Winco ASCO-300-D User Manual

Operator’s
Manual
D desi gn , 30 through 230 amp. sizes
DANGER is used in this manual to warn of high
voltages capable of causing shock, burns, or death.
!
WARNINGisusedinthismanualto
warn of possible personal injury.
!
Series 300
Refer to the outline and wiring drawings provided with your ASCO Series 300 ATS for all installation details.
ASCO Series 300 Automatic Transfer Switches (ATSs) are Listed under Underwriters Laboratories UL 1008 Standard for Safety for Automatic Transfer Switches. ASCO Series 300s are also Listed under CSA C22.2 No. 178 Standard for Automatic Transfer Switches. All control features are UL Component Recog nized, which assures that ASCO automatic transfer switches meet OSHA Safety Requ irem ents and will be acceptable to electrical inspectors.
CAUTIONisusedinthismanualtowarn
of possible equipment damage.
An experienced licensed electrician must install the ATS.
ASCO Series 300 Automatic Transfer Switches are suitable for emergency and standby system applications. They meet emergency system rating requirements as defined in National Electrical Code (NEC) Article 700 and UL 1008. Also, they are suitable for the requirements of NEC Article 517 – Health Care Facilities, NEC Article 701 – L egally Required Standby Systems, NEC Article 702 – Optional Standby Systems, NFPA 99 Health Care Facilities, and NFPA 110 Emergency and Standby Power Systems.
Rating Label
Each automatic trans fer switch con tains a rating label to define the loads and fault circuit withstand / closing ratings. Refer to the label on the transfer switch for specific values.
!
Do not exceed the values on the rating label.
Exceeding the rating can cause personal injury
or serious equipment damage.
TABLE OF CONTENTS
section
INSTALLATION 1..........................
SEQUENCE OF OPERATION 2.............
TESTING & SERVICE 3....................
ADJUSTMENTS 4.........................
CONTROL FEATURES 5...................
30–200 amp. sizes
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA 1 800 937–2726 (ASCO), for service call 1 800 800–2726 (ASCO) www.asco.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3 telephone 519 758–8450, fax 519 758–0876, for service call 1 888 234–2726 (ASCO) www.asco.ca
INDEX back cover.........................
381333–228 D
Nameplate
The Transfer Switch nameplate includes data for each specific ASCO Series 300 ATS. Use the ATS only within the limits shown on this nameplate.
D 300 B 3 200 N 1 C
Catalog Number Identification
A typical Catalog Number is shown below with its elements explained. The example is for a Series 300 ATS with switched neutral, 3 pole, 200 amp, 480 V, in a Type 1 enclosure:
Neutral
B –switched C – overlapping
blank – solid
load power connections
emergency power connections
Phase Poles
2 –singleØ 3 –threeØ
terminals for switch
Amperes Voltage Controller Enclosure
30
70
104
150
200 *
* 200 amp. limited
to 480 volts
position contacts
A 115
B 120 C 208
D 220 E 230
F 240
H 380 J 400
K 415
L 440
M 460 N 480
P 550
Q 575
R 600
membrane
controls
1 –standard
1X –if
accessories
ordered
C –type1
F –type3R
G –type4
L –type12
blank – open type
Controller
Transfer
Switch
maintenance
handle
(see WARNING
under Manual
Operation)
terminals for
engine start
contacts
normal power connections
cable spacers (see INSTALLATION)
200 amp. size in typical enclosure with location of customer connections
Catalog Number Identification
A typical Catalog Number is shown below with its elements explained. The example is for a Series 300 ATS with switched neutral, 3 pole, 230 amp, 480 V, in a Type 1 enclosure:
D 300 B 3 230 N 1 C
Neutral
B –switched C – overlapping
blank – solid
load power connections
emergency power connections
Phase Poles
2 –singleØ 3 –threeØ
Amperes Voltage Controller Enclosure
230 **
** 230 amp. limited
to 480 volts
terminals for switch
position contacts
A 115
B 120 C 208
D 220 E 230
F 240
H 380
J 400
K 415
L 440
M 460 N 480
1 –standard
1X –if
accessories
ordered
membrane
controls
C –type1
F –type3R
G –type4
L –type12
blank – open type
Controller
Transfer Switch
maintenance handle
(see WARNING under
Manual Operation)
terminals for
engine start contacts
normal power connections
cable spacers (see INSTALLATION)
230 amp. size in typical enclosure with location of customer connections
SECTION 1 INSTALLATION
Series 300 AutomaticTransfer Switchesare factory wired and tested. Installation requires skid removal then securing the enclosure to the supporting foundation.
Mounting
Refer to the applicable enclosure outline drawing fur­nished with this switch and mount the Series 300 according to details and instructions shown on diagram.
!
Protect the automatic transfer switch from
construction grit and metal chips to prevent
malfunction or shortened life of the ATS.
Mount the ASCO ATS vertically to a rigid supporting structure. Level all mounting points by using flat washers behind the holes to avoid distortion of the switch.
Connecting Power Conductors
After the powercables have been tested, connect them to the appropriate terminal lugs on the transfer switch as shown on the wiring diagram provided wit h this Series
300. M ake sure the lugs provided are suitable for use with the cables being installed. Standard terminal lugs are solderless screw type and will accept the wire sizes listed on the drawings provided with the Series 300. Be careful when stripping insulation from the cables; avoi d nicking or ringing the conductor. Remove surface oxides from cables by cleaning with a wire brush. When aluminum cable is used, apply joint compound to conductors. Tighten cable lugs to the torque specified on rating label.
Three cable spacers are included with 150, 200, and 230 ampere transfer switches. When installing power cables, run the cables through the cable spacers as shown in Figure 1–1. Position cable spacers within 1½ inches from lugs.
Line Connections
Refer to the Wiring Diagram provided with your Series 300 ATS. All wiring must be made in accordance with the National Electrical Code and local codes.
De–energize the conductors before making any line or auxiliary circuitry connections. Be sure that Normal and Emergency line connections are in proper phase rotation. Place engine gen­erator starting control in the OFF position. Make sure engine generator is not in operation.
It is unnecessary to remove pole covers from the transfer switch. If you do remove them, reinstall them carefully.
Testing Power Conductors
Do not connect the power conductors to the ASCO Series 300 transfer switch until they are tested. Installing power cables in conduit, cable troughs and ceiling-sus­pended hangers often requires considerable force. The pulling of cables can damage insulation and stretch or break the conductor’s strands. For this reason, after the cables are pulled into position, and before connected, they should be tested to verify that they are not defective or have been damaged during installation.
they are
!
The cable spacers must be located as shown
for 150, 200, and 230 ampere transfer switches.
cable spacers
1 ½ inch approximate
cable spacer
Figure 1–1. Cable spacers for 150, 200, & 230 amp.
transfer switches.
1--1
INSTALLATION (continued)
Engine Starting Contacts
Controller Ground
Customer connections for engine control contact connections are located on the transfer switch. Refer to wiring diagram provided with the Series 300 A TS and connect the engine start wires to the appropriate terminals . See Figure 1–2 and Table A.
Table A. Engine start connections.
When normal source
fails
Terminals on transfer
switch
contact closes TB14 and TB15 contact opens TB14 and TB16
ENGINE STARTING CONTACTS
( SHOWN DE–ENERGIZED )
TOP
STUD
MIDDLE
STUD
BOTTOM
STUD
14
TS
15
NR
16
NR
TB 14
TB 16
left side
of switch
TB 15
Figure 1–2. Engine starting contact label and
terminals located on the transfer switch.
A grounding wire must be connected to the controller’s lower left mounting stud. Because the controller is mounted on the enclosure door, a conductive strap must be used between the enclosure and the door. This connection provides proper grounding which does not rely upon the door hinges.
Harnesses
The transfer switch is connected to the left side of the controller by a plug–in harness (two plugs).
Auxiliary Circuits
Connect auxiliary circuit wires to appropriate terminals on transfer switch as shown on the wiring diagram provided with this Series 300 Automatic Transfer Switch. Make the necessary auxiliary connections by referring to Section 5, Control Features.
Load Disconnect
Feature
Connections
(see Wiring Diagram
& refer to page 5–5
for DIP switch settings)
Connections to Controller for other Control Features
(located on bottom of Controller)
Programmable
Engine Exerciser
connection,
if provided
(refer to
page 5–2)
Remote Control Features Connections
(refer to the Wiring Diagram &
page 5–5 for DIP switch settings)
Each control contact must be suitable
for a 5 V DC low energy circuit.
for factory
use only
Figure 1–3. Input / output label on the Controller showing possible connections to the lower terminal block.
1--2
INSTALLATION (continued)
Functional Test
The Functional Test consists of three checks: manual operation, voltage checks, and electrical operation.
!
Do these checks in the order presented to
avoid damaging the automatic transfer switch.
Read all instructions on the Wiring Diagram and labels affixed to the automatictransfer switch. Note the control features that are provided and review their operation before proceeding.
1 – Manual Operation Te st
A maintenance handle is provided on the Transfer Switch for maintenance purposes only transfer switch should be checked before it is energized (operated electrically).
!
Do not manually operate the transfer switch
until both power sources are disconnected:
open both circuit breakers.
1. After deenergizing both power sources, open the enclosure door. Locate and the maintenance handle on the left side of the transfer switch frame. See Figure 1–4.
2. Grasp the attached maintenance handle and turn it with thumb and fingers as shown to manually operate it. The maintenance handle turns the opposite direc­tion of the weight. Move it up or down as shown to manually operate the transfer switch. It should operate smoothly without any binding. If it does not, check for shipping damage or construction debris.
3. Return the transfer switch to the Normal position.
Note: If Normal and Emergency connections are
reversed this operation is also reversed.
. Manual operation of the
Position of the transfer switch is indicated here
weight marked N (normal) and E (emergency)
maintenance handle
weight
floating weight
With ALL POWER OFF grasp
maintenance handle and turn it
quickly with your thumb and fingers.
Figure 1–4. Maintenance handle and positions.
Now continue to 2–VoltageCheckson next page.
1--3
Loading...
+ 14 hidden pages