ist eine geschützte Marke in verschiedenen Ländern.
WIKA
Prior to starting any work, read the operating instructions!
Keep for later use!
Vor Beginn aller Arbeiten Betriebsanleitung lesen!
Zum späteren Gebrauch aufbewahren!
Lire le mode d'emploi avant de commencer toute opération !
A conserver pour une utilisation ultérieure !
¡Leer el manual de instrucciones antes de comenzar cualquier trabajo!
¡Guardar el manual para una eventual consulta!
2WIKA operating instructions submersible pressure transmitter, model LH-10
14075011.01 08/2013 GB/D/F/E
Contents
Contents
1. General information 4
2. Safety 5
3. Specications8
4. Design and function 9
5. Transport, packaging and storage 10
6. Commissioning, operation 11
7. Maintenance and cleaning 13
8. Faults 13
9. Dismounting, return and disposal 14
Appendix 1: EC Declaration of conformity model LH-10 16
GB
Declarations of conformity can be found online at www.wika.com.
14075011.01 08/2013 GB/D/F/E
3WIKA operating instructions submersible pressure transmitter, model LH-10
1. General information
1. General information
■
The submersible pressure transmitter described in the operating instructions has been designed and manufactured
using state-of-the-art technology. All components are subject to stringent quality and environmental criteria during
GB
production. Our management systems are certied to ISO 9001 and ISO 14001.
■
These operating instructions contain important information on handling the instrument. Working safely requires that
all safety instructions and work instructions are observed.
■
Observe the relevant local accident prevention regulations and general safety regulations for the instrument's range
of use.
■
The operating instructions are part of the product and must be kept in the immediate vicinity of the instrument and
readily accessible to skilled personnel at any time.
■
Skilled personnel must have carefully read and understood the operating instructions prior to beginning any work.
■
The manufacturer's liability is void in the case of any damage caused by using the product contrary to its intended
use, non-compliance with these operating instructions, assignment of insuciently qualied skilled personnel or
unauthorised modications to the instrument.
■
The general terms and conditions contained in the sales documentation shall apply.
■
Subject to technical modications.
■
Further information:
- Internet address:www.wika.de / www.wika.com
- Relevant data sheet:PE 81.09
- Application consultant:Tel.: +49 9372 132-8976
Fax: +49 9372 132-8008976
support-tronic@wika.de
4WIKA operating instructions submersible pressure transmitter, model LH-10
14075011.01 08/2013 GB/D/F/E
1. General information / 2. Safety
Explanation of symbols
WARNING!
... indicates a potentially dangerous situation that can result in serious injury or death, if not avoided.
CAUTION!
... indicates a potentially dangerous situation that can result in light injuries or damage to equipment or the
environment, if not avoided.
Information
... points out useful tips, recommendations and information for ecient and trouble-free operation.
WARNING!
... indicates a potentially dangerous situation that can result in burns, caused by hot surfaces or liquids, if
not avoided.
2. Safety
WARNING!
Before installation, commissioning and operation, ensure that the appropriate submersible pressure trans-
mitter has been selected in terms of measuring range, design and specic measuring conditions.
Non-observance can result in serious injury and/or damage to the equipment.
Further important safety instructions can be found in the individual chapters of these operating instructions.
2.1 Intended use
The submersible pressure transmitter is used to convert hydrostatic pressure into an electrical signal.
GB
The instrument has been designed and built solely for the intended use described here, and may only be used
accordingly.
14075011.01 08/2013 GB/D/F/E
5WIKA operating instructions submersible pressure transmitter, model LH-10
2. Safety
The technical specications contained in these operating instructions must be observed. Improper handling or operation of the pressure transmitter outside of its technical specications requires the instrument to be taken out of service
immediately and inspected by an authorised WIKA service engineer.
The manufacturer shall not be liable for claims of any type based on operation contrary to the intended use.
GB
2.2 Personnelqualication
WARNING!
Riskofinjuryshouldqualicationbeinsucient!
Improper handling can result in considerable injury and damage to equipment.
The activities described in these operating instructions may only be carried out by skilled personnel who
have the qualications described below.
Skilled personnel
Skilled personnel are understood to be personnel who, based on their technical training, knowledge of measurement
and control technology and on their experience and knowledge of country-specic regulations, current standards and
directives, are capable of carrying out the work described and independently recognising potential hazards.
Special operating conditions require further appropriate knowledge, e.g. of aggressive media.
2.3 Special hazards
WARNING!
For hazardous media such as acetylene, ammable or toxic gases and liquids, etc., in addition to all
standard regulations, the appropriate existing codes or regulations must also be followed.
WARNING!
Residual media in the dismounted instrument can result in a risk to persons, the environment and
equipment.
Take sucient precautionary measures.
Do not use this instrument in safety or emergency stop devices. Incorrect use of the instrument can result in
injury.
6WIKA operating instructions submersible pressure transmitter, model LH-10
14075011.01 08/2013 GB/D/F/E
2. Safety
2.4 Labelling, safety marks
Product label
Model
Measuring range
Output signal
Power supply
S# serial number
P# product number
If the serial number becomes illegible due to mechanical damage or overpainting, traceability will no longer be
possible.
Explanation of symbols
CE, Communauté Européenne
Instruments bearing this mark comply with the relevant European directives.
CSA, Canadian Standard Association®
The instrument has been inspected and certied by CSA International.Instruments bearing this mark
comply with the applicable Canadian standards on safety (including explosion protection).
see explanation of symbols
Pin assignment
GB
14075011.01 08/2013 GB/D/F/E
7WIKA operating instructions submersible pressure transmitter, model LH-10
When choosing the FEP cable, measuring ranges up to and including 0 ...10 bar, 0 ... 150 psi and 0 ... 100 mH2O are
available.
The given measuring ranges are also available in mbar, kPa and MPa.
8WIKA operating instructions submersible pressure transmitter, model LH-10
14075011.01 08/2013 GB/D/F/E
3.Specications/4.Designandfunction
Output signals
Ingress protection (per IEC 60529)
IP 68
Signal typeSignal
Current (2-wire)4 ... 20 mA
Current (3-wire)0 ... 20 mA
Voltage (3-wire)DC 0 ... 5 V
DC 0 ... 10 V
DC 0.5 ... 2.5 V
Power supply
The power supply depends on the selected output signal.
■
4 ... 20 mA:DC 10 ... 30 V
■
0 ... 20 mA:DC 10 ... 30 V
■
DC 0 ... 5 V:DC 10 ... 30 V
■
DC 0 ... 10 V:DC 14 ... 30 V
■
DC 0.5 ... 2.5 V:
DC
5 ... 30 V (suitable for battery
operation)
Permissible temperature ranges
■
Fluid
- PUR cable: -10 ... +50 °C
- FEP cable: -10 ... +85 °C
■
Ambient:-10 ... +50 °C
■
Storage:-30 ... +80 °C
Submersion depths
■
Submersible pressure
transmitter with FEP cable:up to 100 m
■
Submersible pressure
transmitter with PUR cable:up to 300 m
CE conformity
EMC directive 2004/108/EC, EN 61326 emission (group 1,
class B) and immunity (industrial application)
For special model numbers, e.g. LH-10000, please note the specications stated on the delivery note.
For further specications see WIKA data sheet PE 81.09 and the order documentation.
4. Design and function
4.1 Description
The prevailing pressure is measured at the sensor element through the deformation of a diaphragm. By supplying
power, this deformation of the diaphragm is converted into an electrical signal. The output signal from the pressure
transmitter is amplied and proportional to the prevailing pressure.
GB
4.2 Scope of delivery
Cross-check scope of delivery with delivery note.
14075011.01 08/2013 GB/D/F/E
9WIKA operating instructions submersible pressure transmitter, model LH-10
5. Transport, packaging and storage
5. Transport, packaging and storage
5.1 Transport
Check the submersible pressure transmitter for any damage that may have been caused by transport.
Obvious damage must be reported immediately.
GB
5.2 Packaging
Do not remove packaging until just before mounting.
Keep the packaging as it will provide optimum protection during transport (e.g. change in installation site, sending for
repair).
5.3 Storage
Permissible conditions at the place of storage:
Storage temperature: -30 ... +80 °C
Mount the protection cap for storing the submersible pressure transmitter, so that the diaphragm will not be damaged.
Avoid exposure to the following factors:
■
Direct sunlight or proximity to hot objects
■
Mechanical vibration, mechanical shock (putting it down hard)
Store the submersible pressure transmitter in its original packaging in a location that fulls the conditions listed above.
If the original packaging is not available, pack and store the instrument as described below:
1. Wrap the instrument in an antistatic plastic lm.
2. Place the instrument along with shock-absorbent material in the packaging.
3. If stored for a prolonged period of time (more than 30 days), place a bag containing a desiccant inside the packaging.
WARNING!
Before storing the instrument (following operation), remove any residual media. This is of particular
importance if the medium is hazardous to health, e.g. caustic, toxic, carcinogenic, radioactive, etc.
10WIKA operating instructions submersible pressure transmitter, model LH-10
14075011.01 08/2013 GB/D/F/E
6. Commissioning, operation
6. Commissioning, operation
WARNING!
Observe the working conditions in accordance with chapter 3 “Specications”.
CAUTION!
Prior to commissioning, the submersible pressure transmitter must be subjected to a visual inspection.
■
Leaking uid is indicative of damage.
■
Only use the submersible pressure transmitter if it is in perfect condition with respect to safety.
6.1 Mechanical mounting
The protection cap protects the internal diaphragm from damage. Remove the protective cap if the medium is viscous
or contaminated.
Protection cap
Internal diaphragm
6.2 Electrical mounting
6.2.1 Connection assembly
■
Use the submersible pressure transmitter with shielded cable and ground the shield on at least one end of the lead,
if the lines are longer than 30 m or leave the building.
■
When the shield of the cable is being connected, no potential dierences should exist between the medium, the
vessel and the ground connection of the junction box or the control cabinet.
■
Make sure that no moisture enters at the cable end.
GB
14075011.01 08/2013 GB/D/F/E
11WIKA operating instructions submersible pressure transmitter, model LH-10
6. Commissioning, operation
6.2.2 Pin assignment
Cable outlet2-wire3-wire
U
GB
+
U
-
S
+
Shieldgreygrey
6.2.3 Setting up a voltage supply
The power supply for the pressure transmitter must be made via an energy-limited electrical circuit in accordance with
section 9.3 of UL/EN/IEC 61010-1, or an LPS to UL/EN/IEC 60950-1, or (for North America) class 2 in accordance with
UL1310/UL1585 (NEC or CEC). The power supply must be suitable for operation above 2,000 m should the pressure
transmitter be used at this altitude.
■
Power supply
The power supply depends on the selected output signal.
4 ... 20 mA:DC 10 ... 30 V
0 ... 20 mA:DC 10 ... 30 V
DC 0 ... 5 V:DC 10 ... 30 V
DC 0 ... 10 V:DC 14 ... 30 V
DC
DC 0.5 ... 2.5 V:
■
LoadinΩ
5 ... 30 V (suitable for battery operation)
Current output (2-wire): ≤ (power supply - 10 V) / 0.02 A - (cable length in m x 0.14 Ω)
Current output (3-wire): ≤ (power supply - 3 V) / 0.02 A - (cable length in m x 0.14 Ω)
Voltage output (3-wire): > 100 kΩ
6.3 Functional check
The output signal must be proportional to the prevailing pressure. If this is not the case, this may indicate a damaged
diaphragm. In this case, see chapter 8 “Faults”.
brownbrown
greengreen
-white
12WIKA operating instructions submersible pressure transmitter, model LH-10
14075011.01 08/2013 GB/D/F/E
7. Maintenance and cleaning
7. Maintenance and cleaning
7.1 Maintenance
This submersible pressure transmitter is maintenance-free.
Repairs must only be carried out by the manufacturer.
7.2 Cleaning
CAUTION!
■
Prior to cleaning, switch o and disconnect the submersible pressure transmitter from the voltage
supply.
■
Clean the instrument with a moist cloth.
■
Wash or clean the dismounted instrument before returning it, in order to protect persons and the environment from exposure to residual media.
■
Residual media in dismounted instruments can result in a risk to persons, the environment and
equipment. Take sucient precautionary measures.
■
Do not use any pointed or hard objects for cleaning, as they may damage the diaphragm of the process
connection.
For information on returning the instrument see chapter 9.2 “Return”.
8. Faults
In the event of any faults, rst check whether the submersible pressure transmitter is mounted correctly, mechanically
and electrically.
GB
FaultsCausesMeasures
No output signalCable breakCheck the continuity, and if necessary exchange
No/wrong power supplyCorrect the power supply
No/wrong output signalWiring errorRectify the wiring
14075011.01 08/2013 GB/D/F/E
the cable
13WIKA operating instructions submersible pressure transmitter, model LH-10
8. Faults / 9. Dismounting, return and disposal
FaultsCausesMeasures
Signal span too small/dropsMechanical overload caused by overpres-
GB
Signal span varies/inaccurateOperating temperature too high/lowOperate the instrument in the permissible
Deviating zero point signalOperating temperature too high/lowOperate the instrument in the permissible
sure
Diaphragm damaged, e.g. due to impacts,
abrasive/aggressive medium; corrosion at
diaphragm; transmission medium missing
Diaphragm damaged, e.g. due to impacts,
abrasive/aggressive medium; corrosion at
diaphragm; transmission medium missing
Replace instrument; if it fails repeatedly, contact
the manufacturer.
Replace instrument; if it fails repeatedly, contact
the manufacturer.
temperature range
temperature range
Replace instrument; if it fails repeatedly, contact
the manufacturer.
If complaint is unjustied, we will charge you the complaint processing fees.
CAUTION!
If faults cannot be eliminated by means of the measures listed above, shut down the submersible pressure
transmitter immediately, and ensure that pressure is no longer present, and secure the instrument from
being put back into operation inadvertently. In this case, contact the manufacturer. If a return is needed,
please follow the instructions given in chapter 9.2 “Return”.
9. Dismounting, return and disposal
WARNING!
Residual media in the dismounted instrument can result in a risk to persons, the environment and
equipment. Take sucient precautionary measures.
9.1 Disassembly
WARNING!
Risk of burns!
Let the instrument cool down suciently before dismounting it!
During dismounting there is a risk of residual, dangerously hot media.
14WIKA operating instructions submersible pressure transmitter, model LH-10
14075011.01 08/2013 GB/D/F/E
9. Dismounting, return and disposal
9.2 Return
WARNING!
Strictly observe the following when shipping the submersible pressure transmitter:
All submersible pressure transmitters delivered to WIKA must be free from any kind of hazardous substances
(acids, bases, solutions, etc.).
When returning the instrument, use the original packaging or a suitable transport package.
To avoid damage:
1. Wrap the instrument in an antistatic plastic lm.
2. Place the instrument along with shock-absorbent material in the packaging. Place shock-absorbent material evenly
on all sides of the transport packaging.
3. If possible, place a bag containing a desiccant inside the packaging.
4. Label the shipment as carriage of a highly sensitive measuring instrument.
5. Mount the protection cap.
Information on returns can be found under the heading “Service” on our local website.
9.3 Disposal
Incorrect disposal can put the environment at risk.
Dispose of instrument components and packaging materials in an environmentally compatible way and in accordance
with the country-specic waste disposal regulations.
GB
14075011.01 08/2013 GB/D/F/E
15WIKA operating instructions submersible pressure transmitter, model LH-10
Appendix 1: EC Declaration of conformity model LH-10
GB
16WIKA operating instructions submersible pressure transmitter, model LH-10
14075011.01 08/2013 GB/D/F/E
Inhalt
Inhalt
1. Allgemeines 18
2. Sicherheit 19
3. Technische Daten 22
4. Aufbau und Funktion 23
5. Transport, Verpackung und Lagerung 24
6. Inbetriebnahme, Betrieb 25
7. Wartung und Reinigung 27
8. Störungen 27
9. Demontage, Rücksendung und Entsorgung 28
Anlage 1: EG-Konformitätserklärung Typ LH-10 30
D
Konformitätserklärungen nden Sie online unter www.wika.de.
14075011.01 08/2013 GB/D/F/E
17WIKA Betriebsanleitung Pegelsonde, Typ LH-10
1. Allgemeines
1. Allgemeines
■
Die in der Betriebsanleitung beschriebene Pegelsonde wird nach dem aktuellen Stand der Technik konstruiert und
gefertigt. Alle Komponenten unterliegen während der Fertigung strengen Qualitäts- und Umweltkriterien. Unsere
Managementsysteme sind nach ISO 9001 und ISO 14001 zertiziert.
■
Diese Betriebsanleitung gibt wichtige Hinweise zum Umgang mit dem Gerät. Voraussetzung für sicheres Arbeiten ist
D
die Einhaltung aller angegebenen Sicherheitshinweise und Handlungsanweisungen.
■
Die für den Einsatzbereich des Gerätes geltenden örtlichen Unfallverhütungsvorschriften und allgemeinen
Sicherheitsbestimmungen einhalten.
■
Die Betriebsanleitung ist Produktbestandteil und muss in unmittelbarer Nähe des Gerätes für das Fachpersonal
jederzeit zugänglich aufbewahrt werden.
■
Das Fachpersonal muss die Betriebsanleitung vor Beginn aller Arbeiten sorgfältig durchgelesen und verstanden
haben.
■
Die Haftung des Herstellers erlischt bei Schäden durch bestimmungswidrige Verwendung, Nichtbeachten dieser
Betriebsanleitung, Einsatz ungenügend qualizierten Fachpersonals sowie eigenmächtiger Veränderung am Gerät.
■
Es gelten die allgemeinen Geschäftsbedingungen in den Verkaufsunterlagen.
■
Technische Änderungen vorbehalten.
■
Weitere Informationen:
- Internet-Adresse:www.wika.de / www.wika.com
- zugehöriges Datenblatt:PE 81.09
- Anwendungsberater:Tel.: +49 9372 132-8976
Fax: +49 9372 132-8008976
support-tronic@wika.de
18WIKA Betriebsanleitung Pegelsonde, Typ LH-10
14075011.01 08/2013 GB/D/F/E