Winco ASCO-300-E User Manual

Operator’s
Manual
E design, 260 and 400 amp. sizes
DANGER is used in this manual to warn of high
voltages capable of causing shock, burns, or death.
!
WARNINGisusedinthismanualto
warn of possible personal injury.
!
Series 300
Refer to the outline and wiring drawings provided with your ASCO Series 300 ATS for all installation details.
ASCO Series 300 Automatic Transfer Switches (ATSs) are Listed under Underwriters Laboratories UL 1008 Standard for Safety for Automatic Transfer Switches. ASCO Series 300s are also Listed under CSA C22.2 No. 178 Standard for Automatic Transfer Switches. All control features are UL Component Recog nized, which assures that ASCO automatic transfer switches meet OSHA Safety Requ irem ents and will be acceptable to electrical inspectors.
CAUTIONisusedinthismanualtowarn
of possible equipment damage.
An experienced licensed electrician must install the ATS.
ASCO Series 300 Automatic Transfer Switches are suitable for emergency and standby system applications. They meet emergency system rating requirements as defined in National Electrical Code (NEC) Article 700 and UL 1008. Also, they are suitable for the requirements of NEC Article 517 – Health Care Facilities, NEC Article 701 – L egally Required Standby Systems, NEC Article 702 – Optional Standby Systems, NFPA 99 Health Care Facilities, and NFPA 110 Emergency and Standby Power Systems.
Rating Label
Each automatic trans fer switch con tains a rating label to define the loads and fault circuit withstand / closing ratings. Refer to the label on the transfer switch for specific values.
!
Do not exceed the values on the rating label.
Exceeding the rating can cause personal injury
or serious equipment damage.
TABLE OF CONTENTS
section
INSTALLATION 1..........................
SEQUENCE OF OPERATION 2.............
TESTING & SERVICE 3....................
ADJUSTMENTS 4.........................
CONTROL FEATURES 5...................
INDEX back cover.........................
260 & 400 amp sizes
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA 1 800 937–2726 (ASCO), for service call 1 800 800–2726 (ASCO) www.asco.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3 telephone 519 758–8450, fax 519 758–0876, for service call 1 888 234–2726 (ASCO) www.asco.ca
381333–067 F
Nameplate and Catalog Number Identification
The Transfer Switch nameplate includes data for each specific ASCO Series 300 ATS. Use the ATS only within the limits shown on this nameplate. A typical Catalog Number is shown below with its elements explained.
The example is for a Series 300 ATS with switched neutral, 3 pole, 400 amp., 480 V, in a Type 1 enclosure:
E 300 C 3 400 N 1 C
transfer switch prefix letter
Neutral
C – overlapping
blank – solid
load power connections
emergency power connections
Phase Poles
2 –singleØ 3 –threeØ
Amperes Voltage Controller Enclosure
260 400
A 115 B 120
C 208
D 220 E 230
F 240
H 380
K 415
L 440
M 460 N 480
P 550
Q 575
R 600
1 –standard
1X –if
accessories
ordered
C –type1
F –type3R
G –type4
L –type12
blank – open type
J 400
membrane
controls
terminals for
engine start
contacts
Transfer
Switch
terminals for
switch position
contacts
normal power connections
400 amp. size in typical enclosure with location of customer connections
Controller
SECTION 1 INSTALLATION
Series 300 Automatic Transfer Switches are factory wired and tested. Installation requires skid removal then secur­ing the enclosure to the supporting foundation.
Supporting Foundation
The supporting foundation for the enclosure must be level and straight. Refer to the applicable enclosure outline drawing included with the Series 300 for all mounting details including door opening space.
If bottom cable entry is used, the foundation must be prepared so that the conduit stubs are located correctly. Refer to the enclosure outline drawing for specified area and location. Provide cable bendingspace and clearanceto live metal parts. When a concrete floor is poured, use interlocking conduit spacer caps or a wood or metal template to maintain proper conduit alignment.
!
Be sure that the insulator piece is behind
260 and 400 ampere transfer switches.
insulator backing piece
Mounting
Refer to the applicable enclosure outline drawing fur­nished with this switch and mount the Series 300 according to details and instructions shown on diagram.
!
Protect the switch from construction grit
and metal chips to prevent malfunction or
shortened life of the automatic switch switch.
Mount the ASCO ATS vertically to a rigid supporting structure. Level all mounting points by using flat washers behind the holes to avoid distortion of the switch.
Transfer switches rated 260 and 400 amp. are mounted on an insulator backing piece (installed behind the transfer switch). If the transfer switch is removed from the cabinet and then reinstalled, this insulator piece must be placed behind the transfer switch. See Figure 1–1.
Line Connections
Refer to the Wiring Diagram provided with your Series 300 ATS. All wiring must be made in accordance with the National Electrical Code and local codes.
De–energize the conductors before making any line or auxiliary circuitry connections. Be sure that Normal and Emergency line connections are in proper phase rotation. Place engine gen­erator starting control in the OFF position. Make sure engine generator is not in operation.
It is not necessary to remove the barriers from the transfer switches to install cables.
Figure 1-1. Insulator for 260 and 400 amp. E–design
transfer switches.
The controller is mounted on the cabinet door. Anadd-on DIN rail is provided for some optional accessories and is mounted below the controller on the door.
Testing Power Conductors
Do not connect the power conductors to the ASCO Series 300 transfer switch until they are tested. Installing power cables in conduit, cable troughs and ceiling-suspended hangers often requires considerable force. The pulling of cables can damage insulation and stretch or break the conductor’s strands. For this reason, after the cables are pulled into position, and before should be tested to verify that they are not defective or have been damaged during installation.
they are connected, they
Connecting Power Conductors
After the power cables have been tested, connect them to the appropriate terminal lugs on the transfer switch as shown on the wiring diagram provided with this Series 300. Make sure the lugs provided are suitable f or use with the cables being installed. Standard terminal lugs are solder­less screw type and will accept the wire sizes listed on the drawings provided with the Series 300. Be careful when stripping insulation from the cables; avoid nicking or ringing the conductor. Remove surface oxides from cables by cleaning with a wire brush. When aluminum cable is used, apply joint compound to conductors. Tighten cable lugs to the torque specified on rating label.
Do not run cables behind the switch. Cables can be bundled on the right side of the switch. Maintain proper electrical clearance between the live metal parts and grounded metal: ½ inch minimum.
1--1
INSTALLATION (continued)
Engine Starting Contacts
Controller Ground
The engine control contact connections are located on the transfer switch. Connect signal wires to appropriate term– inals as specified in T able A, shown in Figure 1–2.
Table A. Engine start connections.
When normal source
fails
contact closes TB14 and TB15 contact opens TB14 and TB16
Transfer Switch
Terminals on transfer
switch
A grounding wire must be connected to the controller’s lower left mounting stud. Because the controller is mounted on the enclosure door, a conductive strap must be used between the enclosure and the door. This connection provides proper grounding which does not rely upon the door hinges.
Harnesses
The transfer switch is connected to the left side of the controller by a plug–in harness (two plugs).
Auxiliary Circuits
Connect auxiliary circuit wires to appropriate terminalson transfer switch. Note the control f eatures that are fur­nished on this switch. Make the necessary auxiliary connections by referring to Section 5, Control Features.
Figure 1-2. Engine starting contact label and location
for 260 and 400 amp. E–des ign transfer switches.
Connections to Controller for other Control Features (located on bottom of Controller):
Load Disconnect
Feature
Connections
(see Wiring Diagram
& refer to page 5–5
for DIP switch settings)
Programmable
Engine Exerciser
connection,
if provided
(refer to
page 5–2)
Remote Control Features Connections
(refer to the Wiring Diagram &
page 5–5 for DIP switch settings)
Each control contact must be suitable
for a 5 V DC low energy circuit.
for factory
use only
Figure 1-3. Input / output label on the Controller showing possible connections to the lower terminal block.
1--2
INSTALLATION (continued)
Functional Test
The Functional Test consists of three checks: manual operation, voltage checks, and electrical operation.
!
Do these checks in the order presented to
avoid damaging the automatic transfer switch.
Read all instructions on the Wiring Diagram and labels affixed to the automatic transfer switch. Note the control features that are provided and review their operation before proceeding.
1 – Manual Operation Te st
A detach ab l e manual operator handle is provided on the Transfer Switch for maintenance purposes only operation of the transfer switch should be checked before it is energized (operated electrically).
!
Do not manually operate the transfer switch
until both power sources are disconnected:
open both circuit breakers.
1. Insert the maintenance handle into the hole in the shaft, left side of the operator.
2. Move the maintenance handle as shown to manuall y operate the transfer switch. The switch should operate smoothly without any binding. If it does not, check for shipping damage or construction debris.
.Manual
maintenance
hole
handle
shaft
Figure 1-4. Removable maintenance handle on
260 and 400 amp. E–design transfer switches.
3. Return the transfer switch to the N (normal) position.
4. R emove the maintenance handle and store it on the transfer switch in the place provided.
!
Verify that the maintenance handle has
been removed before proceeding!
Now continue to 2–VoltageCheckson next page.
1--3
INSTALLATION (continued)
TRANSFER SWITCH TEST BYPASS TIME DELAY SET ENGINE EXERCISER
observe these lights
Press for 15 Seconds
Figure 1–5. Standard controls and indicators.
2–VoltageChecks
First check nameplate on transfer switch; rated voltage mustbethesameasnormalandemergencylinevoltages.
!
Verify that the feeders have been
connected to the proper lugs.
Use extreme caution when using a meter to measure voltages in the following steps. Do not touch power terminals; shock, burns, or death could result !
Perform steps 1 through 6 at the right. Observe the status lights. See Figure 1–5.
Black circle means light is on.White circle means light is off.
* If necessary, adjust voltage regulator on the generator according to the manufacturer’s recommendations. The Automatic Transfer Switch will respond only to the rated voltage specified on the Transfer Switch nameplate.
Press until light FLASHES
Close the normal source circuit breaker. The Transfer Switch Connected To Normal and the
1
Normal Source Available lights should come on.
Use an accurate voltmeter to check phase to phase and phase to neutral voltages pres -
2
entatthetransferswitchnormal source terminals.
Close the emergency source circuit breaker. (Start generator, if necessary.) The Transfer
3
Switch Connected To Normal and the Emergency Source Available lights should come on.
Use an accurate voltmeter to check phase to phase and phase to neutral voltages pres -
4
ent at the transfer switch emer­gency source terminals.*
Useaphaserotationmeterto check phase rotation of emer-
5
gency source; it must be the same
as the normal source.
C
B
A
1--4
Shut down the engine–genera­tor , if applicable. The Emergen- cy Source Accepted light should go off. Then put the starting
6
control selector switch (on the generator set) in the automatic position. Close enclosure door.
Now continue to 3 – Electrical Operation on next page.
Loading...
+ 13 hidden pages