WOLF ICBCI152TF/S, ICBCI152T-S, ICBCI243CB, ICBCI243TFS, ICBCI304TFS, ICBCI365TFS Installation Guide
INDUCTION AND ELECTRIC COOKTOPS
INSTALLATION GUIDE
GUÍA DE INSTALACIÓN
GUIDE D’INSTALLATION
GUIDA ALL’INSTALLAZIONE
INSTALLATIONSANLEITUNG
INDUCTION AND ELECTRIC COOKTOPS
SPECIFICATIONS
Contents
2 Induction and Electric Cooktops
2 Specications
5 Installation
5 Troubleshooting
Features and specications are subject to change at any
time without notice.
Important Note
To ensure this product is installed and operated as safely
and efciently as possible, take note of the following types
of highlighted information throughout this guide:
IMPORTANT NOTE highlights information that is especially
important.
CAUTION indicates a situation where minor injury or product
damage may occur if instructions are not followed.
WARNING states a hazard that may cause serious injury or
death if precautions are not followed.
IMPORTANT NOTE: Save these instructions for the local
electrical inspector.
Product Information
Important product information including the model and
serial number are listed on the product rating plate. The
rating plate is located on the bottom of the cooktop. Refer
to the illustration below.
If service is necessary, contact Wolf factory certied service
with the model and serial number.
RATING PLATERATING PLATE
Induction cooktop.
Electric cooktop.
Installation Requirements
A minimum height clearance of 159 mm is required from the
top of the countertop to any combustible surface directly
below the cooktop.
Clearance is required for the power inlet box located at the
right rear of induction and electric cooktops. Refer to the
illustration below for dimensions.
Refer to the illustrations on pages 3–4 for additional
minimum clearances. Installation dimensions are the same
for induction and electric cooktops of the same width.
WARNING
Failure to locate the cooktop without proper clearances
will result in a fire hazard.
32 mm
56
mm
38 mm
84
mm
40
mm
Power inlet box clearance.
FLUSH INSTALLATION
Contemporary induction and electric cooktops can be
mounted ush with the top of the countertop, or as a frameless installation sitting on top of the countertop surface. If
the cooktop is to be mounted ush with the countertop, a
recessed area surrounding the cooktop cut-out must be
provided. Wolf downdraft systems cannot be used with
contemporary induction and electric cooktops.
An installation kit and instructions required for a ush
installation are provided with the contemporary cooktop.
CAUTION
Flush installation is intended for granite, solid surface
or stone countertop surfaces only.
MULTIPLE COOKTOPS
When multiple cooktops or modules are installed side by
side, the countertop cut-out width is determined by adding
the width of each unit, then subtracting 25 mm. Refer to the
illustration below.
IMPORTANT NOTE: Contemporary induction and electric
cooktops are not designed to be installed in combination
with other cooktops.
64 mm
495 mm
CUT-OUT
DEPTH
2 | English
Countertop cut-out.
CUT-OUT WIDTH
(COMBINED WIDTH OF COOKTOPS
MINUS 25 mm)
64 mm
SPECIFICATIONS
Electrical
Installation must comply with all applicable electrical codes
and be properly grounded (earthed).
Locate the electrical supply as shown in the illustrations on
pages 3–4. A separate circuit, servicing only this appliance
is required. A ground fault circuit interrupter (GFCI) is not
recommended and may cause interruption of operation.
Performance may be compromised if the electrical supply is
less than 220 volts.
When multiple cooktops are installed side by side, each unit
must have its own separate recommended electrical circuit.
REQUIRED POWER SUPPLY
INDUCTION / ELECTRIC
Single phase220-240V AC, 50/60 Hz
3phase380-415V AC, 50 Hz
Refer to the wiring diagram showing the connections for
each lead to the terminal box on the unit.
WARNING
The complete appliance must be properly grounded at
all times when electrical power is applied.
Do not ground appliance with the neutral (white) house
supply wire. A separate ground wire must be utilized.
If aluminum house supply wiring is utilized, splice the
appliance copper wire to the aluminum house wiring
using special connectors design and agency certified
for joining copper and aluminum. Follow the connector
manufacturer’s recommended procedure carefully.
Improper connection can result in a fire hazard.
IMPORTANT NOTE: Connection of this appliance should be
through a fused connection unit or a suitable isolator, which
complies with national and local safety regulations. The
on/off switch should be easily accessible after the appliance has been installed. If the switch is not accessible after
installation (depending on country) an additional means of
disconnection must be provided for all poles of the power
supply. When switched off there must be an all pole contact
gap of 3 mm in the isolator switch. This 3 mm contact disconnect gap must apply to any isolator switch, fuses and/or
relays according to EN60335.
3N
˜
L1
N
˜
L1
L2
L3
N
381 mm Cooktop
STANDARD INSTALLATION
343 mm
COUNTERTOP CUT-OUT
330 mm457 mm
914 mm min
FLOOR TO
COUNTERTOP
NOTE: Shaded area above countertop indicates minimum clearance to combustible surfaces,
combustible materials cannot be located within this area.
mm
762 mm
51
E
FRONT VIEWSIDE VIEW
64 mm
495 mm
64 mm
Single phase wiring diagram. 3phase wiring diagram.
wolfappliance.com | 3
SPECIFICATIONS
610 mm, 762 mm and 914 mm Cooktops
STANDARD INSTALLATION
51
mm
914 mm min
FLOOR TO
COUNTERTOP
W
WIDTH
COUNTERTOP CUT-OUT
762 mm330 mm457 mm
114 mm
89 mm
254 mm
610 mm, 762 mm and 914 mm Cooktops
FLUSH INSTALLATION
64 mm
495 mm
64 mm
mm
22
COUNTERTOP
PROFILE
MAX
8 mm
537 mm
RECESS
40 mm min
W
CUT-OUT WIDTH
A
RECESS
COUNTERTOP CUT-OUT
762 mm330 mm457 mm
51
mm
114 mm
E
89 mm
254 mm
914 mm min
FLOOR TO
COUNTERTOP
64 mm
495 mm
64 mm
E
FRONT VIEWSIDE VIEW
NOTE: Shaded area above countertop indicates minimum clearance to combustible surfaces,
combustible materials cannot be located within this area.
Electrical supply location only applies to installations with built-in oven.
CUT-OUT WIDTH
INDUCTION / ELECTRIC COOKTOPW
610 mm Induction562 mm
762 mm Induction / Electric724 mm
914 mm Induction / Electric876 mm
4 | English
FRONT VIEWSIDE VIEW
NOTE: Shaded area above countertop indicates minimum clearance to combustible surfaces,
combustible materials cannot be located within this area.
Electrical supply location only applies to installations with built-in oven.
Outside corner radius 11 mm.
CUT-OUT WIDTH
INDUCTION / ELECTRIC COOKTOPWA
610 mm Induction562 mm603 mm
762 mm Induction / Electric724 mm765 mm
914 mm Induction / Electric876 mm918 mm
INSTALLATION
Flush Installation
To ensure a proper installation, a template for the countertop
cut-out should be created using the cooktop glass.
ROUTING OPTION
For this installation, a recessed area surrounding the countertop cut-out is required. Fabrication of the recessed area
must take place before the countertop is installed.
This option is not recommended for countertops with a
molded backsplash.
CLEAT OPTION
For this installation, the countertop cut-out will be the same
size as the outer edge of the cooktop glass.
Attach L-shaped cleats to the perimeter of the countertop
cut-out. The top edge of the cleat can not be wider than
22 mm and will be attached 8 mm below the surface of the
countertop. Refer to the illustration below. Attach the cleats
to the countertop. Consult a countertop supplier for proper
methods of attachment.
8 mm
L-SHAPED
CLEATS
22 mm
Support cleats.
Cooktop Installation
Remove the cooktop and components from the shipping
package and recycle packing materials.
Lower the cooktop into the countertop cut-out. Center the
cooktop in the opening with the front edge aligned parallel
to the front edge of the countertop. Using a pencil, outline
the rear edge of the cooktop on the countertop. Remove the
cooktop.
Apply the foam strip provided, to the perimeter of the countertop opening. Refer to the illustration below. Do not seal
the cooktop to the countertop.
Insert the cooktop into the opening. Verify the cooktop is
aligned with the front edge of the countertop.
Attach the brackets provided, to the bottom of the unit.
Insert the 89 mm clamping screws into the brackets. Use
a screwdriver to tighten the clamping screws against the
bottom of the countertop. Do not overtighten screws. Refer
to the illustration below.
FOAM STRIP
COUNTERTOP
BRACKET
Cooktop installation.
CLAMPING
SCREW
Troubleshooting
IMPORTANT NOTE: If the cooktop does not operate prop-
erly, follow these troubleshooting steps:
• Verify electrical power is supplied to the cooktop.
• If the cooktop does not operate properly, contact Wolf
factory certied service. Do not attempt to repair the
cooktop. Wolf is not responsible for service required to
correct a faulty installation.
Wolf, Wolf & Design, Wolf Gourmet, W & Design and the color red as applied to knobs are registered trademarks and service marks of Wolf Appliance, Inc. Sub-Zero, Sub-Zero
& Design, Dual Refrigeration, The Living Kitchen, Great American Kitchens The Fine Art of Kitchen Design, and Ingredients are registered trademarks and service marks of
Sub-Zero, Inc. (collectively, the “Company Marks.”) All other trademarks or registered trademarks are property of their respective owners in the United States and other countries.
wolfappliance.com | 5
PLACAS VITROCERÁMICAS Y DE INDUCCIÓN
ESPECIFICACIONES
Índice
6 Placas vitrocerámicas y de inducción
6 Especicaciones
9 Instalación
9 Localización y solución de problemas
Las características y especicaciones están sujetas a
cambios sin previo aviso.
Nota importante
Para garantizar que este producto se instala y funciona de
la forma más ecaz y segura posible, tenga en cuenta la
información que se destaca en esta guía:
Cuando aparece
que resulta especialmente importante.
PRECAUCIÓN indica una situación en la que se pueden
sufrir heridas leves o provocar daños al producto si no se
siguen las instrucciones.
AVISO indica el peligro de que se produzcan heridas graves
o incluso la muerte si no se respetan las precauciones.
NOTA IMPORTANTE: conserve estas instrucciones para el
inspector eléctrico local.
NOTA IMPORTANTE, se resalta información
Información sobre el producto
En la placa de datos del producto encontrará información
importante, incluyendo el modelo y el número de serie. La
placa de datos está ubicada en la parte inferior del aparato.
Observe la siguiente ilustración.
Si necesita recurrir a un servicio técnico, póngase en
contacto con un servicio de Wolf certicado con el modelo y
el número de serie.
PLACA DE DATOSPLACA DE DATOS
Placa de inducción.
Placa vitrocerámica.
Requisitos de instalación
Es necesario dejar un espacio mínimo de altura de 159 mm
entre la parte superior de la encimera y cualquier supercie
combustible que se encuentre justo debajo de la placa.
Se necesita dejar un espacio para el bloque de terminales
en la parte trasera derecha de las placas vitrocerámicas y
de inducción. Observe la siguiente ilustración para ver las
medidas.
Consulte las ilustraciones de las páginas 3 y 4 para más
información sobre las distancias mínimas. Las medidas de
instalación son las mismas para las placas vitrocerámicas y
de inducción del mismo ancho.
AVISO
Si no coloca la placa siguiendo las distancias de
separación correctas, es posible que se produzca un
incendio.
32 mm
56
mm
38 mm
84
mm
40
mm
Distancia del bloque de terminales.
INSTALACIÓN EMPOTRADA
Las placas vitrocerámicas y de inducción contemporáneas
se pueden instalar empotradas con la parte superior
de la encimera o como una instalación sin marco
sobre la supercie de la encimera. Si la placa se instala
empotrada en la encimera, se necesitará un área acoplada
alrededor del corte de la placa. No se pueden utilizar las
campanas extractoras de encimera de Wolf con las placas
vitrocerámicas y de inducción contemporáneas.
La placa contemporánea incluye un kit de instalación y las
instrucciones necesarias para una instalación empotrada.
PRECAUCIÓN
La instalación empotrada está diseñada para colocarse
únicamente en superficies sólidas, de granito o en
encimeras de piedra.
VARIAS PLACAS
Cuando se instalen varias placas o módulos juntos, el
ancho de corte de la encimera se determina sumando el
ancho de cada unidad y, a continuación, restando 25mm.
Consulte la siguiente ilustración.
NOTA IMPORTANTE: las placas vitrocerámicas y de
inducción contemporáneas no están diseñadas para
instalarse junto con otras placas.
64 mm
495 mm
PROFUNDIDAD
DEL CORTE
6 | Español
Corte de la encimera.
ANCHURA DEL CORTE
(ANCHO COMBINADO DE
LAS PLACAS MENOS 25 mm)
64 mm
ESPECIFICACIONES
Potencia
La instalación debe cumplir con todas las normativas
eléctricas aplicables y debe estar correctamente conectada
a tierra.
Localice la toma eléctrica tal como se indica en las
ilustraciones en las páginas 3-4. Se necesita un circuito
independiente para esta unidad. No se recomienda utilizar
un interruptor de circuito de fallos de toma de tierra (GFCI),
ya que puede interrumpir el funcionamiento de la unidad.
El rendimiento puede verse afectado si el suministro
eléctrico es inferior a 220 voltios.
Cuando se instalen varias placas juntas, cada unidad debe
tener su propio circuito eléctrico recomendado.
ALIMENTACIÓN NECESARIA
VITROCERÁMICA / DE INDUCCIÓN
Cableado monofásico220-240 V CA, 50/60 Hz
Trifásico380-415 V AC, 50 Hz
Consulte el cuadro de conexiones que muestra las
conexiones de cada cable a la caja de cables en la unidad.
AVISO
El aparato debe estar conectado a tierra de manera
correcta siempre que esté conectado a la red eléctrica.
No conecte a tierra el aparato con el cable neutro
(blanco) de la instalación de la vivienda. Debe utilizar
un cable de conexión a tierra independiente.
Si utiliza el cable de aluminio de la instalación de la
vivienda, empalme el cable de cobre del aparato al
cable de aluminio de la vivienda utilizando conectores
especiales diseñados y autorizados por el organismo
regulador para unir el cable y el aluminio. Realice el
procedimiento recomendado por el fabricante del
conector. Si la conexión no se realiza de manera
correcta, existe riesgo de que se produzca un incendio.
NOTA IMPORTANTE: la conexión de este aparato debe
realizarse a una unidad de conexión con fusibles o a un
aislador adecuado, que cumpla con las normativas de
seguridad nacionales y locales. El interruptor de encendido/
apagado debe situarse en un lugar accesible después de
haber instalado el aparato. Si no es posible acceder al
interruptor después de la instalación (según el país), se
deberá suministrar un medio de desconexión adicional
para todos los polos de la alimentación eléctrica. Al estar
desconectado, deberá existir una separación de contacto
entre todos los polos de 3 mm en el interruptor del aislador.
Esta separación de 3 mm de desconexión de los contactos
deberá aplicarse a cualquier interruptor, fusibles o relés del
aislador según la norma EN60335.
Placa de 381 mm
INSTALACIÓN ESTÁNDAR
330 mm457 mm
914 mm mín
DEL SUELO A
LA ENCIMERA
343 mm
CORTE DE LA ENCIMERA
762 mm
51
mm
64 mm
495 mm
64 mm
E
˜
L1
N
Diagrama de cableado
monofásico.
3N
˜
L1
L2
L3
N
Diagrama de cableado trifásico.
VISTA FRONTALVISTA LATERAL
NOTA: el área sombreada sobre la encimera indica la distancia mínima a superficies combustibles,
por lo que no puede haber materiales combustibles en esta área.
wolfappliance.com | 7
Loading...
+ 15 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.