Wilo-Control IF-Modul LON / IF-Modul Stratos LON
D Einbau- und Betriebsanleitung GB Installation and operating instructions
/ www.wilo.com/automation
2 084 903-Ed.02 / 2011-05 Wilo
nv1
nviRequest SNVT_obj_request
nv2
nvoStatus SNVT_obj_status
nv8
nvoFileDirectory SNVT_address
Mandatory
Configuration
Optional
Node Object
Mandatory
Optional
nciMaxStsSendT scpt22 nciDevMajVer scpt165 nciDevMinVer scpt166
nciLocation scpt17
Sollwertobergrenze (Hersteller- ,
Pumpen- und Regelartspezifisch)
Tatsächlicher Sollwert [%]
STOP
X
100%
Pump Setpoint
nviPumpSetpoint
[%]
Sollwertuntergrenze (Hersteller- ,
Pumpen- und Regelartspezifisch)
X = ( Sollwertuntergrenze / Sollwertobergrenze ) * 100%
Fig.1a:
Fig.2:
nv1
nviPumpSetpoint SNVT_switch
nv2
nviPumpOpMode SNVT_hvac_mode
nv3
nvoPumpCapacity SNVT_lev_percent
nv4
nvoEffOpMode SNVT_hvac_mode
nv5
nvoControlMode SNVT_dev_c_mode
nv13
nvoPumpStatus SNVT_dev_status
nv6
nviPumpOvdStop SNVT_switch
nv7
nviOvdSpeed SNVT_lev_percent
nv8
nviOvdPress SNVT_press
nv10
nviRemotePress SNVT_press
nv12
nviRemoteTemp SNVT_temp_p
nv14
nvoPressure SNVT_press
nv15
nvoFlow SNVT_flow_p
nv16
nvoSpeed SNVT_rpm
nv17
nvoPumpOverride SNVT_switch
nv18
nvoRuntime SNVT_time_hour
nv19
nvoPumpFault SNVT_dev_fault
nv20
nvoMaintenance SNVT_dev_maint
nv21
nvoFluidTemp SNVT_temp_p
nv22
nvoPower SNVT_power
nv23
nvoPowerKilo SNVT_power_kilo
nv24
nvoEnergyConsum SNVT_elec_kwh
Mandatory
Optional
Configuration
Pump Controller Object
Mandatory
Optiona l
nciRcvHrtBt scpt48
nciSndHrtBt scpt49
nciMinOutTm scpt52
nciControlMode scpt238 nciRemMinPress scpt239 nciRemMaxPress scpt240 nciRemMinTemp scpt243 nciRemMaxTemp scpt244
nciObjMajVer scpt167 nciObjMinVer scpt168
nroPumpChar scpt233
nciPressTemp ucpt nciSetpPreset scpt213
nv38
nvoCurrentErrorM SNVT_count
nv39
nvoCurrentErrorS SNVT_count
nv40
nvoPumpStatusM SNVT_dev_status
nv41
nvoPumpStatusS SNVT_dev_status
nv42
nvoPumpType SNVT_count
Fig.1b: Fig.3a:
I
F
-M
o
d
ul
n
u
n
g
A
t
t
e
n
t
ion
M
ai
n
s
V
ol
tage
L N SSM
e
g
g n
!
a
lt
o V
Mains
on
ti
en
tt
A
l
u
d
o
M
­F
I u n
n a
zsp
t
e
N
n
o
ti
p
O
g
n
tu
h
c
A
on
V
ng
i
0
t
u t
3 2
h
en t
c
t
A
1 -
A
Fig.3b:
Fig.3c:
Fig.4a:
~15 mm
~15 mm
~15 mm
~15 mm
Fig.4b:
Fig.4c:
~15 mm
~15 mm
Fig.5a: IF-Modul Stratos LON
Fig.5b: IF-Modul LON
D Einbau- und Betriebsanleitung 2 GB Installation and operating instructions 39
Deutsch
Einbau- und Betriebsanleitung
1 Allgemeines
1.1 Über dieses Dokument
Die Sprache der Originalbetriebsanleitung ist Deutsch. Alle weiteren Sprachen dieser Anleitung sind eine Übersetzung der Originalbetriebsanleitung. Die Einbau- und Betriebsanleitung ist Bestandteil des Produktes. Sie ist jeder­zeit in Produktnähe bereitzustellen. Das genaue Beachten dieser Anweisung ist Voraussetzung für den bestimmungsgemäßen Gebrauch und die richtige Bedie­nung des Produktes. Die Einbau- und Betriebsanleitung entspricht der Ausführung des Produktes und dem Stand der zugrunde gelegten sicherheitstechn ischen Vorschriften und Normen bei Drucklegung.
Diese Einbau- und Betriebsanleitung ist als Ergänzung zur Einbau- und Betriebsanleitung der an den LON-Bus angeschlossenen Pumpen zu betrach­ten.
2Sicherheit
Diese Betriebsanleitung enthält grundlegende Hinweise, die bei Montage, Betrieb und Wartung zu beachten sind. Daher ist diese Betriebsanleitung unbe­dingt vor Montage und Inbetriebnahme vom Monteur sowie dem zuständigen Fachpersonal/Betreiber zu lesen. Es sind nicht nur die unter diesem Hauptpunkt Sicherheit aufgeführten allge­meinen Sicherheitshinweise zu beachten, sonde rn auch die unter den folgenden Hauptpunkten mit Gefahrensymbolen eingefügten, speziellen Sicherheitshin­weise.
2.1 Kennzeichnung von Hinweisen in der Betriebsanleitung
Symbole: Allgemeines Gefahrensymbol
Gefahr durch elektrische Spannung
HINWEIS: ...
Signalwörter: GEFAHR! Akut gefährliche Situation. Nichtbeachtung führt zu Tod oder schwersten Verletzungen.
Einbau- und Betriebsanleitung Wilo-Control IF-Modul LON / IF-Modul Stratos LON 2
Deutsch
WARNUNG! Der Benutzer kann (schwere) Verletzungen erleiden. 'Warnung' beinhaltet, dass (schwere) Personenschäden wahrscheinlich sind, wenn der Hinweis missachtet wird.
VORSICHT! Es besteht die Gefahr, die Pumpe/Anlage zu beschädigen. 'Vorsicht' bezieht sich auf mögliche Produktschäden durch Missachten des Hinweises.
HINWEIS: Ein nützlicher Hinweis zur Handhabung des Produktes. Er macht auch auf mög­liche Schwierigkeiten aufmerksam.
Direkt am Produkt angebrachte Hinweise wie z.B.
•Drehrichtungspfeil,
• Kennzeichen für Anschlüsse,
• Typenschild,
•Warnaufkleber, müssen unbedingt beachtet und in vollständig lesbarem Zustand gehalten wer­den.
2.2 Personalqualifikation
Das Personal für die Montage, Bedienung und Wartung muss die entsprechende Qualifikation für diese Arbeiten aufweisen. Verantwortungsbereich, Zuständig­keit und Überwachung des Personals sind durch den Betreiber sicherzustellen. Liegen dem Personal nicht die notwendigen Kenntnisse vor, so ist dieses zu schulen und zu unterweisen. Falls erforderlich kann dies im Auftrag des Betrei­bers durch den Hersteller des Produktes erfolgen.
2.3 Gefahren bei Nichtbeachtung der Sicherheitshinweise
Die Nichtbeachtung der Sicherheitshinweise kann eine Gefährdung für Perso­nen, die Umwelt und Produkt/Anlage zur Folge haben. Die Nichtbeachtung der Sicherheitshinweise führt zum Verlust jeglicher Schadenersatzansprüche. Die Nichtbeachtung der Sicherheitshinweise kann zum Ve rlust jeglicher Schadener­satzansprüche führen. Im Einzelnen kann Nichtbeachtung beispielsw eise folgende Gefährdungen nach sich ziehen:
• Gefährdungen von Personen durch elektrische, mechanische und bakteriologi­sche Einwirkungen,
• Gefährdung der Umwelt durch Leckage von gefährlichen Stoffen,
• Sachschäden,
• Versagen wichtiger Funktionen des Produktes/der Anlage,
• Versagen vorgeschriebener Wartungs- und Reparaturverfahren.
3 WILO SE 05/2011
2.4 Sicherheitsbewusstes Arbeiten
Die in dieser Betriebsanleitung aufgeführten Sicherheitshinweise, die bes te­henden nationalen Vorschriften zur Unfallverhütung sowie eventuelle interne Arbeits-, Betriebs- und Sicherheitsvorschriften des Betreibers sind zu beach­ten.
2.5 Sicherheitshinweise für den Betreiber
Dieses Gerät ist nicht dafür bestimmt, durch Personen (einschließlich Kinder) mit eingeschränkten physischen, sensorischen oder geistigen Fähigkeiten oder mangels Erfahrung und/oder mangels Wissen benutzt zu werden, es sei denn, sie werden durch eine für ihre Sicherheit zuständige Person beaufsichtigt oder erhielten von ihr Anweisungen, wie das Gerät zu benutzen ist. Kinder müssen beaufsichtigt werden, um sicherzustellen, dass sie nicht mit dem Gerät spielen.
• Führen heiße oder kalte Komponenten am Produkt/der Anlage zu Gefahren, müssen diese bauseitig gegen Berührung gesichert sein.
• Berührungsschutz für sich bewegende Komponenten (z.B. Kupplung) darf bei sich im Betrieb befindlichem Produkt nicht entfernt werden.
• Leckagen (z.B. Wellendichtung) gefährlicher Fördermedien (z.B. explosiv, giftig, heiß) müssen so abgeführt werden, dass keine Gefährdung für Personen und die Umwelt entsteht. Nationale gesetzliche Bestimmungen sind einzuhalten.
• Gefährdungen durch elektrische Energie sind auszuschließen. Weisungen loka­ler oder genereller Vorschriften [z.B. IEC, VDE usw.] und der örtlichen Energie­versorgungsunternehmen sind zu beachten.
Deutsch
2.6 Sicherheitshinweise für Inspektions- und Montagearbeiten
Der Betreiber hat dafür zu sorgen, dass alle Montage- und Wartungsarbeiten von autorisiertem und qualifiziertem Fachpersonal ausgeführt werden, das sich durch eingehendes Studium der Betriebsanleitung ausreichend informiert hat. Die Arbeiten an dem Produkt/der Anlage dürfen nur im Stillstand durchgeführt werden. Die in der Einbau- und Betriebsanleitung beschriebene Vorgehens­weise zum Stillsetzen des Produktes/der Anlage muss unbedingt eingehalten werden. Unmittelbar nach Abschluss der Arbeiten müssen alle Sicherheits- und Schutz­einrichtungen wieder angebracht bzw. in Funktion gesetzt werden.
2.7 Eigenmächtiger Umbau und Ersatzteilherstellung
Eigenmächtiger Umbau und Ersatzteilherstellung gefährden die Sicherheit des Produktes/Personals und setzen die vom Hersteller abgegebenen Erklärungen zur Sicherheit außer Kraft. Veränderungen des Produktes sind nur nach Absprache mit dem Hersteller zulässig. Originalersatzteile und vom Hersteller autorisiertes Zubehör dienen der Sicherheit. Die Verwendung anderer Teile hebt die Haftung für die daraus entstehenden Folgen auf.
Einbau- und Betriebsanleitung Wilo-Control IF-Modul LON / IF-Modul Stratos LON 4
Deutsch
2.8 Unzulässige Betriebsweisen
Die Betriebssicherheit des gelieferten Produktes ist nur bei bestimmungsgemä­ßer Verwendung entsprechend Abschnitt 4 der Betriebsanleitung gewährleis­tet. Die im Katalog/ Datenblatt ange gebenen Grenzwerte dürfen auf keinen Fall unter- bzw. überschritten werden.
3 Transport und Zwischenlagerung
Bei Erhalt Produkt sofort auf Transportschäden überprüfen. Bei Festst ellung von Transportschäden sind die notwendigen Schritte innerhalb der entsprechenden Fristen beim Spediteur einzuleiten.
VORSICHT! Beschädigungsgefahr für das IF-Modul! Gefahr der Beschädigung durch unsachgemäße Handhabung bei Transport und Lagerung.
• Die IF-Module sind bei Transport und Zwischenlagerung gegen Feuchtigkeit, Frost und mechanische Beschädigung zu schützen.
• Die IF-Module dürfen keinen Temperaturen außerhalb des Bereiches von
- 10°C bis + 70°C ausgesetzt werden.
4 Bestimmungsgemäße Verwendung
Das IF-Modul LON bzw. Stratos LON dient zum Anschluss von elektronisch geregelten Nassläufer- oder Trockenläuferpumpen an ein LON-Netzwerk. Über den LON-Bus können der Pumpe Sollwerte, Betriebsarten und die Daten exter­ner Sensoren vorgegeben werden und aktuelle Betriebsdaten und Fehlermel­dungen können von der Pumpe übermittelt werden. Gleichzeitig bietet das IF-Modul LON/Stratos LON die Möglichkeit, über eine weitere Schnittstelle DP zwei Pumpen zu einer Doppelpumpe zusammenzu­schalten. Diese Schnittstelle ist separat ausgeführt, es handelt sich nicht um eine auf LON basierende Schnittstelle. Deshalb wird der LON-Bus für die Dop­pelpumpenschnittstelle nicht belastet und die Slave-Pumpe kann mit einem kostengünstigen IF-Modul PLR ausgestattet werden.
5 WILO SE 05/2011
Anschließbare Pumpentypen:
Deutsch
Wilo-IF-Modul Stratos LON für Nassläuferpumpen
•Wilo-Stratos
•Wilo-Stratos-D
•Wilo-Stratos-Z
•Wilo-Stratos-ZD
• weitere: siehe www.wilo.de/automation
Wilo-IF-Modul LON für Trockenläuferpumpen
• Wilo-Stratos GIGA
• Wilo-VeroLine-IP-E/DP-E
• Wilo-VeroTwin-IL-E/DL-E
• Wilo-Economy MHIE
• Wilo-Multivert MVIE (1,1-7,5 kW)
• Wilo-Helix VE
• Wilo-Helix Excel
• weitere: siehe www.wilo.de/automation
Tabelle 4.1
5 Angaben über das Erzeugnis
5.1 Typenschlüssel
Beispiel: Wilo-Control IF-Modul LON
Control Baureihenbezeichnung
Typenbezeichnung: IF-Modul LON
IF-Modul Stratos LON
5.2 Technische Daten
Schnittstelle: TP/FT10 Klemmenquerschnitt: Buskabel: max. Länge Buskabel: • 900 m bei Bustopologie mit max. 3 m langen Stich-
Programm-ID (Software): 9F:FF:CC:51:14:06:04:05 Software-Version:
2,5 mm² paarweise verdrillt, geschirmt
leitungen
• 450 m bei freier Topologie, dabei max. 250 m zwi­schen 2 untereinander kommunizierenden Knoten
3.00 oder höher
Einbau- und Betriebsanleitung Wilo-Control IF-Modul LON / IF-Modul Stratos LON 6
Deutsch
5.3 Standards
Das IF-Modul LON entspricht folgenden Standards:
• LonMark Application Layer Interoperability Guidelines Version 3.4
• LonMark Layers 1-6 Interoperability Guidelines Version 3.4
• LonMark node object 0000_20
• LonMark pump controller object 8120_10
• LonMark Resource Files Version 13.04 Die gesamte Dokumentation ist unter www.wilo.de/automation zu finden.
5.4 Lieferumfang
• IF-Modul LON oder IF-Modul Stratos LON
• Metallische Kabelverschraubung Pg7 (nur IF-Modul Stratos LON)
• Metallische Kabelverschraubung Pg9 (nur IF-Modul Stratos LON)
• Einbau- und Betriebsanleitung
• CD mit ergänzenden Informationen
5.4.1 Auslieferungszustand
Gemäß den LonMark Application Layer Interoperability Guidelines wird das IF­Modul LON im Zustand “Application unconfigured” ausgeliefert. In diesem Zustand kann das IF-Modul LON über den LON-Bus angesprochen werden, aber die Applikation, die normalerweise die Kommunikation mit der Pumpe ausführt, ist noch nicht in Betrieb. Somit ist nach dem Aufstecken des IF-Moduls LON und dem Einschalten der Stromversorgung der Pumpe noch keine Aktivität zu sehen.
6 Beschreibung und Funktion
6.1 Beschreibung der Objekte
Im IF-Modul LON sind 2 Objekte realisiert, das Knoten-Objekt und das Pumpen­Objekt. Das Knoten-Objekt dient zur Steuerung einzelner Objekte innerhalb des Knotens, hier werden auch zentral Fehler signalisiert, die in den einzelnen Objekten auftreten. Fig.1a zeigt das Knoten-Objekt (Node Object) mit den zugehörigen Ne tz we rk ­variablen und Fig.1b zeigt das Pumpen-Objekt (Pump Controller Object) mit den zugehörigen Netzwerkvariablen. HINWEIS:
• Doppelpumpen sind immer mit dem integrierten Doppelpumpenmanagement zu betreiben.
• Bei Doppelpumpen wird das IF-Modul LON an den Master angeschlossen.
• Wird bei Doppelpumpen das integrierte Doppelpumpenmanagement nicht benutzt, so sind die beiden Antriebe wie zwei separate Einzelpumpen zu behan­deln. In diesem Fall sind zwei IF-Module LON erforderlich.
• Steuerfunktionen beziehen sich auf die Doppelpumpe als gesamtes Aggregat.
7 WILO SE 05/2011
6.2 Beschreibung der Netzwerkvariablen
6.2.1 Wertebereiche und Auflösungen der Netzwerkvariablen Eingänge
Data Range and
effective
resolution WILO
.object_id: 0 - 1
.object_request:
RQ_NORMAL
RQ_DISABLED
RQ_ENABLE
RQ_UPDATE_STATUS
RQ_REPORT_MASK
RQ_CLEAR_STATUS
.state: 0 – 1
.value: 0.0 – 100.0%
HVAC_AUTO
HVAC_MRNG_WRMUP
HVAC_PRE_COOL
HVAC_ECONOMY
.state: 0 – 1
.value: 0.0 – 100.0%
0 - 100%
Eff. Resolution: 0.5%
Range depends on
Pumptype.
Eff. Resol.: 0.981kPa
0–3276.6kPa
Eff. Resol.: 0.981kPa
-273.1 – 327.6 °C
Invalid Data
-
Default Value
-
Resolution
-
-
SCPTsetpoint
-
0xFF
(HVAC_NUL)
HVAC_AUTO
-
.state: 0xFF
.state: 0xFF
-
.value: 0xFF
0x7FFF
0x7FFF
0.005 %
0x7FFF
0x7FFF
0.1 kPa
0x7FFF
0x7FFF
0.1 kPa
0x7FFF
0x7FFF
0.01°C
Deutsch
Eff. Resol.: 0.1°C
Data Range
and Units
Receive
Heartbeat
No.
Object
NVT
Mand.
Opt.
Input-
Networkvariable
-
no 1
0
SNVT_obj_request
M
nviRequest
.state: 0 – 1
.value: 0.0
- 100.0%
enum 0 ... 17
no
no
1
2
1
1
SNVT_switch
SNVT_hvac_mode
M
M
nviPumpSetpoint
nviPumpOpMode
(hvac_t)
.state: 0 – 1
.value: 0.0
... +100.0%
-163.84
no
no
6
7
1
1
SNVT_switch
SNVT_lev_percent
O
O
nviPumpOvdStop
nviOvdSpeed
... +163.83 %
-3276.8
... +3276.6 kPa
no 8
1
SNVT_press
O
nviOvdPress
-3276.8
... +3276.6 kPa
-273.17
yes
yes
10
12
1
1
SNVT_press
SNVT_temp_p
O
O
nviRemotePress
nviRemoteTemp
... +327.66 °C
Tabelle 6.2.1
Einbau- und Betriebsanleitung Wilo-Control IF-Modul LON / IF-Modul Stratos LON 8
Deutsch
Send when value
Range and effective
Invalid
Resolution
6.2.2 Wertebereiche und Auflösungen der Netzwerkvariablen Ausgänge
changes more
than
Send upon nviRequest:
resolution WILO
Data
update
invalid_id
invalid_request
disabled
electrical_fault
unable_to_measure
manual_control
-
5 % of nroPump-
Char.pressMax
or 2 % of nroPump-
Char.speedMax resp.,
control mode changes
5 % of
nroPumpChar.pressMax
5 % of
nroPumpChar.flowMax
1 kWh
10 % of max. Power
10 % of max. Power
10 h
2 % of nroPump-
Char.speedMax
5 °C
immediately
/h
3
in_alarm
0 – 100.0%
Res: 0.2%
0x7FFF
0.005 %
Range depends on
Pumptype
0x7FFF
0.1 kPa
Res. :0.981 kPa
Range depends on
Pumptype
Res : 0.1 m
0xFFFF /h
3
0.01 m
/h
3
0 – 65535 kWh
-
1 kWh
Res: 1 kWh
0 – 6553W
-
0.1 W
Res: min. 1 W
0 – 65.5 kW
-
0.1 kW
Res: 0.1 kW
0 – 65535 h
Res: 10 h
-
1 h
0 – 65535 rpm
Res: min.1 rpm
-
1 rpm
-50 °C – 205°C
Res : min. 0.1 °C
DCM_SPEED_CONST
0x7FFF
0xFF
0.01 °C
-
DCM_PRESS_CONST
DCM_PRESS_COMP
DCM_PRESS_AUTO
DCM_NUL
0 – 65535 kWh
0 – 6553.5 W
0 – 6553.5 kW
0 – 65535 h
0 – 65535 rpm
-273.17
– 327.66 °C
ENUM 0 – 29
yes
no 21 1
SNVT_temp_p
O
nvoFluidTemp
(device_c_mode_t)
yes
yes 5 1
SNVT_dev_c_mode
M
nvoControlMode
Data Range
and Units
Min.
Send
Time
Send
Heartbt /
Ack No. Obj
NVT
Mand.
Opt.
Output-
Networkvariable
yes
yes 2 0
SNVT_obj_status
M
nvoStatus
no
no 8 0
SNVT_address
O
nnvoFileDirectory
-163.84
– 163.83 %
yes
yes 3 1
SNVT_lev_percent
M
nvoPumpCapacity
-3276.8
– 3276.6 kPa
yes
no 14 1
SNVT_press
O
nvoPressure
0 – 655.34 m
yes
yes
no
no
15
24
1
1
SNVT_flow_p
SNVT_elec_kWh
O
O
nvoFlow
nvoEnergyConsum
yes
yes
no
no
22
23
1
1
SNVT_power
SNVT_power_kilo
O
O
nvo Power
nvoPowerkilo
yes
yes
no
no
18
16
1
1
SNVT_time_hour
SNVT_rpm
O
O
nvoRuntime
nvoSpeed
Tabelle 6.2.2
9 WILO SE 05/2011
Send when value
changes more
than
Range and effective
resolution WILO
Invalid
Data--
Resolution
immediately
service_required
-
immediately
sf_voltage_low
-
Deutsch
immediately
sf_voltage_high
sf_phase
sf_no_fluid
df_motor_temp
df_motor_failure
df_pump_blocked
df_elect_temp
df_elect_failure_nf
df_elect_failure
df_sensor_failure
device_fault
supply_fault
speed_low
speed_high
setpt_out_of_range
local_control
-
-
running
remote_press
remote_temp
immediately
HVAC_AUTO
HVAC_MRNG_WRMUP
HVAC_PRE_COOL
0xFF
-
HVAC_ECONOMY
immediately
immediately
immediately
immediately
immediately
after reset
HVAC_NUL
.state: 0 – 1
.value: 0.0%, 100.0%, 0xFF
Error Codes WILO
Error Codes WILO
device_fault
supply_fault
running
device_fault
supply_fault
running
Pump Type List WILO
.state: 0xFF
0xFFFF
0xFFFF
-
-
-
-
---
-
-
Data Range
and Units
bitset
Min.
Send
Send
Heartbt / No. Obj
NVT
Mand.
Opt.OO
Output-
Networkvariable
Time
yes
Acknono
20 1
SNVT_dev_maint
nvoMaintenance
bitset
yes
19 1
SNVT_dev_fault
nvoPumpFault
bitset
yes
yes 13 1
SNVT_dev_status
O
nvoPumpStatus
ENUM 0 – 17
(hvac_t)
yes
yes 4 1
SNVT_hvac_mode
M
nvoEffOpMode
.state: 0 – 1
.value: 0.0-100.0%,
bitset
yes
yes
yes
yes
nonono 173839 1
SNVT_switch
O
nvoPumpOverride
no 40
111
SNVT_count
SNVT_count
SNVT_dev_status
OOO
nvoCurrentErrorM
nvoCurrentErrorS
nvoPumpStatusM
bitset
yes
yes
no
no
41
42
1
1
SNVT_dev_status
SNVT_count
O
O
nvoPumpStatusS
nvoPumpType
Tabelle 6.2.2, Fortsetzung
Einbau- und Betriebsanleitung Wilo-Control IF-Modul LON / IF-Modul Stratos LON 10
Deutsch
Data Range and effective
Number
Object
CPT / NVT
6.2.3 Wertebereiche und Auflösungen der Netzwerkvariablen Konfigurationseingänge
resolution WILO
0–0d17h59m59s
eff. Res: 1s-0–6553s
eff. Res: 1s
0–6553s
eff. Res: 1s
0–6553s
eff. Res: 1s
DCM_SPEED_CONST
DCM_PRESS_CONST
DCM_PRESS_COMP
DCM_PRESS_AUTO
0 – 3276.7 kPa
eff. Res: 0.981 kPa
0 – 3276.7 kPa
eff. Res: 0.981 kPa
-273.1 – 327.6 °C
eff. Res: 0.1°C
-273.1 – 327.6 °C
eff. Res: 0.1°C
.TempMin, .TempMax:
0 – 110 °C
eff. Res: 0.1°C
221748
0
SCPTmaxSndT
0
1
SCPTlocation
SCPTmaxRcvTime
49
52
1
1
SCPTmaxSendTime
SCPTminSendTime
238
1
SCPTdeviceControlMode
239
1
SCPTminRemotePressureSetpoint
240
243
1
1
SCPTmaxRemotePressureSetpoint
SCPTminRemoteTempSetpoint
244
1
1
SCPTmaxRemoteTempSetpoint
UCPTPressTemp
.PressMin, .PressMax:
0 – 3276.7 kPa
eff. Res: 0.981kPa
.state: 0–1
.value: 0–255
213
1
SCPTsetpoint
Mandatory /
Optional /
User
O
O
O
M
O
O
Input Configuration Variable
nciMaxStsSendT
nciLocation
nciRcvHrtBt
nciSndHrtBt
nciMinOutTm
nciControlMode
O
nciRemMinPress
O
O
nciRemMaxPress
nciRemMinTemp
O
U
nciRemMaxTemp
nciPressTemp
O
nciSetpPreset
Tabelle 6.2.3
11 WILO SE 05/2011
6.2.4 Wertebereiche und Auflösungen der Netzwerkvariablen Konfigurationsausgänge
Output Configuration
Mandat./ Optional
CPT/NVT Object Number Value
Variable
nciDevMajVer O SCPTdevMajVer 0 165 03 nciDevMinVer O SCPTdevMinVer 0 166 00 nroPumpChar M SCPTpumpCharacteristic 1 233 depends on
pumptype nciObjMajVer O SCPTobjMajVer 1 167 03 nciObjMinVer O SCPTobjMinVer 1 168 00
6.2.5 Beschreibung der Netzwerkvariablen
Objekt-Request
network input SNVT_obj_request nviRequest
Diese Eingangs-Netzwerkvariable veranlasst verschiedene Operationen, die den Knoten- und Objektstatus betreffen. Sie besteht aus 2 Bytes, dem ID-Byte und dem Wert-Byte. Das ID-Byte gibt die Nummer des Objektes an, auf das sich der Request bezieht. Der ID-Wert 0 bezieht sich auf das Knoten-Objekt, hier haben Requests evtl. auch Auswirkungen auf alle anderen Objekte. Der ID-Wert 1 bezieht sich auf das pump-controller-Objekt.
Wertebereich:
Wert Funktion bei ID = 0 Funktion bei ID = 1
RQ_NORMAL Normalbetrieb aller Objekte Normalbetrieb pump control-
ler RQ_DISABLED Stop aller Objekte Stop des pump controller RQ_ENABLE Enable des Knotenobjekts Enable des pump controller RQ_UPDATE_STATUS Status Knotenobjekt aktuali-
sieren (Oderverknüpfung über
Status pump controller aktu-
alisieren
alle Objekte)
RQ_REPORT_MASK Unterstützte Statusmeldun-
gen Knotenobjekt (Oderver-
Unterstützte Statusmeldun-
gen pump controller
knüpfung über alle Objekte)
RQ_CLEAR_STATUS Bestimmte Statusmeldungen
in allen Objekten löschen
Bestimmte Statusmeldungen
des pump controller löschen
Deutsch
Einbau- und Betriebsanleitung Wilo-Control IF-Modul LON / IF-Modul Stratos LON 12
Deutsch
Objekt-Status
network output SNVT_obj_status nvoStatus Diese Ausgangs-Netzwerkvariable liefert Statusinformationen zu den einzel-
nen Objekten. Die Informationen sind Bit-Codiert. Alle Bits sind nach einem Reset wieder gelöscht.
Wertebereich:
Bit Funktion
invalid_id Es wurde ein nicht existierendes Objekt angesprochen invalid_request Es wurde ein unbekannter Request gesendet disabled Das betreffende Objekt ist abgeschaltet electrical_fault Das pump-controller-Objekt meldet einen elektrischen Fehler unable_to_measure Das pump-controller-Objekt kann nicht mit der Pumpe kom-
munizieren
manual_control Das pump-controller-Objekt wird durch Hardware-Vorgaben
an der Pumpe an der Steuerung gehindert (ext. Off, ext. Min, IR-
Monitor) in_alarm Das pump-controller-Objekt meldet einen Fehler report_mask Signalisiert, daß nvoStatus aufgrund einer vorangegangenen
RQ_REPORT_MASK-Aufforderung die Status-Maske enthält,
also die Liste aller Bits, die unterstützt werden.
File Directory Address
network output SNVT_address nvoFileDirectory Diese Netzwerkvariable gibt die Startadresse des Konfigurationsdatei-
Verzeichnisses an. Weitere Informationen stehen in der LONmark Dokumentation des Knoten­objektes.
13 WILO SE 05/2011
Maximum Status Send Time
network input config SNVT_elapsed_tm nciMaxStsSendT Diese optionale Eingangs-Konfigurations-Netzwerkvariable definiert einen
Zeittakt, in welchem die Objekt-Stati automatisch aktualisiert werden. Es wer­den abwechselnd der Status des node-Objekts und der des pump-controller­Objekts aktualisiert.
Wertebereich: 0d0h0m0s0ms – 0d17h59m59s999ms (in 1 s-Schritten). Der Wert 0d0h0m0s0ms schaltet das automatische Aktualisieren aus. Startwert: 0d0h0m0s0ms (automatisches Aktualisieren ausgeschaltet)
SCPT Reference: SCPTmaxSendT (22)
Device Major Version
network output config unsigned short nciDevMajVer Diese optionale Ausgangs-Konfigurations-Netzwerkvariable liefert das High-
byte der Modulversion. SCPT Reference: SCPTdevMajVer (165)
Device Minor Version
network output config unsigned short nciDevMinVer Diese optionale Ausgangs-Konfigurations-Netzwerkvariable liefert das Low-
byte der Modulversion. SCPT Reference: SCPTdevMinVer (166)
Deutsch
Location Label
network input config SNVT_str_asc nciLocation Diese optionale Eingangs-Konfigurations-Netzwerkvariable kann genutzt wer-
den, um Informationen über den Einbauort der Pumpe abzuspeichern, die über den im Neuron Chip abgelegten, nur 6Byte umfassenden Informationsstring hinausgehen.
Wertebereich: Beliebiger, NUL-terminierter ASCII-String von max. 31 Bytes Länge (incl. NUL).
Startwert: ASCII-String, der nur aus NUL ("\0") besteht.
SCPT Reference: SCPT_location (17)
Einbau- und Betriebsanleitung Wilo-Control IF-Modul LON / IF-Modul Stratos LON 14
Deutsch
Sollwertobergrenze (Hersteller- , Pumpen- und Regelartspezifisch)
Tatsächlicher Sollwert [%]
STOP
X
100%
Pump Setpoint
nviPumpSetpoint
[%]
Sollwertuntergrenze (Hersteller- , Pumpen- und Regelartspezifisch)
X = ( Sollwertuntergrenze / Sollwertobergrenze ) * 100%
Pump Setpoint
network input SNVT_switch nviPumpSetpoint
Diese Eingangs-Netzwerkvariable dient zum Ein- und Ausschalten der Pumpe und zur Vorgabe eines Sollwertes. Die Netzwerkvariable besteht aus einem Status-Byte, in welchem der Ein­schaltzustand übertragen wird, und aus einem Werte-Byte, in welchem der Soll­wert übertragen wird. Bei Vorgabe eines Status-Bytes von 0 ist die Pumpe ausgeschaltet, bei Vorgabe eines Status-Bytes von 1 hängt der Einschaltzustand noch vom Werte-Byte ab. Bei Vorgabe eines Sollwertes von 0% wird die Pumpe ausgeschaltet, bei Vor­gabe eines Sollwertes größer 0% ist die Pumpe eingeschaltet, wenn das Status­Byte 1 ist. Der Sollwert kann in 0,5%-Schritten verändert werden. Bei Vorgabe von Sollwerten oberhalb der Sollwertobergrenze wird auf die Soll-
15 WILO SE 05/2011
wertobergrenze begrenzt, entsprechend wird bei Vorgabe von Sollwerten unterhalb der Sollwertuntergrenze auf die Sollwertuntergrenze begrenzt.
Die Sollwertober- und Sollwertuntergrenzen können sich ändern, wenn die Pumpe mit einem externen Sensor betrieben wird (siehe nviRemotePress, nciRemMinPress und nciRemMaxP re ss ).
Wertebereich:
Status Wert Funktion
0 0 – 255 STOP 10 STOP 1 1 – 200 0,5 – 100,0% 1 201 - 255 100,0%
Startwert: Status = 1, Wert = 200 = 100,0%. Startwert entspricht der Vorgabe, die im Konfigurationsparameter SCPTsetpoint nichtflüchtig abgespeichert wer­den kann.
Requested Pump-Operating Mode
network input SNVT_hvac_mode nviPumpOpMode Diese Eingangs-Netzwerkvariable dient zur Vorgabe eines Betriebsmodus. Wird
ein Betriebsmodus vorgegeben, der nicht definiert oder ungültig ist, verbleibt die Pumpe im aktuellen Modus.
Wertebereich:
Wert Funktion Bemerkung
HVAC_AUTO Normalbetrieb Sollwert über
nviPumpSetpoint HVAC_MRNG_WRMUP Aufwärmbetrieb Maximale Drehzahl HVAC_PRE_COOL Abkühlbetrieb Maximale Drehzahl HVAC_ECONOMY Energiesparbetrieb Drehzahl Absenkbetrieb
(Pumpentypspezifisch) HVAC_NUL Ungültig
Deutsch
Startwert: HVAC_AUTO
Pump Capacity
network output SNVT_lev_percent nvoPumpCapacity Diese Ausgangs-Netzwerkvariable liefert den aktuellen Arbeitspunkt der
Pumpe als auf den maximalen Sollwert bezogenen Prozentwert. Bei Verwendung eines externen Druck- oder Temperatursensors liefert diese Variable den Sensorwert als auf den maximalen Sensorwert bezogenen Prozentwert.
Einbau- und Betriebsanleitung Wilo-Control IF-Modul LON / IF-Modul Stratos LON 16
Deutsch
Wertebereich:
-163,840% – 163,830% (in 0,02%-Schritten). Der Wert 163,835% stellt einen ungültigen Wert dar.
Übertragung: Dieser Wert wird automatisch übertragen, wenn die Abweichung vom zuletzt übertragenen Wert mehr als 5% des Wertes in nroPumpChar.pressMax (bei Dif­ferenzdruckregelung) oder 2% des Wertes in nroPumpChar.sp eedMax (bei Drehzahlsteller) beträgt. Außerdem wird dieser Wert regelmäßig übertragen, wenn der Konfigurationseingang nciSndHrtBt mit einem gültigen Zeittakt beschrieben wurde. Ebenso wird dieser Wert übertragen, wenn durch vorran­gige Vorgaben oder Anschließen eines externen Sensors die Regelart geändert wurde.
Übertragungstakt: Durch Beschreiben des Konfigurationseingangs nciMinOutTm mit einem gülti­gen Zeittakt kann die minimale Zeit zwischen zwei Übertragungen einer Netz­werkvariablen eingestellt werden.
Voreingestellter Servicetyp: acknowledged
Effective Operating Mode
network output SNVT_hvac_mode nvoEffOpMode Diese Ausgangs-Netzwerkvariable liefert den aktuellen Betriebsmodus der
Pumpe. Dieser Wert entspricht der Vorgabe in der Eingangs-Netzwerkvaria blen nviPumpOpMode, wenn nicht über lokale Vorgaben an der Pumpe (ext. off, ext. min oder IR-Monitor) ein anderer Betriebsmodus erzwungen wird.
Wertebereich:
Wert Funktion Bemerkung
HVAC_AUTO Normalbetrieb Sollwert über
nviPumpSetpoint HVAC_MRNG_WRMUP Aufwärmbetrieb Maximale Drehzahl HVAC_PRE_COOL Abkühlbetrieb Maximale Drehzahl HVAC_ECONOMY Energiesparbetrieb Drehzahl Absenkbetrieb
(Pumpentypspezifisch) HVAC_OFF Offlinebetrieb Ext. Off oder Manueller
Betrieb über IR-Monitor HVAC_NUL Ungültig
Übertragung: Dieser Wert wird bei jeder Änderung automatisch übertragen. Außerdem wird dieser Wert regelmäßig übertragen, wenn der Konfigurations­eingang nciSndHrtBt mit einem gültigen Zeittakt beschrieben wurde.
17 WILO SE 05/2011
Übertragungstakt: Durch Beschreiben des Konfigurationseingangs nciMinOutTm mit einem gülti­gen Zeittakt kann die minimale Zeit zwischen zwei Übertragungen einer Netz­werkvariablen eingestellt werden.
Voreingestellter Servicetyp: acknowledged
Effective Device-Control Mode
network output SNVT_dev_c_mode nvoControlMode Diese Ausgangs-Netzwerkvariable liefert die aktuelle Regelart der Pumpe. Wertebereich:
Wert Funktion
DCM_SPEED_CONST Drehzahlsteller DCM_PRESS_CONST Differenzdruck konstant / Druck konstant DCM_PRESS_COMP Differenzdruck volumenstromabhängig DCM_PRESS_AUTO Differenzdruck temperaturabhängig
Übertragung: Dieser Wert wird bei jeder Änderung automatisch übertragen. Außerdem wird dieser Wert regelmäßig übertragen, wenn der Konfigurations­eingang nciSndHrtBt mit einem gültigen Zeittakt beschrieben wurde.
Übertragungstakt: Durch Beschreiben des Konfigurationseingangs nciMinOutTm mit einem gülti­gen Zeittakt kann die minimale Zeit zwischen zwei Übertragungen einer Netz­werkvariablen eingestellt werden.
Voreingestellter Servicetyp: acknowledged
Deutsch
Pump Override Stop Command
network input SNVT_switch nviPumpOvdStop Diese optionale Eingangs-Netzwerkvariable stellt eine vorrangige Ein-/Aus-
schaltfunktion zur Verfügung und ist für z. B. Wartungsarbeiten gedacht. Die Netzwerkvariable besteht aus einem Status-Byte und aus einem Werte-Byte. Die Vorgabe “OVDSTOP” hat Vorrang vor dem in nviPumpSetpoint vorgegebe­nen Sollwert sowie vor den in nviOvdSpeed und nviOvdPress vorgegebenen vorrangigen Sollwerten. In der Ausgangs-Netzwerkvariable nvoPumpOverride wird eine vorrangige Vor­gabe signalisiert.
Einbau- und Betriebsanleitung Wilo-Control IF-Modul LON / IF-Modul Stratos LON 18
Deutsch
Wertebereich
Status Wert Funktion
0 0 – 255 NORMAL 10 NORMAL 1 1 – 255 OVDSTOP 255 0 – 255 ungültig (NORMAL)
Startwert: Status = 255, Wert = 255
Override Setpoint for Speed
network input SNVT_lev_percent nviOvdSpeed Diese optionale Eingangs-Netzwerkvariable dient zur vorrangigen Vorgabe
eines Drehzahlsollwertes, z. B. für Wartungsarbeiten. Der Wert wird in Prozent des maximalen Wertes der Pumpe vorgegeben. Wenn ein gültiger Wert em pfan­gen wird , wird der über nviPumpSetpoint oder nviOvdPress vorgegebene Soll­wert überschrieben und automatisch auf die Regelart Drehzahlsteller umgeschaltet. Ein ungültiger Wert in allen vorrangigen Sollwertvorgaben nviOvdSpeed und nviOvdPress sowie eine Vorgabe “Normal” über nviPumpOvdStop setzt die Pumpe zurück in den Normalzustand. In der Ausgangs-Netzwerkvariablen nvoPumpOverride wird eine vorrangige Vorgabe signalisiert.
Wertebereich:
-163,84% - 163,83% (in 0,005%-Schritten). Der Wert 163,835% stellt einen ungültigen Wert dar. Werte kleiner als 0% und Werte größer als 100% werden entsprechend begrenzt und nvoPumpStatus.pump_ctrl.setpt_out_of_range wird gesetzt.
Startwert: 163,835%
Override Setpoint for Pressure
network input SNVT_press nviOvdPress Diese optionale Eingangs-Netzwerkvariable dient zur vorrangigen Vorgabe
eines Differenzdrucksollwertes, z. B. für Wartungsarbeiten. Der Wert wird in kPa vorgegeben. Wenn ein gültiger Wert empfangen wird, wird der über nviPump­Setpoint oder nviOvdSpeed vorgegebene Sollwert überschrieben und automa­tisch auf die Regelart Differenzdruck konstant umgeschaltet. Ein ungültiger Wert in allen vorrangigen Sollwertvorgaben nviOvdSpeed und nviOvdPress sowie eine Vorgabe “Normal” über nviPumpOvdStop setzt die Pumpe zurück in den Normalzustand. In der Ausgangs-Netzwerkvariablen nvoPumpOverride wird eine vorrangige Vorgabe signalisiert.
19 WILO SE 05/2011