Xylem 205546 User Manual

Page 1
Modbus Communication Modules
Modbus Communication Modules
for Displays
Order no. 205546
Modbus and RS 485 Communication Module
EN 6.81 Modbus Communication Module 205546 Manual 1212
Manual
1
Page 2
Modbus Communication Modules
Table of Contents
1. Introduction 3
2. Communication Modules 4
2.1 Modbus and RS 485 Communication Module . . . . . . . . . . . . . . 4
2.1.1 Version Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1.2 Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1.3 Physical mounting of Modbus module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1.4 Configuration Remarks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.1.5 Connection Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.1.5.1 One Connected Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.1.5.2 Three Connected Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.1.5.3 Three Connected Units and One Common Display . . . . . . . . . . . . . . . . . . . 14
3. Order Numbers 15
4. Register Lists 16
4.1 MagFlux Register List . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.2 Oxix / SuSix Register List . . . . . . . . . . . . . . . . . . . . . . . . 21
4.3 mA-Bus Converter List . . . . . . . . . . . . . . . . . . . . . . . . . . 25
MagFlux®, SuSix® and Oxix® are registered trademarks of MJK Automation A/S, Denmark.
Modbus® is a registered trademark of the Modbus Organization
Bluetooth® is a registered trademark of Bluetooth SIG.
EN 6.81 Modbus Communication Module 205546 Manual 1212
2
Page 3
Modbus Communication Modules
1. Introduction
Thank you for choosing MJK Modbus communication module. We have done our utmost to design and manufacture a high quality product that should satisfy your requirements.
The MJK modem and communication modules is easy to install in MJK MagFlux©, SuSix© and Oxix© units and to put into service. However, read this manual first to learn more about the specifications, how to install and how to operate the equipment.
The equipment must be handled and operated as instructed by the manufac­turer, MJK Automation A/S, to ensure stable operation.
The MJK modem and communication modules can be obtained in several dif­ferent versions supporting standard communication types and protocols like PSTN, GSM, GPRS, RS 232, RS 485, Modbus RTU, Profibus PA and Blue­tooth. This manual covers Modbus RS 485.
You can always contact your local representative or the MJK hot lines for advice and guidance:
Europe Tel.: +45 45 56 06 56 E-mail: mjk@mjk.com
Denmark Tel.: +45 45 56 06 56 E-mail: mjk@mjk.dk
Norway Tel.: +47 69 20 60 70 E-mail: mjk@mjk.no
Holland Tel.: +31 251 672171 E-mail: mjknl@mjk.com
USA Tel.: +1 847 482 8655 E-mail: mjkusa@mjk.com
Visit our web sites at www.mjk.com to learn more about MJK Automation A/S, our products and the people behind them.
MJK Automation A/S is a Xylem brand.
1. Introduction
3
Page 4
Modbus Communication Modules
2. Communication Modules
2.1 Modbus and RS 485 Communication Module
PCB no.: 510327-xxx Communication RS485
GND
3V3
Figure 1. Modbus and RS 485 Communication Module
2.1.1 Version Requirements
The following software, firmware and hardware versions (or higher) are re­quired for displays without an installed communication module:
• Converter HW ver.: 807000
• Converter FW ver.: 842009-001
• Display HW ver.: 807056
• Display FW ver.; 841018-000
• Text file ver.: 841513-011
• MJK-Field Link ver.: 840110-48
Termination
ON
OFF
GNDB
GND
RS485
B
A
GND
5V
RTS
GND
Rx Tx 3V3
5V5
EN 6.81 Modbus Communication Module 205546 Manual 1212
4
Page 5
Modbus Communication Modules
2.1.2 Technical Specifications
Specification Description
Mounting With 4 screws on transmitter’s I/O board
Protection IP 20
Dimensions 51 x 82 mm ( H x W)
Connectors One 5-position plugable screw terminal and one 20-pin bus
connector
Temperature -20 to +60 °C
Settings One “Termination” dip switch
LEDs White LEDs for “5V”, “Rx”, “Tx” and “3V3”
Power consump. Approx. 0.18 VA
Com. type RS 485 asynchronous, half duplex
Baud rate 300, 1200, 4800, 9600, 19200, 38400, 57600, 115200
Parity Even, odd, none
Stop bits 1 , 2
Modbus ID offset 0 - 240
Protocol Modbus RTU
Table 1. Specifications - Modbus and RS 485 Communication Module
2. Communication Modules
5
Page 6
Modbus Communication Modules
2.1.3 Physical mounting of Modbus module
1. Dismount screws
2. Remove back plate
EN 6.81 Modbus Communication Module 205546 Manual 1212
3. Remove lid using a screwdriver
6
Page 7
Modbus Communication Modules
4. Align pins with contacts
5. Check all pins is in place in the Modbus slot and check placing for screws
2. Communication Modules
6. Secure module using 4 screws
7
Page 8
Modbus Communication Modules
7. Ensure all 4 screws are in place
8. Make sure the rubber protection for cable is in place
EN 6.81 Modbus Communication Module 205546 Manual 1212
9. Remount the back using the 3 screws
8
Page 9
Modbus Communication Modules
10. Terminal should be “ON” if the display is last or only in chain
2. Communication Modules
9
Page 10
Modbus Communication Modules
2.1.4 Configuration Remarks
• The connected units on the Modbus have unique assigned IDs built as follows: SRO modbus ID = Instrument modbus ID + modbus ID offset
• ID 0 (broadcast) cannot be used (a broadcast is used for synchronous transmission of messages to all connected units).
• Available registers are limited to the measured value registers of the indi­vidual units. Configuration settings cannot be accessed.
• The PLC time-out on the Modbus must be set to 5 seconds from the SCADA system or the master PLC unit.
• COM module configuration/setup is executed from the “Display Setup/ Communication” menu (see below).
• The “Communication” option in the display menu automatically appears, when a communication module is connected to the display.
Display Setup
Language Set Clock Modbus Factory settings Display SW version Communication
Back Select OK
Communication
Baud rate Parity Stop bits Modbus ID offset
Back Select OK
Baud rate 300 1200 4800 9600 19200 38400 57600 115200
Back Select OK
Default:
9600
Figure 2. COM Module Configuration
EN 6.81 Modbus Communication Module 205546 Manual 1212
Parity Even Odd None
Back Select OK
Stop bits 1 2
Back Select OK
Modbus ID offset
000
Back Select >
10
Even
1
000
Page 11
Modbus Communication Modules
2.1.5 Connection Examples
2.1.5.1 One Connected Unit
This example illustrates connection, termination and ID configuration of a single unit with a communication module and a PLC.
Termination
OFF
GND
B
RS485
A
GND
GND
5V5
ON
GND
B
A
GND
GND
Termination
OFF
ON
PLC
B
A
GND
PE
Unit #1
PCB no.: 510327-xxx Communication RS485
GND
GNDB
RS485
5V
RTS Rx Tx 3V3
3V3
Figure 3. One Connected Unit
Exampe ID settings
If the connected unit has ID=1 (seen from the com module), and the com module has ID offset=200, the SRO Modbus ID is “201” (200 + 1, seen from the PLC).
Termination
Modbus RS 485 communication requires bus termination. Therefore the con­nected COM module’s termination dip switch is set in “ON” position.
2. Communication Modules
11
Page 12
Modbus Communication Modules
2.1.5.2 Three Connected Units
This example illustrates connection, termination and ID configuration of three units each with a communication module and a PLC.
Unit #1
Unit #2
Unit #3
PCB no.: 510327-xxx Communication RS485
PCB no.: 510327-xxx Communication RS485
Termination
Termination
ON
OFF
GND
GNDB
GND
GND
RS485
B
RS485
A
B
GND
5V
RTS
GND
Rx Tx 3V3
A
3V3
5V5
GND
GND
Termination
Termination
ON
OFF
GND
GNDB
GND
GND
RS485
B
RS485
A
B
GND
5V
RTS
GND
Rx Tx 3V3
A
3V3
5V5
OFF
OFF
ON
ON
PLC
B
A
GND
PE
GND
GND
Termination
OFF
ON
PCB no.: 510327-xxx Communication RS485
Termination
ON
OFF
GND
GNDB
GND
GND
RS485
B
RS485
A
B
GND
5V
RTS
GND
Rx Tx 3V3
A
3V3
5V5
GND
GND
Figure 4. Three Connected Units
EN 6.81 Modbus Communication Module 205546 Manual 1212
12
Page 13
Modbus Communication Modules
Exampe ID settings
Unit #1 ID=1 and COM module offset ID=1 -> SRO ID=2 (1 + 1)
Unit #2 ID=1 and COM module offset ID=2 -> SRO ID=3 (1 + 2)
Unit #3 ID=4 and COM module offset ID=3 -> SRO ID=7 (4 + 3)
Termination
Modbus RS 485 communication requires bus termination. If the PLC is termi­nated, unit #1 must be set in “OFF” position, unit #2 in “OFF” position and unit #3 in “ON” position.
If, on the other hand, the PLC is NOT terminated, unit #1 must be set in “ON” position.
2. Communication Modules
13
Page 14
Modbus Communication Modules
2.1.5.3 Three Connected Units and One Common Display
This example illustrates connection and ID configuration of for example three MagFlux units without display, one common, remote display unit with a com­munication module and a PLC unit.
MagFlux #1
MagFlux #2
MagFlux #3
Display unit with COM module
PCB no.: 510327-xxx Communication RS485
Termination
ON
OFF
Termination
ON
OFF
GND
GNDB
GND
GND
RS485
B
RS485
A
B
GND
5V
RTS
GND
Rx Tx 3V3
A
3V3
5V5
GND
GND
PLC
B
A
GND
PE
Figure 5. Three Connected Units and One Common Display Unit
Exampe ID settings
If Magflux #1 has ID=1 (seen from the com module), and the com module has ID offset=100, the SRO Modbus ID is 101 (100 + 1) seen from the PLC.
Likewise the other MagFlux units with ID=2 and ID=3 would have the SRO Modbus IDs 102 and 103.
EN 6.81 Modbus Communication Module 205546 Manual 1212
14
Page 15
Modbus Communication Modules
3. Order Numbers
Order number Communication Module
205546 MODBUS and RS 485 communications module
3. Order Numbers
15
Page 16
Modbus Communication Modules
4. Register Lists
4.1 MagFlux Register List
• Date: 2009-03-10
• Firmware: 842009-001
• Protocol: Modbus RTU
• Transfer rate: 9600 baud
• Format for serial com: 1-Startbit, 8-Databits, 1-Parity (Even), 1-Stopbit
• Password: OFF (default)
• To set up the converter, use the MagFlux Display Unit
When a MagFlux Converter is connected to an external master, for example a PLC or an HMI interface, the MagFlux Display Unit can not be used simulta­neous on the RS 485 communication port.
Support only Read is ”func. 03 (0x03) Read Holding Registers” or ”func. 04 (0x04) Read Input Registers” and write ”func. 16 (0x10) Write Multiple regis­ters”
Register address
Flow now
600 Flow now F32 {low} None Read-only Flow now [m3/sec]
601
Totalizer Forward
604
605 Total forward flow 1 - 2 U64{2} - Read-only Forward total [mm3]
606 Total forward flow 1 - 3 U64{3} - Read-only Forward total [mm3]
607
608
609
Totalizer Reverse
610
611 Total reverse flow 1 - 2 U64{2} - Read-only Reverse total [mm3]
EN 6.81 Modbus Communication Module 205546 Manual 1212
Register name
Flow now F32
Total forward flow 1 - LS word
Total forward flow 1 - MS word
Resetable total forward flow 2 - value
Resetable total forward flow 2 - value
Total reverse flow 1 - LS word
Type Security
{high}
U64{1} None Read-only
U64{4} - Read-only
U32 {low} Password Read/
U32 {high}
U64{1} None Read-only
- -
- Read/
16
Read/ Write
Reset
Reset
Comments
Flow now [m3/sec]
Forward total [mm3]
Forward total [mm3]
Forward total [liter]
Forward total [liter]
Reverse total [mm3]
Page 17
Modbus Communication Modules
Register address
612
613
614
615
Totalizer Sum
616
617 Total sum flow 1 - 2 S64{2} - Read-only See above
618 Total sum flow 1 - 3 S64{3} - Read-only See above
619
620
621
Batch Counter 1
627
628
629
630
631
632
Batch Counter 2
633
634
635
636
Register name
Total reverse flow 1 - 3 U64{3} - Read-only
Total reverse flow1 - MS word
Resetable total reverse flow 2 - value
Resetable total reverse flow 2 - value
Total sum flow 1 - LS word
Total sum flow 1 - MS word
Resetable total sum flow 2
- value
Resetable total sum flow 2
- value
Batch counter 1 - Batch count
See above U32
Batch counter 1 - value batch now
See above F32
Batch counter 1 - value batch missing
See above F32
Batch counter 2 - batch count
See above U32
Batch counter 2 - value batch now
See above F32
Type Security
U64{4} - Read-only
U32 {low} Password Read/
U32 {high}
S64{1} None Read-only
S64{4} - Read-only
S32 {low} Password Read/
S32 {high}
U32 {low} Pass-
{high}
F32 {low} None Read-only
{high}
F32 {low} None Read-only
{high}
U32 {low} Pass-
{high}
F32 {low} None Read-only
{high}
- Read/
- Read/
word*
- -
- -
- -
word*
- -
- -
Read/ Write
Reset
Reset
Reset
Reset
R/Reset
R/Reset
Comments
Reverse total [mm3]
Reverse total [mm3]
Reverse total [liter]
Reverse total [liter]
Sum total [mm3] Sum total= (Forward + Reverse) {exsample. 12 + (-2) =10 mm3}
See above
Sum total [liter]
Sum total [liter]
(* = password can be disabled for this setting )
(* = password can be disabled for this setting )
4. Register Lists
17
Page 18
Modbus Communication Modules
Register address
637
638
Status I/O Bits
Register address
1001
Register address
1002
Register name
Batch counter 2 - value batch missing
See above F32
Register name Type Security Read/Write
System error bit 1-16 B16 None Read-only
Bits
System error bit { on = 1 & off = 0 } (to force zero write 12(0x0C) in address 5120 )
Bit 1 = Factory reset has occurred (some settings have changed) Bit 2 = Eeprom write error (see log for details) Bit 3 = Flow totalizer eeprom error (None-resetable counter may be invalid in Eprom) Bit 4 = Sensor setting error (some settings are invalid or changed) Bit 5 = Counter output Forward Pulsoverflow (too low puls volume) Bit 6 = Counter output Reverse Pulsoverflow (too low puls volume) Bit 7 = Batch1 counter overflow Bit 8 = Batch2 counter overflow Bit 9 = Flow totalizer overflow (none-resetable counter may be invalid in Eprom) Bit 10-16 = Reserved and read-value is 0 (zero)
Register name Type Security
Alarm / sensor error B16 None Read-only
Bits
Status bit resetable { On = 1 & Off = 0 }
Bit 1 = empty pipe (see settings for possible enable / disable and on delay) Bit 2 = low flow (see settings for possible enable / disable and on delay) Bit 3 = high flow (see settings for possible enable / disable and on delay) Bit 4 = mA flow error (flow is over or under possibel output) Bit 5 = output coil error (see settings for possible enable / disable and on delay) Bit 6 = sensor error (see settings for possible enable / disable and on delay) Bit 7 = mA out not connected (see settings for possible enable / disable and on delay) Bit 8 = Input over range error (see settings for possible enable / disable and on delay) Bits 9-16 = Reserved and read-value is 0 (zero)
Type Security
F32 {low} None Read-only
- -
{high}
Read/ Write
Comments
Read/Write
Register address
1003
EN 6.81 Modbus Communication Module 205546 Manual 1212
Register name Type Security
Status bits (Part 1) B16 None Read-only
Bits
Bit 1 = batch counter 1 - batch is ended = 1 / running = 0 Bit 2 = batch counter 2 - batch is ended = 1 / running = 0 Bit 3 = batch counter 1 - too big adaptive batch error = 1 / no error = 0 Bit 4 = batch counter 2 - too big adaptive batch error = 1 / no error = 0 Bits 5-16 = reserved
Read/Write
18
Page 19
Modbus Communication Modules
Register address
1004
Login
5000
5001
5002
5003
5004 Not in use U16 None None
5005 Not in use U16 None None
Batch Counter 1
6703
6704
6705
6706
6707
6708
6709
6710
6711
Batch Counter 2
6753
6754
Register name Type Security
Status bits (Part 2) B16 None Read-only
Bits
Bit 1 = flow direction bit - forward flow = 0 / reverse flow = 1 (see settings for possible delay) Bit 2 = flow direction bit - A = 0 / B = 1 (see settings for possible delay) Bits 3-16 = reserved and read-value is 0 (zero)
Login - value U16 None Read/
Min. U16 None Read-
Max. U16 None Read-
Login status ­value
Stop / Start / Pause Manual Batch - value
Min. U16 None Read-
Max. U16 None Read-
Batch stop volume - value
See above F32
Min. F32
See above F32
Max. F32
See above F32
Stop / Start / Pause Manual Batch - value
Min. U16 None Read-
U16 None Read/
U16 None R/W
F32 {low}
{high}
{low}
{high}
{low}
{high}
U16 None Read/
Pass­word*
- -
None Read-
- -
None Read-
- -
Write
only
only
Write
only
only
Read/ Write
only
only
Write
only
Read/Write
Write = 0 or 65535 to logout
0
65.535
Login status read = { 65535 = lockout mode - 0 = no code - 1 = code accepted }
Stop / start / pause start manual batch 0 = stop 1 = start 2 = pause
0
2
[m3] (* = password can be disabled for this setting )
Stop / start / pause start manual batch 0 = stop 1 = start 2 = pause “
0
4. Register Lists
19
Page 20
Modbus Communication Modules
6755
6756
6757
6758
6759
6760
6761
Max. U16 None Read-
Batch stop volume - value
See above F32
Min. F32
See above F32
Max. F32
See above F32
F32 {low}
{high}
{low}
{high}
{low}
{high}
Pass­word*
- -
None Read-
- -
None Read-
- -
Table 2. MagFlux Register List
only
Read/ Write
only
only
2
[m3] (* = password can be disabled for this setting )
EN 6.81 Modbus Communication Module 205546 Manual 1212
20
Page 21
Modbus Communication Modules
4.2 Oxix / SuSix Register List
• Date: 2009-03-10
• Firmware: 846001
• Protocol: Modbus RTU
• Transfer rate: 9600 baud
• Format for serial com: 1-Startbit, 8-Databits, 1-Parity (Even), 1-Stopbit
• Password: OFF (default)
• To set up the converter, use the SuSix/Oxix Display Unit
When a SuSix/Oxix Converter is connected to an external master, for example a PLC or an HMI interface, the SuSix/Oxix Display Unit can not be used simultaneous on the RS 485 communication port.
Support only Read is ”func. 03 (0x03) Read Holding Registers” or ”func. 04 (0x04) Read Input Registers” and write ”func. 16 (0x10) Write Multiple regis­ters”
Reg. addr.
606
607
608
609
4. Register Lists
Reg. name
Read­ing
- prim
- xtra
See above
Read­ing
- sec
- xtra
See above
Type
F32 {LW}
F32 {HW}
F32 {LW}
F32 {HW}
Se-
Read/
curity
Write
None Read-
only
None Read-
only
Oxix SuSix
Primary value (dissolved oxygen) [unit is setting dependent]
See above
Secondary value [de­grees C]
See above
21
Primary value (turbidity / solid) [unit is setting-de­pendent]
See above
Secondary value standard deviation turbidity / solid [%]
See above
Page 22
Modbus Communication Modules
Status I/O Bits
Register address
1001
Register name Type Security Read/Write
System error bit (alarm) B16 Password Read/Reset
Bits
Oxix
System error bit { on = 1 & off = 0 }
Bit 1 = Factory reset has occurred (some settings have changed - check all used settings) Bit 2 = Eeprom write error (see log for details) Bit 3 = Sensor setting error (some settings are invalid or changed) Bit 4 = System error in eventlog (log in eventlog for details) Bit 5 = Current out not connected (If current out is not used, deactivate to stop pop-up) Bit 6 = Primary measurement is over or under settings for current Bits 7-16 = Reseved and read-value is 0 (zero)
SuSix
System error bit { on = 1 & off = 0 }
Bit 1 = Factory reset has occurred (some settings have changed - check all used settings) Bit 2 = Eeprom write error (See log for details) Bit 3 = Sensor setting error (some settings are invalid or changed) Bit 4 = System error in eventlog (log in eventlog for details) Bit 5 = Current out not connected (if current out is not used, deactivate to stop pop-up) Bit 6 = Primary measurement is over or under settings for current Bits 7-16 = Reseved and read-value is 0 (zero)
Register address
1002
EN 6.81 Modbus Communication Module 205546 Manual 1212
Register name Type Security Read/Write
System alarm 1 B16 None Read-only
Bits
Oxix
Status bit { on = 1 & off = 0 }
Bit 1 = reseved Bit 2 = reseved Bit 3 = reseved Bit 4 = primary value - low alarm active Bit 5 = primary value - high alarm active Bits 6-16 = reseved and read-value is 0 (zero)
SuSix
Status bit { on = 1 & off = 0 }
Bit 1 = reseved Bit 2 = reseved Bit 3 = reseved Bit 4 = primary value low - alarm active Bit 5 = primary value high - alarm active Bits 6-16 = reseved and read-value is 0 (zero)
22
Page 23
Modbus Communication Modules
Status I/O Bits
Register address
1003
Register name Type Security Read/Write
Sensor error (Alarm) B16 None Read-only
Bits
Oxix
Status bit { on = 1 & off = 0 }
Bit 1 = sensor - replace sensor Bit 2 = sensor - fix error / redo calibration point or clear all points and redo calibration Bit 3 = sensor - temperature error (thermistor is damaged) Bit 4 = sensor - check sensor cable Bit 5 = sensor - check sensor wiper Bit 6 = sensor - probe polluted => clean - if message is repeated, return probe Bit 7 = sensor - main photo diode saturated (circuit or sensor coating damaged) Bit 8 = sensor - main photo diode negative (excessive electrical noise or damage) Bit 9 = sensor - reference photo diode saturated (same causes as bit 7) Bit 10 = sensor - reference photo diode negative (same causes as bit 8) Bit 11 = reseved - read-value is 0 (zero) Bit 12 = reseved - read-value is 0 (zero) Bit 13 = reseved - read-value is 0 (zero) Bit 14 = reseved - read-value is 0 (zero) Bit 15 = sensor - supply is to high / low. Check sensor connection Bit 16 = sensor - temperature error (temperature is out of range)
SuSix
Status bit { on = 1 & off = 0 }
Bit 1 = sensor - replace sensor Bit 2 = sensor - fix error / redo calibration point or clear all points and redo calibration Bit 3 = sensor - is not in solid mode - choose a unit of solid type Bit 4 = sensor - check sensor cable Bit 5 = sensor - check sensor wiper Bit 6 = sensor - probe polluted => clean - if message is repeated, return probe Bit 7 = sensor - turbidity value out of range (higher then 4000 NTU) - only implemented to display unexpected error Bit 8 = sensor - calibration insufficient - make another calibration on lower solid test sample Bit 9 = sensor - calibration insufficient - make another calibration on higher solid test sample Bit 10 = sensor - overflow - clean sensor / or check range and ensure that probe is used to measure Bit 11 = sensor - offset error (only implemented to display unexpected error Bit 12 = sensor - measuring start failed - please try again Bit 13 = sensor - measuring timeout - try again Bit 14 = sensor - measuring adjustment missing Bit 15 = sensor - supply is to high / low. Check sensor connection Bit 16 = reseved and read-value is 0 (zero)
4. Register Lists
23
Page 24
Modbus Communication Modules
Status I/O Bits
Register address
1004
Login
Reg. addr.
5000
5001
5002
5003
5004
5005
Register name Type Security Read/Write
Status no. 1 B16 None Read-only
Bits
Oxix
Bit 1 = converter has experienced a software or hardware reset (expected if sensor number has been changed or factory setting is reloaded) Bit 2 = system error alarm (see settings for possible enable / disable and on delay) Bit 3 = sensor error alarm (see settings for possible enable / disable and on delay) Bit 4 = sensor autodetect type is running - normal if sensor com error is detected x times Bit 5 = hold of measurment value (normal for a short time) Bit 6 = sensor cleaning in progress Bit 7 = limit control
SuSix
Status bit { on = 1 & off = 0 } Bit 1 = converter has experience a software or hardware reset (expected if sensor number has been changed or factory setting is reloaded) Bit 2 = system error alarm (see settings for possible enable / disable and on delay) Bit 3 = sensor error alarm (see settings for possible enable / disable and on delay) Bit 4 = sensor autodetect type is running - normal if sensor com error is detected x times Bit 5 = hold of measurment value (normal for a short time) Bit 6 = sensor cleaning in progress Bit 7 = limit control
Reg. name
Login ­Value
Min. U16 None Read-
Max. U16 None Read-
Login status
- value
Not in use
Not in use
Se­cu­rity
Read/ Write
Write
only
only
Write
Type
U16 None Read/
U16 None Read/
U16 None None
U16 None None
Oxix SuSix
Write = 0 or 65535 to logout
0
65.535
Login status Read = { 65535 = lockout mode - 0 = no code - 1 = code accepted }
Write = 0 or 65535 to logout
0
65.535
Login status Read = { 65535 = lockout mode - 0 = no code - 1 = code accepted }
Table 3. Oxix and SuSix Register List
EN 6.81 Modbus Communication Module 205546 Manual 1212
24
Page 25
Modbus Communication Modules
4.3 mA-Bus Converter List
• Date: 2008-06-11
• Firmware: 845001-003
• Protocol: Modbus RTU
• Transfer rate: 9600 baud
• Format for serial com: 1-Startbit, 8-Databits, 1-Parity (Even), 1-Stopbit
• Password: OFF (default)
• To set up the converter, use the Display Unit
When a mA-Bus Converter is connected to an external master, for example a PLC or an HMI interface, the Display Unit can not be used simultaneous on the RS 485 communication port. Support only Read is ”func. 03 (0x03) Read Holding Registers” or ”func. 04 (0x04) Read Input Registers” and write ”func. 16 (0x10) Write Multiple registers”
Reg.
Reg.
addr.
name
100 DI 3-1 status U16 None
200 Digital input Bit 1-16 U16
AI 1 Scaled value F32 {Low} None
300
301 - F32 {High}
302 AI 1 Unit U16
303 AI 1 Precision S16
304 AI 2 Scaled value F32 {Low} None
305 - F32 {High}
306 AI 2 Unit U16
307 AI 2 Precision S16
1001 System Error bit 1-16 U16
1002 Alarm Error 1 U16
1003 Alarm Error 2 U16
Type
Se­cu­rity
Read/ Write
4. Register Lists
25
Page 26
Byageren 7 DK 2850 Nærum Denmark
Tlf: +45 45 56 06 56 Fax: +45 45 56 06 46
mjk@mjk.com www.mjk.com
MJK Automation A/S
Modbus Communication Modules
Liability
MJK Automation A/S is liable to the common rules of Danish law on product liability. However, the liability is reduced to coverage of our public liability insurance of products. To the extent where nothing else follows in lines of invariable rules of law, we are not liable for loss of profits and working deficits or other indirect losses.
Changes
As our products are developed continuously, we reserve the right to make any alterations without prior notice..
EN 6.81 Modbus Communication Module 205546 Manual 1212
Loading...