WIKA T91.30 User Manual

Operating Instructions
1. Safety instructions
When mounting, commissioning and operating these transmitters, it is important to observe the respective national safety precautions and regulations in effect
!
(e.g. VDE 100). Nonobservance of the applicable regulations may cause severe injury to persons or damage to equipment. Only staff with suitable qualifications should work with these transmitters. Before commissioning, check the instrument's suitability for the intended application. In particular, it is important to observe the ambient and operating limits as specified in the WIKA data sheet, TE 91.02.
2. Mounting
The model T91.30 transmitters are intended for mounting on a standard rail. They can be fastened without tooling by clipping onto a 35 mm DIN rail (DIN EN 50 022-35). To remove, release the clip mechanism.
3. Maintenance
The temperature transmitters described here are maintenance free! The electronics do not incorporate any components which could be repaired or replaced. Depending upon operating conditions, it may be advisable to check the calibration of the transmitter yearly.
4. Electrical connections
These transmitters have an internal galvanic connection between the sensor input and analogue output. No external connection should be made (for example, by earthing) between the connected temperature sensor and analogue output! For this reason it is best to use isolated thermocouples. (With the exception of model T91.30.232: This transmitter is galvanically isolated between input and output. For further information on this model, see point 4.2). For flying leads we recommend using crimped connector sleeves. To connect a thermocouple: Make sure that the thermocouple is connected with the correct polarity. If the cable between the thermocouple and the transmitter must be extended, only use the appropriate thermal or compensating cable for the connected thermocouple type.
4.1 Pt100 input
Model T91.30.214
Pt100 in 2- or 3-wire connection. For a 2-wire connection the resistance of the wires affects the measurement results. Therefore this circuit should only be selected if the wires are short, or accuracy requirements are low. If using a 2-wire connection, always connect a jumper between terminals 1 and 2, and 3 and 4 respectively. With a 3-wire connection the measurement results are not affected by the resistance of the corresponding partial circuit due to the isolation between the input leads and the power and signal terminals. If using a 3-wire connection, always connect a jumper between input terminals 1 and 2.
230 VAC
24 VDC
Zero
876
12 34
Pt100
Model T91.30.224 Pt100 in 2- or 3-wire connection. With a 2-wire connection, the resistance of the input leads affects the measurement results. Therefore this connection should only be selected if the wires are short, or accuracy requirements are low. If using a 2-wire connection, always connect a jumper between input terminals 3 and 4.
Span
Load (PLC, PC)
C_214.01
Technical alteration rights reserved.
WIKA Alexander Wiegand GmbH & Co. KG
Alexander-Wiegand-Straße 30 63911 Klingenberg/Germany Phone (+49) 93 72/132-0 Fax (+49) 93 72/132-406 E-Mail info@wika.de www.wika.de
09/2006 GB
230 VAC
24 VDC
Zero
Load (PLC, PC)
C_224.01
876
Span
12 34
Pt100
Model T91.30.254 Pt100 in 2- or 3-wire connection. With a 2-wire connection, the resistance of the input leads affects the measurement results. Therefore this connection should only be selected if the wires are short, or accuracy requirements are low. If using a 2-wire connection, always connect a jumper between input terminals 3 and 4.
230 VAC
Load (PLC, PC)
24 VDC
C_254.01
5.1 Preparation
Connect a suitable simulation source to the input of the T91 (Pt100 or thermocouple simulator). When simulating a Pt100, connect the simulator in a 2-, 3- or 4-wire configuration. We recommend the use of passive resistances. When simulating a thermocouple, the actual terminal temperature of the transmitter must be pre-set on the simulator (Cold Junction Compensation).
T
Connect a multimeter to the 0 … 10 V output signal
T
Connect a suitable power supply to the transmitter
Span
876
1 34
Pt100
Zero
4.2 Thermocouple input
Model T91.30.212
The positive lead of the thermocouple is connected to terminal 3 on the transmitter and the negative lead to terminal 2. The output voltage follows the applied input voltage linearly. There should be no galvanic coupling between the sensor and the supply or output voltage.
Model T91.30.232
The positive lead of the thermocouple is connected to terminal 3 on the transmitter and the negative lead to terminal 2. The transmitter is galvanically isolated between input and output; so non-isolated thermocouples can therefore be used.
230 VAC
24 VDC
Zero
876
Span
23
Thermocouple
Load (PLC, PC)
C_212-232.01
4.3 Electrical connection 0 ... 10 V output signal
Model Terminals
T91.30 6 (+signal), 8 (+24 V), 7 (-GND)
Maximum power supply: 15 …35 VDC (reverse-polarity protected) The output voltage follows the applied input signal linearly. Please note that the output can only be regulated to within approx. 0.02 V at the lower supply voltage.
5. Transmitter adjustment
5.2 Adjustment
1) Set the simulator with approx. 1 V offset from the lower limit of the measuring range. (e.g. -20 °C = 1 V for a measurement range -30 ... +70 °C)
2) Turn the zero potentiometer Z, until the output signal (in our example -20 °C = 1 V output signal) matches the desired value
3) Set the simulator to the upper limit of the measuring range , e.g. +70 °C for measurement range -30 ... +70 °C
4) Turn the span potentiometer S, until the output signal (in our example 70 °C = 10 V) matches the desired value
5) Repeat step 1 and check signal (1 V)
6) Repeat step 3 and check signal (10 V)
5.3 Closing steps
Disconnect the simulator, the multimeter and the power supply
6. Fault diagnostics
When measuring with resistance thermometers or thermocouples, factors arising from the design and measuring technology used can falsify the results measured. The most important effects that can lead to faults are listed below:
Error Possible cause
No voltage output - No supply voltage
- Display unit not working
- Circuit interruption in the supply line
Output signal
1) 0 V - Short circuit in the Pt100
2) corresponds to room temperature - Short circuit in the thermocouple Output signal - Sensor break > 10 V Temperature read out - Poor lead insulation resistance too low/fluctuates Read out obviously - Moisture in the sensor or in the senor too high or too low wire
- Not correct compensation wire or incorrect thermocouple
If the measuring point is - Thermocouple polarity incorrect heated up the output signal reduces When only one pole of the - Electromagnetic disturbances are thermocouple is connected, coupled to the input lead a value is still displayed - Through poor galvanic isolation, and
poor insulation, parasitic voltages are present, e.g. through the thermal insulation
Displayed value obviously - Electromagnetic disturbances are incorrect coupled to the input lead
- Parasitic galvanic voltages, e.g. as a result of moisture in the compensation cable insulation
Zero point and Span adjustment is carried out via potentiometers. These are under the transparent cover. To open the transparent cover, it must be pressed inwards on its shortest sides and pulled away carefully. The potentiometers are protected against accidental alteration. The zero-point potentiometer can be adjusted to make small corrections. After any adjustment of the span potentiometer, a complete adjustment of the transmitter is necessary.