Xylem 702 User Manual

Manual
MJK Comtroller 702
Effective for software version 83XXXX
COMLI PROTOKOL
Unit ID:
Serial no.:
M702GB/0110 Rev. 111001
As our products are developed continuously, we reserve the right
CE - CERTIFICATE OF CONFORMITY
This product complies with the requirements concerning electromagnetic compatibility (EMC) stipulated in Council directive no. 89/336/EEC of 3rd May 1989, altered at directive no. 92/31/EEC, on the approximation of the laws of the Member States relating to electromagnetic compatibility.
We declare that the product complies to the values stipulated in EN 50081-1 and EN 50082-1.
M702GB/0110 Rev. 111001
2
ComTroller 702
Contents
1 General .................................................5
1.2 MJK-Link™ ...................................................5
2 Operation .............................................. 6
3 Menus ................................................... 8
3.1 F0 - Unit type/ID, software version, clock and
protocol type .................................................8
3.2 F1 - Inputs on/off ........................................... 8
3.3 F2 - Outputs on/off........................................8
3.4 F3 - Limits high/low .......................................8
3.5 F4 - Analog inputs # ...................................... 8
3.6 F5 - Analog input scaled ................................8
3.7 F6 - Counter .................................................9
3.8 F7 - Hour ...................................................... 9
3.9.1 F8.1 - Alarm List ........................................... 9
3.9.2 F8.2 Alarm # ................................................. 9
3.10 F9.1 Storm flow volume.................................9
3.11 F9.2 Storm flow calculation ...........................9
4 Main functions ...................................10
4.1 Choose language ........................................10
4.2 Set time and date .......................................10
4.3 Password enabled/disabled ......................... 10
4.4 Summer time / winter time .......................... 10
4.5 Enter password ........................................... 10
4.6 Analog inputs averaging...............................10
4.7 Data logging interval (MM:SS) ...................... 10
4.8 Tone or pulse dialing .................................... 10
4.9 Telephone call at power failure ..................... 10
4.10 Number of incoming rings before answer ..... 10
4.11 Unit ID no. for Comtroller ............................. 10
4.12 Automatic reset of alarms............................ 10
4.13 Telephone number ...................................... 10
4.14 SMSC telephone numbers .......................... 10
4.15 Master or Slave ........................................... 10
6 Digital inputs ..................................... 12
6.1 Digital input # .............................................. 12
6.2 Alarm / in use .............................................. 12
6.3 Signal delayed ............................................. 12
6.4 NO / NC ..................................................... 12
6.5 Alarm - call by telephone ............................. 12
7 Digital outputs ................................... 12
7.1 Digital output # ............................................ 12
7.2 NO / NC ..................................................... 12
7.3 Time / Fixed ................................................ 12
7.4 Time before start ......................................... 12
7.5 Set ON-time ............................................... 12
7.6 Special functions for the digital outputs ........ 12
8 Interlock .............................................. 13
8.1 Interlock in use yes/no ................................ 13
8.2 Start of interlock .......................................... 13
8.3 Stop interlock .............................................. 13
8.4 Interlock on receivers output # ....................13
8.5 Receivers telephone number ....................... 13
8.6 Receivers output # ...................................... 13
9 Pump control ..................................... 13
9.1 Pump control activated YES / NO ............... 13
9.2 Pump control EMPTYING / FILLING ............ 13
9.3 Pump control DO 2 ACTIVE ........................ 13
9.4 Pump alternation YES / NO ......................... 13
9.5 Level 2 in use YES / NO .............................. 13
9.6 Pump control start level ...............................13
9.7 Pump control start level ...............................13
10 Telephone list for alarms .................. 14
10.1 Telephone number 1-9 ................................ 14
10.2 Key In PS Message .....................................14
10.3 Entering SMS messages ............................. 14
5 Analog inputs ....................................11
5.1 Analog input # ............................................. 11
5.2 Input no 1 0 - 20 / 4 / 20 mA ...................... 11
5.3 Input no 1 scaled 0 / 4 mA ..........................11
5.4 Input no 1 scaled 20 mA ............................. 11
5.5 High limit yes / no ........................................11
5.6 Set high limit ...............................................11
5.7 High limit alarm / in use ............................... 11
5.8 High limit - signal delayed ............................ 11
5.9 High alarm - call by telephone ..................... 11
5.10 Low limit yes / no ........................................ 11
5.11 Set low limit................................................. 11
5.12 Low limit alarm / in use ................................ 11
5.13 Low limit - signal delayed............................. 11
5.14 Low limit - call by telephone ........................ 11
M702GB/0110 Rev. 111001
11 Programming of storm flow
calculation .......................................... 15
11.1 Stormflow calculation .................................. 15
11.2 Stormflow calculation in use Yes/no ............. 15
11.3 Zero-point DI # ............................................ 15
11.5 Key in the number of Q(h) points (1-9).......... 15
11.6 Key in the level mark ................................... 15
11.7 Key in the flow mark ................................... 15
12 Combi alarms ..................................... 15
12.1 Combi alarm # ............................................ 15
12.2 Combi alarm in use ..................................... 15
12.3 Combi alarm signals .................................... 15
12.4 Signal delay ................................................. 15
12.5 Combi alarm calls ........................................ 15
MJK Automation A/S
3
Byageren 7 2850 Nærum Tlf: 45 56 06 56 Fax: 45 56 06 46
ComTroller 702
13 Alarms ................................................. 16
13.1 Operational or alarm signal .......................... 16
13.2 Alarm calls .................................................. 16
13.3 Reset of alarms ........................................... 16
13.4 Special factory codes .................................. 16
13.5 Access code ............................................... 16
13.6 Setting up the serial port ............................. 16
13.7 Forced reset to factory settings ...................16
13.8 SMSC telephone numbers .......................... 16
14 Other information ..............................17
14.1 Specifications ..............................................17
14.2 Maintenance ............................................... 17
15 Electrical connection .......................... 18
15.1 Digital inputs ................................................ 18
15.2 Analog inputs .............................................. 18
15.3 Serial ports .................................................. 18
15.4 External 15 V DC supply .............................. 18
15.5 Software upgrade........................................ 18
16 Factory settings ................................. 20
M702GB/0110 Rev. 111001
4
ComTroller 702
1 General
MJK Comtroller 702 is developed for control and
surveillance of small pumping stations and water borings. Comtroller 702 is a complete unit with in­and outputs, CPU, data logger, real time clock and communications port for data transmission on owned lines.
Comtroller 702 is an advanced product based on the experience from the thousands of monitoring systems delivered during the past 15 years.
Comtroler 702 is an advanced product for on-site mounting with control, data logging storing and transmission of analog and digital measuring values to be used in both small and large SCADA sy­stems.
Comtroller 702 is typically arranged in clusters where each Comtroller is connected to a 2-wire communications line. A Data Transmitter 795 is then connected as a master communications unit. Every single Comtroller 702 can be called individually by their different ID numbers, and the Data Transmitter 795 simply handles the data transmission via a telephone modem, a radio transceiver or a GSM modem directly to the SCADA system.
Comtroller 702 has all necessary functions built in such as interface to measuring and control equipment, a data logger, counters and data
transmission. Comtroller 702 is programmed directly from a PC, from the SCADA system or via a MJK Data Transmitter 795 as a master communications unit.
Comtroller 702 is a compact unit containing all necessary functions such as communications inter­face and drivers, software, I/O ports, data storage memory and RS485 repeater.
Comtroller 702 is simple and economic to utilize since it contains all necessary facilities to decrease the number of external components needed to form a complete unit for control, monitoring and data transmission.
The RS 232 port is used for interconnection through external modems, GSM-modems or a PC for configuring or data readout.
1.2 MJK-Link™
The MS-Windows™-based program MJK-Link™ can be used for monitoring one or more Comtroller
702. It is possible with MJK-Link™ via a PC with a modem to read realtime values, stored values for investigation of storm flows and changing of setpoints.
This manual deals with MJK Comtroller 702 with Comli-protocol for telephone modems. GSM­modems, RS 485 on owned lines, powerline modems and closed radio networks.
Screen dump from the monitoring program MJK-Link™, where a pumping station with 2 pumps, monitored and
controlled by a Comtroller 702 are operated in a window that appears as the well-known MJK Data Transmitter 795.
MJK Automation A/S
M702GB/0110 Rev. 111001
5
Byageren 7 2850 Nærum Tlf: 45 56 06 56 Fax: 45 56 06 46
ComTroller 702
2 Operation
A Comtroller 702 can be considered as a Data Transmitter 795 without display and keypad and with a built-in pump controller. Instead of display and keypad the Comtroller 702 is operated via the serial communications port from either a PC with MJK-Link™ or a Data Transmitter 795.
MJK-Link™ is used for monitoring and operation of Comtroller 702. The Comtroller 702 will appear exactly as a Data Transmitter 795 in MJK-Link™ with its well-known 2 x 24 character display and keypad. The kepad is simply operated via the PC keyboard.
MJK-Link™ makes it possible to upload, download and save the settings for one or more Comtroller 702's interconnected on the same multi­drop communications æline. It is thus possible to download the setting from Comtroller no. 9, save the setting as i.e. "Pumping station at the bend" and upload the setting to Comtroller no. 14, placed at "Pumping station at the pond". It is also possible to name the in- and outputs individually.
A Data Transmitter 795 with Master-software can also be used to operate a number of Comtroller
702's on the same multidrop communications line. The desired Comtroller 702 is selected by entering the corresponding ID-number on the Data Trans­mitter 795, after which the selected Comtroller can be operated exactly as if it were a Data Transmitter
795. At the same time the Data Transmitter 795 contains a surveillance function that calls the Comtrollers one by one over an adjustable interval. If a Comtroller does not respond, the Data trans­mitter will send a system alarm.
A Data Transmitter 795 also manages comunication to the SCADA system, MJK-Link™ etc.
A typical installation covers five to 20 Comtrollers in an area where communication takes place via owned lines or with MJK PowerLine modems through the mains supply network.
On ie. the main pumping station, a Data Transmit­ter 795 with master software is installed, which will be able to send alarms via a telephone- or GSM modem to the SCADA system and/or one or more mobile telephones as SMS messages.
M702GB/0110 Rev. 111001
The figure shows an overview of the functional buttons and their general function.
6
ComTroller 702
Display
2 x 24 character backlit display for indication of programming menus, measuring values alarms etc.
ESC.-key
This key changes back to the previous menu or cancels a selection. By pressing the ESC.-key 2-3 times you will always return to the functional indication.
MENU
The MENU key are used to switch between main menus and submenus.
Arrow keys
The arrow keys are used for altering the current setting. In a submenu with selections, the top line shows the current setting and the bottom line shows the alternative setting (in brackets). The arrow keys are used to scroll between the selections. The arrow keys also alters the in­and output no. By activating the key, the number in the display will increase. By Activating the key the number will decrease.
Numerical keys
The keys 0-9,# and * are used for configuring telephone numbers, delays, analog scaling etc.
Function key F
The function key is used for selecting which functional indication to show on the display, e.g. F0.
ENTER
Press ENTER to change from a main menu to a sub menu, as well as between sub menus. Any choice made in the sub menus must be confirmed by pressing ENTER.
M702GB/0110 Rev. 111001
MJK Automation A/S
7
Byageren 7 2850 Nærum Tlf: 45 56 06 56 Fax: 45 56 06 46
ComTroller 702
3 Menus
3.1 F0 - Unit type/ID, software version, clock and protocol type
Menu F0 show the MJK unit type, protocol type, program version and date / time.
MJK 702 : 3 COMLI 830802 16:07:29 24/10/01
In above example, the Data Transmitter is connected to a Comtroller 702 with unit ID no. 3.
The Unit ID no. is set binary by means of 8 switches on the front panel. (All OFF = 0 - All ON =
255.) Note! The unit ID no. must be set within the
range 1 to 247.
3.2 F1 - Inputs on/off
In menu F1 is shown whether the digital inputs are ON or OFF.
INPUTS 1 2 3 4
ON : OFF:
The first two fields indicate if the high limits are exceeded and the last two show if the low limits are exceeded.
LIMITS HIGH/LOW 1 2
3 4 5 6 1 2
ON : OFF:
A delay time can be set individually for each analog input allowing the input to exceed the limit momentarily without i.e. activating an alarm. (See section 5.)
If the analog input are within limits, the field will be empty. If the limits are exceeded, the field will flash during the delay time. When the delay time has expired, the field is shown in a steady state.
3.5 F4 - Analog inputs #
Menu F4 shows the immediate value of an analog in­put as a horizontal bar formed of up to 24 fields. If the input signal is 4 (0) mA (see also section 5.2), none of the fields is lit (0 %). If the input signal is 20 mA, all 24 fields is lit (100 %).
In above example, DI no. 1 and 2 are ON while DI 3 and 4 are OFF.
A delay time can be set individually for each digital input in order to allow the input to go ON without activating i.e. an alarm. (See section 6.)
When the input is OFF an empty field is shown. When the input is ON, the field will flash for the duration of the delay time. When the delay time has expired, a full field will be lit.
3.3 F2 - Outputs on/off
Menu F2 show the status of the digital outputs.
OUTPUTS 1 2 3 4
ON : OFF:
In above example, DO no. 1 and 2 are ON while DO 3 and 4 are OFF.
A delay time can be set individually for each digital output in order to delay the activation of the corresponding output relay. (See section 7.)
When the output is OFF an empty field is shown. When the output is ON the field will flash for the duration of the delay time. When the delay time has expired, the output relay is activated and the field will be shown in a steady state .
ANALOG INPUT NO #
Select the desired analog input with the arrow keys or by keying the corresponding input number (1 - 2).
3.6 F5 - Analog input scaled
Menu F5 shows the immediate value of an analog input in digits rather than a horizontal bar as in the previous menu.
The first set of digits read out the signal value as the percentage between the low mA value (0/4 mA) (see also section 5.2) and the high mA value (20 mA). The next set of digits read out the same signal multiplied with a programmable scaling factor.
The readout scaling is determined by programming the desired readout range corresponding to the low mA value (0 / 4 mA) and the high mA value (20 mA) respectively. If e.g. a tank level is measured, and the level varies between 2 metres and 3 metres, the low mA value is set to correspond to "200" and the high mA value is set to "300". A level measurement of i.e. 2,5 metres will corespond to a signal value of 50 %, resulting in a readout of "250" (See section 5.3 - 5.4)
3.4 F3 - Limits high/low
Menu F3 indicate if the high and low limits for the analog inputs are exceeded.
M702GB/0110 Rev. 111001
ANALOG INPUT NO #
50 % SKALERET 250
Select the desired analog input with the arrow keys or by keying the corresponding input number (1 - 2).
8
ComTroller 702
3.7 F6 - Counter
Menu F6 shows how many times a digital input or an analog high or low limit has been set ON.
COUNTER DI # RESET: ENTER 257
Every single input / high and low limit has its own counter. Use the arrow keys to change the readout between:
- digital input 1 - 4
- analog input high limit 1 - 2
- analog input low limit 1 - 2
(Pressing key 1 to 4 will change the display read­out directly to digital input 1 to 4.)
If the ENTER button is keyed, the counter present in the display - and only this - will be reset.
3.8 F7 - Hour
Menu F7 show the total time the digital inputs and the analog high limits and low limits have been set ON.
The ON time is registered continuously; meaning that if an input or limit is set to OFF and later is set back to ON, the timer continues from its previous value.
HOUR : AI # LOW RESET: ENTER 2:43
Every single input / high and low limit has its own counter. Use the arrow keys to change the readout between:
- digital input 1 - 4
- analog input high limit 1 - 2
- analog input low limit 1 - 2
(Pressing key 1 to 4 will change the display read­out directly to digital input 1 to 4.)
ALARM NO 1 2 3 4 5 6 7 8 9
A flashing field indicates that the alarm is ON, an empty field indicates that the alarm is OFF, and a steady field indicates that the alarm has been reset.
All alarms in the list will be reset by pressing ENTER.
3.9.2 F8.2 Alarm #
By depressing an arrow key or 1-9, menu F8.2 will appear displaying the input number and type causing the alarm, the corresponding alarm desig­nation, the immediate status of the alarm and the time when the alarm was set.
ALARM # : AI 2 LAV START 15:23:1724/12/95
Use either the arrow keys to scroll through the alarm list or 1 to 9 to jump directly to the desired alarm number.
The alarm shown in the display will be reset by pressing ENTER.
Menu F8.1 will reappear by repetitous depressing of the arrow keys or 0.
3.10 F9.1 Storm flow volume
Menu F9 display the volume of the overflow. The volume meter is reset by depressing ENTER
STORM FLOW VOLUME RESET: ENTER 1204 m
3
3.11 F9.2 Storm flow calculation
Menu F9.2 display the immediate flow.
If the ENTER button is keyed, the counter present in the display - and only this - will be reset.
3.9.1 F8.1 - Alarm List
Menu F8.1 show a list of the last 9 alarms and their immediate status.
Whenever an alarm occurs, it will be registered as alarm no. 1 and all other alarms in the list is moved one place to the right. Furthermore, the previous alarm no. 9 will be erased and also be automatically reset if it has not already been reset manually via the Data Transmitter keypad or via the SCADA system. Also, an alarm deriving from a specific input has to be reset before a new alarm from that input will be put in the list.
M702GB/0110 Rev. 111001
STORM FLOW CALCULATION FLOW RATE 12.40 m
9
3
/t
MJK Automation A/S
Byageren 7 2850 Nærum Tlf: 45 56 06 56 Fax: 45 56 06 46
ComTroller 702
4 Main functions
4.1 Choose language
The desired language is chosen using the arrow keys - confirm with ENTER.
4.2 Set time and date
The time and date can be set using the arrow keys or the numerical keys. Confirm the changes with ENTER or press MENU if no changes are desired.
4.3 Password enabled/disabled
If password protection is enabled, a code must be keyed in before access is given to the menus with the MENU key.
If a password is desired, it must be keyed in before the system can be set up.
Use the arrow keys to select and confirm with ENTER.
4.4 Summer time / winter time
Select summer time or winter time with the arrow keys and confirm the selection with ENTER.
4.5 Enter password
Enter the password number with the numerical keys and confirm with ENTER.
4.6 Analog inputs averaging
Every second the value of the analog inputs are registered, and for every 5 minutes the analog values are logged. If averaging is wanted, a mean of all the 1 sec. registrations for the last 5 minutes is logged. If averaging is not wanted, the current analog value is logged.
Use the arrow keys to select and press ENTER to confirm.
that would be caused by very short voltage failures.
This function is only available if the Comtroller is supplied from an external 12 V DC source with battery backup.
Use the arrow keys to select and confirm with ENTER.
4.10 Number of incoming rings before answer
Select the number of rings before the Comtroller 702 should answer a call. The number of rings can be set between 1 and 5. Use the arrow keys to select and confirm with ENTER.
4.11 Unit ID no. for Comtroller
In this menu the Unit ID no. of the current Comtroller is displayed. The Unit ID no. is used to identify the different Comtroller 702's that may be interconnected through the same multidrop line. The Unit ID no. is set binary by means of 8 switches on the front panel. (All OFF = 0 - All ON =
255.)
Note! The unit ID no. must be set within the range 1 to 247.
4.12 Automatic reset of alarms
Select whether an active alarm should be reset automatically if (1) the alarm cause disappears before the alarm are transmitted or (2) the alarm is not reset from the SCADA terminal. Use the arrow keys to select and confirm with ENTER.
4.13 Telephone number
Enter the number of the telephone line to which the Comtroller is connected. The telephone number is used as ID-number when SMS alarms are transmitted.
4.7 Data logging interval (MM:SS)
The data logging interval are used for the enhanced logging function that stores the values from the analog inputs. The logging interval can be selected in the following fixed intervals: 30 sec. (00:30), 1 min. (01:00), 5 min. (05:00), 10 min. (10:00), 30 min. (30:00), and 60 min. (60:00).
Use the arrow keys to select and press ENTER to confirm.
4.8 Tone or pulse dialing
Select whether the telephone call is to be carried out with tone or pulse signals.
Use the arrow keys to select and confirm with ENTER.
4.9 Telephone call at power failure
If this function is selected, the Comtroller will dial the first number on the telephone list (see section
10) if the mains supply disappears for more than 30
seconds. The 30 second delay avoids alarm calls
M702GB/0110 Rev. 111001
Key in the number and confirm with ENTER.
This function is only available if a modem is connected.
4.14 SMSC telephone numbers
In order to make the Comtroller able to transmit SMS messages, the SMS message must be dialed to a particular SMSC server. See section 10 for telephone numbers to SMSC-servers.
Key in the number and confirm with ENTER.
This function is only available if a modem is connected.
4.15 Master or Slave
Select whether the Comtroller 702 should act as a Master or a Slave on the multidrop communications line.
Use the arrow keys to select and confirm with ENTER.
10
ComTroller 702
5 Analog inputs
5.1 Analog input #
Select the input to be set by pressing 1. Confirm with ENTER.
5.2 Input no 1 0 - 20 / 4 / 20 mA
Select if the signal range for the analog input should be either 0 - 20 mA or 4 - 20 mA.
Use the arrow keys to select and confirm with ENTER.
5.3 Input no 1 scaled 0 / 4 mA
Set the equivalent of the low mA value. If i.e. "200" is entered, the display will read out "200" at an in­put value of 0 / 4 mA. Use the arrow keys or the numeric keys and confirm with ENTER.
5.4 Input no 1 scaled 20 mA
Set the equivalent of the high mA value. If i.e. "300" is entered, the display will read out "300" at an input value of 20 mA. Use the arrow keys or the numeric keys and confirm with ENTER.
5.5 High limit yes / no
Select if exceeding the high limit setting on the analog input should be registered.
Use the arrow keys to select and confirm with ENTER.
5.10 Low limit yes / no
Select if exceeding the low limit setting on the ana­log input should be registered.
Use the arrow keys to select and confirm with ENTER.
5.11 Set low limit
Set the low limit that the analog input should exceed before the event is registered.
Use the arrow keys to select and confirm with ENTER.
5.12 Low limit alarm / in use
See section 13.1 for a description between "Limit alarm" and "In use".
Use the arrow keys to select and confirm with ENTER.
5.13 Low limit - signal delayed
Set the delay time that the input can exceed the high limit setting without an alarm is being activated. The format for the delay period is MM:SS.
In the case of a power failure the analog input will detect 0 mA. If analog low limit is set to ALARM simultaneously with a alarm call at power failure (see section 4.9), the delay time of the low limit must be set to more than 30 sec.
5.6 Set high limit
Set the high limit that the analog input should exceed before the event is registered.
Use the arrow keys to select and confirm with ENTER.
5.7 High limit alarm / in use
See section 13.1 for a description between "Limit alarm and In use".
Use the arrow keys to select and confirm with ENTER.
5.8 High limit - signal delayed
Set the delay time that the input can exceed the high limit setting without an alarm is being activated. The format for the delay period is MM:SS.
Use the arrow keys (double arrow for minutes and single arrow for seconds) or the numeric keys and confirm with ENTER.
5.9 High alarm - call by telephone
Select whether an activated high limit alarm is to set off a telephone call.
Use the arrow keys (double arrow for minutes and single arrow for seconds) or the numeric keys and confirm with ENTER.
5.14 Low limit - call by telephone
Select whether an activated low limit alarm is to set off a telephone call.
Use the arrow keys to select and confirm with ENTER.
Use the arrow keys to select and confirm with ENTER.
M702GB/0110 Rev. 111001
11
MJK Automation A/S
Byageren 7 2850 Nærum Tlf: 45 56 06 56 Fax: 45 56 06 46
ComTroller 702
6 Digital inputs
6.1 Digital input #
Use the arrow keys or enter 1 to 4 to select the in­put to be programmed.
6.2 Alarm / in use
See section 13.1 for a description between "Limit alarm" and "In use".
Use the arrow keys to select and confirm with ENTER.
6.3 Signal delayed
Set the delay time the input can be ON without an alarm is being activated.
The format for the delay period is MM:SS.
Use the arrow keys (double arrow for minutes and single arrow for seconds) or the numeric keys and confirm with ENTER.
6.4 NO / NC
Select the input as normally open (NO) or normally closed (NC). At NO the input is ON when the power is connected; at NC the input is ON when the power is disconnnected.
Use the arrow keys to select and confirm with ENTER.
6.5 Alarm - call by telephone
Select if a digital input is to set off a telephone call when going ON.
Use the arrow keys to select and confirm with ENTER.
7 Digital outputs
7.1 Digital output #
Use the arrow keys or enter 1 to 4 to select the output to be programmed.
7.2 NO / NC
Select the relay function to normally open (NO) or normally closed (NC). At NO the relay switch will go ON when the output is activated; at NC the relay switch will go OFF when activated.
Use the arrow keys to select and confirm with ENTER.
At power failure all the outputs will go OFF.
7.3 Time / Fixed
A time controlled output is only ON for a certain period of time (the ON-time) whereafter it goes OFF. A fixed output which is turned ON must receive a command in order to set the output OFF.
Use the arrow keys to select and confirm with ENTER.
7.4 Time before start
Enter the delay time before start - which is the time passing from an ON-command is transmitted until the output responds.
The format for the delay period is MM:SS.
Use the arrow keys (double arrow for minutes and single arrow for seconds) or the numeric keys and confirm with ENTER.
7.5 Set ON-time
Enter the ON-time for the output. The On-time is the period of time the output is turned ON if the output is set to "time controlled".
The format for the delay period is MM:SS.
Use the arrow keys (double arrow for minutes and single arrow for seconds) or the numeric keys and confirm with ENTER.
7.6 Special functions for the digital outputs
(This menu is only accessible if 'Fixed' is selected as described in section 7.3.)
It is possible to perform AND logic sequences by means of the digital in- and outputs.
For example the Comtroller 702 can be program­med to activate a digital output when 2 digital inputs are ON. The digital signals can also derive from exeeding a limit value on an analog input - or a combination of a signal caused by exceeding a limit value and an active digital input.
The following signals can be combined:
- digital input 1 - 4
- analog limit HIGH 1 - 2
- analog limit LOW 1 - 2
- combi alarm 1 - 8
M702GB/0110 Rev. 111001
12
ComTroller 702
8 Interlock
When interlocking two MJK Comtroller 702's they will communicate with one another. In this way one data transmitter can control a digital output remotely on the other.
8.1 Interlock in use yes/no
Select whether the interlock function is to be used or not.
Use the arrow keys to select and confirm with ENTER.
8.2 Start of interlock
Select the signal which - when it goes ON - will make the Comtroller call the other Comtroller and set an output ON.
Use the arrow keys to select and confirm with ENTER.
The following signals can be selected:
- digital input 1 - 4
- analog limit HIGH 1 - 2
- analog limit LOW 1 - 2
- combi alarm 1 - 8
As long as the signal is ON, calls will take place in 10 minutes interval. The remote controlled output must therefore be set to "time controlled" and configured with an ON-time of more than 10 minutes (e.g. 15 min.), thus securing that the out­put is not constantly ON if an error situation should occur (e.g. a broken telephone cable). This way the output is certain to go OFF even in the case of communication failure.
At faultless communication the ON time of the remote controlled output will be initialised at each call and the remote controlled output will stay ON as long as the controlling signal is active.
8.3 Stop interlock
Select the signal which - when it goes ON - will make the Comtroller call the other Comtroller and set an output ON.
Use the arrow keys to select and confirm with ENTER.
The following signals can be selected:
- digital input 1 - 4
- analog limit HIGH 1 - 2
- analog limit LOW 1 - 2
- combi alarm 1 - 8
Only one call attempt will be made. If the same signal is chosen both as start and finish condition for the inter lock, the finish condition will be when the signal goes OFF.
8.4 Interlock on receivers output #
Select which digital output of the remote Comtroller is to be controlled.
Use the arrow keys to select and confirm with ENTER.
8.5 Receivers telephone number
Enter the ID number of the remote Comtroller and confirm with ENTER or start press ENTER to correct a number already keyed in.
If Powerline modems, radio modems, or the RS485 port are used, the ID number of the remote Comtroller should also be used.
8.6 Receivers output #
Select which output on the remote Comtroller to be controlled.
Use the arrow keys to select and confirm with ENTER.
9 Pump control
9.1 Pump control activated YES / NO
Select if the pump controller should be activated.
Use the arrow keys to select and confirm with ENTER.
9.2 Pump control EMPTYING / FILLING
Select if output no. 1 or 2 should be configured for either emptying or filling.
Use the arrow keys to select and confirm with ENTER.
9.3 Pump control DO 2 ACTIVE
Select if 1 og 2 pumps are used.
Use the arrow keys to select and confirm with ENTER.
9.4 Pump alternation YES / NO
Select if the pumps should alternate. This menu is only available when 2 pumps are selected in section 9.2.
Use the arrow keys to select and confirm with ENTER.
9.5 Level 2 in use YES / NO
Select if both pumps may start at the same time. This menu is only available when 2 pumps are selected in section 9.2.
Use the arrow keys to select and confirm with ENTER.
9.6 Pump control start level
Set the start level for the pump(s)
Use the arrow keys to select and confirm with ENTER.
9.7 Pump control start level
Set the stop level for the pump(s)
Use the arrow keys to select and confirm with ENTER.
M702GB/0110 Rev. 111001
13
MJK Automation A/S
Byageren 7 2850 Nærum Tlf: 45 56 06 56 Fax: 45 56 06 46
ComTroller 702
10 Telephone list for alarms
(This section applies is only
10.1 Telephone number 1-9
In this menu up to 9 telephone numbers are keyed in which will be dialed chronologically at an alarm situation.
Press key 1 - 9 to select the number which is to be changed, press ENTER to change the receiver type (PC, Pager, ph [phone], SMS), press ENTER to correct the number - key in the number with the numerical keys, and confirm with ENTER.
After keying in the telephone number the MENU key must be used in order to move on to the next menu, the ENTER key will be of no use here.
When calling through a switchboard, a * can be used for awaiting a dialtone. A * gives a pause of 2 seconds. I.e. 0*00454556,656##23 means:
First dial 0 to get an external line, await the dialling tone, then dial 0045 45560656, wait for 4 seconds, then dial 23.
In the parenthesis following the number, it is stated which type of reciever the call has been made to. When calling a modem set to 1 [PC]. When calling a beeper / pager set to 2 [Pager]. When calling an ordinary telephone set to 3 [PHONE].
10.2 Key In PS Message
If a telephone number has been chosen as a PS number, a message of up to 8 digits can be typed in (e.g. the telephone number of the data transmit­ter), the message can be different for the various telephone numbers. The message for the pager is shown in the pager display together with a code for the alarm, which has caused the call.
E.g. a datatransmitter with telephone number 455660656 where digital input 5 has an active alarm input; will give the following alarm message in the PS:
05-45560656
The configuration is stored in a EEPROM which is not lost even if the supply is disconnected
10.3 Entering SMS messages
Up to 8 characters can be entered here if a recei­ver type is selected as an SMS type.
It is possible to enter digits as an SMS message via Data Transmitter 795, and with MJK-Link32™ it is also possible to enter a text.
The SMS message will be shown on the cellular phone with "MJK-702" as the opening text, followed by the cause of the alarm and the corresponding SMS message. If a GSM modem are used as communications unit, the pager message will be changed to an SMS message. Check the SIM card in a cellular phone if no SMS message is transmitted, and check, if the phone number to the SMSC-server is correct. The phone number to the SMSC-server depends on the GSM network service provider.
When sending SMS messages and pager messages, it is not possible to check whether the message is sent to the recipient or not, since the messages are delivered to an external server.
The alarm codes are:
01 : Digital input no 1 02 : Digital input no 2 03 : Digital input no 3 04 : Digital input no 4
21 : Analog limit no 1 LOW 22 : Analog limit no 2 LOW
31 : Analog limit no 1 HIGH 32 : Analog limit no 2 HIGH
51 : Combi alarm no. 1 52 : Combi alarm no. 2 53 : Combi alarm no. 3 54 : Combi alarm no. 4 55 : Combi alarm no. 5 56 : Combi alarm no. 6 57 : Combi alarm no. 7 58 : Combi alarm no. 8
90 : Comtroller power failure
M702GB/0110 Rev. 111001
14
ComTroller 702
11 Programming of storm flow
calculation
11.1 Stormflow calculation
Comtroller 702 can be applied for calculation of storm flow by means of one digital and analogue input. Generally Comtroller 702 is applied to a level meter with measuring range adapted to the pump controller. This measuring range is normally considerably higher, than what is necessary for flow measurement, generally 10m for the pump controller and 10-20cm for flow calculation. The accuracy of the pump controller’s level measurement is as the whole measuring range. The data transmitter will compensate by means of a digital input. An electrode relay, e.g. MJK 501 and a level electrode e.g. MJK 222860 are applied.
The level electrode is applied where the storm flow starts. By this, the chosen level meter will be in zero position and calculate flow on the level signal. This will improve the accuracy 10 to 15 times in short term. The system provides a simple and accurate measurement to a reasonable price.
11.2 Stormflow calculation in use Yes/no
Indicate application of stormflow calculation.
Use the arrow keys and confirm with enter key.
11.3 Zero-point DI #
Indicates the digital input that sets zero-point and activates the flow calculation.
Choose between AI 1-2
Use the arrow keys, confirm with ENTER.
11.5 Key in the number of Q(h) points (1-9)
Indicate the number of Q/H points for single linearization of the actual flow. The number can be set between 1 and 9, as zero-point is set to a flow
3
of 0 m
/h.
12 Combi alarms
It is possible by means of a combi alarm to set off an alarm call when 2 digital signals is activated simultaneously. A digital signal can derive from a digital input or from a limit alarm.
12.1 Combi alarm #
Use the arrow keys or enter 1 to 8 to select the combi alarm to be programmed.
12.2 Combi alarm in use
Select if the combi alarm should be used. Use the arrow keys and confirm with ENTER.
12.3 Combi alarm signals
Select the two digital signals to be AND'ed to activate a combi alarm. The following digital signal can be selected:
- digital input 1 - 4
- analog limit HIGH 1 - 2
- analog limit LOW 1 - 2
- power failure
12.4 Signal delay
Select the delay for the combilalarm. The delay time is the time the two digital signals should be active at the same time to set a combi alarm.
The format for the delay period is MM:SS.
Use the arrow keys (double arrow for minutes and single arrow for seconds) or the numeric keys and confirm with ENTER.
12.5 Combi alarm calls
Select if a combi alarm should set off an alarm call. Use the arrow keys and confirm with ENTER.
Use the arrow keys and confirm with ENTER.
11.6 Key in the level mark
Key in the level (h) in a Q(h) – point. Use the keys 0-9, confirm with ENTER.
The level must be higher than the previous.
11.7 Key in the flow mark
Key in the volume (Q) in a Q(h) point. Use the keys 0-9 and confirm with ENTER.
M702GB/0110 Rev. 111001
15
MJK Automation A/S
Byageren 7 2850 Nærum Tlf: 45 56 06 56 Fax: 45 56 06 46
ComTroller 702
13 Alarms
13.1 Operational or alarm signal
The digital signals can be chosen as either operational or alarm signals.
A operational signal can be defined as non-critical, i.e. a signal, that one want to be registered. Typically a signal, that indicate if a pump is running or not.
An alarm signal is on the other hand a signal, that normally is inactive and only will be active, when a fault condition occurs. A thermal cutout on a pump is a typical alarm signal.
Alarm signals has memory and reset, i.e, when the alarm signal becomes non-active, it will be memorized that the signal has been active. The "active" state must be reset by the user before a new active signal can be accepted as an alarm signal. For both types of signals applies that both the number of active conditions and the time frame within the signal has been active, will be registered.
13.2 Alarm calls
If the function "Alarm - call by telephone" is selected (see section 6.5), the Comtroller 702 will start a call routine by making a call attempt to the first number in the phone list, then the next number etc.
There will be a pause between the call attemps. See also section 10.
When dialing to a telephone modem, it will be the SCADA terminal that will be responsible for resetting the alarm and stop the call routine.
When dialing a pager or telephone, the call routine must be stopped with a telephone call back to the Comtroller. This procedure will not reset the alarm, only stop the call routine. If an alarm occurs during the call routine, the call routine will not stop, i.e. the new alarm will not be reported until the next call succeeds.
The telephone list is not used if the RS485 port are used for communication (via radio modem, Powerline modem owned lines etc.). All alarm calls is sent to the Master communications unit.
13.3 Reset of alarms
When a digital alarm signal becomes active, it will be displayed in function menu F 8.1. Function menu F 8.2 will display the input number and type causing the alarm, the corresponding alarm desig­nation, the immediate status of the alarm and the time when the alarm was set.
indicating the status. The symbol flashes until the alarm is registered which makes the symbol permanently lit. The symbol stays lit until the alarm signal is no longer active, then the signal disapears and the stop time will show instead of the start time.
To reset an alarm directly from the Data Transmit­ter keyboard, the display must show indication F8.1. With the arrow keys the alarm to cancel is chosen then press ENTER. The symbol will then stop flashing and the alarm is registered.
An alarm can also be reset from the SCADA sta­tion via modem. This is carried out via the communications protocol. If you do not wish to have more calls on the account of a specific alarm signal, it can be left unregistered, and there will be no more calls, even if the signal changes from not active to active.
If the alarm is not registered, and a further 9 alarms occur, i.e. the unregistered alarm becomes no 10 the alarm will be cancelled.
13.4 Special factory codes
Comtroller 702 is provided with functions which should not be served by the final user.
13.5 Access code
If the access code is lost, the code 1111 can always be used.
13.6 Setting up the serial port
If the service code 2222 is used, it gives access to adjustment of the baud rate. Contact the technical hotline for help.
13.7 Forced reset to factory settings
It is possible to reset all settings to factory setting, meaning that all settings must be made once again. Use service code 2045.
13.8 SMSC telephone numbers
SMS-beskederne from Data transmitter 795 and Comtroller 702 is sent to an SMSC server on the following telephone numbers:
Denmark: (0045) 43 62 52 50
Nederlands: (0031) 653 14 14 14
Norge: (0047) 90 00 21 98
Portugal: (0035) 19 62 11 3000
Sweden: (0046) 7 40 93 00 00
Germany: (0049) 172 227 80 20
When a digital alarm signal become active, the alarm status will be shown in funtional indication F8.1. In functional indication F8.2 will be shown: the type of alarm, the time of start and a symbol
M702GB/0110 Rev. 111001
16
ComTroller 702
14 Other information
14.1 Specifications
Supply: 230 V AC / 12 V DC.
Fuse: 63 mA T built-in
Analog inputs: 2 AI, 0-20 / 4-20 mA
or 0 - 1 V DC
Digital inputs: 4 DI, optocoupler with10 k
serial resistor
Digital outputs: 4 DO, relays, maxs. 48 V AC, 1A
Consumption: Approx. 5 VA
Temp. range: – 20 … + 60 °C
Material: Polystyrol
Enclosure: IP 21
Clock: Real time clock with built in
backup battery
Data- 1 x RS 232 for modem, UHF communication: radio, GSM modem,
Data Transmitter 795 or PC. 2 x RS 485 for owned lines / APL lines (multidrop)
Indication: 5 LED's for power indication and
for indication of the relay state.
14.2 Maintenance
MJK Comtroller 702 requires no particular maintenance.
M702GB/0110 Rev. 111001
17
MJK Automation A/S
Byageren 7 2850 Nærum Tlf: 45 56 06 56 Fax: 45 56 06 46
ComTroller 702
15 Electrical connection
Al connections are shown on the front panel.
15.1 Digital inputs
The digital inputs (DI 1-4) has optocouplers with 10 k serial resistors. The inputs can be configured individually to normally open (NO) or normally closed (NC).
15.2 Analog inputs
The input can be configured for either 0 - 20 mA or 4
- 20 mA. Below is shown a connection example with
an active a non-active signal source. The pressure transmitter is an non-active signal source. The active power source is fed from a separate power supply.
15.5 Software upgrade
If a software upgrade becomes necessary, it is possible to perform the upgrade yourself. The soft­ware is loaded into an EPROM. Do the following to change the EEPROM::
Select NO in the menu "Alarm - call by telephone" is selected (see section 6.5)
Disconnect the Comtroller 702.
Remove the old EPROM from the socket and insert the new one. Note that the little notch in the EEPROM is oriented correctly in relation to the socket.
Connect the Comtroller 702.
Remember to select "Alarm - call by telephone".
15.3 Serial ports
The Comtroller 702 is equipped with 1 x RS232­port on terminal 28 - 32, that can be used for communication to i.e. a PC or PLC that supports the current communications protocol.
2 RS485 ports is available on terminal 23 - 25 and 26
- 28 for communication via owned lines / APL-lines.
Comtroller 702 is equipped with a repeater, so maximum distance between every Comtroller on the multidrop line can be obtained.
15.4 External 15 V DC supply
Terminal 33 / 34 is a 15 V DC output for external use. Max. load 100 mA.
M702GB/0110 Rev. 111001
18
ComTroller 702
M702GB/0110 Rev. 111001
19
MJK Automation A/S
Byageren 7 2850 Nærum Tlf: 45 56 06 56 Fax: 45 56 06 46
ComTroller 702
16 Factory settings
Main functions: Setting:
Language English Access code No Change between summer and winter time No Analog input averaging No Data logging interval 00:30 (30 sek.) Tone/Pulse dialing Tone Alarm - call by telephone No Rings before answer 1 ID-nr. for Comtroller Set via switches on the front Automatic reset of alarms No 702 phone number ­SMSC phone number ­Master or Slave Slave
Analog inputs: Analog input 1: Analog input 2:
0-20mA/4-20mA 4-20 mA 4-20 mA Min. scaling 0 00 Max. scaling 999 999 High limit Nej Nej High limit setting 999 999 High limit operation /alarm Operation Operation Alarm delay (sec.) 0 0 Call by phone No No Low limit No No Low limit setting 0 0 Low limit operation / alarm Operation Operation Alarm delay (sec.) 0 0 Call by phone No No
Digital inputs: Operation/Alarm: Signal delayed: NO/NC: Call by phone:
Digital input no. 1 Operation 0 NO No Digital input no. 2 Operation 0 NO No Digital input no. 3 Operation 0 NO No Digital input no. 4 Operation 0 NO No
Digital outputs: NO/NC: Timer/Fixed: Time before start: On-time:
Digital output no. 1 NO Tid 5 10 Digital output no. 1 NO Tid 5 10 Digital output no. 1 NO Tid 5 10 Digital output no. 1 NO Tid 5 10
M702GB/0110 Rev. 111001
20
ComTroller 702
Pump Controller: Setting:
Pump control activated Yes / No No
Telephone list:
Telephone no 1 Available 0 0 Telephone no 2 Available 0 0 Telephone no 3 Available 0 0 Telephone no 4 Available 0 0 Telephone no 5 Available 0 0 Telephone no 6 Available 0 0 Telephone no 7 Available 0 0 Telephone no 8 Available 0 0 Telephone no 9 Available 0 0
Storm flow calculation: Setting:
In use Yes / No No Zero level DI 1 Level measurement AI 1 Number of points 9 Q/H point no 1 Level: 10 (cm) ; Flow (m Q/H point no 2 Level: 20 (cm) ; Flow (m Q/H point no 3 Level: 30 (cm) ; Flow (m Q/H point no 4 Level: 40 (cm) ; Flow (m Q/H point no 5 Level: 50 (cm) ; Flow (m Q/H point no 6 Level: 60 (cm) ; Flow (m Q/H point no 7 Level: 70 (cm) ; Flow (m Q/H point no 8 Level: 80 (cm) ; Flow (m Q/H point no 9 Level: 90 (cm) ; Flow (m
Combi alarms: In use: Alarm signals: Signal delayed: Alarm call:
Combi alarm 1 No DI 1 AND DI 1 00:00 No Combi alarm 2 No DI 1 AND DI 1 00:00 No Combi alarm 3 No DI 1 AND DI 1 00:00 No Combi alarm 4 No DI 1 AND DI 1 00:00 No Combi alarm 5 No DI 1 AND DI 1 00:00 No Combi alarm 6 No DI 1 AND DI 1 00:00 No Combi alarm 7 No DI 1 AND DI 1 00:00 No Combi alarm 8 No DI 1 AND DI 1 00:00 No
Type (PC/OPS/ Telephone OPS/SMS-
Telefon/SMS): number: message:
3
/h) : 1.11
3
/h) : 2.22
3
/h) : 3.33
3
/h) : 4.44
3
/h) : 5.55
3
/h) : 6.66
3
/h) : 7.77
3
/h) : 8.88
3
/h) : 9.99
Pause in min.:
M702GB/0110 Rev. 111001
21
MJK Automation A/S
Byageren 7 2850 Nærum Tlf: 45 56 06 56 Fax: 45 56 06 46
Loading...