WIKA IS-20, IS-21 Operating Manual

IS-20-S, IS-21-S, IS-20-F, IS-21-F, IS-20-H
Operating instructions Betriebsanleitung Mode d'emploi
Pressure Transmitter
Druckmessumformer
Transmetteur de pression
WIKA Alexander Wiegand GmbH & Co. KG
Alexander-Wiegand-Straße 30 63911 Klingenberg/ Germany Tel. (+49) 93 72/132-295 Fax (+49) 93 72/132-706 E-Mail support-tronic@wika.de www.wika.de
2132926.02 GB/D/F 01/2006
IS-21-S
IS-20-F
IS-20-H
D
F
Operating instructions Betriebsanleitung Mode demploi
IS-20-S, IS-21-S IS-20-F, IS-21-F IS-20-H
Pressure transmitter / Druckmessumformer / Transmetteur de pression
WIKA Alexander Wiegand GmbH & Co. KG
Alexander-Wiegand-Straße 30 63911 Klingenberg Phone (+49) 93 72/132-295 Fax (+49) 93 72/132-706 E-Mail support-tronic@wika.de www.wika.de
2132926.02 GB/D/F 01/2006
/Germany
IS-21-S
IS-20-H
IS-20-F
Contents / Inhalt / Contenu
Contents Page 3-20
1. Important details for your information
2. A quick overview for you
3. Abbreviations, signs and symbols
4. Function and accessories
5. For your safety
6. Packaging
7. Starting, operation
8. Maintenance, spare parts
9. Trouble shooting
10. Storage, disposal
11. EC declaration of conformity
Inhalt Seite 21-39
1. Wichtiges zu Ihrer Information
2. Der schnelle Überblick für Sie
3. Zeichenerklärungen, Abkürzungen
4. Funktion und Zubehör
5. Zu Ihrer Sicherheit
6. Verpackung
7. Inbetriebnahme, Betrieb
8. Wartung, Ersatzteile
9. Störbeseitigung
10. Lagerung, Entsorgung
11. EG-Konformitätserklärung
2
WIKA Operating instructions / Betriebsanleitung / Mode d'emploi IS-2
GB
Contenu Page 40-59
1. Informations inportantes
2. Aperçu rapide
3. Explication des symboles,abréviations
4. Fonction et accessoires
5. Pour votre sécurité
6. Emballage
7. Mise en service, exploitation
8. Entretien, Pièces de rechange
9. Elimination de perturbations
10. Stockage, mise au rebus
11. Déclaration de conformité CE
Contents/Inhalt/Contenu
D
12. Control Drawing FM, CSA 60
Current terms and conditions apply. Details are available on www.wika.de
Es gelten unsere aktuellen Verkaufs- und Lieferbedingungen siehe unter www.wika.de
Toute commande est assujettie à nos conditions de ventes et de fournitures dans leur dernière version en vigueur, voir sous www.wika.de
S -S, IS-2 S -F, IS-20-H
GB
FDGB
F
1. Important details for your information
1. Important details for your information
GB
Read these operating instructions before installing and starting the pressure transmitter. Keep the operating instructions in a place that is accessible to all users at any time. The following installation and operating instructions have been compiled by us with great care but it is not feasible to take all possible applications into consideration. These installation and operation instructions should meet the needs of most pressure measurement applications. If questions remain regarding a specific application, you can obtain further information (data sheets, instructions, etc.) via our Internet address (www.wika.de / www.wika.com ) or contact WIKA for additional technical support (see section7 Starting, Operation/Further information). The product data sheet is designated as PE 81.50 / PE 81.51 WIKA pressure transmitters are carefully designed and manufactured using state-of-the-art technology. Every component undergoes strict quality inspection before assembly and each instrument is fully tested prior to shipment.
Use of the product in accordance with the intended use IS-2S-S, IS-2S-F, IS-20-H:
Use the intrinsically safe pressure transmitter for pressure measurement in hazardous areas.
D
F
Certificate ATEX: Pressure transmitter for operation in hazardous areas in compliance
with the respective certificate (see attached EC-type examination certificate BVS 04 ATEX E 068 X). ATEX Approval ratings: Gases and mist connection to Zone 0, Zone 1, Zone 2. Dust connection to Zone 20, Zone 21, Zone 22 (not for IS-20-H). Mining Category M1, M2.
Certificate FM/CSA: Pressure transmitter for operation in hazardous areas in compliance
with the respective certificate (see Control drawing No. 2323880, section 13). FM / CSA Approval ratings: Intrinsically Safe with entity approval for Class I, II and III Division 1, Groups A, B, C, D, E, F, G and Class I, Zone 0, AEx ia IIC Dust-ignitionproof for Class II and III, Division 1, Groups E, F, and G. Non-incendive for Class I Division 2 Groups A, B, C and D FM standards according to FMRC 3600, 3610, 3611, 3810 (including supplement #1), ISA-S12.0.01, IEC60529 (including amendment #1) CSA Standard C22.2 No. 0-M1991 / 94-M1991 / 142-M1987 / 157-M1992 UL 50, Eleventh Edition / UL 508, Seventeenth Edition / UL 913, Sixth Edition
2132926.02 GB/D/F 01/2006
WIKA Operating instructions / Betriebsanleitung / Mode d'emploi IS-2
2132926.02 GB/D/F 01/2006
S -S, IS-2 S -F, IS-20-H
3
2. A quick overview for you / 3. Abbreviations, signs and symbols
GB GB
Knowledge required: Install and start the pressure transmitter only if you are familiar with the
relevant regulations and directives of your country and if you have the qualification required. You have to be acquainted with the rules and regulations on hazardous areas, measurement and control technology and electric circuits, since this pressure transmitter is electrical equipment as defined by EN 50178. Depending on the operating conditions of your application you have to have the corresponding knowledge, e.g. of aggressive media.
2. A quick overview for you
If you want to get a quick overview, read Chapters 3, 5, 7 and 10. There you will get some short safety instructions and important information on your product and its starting. Read these chapters in any case. Get some more detailed information on this product in Chapters 4 Function and accessories and 6 Packaging. Read Chapter 8 for Maintenance. In the case of failures please refer to Chapter 9.
3. Abbreviations, signs and symbols
!
Warning
Warning
Caution
4
Potential danger of life or of severe injuries.
Potential danger of life or of severe injuries due to catapulting parts.
Potential danger of burns due to hot surfaces.
Notice, important information, malfunction.
The product complies with the applicable European directives.
Power supply
Load (e.g. display)
WIKA Operating instructions / Betriebsanleitung / Mode d'emploi IS-2
The product complies with the re­quirements of the European direc­tive 94/9/EC (ATEX) on explosion protection.
The product was tested and certi­fied by FM Approvals. It complies with the applicable US-American standards on safety (including explosion protection).
The product was tested and certi­fied by CSA International. It com­plies with the applicable Canadian and US-American standards on safety (including explosion protec­tion).
S -S, IS-2 S -F, IS-20-H
3. Abbreviations, signs and symbols / 4. Function and accessories
With a line transformer you realise the mandatory galvanic isolation of the voltage and current supply between hazardous and non-hazardous areas and ensure the safety connection data.
2-wire Two connection lines are intended for the voltage supply.
The supply current is the measurement signal. UB+/Sig+ Positive supply / measurement connection OV/Sig- Negative supply / measurement connection ATEX European guideline for explosion protection (Atmosphäre=AT, Explosion=EX) CSA Canadian Standard Association EHEDG European Hygienic Equipment Design Group FDA Food and Drug Administration FM Factory Mutual
4. Function and accessories
IS-20: Standard pressure connection (intrinsically safe). IS-21: Pressure connection with flush diaphragm (intrinsically safe) for highly viscous
S
-S Pressure transmitter (intrinsically safe), version with electrical connector or flying
IS-2
S
-F Pressure transmitter (intrinsically safe), field case version.
IS-2 IS-20-H Pressure transmitter
Function: With the pressure transmitter you measure the pressure of your application, which is trans-formed into an electric signal. This electric signal changes in proportion to the pressure and can be evaluated correspondingly.
Accessories: For details about the accessories, please refer to WIKAs price list, WIKAs product catalog on CD or WIKAs web site www.wika.de. Please refer to our data sheet Pressure gauge sealing washers AC 09.08 in WIKAs product catalog Pressure and Temperature Measurement or our web site www.wika.de for details about sealing washers.
WIKA Operating instructions / Betriebsanleitung / Mode d'emploi IS-2
2132926.02 GB/D/F 01/2006
2132926.02 GB/D/F 01/2006
or solids entrained media which might clog the pressure port.
leads.
(intrinsically safe), highest pressure version.
S -S, IS-2 S -F, IS-20-H
5
5. For your safety
5. For your safety
n Select the appropriate pressure transmitter with regard to scale range,
!
Warning
n Open pressure connections only after the system is without pressure! n Please make sure that the pressure transmitter is only used within the overload
n Observe the ambient and working conditions outlined in section 7 Technical data. n Ensure that the pressure transmitter is only operated in accordance with the
n Do not interfere with or change the pressure transmitter in any other way than
n Remove the pressure transmitter from service and mark it to prevent it from being
n Take precautions with regard to remaining media in removed pressure
n Have repairs performed by the manufacturer only. n Consider the details given in the EC-type examination certificate as well as the
Information about material consistency against corrosion and diffusion can be found in our WIKA-Handbook, 'Pressure and Temperature Measurement'.
6
performance and specific measurement conditions prior to installing and starting the instrument.
n Observe the relevant national regulations (e.g.: EN 50178, NEC, CEC) and
observe the applicable standards and directives for special applications (e.g. with dangerous media such as oxygen, acetylene, flammable gases or liquids and toxic gases or liquids and with refrigeration plants or compressors).
If you do not observe the appropriate regulations, serious injuries and/or damage can occur!
threshold limit at all times!
provisions, i.e. as described in the following instructions.
described in these operating instructions
used again accidentally, if it becomes damaged or unsafe for operation.
transmitter. Remaining media in the pressure port may be hazardous or toxic!
respective specifications for explosion hazard use of the country concerned (e.g.: IEC 60079, NEC, CEC). If you do not observe these stipulations, serious injuries and/or damage can occur.
WIKA Operating instructions / Betriebsanleitung / Mode d'emploi IS-2
.
S -S, IS-2 S -F, IS-20-H
GB
5. For your safety
Special advice for intrinsic safety
n Protect the diaphragm against any contact with abrasive substances and
!
Warning
Measurement of process media with higher temperatures than the media temperature ranges specified in the tables of the EC-type examination certificate under item 15.1.2 is permissible, if special cooling elements are used (not for IS-20-H).
!
Warning
n Ensure an unhindered air circulation at the cooling element. n Protect the pressure transmitter against touching or affix a warning notice. n Insulate heat sources thermally from the pressure transmitter (e.g. pipes or tanks) n Protect the cooling element against contamination and dust deposits.
Special wiring advice
!
Warning
n Connect the shield to ground exclusively in safe (i.e. non-hazardous) areas in
n Consider both the internal capacitance and inductance. n Consider that cables for use in zones 1 and 2 must be checked with a test voltage
n Cover flying leads with fine wires by an end splice (cable preparation).
WIKA Operating instructions / Betriebsanleitung / Mode d'emploi IS-2
2132926.02 GB/D/F 01/2006
2132926.02 GB/D/F 01/2006
pressure peaks and do not touch it with tools. If you damage the diaphragm, no intrinsic safety can be guaranteed (ATEX, FM, CSA)!
n Ensure that under hazardous dust ennvironment the pressure transmitter is
mounted in a shielded section and protect it against shocks.
n Observe the permissible surface temperatures applicable for this range
according to the defined temperature classes.
n Observe the maximum temperature value (of the temperature range defined
under item 15.1.2 in the EC-type examination certificate) at the hexagon of the tubular case.
n The bayonet-connector is made of light metal, a material which is not
permissible for group I applications (mining).
n Always connect the case to earth to protect the pressure transmitter against
electromagnetic fields and electrostatic charges.
accordance with EN 60079-14. Ensure that with flying leads the shield is always connected to ground on the instrument side by the manufacturer.
between conductor/earth, conductor/screen, screen/earth of more than 500V (AC).
S -S, IS-2 S -F, IS-20-H
GB
.
7
5. For your safety / 6. Packaging
Installation in / connection to zone 0 and zone 20 (zone 20 not with IS-20-H)
(In general Zone 0 is given when the pressure transmitter is surrounded by a mixture of explosive gases more than 1.000 hours per year = continuous hazard).
n For the seperation of the zones the pressure transmitter or the cable gland
!
Warning
in the wall must have the ingress protection according to IEC 60 529 namely for zone 0: IP 67 and for zone 20: IP 6X.
n Observe the technical data for the use of the pressure transmitter in
connection with aggressive / corrosive media and for the avoidance of mechanical hazards.
n Lay out the circuits according to type Ex ia.
6. Packaging
n Inspect the pressure transmitter for possible damage during transportation.
Should there be any obvious damage, inform the transport company and WIKA without delay.
n Keep the packaging, as it offers optimal protection during transportation
(e.g. changing installation location, shipment for repair).
n Keep the protection cap of the pressure connection thread and the diaphragm
for later storage or transport.
In order to protect the diaphragm, the pressure connection of the instrument IS-21-S, -F is provided with a special protection cap.
n Remove this protection cap only just before installing the pressure transmitter
in order to prevent any damage to the diaphragm.
n Mount the protection cap when removing and transporting the instrument. n Ensure that the pressure connection thread and the connection contacts will
not be damaged.
8
WIKA Operating instructions / Betriebsanleitung / Mode d'emploi IS-2
S -S, IS-2 S -F, IS-20-H
GB
7. Starting, operation
7. Starting, operation
Has everything been supplied?
Check the scope of supply: n Completely assembled pressure transmitters; with flush version IS-21-S, -F
including pre-assembled sealings and protection cap.
n EC-type examination certificate
Required tools: wrench (flats 27), screw driver
Diaphragm test for your safety
It is necessary that before starting the pressure transmitter you test the diaphragm, as this is a safety-relevant component.
n Pay attention to any liquid leaking out, for this points to a diaphragm damage
(not necessary for IS-20-H).
n Check the diaphragm visually for any damage. n Use the pressure transmitter only if the diaphragm is undamaged. n Use the pressure transmitter only if it is in a faultless condition as far as the
safety-relevant features are concerned.
n Remove the protection cap only just before installation and absolutely avoid
any damage to the diaphragm during installation as well.
n Ensure that the cable diameter you select fits to the cable gland of the
connector. Ensure that the cable gland of the mounted connector is positioned correctly and that the sealings are available and undamaged. Tighten the threaded connection and check the correct position of the sealings in order to ensure the ingress protection.
n When mounting the instrument, ensure that the sealing faces of the instrument
and the measuring point are clean and undamaged.
n Screw in or unscrew the instrument only via the flats using a suitable tool and
and the prescribed torque. Do not use the case as working surface for screwing in or unscrewing the instrument.
n When screwing the transmitter in, ensure that the threads are not jammed.
S -S, IS-2 S -F, IS-20-H
2132926.02 GB/D/F 01/2006
2132926.02 GB/D/F 01/2006
!
Warning
Installation
WIKA Operating instructions / Betriebsanleitung / Mode d'emploi IS-2
GB
9
7. Starting, operation
IS-20-F , IS-21-F
max. 50Nm
Sealing
For Model IS-20-S/-F the sealing ring is avail­able as an optional extra. For Model IS-21-S/-F the sealing ring is included in delivery.
For tapped holes and welding sockets please see Technical Information IN 00.14 for download at www.wika.de -Service
Wiring: Ingress protection per IEC 60529
(The ingress protection classes specified only apply while the pressure transmitter is connected with female connectors that provide the corres-ponding ingress protection). Please make sure that the ends of cables with flying leads do not allow any ingress of moisture.
(D) Mounting hole
IS-20-S, IS-21-S
max. 50Nm
Product label (example)
Coded manufacture date Signal
Power Supply
P #
Product No. Order code Serial No.
S #
PIN assignment
(2)
(3)
(4)
(1)
(5)
Female connector
(6)
Sealing
Clamping nut, Male connector, Case with pressure connection
GB
7. Starting, operation
1. Loosen the screw (1).
2. Loosen the cable gland (2).
3. Pull the angle housing (5), with the terminal block (6) inside, away from the instrument.
4. Using the head of a small screwdriver in the mounting hole (D), lever the terminal block (6) out of the angle housing (5). In order not to damage the sealing of the angle housing, do not try to push the terminal block (6) out using the screw hole (1) or the cable gland (2).
5. Ensure that the conducteur outer diameter you select is matched to the angle housings cable gland. Slide the cable through the cable gland nut (2), washer (3), gland seal (4) and angle housing (5).
6. Connect the flying leads to the screw terminals on the terminal block (6) in accordance with the pin-assignment drawing.
7. Press the terminal block (6) back into the angle housing (5).
8. Tighten the cable gland (2) around the cable. Make sure that the sealing isnt damaged and that the cable gland and seals are assembled correctly in order to ensure ingress protection.
9. Place the flat, square gasket over the connection pins on the top of the instru­ment housing.
10. Slide the terminal block (6) onto the connection pins.
11. Secure the angle housing (5) and terminal block (6) to the instrument with the screw (1).
Model IS-20-S, IS-21-S, IS-20-H 2-wire
L-Connector, DIN EN 175301-803, Form A, for conducter cross section up to max. 1.5 mm², conducter outer diameter 6 to 8 mm (ship approval: 10 to 14 mm), IP 65, Order code: A4 and G (ship approval)
Non hazardous area Hazardous (classified) area
GB
10
WIKA Operating instructions / Betriebsanleitung / Mode d'emploi IS-2
S -S, IS-2 S -F, IS-20-H
2132926.02 GB/D/F 01/2006
WIKA Operating instructions / Betriebsanleitung / Mode d'emploi IS-2
2132926.02 GB/D/F 01/2006
S -S, IS-2 S -F, IS-20-H
11
7. Starting, operation
Flying leads, conducter cross section up to max. 0.5 mm ²/AWG 20 with end splices,
Non hazardous area
Hazardous (classified) area
brown
GB
conducter outer diameter 6.8 mm, IP67, Order-Code: DL / zero/span not adjustable, IP68,Order-Code:EM/ zero/span adjustable, IP68, Order-Code: XM
Circular connector M 12x1, IP 67, Order-Code: M4
Non hazardous area Hazardous (classified) area
Cable connection in the spring clip terminal
n Cover the stripped wire ends with end splices. n Unscrew the case cover.
Bayonet-connector, IP 67 / Order-Code: C6
Non hazardous area Hazardous (classified) area
Model IS-20-F, IS-21-F, IS-20-H with field case
Order-Code: FC, FH
Non hazardous area
green
screen
Hazardous (classified) area
n Loosen the cable gland using an open-end
wrench, wrench size 24.
n Lead the cable through the cable gland into
the opened case head.
n Press the corresponding plastic lever at the
spring clip terminal down using a screw driver, so that the clamped contact will be released.
n Lead the prepared flying lead into the opening and let go of the plastic lever, so that the
flying lead will be squeezed inside the spring clip terminal.
n After connecting the individual wires, tighten the cable gland and screw down the case over.
12
WIKA Operating instructions / Betriebsanleitung / Mode d'emploi IS-2
S -S, IS-2 S -F, IS-20-H
7. Starting, operation
Function of the test circuit for 2-wire: By means of the test circuit the current can be me­tered during normal operation without having to disconnect the instrument. For that purpose you have to connect an ammeter (for applications in hazardous areas; internal resistance < 15 Ohm) to the test +/- terminals.
Specifications Model IS-20-S, IS-21-S, IS-20-F, IS-21-F, IS-20-H
Specifications without model designation apply for all models.
Pressure ranges *) IS-2 Over pressure safety IS-2 Burst pressure IS-2 Pressure ranges *)IS-2 Over pressure safety IS-2 Burst pressure IS-2 Pressure ranges *) IS-2 Over pressure safety IS-2 Burst pressure IS-2
Materials
Wetted parts
n
Model IS-20-S, IS-20-F, IS-20-H *
Ø
Model IS-21-S, IS-21-F
Ø
n Case Stainless steel Internal transmission fluid
WIKA Operating instructions / Betriebsanleitung / Mode d'emploi IS-2
2132926.02 GB/D/F 01/2006
2132926.02 GB/D/F 01/2006
S S S
S S S
S S S
3)
-S, IS-2
-S, IS-2
-S, IS-2
-S, IS-2
-S, IS-2
-S, IS-2
-S, IS-2
-S, IS-2
-S, IS-2
S
-F bar 0.1 0.16 0.25 0.4 0.6 1 1.6 2.5
S
-F bar 1 1.5 2 2 4 5 10 10
S
-F bar 2 2 2.4 2.4 4.8 6 12 12
S
-F bar 4 6 10 16 25 40 60 100
S
-F bar 17 35 35 80 50 80 120 200
S
-F bar 20.5 42 42 96 96 400 550 800
S
-F bar 160 250 400 600 1000
S
-F bar 320 500 800 1200 1500
S
-F bar 1000 1200 17002)24002)3000
Pressure ranges for IS-20-H see additional operating instructions 11126418 High pressure {Vacuum, gauge pressure, compound range, absolute pressure are available}
1)
Only Model IS-20-S, IS-20-F.
2)
For model IS-21-S, IS-21-F: the value specified in the table applies only when sealing is realised with the sealing ring underneath the hex. Otherwise max. 1500 bar applies.
)
3)
Not for model IS-20-S, IS-20-F with pressure ranges > 25 bar and IS-20-H
(other materials see WIKA diaphragm seal program)
Stainless steel
Stainless steel {Hastelloy C4} O-ring: NBR {FPM/FKM or EPDM}
Synthetic oil {Halocarbon oil for oxygen applications} {Listed by FDA for Food & Beverage}
S -S, IS-2 S -F, IS-20-H
1)
GB
13
7. Starting, operation
)
GB
7. Starting, operation
GB
Specifications Model IS-20-S, IS-21-S, IS-20-F, IS-21-F, IS-20-H Specifications Model IS-20-S, IS-21-S, IS-20-F, IS-21-F, IS-20-H
8)
Power supply U
B
UB in DC V
10 < U
30
B
(11 < UB < 30 with model IS-2
-F and IS-20-H with field case)
S
Signal output and 4 ... 20 mA, 2-wire maximum load R
Model IS-2
Ø
Model IS-2
Ø
A
S
-S
S
-F, IS-20-H with
RA in Ohm
RA ≤ (UB–10 V) / 0.02 A–(length of flying leads in m x0,14Ohm
≤ (UB – 11 V) / 0.02 A
R
A
field case
S
Test circuit signal and maximum load RA < 15 (only model IS-2 Adjustability zero/span % Response time (10 ... 90 %) ms < 1
4)
Response time IS-20-S/-F: < 10 ms at medium temp. Below <-30°C for pressure ranges up to 25 bar. Response time IS-21: < 10 ms at medium temp. below < -30 °C (-22°F).
10 using potentiometers inside the instrument
±
4)
-F, IS-20-H with field case)
Dielectric strength Insulation complies with EN 50020, 6.4, 12 Accuracy % of span
% of span
5)
Accuracy
6
)
Including non-linearity, hysteresis, non-repeatability, zero signal and full scale error (corresponds to error of measurement per IEC 61298-2). Adjusted in vertical mounting position with lower pressure connection.
Non-linearity % of span 1-year stability % of span Permissible temperature of n Medium 7)
9) *)
0.25 {0.125}
0.5 {0.25}
for pressure ranges > 0.25 bar, not for IS-20-H
{ }
0.2 (BFSL) according to IEC 61298-2
0.2 (at reference conditions)
-20 ... +80 °C
5) 6)
8)
6)
(BFSL)
-4 ... +176 °F (Extended temperature ranges see chapter 7 Relation of medium temperature to ambient temperature“)
-20 ... +80 °C
8)
-4 ... +176 °F
-30 ... +105 °C -22 ... +221 °F
n Ambience 7) n Storage
7)
9)
7)
Also complies with EN 50178, Tab. 7, Operation (C) 4K4H, Storage (D) 1K4, Transport (E) 2K3
Compensated temp range 0 ... +80 °C 32 ... +176 °F Temperature coefficients within compensated temp range n Mean TC of zero % of span
Mean TC of range % of span
n
d
- protection
Ignition protection type EEx ia I/II C T4, EEx ia I/II C T5, EEx ia I/II C T6
– protection
Ex
Ignition protection type Instrinsic safe Class I, II, III Division 1,
a
- conformitiy
FM, CSA FM standards according to FMRC 3600, 3610, 3611
8)
8)
HF-immunity V/m 10 BURST KV 2 Shock resistanceØ Model IS-2
Model IS-2
Ø
S
-S g 1000 according to IEC 60068-2-27 (mechanical shock)
S
-F g 600 according to IEC 60068-2-27 (mechanical shock)
Other temperature ranges are possible, depending on the electrical connection; see EC-type examination certificate, e.g. -30…+105 °C / -22 ... +221 °F
0.2 / 10 K (< 0,4 for pressure range < 250 mbar)
0.2 / 10 K
ATEX Category 9) 1G, 1/2G, 2G, 1D
9)
the operating conditions and safety-relevant data in the
Read EC-type examination certificate in any case
10)
Not for IS-20-H
10)
10)
, 2D
10)
, M1, M2
, 1/2D
(BVS 04 ATEX E 068 X)
FM, CSA Class I, II and III
Group A, B, C, D, E, F, G and Class I, Zone 0 AEx ia II C 89/336/EEC interference emission and immunity see
EN 61 326, interference emission limit class A and B ATEX EN 50 014 (general part), EN 50 020 (instrinsic safety), {EN 50 284 (Zone 0)}, {EN 50 281-1 (dust -Ex)}, {EN 50 303 (mining industry)}
(including supplement #1), ISA-S12.0.01, IEC 60 529 (including amendment #1), CSA standard C22.2 No. 0-M1991 / 142-M1987 / 157-M1992, UL 50, Eleventh Edition / UL 508, Seventeenth Edition / UL 913, Sixth Edition
14
WIKA Operating instructions / Betriebsanleitung / Mode d'emploi IS-2
S -S, IS-2 S -F, IS-20-H
2132926.02 GB/D/F 01/2006
WIKA Operating instructions / Betriebsanleitung / Mode d'emploi IS-2
2132926.02 GB/D/F 01/2006
S -S, IS-2 S -F, IS-20-H
15
7. Starting, operation
GB
Specifications Model IS-20-S, IS-21-S, IS-20-F, IS-21-F, IS-20-H
Vibration resistanceØ Model IS-2
Model IS-2
Ø
Wiring protection Protected against reverse polarity and short circuiting on the
Mass
*) In an oxygen version model IS-21 is not available. In an oxygen version model IS-20 is only available in gauge pressure ranges > 0.25 bar
with media temperatures between -20 +60 °C / -4 +140 °F and using stainless steel or Elgiloy® wetted parts.
{ } Items in curved brackets are optional extras for additional price.
Model IS-2
Ø
Model IS-2
Ø
Model IS-20-H
Ø
S
-S g 20 according to IEC 60068-2-6 (vibration resonance)
S
-F g 10 according to IEC 60068-2-6 (vibration resonance)
instrument side
S
-S kg Approx. 0.2
S
-F kg Approx. 0.35
kg Approx. 0.3 (approx. 0.45 with version field case)
When designing your plant, take into account that the stated values (e.g. burst pressure, over pressure safety) apply depending on the material, thread and sealing element used.
Relation of medium temperature to ambient temperature
120 110 100
90 80 70 60 50 40 30 20 10
0
40 80 120 160 200 240 280 320
Temperature of ambient [°C]
Model Version
Cooling fin - 2 3 5 Constant K 0.34 0.47 0.68 0.76
IS-20-H IS-2
A B
Calculation of max. temperature of ambience:
= T
16
+ (TB - T
med
T
amb
) / K
med
WIKA Operating instructions / Betriebsanleitung / Mode d'emploi IS-2
A
5
-S/ -F
C
B
C
D
Temperature of medium [°C]
Calculation of cooling element: T
= T
- (T
- T
B
med
D
T
B
T
med
T
amb
K = Constant of cooling element
med
= Operation temperature of transmitter = max. temperature of process medium = max. temperature of ambience
) x K
amb
S -S, IS-2 S -F, IS-20-H
7. Starting, operation
Functional test
Warning
Caution
Adjustment of zero point/span (only for pressure transmitter with clamping nut and field case) IS-20-S, IS-21-S, IS-20-H:
A
A
2132926.02 GB/D/F 01/2006
2132926.02 GB/D/F 01/2006
n Open pressure connections only after the system is without pressure! n Observe the ambient and working conditions outlined in section 7 Technical
data.
n Please make sure that the pressure transmitter is only used within overload
threshold limit at all times! When touching the pressure transmitter, keep in mind that the surfaces of the
instrument components might get hot during operation.
The output signal must be proportional to the pressure. If not, this might point to a damage of the diaphragm. In that case refer to chapter 9 Troubleshooting.
IS-20-F, IS-21-F, IS-20-H with field case:
Female connector
Sealing Clamping
nut
Male connector
Sealing
S = Span
Case with pressure connection
WIKA Operating instructions / Betriebsanleitung / Mode d'emploi IS-2
C
B
Z = Zero
Z = Zero
S -S, IS-2 S -F, IS-20-H
GB
S = Span
17