Operating Instructions
Process pressure transmitter IPT-1* Vers. 3.0 - metalic
sensor
Probus PA
Page 2
Contents
1 About this document
4
1.2 Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
1.3 Symbolism used . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
2 For your safety
2.1 Authorised personnel . . . . . . . . . . . . . . . . . . . . . . . .
5
2.2 Appropriate use . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
2.3 Warning about misuse . . . . . . . . . . . . . . . . . . . . . . .
5
2.4 General safety instructions . . . . . . . . . . . . . . . . . . . .
5
2.5 Safety approval markings and safety tips . . . . . . . . . .
6
2.6 CE conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
2.7 Fulllment of NAMUR recommendations . . . . . . . . . .
6
2.8 Safety instructions for Ex areas . . . . . . . . . . . . . . . . .
6
2.9 Safety instructions for oxygen applications . . . . . . . . .
6
3 Product description
3.1 Conguration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
3.2 Principle of operation . . . . . . . . . . . . . . . . . . . . . . . .
8
3.3 Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
3.4 Packaging, transport and storage . . . . . . . . . . . . . . .
9
4 Mounting
4.1 General instructions . . . . . . . . . . . . . . . . . . . . . . . . .
10
4.2 Mounting instructions . . . . . . . . . . . . . . . . . . . . . . . .
12
4.3 Mounting steps. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12
5 Connecting to power supply
5.1 Preparing the connection . . . . . . . . . . . . . . . . . . . . .
13
5.2 Connection procedure. . . . . . . . . . . . . . . . . . . . . . . .
14
5.3 Wiring plan, single chamber housing . . . . . . . . . . . . .
15
16
5.5 Switch on phase. . . . . . . . . . . . . . . . . . . . . . . . . . . .
18
6 Set up with the indicating and adjustment module
6.1 Short description . . . . . . . . . . . . . . . . . . . . . . . . . . .
20
6.2 Insert indicating and adjustment module. . . . . . . . . . .
20
6.3 Adjustment system . . . . . . . . . . . . . . . . . . . . . . . . . .
22
6.4 Setup procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . .
23
6.5 Menu schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . .
32
6.6 Saving the parameter adjustment data . . . . . . . . . . . .
34
7 Setup with PDM
7.1 Parameter adjustment with PDM . . . . . . . . . . . . . . . .
35
8 Maintenance and fault rectication
8.1 Maintenance, cleaning . . . . . . . . . . . . . . . . . . . . . . .
36
8.2 Remove interferences . . . . . . . . . . . . . . . . . . . . . . . .
36
2 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
Contents
31544-EN-081211
Page 3
8.3 Instrument repair . . . . . . . . . . . . . . . . . . . . . . . . . . .
38
9 Dismounting
9.1 Dismounting steps . . . . . . . . . . . . . . . . . . . . . . . . . .
39
9.2 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
39
10 Supplement
10.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
40
10.2 Information on Probus PA . . . . . . . . . . . . . . . . . . . .
46
10.3 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
51
Supplementary documentation
Information:
Supplementary documents appropriate to the ordered version come with the delivery. You can nd them listed in chapter "Product
description".
Instructions manuals for accessories and replacement parts
Tip:
To ensure reliable setup and operation of your IPT-1* Vers. 3.0, we oer accessories and replacement parts. The associated documents are:
l Operating instructions manual "External indicating and adjustment
unit"
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor • Probus PA 3
Contents
31544-EN-081211
Page 4
1 About this document
1.1 Function
This operating instructions manual provides all the information you need for mounting, connection and setup as well as important instructions for maintenance and fault rectication. Please read this information before putting the instrument into operation and keep this manual accessible in the immediate vicinity of the device.
1.2 Target group
This operating instructions manual is directed to trained qualied personnel. The contents of this manual should be made available to these personnel and put into practice by them.
1.3 Symbolism used
Information, tip, note
This symbol indicates helpful additional information.
Caution: If this warning is ignored, faults or malfunctions can result. Warning: If this warning is ignored, injury to persons and/or serious damage to the instrument can result. Danger: If this warning is ignored, serious injury to persons and/or destruction of the instrument can result.
Ex applications
This symbol indicates special instructions for Ex applications.
l List
The dot set in front indicates a list with no implied sequence.
à Action
This arrow indicates a single action.
1 Sequence
Numbers set in front indicate successive steps in a procedure.
4 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
1 About this document
31544-EN-081211
Page 5
2 For your safety
2.1 Authorised personnel
Mount and set up the pressure transmitter only if you know the applicable national regulations and have the appropriate qualication. You must be aquainted with the regulations and instructions for hazardous areas, measurement and control technology as well as electrical circuits because the pressure transmitter is "electrical equipment" according to EN 50178. Depending on the application conditions, it is necessary that you have appropriate knowledge, e.g. concerning corrosive products or high pressure.
2.2 Appropriate use
IPT-1* Vers. 3.0 is a pressure transmitter for measurement of gauge pressure, absolute pressure and vacuum.
You can nd detailed information on the application range in chapter
"Product description".
Operational reliability is ensured only if the instrument is properly used according to the specications in the operating instructions manual as well as possible supplementary instructions.
For safety and warranty reasons, any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer. Arbitrary conversions or modications are explicitly forbidden.
2.3 Warning about misuse
Inappropriate or incorrect use of the instrument can give rise to application-specic hazards, e.g. vessel overll or damage to system components through incorrect mounting or adjustment.
2.4 General safety instructions
This is a high-tech instrument requiring the strict observance of standard regulations and guidelines. The user must take note of the safety instructions in this operating instructions manual, the country­specic installation standards as well as all prevailing safety regulations and accident prevention rules.
The instrument must only be operated in a technically awless and reliable condition. The operator is responsible for trouble-free operation of the instrument.
During the entire duration of use, the user is obliged to determine the compliance of the required occupational safety measures with the current valid rules and regulations and also take note of new regulations.
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 5
2 For your safety
31544-EN-081211
Page 6
2.5 Safety approval markings and safety tips
The safety approval markings and safety tips on the device must be observed.
2.6 CE conformity
This device fullls the legal requirements of the applicable EC guidelines. By attaching the CE mark, VEGA provides a conrmation of successful testing.
2.7 Fulllment of NAMUR recommendations
With respect to interference resistance and emitted interference, the NAMUR recommendation NE 21 is fullled.
With respect to compatibility, the NAMUR recommendation NE 53 is
fullled. This applies also to the corresponding indicating and adjustment components. WIKA instruments are generally upward and downward compatible.
l Sensor software for DTM IPT-1* Vers. 3.0 HART, PA or FF l DTM IPT-1* Vers. 3.0 for adjustment software PACTware l Indicating and adjustment module for sensor software
The parameter adjustment of the basic sensor functions is indepen­dent of the software version. The range of available functions depends on the respective software version of the individual components.
The software version of IPT-1* Vers. 3.0 can be determined as follows:
l via PACTware l on the type label of the electronics l via the indicating and adjustment module
2.8 Safety instructions for Ex areas
Please note the Ex-specic safety information for installation and operation in Ex areas. These safety instructions are part of the operating instructions manual and come with the Ex-approved instruments.
2.9 Safety instructions for oxygen applications
For instruments in oxygen applications the special instructions in chapters "Storage and transport", "Mounting" as well as "Technical data" under "Process conditions"must be noted. Furthermore the valid national regulations, implementation instructions and memorandums of the BG (professional assoc.) must be noted.
6 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
2 For your safety
31544-EN-081211
Page 7
3 Product description
3.1 Conguration
The scope of delivery encompasses:
l IPT-1* Vers. 3.0 process pressure transmitter l Documentation
- this operating instructions manual
- Operating instructions manual "Indicating and adjustment
module" (optional)
- Supplementary instructions manual "Plug connector for con- tinuously measuring sensors" (optional)
- Ex-specic "Safety instructions" (with Ex-versions)
- if necessary, further certicates
Instruments in the version "Oil and grease-free for oxygen ap- plications" are equipped with a supplementary label. The sup-
plementary label contains instructions on oil and grease-free parts of the instrument.
IPT-1* Vers. 3.0 consists of the following components:
l Process tting with measuring cell l Housing with electronics, optionally available with plug connector l Housing cover, optionally available with indicating and adjustment
module
The components are available in dierent versions.
1
2
3
Fig. 1: Example of a IPT-1* Vers. 3.0 with manometer connection G½ A according to EN 837 and Alu housing
1 Housing cover with integrated indicating and adjustment module (optional) 2 Housing with electronics 3 Process tting with measuring cell
The type label contains the most important data for identication and use of the instrument:
l Article number
Scope of delivery
Supplementary label
"Oil and grease-free for oxygen applications"
Components
Type label
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 7
3 Product description
31544-EN-081211
Page 8
l Serial number l Technical data
3.2 Principle of operation
IPT-1* Vers. 3.0 is a pressure transmitter for measurement of overpressure, absolute pressure or vacuum. Measured products are gases, vapours and liquids in measuring ranges up to 4000 bar (400 MPa); with front-flush version also viscous liquids in measuring ranges up to 600 bar (60 MPa).
The process pressure acts on the sensor element via the stainless steel diaphragm. The process pressure causes a resistance change which is converted into a corresponding output signal and outputted as measured value.
1)
Power supply via the Probus DP/PA segment coupler. A two-wire cable according to Probus specication serves as carrier of both power and digital data transmission for multiple sensors. The instrument prole of IPT-1* Vers. 3.0 corresponds to prole specifi- cation version 3.0.
The GSD (instrument master les) and bitmap les necessary for planning your Probus-DP-(PA) communication network are available from the download section on the WIKA homepage
www.wika.com under "Service". There you can also nd the appropriate certicates. In a PDM environment, an EDD (Electronic Device Description) is also required to enable the full range of sensor functions (also available as a download).A CD with the appropriate les can be ordered via e-mail under info@de.WIKA.com or by phone from one of the WIKA agencies.
The backlight of the indicating and adjustment module is powered by the sensor. Prerequisite is a certain level of operating voltage.
The data for power supply are specied in chapter "Technical data".
This function is available at a later date for instruments with StEx, WHG or ship approval as well as country-specic approvals such as those according to FM or CSA.
3.3 Operation
IPT-1* Vers. 3.0 can be adjusted with dierent adjustment media:
l with indicating and adjustment module l the Simatic adjustment program PDM
The entered parameters are generally saved in IPT-1* Vers. 3.0, optionally also in the indicating/adjustment module.
1)
Measuring ranges up to 16 bar: piezoresistive sensor element with internal transmission liquid, with measuring ranges up to 25 bar: Strain gauge (DMS) sensor element on the rear of the stainless steel diaphragm (dry).
Application area
Functional principle
Power supply and bus
communication
GSD/EDD
8 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
3 Product description
31544-EN-081211
Page 9
3.4 Packaging, transport and storage
Your instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test according to DIN EN 24180.
The packaging of standard instruments consists of environment­friendly, recyclable cardboard. For special versions, PE foam or PE foil is also used. Dispose of the packaging material via specialised recycling companies.
Instruments for oxygen applications are sealed in PE foil and provided with a label "Oxygen! Use no Oil". Remove this foil just before mounting the instrument! See instruction under "Mounting".
Transport must be carried out under consideration of the notes on the transport packaging. Nonobservance of these instructions can cause damage to the device.
The delivery must be checked for completeness and possible transit damage immediately at receipt. Ascertained transit damage or concealed defects must be appropriately dealt with.
Up to the time of installation, the packages must be left closed and stored according to the orientation and storage markings on the outside.
Unless otherwise indicated, the packages must be stored only under the following conditions:
l Not in the open l Dry and dust free l Not exposed to corrosive media l Protected against solar radiation l Avoiding mechanical shock and vibration
l Storage and transport temperature see chapter "Supplement -
Technical data - Ambient conditions"
l Relative humidity 20 85 %
Packaging
Transport
Transport inspection
Storage
Storage and transport
temperature
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 9
3 Product description
31544-EN-081211
Page 10
4 Mounting
4.1 General instructions
Make sure that all parts of the instrument in contact with the measured product, especially the sensor element, process seal and process tting, are suitable for the existing process conditions such as process pressure, process temperature as well as t he chemical properties of the medium.
You can nd the specications in chapter "Technical data" in the or on the type label.
Caution:
After removal of the diaphragm protective cover, the diaphragm must not be pressed.
Select an installation position you can easily reach for mounting and connecting as well as later retrotting of an indicating and adjustment module. The housing can be rotated by 330° without the use of any tools. You can also install the indicating and adjustment module in four dierent positions (each displaced by 90°).
Use the recommended cables (see chapter "Connecting to power supply") and tighten the cable gland.
You can give your instrument additional protection against moisture penetration by leading the connection cable downward in front of the cable entry. Rain and condensation water can thus drain off. This applies mainly to outdoor mounting as well as installation in areas where high humidity is expected (e.g. through cleaning processes) or on cooled or heated vessels.
Fig. 2: Measures against moisture penetration
Suitability for process conditions
Diaphragm pro­tection
Mounting position
Moisture
10 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
4 Mounting
31544-EN-081211
Page 11
The ventilation of the measuring cell is realised by a lter element in the socket of the electronics housing. The ventilation of the electronics housing is realised via an additional lter element around the cable glands.
2)
1
2
Fig. 3: Position of the lter elements 1 Filter element for ventilation of the measuring cell 2 Filter element for ventilation of the electronics housing
Information:
Make sure that the lter elements are always free of buildup during operation. A pressure washer must not be used for cleaning.
Higher process temperatures mean often also higher ambient temperatures.
1
2
Fig. 4: Temperature ranges 1 Process temperature 2 Ambient temperature
Make sure that the upper temperature limits for the environment of electronics housing and connection cable specied in chapter "Technical data" are not exceeded.
2)
With previous instrument versions, ventilation and pressure compensation were carried out together via a lter element.
Ventilation and pressure compensation
Temperature limits
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 11
4 Mounting
31544-EN-081211
Page 12
Danger:
Instruments in the version "Oil and grease free for oxygen" should be unpacked just before mounting. After the protective cover of the process tting has been removed, the label "O" on the process tting is visible. Contamination by oil, grease and dirt should be avoided. Danger of explosion!
4.2 Mounting instructions
IPT-1* Vers. 3.0 functions in any installation position. It is mounted according to the same directives as a manometer (DIN EN 839-2).
3)
Information:
We recommend using lock ttings, measuring instrument holders and siphons from the line of WIKA accessories.
4.3 Mounting steps
To mount IPT-1* Vers. 3.0, a welded socket is necessary. Use components from the line of WIKA mounting accessories.
à Note the applicable we lding standards (segment welding proce-
dure) when welding the socket.
Use the seal corresponding to the instrument:
l Process tting GD: Tesnit seal in front of the thread
- or -
Seal the thread with teon, hemp or a similar resistant seal material:
l Process tting GN
à Screw IPT-1* Vers. 3.0 into the welded socket. Tighten the
hexagon on the process tting with a suitable wrench. Wrench size, see chapter "Dimensional drawings".
Warning:
The housing must not be used to screw the instrument in! Applying tightening force can damage internal parts of the housing.
3)
Probable position correction see chapter "Setup steps".
Oxygen applica­tions
Mounting position
Welding the socket
Sealing/Screwing in
12 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
4 Mounting
31544-EN-081211
Page 13
5 Connecting to power supply
5.1 Preparing the connection
Always keep in mind the following safety instructions:
l Connect only in the complete absence of line voltage l If overvoltage surges are expected, overvoltage arresters should
be installed according to Probus specications
In hazardous areas you should take note of the appropriate
regulations, conformity and type approval certicates of the sensors and power supply units.
Power is supplied via a P robus DP/PA segment coupler. The power supply range can dier depending on the instrument version. The exact range is stated in the "Technical data".
IPT-1* Vers. 3.0 is connected with screened cable according to the Probus specication. Power supply and digital bus signal are carried
over the same two-wire connection cable.
Use cable with round cross-section. A cable outer diameter of 5 … 9 mm (0.2 0.35 in) ensures the seal eect of the cable gland. If you are
using cable with a dierent diameter or cross-section, exchange the seal or use a suitable cable gland.
Please make sure that your installation is carried out according to the Probus specication. In particular, make sure that the termination of
the bus is done with appropriate terminating resistors.
In systems with potential equalisation, connect the cable screen directly to ground potential at the power supply unit, in the connection box and at the sensor. The screen in the sensor must be connected directly to the internal ground terminal. The ground terminal outside on the housing must be connected to the potential equalisation (low impedance).
In systems without potential equalisation, connect the cable screen directly to ground potential at the power supply unit and at the sensor. In the connection box or T-distributor, the screen of the short stub to the sensor must not be connected to ground potential or to another cable screen. The cable screens to the power supply unit and to the next distributor must be connected to each other and also connected to ground potential via a ceramic capacitor (e.g. 1 nF, 1500 V). The low frequency potential equalisation currents are thus suppressed, but the protective eect against high frequency interference signals remains.
The total capacitance of the cable and of all capacitors must not exceed 10 nF in Ex applications.
Note safety instructions
Take note of
safety instruc­tions for Ex ap­plications
Select power supply
Selecting connection
cable
Cable screening and grounding
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 13
5 Connecting to power supply
31544-EN-081211
Page 14
Take note of the corresponding installation regulations for Ex applications. In particular, make sure that no potential equalisation currents ow over the cable screen. In case of grounding on both sides this can be achieved by the use of a capacitor or a separate potential equalisation.
5.2 Connection procedure
Proceed as follows:
1 Unscrew the housing cover 2 If an indicating and adjustment module is installed, remove it by
turning it slightly to the left.
3 Loosen compression nut of the cable entry 4 Remove approx. 10 cm (4 in) of the cable mantle, strip approx.
1 cm (0.4 in) insulation from the ends of the individual wires 5 Insert the cable through the cable gland into the sensor 6 Lift the opening levers of the terminals with a screwdriver (see
following illustration) 7 Insert the wire ends into the open terminals according to the wiring
plan
Fig. 5: Connection steps 6 and 7
8 Press down the opening levers of the terminals, you will hear the
terminal spring closing
Select connec­tion cable for Ex applications
14 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
5 Connecting to power supply
31544-EN-081211
Page 15
9 Check the hold of the wires in the terminals by lightly pulling on
them
10 Connect the screen to the internal ground terminal, connect the
outer ground terminal with potential equalisation
11 Tighten the compression nut of the cable entry. The seal ring must
completely encircle the cable
12 Screw the housing cover on
The electrical connection is nished.
5.3 Wiring plan, single chamber housing
The following illustrations apply to the non-Ex as well as to the Ex-ia
version.
1 2 3
5
4
5
5
4
4
Fig. 6: Material versions, single chamber housing
1 Plastic
2 Aluminium
3 Stainless steel
Housing overview
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 15
5 Connecting to power supply
31544-EN-081211
Page 16
I²C
Display
1 2 5 6 7 8
3
4
1
2
Fig. 7: Electronics and connection compartment, single chamber housing 1 Plug connector for service 2 Spring-loaded terminals for connection of the external indicating and
adjustment module
3 Ground terminal for connection of the cable screen 4 Spring-loaded terminals for voltage supply
I2C
Display
1
1 2 5
6 7 8
Fig. 8: Wiring plan, single chamber housing 1 Voltage supply/Signal output
5.4 Wiring plan, double chamber housing
The following illustrations apply to the non-Ex as well as to the Ex-ia version.
Electronics and connec­tion compartment
Wiring plan
16 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
5 Connecting to power supply
31544-EN-081211
Page 17
1 2 3
4
5
Fig. 9: Double chamber housing
1 Housing cover, connection compartment
2 Blind stopper or plug M12 x 1 for the external indicating and adjustment
module (optional)
3 Housing cover, electronics compartment
4 Filter element for air pressure compensation
5 Cable entry or plug
1
3
2
Display
1 2 5 6 7 8
I²C
Fig. 10: Electronics compartment, double chamber housing
1 Plug connector for service
2 Internal connection cable to the connection compartment
3 Terminals for the external indicating and adjustment module
Housing overview
Electronics compart-
ment
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 17
5 Connecting to power supply
31544-EN-081211
Page 18
3
1
2
Display
1 2
I²C
Fig. 11: Connection compartment, double chamber housing 1 Plug connector for service 2 Ground terminal for connection of the cable screen 3 Spring-loaded terminals for voltage supply
I2C
1
1 2
Fig. 12: Wiring plan, double chamber housing 1 Voltage supply/Signal output
5.5 Switch on phase
After IPT-1* Vers. 3.0 is connected to voltage supply or after voltage recurrence, the instrument carries out a self-check for approx. 30 seconds. The following steps are carried out:
l Internal check of the electronics l Indication of the instrument type, the rmware as well as the
sensor TAGs (sensor designation)
l Status byte goes briey to fault value
Connection compart­ment
Wiring plan
Switch on phase
18 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
5 Connecting to power supply
31544-EN-081211
Page 19
Then the current measured value will be displayed and the corre-
sponding digital output signal will be outputted to the cable.
4)
4)
The values correspond to the actual measured level as well as to the set­tings already carried out, e.g. default setting.
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 19
5 Connecting to power supply
31544-EN-081211
Page 20
6 Set up with the indicating and adjustment
module
6.1 Short description
The indicating and adjustment module is used for measured value display, adjustment and diagnosis. It can be mounted in the following housing versions and instruments:
l All sensors of the IPT-1* instrument family, in the single as well as
double chamber housing (optionally in the electronics or connec-
tion compartment)
l External indicating and adjustment unit
Note:
You can nd detailed information on adjustment in the operating instructions manual "Indicating and adjustment module".
6.2 Insert indicating and adjustment module
The indicating and adjustment module can be inserted and removed at any time. It is not necessary to interrupt the voltage supply.
For mounting, proceed as follows:
1 Unscrew the housing cover 2 Place the indicating and adjustment module in the desired position
on the electronics (you can choose any one of four dierent
positions - each displaced by 90°) 3 Press the indicating and adjustment module onto the electronics
and turn it to the right until it snaps in.
4 Screw housing cover with inspection window tightly back on
Removal is carried out in reverse order.
The indicating and adjustment module is powered by the sensor, an
additional connection is not necessary.
Function/Conguration
Mount/Dismount indicat-
ing and adjustment module
20 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
6 Set up with the indicating and adjustment module
31544-EN-081211
Page 21
Fig. 13: Mounting the indicating and adjustment module
Note:
If you intend to retrot the instrument with an indicating and adjustment
module for continuous measured value indication, a higher cover with
an inspection glass is required.
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 21
6 Set up with the indicating and adjustment module
31544-EN-081211
Page 22
6.3 Adjustment system
1.1
2
3
1
Fig. 14: Indicating and adjustment elements 1 LC display 2 Indication of the menu item number 3 Adjustment keys
l [OK] key:
- Move to the menu overview
- Conrm selected menu
- Edit parameter
- Save value
l [->] key to select:
- menu change
- list entry
- Select editing position
l [+] key:
- Change value of the parameter
l [ESC] key:
- interrupt input
- jump to the next higher menu
The sensor is adjusted via the four keys of the indicating and adjustment module. The LC display indicates the individual menu items. The functions of the individual keys are shown in the above illustration. Approx. 10 minutes after the last pressing of a key, an automatic reset to measured value indication is triggered. Any values not conrmed with [OK] will not be saved.
Key functions
Adjustment system
22 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
6 Set up with the indicating and adjustment module
31544-EN-081211
Page 23
6.4 Setup procedure
Before starting the actual parameter adjustment of a Probus PA
sensor, the address setting must rst be carried out. You will nd a
detailed description in the operating instructions manual of the
indicating and adjustment module or in the online help of PACTware or
DTM.
IPT-1* Vers. 3.0 can be used for level as well as for process pressure
measurement. D efault setting is level measurement. The mode can be
changed in the adjustment menu.
Depending on the application only the respective subchapter "Level or
process pressure measurement" is of importance. There, you nd the
individual adjustment steps.
Level measurement
Set up IPT-1* Vers. 3.0 in the following sequence:
1 Selecting adjustment unit/density unit
2 Carry out position correction
3 Carrying out min. adjustment
4 Carrying out max. adjustment
In the menu item "Adjustment unit" you select the physical unit in which
the adjustment should be carried out, e.g. mbar, bar, psi…
The position correction compensates the inuence of the mounting
position or static pressure on the measurement. It does not inuence
the adjustment values.
Information:
The steps 1, 3 and 4 are not necessary for instruments which are
already preset according to customer specications!
You can nd the d ata on the type label on the instrument or in the
menu items of the min./max. adjustment.
The indicating and adjustment module enables the adjustmetn without
lling or pressure. Thanks to this, you can carry out your settings
already in the factory without the instrument having to be installed.
The actual measured value is also displayed in the menu items for
min./max. adjustment.
In this menu item you sel ect the adjustment unit as well as the unit for
the temperature indication in the display.
To select the adjustment unit (in the example switching over from bar
to mbar) you have to proceed as follows:
5)
5)
Selection options: mbar, bar, psi, Pa, kPa, MPa, inHg, mmHg, inH
2
O,
mmH
2
O.
Address setting
Level or process pres-
sure measurement
Parameter ad­justment "Level measurement"
Select unit
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 23
6 Set up with the indicating and adjustment module
31544-EN-081211
Page 24
1 Push the [OK] button in the measured value display, the menu
overview is displayed.
Basic adjustment Display Diagnostics Service Info
2 Conrm the menu "Basic adjustment" with [OK], the menu item
"Unit" will be displayed.
Unit Unit of measurement
bar
Temperature unit °C
3 Activate the selection with [OK] and select "Units of measure-
ment with [->].
4 Activate the selection with [OK] and select the requested unit with
[->] (in the example mbar).
5 Conrm with [OK] and move to position correction with [->].
The adjustment unit is hence switched over from bar to mbar.
Information:
When switching over to adjustment in a height unit (in the example from bar to m), the density also has to be entered.
Proceed as follows:
1 Push the [OK] button in the measured value display, the menu
overview is displayed.
2 Conrm the menu "Basic adjustment" with [OK], the menu item
"Units of measurement" will be displayed.
3 Activate the selection with [OK] and select the requested unit with
[->] (in the example m).
4 Conrm with [OK], the submenu "Density unit" appears.
Unit of measurement
Density unit
kg/dm³ pcf
5 Select the requested unit, e.g. kg/dm³ with [->] and conrm with
[OK], the submenu "Density" appears.
Unit of measurement
Density
0001000 kg/dm³
24 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
6 Set up with the indicating and adjustment module
31544-EN-081211
Page 25
6 Enter the requested density value with [->] and [+], conrm with
[OK] and move to position correction with [->].
The adjustment unit is hence switched over from bar to m.
Proceed as follows to select the temperature unit:
6)
à Activate the selection with [OK] and select "Temperature unit
with [->].
à Activate the sel ection with [OK] and select the requested unit with
[->] (e.g. °F).
à Conrm with [OK].
The temperature unit is hence switched over from °C to °F.
Proceed as follows:
1 Activate in the menu item "Position correction" the selection with
[OK].
Position correction Oset
P
= +0000 mbar
53 mbar
2 Select with [->], e.g. to accept actual measured value.
Position correction Accept current measured
value?
Accept Edit
3 Conrm with [OK] and move to min.(zero) adjustment with [->].
Proceed as follows:
1 Edit the % value in the menu item "Min. adjustment" with [OK].
Min. adjustment
+000.0 %
=
+0000.0 mbar
0000.0 mbar
2 Set the requested percentage value with [+] and [->].
3 Edit the requested mbar value with [OK].
4 Set the requested mbar value with [+] and [->].
5 Conrm with [+] and move to max. adjustment with [->].
The min. adjustment is nished.
6)
Selection options: °C, °F.
Carry out position cor­rection
Carrying out min. ad­justment
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 25
6 Set up with the indicating and adjustment module
31544-EN-081211
Page 26
Information:
For an adjustment with lling, you simply enter the displayed actual measured value. If the adjustment ranges are exceeded, the message "Outside parameter limits" appears. The editing procedure can be aborted with [ESC] or the displayed limit value can be accepted with
[OK].
Proceed as follows:
1 Edit the % value in the menu item "Max. adjustment" with [OK].
Max. adjustment
+100.0 %
=
+1000.0 mbar
0000.0 mbar
Information:
The displayed pressure for 100 % corresponds to the nominal measuring range of the sensor (in the above example 1 bar =
1000 mbar).
2 Set the requested percentage value with [->] and [OK]. 3 Edit the requested mbar value with [OK]. 4 Set the requested mbar value with [+] and [->]. 5 Conrm with [OK] and move to the menu overview with [ESC].
The max. adjustment is nished.
Information:
For an adjustment with lling, you simply enter the displayed actual measured value. If the adjustment ranges are exceeded, the message "Outside parameter limits" appears. The editing procedure can be aborted with [ESC] or the displayed limit value can be accepted with
[OK].
Process pressure measurement
Set up IPT-1* Vers. 3.0 in the following sequence:
1 Select application "Process pressure measurement" 2 Select the unit of measurement 3 Carry out position correction 4 Carrying out zero adjustment 5 Carrying out span adjustment
In the menu item "Adjustment unit" you select the physical unit in which the adjustment should be carried out, e.g. mbar, bar, psi…
The position correction compensates the inuence of the mounting position or static pressure on the measurement. It does not inuence the adjustment values.
Carrying out max. ad­justment
Parameter ad­justment "Proc­ess pressure measurement"
26 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
6 Set up with the indicating and adjustment module
31544-EN-081211
Page 27
In the menu items "zero" and "span" you determine the span of the
sensor, the span corresponds to the end value.
Information:
The steps 1, 3 and 4 are not necessary for instruments which are
already preset according to customer specications!
You can nd the d ata on the type label on the instrument or in the
menu items of the zero/span adjustment.
The indicating and adjustment module enables the adjustmetn without
lling or pressure. Thanks to this, you can carry out your settings
already in the factory without the instrument having to be installed.
The actual measured value is displayed in addition to the menu items
for zero/span adjustment.
IPT-1* Vers. 3.0 is preset to application "Level measurement".
Proceed as follows when switching over to application "Process
pressure measurement":
1 Push the [OK] button in the measured value display, the menu
overview is displayed.
2 Select the menu "Service" with [->] and conrm with [OK].
Basic adjustment Display Diagnostics
Service Info
3 Select the menu item "Application" with [->] and edit with [OK].
Warning:
Note the warning: "Output can change".
4 Select with [->] "OK" and conrm with [OK].
5 Select "Process pressure" from the list and conrm with [OK].
In this menu item you sel ect the adjustment unit as well as the unit for
the temperature indication in the display.
To select the adjustment unit (in the example switching over from bar
to mbar) you have to proceed as follows:
7)
1 Push the [OK] button in the measured value display, the menu
overview is displayed.
7)
Selection options: mbar, bar, psi, Pa, kPa, MPa, inHg, mmHg, inH
2
O,
mmH
2
O.
Select application
"Process pressure measurement"
Select unit
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 27
6 Set up with the indicating and adjustment module
31544-EN-081211
Page 28
Basic adjustment Display Diagnostics Service Info
2 Conrm the menu "Basic adjustment" with [OK], the menu item
"Unit" will be displayed.
Unit Unit of measurement
bar
Temperature unit °C
3 Activate the selection with [OK] and select "Units of measure-
ment with [->].
4 Activate the selection with [OK] and select the requested unit with
[->] (in the example mbar).
5 Conrm with [OK] and move to position correction with [->].
The adjustment unit is hence switched over from bar to mbar.
Proceed as follows to select the temperature unit:
8)
à Activate the selection with [OK] and select "Temperature unit
with [->].
à Activate the sel ection with [OK] and select the requested unit with
[->] (e.g. °F).
à Conrm with [OK].
The temperature unit is hence switched over from °C to °F.
Proceed as follows:
1 Activate in the menu item "Position correction" the selection with
[OK].
Position correction Oset
P
= +0000 mbar
53 mbar
2 Select with [->], e.g. to accept actual measured value.
Position correction Accept current measured
value?
Accept Edit
3 Conrm with [OK] and move to min.(zero) adjustment with [->].
8)
Selection options: °C, °F.
Carry out position cor­rection
28 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
6 Set up with the indicating and adjustment module
31544-EN-081211
Page 29
Proceed as follows:
1 Edit the mbar value in the menu item "zero" with [OK].
Zero adjustment
000.0 %
P
=
+0000.0 mbar
0000.0 mbar
2 Set the requested mbar value with [+] and [->].
3 Conrm with [+] and move to span adjustment with [->].
The zero adjustment is nished.
Information:
The zero adjustment shifts the value of the span adjustment. The span,
i.e. the dierence between these values, however, remains unchan-
ged.
Information:
For an adjustment with pressure, you simply enter the displayed actual
measured value. If the adjustment ranges are exceeded, the message
"Outside parameter limits" appears. The editing procedure can be
aborted with [ESC] or the displayed limit value can be accepted with
[OK].
Proceed as follows:
1 Edit the mbar value in the menu item "span" with [OK].
Span adjustment
100.0 %
P
=
+1000.0 mbar
0000.0 mbar
Information:
The displayed pressure for 100 % corresponds to the nominal
measuring range of the sensor (in the above example 1 bar =
1000 mbar).
2 Set the requested mbar value with [->] and [OK].
3 Conrm with [OK] and move to the menu overview with [ESC].
The span adjustment is nished.
Information:
For an adjustment with pressure, you simply enter the displayed actual
measured value. If the adjustment ranges are exceeded, the message
"Outside parameter limits" appears. The editing procedure can be
aborted with [ESC] or the displayed limit value can be accepted with
[OK].
Carrying out zero ad­justment
Carrying out span ad­justment
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 29
6 Set up with the indicating and adjustment module
31544-EN-081211
Page 30
This function enables reading out parameter adjustment data as well as writing parameter adjustment data into the sensor via the indicating and adjustment module. A description of the function is available in the operating instructions manual "Indicating and adjustment module".
The following data are read out or written with this function:
l Measured value presentation l Adjustment l Damping l Linearisation curve l Sensor-TAG l Displayed value l Scaling unit (Out-Scale unit) l Positions after the decimal point (scaled) l Scaling PA/Out-Scale 4 values l Unit of measurement l Language
The following safety-relevant data are not read out or written:
l Sensor address l PIN l Application
Copy sensor data
Copy sensor data?
Basic adjustment
If the "Reset" is carried out, the sensor resets the values of the following menu items to the reset values (see chart):
9)
Menu section Function Reset value
Basic settings Unit of measurement bar
Temperature unit °C
Zero/Min. adjustment Measuring range begin
Span/Max. adjustment Measuring range end
Density 1 kg/l
Density unit kg/l
Damping 0 s
Linearisation linear
Sensor-TAG Sensor
Display Displayed value PA-Out
Service Additional PA value Secondary Value 1
Out-Scale-Unit Volume/l
Scaling 0.00 to 100.0
9)
Sensor-specic basic adjustment.
Copy sensor data
Reset
30 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
6 Set up with the indicating and adjustment module
31544-EN-081211
Page 31
Menu section Function Reset value
Decimal point indication 8888.8
The values of the following menu items are not reset with "Reset:
Menu section Function Reset value
Basic settings Position correction no reset
Display Lighting no reset
Service Language no reset
Application no reset
Factory setting
Like basic adjustment, furthermore special parameters are reset to
default values.
10)
Pointer
The min. and max. distance values are reset to the actual value.
Additional adjustment and diagnosis options such as e.g. scaling,
simulation or trend curve pr esentation are shown in the following menu
schematic. You will nd a detailed description of these menu items in
the operating instructions manual "Indicating and adjustment module".
10)
Special parameters are parameters which are set customer-specically on the service level with the adjustment software PACTware.
Optional settings
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 31
6 Set up with the indicating and adjustment module
31544-EN-081211
Page 32
6.5 Menu schematic
Information:
Depending on the version and application, the highlighted menu windows are not always available.
Basic adjustment
1
Basic adjustment Display Diagnostics Service Info
1.1
Sensor address
126
1.1
Unit Unit of measurement
bar
Temperature unit °C
1.2
Position correction Oset
P
=
0.2 mbar 0000 mbar
1.3
Min. adjustment
000.0 %
=
0.0 mbar
0.0 mbar
1.4
Max. adjustment
100.00 %
=
100.00 mbar
0.0 mbar
1.5
Damping
0 s
1.6
Linearisation curve
linear
1.7
Sensor-TAG
Sensor
Display
2
Basic adjustment
Display Diagnostics Service Info
2.1
Displayed value
PA-Out
2.4
Lighting
Switched o
Diagnostics
3
Basic adjustment Display
Diagnostics Service Info
3.1
Pointer p-min.: -5.8 mbar p-max.: 167.5 mbar
T-min.: -12.5 °C T-max.: +85.5 °C
3.2
Sensor status
OK
3.3.1
Trend curve
Start trend curve?
32 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
6 Set up with the indicating and adjustment module
31544-EN-081211
Page 33
Service
4
Basic adjustment Display Diagnostics
Service Info
4.1
Additional PA value
Secondary Value 1
4.2
Out-Scale-Unit
Volume
l
4.3
PA-Out-Scale
100.00 lin % = 0.0 l
0.00 lin % = 100.0 l
4.2
Simulation
Start simulation
4.3
Reset
Select reset
4.6
Language
Deutsch
4.7
Copy sensor data
Copy sensor data?
4.8
PIN
Enable?
4.9
Application
Level
Info
5
Basic adjustment Display Diagnostics Service
Info
5.1
Sensor type
Serial number
12345678
5.2
Date of manufacture e.g. 16. May 2008 Software version e.g. 3.50
5.3
Last change using PC
e.g. 16. May 2008
5.4
Sensor characteristics
Display now?
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 33
6 Set up with the indicating and adjustment module
31544-EN-081211
Page 34
6.6 Saving the parameter adjustment data
It is recommended noting the adjusted data, e.g. in this operating instructions manual and archive them afterwards. They are hence available for multiple use or service purposes.
If IPT-1* Vers. 3.0 is equipped with an indicating and adjustment module, the most important data can be read out of the sensor into indicating and adjustment module. The procedure is described in the operating instructions manual "Indicating and adjustment module" in the menu item "Copy sensor data". The data remain there permanently even if the sensor power supply fails.
If it is necessary to exchange the sensor, the indicating and adjustment module is inserted into the replacement instrument and the data are written into the sensor under the menu item "Copy sensor data".
34 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
6 Set up with the indicating and adjustment module
31544-EN-081211
Page 35
7 Setup with PDM
7.1 Parameter adjustment with PDM
For WIKA sensors, instrument descriptions for the adjustment program
PDM are available as EDD. The instrument descriptions are already
implemented in the current version of PDM. For older versions of PDM,
a free-of-charge download is available via Internet.
Go via
www.wika.com to the item "Service".
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 35
7 Setup with PDM
31544-EN-081211
Page 36
8 Maintenance and fault rectication
8.1 Maintenance, cleaning
When used in the correct way, no special maintenance is required in normal operation.
In some applications, product buildup on the sensor diaphragm can inuence the measuring result. Depending on the sensor and application, take precautions to ensure that heavy buildup, and especially a hardening thereof, is avoided.
If necessary, the transmitter has to be cleaned. In this case, make sure that the materials are resistant against the cleaning detergents.
8.2 Remove interferences
The operator of the system is responsible for taken suitable measures to remove interferences.
A maximum of reliability is ensured. Nevertheless, faults can occur during operation. These may be caused by the following, e.g.:
l Sensor l Process l Power supply l Signal processing
The rst measures to be taken are to check the output signals as well as to evaluate the error messages via the indicating and adjustment module. The procedure is described below. Further comprehensive diagnostics can be carried out on a PC with the software PACTware and the suitable DTM. In many cases, the causes can be determined in this way and faults can be rectied.
? When an additional instrument is connected, the segment fails.
l Max. supply current of the segment coupler exceeded
à Measure the current consumption, reduce size of segment
? Wrong presentation of the measured value in Simatic S5
l Simatic S5 cannot interpret the number format IEEE of the
measured value
à Insert converting component from Siemens
? In Simatic S7 the measured value is always presented as 0
l Only four bytes are consistently loaded in the PLC
à Use function component SFC 14 to load 5 bytes consistently
Reaction when malfunc­tions occur
Causes of malfunction
Fault rectication
Checking Probus PA
36 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
8 Maintenance and fault rectication
31544-EN-081211
Page 37
? Measured value on the indicating and adjustment module does not
correspond to the value in the PLC
l The menu item "Display - Display value" is not set to "PA-Out"
à Check values and correct, if necessary
? No connection between PLC and PA network
l Incorrect adjustment of the bus parameter and the segment
coupler-dependent baud rate
à Check data and correct, if necessary
? Instrument does not appear during connection setup
l Probus DP cable pole-reversed
à Check cable and correct, if necessary
l Incorrect termination
à Check termination at the beginning and end points of the bus
and terminate, if necessary, according to the specication
l Instrument not connected to the segment, double assignment
of an address
à Check and correct, if necessary
In Ex applications, the regulations for the wiring of intrinsically safe
circuits must be observed.
? E013
l no measured value available
11)
à Exchange instrument or return instrument for repair
? E017
l Adjustment span too small
à repeat with modied values
? E036
l no operable sensor software
à Carry out a software update or send the instrument for repair
? E041
l Hardware error, electronics defective
à Exchange instrument or return instrument for repair
? E113
l Communication conict
à Exchange instrument or return instrument for repair
11)
Fault message can also appear if the pressure is higher than the nominal range.
Fault messages via the indicating/adjustment module
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 37
8 Maintenance and fault rectication
31544-EN-081211
Page 38
Depending on the failure reason and measures taken, the steps described in chapter "Set up" must be carried out again, if necessary.
8.3 Instrument repair
You can download a return form (24 KB) in the Internet from our homepage
www.wika.com under the item "Service".
If a repair is necessary, please pr oceed as follows:
l Print and ll out one form per instrument l If necessary, state a contamination l Clean the instrument and pack it damage-proof l Attach the completed form and probably a safety data sheet to the
instrument
l Please contact the agency serving you for the address of the
return shipment
By doing this you help us carry out the repair quickly and without having to call back for needed information.
Reaction after fault rec­tication
38 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
8 Maintenance and fault rectication
31544-EN-081211
Page 39
9 Dismounting
9.1 Dismounting steps
Warning:
Before dismounting, be aware of dangerous process conditions such
as e.g. pressure in the vessel, high temperatures, corrosive or toxic
products etc.
Take note of chapters "Mounting" and "Connecting to power supply"
and carry out the listed steps in reverse order.
9.2 Disposal
Note:
When disposing of old instruments, take note of the valid legal and
municipal regulations. The appropriate parts must be recycled.
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 39
9 Dismounting
31544-EN-081211
Page 40
10 Supplement
10.1 Technical data
General data
Pressure type Gauge pressure or gauge pressure
Measuring principle
- Measuring ranges 16 bar piezoresistive with internal transmission liquid
- Measuring ranges > 16 bar Strain gauge (DMS) dry
Service interface I²C-Bus
Materials and weights
316L corresponds to 1.4404 or 1.4435, 316Ti corresponds to 1.4571
Materials, wetted parts
- Process tting 316Ti, Hastelloy C4
- Diaphragm 316Ti, Hastelloy C4
- Diaphragm from measuring range 25 bar,
with not ush version
Elgiloy 2.4711
- Seal ring, O-ring FKM, EPDM, NBR
Materials, non-wetted parts
- Internal transmission liquid Synthetic oil, Halocarbon oil
12)13)
- Housing Plastic PBT, Alu die-casting powder-coated, 316L
- Seal between housing and housing
cover
NBR (stainless steel housing), silicone (Aluminium housing)
- Inspection window in housing cover for
indicating and adjustment module
Polycarbonate (UL-746-C listed)
- Ground terminal 316Ti/316L
Weight approx. 1.2 kg (2.646 lbs)
Output variable
Output signal digital output signal, format according to IEEE-754 Sensor address 126 (default setting) Current value 10 mA, ±0.5 mA
Dynamic behaviour output
Run-up time approx. 10 s
12)
Synthetic oil for measuring ranges up to 16 bar, FDA listed for the food
processing industry. For measuring ranges up to 25 bar dry measuring cell.
13)
Halocarbon oil: Generally in oxygen applications, not with vacuum meas-
uring ranges, not with absolute measuring ranges < 1 bar
abs
.
40 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
10 Supplement
31544-EN-081211
Page 41
90 %
100 %
10 %
t
t
T
A
t
t
S
2
1
Fig. 15: Sudden change of the process variable, dead time tT, rise time tAand step response time t
S
1 Process variable 2 Output signal
Dead time 150 ms Rise time 100 ms (10 90 %) Step response time 250 ms (ti: 0 s, 10 90 %) Damping (63 % of the input variable) 0 999 s, adjustable
Input variable
Adjustment
Adjustment range of the min./max. adjustment relating to the nominal measuring range:
- Min. -5 +95 %
- Max. -5 +105 %
Adjustment range of the zero/span adjustment relating to the nominal measuring range:
- zero -5 +95 %
- Span -5 +105 %
Recommended max. turn down 10 : 1 (no limitation)
Nominal measuring ranges and overload resistance
Nominal range Overload, max. pressure Overload, min. pressure
Gauge pressure
0 … 0.4 bar/0 … 40 kPa 2 bar/200 kPa -1 bar/-100 kPa
0 … 1.6 bar/0 … 160 kPa 10 bar/1000 kPa -1 bar/-100 kPa
0 … 16 bar/0 … 1.6 MPa 80 bar/8 MPa -1 bar/-100 kPa
0 40 bar/0 4 MPa 80 bar/8 MPa -1 bar/-100 kPa
0 100 bar/0 10 MPa 200 bar/20 MPa -1 bar/-100 kPa
0 250 bar/0 25 MPa 500 bar/50 MPa -1 bar/-100 kPa
0 600 bar/0 60 MPa 1200 bar/120 MPa -1 bar/-100 kPa
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 41
10 Supplement
31544-EN-081211
Page 42
Nominal range Overload, max. pressure Overload, min. pressure
-1 3 bar/-100 300 kPa 17 bar/1700 kPa -1 bar/-100 kPa
-1 5 bar/-100 500 kPa 35 bar/3500 kPa -1 bar/-100 kPa
-1 15 bar/-100 1.5 MPa 80 bar/8 MPa -1 bar/-100 kPa
Absolute pressure
0 0.4 bar/0 40 kPa 2 bar/200 kPa
0 bar abs.
0 1.6 bar/0 160 kPa 10 bar/1000 kPa
0 bar abs.
0 6 bar/0 600 kPa 35 bar/3500 kPa
0 bar abs.
0 16 bar/0 1.6 MPa 80 bar/8 MPa
0 bar abs.
Reference conditions and actuating variables (similar to DIN EN 60770-1)
Reference conditions according to DIN EN 61298-1
- Temperature +18 … +30 °C (+64 +86 °F)
- Relative humidity 45 75 %
- Air pressure 860 … 1060 mbar/86 106 kPa (12.5 15.4 psig)
Determination of characteristics Limit point adjustment according to IEC 61298-2
Characteristics linear
Reference installation position upright, diaphragm points downward
Inuence of the installation position depending on the isolating diaphragm version
Deviation determined according to the limit point method according to IEC 60770
14)
Applies to digital interfaces (HART, Probus PA, Foundation Fieldbus) as well as to analogue current output 4 … 20 mA. Specications refer to the set span. Turn down (TD) is the relation nominal measuring range/set span.
Deviation for measuring ranges 0.4 1000 bar
- Turn down 1 : 1 up to 5 : 1 < 0.1 %
- Turn down > 5 : 1 < 0.02 % x TD
Deviation for measuring ranges > 1000 bar
- Turn down 1 : 1 up to 2 : 1 < 0.6 % Deviation with absolute pressure measuring range 0.1 bar
- Turn down 1 : 1 up to 5 : 1 < 0.25 %
- Turn down > 5 : 1 < 0.05 % x TD
Inuence of the product or ambient temperature
Applies to instruments with digital signal output (HART, Probus PA, Foundation Fieldbus) as well as to instruments with analogue current output 4 … 20 mA. Specications refer to the set span. Turn down (TD) = nominal measuring range/set span.
14)
Incl. non-linearity, hysteresis and non-repeatability.
42 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
10 Supplement
31544-EN-081211
Page 43
Thermal change zero zignal, reference temperature 20 °C (68 °F):
- In the compensated temperature range
0 … +100 °C (+32 … +212 °F)
< 0.05 %/10 K x TD
- Outside the compensated temperature
range
typ. < 0.05 %/10 K x TD
Applies also to instruments with analogue 4 20 mA current output and refers to the set span.
Thermal change, current output < 0.15 % at -40 +80 °C (-40 +176 °F)
Long-term stability (similar to DIN 16086, DINV 19259-1 and IEC 60770-1)
Applies to digital interfaces (HART, Probus PA, Foundation Fieldbus) as well as to analogue current output 4 … 20 mA. Specications refer to the set span. Turn down (TD) = nominal measuring range/set span.
Long-term drift of the zero signal < (0.1 % x TD)/year
Ambient conditions
Ambient, storage and transport temperature
- Standard version -40 +80 °C (-40 +176 °F)
- Standard version with indicating and
adjustment module
-15 +70 °C (+5 +158 °F)
- Connection G1 A front-ush according to
EHEDG
-10 +80 °C (+14 +176 °F)
- Fitting G1 A front-ush according to
EHEDG with indicating and adjustment
module
-10 +70 °C (+14 +158 °F)
- Version for oxygen applications
15)
-40 +60 °C (-40 +140 °F)
- Version for oxygen applications with
indicating and adjustment module
16)
-15 +60 °C (+5 +140 °F)
Process conditions
The specications are used as an overview. For pressure stage and product temperature the specications on the type plate are applicable.
Product temperature standard, depending on the seal
17)
- FKM (VP2/A) -20 +105 °C (-4 +221 °F)
- EPDM (A+P 75.5/KW75F) -40 +105 °C (-40 +221 °F)
- NBR (COG) -20 +105 °C (-4 +221 °F)
Product temperature front-ush threaded tting G1 A according to EHEDG, threaded tting M44 x 1.25 as well as hygienic ttings, depending on seal
18) 19)
15)
Up to 60 °C (140 °F).
16)
Up to 60 °C (140 °F).
17)
Version for oxygen applications up to 60 °C (140 °F).
18)
Not with hygienic tting with compression nut F40 PN40/316L
19)
Version for oxygen applications up to 60 °C (140 °F).
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor • Probus PA 43
10 Supplement
31544-EN-081211
Page 44
- FKM (VP2/A) -20 +150 °C (-4 +302 °F)
- EPDM (A+P 75.5/KW75F) -30 +150 °C (-22 +302 °F)
- NBR (COG) -20 +150 °C (-4 +302 °F)
Vibration resistance mechanical vibrations with 4 g and 5 100 Hz
20)
Shock resistance Acceleration 100 g/6 ms
21)
Electromechanical data - version IP 66/IP 67
Cable entry/plug
22)
- Single chamber housing l 1 x cable gland M20 x 1.5 (cable: ø 5 9 mm), 1 x blind stopper M20 x 1.5
or:
l 1 x closing cap ½ NPT, 1 x blind plug ½ NPT
or:
l 1 x plug (depending on the version), 1 x blind
stopper M20 x 1.5
- Double chamber housing l 1 x cable entry M20 x 1.5 (cable: ø 5 9 mm), 1 x blind stopper M20 x 1.5; plug M12 x 1 for
the external indicating and adjustment module (optional)
or:
l 1 x closing cap ½ NPT, 1 x blind stopper
½ NPT, plug M12 x 1 for the external indicating
and adjustment module (optional)
or:
l 1 x plug (depending on the version), 1 x blind
stopper M20 x 1.5; plug M12 x 1 for the external indicating and adjustment module (optional)
Spring-loaded terminals for wire cross-sec­tion up to
2.5 mm² (AWG 14)
Indicating and adjustment module
Voltage supply and data transmission through the sensor
Indication LC display in dot matrix Adjustment elements 4 keys
Protection
- unassembled IP 20
- mounted into the sensor without cover IP 40
20)
Tested according to the regulations of German Lloyd, GL directive 2.
21)
Tested according to EN 60068-2-27.
22)
Depending on the version M12 x 1, according to DIN 43650, Harting, 7/ 8" FF.
44 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
10 Supplement
31544-EN-081211
Page 45
Materials
- Housing ABS
- Inspection window Polyester foil
Power supply
Operating voltage
- Non-Ex instrument 9 32 V DC
- EEx-ia instrument 9 24 V DC
- EEx-d instrument 9 32 V DC
Operating voltage with lighted indicating and adjustment module
- Non-Ex instrument 13 32 V DC
- EEx-ia instrument 13 24 V DC
- EEx-d instrument 13 32 V DC
Power supply by DP/PA segment coupler max. number of sensors 32 (10 with Ex)
Electrical protective measures
Protection
- Housing, standard IP 66/IP 67
23)
Overvoltage category III
Protection class II
Approvals
Depending on the version, instruments with approvals can have dierent technical data. For these instruments, please note the corresponding approval documents. They are included in the scope of delivery.
23)
Instruments with gauge pressure measuring ranges cannot detect the am­bient pressure when submerged, e.g. in water. This can lead to falsication of the measured value.
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 45
10 Supplement
31544-EN-081211
Page 46
10.2 Information on Probus PA
Instrument master le
The instrument master le (GSD) contains the characteristic data of the Probus PA instrument. These data are, e.g. the permissible transmission rates as well as information on diagnostics values and the format of the measured value outputted by the PA instrument.
A bitmap le is also provided for the Probus network planning tool. This le is installed automatically
when the GSD le is integrated. The bitmap le is used for symbolic indication of the PA instrument in the conguration tool.
Ident number
Each Probus instrument gets an unambiguous ident number (ID number) from the Probus user organisation (PNO). This ID number is also included in the name of the GSD le. For IPT-1* Vers. 3.0 the ID number is 0 x 076F(hex) and the GSD le BR__076F.GSD. As an option to this manufacturer­specic GSD le, PNO provides also a general so-called prole-specic GSD le. For IPT-1* Vers.
3.0 you have to use the general GSD le PA139701.GSD. If the general GSD le is used, the sensor
must be set to the prole-specic ident number via the DTM software. By default, the sensor operates with the manufacturer-specic ID number.
Note:
When using the prole-specic GSD file, the PA-OUT value as well as the temperature value are transmitted to the PLC (see block diagram
"Cyclical data trac").
Cyclical data trac
The master class 1 (e.g. PLC) cyclically reads out measured values from the sensor during operation. The below block diagram below shows which data can be accessed by the PLC.
46 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
10 Supplement
31544-EN-081211
Page 47
bar
% Lin%
Min-Max
adjustment
Linearization
PROFIBUS PA-output
Primary
Value
Secondary
Value 1
Secondary
Value 2
Target
Mode
Failure
mode
AlarmsScaling
Source for
scaling
t
i
Damping
Sensor
characteristics
PA -Out
TB
FB
Select additional cyclic
value
Sensor mounting
correction
Fig. 16: IPT-1* Vers. 3.0: Block diagram with AI (PA-OUT) value and Additional Cyclic Value
PROFIBUS PA-output
Ta r get
Mode
Failure
mode
AlarmsScaling
Source for
scaling
t
i
Damping
Sensor
characteristics
PA - Out
˚C
TB
FB 2
Fig. 17: IPT-1* Vers. 3.0: Block diagram with temperature value
Module of the PA sensors
For the cyclic data trac, IPT-1* Vers. 3.0 provides the following modules:
l AI (PA-OUT)
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 47
10 Supplement
31544-EN-081211
Page 48
- PA-OUT value of the FB1 after scaling
l Temperature
- PA-OUT value of the FB2 after scaling
l Additional Cyclic Value
- Additional cyclical value (depending on the source)
l Free Place
- This module must be used if a value should not be used in the data telegram of the cyclical data
trac (e.g. replacement of the temperature and Additional Cyclic Value)
Max. three modules can be active. By means of the conguration software of the Probus master, you can determine the conguration of the cyclical data telegram with these modules. The procedure depends on the respective conguration software.
Tip:
The modules are available in two versions:
l Short for Probus master supporting only one "Identier Format"
byte, e.g. Allen Bradley
l Long for Probus master only supporting the " Identier Format"
byte, e.g. Siemens S7-300/400
Examples of telegram conguration
In the following you will see how the modules can be combined and how the appendant data telegram is structured.
Example 1 (standard setting) with pressure value, temperature value and additional cyclical value:
l AI (PA-OUT) l Temperature l Additional Cyclic Value
Byte-No.
1 2 3 4 5 6 7 8 9 10 11 12 13 14
15
Format
Value
IEEE-754-
Flieskommazahl
PA -OUT
(FB1)
Status
Status
(FB1)
IEEE-754-
Flieskommazahl
Temperature
(FB2)
IEEE-754-
Flieskommazahl
Additional Cyclic
Value
Status
Status
(FB2)
Status
Status
Fig. 18: Telegram conguration example 1
Example 2 with pressure value and temperature value without additional cyclical value:
l AI (PA-OUT) l Temperature l Free Place
48 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
10 Supplement
31544-EN-081211
Page 49
Byte-No.
1 2 3 4 5 6 7 8 9 10
Format
Value
IEEE-754-
Flieskommazahl
PA -OUT
(FB1)
Status
Status
(FB1)
IEEE-754-
Flieskommazahl
Temperature
(FB2)
Status
Status
(FB2)
Fig. 19: Telegram conguration example 2
Example 3 with pressure value and additional cyclical value without temperature value:
l AI (PA-OUT) l Free Place l Additional Cyclic Value
Byte-No.
1 2 3 4 5 6 7 8 9 10
Status
Status
Status
Status
(FB1)
IEEE-754-
Floating point value
PA -OUT
(FB1)
IEEE-754-
Floating point value
Additional Cyclic
Value
Format
Value
Fig. 20: Telegram conguration example 3
Data format of the output signal
Byte4
Byte3
Byte2
Byte1
Byte0
Status Value (IEEE-754)
Fig. 21: Data format of the output signal
The status byte corresponds to prole 3.0 "Probus PA Prole for Process Control Devices" coded. The status "Measured value OK" is coded as 80 (hex) (Bit7 = 1, Bit6 … 0 = 0).
The measured value is transferred as a 32 bit oating point number in the IEEE-754 format.
Byte n
Byte n+1
Bit
7
VZ
Exponent
Bit
6 2
Bit
5 2
Bit
4 2
Bit
3 2
Bit
2 2
Bit
1 2
Bit
0 2
Bit
7 2
Bit
6 2
Bit
5 2
Bit
4 2
Bit
3 2
Bit
2 2
Bit
1 2
Bit
0 2
Sign
Bit
Significant
7
6 5
4
3
2 1
0
-1
-2
-3
-4
-5
-6 -7
Byte n+2
Byte n+3
Bit
7 2
Significant
Bit
6 2
Bit
5 2
Bit
4 2
Bit
3 2
Bit
2 2
Bit
1 2
Bit
0 2
Bit
7 2
Bit
6 2
Bit
5 2
Bit
4 2
Bit
3 2
Bit
2 2
Bit
1 2
Bit
0 2
Significant
-9
-10 -11
-12
-13
-14 -15
-16
-17
-18
-19
-20
-21
-22
-23
-8
Value = (-1)
VZ
2
(Exponent - 127)
(1 + Significant)
Fig. 22: Data format of the measured value
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 49
10 Supplement
31544-EN-081211
Page 50
Coding of the status byte associated with the PA output value
Status
code
Description according to Pro­bus standard
Possible cause
0x00 bad - non-specic Flash-Update active
0x04 bad - conguration error l Adjustment error
l Conguration error with PV-Scale (PV-Span too small) l Unit irregularity l Error in the linearization table
0x0C bad - sensor failure l Hardware error
l Converter error l Leakage pulse error l Trigger error
0x10 bad - sensor failure l Measured value generation error
l Temperature measurement error
0 x 1f bad - out of service constant "Out of Service" mode switched on
0 x 44 uncertain - last unstable value Failsafe replacement value (Failsafe-Mode = "Last value" and
already valid measured value since switching on)
0 x 48 uncertain substitute set l Switch on simulation
l Failsafe replacement value (Failsafe-Mode = "Fsafe value")
0 x 4c uncertain - initial value Failsafe replacement value (Failsafe-Mode = " Last valid value" and
no valid measured value since switching on)
0 x 51 uncertain - sensor; conversion
not accurate - low limited
Sensor value < lower limit
0 x 52 uncertain - sensor; conversion
not accurate - high limited
Sensor value > upper limit
0 x 80 good (non-cascade) - OK OK
0 x 84 good (non-cascade) - active
block alarm
Static revision (FB, TB) changed (10 sec. active, after the parameter of the static category was written)
0 x 89 good (non-cascade) - active ad-
visory alarm - low limited
Lo-Alarm
0 x 8a good (non-cascade) - active ad-
visory alarm - high limited
Hi-Alarm
0 x 8d good (non-cascade) - active crit-
ical alarm - low limited
Lo-Lo-Alarm
0 x 8e good (non-cascade) - active crit-
ical alarm - high limited
Hi-Hi-Alarm
50 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
10 Supplement
31544-EN-081211
Page 51
10.3 Dimensions
Housing
M20x1,5
M20x1,5/ ½ NPT
2
3
4
M20x1,5/ ½ NPT
~ 69 mm
(2 23/32")
ø 77 mm
(3
1
/32")
112 mm (4
13
/
32
")
M20x1,5/ ½ NPT
1
~ 69 mm (2 23/32")
ø 77 mm
(3
1
/32")
117 mm (4
39
/
64
")
M20x1,5/ ½ NPT
116mm
(4
9
/
16
")
~ 116mm
(4 9/16")
ø 84mm
(3
5
/16")
120mm (4
23
/
32
")
~ 87mm (3 27/64")
ø 84mm (3
5
/16")
Fig. 23: Housing versions (with integrated indicating and adjustment module the housing is 9 mm/0.35 in higher) 1 Plastic housing 2 Stainless steel housing 3 Aluminium double chamber housing 4 Aluminium housing
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 51
10 Supplement
31544-EN-081211
Page 52
IPT-1* Vers. 3.0 - threaded tting
SW27
SW27
60°
23mm
(
29
/
32
")
G ½ A
63mm
(2
31
/
64
")
57mm
(2
1
/
4
")
15mm
(
19
/
32
")
3mm
(
1
/
8
")
ø 3mm
(
1
/
8
")
ø 6mm
(
15
/
64
")
½“NPT
¼“NPT
65mm
(2
9
/
16
")
25mm
(
63
/
64
")
15mm
(
19
/
32
")
20mm
(
25
/
32
")
M 20x1,5
NDGD
ML
ø 4,8
(
3
/
16
")
MI
SW27
60°
57mm
(2
1
/
4
")
12mm
(
15
/
32
")
M 16x1,5
ø 4,8
(
3
/
16
")
Fig. 24: IPT-1* Vers. 3.0 GD = G½ EN 837, ND = ½ NPT, ML = M16 x 1.5 inner, MI = M20 x 1.5 inner
52 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
10 Supplement
31544-EN-081211
Page 53
IPT-1* Vers. 3.0 - front-ush connection, part 1
SW41
20,5 mm
(
13
/
16
")
G1B G½B
65 mm
(2
9
/
16
")
ø 30 mm
(1
3
/
16
")
SW60
22 mm
(
55
/
64
")
SW27
20,5 mm
(
13
/
16
")
ø 30 mm
(1
3
/
16
")
ø 18 mm
(
45
/
64
")
G1½A
71 mm
(2
51
/
64
")
SW41
28 mm
(1
7
/
64
")
G1B
68 mm
(2
43
/
64
")
65 mm
(2
9
/
16
")
85
G6 83
86
Fig. 25: IPT-1* Vers. 3.0 85 = G1 A front-ush 0 … 0.4 bar and 0 … 1.6 bar, 86 = G½ A front-ush > 1.6 bar, 84 = G1 A front-ush up to 150 °C according to EHEDG 0 … 0.4 bar and 0 … 16 bar
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 53
10 Supplement
31544-EN-081211
Page 54
IPT-1* Vers. 3.0 - front-ush connection, part 2
51 mm
(2
1
/
64
")
ø 84 mm (3
5
/
16
")
RT RASA
ø64 mm
(2
33
/
64
")
82 mm
(3
15
/
64
")
3T 3R
ø 65 mm (2
9
/
16
")
ø 84 mm (3
5
/
16
")
ø 105 mm (4
9
/
64
")
82 mm
(3
15
/
64
")
ø50 mm (1
31
/
32
")
82 mm
(3
15
/
64
")
81 mm
(3
3
/
16
")
ø 74 mm (2
29
/
32
")
Fig. 26: IPT-1* Vers. 3.0 - SA = Tri-Clamp 2", RA = bolting DN 40/PN 40 according to DIN 11851, RT = Tri-Clamp 1½", 3T = DRD, 3R = Varivent Form F
54 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA
10 Supplement
31544-EN-081211
Page 55
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor Probus PA 55
10 Supplement
31544-EN-081211
Page 56
WIKA Alexander Wiegand GmbH & Co. KG
Alexander-Wiegand-Straße 30 63911 Klingenberg/Germany
Phone +49 9372 132295 Fax +49 9372 132706
e-mail: support-tronic@wika.de www.wika.de
Printing date::
All statements concerning scope of delivery, application,
practical use and operating conditions of the sensors and
processing systems correspond to the information avail-
able at the time of printing.
Subject to change without prior notice 31544-EN-081211
Loading...