Since the use of this manual and the conditions or methods of installation, operation, use and
maintenance of the unit are beyond the control of Xantrex Technology Inc., the company does not
assume responsibility and expressly disclaims liability for loss, damage, or expense arising out of or
any way connected with such installation, operation, use or maintenance.
This manual contains important safety instructions that should be followed during the installation
and maintenance of this product.
To reduce the risk of electrical shock, and to ensure the safe installation and operation of this
product, the following safety symbols have been placed throughout this manual to indicate dangerous conditions and important safety instructions.
WARNING - A dangerous voltage or condition exists in this area.
Use extreme caution when performing these tasks.
AVERTISSEMENT - Une tension ou condition dangereuse existe dans cette zone.
Faire preuve dextrême prudence lors de la réalisation de ces tâches.
CAUTION - This procedure is critical to the safe installation or operation of the unit. Follow these
instructions closely.
ATTENTION - Cette procédure est essentielle à linstallation ou lutilisation
de lunité en toute sécurité. Suivre ces instructions de près.
NOTE - This statement is important. Follow instructions closely.
NOTE - Cette déclaration est importante. Suivre les instructions de près.
·
All electrical work must be done in accordance with local, national and/or international electrical
codes.
·
Before installing or using this device, read all instructions and cautionary markings located in (or
on) the manual, the inverter, the controller, the batteries and the PV array.
·
Do not expose this unit to rain, snow or liquids of any type. This product is designed only for
indoor installation.
·
To reduce the chance of short-circuits when installing or working with the inverter, the batteries
or the PV array, use insulated tools.
·
Remove all jewelry such as rings, bracelets, necklaces, etc., prior to installing this system. This
will greatly reduce the chance of accidental exposure to live circuits.
·
The inverter contains more than one live circuit (batteries and AC line). Power may be present
at more than one source.
·
This product contains no user serviceable parts. Do not attempt to repair this unit.
·
Do not install 120 volt AC stand-alone inverters onto 120/240 volt AC multi-branch circuit wiring.
This could pose a fire hazard due to an overloaded neutral return wire in this configuration.
Always wear eye protection, such as safety glasses, when working with batteries.
·
Remove all loose jewelry before working with batteries.
·
Never work alone. Have someone assist you with the installation or be close enough to come to
your aid when working with batteries.
·
Always use proper lifting techniques when handling batteries.
·
Always use identical types of batteries.
·
Never install old or untested batteries. Check each batterys date code or label to ensure age
and type.
·
Batteries are temperature sensitive. For optimum performance, they should be installed in a
stable temperature environment.
·
Batteries should be installed in a well vented area to prevent the possible buildup of explosive
gasses. If the batteries are installed inside an enclosure, vent its highest point to the outdoors.
·
When installing batteries, allow at least 1 inch of air space between batteries to promote cooling
and ventilation.
·
NEVER smoke in the vicinity of a battery or generator.
·
Always connect the batteries first, then connect the cables to the inverter or controller. This will
greatly reduce the chance of spark in the vicinity of the batteries.
·
Use insulated tools when working with batteries.
·
When connecting batteries, always verify proper voltage and polarity.
·
Do not short-circuit battery cables. Fire or explosion can occur.
·
In the event of exposure to battery electrolyte, wash the area with soap and water. If acid enters
the eyes, flood them with running cold water for at least 15 minutes and get immediate medical
attention.
·
Always recycle old batteries. Contact your local recycling center for proper disposal information.
Thank you for purchasing the DR Series inverter/charger from Xantrex Technology Inc. The
DR Series is one of the finest inverter/chargers on the market today, incorporating state-of-the-art
technology and high reliability. The inverter features an AC pass-through circuit, powering your
home appliances from utility or generator power while charging the batteries. When utility power
fails, the battery backup system keeps your appliances powered until utility power is restored.
Internal protection circuits prevent over-discharge of the batteries by shutting down the inverter
when a low battery condition occurs. When utility or generator power is restored, the inverter
transfers to the AC source and recharges the batteries.
The front panel features LEDs for reading system status, and controls to customize the inverter
Carefully unpack the inverter/charger from its shipping carton.
NOTE: The unit weighs 3545 lb/15.920.4 kg (depending on model). Have additional help available
if necessary, to assist in lifting the unit during installation.
Verify all of the items listed on the packing material sheet are present. Please call Xantrex
Customer Service at (360) 435-8826 if any items are missing.
Save your proof-of-purchase. This is required if the unit should require warranty service.
Save the original shipping carton and packing materials! If the inverter ever needs to be returned
for service, it should be shipped in the original carton. This is also a good way to protect the
inverter if it ever needs to be moved.
Record the units model, serial number and date of purchase in the appropriate fields in section
10.0 SERVICE INFORMATION.
NOTE: Due to continual improvement through product updates, photographs and/or illustrations
used in this manual may not exactly match your unit. Xantrex Technology Inc. reserves the right to
update this product without notice or releasing an updated manual when fit, form or function are not
affected.
The DR Series inverter/charger is identified by the model/serial number label located next to the
AC access cover. All the necessary information is provided on the label such as AC output voltage,
power and frequency (punch holes).
The inverter also has a letter designator followed by 4 or 5 digits (depending on revision). The
model number describes the type of inverter, the output specifications, the required battery voltage
and the output voltage and frequency.
DRindicates the type of inverter/charger - DR Series.
15the first two digits of the numerical designator indicate the inverters output power - 1500
Watts.
12the second two digits indicate the required nominal battery bank voltage - 12 VDC.
Ethe letter suffix code indicates the output voltage and frequency of the inverter - 230
120 VAC/60 Hz models of the DR Series inverter/charger models are listed to UL Standard 1741,
Power Conditioning Units for use in Residential and Commercial Photovoltaic Power Systems. These
units are also ETL listed to CAN/CSA-22.2, No. 107.1-M91, the Canadian safety standard. These
standards guarantee that the inverter/charger has been tested to nationally recognized safety
standards (UL for the US and CSA for Canada) and have been found to be free from reasonably
foreseeable risk of fire, electric shock and related hazards.
The inverter/charger is intended to be used for residential or commercial applications. Do NOT
use this unit for applications for which it is not listed (i.e., land vehicles or marine craft). It may not
comply with the safety code requirements, or could possibly present other operational or safety
hazards.
The DR Series inverter/charger is an economical product designed to provide a reliable supply of
electricity to all the essential circuits in the home or business during a power outage. The critical
loads can be powered for hours or days, depending on the size of the system battery bank. When
utility grid power returns, the batteries are quickly recharged to ensure they will be ready to supply
backup power during the next outage.
Accessories allow the DR Series to also serve as a central hub of a renewable energy system.
Features
Modified Sine Wave Power
The DR Series inverters provide a modified sine wave output which operates most AC appliances
and equipment.
Battery Charger/AC Transfer Relay
The inverter/charger includes a 3-stage battery charger designed to recharge any type of battery
in the shortest possible time. The built-in, fully automatic AC transfer relay automatically transfers
power from the utility to the inverter and handles a full 60 amps of current at 120 VAC (30 amps
for pass-through plus 30 amps for charging).
Simplicity
The DR Series is simple to operate. All inverter and battery charger controls are located on the
front panel.
High Efficiency
The inverter/charger operates at over 90% efficiency through most of its power range.
Low Power Consumption
DR Series inverters use extremely low current while in the search mode, consuming little more
than one watt of power. In the ON mode, the inverter/charger uses less than 20 watts of power.
Options
The following options are available for the DR Series inverter/chargers:
RC4/RC8
The RC4/RC8 allows the inverter to be switched ON or OFF remotely and includes an LED status
indicator.
DRI
The DRI stacking interface provides 3-wire 120/240 VAC at twice the power using dual DR Series
inverters (120 VAC/60 Hz units only).
DRCB
The DRCB conduit box connects to the DC side of the inverter and accepts a DC conduit run.
NOTE: Before installing the inverter/charger, read all instructions and cautionary markings located in
this manual.
NOTE: The inverter/charger can weigh up to 45 lb. (20.4 kg) depending upon configuration. Always
use proper lifting techniques during installation to prevent personal injury.
Location
Inverters contain sophisticated electronic components and should be located in a well
protected, dry environment away from sources of fluctuating or extreme temperatures and
moisture. Exposure to saltwater is particularly destructive and potentially hazardous.
NOTE: If the inverter is installed in a location where it is exposed to a corrosive or condensing
environment, and fails due to corrosion, it will not be covered under warranty.
Locate the inverter as close to the batteries as possible in order to keep the battery cable
length short. However, do not locate the inverter above the batteries or in the same
compartment as vented batteries. Batteries generate hydrogen sulfide gas which is corrosive
to electronic equipment. They also generate hydrogen and oxygen. If accumulated, an arc
caused by connecting the battery cables or switching a relay could ignite this mixture.
Mounting the inverter in a ventilated enclosure with sealed batteries is acceptable.
NOTE: Inverters can generate RFI (Radio Frequency Interference). Locate any sensitive electronic
equipment susceptible to RFI as far away from the inverter as possible. This includes radios and
TVs.
Mounting
UL Standard 1741 requires the inverter be mounted on a vertical surface (or wall). The
keyhole slots must not be used as the only method of mounting. The purpose of the wall
mounting requirement is to orient the inverter so that its bottom cover, which has no holes,
will not allow burning material to be ejected in the event of an internal fire. Use 0.25 inch
diameter bolts for mounting. The mounting surface must be capable of supporting twice the
weight of the inverter to comply with UL 1741.
Ventilation
Install the inverter in a well ventilated area/enclosure for proper operation. The inverters
thermal shutdown point will be reached sooner than normal in a poorly ventilated
environment, resulting in reduced peak power output and surge capability, as well as shorter
inverter life.
The inverter contains an internal fan. Ensure the air vents and intakes are not obstructed in
any way. Provide a minimum clearance of 1-1/2 inches around the top and sides of the
inverter for ventilation.
4 ft. x 4 ft. sheet of 3/4" plywood or 2 x 4s studding material
#12 wood screws (or 1/2" x 1-1/4" lag bolts)
Conduit and appropriate fittings
Wire nuts
Wiring:
All wiring and installation methods should conform to applicable electrical and building codes.
Pre-plan the wire and conduit runs. The AC circuits accept cable sizes up to #6 AWG. The DC
circuits accept cable sizes up to #4/0 AWG.
For maximum safety, run both AC and DC cables in conduit.
Refer to the Figure 25 (page 29) for an example of AC wiring to the sub-panel for 120 VAC
circuits.
AC Connections:
Use #6 AWG THHN wire for all AC wiring.
DC Connections:
Battery to inverter cabling should be only as long as required. If #4/0 AWG cables are used
for example, do not exceed 5 feet (one way) in 12 VDC systems; do not exceed 10 feet (one
way) in 24 VDC systems. For optimum performance, use pre-assembled battery cables
designed specifically for this application (available from Xantrex).
Grounding:
AC Grounding
The inverter/charger should be connected to a grounded, permanent wiring system. Neutral
and ground conductors should only be bonded at the main utility service panel.
DC Grounding
The negative battery conductor should be bonded to the grounding system at only one point
in the system. The size for the conductor is usually based on the size of the largest conductor
in the DC system.
The battery voltage MUST match the voltage requirements of the inverter. To determine the
correct voltage for the system, check the last two digits on the inverters model number. For
example, the DR1512 is a 12 volt inverter and requires a 12 VDC battery system. The
DR2424 is a 24 volt inverter and requires a 24 VDC battery system.
Battery Location:
Locate the batteries in an accessible location. Two feet clearance above the batteries is
recommended for access to the battery caps. They should be located as close to the inverter
as possible without limiting access to the inverters disconnects. Install the batteries to the left
of a wall mounted inverter for easy access to the DC side of the inverter and shorter cable
runs.
For safety and to limit access to the batteries, a lockable, ventilated, battery enclosure or
dedicated room should be used. If an enclosure is used, it should be vented to the outside
via a one inch vent pipe located at the top of the enclosure. Install an intake vent at the
bottom of the enclosure to promote air circulation. These vents exhaust explosive hydrogen
gases and must not be overlooked when designing an enclosure.
The enclosure should be made of an acid resistant material or have a finish that resists acid
to prevent corrosion. It should be capable of holding the electrolyte from at least one battery
should a leak occur.
Place a layer of baking soda on the shelves to neutralize any acid that may be spilled in the
future (lead-acid batteries only).
Enclosures located outside must be rainproof and screened to prevent access by rodents or
insects.
Battery Temperature
The battery enclosure should provide a fairly stable temperature for the batteries. If it is installed
in a cold environment, insulation should be used to protect the batteries from the cold. The insulation
also provides a more consistent temperature and better system performance.
The battery enclosure should not be installed in direct sunlight where the summer sun can
overheat the batteries. Locate the enclosure where it will be protected from the afternoon sun and
provide vents in the top and bottom of the enclosure to provide air flow. High battery
temperatures greatly shortens the life of the batteries.
The input to the inverter requires a minimum 60 amp breaker (for each inverter if stacked). This
circuit breaker must be located in the utility service panel.
Sub-Panel:
Loads backed up by the inverter will need to be rerouted from the main service panel to a sub-
panel. This can be done several different ways, depending upon the installation. Always refer to
electrical codes for safe wiring practices.
AC Circuit Breakers:
Always use a properly rated circuit breaker. Depending upon the application, circuit breakers
used to protect the load can be removed from the main service panel and put into the sub-panel
ONLY if the two panels are from the same manufacturer.
DC Disconnect:
Install a DC disconnect breaker or fuse in the positive battery line. This breaker protects the DC
wiring in the event of an accidental short. Size the breaker in accordance with the battery cables.
Switch this breaker OFF whenever servicing the batteries.
Wire Routing:
Determine all wire routes both to and from the inverter and which knockouts are best suited for
connecting the AC conduits. Possible routing scenarios include:
AC Input wiring from the main utility service panel to the inverter/charger
AC Input wiring from the generator to the inverter/charger (if used)
DC Input wiring from the PV array (wind, hydro, etc.) to the inverter/charger (if used)
DC Input wiring from the batteries to the inverter/charger
AC Output wiring from the inverter/charger to the sub-panel
Battery Temperature Sensor cable from the batteries to the inverter/charger (if used)
Remote Control cable to the inverter/charger (if used)
DC Ground from the batteries to an external ground rod
Load circuit wiring rerouted from the main service panel to the sub-panel
Check for existing electrical or plumbing prior to making cuts in the walls. Cut holes in the walls
at appropriate locations for routing wiring/cables.
The DR Series inverter can weigh as much as 45 lb. (20.4 kg). Wallboard is not strong enough
to support its weight so additional support must be added. The easiest method for securing it to an
existing wall is to place two 2 x 4s horizontally on the wall (spanning at least three studs) and
securing the inverter to the 2 x 4s.
WARNING: USE APPROPRIATE LIFTING TECHNIQUES. HAVE EXTRA PEOPLE ON HAND TO
ASSIST IN LIFTING THE INVERTER INTO POSITION WHILE IT IS BEING SECURED.
Procedure
Locate the studs and mark their location on the wall.
Measure the desired height from the floor for the inverter to be mounted.
Using a level, run a horizontal line. The length of the line must span at least 3 studs.
Place a pre-cut 2 x 4 on the marked location and drill pilot holes through the 2 x 4s and
studs.
Secure the 2 x 4 with #10 wood screws (length to penetrate 1-1/2 inches into the studs).
Referring to Figure 8, drill out the mounting hole locations for the inverter.
With assistance, lift the inverter into position and install it onto the 2 x 4s using 1/4 x 1-1/2
inch lag bolts and washers.
Alternatively, a half or quarter sheet of 3/4 inch plywood can also be used as a backing, with the
inverter mounted directly to the plywood using 1/4 inch diameter lag bolts and washers. The plywood
must span three studs for adequate support.
Proper cable sizing (diameter and length) is critical to the safe and efficient operation of an
inverter system. Larger diameter cables (smaller AWG number) have less voltage drop and are,
therefore, more efficient when transferring power to and from the batteries. If a cable is undersized
(diameter too small), it could potentially overheat, creating a fire hazard.
Cable length is another important factor. Runs should be kept as short as practical. Longer
cable runs increase resistance, thus lowering the overall efficiency of the system. This is especially
true in lower voltage systems (i.e., 12 VDC) where, depending upon the length of the cable run, it
may be necessary to oversize the diameter of the wire, or parallel (double) the cables.
Always use a properly sized cable and length rated for the amperage of the inverter and
batteries.
WARNING: UNDERSIZED CABLES CAN OVERHEAT AND MELT, CREATING A FIRE HAZARD
WHEN SUBJECTED TO HEAVY (PEAK) LOADS.
NOTE: If the system will be operated at the inverters peak power rating exceeding one hour, larger
cables and disconnects MUST be used (see Tables 1 and 2).
NOTE: If the system includes a large battery bank or large DC source (such as a micro-hydroelectric
plant or wind generator), increasing the size of the cables and disconnects will greatly reduce the
number of nuisance outages associated with breaker tripping and open fuses.
Table 1 provides recommended minimum cable sizes for various cable lengths and inverter
amperages. These recommendations may not meet all local or NEC requirements.
NOTE: Use only copper cables.
NOTE: Run the positive and negative battery cables as close to each other as possible by taping
them together. This reduces the effects of inductance and produces a better waveform thus
increasing efficiency.
Inverter
Model
DR1512
DR2412
DR1524
DR2424
DR3624
Typical
Amperage
150 A#2/0 AWG (67.4 mm
240 A#4/0 AWG (107 mm
75 A#2/0 AWG (67.4 mm
120 A#2/0 AWG (67.4 mm
180 A#4/0 AWG (107 mm
1 to 3 Feet (one-way)3 to 5 Feet (one-way)5 to 10 Feet (one-way)
For safety and to comply with regulations, battery over-current protection is required. Fuses and
disconnects must be sized to protect the wiring in the system and are required to open before the
wire reaches its maximum current carrying capability.
The National Electrical Code (NEC) requires both over-current protection and a disconnect
switch for residential and commercial electrical systems. These items are not supplied as part of the
inverter. However, Xantrex offers a DC rated, DC250/175 ETL listed, circuit breaker disconnect
module specifically designed for use with Trace inverters to meet NEC compliance. Two amperage
ratings are available: a DC250 (250 amps) and a DC175 (175 amps) in either single or dual breaker
configurations for single or dual inverter installations.
NOTE: Trace DC disconnects are not designed to accept doubled (paralleled) cables which may
be required for long cable runs. Also, the plastic red and black covers on the DC inverter inputs are
not designed to accommodate dual cables. If dual cables are used, the optional conduit box (DRCB)
must be used.
Some installations may not require conduit or a disconnect device, although over-current
protection is still required. Xantrex offers a fuse block (TFB) providing the code required inverter
over-current protection for these applications. Refer to the table below for the proper size disconnect
device for specific cable diameters.
Cable Size
Required
#2 AWG115 amps maxN/A170 amps maxTFB200
#2/0 AWG175 amps maxDC175265 amps maxTFB300
#4/0 AWG250 amps maxDC250360 amps maxTFB400
Rating in
Conduit
Maximum
Breaker Size
Rating in "Free
Air"
Maximum Fuse
Size
975-0012-005
Table 2
Battery Cable to Maximum Breaker/Fuse Size
NOTE: The NEC allows rounding to the next standard fuse size from the cable rating (i.e., 150 amp
cable size rounds up to a standard 175 amp size). The term free air is defined by the NEC as
cabling that is not enclosed in a conduit or a raceway. Cables enclosed in conduit or raceways have
substantially lower continuous current carrying ability due to heating factors.
Battery cables must have crimped (or preferably, soldered and crimped) copper compression
lugs unless aluminum mechanical lugs are used. Soldered connections alone are not acceptable.
High quality, UL-listed battery cables are available from Trace Engineering in an assortment of
lengths: 1-1/2 to 10 feet, and in #2/0 AWG or #4/0 AWG sizes. These cables are color-coded with
pressure crimped, sealed ring terminals.
Figure 9 illustrates the proper method to connect the battery cables to the DR Series inverter/
charger terminals.
CAUTION: THE INVERTER IS NOT REVERSE POLARITY PROTECTED. REVERSING THE
BATTERY POLARITY ON THE DC INPUT CONNECTIONS WILL CAUSE PERMANENT DAMAGE
TO THE INVERTER WHICH IS NOT COVERED UNDER WARRANTY. ALWAYS CHECK
POLARITY BEFORE MAKING CONNECTIONS TO THE INVERTER.
WARNING: ENSURE THE INVERTER IS OFF BEFORE CONNECTING OR DISCONNECTING
THE BATTERY CABLES, AND THAT AC POWER IS DISCONNECTED FROM THE INVERTER
INPUT.
The size of the battery bank determines how long the AC loads will operate in a backup mode
without utility power. The larger the battery bank, the longer the run time. Size the battery bank to the
systems AC load requirements and length of time required to run from the batteries. In general, the
battery bank should not be discharged more than 50%. Additional DC charging devices such as
solar, wind, hydro, etc., can provide longer run times by recharging the batteries in the absence of
AC utility or generator power.
Additional details on estimating battery bank size and capacity can be found in the Appendix
section of this manual.
Battery Types
Batteries are available in different sizes, amp-hour ratings, voltage, liquid or gel, vented or nonvented, chemistries, etc. They are also available for starting applications (such as an automobile
starting battery) and deep discharge applications. Only the deep discharge types are recommended
for inverter applications. Choose the batteries best suited for the inverter installation and cost. Use
only the same battery type for all batteries in the bank. For best performance, all batteries should be
from the same lot and date. This information is usually printed on a label located on the battery.
Additional information regarding batteries can be found in the Appendix section of this manual.
Battery Configuration
The battery bank must be wired to match the inverters DC input voltage specifications (12, 24 or
48 VDC). In addition, the batteries can be wired to provide additional run time. The various wiring
configurations are:
SERIES
Wiring batteries in series increases the total bank output voltage (to match the inverters DC
requirements).
PARALLEL
Wiring the batteries in parallel increases the total run time the batteries can operate the AC loads.
SERIES-PARALLEL
Series-parallel configurations increase both the battery voltage (to match the inverters DC
requirements) and run-time for operating the AC loads.
Wiring the batteries in a series configuration increases the voltage of the battery string. 6 volt
batteries can be combined to form 12 V, 24 V, or 48 V battery banks. In the same way, 12 volt
batteries connected in series form 24 V or 48 V battery banks. The total current capacity of the bank
does not increase and it retains the same amp-hour rating as a single battery.
Wiring the batteries in a parallel configuration increases the current of the battery string. This is
commonly used in 12 volt configurations. The voltage of the battery bank remains the same as an
individual battery. Parallel configurations extend the run times of the AC loads by providing
increased current for the inverter to draw from. In a parallel configuration, all of the negative battery
terminals are connected together and all of the positive battery terminals are connected together.
–
+
–
12 V
+
–
12 V
+
–
12 V
12 V
+
Each batterys amp-hour
rating is 50 Ah
+–
12 V INVERTER
(Total battery capacity = 200 Ah)
3597-F00-D26
Figure 13
12 Volt Battery WiringParallel Configuration
Wiring Batteries in Series-Parallel
Wiring the batteries in a series-parallel configuration increases the
current and voltage of the
battery bank. Series-parallel wiring is more complicated and care should be taken when wiring these
banks.
To construct a series-parallel battery bank follow these instructions:
Step 1
First wire the batteries in series (voltage adds) with the positive terminal of one battery
connected to the negative terminal of the next battery to meet the inverters DC input
requirements.
18
Repeat this step for the next battery string.
Two identical strings of batteries are now wired in series.