voltages capable of causing shock, burns, or death.
!
WARNINGisusedinthismanualto
warn of possible personal injury.
!
Series 300
Refer to the outline and wiring drawings provided with
your ASCO Series 300 ATS for all installation details.
ASCO Series 300 Automatic Transfer Switches (ATSs) are
Listed under Underwriters Laboratories UL 1008 Standard
for Safety for Automatic Transfer Switches. ASCO Series
300s are also Listed under CSA C22.2 No. 178 Standard for
Automatic Transfer Switches. All control features are UL
Component Recog nized, which assures that ASCO automatic
transfer switches meet OSHA Safety Requ irem ents and will
be acceptable to electrical inspectors.
CAUTIONisusedinthismanualtowarn
of possible equipment damage.
An experienced licensed electrician must install the ATS.
ASCO Series 300 Automatic Transfer Switches are suitable
for emergency and standby system applications. They meet
emergency system rating requirements as defined in
National Electrical Code (NEC) Article 700 and UL 1008.
Also, they are suitable for the requirements of NEC Article
517 – Health Care Facilities, NEC Article 701 – L egally
Required Standby Systems, NEC Article 702 – Optional
Standby Systems, NFPA 99 Health Care Facilities, and
NFPA 110 Emergency and Standby Power Systems.
Rating Label
Each automatic trans fer switch con tains a rating label to
define the loads and fault circuit withstand / closing ratings.
Refer to the label on the transfer switch for specific values.
!
Do not exceed the values on the rating label.
Exceeding the rating can cause personal injury
or serious equipment damage.
TABLE OF CONTENTS
section
INSTALLATION1..........................
SEQUENCE OF OPERATION2.............
TESTING & SERVICE3....................
ADJUSTMENTS4.........................
CONTROL FEATURES5...................
30–200 amp. sizes
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA
1 800 937–2726 (ASCO), for service call 1 800 800–2726 (ASCO) www.asco.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3
telephone 519 758–8450, fax 519 758–0876, for service call 1 888 234–2726 (ASCO) www.asco.ca
INDEXback cover.........................
381333–228 D
Page 2
Nameplate
The Transfer Switch nameplate includes data for each
specific ASCO Series 300 ATS. Use the ATS only
within the limits shown on this nameplate.
D 300B3200N1C
Catalog Number Identification
A typical Catalog Number is shown below with its
elements explained. The example is for a Series 300
ATS with switched neutral, 3 pole, 200 amp, 480 V, in
a Type 1 enclosure:
Neutral
B –switched
C – overlapping
blank – solid
load power
connections
emergency power
connections
Phase Poles
2 –singleØ
3 –threeØ
terminals for switch
AmperesVoltageControllerEnclosure
30
70
104
150
200 *
* 200 amp. limited
to 480 volts
position contacts
A 115
B 120
C 208
D 220
E 230
F 240
H 380
J 400
K 415
L 440
M 460
N 480
P 550
Q 575
R 600
membrane
controls
1 –standard
1X –if
accessories
ordered
C –type1
F –type3R
G –type4
L –type12
blank – open type
Controller
Transfer
Switch
maintenance
handle
(see WARNING
under Manual
Operation)
terminals for
engine start
contacts
normal power
connections
cable spacers
(see INSTALLATION)
200 amp. size in typical enclosure with location of customer connections
Page 3
Catalog Number Identification
A typical Catalog Number is shown below with its elements explained. The example is for a Series 300 ATS with
switched neutral, 3 pole, 230 amp, 480 V, in a Type 1 enclosure:
D 300B3230N1C
Neutral
B –switched
C – overlapping
blank – solid
load power
connections
emergency power
connections
Phase Poles
2 –singleØ
3 –threeØ
AmperesVoltageControllerEnclosure
230 **
** 230 amp. limited
to 480 volts
terminals for switch
position contacts
A 115
B 120
C 208
D 220
E 230
F 240
H 380
J 400
K 415
L 440
M 460
N 480
1 –standard
1X –if
accessories
ordered
membrane
controls
C –type1
F –type3R
G –type4
L –type12
blank – open type
Controller
Transfer Switch
maintenance handle
(see WARNING under
Manual Operation)
terminals for
engine start contacts
normal power
connections
cable spacers
(see INSTALLATION)
230 amp. size in typical enclosure with location of customer connections
Page 4
SECTION 1INSTALLATION
Series 300 AutomaticTransfer Switchesare factory wired
and tested. Installation requires skid removal then
securing the enclosure to the supporting foundation.
Mounting
Refer to the applicable enclosure outline drawing furnished with this switch and mount the Series 300
according to details and instructions shown on diagram.
!
Protect the automatic transfer switch from
construction grit and metal chips to prevent
malfunction or shortened life of the ATS.
Mount the ASCO ATS vertically to a rigid supporting
structure. Level all mounting points by using flat washers
behind the holes to avoid distortion of the switch.
Connecting Power Conductors
After the powercables have been tested, connect them to
the appropriate terminal lugs on the transfer switch as
shown on the wiring diagram provided wit h this Series
300. M ake sure the lugs provided are suitable for use with
the cables being installed. Standard terminal lugs are
solderless screw type and will accept the wire sizes listed
on the drawings provided with the Series 300. Be careful
when stripping insulation from the cables; avoi d nicking
or ringing the conductor. Remove surface oxides from
cables by cleaning with a wire brush. When aluminum
cable is used, apply joint compound to conductors.
Tighten cable lugs to the torque specified on rating label.
Three cable spacers are included with 150, 200, and 230
ampere transfer switches. When installing power cables,
run the cables through the cable spacers as shown in
Figure 1–1. Position cable spacers within 1½ inches from
lugs.
Line Connections
Refer to the Wiring Diagram provided with your Series
300 ATS. All wiring must be made in accordance with the
National Electrical Code and local codes.
De–energize the conductors before making any
line or auxiliary circuitry connections. Be sure
that Normal and Emergency line connections
are in proper phase rotation. Place engine generator starting control in the OFF position. Make
sure engine generator is not in operation.
It is unnecessary to remove pole covers from the transfer
switch. If you do remove them, reinstall them carefully.
Testing Power Conductors
Do not connect the power conductors to the ASCO
Series 300 transfer switch until they are tested. Installing
power cables in conduit, cable troughs and ceiling-suspended hangers often requires considerable force. The
pulling of cables can damage insulation and stretch or
break the conductor’s strands. For this reason, after the
cables are pulled into position, and before
connected, they should be tested to verify that they are
not defective or have been damaged during installation.
they are
!
The cable spacers must be located as shown
for 150, 200, and 230 ampere transfer switches.
cable spacers
1 ½ inch approximate
cable spacer
Figure 1–1. Cable spacers for 150, 200, & 230 amp.
transfer switches.
1--1
Page 5
INSTALLATION(continued)
Engine Starting Contacts
Controller Ground
Customer connections for enginecontrol contact
connections are located on the transfer switch. Refer to
wiring diagram provided with the Series 300 A TS and
connect the engine start wires to the appropriate
terminals . See Figure 1–2 and Table A.
Table A. Engine start connections.
When normal source
fails
Terminals on transfer
switch
contact closesTB14 and TB15
contact opensTB14 and TB16
ENGINE STARTING CONTACTS
( SHOWN DE–ENERGIZED )
TOP
STUD
MIDDLE
STUD
BOTTOM
STUD
14
TS
15
NR
16
NR
TB 14
TB 16
left side
of switch
TB 15
Figure 1–2. Engine starting contact label and
terminals located on the transfer switch.
A grounding wire must be connected to the controller’s
lower left mounting stud. Because the controller is
mounted on the enclosure door, a conductive strap must
be used between the enclosure and the door.This
connection provides proper grounding which does not
rely upon the door hinges.
Harnesses
The transfer switch is connected to the left side of the
controller by a plug–in harness (two plugs).
Auxiliary Circuits
Connect auxiliary circuit wires to appropriate terminals
on transfer switch as shown on the wiring diagram
provided with this Series 300 Automatic Transfer Switch.
Make the necessary auxiliary connections by referring to
Section 5, Control Features.
Load Disconnect
Feature
Connections
(see Wiring Diagram
& refer to page 5–5
for DIP switch settings)
Connections to Controller for other Control Features
(located on bottom of Controller)
Programmable
Engine Exerciser
connection,
if provided
(refer to
page 5–2)
Remote Control Features Connections
(refer to the Wiring Diagram &
page 5–5 for DIP switch settings)
Each control contact must be suitable
for a 5 V DC low energy circuit.
for factory
use only
Figure 1–3. Input / output label on the Controller showing possible connections to the lower terminal block.
1--2
Page 6
INSTALLATION(continued)
Functional Test
The Functional Test consists of three checks: manual
operation, voltage checks, and electrical operation.
!
Do these checks in the order presented to
avoid damaging the automatic transfer switch.
Read all instructions on the Wiring Diagram and labels
affixed to the automatictransfer switch. Note the control
features that are provided and review their operation
before proceeding.
1 – Manual Operation Te st
A maintenance handle is provided on the Transfer Switch
for maintenance purposes only
transfer switch should be checked before it is energized
(operated electrically).
!
Do not manually operate the transfer switch
until both power sources are disconnected:
open both circuit breakers.
1. After deenergizing both power sources, open the
enclosure door. Locate and the maintenance handle
on the left side of the transfer switch frame. See
Figure 1–4.
2.Grasp the attached maintenance handle and turn it
with thumb and fingers as shown to manually operate
it. The maintenance handle turns the opposite direction of the weight. Move it up or down as shown to
manually operate the transfer switch. It should operate
smoothly without any binding. If it does not, check for
shipping damage or construction debris.
3.Return the transfer switch to the Normal position.
Note: If Normal and Emergency connections are
reversed this operation is also reversed.
. Manual operation of the
Position of the transfer switch is indicated here
weight marked N (normal)
and E (emergency)
maintenance
handle
weight
floating
weight
With ALL POWER OFF grasp
maintenance handle and turn it
quickly with your thumb and fingers.
Figure 1–4. Maintenance handle and positions.
Now continue to 2–VoltageCheckson next page.
1--3
Page 7
INSTALLATION(continued)
TRANSFER SWITCH TEST BYPASS TIME DELAY SET ENGINE EXERCISER
observe these lights
Press for 15 Seconds
Figure 1–5. Standard controls and indicators.
2–VoltageChecks
First check nameplat e on transfer switch; rated voltage
mustbethesameasnormalandemergencylinevoltages.
!
Verify that the feeders have been
connected to the proper lugs.
Use extreme caution when using a meter
to measure voltages in the following
steps. Do not touch power terminals;
shock, burns, or death could result !
Performsteps 1 through 6 at the right. Observe the status
lights. See Figure 1–5.
● Black circle means light is on.
❍ White circle means light is off.
* If necessary, adjust voltage regulator on the generator
according to the manufacturer’s recommendations. The
Automatic Transfer Switch will respond only to the rated
voltage specified on the Transfer Switch nameplate.
Also see page 4–1 for the HI–LOW voltage adjust setting
in the controller. The LOW setting shifts all voltage
settings down 4.2%; for example, 240 V to 230 V.
Press until light FLASHES
Close the normal source circuit
breaker. The Load ConnectedTo No r mal and t he Normal
1
Source Available lights should
come on.
Use an accurate voltmeter to
check phase to phase and
phase to neutral voltages
2
present at the transfer switch
normal source terminals.
Close the emergency source
circuit breaker. (Start generator,
if necessary.) The Load
3
Connected To Normal and the
Emergency Source Available
lights should come on.
Use an accurate voltmeter to
check phase to phase and
phase to neutral voltages
4
present at the transfer switch
emergency source terminals.*
Useaphaserotationmeterto
check phase rotation of
5
emergency source; it must be
the same
as the normal source.
Shut down the
engine–generator, if applicable.
The Emergency SourceAccepted light should go off.
6
Then put the starting control
selector switch (on the
generator set) in the automatic
position. Close enclosure door.
C
B
A
1--4
Now continue to 3 – Electrical Operation on next page.
Page 8
INSTALLATION(continued)
observe these lights
pressthisbutton
TRANSFER SWITCH TEST BYPASS TIME DELAY SET ENGINE EXERCISER
Press for 15 Seconds
Figure 1–6. Standard controls and indicators.
3 – Electrical Operation
This procedure will check the electrical operation of the
Automatic Transfer Switch. See Figure 1–6.
!
Close the enclosure door first !
Transfer Test
Both normal and emergency sources must be available
and the emergency source generator (if used) must be
capable of being started in this procedure.
Performsteps 1 through 8 at the right. Observe the status
lights. See Figure 1–6.
● Black circle means light is on.
❍ White circle means light is off.
NOTE: IfMotorLoadTransferfeature
is activated, then transfer may not occur
immediately after the respective time
delays. Transfer will only occur when
the phase relationship between sources
is correct.
This completes the Functional T es t of the ASCO Series 300
Au tom atic Tran sfer Switch. Leave the engine–generator
starting control in the automatic position.
Press until light FLASHES
The normal source must be
available and the generator
must be ready to start.
1
Check that the Normal SourceAvailable light is on.
Press and hold the TransferSwitch Test button until the
2
engine starts and runs. This
should happen within 15 sec.
The Emergency Source
3
Available light should come on.
The transfer switch should
transfer to the Emergency
position. The Load Connected
4
to Emergency light should come
on and the Load Connected toNormal light should go off.
If the transfer to emergencydelay is used the transfer
should occurs after a time delay
5
(up to 5 minutes).
Forimmediatetransferpress
the Bypass Time Delay button.
The transfer switch should
transfer back to the Normal
position. The Load Connected
6
to Normal light should come on
and the Load Connected toEmergency light should go off.
If the retransfer to normal delay
is used the retransfer should
occur after a time delay
7
(up to 30 minutes).
Forimmediateretransferpress
the Bypass Time Delay button.
TRANSFER SWITCH TEST
BYPAS S TIME D ELAY
BYPAS S TIME D ELAY
1--5
The unloaded running delay
keeps the generator running for
5 minutes (cool–down period).
8
Then the generator should stop
and the Emergency SourceAvailable light should go off.
Page 9
SECTION 2SEQUENCE OF OPERATION
lights show position of transfer switch
Transfer To Emergency
Thesequenceforloadtransferto
emergency source begins automatically when normal source voltage
falls below the preset dropout point
or when Transfer Switch Test button
is pressed. An under voltage condition on any phase of the normal
source is detected by the sensor.
Whenthenormal
source voltage fails or
the Transfer Switch Test
button is pressed, the
SE relay de-energizes
and relay NR begins its
timin g cycle ( 1 or 3
seconds, mome n t ary
Hold 15 sec.to
start the engine
generator and to
transfer the load
to emergency.
normal source outage
delay). The NR rel ay is provided with a time delay on
dropout to override momentary outages and prevent
nuisance starting of the engine-driven generator. If the
normal source voltage returns above the sensor dropout
setting before the time delay expires, the NR relay timing
cycle is reset to zero and relay SE energizes.
If the normal source voltage does not return above the
sensor dropout setting before the time delay expires, the
NR relay de-energizes and signals the engine-driven
generator to start. At the same time, a voltage and
frequency sensor begins monitoring the emergency source.
The sensor will accept the emergency source only when
voltage and frequency reach preset pickup points.
both
Usually about ten seconds elapse from dropout of the NR
relay to acceptance by the sensor. This time span occurs
because the engine-driven generator must crank, start, and
run up to nominal pickup points. For this reason, if the
Transfer Switch Test buttonispresseditmustbeheldfor15
seconds. If the emergency source is available immediately,
the sensor may accept it as soon as NR relay drops out.
When the emergency source is accepted by the sensor,
relay ER begins its timing cycle (transfer to emergencydelay). ER relay is provided with an adjustable (0 to 5
minutes) time delay on pickup to delay transfer of the
load to the emergency source. For immediate transfer
press Bypass Time Delay button.
ER relay energizes, the TS coil is energized, the transfer
switch operates, and all switch contacts (mains, controls,
auxiliaries) reverse position. The transfer switch i s now
supplying the load from the emergency source.
The t ransfer switch will remain in the Emergency
position until the normal source is restored. If the
Transfer Switch Test button is used, the transfer switch will
remain on emergency until the retransfer to normal delay
times out.
TRANSFER SWITCH TEST BYPASS TIME DELAY SET ENGINE EXERCISER
Press for 15 Seconds
Press to cancel the
active exercise period
(stops engine now or
after cooldown) See
page 5–1.
lights show the sources available
light for built–in
engine exercise timer
· blinks rapidly when
button is held 5 sec.
while being set
· blinks slowly when
button is released (set)
and during 20 min.
exercise period.
· stays on after engine
stops (exerciser is
Press until light FLASHES
Hold 5 sec
20 min. engine exercise
period immediately (engine
starts) and weekly thereafter.
.toset
enabled for weekly
operation)
Seepage5–1
for complete
instructions
Figure 2–1. Membrane controls and indicator lights.
Retransfer to Normal
The sequence for load retransfer to the normal source
automatically begins when the voltage sensor detects
restoration of the normal source. The voltage level must
rise above the preset pickup point on all phases before
the sensor will accept the normal source.
Whenthenormalsourceisacceptedbythesensor,relay
SE begins its timing cycle (adjustable 1 sec. to 30 min.,
retransfer to normal delay). For immediate retransfer
press Bypass Time Delay button. SE relay is provided with
a time delay on pickup to prevent immediate load
retransfer to the normal source. The delay insures that
the normal source has stabilized before reconnection of
vital loads. If the normal source voltage falls below the
present dropout point before the time delay expires, the
timing cycle is reset to zero. If the emergency source fails
for more than 4 seconds during the t iming cycle, ER relay
drops out and the load is immediately retransferred to
the normal source, if that source is acceptable.
SE relay energizes and ER relay is droppe d out. The TS
coil is energized, the transfer switch operates, and all
switch contacts (mains, controls, auxiliaries) reverse
position. The transfer switch is now supplying the load
from the normal source a gai n.
Upon retransfer to the normalsource, NR relay begins its
timing cycle (unloaded running delay [engine cooldown] ).
NRrelay is provided witha 5 minute time delay on pickup
to keep the engine running for a cool-down period.
NR relay energizes after the time delay and signals the
engine-driven generator to shut down. All circuits are
reset for any future normal source failure.
Activation of standard control features shown in Section 5
will alter the sequence of operation and introduce
additional time delays during transfer operations.
2--1
Page 10
SECTION 3TESTING & SERVICE
PREVENTIVE MAINTENANCE
Reasonable care in preventive maintenance will insure
high reliability and long life for the automatic transfer
switch.
Operate the switch at least once a month.Performthis
four step Electrical Operation Test. This i s a test with
load transfer.
TRANSFER SWITCH TEST BYPASS TIME DELAY SET ENGINE EXERCISER
Press for 15 Seconds
Transfer Switch Test
1. Press and hold the door-mounted TRANSFER
SWITCH TEST button until the engine starts a nd
runs. This should happen within 15 seconds.
2. The transfer switch will operate to the Emergency
position. If the Transfer To Emergency D elay is
used, the transfer w ill occur after a time delay
(up to 5 minutes). For immediate transfer press
BYPASS TIME DELAY button.
3. The Transfer Switch will operate back to the
Normal position after the Retr ansfer To NormalDelay (up t o 30 minutes).For immediate
retransfer press BYPASS TIME DELAY button.
4. Unloaded Running (Engine Cooldown) Delay
allows engine to run unloaded for 5 minutes.
Clean and inspect the switch once a year. De-energize all
sources, then brush and vacuum away any excessive dust
accumulation. Remove the transfer switch barriers and
check contact condition. Replace contacts when pitted or
worn excessively. Reinstall the barriers carefully.
Maintain transfer switch lubrication. The transfer switch
has been properly lubricated, and under normal operating conditions no further lubricating is required. Renew
factory lubrication if the switchis subjectedto severe dust
or abnormal operating conditions.Relubricate the
operator if TS coil is replaced. Order lubrication
625550–001 (Castrol EndurexR 4000 lubricant).
Replacement parts. Replacement parts are available in
kit form. When ordering parts provide the Serial No. and
Catalog No. from the transfer switchnameplate. Contact
your local ASCO Power T echnologies sales office or ASI.
In the United States call 1–800–800–ASCO (2726), or in
Canada call 1–888–234–ASCO (2726).
Press until light FLASHES
DISCONNECTING THE CONTROLLER
The harness disconnect plugs are furnished for repair
purposes only and should not have to be unplugged. If the
controller must be isolated, follow these steps carefully.
Disconnecting the Plugs
!
Do not unplug the controller until step
1a. or 1b. below is completed.
1. Observe the position of the transfer switch.
a. If the transfer switch is in the Normal position, place
standby engine starting c o ntr o l in the off position.
Then open the emergency source circuit breaker.
b. If the transfer switch i s in the Emergency positi on,
open the normal source circuit breaker. Place t he
engine starting control in the test or run position.
2. Separate the quick disconnect plugs by squeezing the
latches. Do not pull on the harness wires.
3. Label, remove, and tape the signal wires connected
to the engine start terminals on the transfer switch:
TB1 and TB3, or TB1 and TB2.
Reconnecting the Plugs
!
Do not reconnect the controller until step
1a. or 1b. and 2 below are completed.
1. Observe the position of the transfer switch.
a. If the transfer switch is in the Normal position, be
sure that the standby engine starting control is still
in the off position. The emergency source circuit
breaker still should be open.
b. If the transfer switch i s in the Emergency positi on,
normal source circuit breaker still should be open.
2. Reconnect the signal wires connected to the
appropriate engine start terminals on the transfer
switch. See Section 1, Engine Starting Contacts.
3. The harness plugs and sockets are keyed. Carefully
align the plugs with the sockets and press straight in
until both latches click.
4. Restore the opposite source as follows:
a. If the transfer switch is in the Normal position,
place the standby engine starting control in the
automatic position. Then close the emergency
source circuit breaker.
b. If the transfer switch is in the Emergency position,
close the normal source circuit breaker. The load will
be automatically retransferred to the normal source
after the Retransf e r to Normal Delay. For immediate
retransfer, press BYPASS TIME DELAY button.
Place the engine starting control in the autom a ti c
position.
3--1
Page 11
TESTING & SERVICE
PROBLEM
(continued)
MANUAL LOAD TRANSFER
This procedure will manually transfer the load if the
controller is disconnected.
!
Do not manually operate the transfer switch
until both power sources are disconnected:
open both circuit breakers.
TROUBLE-SHOOTING
Note the control features that are activated or furnished
on the switch and review their operation.Refer to Section5, Control Features.
Table 3-1. Trouble-Shooting Checks.
1OPERATION2 GEN-SET3VOLTAGE
Gen-Set does not start when
the TRANSFER SWITCH TEST
button is pressed and held for
15 seconds or when the
normal source fails.
T ransfer switch does not
transfer the load to
emergency source after the
gen-set starts.
T ransfer switch does not
transfer the load to normal
source when normal returns
or when TRANSFER SWITCHTEST button is released.
Gen-Set does not stop after
load retransfer to the normal
source.
Hold the TRANSFER SWITCHTEST button 15 sec. or the
outage must be long enough
to allow for the 1 or 3 sec.
Momentary Normal Source
Outage Delay plus engine
cranking and starting time.
Wait for Transfer to Emergen-cy Delay (0 to 5 min.) to time
out. For immediate transfer,
press the BYPASS TIMEDELAY button. If Motor Load
Transfer is active, wait for inphase condition (see below).
Wait for Retransfer to NormalDelay (1 sec. to 30 min.) to
time out. For immediate re–
transfer, press BYPASS TIMEDELAY button. If Motor Load
Transfer is active, wait for inphase condition (see below).
Wait for the 5 minute
Unloaded Running Delay to
time out.
1. Open normal and emergency source circuit breakers.
2. Use the maintenance handle to manually operate
transfer switch to the opposite source. See page 1–3,
Manual Operation Test .
3. If the transfer switch is in the Emergency position
manually start the engine generator and then close
the emergency source circuit breaker.
!
Proceed with care!
The automatic transfer switch is energized.
CHECK IN NUMERICAL SEQUENCE
Starting control must be in
automatic position. Batteries
must be charged and
connected. Check wiring to
engine starting contacts.
Generator output circuit
breaker must be closed.
Generator frequency must be
at least 57 Hz.
—
Starting control must be in
automatic position.
Voltmeter should read at
least 90% of nominal phase to
phase voltage between
transfer switch terminals EA
and EC (or EL1 and EL2 for 2
pole switches). *
* These are factory settings.
Voltmeter should read at least
90% of nominal phase to
phase voltage between
transfer switch terminals NB
and NC, NC and NA, and NA
and NB (or NL1 and NL2 for 2
pole switches).
—
—
Trouble-Shooting the Motor Load Transfer Feature (refer to page 5–3)
3. Press and hold
The load should transfer to emergency source when
Use extreme caution when using a meter
to measure voltages in the following
steps. Do not touch power terminals;
shock, burns, or death could result !
meter needle is near 0 volts. If transfer does not
occur, Motor Load Transfer feature is not operating.
4. Release the Tra n s fe r S w it c h Te s t button. The load
should retransfer back to the normal source after the
1. Connect a voltmeter (set for t wice system
phase–to–phase volt age) between Transfer Switch
terminals NA and EA.
2. Manually start generator. Voltmeter needle should
sweep back and forth at a regular rate between 0 and
about twice system voltage.
Retransfer to Normal Delay,ifused. Theretransfer
should occur when the needle is near 0 volts. If
retransfer does not occur after the time delay, the
Motor L oad Tra nsfer feature is not operating.
5. For immediate retransfer, press the BYPASS TIME
DELAY button. Then disconnect the voltmeter.
If the problem is isolated to circuits on the controlle r or the transfer switch, c all your local ASCO Power Technologie s
sales office or ASI. In the United States, call 1–800–800–2726. In Canada, c all 1–888–234–2726. Furnish the Serial No.,
Bill of Material (BOM) No., & Catalog No. from transfer switch nameplate.
3--2
TRANSFERSWITCH TEST button.
Page 12
SECTION 4ADJUSTMENTS
y
OverrideMomentary
—
TIMER
0minute
s
0to
5
—
—
TIMER
30minutes
1secondto
—
—
S1DIP
EmergencySource
qy60/50
V
/
V
LOW
/
Time Delay Adjustment
Standard time delays are set to customer specifications
(if none specified, standard factory settings are used).
Table4-1.TimeDelaySettings
DESCRIPTIONLABELS
Override Momentar
Normal Source Outages
T ransfer to Emergency
Override Momentary
Emergency S. Outages
Retransfer to Normal
Unloaded Running
(Engine Cooldown)
FACTORY
SETTING
TD ES3seconds
TIMER0 minutes0to5
N/E
—4secondsnon-adjustable———
TIMER30 minutes1secondto
E/N
—5 minutesnon-adjustable———
(full ccw)
(full cw)
ADJUSTMENT
RANGE
1secondActuator 1 on
3secondsActuator 1 off
minutes
30 minutes
Sensor Adjustments
Voltage and frequency sensor pickup and dropout points
are set to customer specifications (if none specified,
standard factory settings are used). To change a setting,
follow procedure on page 4–2. Use Tables 4-2 and 4–3 for
settings and corresponding DIP switch actuators.
To change a setting, follow procedure on pa ge 4-2. Use
Table 4-1 as a guide to time delay values and their corresponding adjustment DIP switch or potentiometer.
S3 DIP
SWITCH
1
1
!
ADJUSTMENT
POTENTIOMETER
P2
P1
Any change in these settings may affect the
normal operation of the automatic transfer
switch. This changecould allow the load circuits
to remain connected to a low voltage source.
Table 4-2. Voltage and Frequency Settings. (Shaded DIP switches are standard factory settings).
DESCRIPTIONLABELSSETTING
PU/NPickup90 %
Normal Source Voltage
DO/NDropout
EmergencySource
Voltage
Emergency Source
Frequency
oltage Phases3 4 ,143 4/1 43 4
––Pickup90 %non-adjustable
––Dropout75 %non-adjustable
––Pickup95 %non-adjustable
––Dropout85 %non-adjustable
60/50
Hz
60/50 Hz60 Hz
%ofnominal
FACT. S ETADJ RANGE
95 % *Actuator 3 off
90 %Actuator 3 on
90 % *
85 %
85 %
80 %
70 %
60 HzActuator 4 off
50 HzActuator 4 on
3phaseActuator 6 off
1phaseActuator 6 on
Actuator 1 off
Actuator 2 off
Actuator 1 on
Actuator 2 off
Actuator 1 off
Actuator 2 on
Actuator 1 on
Actuator 2 on
––
––
S1 DIP
SWITCH
* If dropout voltage is set to 90%, the pickup voltage must be set to 95%.
Table 4-3. Transformer Voltage Adjust.
(Low setting shifts all voltage settings down 4.2%; for example, 240 V to 230 V, or 480 V to 460 V)
1. Prevent the transfer switchfrom operating by disconnecting one source first, then the other, as follows:
a.If the transfer switch is in the Normal position,
open the emergency source circuit breaker. Turn
the engine starting control to off. Then open the
normal source circuit breaker.
b.If the transfer switch is in the Emergency
position, open the normal source circui t breaker.
Turn engine starting control to test or run.Then
open the emergency source circuit breaker.
2. Disconnect both harness plugs from controller by
squeezing the latches. Do not pull on the wires.
3. Remove cover from the controller by releasing latch
on right side with your thumb. See Figure 4-1.
4. Locate the appropriate adjustmentpotentiometer or
DIP switch for the setting that you want to change.
Refer to Table 4-1 and Table 4–2 on page 4-1 and
Figure 4-2, Figure 4–3, Figure 4–4 on page 4–2.
5. Use a small screwdriver to turn the potentiometer
clockwise to increase the time delay or counterclockwise to decrease it. See Figure 4-3.
6. Use a ball-point pen (or similar pointed tool)to slide
the switch actuators left or right so they match the i llustration next to the setting (left = off, right = on).
Recheck the setting. See Fi gure 4-4.
cover
hook on
left side
Figure 4-1. Controller cover latch.
harness
plugs
S3 DIP
switch
S1 DIP
switch
S2 DIP
switch
Figure 4-2. Location of potentiometers,
DIP switches, battery, and battery jumper.
thumb
latch
J5
retransfer
to normal
time delay
transfer to
emergency
time delay
9volt
alkaline
battery
battery
on/off
jumper
P1
P2
7. Install the cover on the controller by hooking it on
the left side and latching the right side.
8. Reconnect both harness plugs to the controller by
aligning and pressing straight in until lat ches click.
!
Close the enclosure door.
9. Close the enclosure door, then restore both sources:
a.If the transfer switch is in the Normal position
first close the normal source circuit breaker,
then close the emergency source circuit breaker.
b.If the transfer switch is in the Emergency
position, close the normalsource circuit breaker.
The load will be automatically retransferred to
the normal source. Then close the emergency
source circuit breaker.
10. Turn the engine starting control to automatic.
clockwise to
increase
P1 or P2
potentiometer
counterclockwise
to decrease
Figure 4-3. Changing time delay potentiometers.
DIP
switches
SW1
SW2
SW3
actuator
(8 on each DIP switch)
onoff
Figure 4-4. Setting DIP switch actuators.
4--2
Page 14
SECTION 5 CONTROL FEATURES – ENGINE EXERCISERS
These timers periodically exercise the emergency engine-generator plant. They can be set to exercise with or without
loadtransfer, or they can be completely disabled. The engine-generatorshould be exercised under loadonce a week fora
minimum time period of 20 minutes, or follow the recommendations of the engine-generator set manufacturer. Refer to
page 4–2 for location of DIP switches, battery (provided), and jumper block in the controller.
BUILT–IN ENGINE EXERCISER
The engine exerciser included in ASCO Series 300
Automatic Transfer Switches provides a once a week
20–minute exercise period. It occurs immediately
the SET ENGINE EXERCISER push button is pressed
(and held
for at least 5 seconds), andthen at the same time
weekly thereafter. A 9 volt alkaline battery (DuracellR
MN1604, EverreadyR 522, or PanasonicR 6AM6) is
furnished and installed in the controller to maintain the
setting. The battery jumper block must be shifted to
ON position
. See Figure 4–2 on page 4–2.
Fill in day and t ime set. Week Day ______ Time _______.
Press to cancel an
active exercise period
(stops generator).
If Exercise with Load is set,
retransfers load to Normal,
then stops generator after
5 min. cooldown.
Figure 5-1. Operator panel pushbuttons and light.
when
the
FUNCTION
Std. Timer
Enabled
Std. Timer
Disabled
Exercise
without
Load
Exercise
with Load
Shaded DIP switches are standard factory settings.
Press until light FLASHES
DIP Switch Settings
S1 DIP
SWITCH
Actuator
7on
Actuator
7off
Actuator
8off
Actuator
8on
7
7
8
8
status light
Press and hold for 5 sec
light blinks rapidly to set exercise period
immediately and every week hereafter
(generator starts).
If Exerciser with Load is set,
transfers load to Emergency.
S2 DIP
SWITCH
Actuator
5on
Actuator
5on
. or until status
5
5
Select below either Exercise without Load or Exercise with Load accordingto the setting of DIP switch S1, actuator 8. The
load transfers from the Normal source to Emergency source (generator) and back again if Exercise with Load is selected.
Exercise without Load, DIP Switch S1, Actuator 8 off
8
How to Set Built–In Timer
StepFunctionExplanation
Push ButtonStatus Light
SET ENGINE
1
EXERCISER
hold
5sec.
2release
press BYPASS
3
TIME DELAY
blinks rapidly
FfFfFf
blinks slowly
FffFff
set exercise period
exercise period now activeGenerator starts and runs.
Exercise the generator now and
every week at this time hereafter.
F stays oncancel active exercise periodGenerator stops.
4—F stays ongenerator offExerciser enabled; repeats every 7 days.
Exercise with Load, DIP Switch S1, Actuator 8 on
8
How to Set Built–In Timer
StepFunctionExplanation
Push ButtonStatus Light
SET ENGINE
1
EXERCISER
hold
5sec.
2release
press BYPASS
3
TIME DELAY
blinks rapidly
FfFfFf
blinks slowly
FffFff
blinks slowly
FffFff
set exercise period
exercise period now active
cancel active exercise period
Exercise the generator now and
every week at this time hereafter.
Generator starts and runs;
the load transfers to Emergency.
The load retransfers to Normal; then
generator runs for 5 minute cooldown
( light blinks slowly during cooldown ).
4—F stays ongenerator offExerciser enabled; repeats every 7 days.
NOTE:EverytimeSET ENGINE EXERCISER push button is pressed (held 5 seconds) the exercise period is changed.
5--1
Page 15
2–line
display
3 buttons
CONTROL FEATURES (continued)
Optional Accessory 11BG – SOURCE AVAILABILITY SIGNAL
& PROGRAMMABLE ENGINE EXERCISER MODULE
connections
for source
availability
signal contacts
Figure 5–2. Accessory 11BG module (mounted behind operator interface and connected to the controller)
includes source availability signal contacts and a programmable engine exerciser.
Source Availability Signal Contacts
ThemoduleprovidesoneFormCcontacteachforthe
normal and emergency sources signal the acceptability of
the source as sensed by the controller. The signal contacts
operate in conjunction with the Source Available lights on
the operator interface. Field wiring terminals are
provided as shown in Figure 5–3 and the wiring diagram.
Contact ratings:
2 amps @ 30 Vdc, 0.5 amp. @ 125 Vac resistive
Figure 5–3. Source availability signal contacts.
ProgrammableEngineExerciser
Themoduleincludesaprogrammableengineexerciser
that provides for weekly or biweekly operation. This
optional exercise timer may have to be turned on
(enabled) by setting the S1 DIP switch actuator 7 to off,
and S2 DIP switch actuator 5 to off. A backup battery
in
the controller (see page 4–2 and page 5–3) must be turned
on to maintainthe settingsand to allowprogrammingwith
the normal and emergency power turned off (page 5–1).
Theprogrammableengineexerciserincorporatesa7day
or 14 day time base. Proper controller settings must be
made to determine whether or not the test will be done
with or without load transfer (S1 DIP switch actuator 8).
DIP Switch Settings in the Controller
(see page 4–2)
FUNCTION
Opt. Timer
Enabled
Opt. Timer
Disabled
Exercise
without
Load
Exercise
with
Load
SWITCH
Actuator
7off
Actuator
7off
Actuator
8off
Actuator
8on
S1 DIP
7
7
8
8
S2 DIP
SWITCH
Actuator
5off
Actuator
5on
5
5
Seenextpageforinstructionsonsettingthetimer.
Shaded DIP switches are standard factory settings.
5--2
Page 16
CONTROL FEATURES (continued)
How to Set Optional Programmable Engine Exerciser (part of Acc. 11BG module)
Start Time Display
Hazardous voltage capable of causing shock,
burns, or death is used in this transfer switch.
Deenergize both Normal & Emergency power
sources before programming the exerciser.
Navigating the M enu
Use the UP and DOWN arrow keys to move through the
displays.
Fast/Slow Ad ju st
Daylight Saving
Time Adjust
Date
The Start Time Display shows the engine exerciser start
time. There are four parameters that determine the start
time:
weekly (”Every”) or bi–weekly (”Alt”) operation
day of week (”Sun” through “Sat”)
start hour (0 through 23)
start minutes (0 through 59)
For example, if the user wants the exerciser to run every
other Saturday a t 3 PM, the proper configuration would
be:
“Alt Sat @ 15:00”
NOTE: When choosing bi–weekly operation, the
exerciser will always run on the week designated “(1)” on
thedatedisplay.
Run Time Display
The Run Time Display shows the run time for the engine
exerciser. The default setting from the factory is 30
minutes.
Time
Run TIme
Start TIme
Engine Exerciser
Changing the Parameters
Use the UP and DOWN arrow keys to move though the
displaystotheparametertobechanged.PushtheENTERkey
tostartthe editingprocess.Thefirstparameterwill flash.Use
the UPand DOWNarrow keys to adjust the parameter to the
desiredvalueand presstheENTERkeytosavethevalue.The
next parameter will now flash. Repeat theprocess until each
parameter is properly configured.
Engine Exerciser Display
TheEngineExerciserDisplayshowsthestatusofthe
engine exerciser. When the unit is shipped from the
factory the programmable engine exerciser is “Disabled”
and must be set to “Enabled” by the customer. When the
engine exerciser is running, t his display will count down
the remaining time until the end of the exercise period.
Time Display
The Time Display shows the present system time. The
format is “hours:minutes:seconds”.
NOTE: During total power outages, power to the
accessory is maintained by a battery in the Controller (see
page 4–2). Be sure that the 9–volt alkaline battery is fresh
and enabled (jumper in ON position) so that the time and
date settings are not lost.
Date Display
The Date Display shows the present system date. The
format is “day of week (week) month/day of month/year”.
NOTE: Week is either week 1 or week 2. This is used in
conjunction with the bi–weekly timer.
Daylight Savings Time Adjust Display
This display shows whether the automatic daylight saving
time adjustment is active. The factory default is “NO”. If
enabled,theunitwillautomaticallyadjustfordaylightsaving
timeat 2 AMonthe firstSunday ofApril andthe lastSunday
of October.
Fast / Slow Adjust Display
This display shows the automatic fast/slow adjustment
value.Thefactorydefaultis0.Thisfeaturecanbeusedto
trim a clock that runs fast or slow. For example, if your
clock runs 10 seconds slow per week, change the fast/slow
adjust value to “+10” and the unit will automatically add
10 seconds to the clock every week.
NOTE: Adjustments are made Sunday morning at 2 AM.
If you want your exerciser period to start at 2 AM on
Sunday, you cannot use this feature and the adjustment
must be set to 0.
5--3
Page 17
CONTROL FEATURES (continued)
Programmable Engine Exerciser Settings
Fill in your settings for future reference
Weekly or Bi–weeklyDay of WeekStart TimeRun Time
0–23hour
Every = weekly
Sun through Sat
Alt = bi–weekly
0–23hour
0–59minute
0–59minute
30 minutesisthe
default setting
Date exerciser was set ______________________________________
5--4
Page 18
CONTROL FEATURES (continued)
INPHASE MONITOR
FOR MOTOR LOAD TRANSFER
Inphase monitoring logic controls transfer and retransfer
of motor loads, so that inrush currents do not exceed
normal starting currents. It avoids nuisance tripping of
circuit breakers and mechanical damage to motor
couplings.
The Motor Load Transfer feature is built into the
controller. DIP switch S1 (actuator 5) activates this
feature: right = ON, left = OFF.
FUNCTIONS1 DIP SWITCH
enableActuator 5 on
disableActuator 5 off
Shaded DIP switches are standard factory settings.
Note
If the Motor Load Transfer feature is enabled,
it will be activated following
the Load
Disconnect Feature Delay Before Transfer
delay.
5
5
LOAD DISCONNECT FEATURE
Connect external circuitsto the terminalsindicated on the
Wiring Diagram provided with the ATS.
The double t hrow (Form C ) contact is rated for 28 VDC or
120 VAC (5 amps resistive). The contact operates prior to
a selectable 0, 3, 10, or 20 second delay before transfer of
the Automatic Transfer Switch. The contact resets either
immediately following transfer or after the same
delay as
set for pre–signal before transfer.
Time delay between the load disconnect control signal
and initiation of transfer is set on the controller with DIP
switch S2 (actuators 6, 7, 8) as shown below:
Delay Before Transfer
LD TDBTS2 DIP SWITCH
0 (disable)
3seconds
10 seconds
20 seconds
Actuator 7 on
Actuator 8 on
Actuator 7 on
Actuator 8 off
Actuator 7 off
Actuator 8 on
Actuator 7 off
Actuator 8 off
87
87
87
87
Shaded DIP switches are standard factory settings.
Delay After Transfer*
LD TDATS2 DIP SWITCH
enableActuator 6 on
disableActuator 6 off
6
6
*Enabling the Delay After Transfer will cause the control
signal to reset after the same delay
as set for the Delay
Before Transfer.
REMOTE CONTROL FEATURES
These remote control features require a customer–supplied normally closed contact suitable for a 5 V dc low energy
circuit. Refer to the Wiring Diagram provided with the ATS. Activate appropriate DIP switch S2 actuators below.
Remote Test (terminals CP6–7)
RTSWS2 DIP SWITCH
disableActuator 3 on
enableActuator 3 off
3
3
Remote Transfer to Emergency (CP8–9)
RT /ES2 DIP SWITCH
disableActuator 2 on
enableActuator 2 off
2
2
Bypass Transfer Time Delay (CP12–13)
TD E/N BYP.S2 DIP SWITCH
disableActuator 1 on
enableActuator 1 off
1
1
Inhibit Transfer to Emergency (CP10–11)
N/E INHIB.S2 DIP SWITCH
disableActuator 4 on
enableActuator 4 off
5--5
4
4
Page 19
CONTROL FEATURES (continued)
OPTIONAL STRIP HEATER (Accessory 44)
Accessory 44 Strip Heater is designed to keep ambient
temperatures within the Automatic Transfer Switch
enclosure at acceptable levels. This accessory consists of a
mounting bracket with strip heater, thermostat, and
terminal block. A transformer with fuses is included when
the power for the assembly is derive d from voltages above
120 V ac. The 120 V ac customer powered assembly does
not include a transformer. This optional accessory is
available factory installed or in kit form.
Turn the thermostat’s dial to required setting as shown.
adjustment, 4–1
gen–set cooldown, 4–1
how to change, 4–2
override momentary outages, 4–1
settings, 4–1
transfer to emergency, 4–1
transfer to normal, 4–1
timer (plant exerciser), how t o set,
5–1, 5–2, 5–3, 5–4
transfer switch test, 1–5, 3–1
trouble–shooting, 3–2
V
voltage, phase, 4–1
voltage, pickup and dropout settings,
4–1
Printed in USAASCO Power Technologies, L.P. 2004
E
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.