WIKA A2G-70 User Manual [en, de, es, fr, it]

Operating instructions Betriebsanleitung Mode d'emploi Manual de instrucciones Manuale d'uso
Duct sensor for relative humidity and temperature model A2G-70
Kanalfühler für relative Feuchte und Temperatur Typ A2G-70
Capteur de gaine pour l‘humidité relative et la température A2G-70
Sensor de conducto para humedad relativa y temperatura A2G-70
S
onda di temperatura e umidità relativa per condotti A2G-
Duct sensor for relative humidity and temperature, model A2G-70
70
GB
D
F
E
I
GB
Operating instructions model A2G-70 Page 3 - 12
D
Betriebsanleitung Typ A2G-70 Seite 13 - 22
F
Mode d'emploi type A2G-70 Page 23 - 32
E
Manual de instrucciones modelo A2G-70 Página 33 - 42
I
Instruzioni per l'uso modello A2G-70 Pagina 43 - 52
© 2010 WIKA Alexander Wiegand SE & Co. KG All rights reserved. / Alle Rechte vorbehalten.
®
WIKA
is a registered trademark in various countries.
®
WIKA
ist eine geschützte Marke in verschiedenen Ländern.
Prior to starting any work, read the operating instructions! Keep for later use!
Vor Beginn aller Arbeiten Betriebsanleitung lesen! Zum späteren Gebrauch aufbewahren!
Lire le mode d'emploi avant de commencer toute opération ! A conserver pour une utilisation ultérieure !
¡Leer el manual de instrucciones antes de comenzar cualquier trabajo! ¡Guardar el manual para una eventual consulta!
Prima di iniziare ad utilizzare lo strumento, leggere il manuale d'uso! Conservare per future consultazioni!
2
WIKA operating instructions air2guide model A2G-70
40202801.03 08/2012 GB/D/F/E/I
Contents
Contents
1. General information 4
2. Safety 5
3. Specications 6
Design and function
4.
5. Transport, packaging and storage 9
6. Commissioning, operation 9
7. Maintenance and cleaning 12
8. Disposal 12
8
GB
40202801.03 08/2012 GB/D/F/E/I
WIKA operating instructions air2guide model A2G-70
3
1. General information
1. General information
The duct sensor for relative humidity and temperature described in the operating instructions has been manufactured using state-of-the­art technology. All components are subject to stringent quality and
GB
environmental criteria during production. Our management systems
are certied to ISO 9001 and ISO 14001.
These operating instructions contain important information on handling the instrument. Working safely requires that all safety instructions and work instructions are observed.
Observe the relevant local accident prevention regulations and general safety regulations for the instrument's range of use.
The operating instructions are part of the product and must be kept in the immediate vicinity of the instrument and readily accessible to skilled personnel at any time.
Skilled personnel must have carefully read and understood the operating instructions prior to beginning any work.
The manufacturer's liability is void in the case of any damage caused by using the product contrary to its intended use, non-compliance
with these operating instructions, assignment of insuciently quali­ed skilled personnel or unauthorised modications to the instru-
ment.
The general terms and conditions contained in the sales documenta­tion shall apply.
Subject to technical modications.
Further information:
- Internet address: www.wika.de / www.wika.com www.air2guide.com
- Relevant data sheet: TE 62.91
4
WIKA operating instructions air2guide model A2G-70
40202801.03 08/2012 GB/D/F/E/I
1. General information / 2. Safety
Explanation of symbols
WARNING!
... indicates a potentially dangerous situation that can result in serious injury or death, if not avoided.
Information
... points out useful tips, recommendations and information
for ecient and trouble-free operation.
2. Safety
WARNING!
Before installation, commissioning and operation, ensure that the appropriate duct sensor for relative humidity and temperature has been selected in terms of measuring
range, design and specic measuring conditions.
Non-observance can result in serious injury and/or damage to the equipment.
Further important safety instructions can be found in the individual chapters of these operating instructions.
2.1 Intended use
For measuring the relative humidity and temperature of gaseous media in heating, ventilation and air-conditioning systems (e. g. in fresh-air and exhaust-air ducts)
Designed for connection to control and display systems
The instrument has been designed and built solely for the intended use described here, and may only be used accordingly.
The manufacturer shall not be liable for claims of any type based on operation contrary to the intended use.
GB
40202801.03 08/2012 GB/D/F/E/I
WIKA operating instructions air2guide model A2G-70
5
2. Safety / 3. Specications
2.2 Personnel qualication
WARNING!
Risk of injury should qualication be insucient!
GB
Skilled personnel
Skilled personnel are understood to be personnel who, based on their technical training, knowledge of measurement and control technology
and on their experience and knowledge of country-specic regulations,
current standards and directives, are capable of carrying out the work described and independently recognising potential hazards.
Explanation of symbols
3. Specications
Improper handling can result in considerable injury and damage to equipment.
The activities described in these operating instructions may only be carried out by skilled personnel who have
the qualications described below.
CE, Communauté Européenne
Instruments bearing this mark comply with the relevant European directives.
Electrical connection
Screw terminal max. 1.5 mm
2
Cable gland M16 x 1.5 for conductors with D = 8 mm max.
Power supply
DC 15 ... 24 V / AC 24 V ±10 %
Power consumption
Typically 0.5 W / 1.7 VA
6
WIKA operating instructions air2guide model A2G-70
40202801.03 08/2012 GB/D/F/E/I
3. Specications
Transmitter output
Humidity: DC 0 ... 10 V, load: min. 5 kΩ Temperature: DC 0 ... 10 V, load: min. 5 kΩ
Transmitter output 4 ... 20 mA (option)
Humidity: 4 ... 20 mA, load < 500 Ω for DC 24 V Temperature: 4 ... 20 mA, load < 500 Ω for DC 24 V
Dimensions in mm
Insertion length L
Standard 140 mm
Mounting ange MF19-PA
GB
40202801.03 08/2012 GB/D/F/E/I
WIKA operating instructions air2guide model A2G-70
7
3. Specications / 4. Design and function
Ingress protection
IP 65 per EN 60529 / lEC 529 (connection head)
For further specications see WIKA data sheet TE 62.91 and the order
documentation.
GB
4. Design and function
4.1 Description
Design
CE conformity: 2004/108/EC electromagnetic compatibility
Product safety: 2001/95/EC product safety
EMC: EN 607301: 2002 Product safety: EN 607301: 2002
Accuracy
Humidity: ±3 % between 20 … 80 % rH Temperature: ±1 % between 5 … 45 °C
Scale range / measuring range
Humidity: 0 … 100 % rH Temperature: -20 … +80 °C
Permissible temperature
Ambient: -20 … +70 °C Sensor tip: max. 60 °C
4.2 Scope of delivery
Cross-check scope of delivery with delivery note.
8
WIKA operating instructions air2guide model A2G-70
40202801.03 08/2012 GB/D/F/E/I
5. Transport, packaging ... / 6. Commissioning, operation
5. Transport, packaging and storage
5.1 Transport
Duct sensor for relative humidity and temperature for any damage that may have been caused by transport.Obvious damage must be reported immediately.
5.2 Packaging
Do not remove packaging until just before mounting. Keep the packaging as it will provide optimum protection during trans­port (e.g. change in installation site, sending for repair).
5.3 Storage
Permissible conditions at the place of storage
Storage temperature: -20 ... +70 °C Protect the instruments from moisture and dust.
6. Commissioning, operation
Installation and mechanical connection
Protect measuring instruments from contamination, high temperature changes and vibrations
In order to avoid any additional heating, the instruments must not be exposed to direct solar irradiation while in operation.
GB
The duct humidity sensor for relative humidity and temperature can be fastened directly to the ventilation duct using either a
mounting ange or screws.
40202801.03 08/2012 GB/D/F/E/I
WIKA operating instructions air2guide model A2G-70
9
6. Commissioning, operation
GB
Electrical connection
Connection diagram
The instruments are designed to operate with safety extra-low voltage (SELV). The transmitters must be operated at a constant operating voltage (±0.2 V). Current/voltage spikes from switching the power
supply on or o must be prevented by the customer.
Connection diagram for output 4 ... 20 mA (standard)
Out Temp 0-10V Out RH 0-10V UB 15-24V=/ 24V~ Gnd
Temp. sensor
Load
10
Load
WIKA operating instructions air2guide model A2G-70
(option)
DRW_TH0.04a
40202801.03 08/2012 GB/D/F/E/I
6. Commissioning, operation
Connection diagram for output 4 ... 20 mA (option)
UB 15-24 V=
GND / Temp Out 4-20 mA
UB 15-24 V=
GND / rF/rH Out 4-20 mA
Temp.
Oset
rF / rH
Oset
Note
If only the humidity output is used, U
15 ... 24 V= (rF/rH) and the temperature output "GND / Temp Out 4 ... 20 mA"
U
B
must be bridged to GND of the voltage supply.
15 ... 24 V= (temp.) must be bridged to
B
Mounting instructions
Max. air velocity 10 m/s
Notes for users
Due to air circulation, dirt and dust particles might occur on the sintered
lter that protects the sensors; these particles might impair the sensor function. After dismounting the lter, it may be cleaned by blowing it out using oil-free and ltered compressed air, ultrapure air or nitrogen or
washing it using distilled water. Filters that are too heavily soiled should be replaced.
Do not touch the delicate humidity sensors as this voids warranty. If used in aggressive gas atmospheres, an early recalibration or replace­ment of the humidity sensors might be required. Such a recalibration or possible sensor replacement is not covered by warranty.
GB
DRW_TH0.05
40202801.03 08/2012 GB/D/F/E/I
WIKA operating instructions air2guide model A2G-70
11
7. Maintenance and cleaning / 8. Disposal
7. Maintenance and cleaning
The duct sensor for relative humidity and temperature is maintenance-
free and oers long service life provided it is handled and operated
properly.
GB
Clean the instruments with a moist cloth (soap water).
Repairs must only be carried out by the manufacturer or appropriately
qualied skilled personnel.
8. Disposal
Incorrect disposal can put the environment at risk.
Dispose of instrument components and packaging materials in an environmentally compatible way and in accordance with the country-
specic waste disposal regulations.
12
WIKA operating instructions air2guide model A2G-70
40202801.03 08/2012 GB/D/F/E/I
Inhalt
Inhalt
1. Allgemeines 14
2. Sicherheit 15
3. Technische Daten 16
Aufbau und Funktion
4.
5. Transport, Verpackung und Lagerung 19
6. Inbetriebnahme, Betrieb 19
7. Wartung und Reinigung 22
8. Entsorgung 22
18
D
40202801.03 08/2012 GB/D/F/E/I
WIKA Betriebsanleitung air2guide Typ A2G-70
13
1. Allgemeines
1. Allgemeines
Der in der Betriebsanleitung beschriebene Kanalfühler für relative Feuchte und Temperatur wird nach dem aktuellen Stand der Technik konstruiert und gefertigt. Alle Komponenten unterliegen während der Fertigung strengen Qualitäts- und Umweltkriterien. Unsere Manage-
mentsysteme sind nach ISO 9001 und ISO 14001 zertiziert.
D
Diese Betriebsanleitung gibt wichtige Hinweise zum Umgang mit dem Gerät. Voraussetzung für sicheres Arbeiten ist die Einhaltung aller angegebenen Sicherheitshinweise und Handlungsanwei­sungen.
Die für den Einsatzbereich des Gerätes geltenden örtlichen Unfall­verhütungsvorschriften und allgemeinen Sicherheitsbestimmungen einhalten.
Die Betriebsanleitung ist Produktbestandteil und muss in unmittel­barer Nähe des Gerätes für das Fachpersonal jederzeit zugänglich aufbewahrt werden.
Das Fachpersonal muss die Betriebsanleitung vor Beginn aller Arbeiten sorgfältig durchgelesen und verstanden haben.
Die Haftung des Herstellers erlischt bei Schäden durch bestim­mungswidrige Verwendung, Nichtbeachten dieser Betriebsanleitung, Einsatz ungenügend qualizierten Fachpersonals sowie eigenmäch­tiger Veränderung am Gerät.
Es gelten die allgemeinen Geschäftsbedingungen in den Verkaufs­unterlagen.
Technische Änderungen vorbehalten.
Weitere Informationen:
- Internet-Adresse: www.wika.de / www.wika.com www.air2guide.com
- zugehöriges Datenblatt: TE 62.91
14
WIKA Betriebsanleitung air2guide Typ A2G-70
40202801.03 08/2012 GB/D/F/E/I
1. Allgemeines / 2. Sicherheit
Symbolerklärung
WARNUNG!
… weist auf eine möglicherweise gefährliche Situation hin, die zum Tod oder zu schweren Verletzungen führen kann, wenn sie nicht gemieden wird.
Information
… hebt nützliche Tipps und Empfehlungen sowie Infor-
mationen für einen ezienten und störungsfreien Betrieb
hervor.
2. Sicherheit
WARNUNG!
Vor Montage, Inbetriebnahme und Betrieb sicherstellen, dass der richtige Kanalfühler für relative Feuchte und Temperatur hinsichtlich Messbereich, Ausführung und
spezischen Messbedingungen ausgewählt wurde.
Bei Nichtbeachten können schwere Körperverletzungen und/oder Sachschäden auftreten.
Weitere wichtige Sicherheitshinweise benden sich in den
einzelnen Kapiteln dieser Betriebsanleitung.
2.1 Bestimmungsgemäße Verwendung
Zur Messung der relativen Feuchte und Temperatur in gasför­migen Medien von Heizungs-, Lüftungs- und Klimaanlagen (z. B. in Zuluft- und Abluftkanälen)
Ausgelegt zur Aufschaltung an Regler- und Anzeigesystemen
Das Gerät ist ausschließlich für den hier beschriebenen bestimmungs­gemäßen Verwendungszweck konzipiert und konstruiert und darf nur dementsprechend verwendet werden.
Ansprüche jeglicher Art aufgrund von nicht bestimmungsgemäßer Verwendung sind ausgeschlossen.
40202801.03 08/2012 GB/D/F/E/I
WIKA Betriebsanleitung air2guide Typ A2G-70
D
15
2. Sicherheit / 3. Technische Daten
2.2 Personalqualikation
WARNUNG!
Verletzungsgefahr bei unzureichender Qualikation!
Unsachgemäßer Umgang kann zu erheblichen Personen­und Sachschäden führen.
D
Fachpersonal
Das Fachpersonal ist aufgrund seiner fachlichen Ausbildung, seiner Kenntnisse der Mess- und Regelungstechnik und seiner Erfahrungen
sowie Kenntnis der landesspezischen Vorschriften, geltenden Normen
und Richtlinien in der Lage, die beschriebenen Arbeiten auszuführen und mögliche Gefahren selbstständig zu erkennen.
Explanation of symbols
3. Technische Daten
Die in dieser Betriebsanleitung beschriebenen Tätigkeiten nur durch Fachpersonal nachfolgend
beschriebener Qualikation durchführen lassen.
CE, Communauté Européenne
Instruments bearing this mark comply with the relevant European directives.
Elektrischer Anschluss
Schraubklemme max. 1,5 mm
2
Kabelverschraubung M16 x 1,5 für Leiter mit max. D = 8 mm
Hilfsenergie
DC 15 ... 24 V / AC 24 V ±10 %
Leistungsaufnahme
Typ. 0,5 W / 1,7 VA
16
WIKA Betriebsanleitung air2guide Typ A2G-70
40202801.03 08/2012 GB/D/F/E/I