Winco ASCO-300 User Manual

Accessory 11BG
for Series 300
Installation
Accessory 11BG module includes a programmable engine– generator exerciser and power source availabil ity contacts. It can be added to a Series 300 Automatic Transfer Switch (ATS) that has a Group 1 Controller. If an existing engine exerciser (Acc. 11CD) is already installed, it must be disconnected first.
TheAccessory11BGmodulemountsdirectlybehindthe Series 300 ATS opera tor interface on the inside of the enclosure door. The module connects to the Series 300 ATS operator interface board and Group 1 controller.
Kits K629830 & K749999 include the Acc. 11BG module, mounting hardware, and all necessary wiring.
Tools 1/4”, 5/16” nutdrivers, small blade screwdriver required: your Series 300 ATS Operator’s Manual
for setting the DIP switches
ELECTROCUTION – FLASH HAZARD Do not work on the transfer switch until both the utility and generator are off. Turn OFF both circuit breakers.
Automatic Transfer Switches
J1
Figure 1. Accessory 11BG Module in kits.
Module Installation –Figures2&3
1. With all power OFF, open the enclosure door. Locate the operator interface (membrane controls) mounted on the inside of the enclosure door. Use a 5/16” nutdriver to remove (counterclockwise) the four hex nuts from the corners of the operator interface. Do not remove the operator interface board (Figures 2 & 3).
2. Install (clockwise) four standoffs (from the kit) onto the four studs and tighten them with a 1/4” nutdriver.
3. Install the Acc. 11BG module on top of the operator interface so that four standoffs fit through the corner holes. Then install (clockwise)four 6–32 hex nuts (from thekit)tosecuretheassembly.Tightenthenuts.
Figure 2. Series 300 ATS operator Interface board
mounted on the enclosure door (back view).
Step 1
Connecting the Module – Figures 1, 2, 4
1. With all power OFF, locate the two ribbon cables and note direction and orientation of each cable.
2. Unplug the ribbon cable (coming from the Controller) from the operator interface (J3 lower right side) and reconnect it (same orientation) to the Acc. 11BG module (J1 lower right side). See Figures 1, 2, & 4.
3. Connect the new ribbon cable (coming from the Acc. 11BG module upper right side) to the operator interface (J3 lower right side) with the same orientation as the original cable that was moved. See Figures 2 & 4.
4. Strip the insulation from both ends of the #16 gauge white wire (from the kit). Connect this prepared wire between A c c . 11BG module terminal 9 (right side) and the Group 1 Controller terminal 4 (bottom left). Figure 4.
ASCO POWER TECHNOLOGIES L.P. 50 Hanover Road, Florham Park, New Jersey 07932 USA www.asco.com
original mounting of Series 300 ATS
operator interface on enclosure door
stud
Step 2
Step 3
operator interface
board
install Acc. 11BG board
standoff added for Acc. 11BG Module
Figure 3. Module installation hardware.
J3
remove 4 nuts
(with captive
lockwashers)
add 4 standoffs
reinstall
4 nuts
381339–252 B
page 1
2–line display
9
J1
3 buttons
connections for power source availability
J1
signal contacts
wiring
Figure 4. Accessory 11BG module (mounted behind operator interface and connected to the controller)
includes power source availability signal contacts and a programmable engine exerciser.
Power Source Availability Signal Contacts
ThemoduleprovidesoneFormCcontacteachforthe normal and emergency power sources to signal the acceptability of the source as sensed by the controller. The signal contacts operate in conjunction with the Source Available lights on the operator interface. Field wiring terminals are provided as shown in Figure 5 and the wiring diagram.
Contact ratings:
2 amps @ 30 Vdc, 0.5 amp. @ 125 Vac resistive
Figure 5. Power source availability signal contacts.
J3
Programmable Engine–Generator Exerciser
Note: Refer to your Series 300 ATS Operator’s Manual
to set DIP switches S1 & S2 in the Group 1 Controller.
A backup battery (see Operator’s Manual, Sections 4 and 5) must be turned on to maintain the settings and to allow programming with the normal and emergency power sources turned off.
TheAcc.11BGmoduleincludesaprogrammablegenera­tor exerciser that provides for weekly or biweekly opera­tion. The exerciser may have to be turned on (enabled) by setting S1 DIP switch actuator 7 to OFF (left position), and S2 DIP switch actuator 5 to OFF (left position).
The programmable engine–generator exerciser incorpo­rates a 7–day or 14–day time base. Proper Group 1 Controller settings must be made to determine whether or not the test will be done with or without load transfer (S1 DIP switch actuator 8).
Seenextpageforinstructionsonsettingtheexerciser.
381339–252 B
page 2
in the Series 300 ATS Group 1 Controller
ASCO POWER TECHNOLOGIES L.P. 50 Hanover Road, Florham Park, New Jersey 07932 USA www.asco.com
S1 DIP Switch Settings
in Series 300 ATS Group 1 Controller
Programmable
Exerciser
Function
Enabled &
Exercise
without Load
Enabled &
Exercise
with Load
Actuator 7 OFF Actuator 8 OFF
Actuator 7 OFF
Actuator 8 ON
ACTUATORS 7 & 8
OFF ON
7
8
7 8
EXER ACTV
LOAD
EXER ACTV
LOAD
S2 DIP Switch Settings
in Series 300 ATS Group 1 Controller
Programmable
Exerciser
Function
Enabled Actuator 5 OFF
Disabled Actuator 5 ON
Shaded DIP switches are standard factory settings.
ACTUATOR 5
OFF ON
5
5
EXT EXER
EXT EXER
Loading...
+ 2 hidden pages