Winco ASCO-300-H User Manual

Operator’s
Manual
Series 300
H–desi g n 600 throu gh 1200 amps
DANGER is used in this manual to warn of high
voltages capable of causin g shock, burns, or death.
!
WARNINGisusedinthismanualtowarn
of possible personal injury.
!
CAUTIONisusedinthismanualtowarn
of possible equipment damage.
An experienced licensed electrician must install the A TS.
Refer to the outline and wiring drawings provided with ASCO Series 300 ATS for installation details.
TABLE OF CONTENTS
section
INSTALLATION 1..........................
SEQUENCE OF OPERATION 2.............
TESTING & SERVICE 3....................
ADJUSTMENTS 4.........................
CONTROL FEATURES 5...................
INDEX back cover.........................
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA For sales or service call 1 800 800–2726 (ASCO) www.ascopower.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3 telephone 519 758–8450, fax 519 758–0876, for service call 1 888 234–2726 (ASCO) www.asco.ca
1200 amp. size600, 800, 1000 amp. sizes
381333–201 D
Nameplate
The Transfer Switch nameplate includes data for each specific ASCO Series 300 ATS. Use the ATS only within the limits shown on this nameplate.
H 300 B 3 600 N 1 C
Catalog Number Identification
A typical Catalog Number is shown below with its elements explained. The example is for a Series 300 ATS with switched neutral, 3 pole, 600 amp, 480 V, in a Type 1 enclosure:
B –switched C – overlapping
blank – solid
neutral
connections
power
connections
Neutral
Phase Poles
2 –singleØ 3 –threeØ
Amperes Voltage Controller Enclosure
600
800 1000
1200
C 208
D 220 E 230
F 240
H 380
J 400
L 440
M 460 N 480
P 550
Q 575
R 600
1 –standard
1X –if
accessories
ordered
* available 600 – 1000 amp. sizes only
C –type1
F –type3R
G –type4 *
L –type12 *
blank – open type
K 415
Controller
membrane
controls
Transfer
Switch
terminal block TB
for engine start
and switch
position contacts
power
connections
neutral
connections
600 amp. size in typical enclosure with location of customer connections
ASCO Series 300 Automatic Transfer Switches (ATSs) are Listed under Underwriters Laboratories UL 1008 Standard for Safety for Automatic Transfer Switches. All control features are UL Component Recognized, which assures that ASCO automatic transfer switches meet OSHA Safety Requ irem ents and will be acceptable to electrical inspectors.
ASCO Series 300 Automatic Transfer Switches are suitable for emergency and standby system applications. They meet emergency system rating requirements as defined in National Electrical Code (NEC) Article 700 and UL 1008. Also, they are suitable for the requirements of NEC Article 517 – Health Care Facilities, NEC Article 701 – Legally Required Standby Systems, NEC Article 702 – Optiona l
neutral
connections
power
connections
Standby Systems, NFPA 99 Health Care Facilities, and NFPA 110 Emergency and Standby Power Systems.
Rating Label
Each automatic transfer switch contains a rating label to define the loads and fault circuit withstand / closing ratings. Refer to the label on the transfer switch for specific values.
!
Do not exceed the values on the rating label.
Exceeding the rating can cause personal injury
or serious equipment damage.
Controller
Transfer
Switch
terminal block TB
for engine start
and switch
position contacts
power
connections
neutral
connections
membrane
controls
800 and 1000 amp. size in typical enclosure with location of customer connections
neutral
connections
power
connections
Transfer
Switch
Controller
membrane
controls
terminal block TB
for engine start
and switch
position contacts
power
connections
neutral
connections
1200 amp. size in typical enclosure with location of customer connections
SECTION 1 INSTALLATION
Series 300 Automatic Transfer Switches are factory wired and tested. Installation requires skid removal then securing the enclosure to the supporting foundation.
Remove the Shipping Skid
Open the front door and remove the four lag screws (2 in front, 2 i n rear) securing enclosure to the wood skid.
Supporting Foundation
The supporting foundation for the enclosure must be level and straight. Refer to the applicable enclosure outline drawing included with the Series 300 for all mounting details including door opening space.
If bottom cable entry is used, the foundation must be prepared so that the conduit stubs are located correctly. Refer to the enclosure outline drawingfor specifiedarea and location. Provide cable bending space and clearance to live metal parts. When a concrete floor is poured, use interlocking conduit spacer caps or a wood or metal template to maintain proper conduit alignment.
Mounting
Refer to the applicable enclosure outline drawing fur­nished with this switch and mount the Series 300 according to details and instructions shown on diagram.
Testing Power Conductors
Do not connect the power conductors to the ASCO Series 300 transfer switch until they are tested. Installing power cables in conduit, cable troughs and ceiling-sus­pended hangers often requires considerable force. The pulling of cables can damage insulation and stretch or break the conductor’s strands. For this reason, after the cables are pulled into position, and before connected, they should be tested to verify that they are not defective or have been damaged during installation.
!
Protect the automatic transfer switch from
construction grit and metal chips to prevent
malfunction or shortened life of the ATS.
they are
Connecting Power Conductors
After the power cables have been tested, connect them to the appropriate terminal lugs on the transfer switch as shown on the wiring diagram provided with this Series
300. M ake sure the lugs provided are suitable for use with the cables being installed. Standard terminal lugs are solderless screw type and will accept the wire sizes listed on the drawings provided with the Series 300. Be careful when stripping insulation from the cables; avoi d nicking or ringing the conductor. Remove surface oxides from cables by cleaning with a wire brush. When aluminum cable is used, apply joint compound to conductors. Tighten cable lugs to the torque specified on rating label.
Line Connections
Refer to the Wiring Diagram provided with your Series 300 ATS. All wiring must be made in accordance with the National Electrical Code and local codes.
It is unnecessary to remove pole covers from the transfer switch. If you do remove them, reinstall them carefully.
De–energize the conductors before making any line or auxiliary circuitry connections. Be sure that Normal and Emergency line connections are in proper phase rotation. Place engine gen­erator starting control in the OFF position. Make sure engine generator is not in operation.
Controller Ground
A grounding wire must be connected to the controller’s lower left mounting stud. Because the controller is mounted on the enclosure door, a conductive strap must be used between the enclosure and the door. This connection provides proper grounding which does not rely upon the door hinges.
Harnesses
The transfer switch is connected to the left side of the controller by a plug–in harness (two plugs).
1 --- 1
INSTALLATION (continued)
Engine Starting Contacts
Customer connections for engine control contact and TS auxiliary contacts connections are located on terminal block TB which is mounted on the front lower left of the transfer switch. Refer to wiring diagram provided with the Series 300 A TS and connect the engine start wires to the appropriate terminals. See Figure 1–1 and Table A.
TableA.Enginestart
connections.
When normal
source fails
Te r m i n a l s
on transfer
switch
contact closes TB1 and TB2 contact opens TB1 and TB3
Auxiliary Circuits
Connect auxiliary circuit wires to appropriate terminals on transfer switch terminal block TB as shown on the wiring diagram provided with this Series 300 Automatic Transfer Switch. Make the neces­sary auxiliary connections by refer­ring to Section 5, Control Features.
Connections to Controller for other Control Features
(located on bottom of Controller)
COMMON
FEATURE 7
closes to start
FEATURE 8
opens to start
COMMON
FEATURE 14B
closed o n emergency
FEATURE 14A
closed on normal
COMMON
FEATURE 14BA
closed o n emergency
FEATURE 14AA
closed on normal
terminal block for engine start and
auxiliary circuit connections
left side of
transfer switch
Engine Starting
Signals
5amps,32VDC
5ampsresistive28VDC
or 120 V AC max.
TS Auxiliary Contacts
Feature 14A & 14B
10 amps, 32 V DC
10 amps 250 V AC
general purpose
Optional
TS Auxiliary Contacts
Feature 14AA & 14BA
10 amps, 32 V DC 10 amps 250 V AC
general purpose
Figure 1-1. Engine start and auxiliary circuit
terminal block TB located on the transfer switch.
Load Disconnect
Feature
Connections
(see Wiring Diagram
& refer to page 5–4
for DIP switch settings)
Programmable
Engine Exerciser
connection,
if provided
(refer to
page 5–3)
Remote Control Features Connections
(refer to the Wiring Diagram &
page 5–4 for DIP switch settings)
Each control contact must be suitable
for a 5 V DC low energy circuit.
for factory
use only
Figure 1-2. Input / output label on the Controller showing possible connections to the lower terminal block.
1 --- 2
Loading...
+ 14 hidden pages