795. A great effort has been put into developing a product, which complies with all demands.
MJK Data Transmitter 795 is mounted in the field and with its digital in- and output and analogue input it is capable to receive and transmit most types of digital and analogue signals. From a built-in RS232 serial port, the MJK Data Trans­mitter 795 can communicate directly with other equipment i.e. a pc, PLC or a Scada system.
MJK Data Transmitter 795 can with one click on the mouse or from a telephone call activate digital output and/or read in- and outputs, alarm signal type for the latest 9 alarms and all logged data.
All settings, alarms and logged data can be read in the display, from easy to use functionnal menus.
MJK Data Transmitter 795 can be supplied in versions that communicates via a built-in GSM modem or telephone modem, or in versions for radio modem.
MJK Data Transmitter 795 is easy to install and operate, but read the instruction manual carefully in order to make optimum use of the unit.
You can allways contact your sales reprsentative or the MJK Automation Hotline in case of doubt or for guidance. Try also to log onto http:// www.mjk.com.
1.1 Versions
MJK Data Transmitter 795 is as standard supplied in the following hardware versions:
- 8, 12 or 16 digital inputs
- 0,4 or 8 digital outputs
- 4 analogue inputs
- 1 or 2 RS232 ports
Display of a pumping station from a pc with the
monitoring program MJK-Link™.
MJK Data Transmitter 795 can also be program­med to make a telephone call when there is an alarm and transmit the alarm as text to a pc or SCADA system and to a cell phone as SMS text. The Data Transmitter 795 has a bult in battery for telephone calls at power failure.
The RS 232 ports is used as connection to MJK Pump Controller 704 and to connection of a PC for configuration or reading of data in the field for i.e. a portable PC or for configuration or reading of data, when the Data Transmitter 795 is used as data logger.
1.2 Communications protocols
MJK Data Transmitter 795 can be connected to a distribution station either through a serial connection (RS232-RS 485), a built-in Hayes compatible telephone modem, a data radio or a GSM modem.
Communication complies with one protocol which must be followed by master and slave. Data Transmitter 795 is always the slave, i.e. the Data Transmitter must receive a command before it can reply. MJK Data Transmitter 795 is supplied with Comli PLC-protocol as standard. The following historical data are available in this protocol:
- Time counter on digital inputs, total, total today, total yesterday and the latest 24 hours, all with 1 hour interval.
An MJK Data Transmitter 795 with built-in modem
can transmit alarms as SMS messages directly to
the cell phone of employee on duty.
M795GB0503
- Analogue values stored with 5 min. interval 24 hours back, and in the extended log with a user defined logging interval.
5
SW ver. 830434
1.3 MJK-Link™
The Windows based program MJK-Link™ can be applied to monitor one or several MJK Data Transmitter 795. Via a PC with modem it is possible with MJK-Link™ to read values, modify setpoints and read datalogger for e.g. storm flow values. All settings in Data Transmitter 795 can be implemented via MJK-Link™.
Furthermore, MJK Link™ can be used to control the MJK Pump Comtroller 704. This facitily is used when e.g. MJK Data Transmitter 795 and MJK Pump Controller 704 is used together.
This manual covers MJK Data Transmitter 795 in Comli versions for communication via telephone modem, GSM modem or closed radio networks.
1.4 About this manual
The manual is divided into 4 main sections:
1: Introduction
Presentation of Data Transmitter 795 and this manual.
Data Transmitter 795
Explosion hazardous areas
MJK Data Transmitter 795 is not approved for
use in explosion hazardous areas.
All current local and national standards and regulations regarding installation and use of Ex approved material, certifications and safety instructions for Ex equipment that have been used in connection with installation of Data Trans­mitter 795 must be strictly observed.
1.6 Product identification
Check that the item(s) delivered corresponds to the ordered item(s). The item number is printed on a label that is sticked onto the packing.
2: Mounting
Information for performing mechanical and electrical mounting.
3: Basic settings
A look through the most common settings.
4: Field operation
A look through all settings for special applications of Data Transmitter 795.
1.5 Safety instructions
1: Read this manual carefully.
2: Be aware of the environment on the installa-
tion site. Wear necessary protective equipment and follow all current safety regulations.
3: MJK Data Transmitter 795 can give out start
signals to dangerous machinery. Therefore, it must be ensured that eventually connected machinery and other equipment are effectively being put out of service by i.e. removal of main fuses, lock main- and/or security switches in off position before commencing setting, fault finding, service and maintenance work etc.
➀➀
➀➀ ➁➁
➁➁
➂➂
➂➂
➃➃
➃➃
➀➀
Item number
➀➀ ➁➁
Item description
➁➁
➂➂
Serial number
➂➂ ➃➃
Communications program
➃➃
An identical marking can be found on the right hand side of the cabinet:
4: There is a risk of lethal electrical shock from
some of the terminals on Data Transmitter
795. Be careful not touch these while the unit is in operation.
Repair
1: Repair must only be made by MJK or a
representative approved by MJK.
M795GB0503
6
SW ver. 830434
Data Transmitter 795
1.6.1 Standard versions
This manual covers the following standard vers­ions with Comli protocol:
Item no.: In- and outputs: Communication:
204510 204511 204512 204520 204521 204522
MJK Data Transmitter 795 with 2 X RS232 and
4 AI / 8 DI / 8 DO 4 AI / 12 DI / 4 DO 4 AI / 16 DI / 0 DO
4 AI / 8 DI / 8 DO 4 AI / 12 DI / 4 DO 4 AI / 16 DI / 0 DO
built-in telephone modem.
(Item no. 204510/204511/204512)
2 × RS232 w. modem 2 × RS232 w. modem 2 × RS232 w. modem 1 × RS232 wo. modem 1 × RS232 wo. modem 1 × RS232 wo. modem
1.6.2 Versions with built-in options
The following type options can be built into Data Transmitter 795:
Varenr.: Betegnelse:
204570 Galvanically insulated RS232 port 204571 Galvanically insulated RS485 port 204572 Galvanically insulated port for TP 6000 204573 Galvanically insulated port for Niros UHF 204574 205105 GSM modem complete w. aerial 205106 GPRS modem complete w. aerial
Galvanically insulated port for external modem
The factory mounted options can be determined read on the terminal box lid:
MJK Data Transmitter 795 delivered from factory
with galvanically insulated communications port.
MJK Data Transmitter 795 with 1 X RS232 and 1 x
communications option port.
(Item no. 204520/204521/204522)
MJK Data Transmitter 795 delivered from factory
with built-in GSM-modem.
For both types of option applies that the data transmitter is mounted and connected like a stan­dard data transmitter.
Please see separate documentation for the built­in options.
M795GB0503
7
SW ver. 830434
2 Mechanical mounting
Data Transmitter 795
explosion hazardous areas!
Data Transmitter 795 is IP65 enclosed, and can be mounted outdoors directly on a wall or a railing, eventually by means of MJK rain roof 200115 and MJK universal fitting 200205.
must not be mounted in
Data Transmitter 795
Dimensional drawing for mounting screws.
See also page 51.
MJK rain roof 200115 mounted on pole with MJK
universal bracket 200205.
Data Transmitter 795 can also be mounted in a panel by means of MJK panel mounting kit
200105.
Data Transmitter 795 mounted in a panel with MJK
panel mounting kit 200105.
2.1 Mounting on a wall
The cabinet is mounted using three screws. The upper screw is used for the suspension and the two lower screws is used to fix the cabinet.
Remove the terminal box lid to gain access to the
two lower mounting holes.
The cabinet is suspended by the upper screw and.
fastened with the two lower screws.
The distance between the mounting screws is shown on the dimensional drawing.
Please observe minimum distance if more than
one cabinet is mounted.
You will find a jig in full size at the back of this manual.
MJK Data Transmitter 795 must be mou
ted vertically in order to comply with the IP68
standard.
M795GB0503
X
Do not use a screw machine!
8
SW ver. 830434
Data Transmitter 795
3 Electrical mounting
Data Transmitter 795
explosion hazardous areas!
Data Transmitter 795 must not be connected to
the power supply before all connections are
Remove the terminal lid and the front panel to gain acces to all terminals.
3.1 Power supply
Data Transmitter 795 can be supplied from both 230 V AC and 24 V DC.
must not be mounted in
made.
Terminal: Designation:
Protective ground
N 230 V AC neutral
L 230 V AC live
- 24 V DC negative
+ 24 V DC positive
Please note, that 24 V DC will not be available on the terminals marked '24 V DC forsyning' unless the Data Transmitter is fed from the mains.
3.2 In- and output signals
Data Transmitter 795 is delivered in 3 different I/O variants; 4AI / 8DI / 8DO, 4AI / 12DI / 4DO and 4AI / 16DI respectively.
Specifications:
DI: Passive with common negative, max. 24 V DC.
(Optocoupler med 10 k serial resistor)
Trig voltage: < 1 V DC = Off, > 10 V DC = On, pulse length > 100 ms.
DO: Voltage free relay contacts,
max. 1 A @ 24 V DC / 0,5 A @ 48 V AC.
AI: 0/4 - 20 mA or 0 - 1 V DC.
Input impedance = 50 Ω.
3.2.1 I/O terminals, 8 DI/8 DO/4 AI
DO 1 DO 2 DO 3 DO 4
DO 1/2/3/4 common -
DO 5 DO 6 DO 7 DO 8
DO 5/6/7/8 common -
Shield for RS232 to 704
Signal ground for RS232 to 704
24 V DC out +
24 V DC out -
DI 1 + DI 2 + DI 3 + DI 4 + DI 1/2/3/4 common ­DI 5 + DI 6 + DI 7 + DI 8 + DI 5/6/7/8 common ­AI 1 + AI 1 ­AI 2 + AI 2 ­AI 3 + AI 3 ­AI 4 + AI 4 ­Rx for RS232 to 704 Tx for RS232 to 704
M795GB0503
9
SW ver. 830434
3.2.2 I/O terminals, 12 DI/4 DO/4 AI
Data Transmitter 795
DI 9 + DI 10 + DI 11 + DI 12 +
DI 9/10/11/12 common -
DO 1 DO 2 DO 3 DO 4
DO 1/2/3/4 common -
Screen for RS232 to 704
Signal ground for RS232 to 704
24 V DC out +
24 V DC out -
DI 1 + DI 2 + DI 3 + DI 4 + DI 1/2/3/4 common ­DI 5 + DI 6 + DI 7 + DI 8 + DI 5/6/7/8 common ­AI 1 + AI 1 ­AI 2 + AI 2 ­AI 3 + AI 3 ­AI 4 + AI 4 ­Rx for RS232 to 704 Tx for RS232 to 704
3.2.3 I/O terminals, 16 DI/4 AI
DI 9 + DI 10 + DI 11 + DI 12 +
DI 9/10/11/12 common -
DI 13 + DI 14 + DI 15 + DI 16 +
DI 13/14/15/16 common -
Screen for RS232 to 704
Signal ground for RS232 to 704
24 V DC out +
24 V DC out -
DI 1 + DI 2 + DI 3 + DI 4 + DI 1/2/3/4 common ­DI 5 + DI 6 + DI 7 + DI 8 + DI 5/6/7/8 common ­AI 1 + AI 1 ­AI 2 + AI 2 ­AI 3 + AI 3 ­AI 4 + AI 4 ­Rx for RS232 to 704 Tx for RS232 to 704
M795GB0503
10
SW ver. 830434
Data Transmitter 795
3.3 Connection examples
3.3.1 Digital inputs
The digital inputs are passive, i.e. they need to be supplied from an external power source or from the terminals marked '24 V'.
Note, that the inputs has common negative in groups of 4 inputs.
A common installation error is that an input is
not connected to the correct negative terminal!
The inputs can be individually configured to be normally open (NO) or normally closed (NC).
3.3.3 Analogue inputs
The analog inputs are passive. i.e. they must be supplied from an external power source or from the terminals marked '24 V'.
Every input have its own plus and negative termi­nal.
A common installation fault is that an input is
not connected to the correct negative terminal!
The input range can be individually configured to 0-20 mA or 4-20 mA.
Above diagram show an example of connecting two
switches to DI1 and DI2. Note the common
negative terminal!
3.3.2 Digital outputs
The digital outputs are voltage-free relay contacts with a capacity of max. 24 V DC / 1 A or max. 48 V AC / 0,5 A resistive load.
The outputs can be individually configured to be normally open (NO) or normally closed (NC).
M795GB0503
A passive mA signal
from a pressure
transmitter.
11
An active mA signal from
a level transmitter.
SW ver. 830434
3.3 Connection of Pump Controller 704
Only the RS232 port on the plug-in terminals of the Data Transmitter can be used for connecting a MJK Pump Controller 704. A screened, twisted pair cable must be used, and it should be connected as shown below:
Data Transmitter 795
The shield must not be connected to the Pump Controller 704.
Max. cable length is 15 metres.
DO NOT CONNECT
3.4 Connection of communications ports
(Only item no. 204520 / 21 / 22.)
3.4.1 Communications port
All options listed in section 1.6.2 is supplied with a flat cable, that just need to be mounted in the communications port socket on the lower PCB.
See also separate documentation for the option in question.
THE SHIELD IN
THIS END!
3.4.2 Built-in modem
The built-in modem can be connected to a telephone outlet with the enclosed RJ11 cable. If the modem should be connected to a terminal, the cable should be stripped and only the red og blue wire need to be connected. The two other wires are not used.
M795GB0503
12
SW ver. 830434
Data Transmitter 795
4 The front panel
Display
2 x 24 digit backlit alphanumerical display for indication of user menus and measuring values.
4.1 Display and keys
Numerical keys
The keys 0-9, #, used to enter
are
*
telephone numbers, delays, analogue scaling etc.
ESC. key
This key is used to go back to the previous menu, or to cancel a selection. Press this key 2 or 3 times to revert to functional indication.
Functional key F
The function key are used for selecting the different functional menus to be displayed. The illustration show the function menu F0 for program version, time and date.
MENU key
This key is used to switch between main menus and submenus.
ENTER key
The ENTER kry is used to change between the main menu and submenus and to go through the submenus. The ENTER kay is always used to confirm a selection in a submenu.
Arrow keys
The arrow keys are sed for altering the current setting. In a sub-menu the current selection is always shown in the upper line, and the alternative selection is shown in brackets in the lower line. The arrow keys are used to select an alternative setting. The arrow keys are also used to select input and output number.
The key increase and the key
decrease a value.
4.2 Menu structure
Above figure is an overview of the general function of the functional keys.
INDICATION
MENUS
MAIN
MENU
SUBMENU W.
SELECTION
SUBMENU W.
SELECTION
See also page 42.
MAIN
MENU
M795GB0503
13
SW ver. 830434
5 Functional menus
Data Transmitter 795
5.1.1 F0 - Program version, time and date
Menu F0 displays date og and time. Moreover, it will display the current communications protocol and program version.
5.1.2 F0 - Interlock, operation or alarm signal
Menu F0 followed by 1 x 'down arrow' will display which signals that initiate the 9 programmable in­terlock sequences:
'A': alarm signal, '+': operation signal, '-': not in use.
5.1.3 F0 - Internal flag, operation or alarm signal
Menu F0 followed by 2 x 'down arrow' will display which signals that are linked to the internal flags:
5.2 F1 - Digital inputs on/off
Menu F1 indicates if the digital inputs are set ON or OFF. Up to 8 inputs are shown simultaneously.
If there are more than 8 inputs, the remaining inputs will be displayed by pressing one of the arrow keys:
Note, that a delay period can be set for every di­gital input so that the digital input can go ON for a short period without triggering an eventual alarm.
When the input is OFF, an empty field is shown. When the input goes ON, a flashing field is shown during the delay time, after which a field is shown constantly.
5.3.1 F2 - Digital outputs on/off
Menu F2 displays whether the digital outputs are set ON or OFF:
'A': alarm signal, '+': operation signal, '-': not in use.
5.1.4 F0 - Limits, high/low
Menu F0 followed by 2 x 'down arrow' will indicate which analogue inputs that are linked to a high/low alarm limit, and also if the limit will release an operational or alarm signal:
'A': alarm signal, '+': operation signal, '-': not in use.
5.1.5 F0 - Digital inputs, operation or alarm signal
Menu F0 followed by 4 (and 5) x 'down arrow' display which digital inputs, that releases an ope­ration or alarm signal:
'A': alarm signal, '+': operation signal, '-': not in use.
A delay period can be set for every digital output. This delay period must run out before the output are activated.
When the output is OFF, an empty field is shown. When the output goes ON, a flashing field are shown during the delay time, after which a field are shown constantly.
5.3.2 F2 - Internal flag on/off
Menu F2 followed by 1 x 'down arrow' will display the status for the internal flags.
M795GB0503
14
SW ver. 830434
Data Transmitter 795
5.4 F3 - Limits - High/Low
Menu F3 indicates if high and low limit is ON or OFF for the analogue inputs. The first four digits indicate if the high limit setting is exceeded and the last four digits indicate if the low limit setting is exceeded:
A delay time can be set individually for each analogue input in that the the input can exceed the limit for a short period without activating an alarm.
An empty square is displayed when the limit is not exceeded. When the limit is exceeded, a solid square  is displayed. If a delay period is set, the square will flash during the delay period.
5.5 F4 - Analogue input value #
Menu F4 indicates the value of the analogue inputs as a bargraph:
Select the desired input with the arrow keys or the numeric keys.
5.5.1 F5 - Analogue input scaling
Menu F5 indicates the value of an analogue input as a percentage and the mA signal and as a scaled value:
Select the desired input with the arrow keys or the numeric keys.
5.5.2 F5 - Analogue input on Pump Controller 704
Menu F2 followed by 1 x 'down arrow' display the value of the analogue input on the Pump Controller 704 (if connected):
Please observe that the value is collected directly from the Pump Controller 704 and is not scaled.
5.6 F6 - Counter for inputs
Whenever a digital input or an analogue high/low limit is active, it will be recorded by a counter. The number is displayed in menu F6:
Use the arrow keys to change between:
- digital input 1 - 8/12/16
- analogue high limit 1 - 4
- analogue low limit 1 - 4
In addition, the numerical keys 1 - 8 can be used to select the desired input.
The selected counter can be reset by pressing the ENTER key.
5.7 F7 - Counter for time
Menu F7 indicate for how long the digital input and the analogue high and low limits have been active. Time counters is running continuously such as if the input is set to OFF for some time and then is set to ON, the counter will count from the last value. The time is displayed in hours and minutes:
The scaled value is determined by the programming of the analogue input.
If the value represents e.g. a level measurement in a tank, and the level normally varies between 2 m and 3 m, the analogue input will normally be programmed so 2 m corresponds with '200' (low value) and 3 m corresponds with '300' (high value).
A level of 2,5 m will then give a scaled readout of 250 and 50 %.
If the scaled value should be shown as '2,5', it is possible to set a divisor for each input. In this example the divisor should have the value 100.
See also section 7.
M795GB0503
Use the arrow keys to change between:
- digital input 1 - 8/12/16
- analogue high limit 1 - 4
- analogue low limit 1 - 4
In addition, the numerical keys 1 - 8 can be used to select the desired input.
The selected counter can be reset by pressing the ENTER key.
15
SW ver. 830434
Data Transmitter 795
5.8 F8 - Alarm / Alarm number
Menu F8 indicate if the last 9 alarms are ON or OFF:
Each time a new alarm is activated, it will be recorded as alarm no. 1 and all other recorded alarms will move down one place and alarm 9 will be deleted. When the alarm for one input has been ON one time it must be set to OFF before a new alarm from the same input is accepted as an alarm.
If the alarm has not been reset and another 9 alarms occur, i.e. the first alarm become no. 10 and therefore will become invisible in the alarm list, this alarm will be reset automatically.
A flashing square is shown when an alarm goes ON.
If the alarm are being reset but is still active, a so­lid square is shown constantly. When the alarm goes OFF again, a square is shown constantly.
By means of the arrow keys or by entering the alarm number, the status, type and timestamps for on and off time can be displayed. Whenever an alarm goes ON, the input number and start time will be recorded. Similarly, when the alarm is reset, the reset time is recorded, and when the alarm goes OFF, the end time will be recorded:
5.9.2 F9.2 - Stormflow calculation
Whenever a stormflow occur, the flow is
3
displayed as m
/h in menu F9-2:
5.10 F# - Modem/Line status
(Only for versions with built-in telephone modem or GSM modem.)
Menu F# displays the status of outgoing alarm calls or incoming calls:
The following is displayed during an incoming call:
The following is displayed during an outgoing alarm call to one of the telephone numbers in the telephone number list:
When Data Transmitter 795 interlocks another Data Transmitter 795 i.e. in order to perform a remote start or stop of a pump, the following is displayed:
'ID' indicates the ID number of the Data Transmit­ter itself.
If the Data Transmitter are configured as a Master in a multidrop system, the 'ID' can also be the ID number of a connected Slave unit.
Return to normal operating display with the arrow keys or by prssing the '0' key.
5.9.1 F9.1 - Stormflow volume
Menu F9 displays the recorded stormflow volume.
The counter can be reset with the ENTER key.
M795GB0503
5.11 F* - Communication status
Menu F* indicate the communication status on the serial port, the port to Pump Controller 704, and the built-in telephone modem:
795 serial: R = Rx, T = Tx, CD = Carrier Detect, RTS = Request to send og CTS = Clear to send.
704: R = Rx, T = Tx and = Pump Controller 704 not interlocked / Pump Controller 704 interlocked. The Pump Controller 704 signal to the Data Transmitter that the Pump Controller 704 will not activate any control outputs, because the Pump Controller are interlocked.
16
SW ver. 830434
Data Transmitter 795
6 Programming of main functions
6.1 Select language
Select the desired language with the arrow keys and confirm with ENTER.
6.2 Set time and date
Enter time and date with the numerical keys or the arrow keys. Confirm with ENTER:
Just press ENTER at all entries if changes are not needed in order to proceed to the next menu.
6.3 Automatic change between summer time and winter time
Select if the clock should change automatically between summer time and winter time:
6.5 Calculation of average values on analogue inputs
The value of an analogue input is recorded every second, and every 5 minutes the values is log­ged. If averaging of the analogue values are selected, an average of the analogue value over the last 5 minutes will be calculated and logged.
If averaging is not selected, the analogue value at the actual time will be logged.
Use the arrow keys to select and confirm with ENTER.
6.6 Data logging interval
The data logging interval is used for the extended logging function, where the value for the analogue input and the level from MJK Pump Controller 704 is stored.
Use the arrow keys to select and confirm with ENTER.
Just press ENTER at all entries if changes are not needed in order to proceed to the next menu:
6.4 Access code enabled/disabled
Select if an access code is required to gain ac­cess to the remaining system menus. This function make it possible to protect the system configuration from unauthorized changes:
Use the arrow keys to select and confirm with ENTER.
6.4.1 Enter password
If access code protection is selected, a 4-digit access code is required in order to gain access to the remaining system menus.
The interval between loggings can be chosen amongst the following values: 30 sec. (00:30), 1 min. (01:00), 5 min. (05:00), 10 min. (10:00), 30 min. (30:00) and 1 hour (60:00).
Use the arrow keys to select and confirm with ENTER.
6.7 Tone / pulse dialing
Select between pulse or tone dialing from a telephone modem:
Use the arrow keys to select and confirm with ENTER.
6.8 Alarm call on power failure
If alarm call at power failure is selected, the Data Transmitter will call the first telephone number in the telephone list when the power supply fail. A power failure will not be detected before the supply has been gone for minimum 30 sec. Hereby alarm calls on short power surges are avoided.
M795GB0503
Use the arrow keys to select and confirm with ENTER.
17
SW ver. 830434
Loading...
+ 37 hidden pages