WIKA operating instructions air2guide model A2G-45
40389228.01 09/2012 GB/D/F/E/I
Contents
Contents
1.General information4
2.Safety5
3.Specications6
Design and function
4.
5.Transport, packaging and storage8
6.Commissioning, operation9
7.Maintenance and cleaning13
8.Disposal13
7
GB
40389228.01 09/2012 GB/D/F/E/I
WIKA operating instructions air2guide model A2G-45
3
1. General information
1. General information
■
The electronic dierential pressure switch with display described
in the operating instructions has been designed and manufactured
using state-of-the-art technology. All components are subject to
GB
stringent quality and environmental criteria during production. Our
management systems are certied to ISO 9001 and ISO 14001.
■
These operating instructions contain important information on
handling the instrument. Working safely requires that all safety
instructions and work instructions are observed.
■
Observe the relevant local accident prevention regulations and
general safety regulations for the instrument's range of use.
■
The operating instructions are part of the product and must be kept
in the immediate vicinity of the instrument and readily accessible to
skilled personnel at any time.
■
Skilled personnel must have carefully read and understood the
operating instructions prior to beginning any work.
■
The manufacturer's liability is void in the case of any damage caused
by using the product contrary to its intended use, non-compliance
with these operating instructions, assignment of insuciently qualied skilled personnel or unauthorised modications to the instru-
ment.
■
The general terms and conditions contained in the sales documentation shall apply.
■
Subject to technical modications.
■
Further information:
- Internet address:www.wika.de / www.wika.com
www.air2guide.com
- relevant data sheet: SP 69.08
4
WIKA operating instructions air2guide model A2G-45
40389228.01 09/2012 GB/D/F/E/I
1. General information / 2. Safety
Explanation of symbols
WARNING!
... indicates a potentially dangerous situation that can result
in serious injury or death, if not avoided.
Information
... points out useful tips, recommendations and information
for ecient and trouble-free operation.
2. Safety
WARNING!
Before installation, commissioning and operation, ensure
that the appropriate dierential pressure switch has been
selected in terms of measuring range, design and specic
measuring conditions.
Non-observance can result in serious injury and/or damage
to the equipment.
Further important safety instructions can be found in the
individual chapters of these operating instructions.
2.1 Intended use
This electronic dierential pressure switch is used for monitoring the
dierential pressure of air and other non-inammable and non-aggressive gases. And also for controlling air as well for monitoring of air lters,
blowers in ventilation ducts, control of air and re shutters, for overpres-
sure monitoring in clean rooms and laboratories.
The instrument has been designed and built solely for the intended use
described here, and may only be used accordingly.
The manufacturer shall not be liable for claims of any type based on
operation contrary to the intended use.
GB
40389228.01 09/2012 GB/D/F/E/I
WIKA operating instructions air2guide model A2G-45
5
2. Safety / 3. Specications
2.2 Personnel qualication
WARNING!
Risk of injury should qualication be insucient!
GB
Improper handling can result in considerable injury and
damage to equipment.
■
The activities described in these operating instructions
may only be carried out by skilled personnel who have
the qualications described below.
Skilled personnel
Skilled personnel are understood to be personnel who, based on their
technical training, knowledge of measurement and control technology
and on their experience and knowledge of country-specic regulations,
current standards and directives, are capable of carrying out the work
described and independently recognising potential hazards.
Explanation of symbols
CE, Communauté Européenne
Instruments bearing this mark comply with the relevant
European directives.
3. Specications
Process connection
Connecting nozzle (copper alloy), for hoses with inner diameter 4 or
6 mm
Measuring element
Piezo measuring cell
Case/cover
Plastic (ABS)/plastic (PC)
6
WIKA operating instructions air2guide model A2G-45
40389228.01 09/2012 GB/D/F/E/I
3. Specications
Electrical connection
Cable gland M16 and M20, screw terminals max. 1.5 mm²
Output signal
0 … 10 V, 2-wire, load resistance min. 1 kOhm
Voltage supply
AC 24 V ±10 % or DC 21 ... 35 V
Long-term stability
≤ ±8 Pa
≤ ±1 Pa with automatic zero adjustment (option)
Dimensions in mm
GB
Weight
150 g
Ingress protection
IP 54 per EN 60529 / lEC 529
For further specications see WIKA data sheet SP 69.08 and the order
documentation.
40389228.01 09/2012 GB/D/F/E/I
WIKA operating instructions air2guide model A2G-45
7
4. Design and function / 5. Transport, packaging ...
4. Design and function
4.1 Description
Design
CE conformity:
GB
2004/108/EC electromagnetic compatibility
2002/95/EC RoHS (restriction of the use of certain hazardous
substances in electrical and electronic equipment)
Variant 2: 0 ... 2,500 Pa (0 ... +100 Pa, 0 ... +250 Pa, 0 ... +1,000 Pa
to be set via jumper)
Pressure limitation
Maximum pressure: 25 kPa
Permissible temperature
Ambient: -20 … +70 °C
Operation: -10 … +50 °C
(-5 … +50 °C with automatic zero adjustment)
4.2 Scope of delivery
Cross-check scope of delivery with delivery note.
5. Transport, packaging and storage
5.1 Transport
Check the dierential pressure switch for any damage that may have
been caused by transport. Obvious damage must be reported immediately.
8
WIKA operating instructions air2guide model A2G-45
40389228.01 09/2012 GB/D/F/E/I
6. Commissioning, operation
5.2 Packaging
Do not remove packaging until just before mounting.
Keep the packaging as it will provide optimum protection during transport
(e.g. change in installation site, sending for repair).
5.3 Storage
Permissible conditions at the place of storage
Storage temperature: -20 ... +70 °C
Protect the instruments from moisture and dust.
6. Commissioning, operation
Installation
■
When connecting the instrument, the process lines must be free of
pressure.
■
Observe the suitability of the instrument for the media to be
measured
■
Observe maximum pressures
Electrical connection
The instruments are designed to operate with safety extra-low voltage
(SELV). When wiring up the instruments, the technical specications
for those instruments should be followed. In the case of a sensor with
transmitter, as a rule, the transmitter should be operated in the middle of
the measuring range, since deviations can occur at the range limits.
■
The ambient temperature of the transmitter electronics
should be kept constant.
■
Current/voltage spikes from switching the power supply
on or o must be prevented by the customer.
GB
Current consumption
35 mA + switch (7 mA each) + instrument with automatic zero
adjustment (20 mA)
0 … 10 V output (10 mA), max. 80 mA
40389228.01 09/2012 GB/D/F/E/I
WIKA operating instructions air2guide model A2G-45
9
6. Commissioning, operation
Connection diagram
Power supply AC 24 V
Output signal 0 ... 10 V
Relay 1 (standard)
GB
Relay 2 (option)
If the voltages being switched via the relays
are not in accordance with SELV, then the
power supply and signal/control cables of
the relays should be installed so that they
are separated. A separate cable entry is
available for both.
Commissioning
A prerequisite for the commissioning is a proper installation of all
electrical supply, control and measuring lines and of the pressure
connection lines.
■
Before commissioning, the leak tightness of the pressure
connection lines must be checked.
Buttons for setting the individual functions
KeyFunction
MENU
To access the menu, press the "MENU" button for approx. 3
seconds.
BACK
OK
10
To exit the menu, press the "BACK" button.
To open an individual menu point, and to accept the changes,
press the "OK" button.
These buttons enable you to scroll within the menu.
40389228.01 09/2012 GB/D/F/E/I
WIKA operating instructions air2guide model A2G-45
6. Commissioning, operation
Menu selection and initialisation instructions for installation
1. Pressure units selectable: Pa, kPa,
mmH2O, inchWC, mbar
2. Measuring ranges selectable, see
page 3. Specications
3. Response time selectable: 0.5 ... 10 s
4. Zero point adjustment and span
calibration
Calibration of the upper point
Reset the span setting
5. Set point (between min. and max.
pressure)
6. Hysteresis (0 ... 5 % of measuring
range)
GB
40389228.01 09/2012 GB/D/F/E/I
WIKA operating instructions air2guide model A2G-45
11
6. Commissioning, operation
Zero point adjustment
Attention!
Connect the voltage supply one hour before making the
GB
■
Remove both hoses from the pressure connections ⊕ and ⊖.
■
Press both the "up" and "down" buttons simultaneously, or select
zero point adjustment.
"Zero" in the setting menu:
⇒ the green LED switches o and "Zero" is shown in the display.
■
Wait until the green LED switches back on, then reconnect the ⊕ and
⊖ pressure connections.
In normal operation, we recommend that a zero point adjustment is
carried out every 12 months.
Span calibration
Attention!
Connect the voltage supply one hour before making the
span calibration.
A reference pressure measuring instrument is needed for the span
setting.
The span should not be set without pressure being present. If the span
is set with either no test pressure, or too-low a pressure, the instrument
will lose its accuracy and no longer give correct measured values.
If this should occur, select the menu point "Span" and then select
"Reset", in order to reset the span setting.
12
WIKA operating instructions air2guide model A2G-45
40389228.01 09/2012 GB/D/F/E/I
6. Commissioning, operation ... 8. Disposal
Set the span in the following sequence:
1. Carry out a zero point calibration
2. Connect the pressure connections
3. Select "Span" in the menu and then select "Adjust"
4. Using both the "up" and "down" arrow buttons, set the relevant value
for the display or the 0 … 10 V output, so that it matches the reference
pressure instrument's value
5. Conrm the setting by pressing the "OK" button
GB
Pout
10 V
Inuence of the span
setting on the measured
values
Pressure
7. Maintenance and cleaning
The dierntial pressure switches are maintenance-free and oer long
service life provided they are handled and operated properly.
Clean the instruments with a moist cloth (soap water).
Repairs must only be carried out by the manufacturer or appropriately
qualied skilled personnel.
8. Disposal
Incorrect disposal can put the environment at risk.
Dispose of instrument components and packaging materials in an
environmentally compatible way and in accordance with the country-
specic waste disposal regulations.
40389228.01 09/2012 GB/D/F/E/I
WIKA operating instructions air2guide model A2G-45
13
GB
14
WIKA operating instructions air2guide model A2G-45
40389228.01 09/2012 GB/D/F/E/I
Inhalt
Inhalt
1.Allgemeines16
2.Sicherheit17
3.Technische Daten18
Aufbau und Funktion
4.
5.Transport, Verpackung und Lagerung20
6.Inbetriebnahme, Betrieb21
7.Wartung und Reinigung25
8.Entsorgung25
19
D
40389228.01 09/2012 GB/D/F/E/I
WIKA Betriebsanleitung air2guide Typ A2G-45
15
1. Allgemeines
1. Allgemeines
■
Der in der Betriebsanleitung beschriebene elektronische Die-
renzdruckschalter mit Anzeige wird nach dem aktuellen Stand der
Technik konstruiert und gefertigt. Alle Komponenten unterliegen
während der Fertigung strengen Qualitäts- und Umweltkriterien.
Unsere Managementsysteme sind nach ISO 9001 und ISO 14001
D
zertiziert.
■
Diese Betriebsanleitung gibt wichtige Hinweise zum Umgang mit
dem Gerät. Voraussetzung für sicheres Arbeiten ist die Einhaltung
aller angegebenen Sicherheitshinweise und Handlungsanweisungen.
■
Die für den Einsatzbereich des Gerätes geltenden örtlichen Unfallverhütungsvorschriften und allgemeinen Sicherheitsbestimmungen
einhalten.
■
Die Betriebsanleitung ist Produktbestandteil und muss in unmittelbarer Nähe des Gerätes für das Fachpersonal jederzeit zugänglich
aufbewahrt werden.
■
Das Fachpersonal muss die Betriebsanleitung vor Beginn aller
Arbeiten sorgfältig durchgelesen und verstanden haben.
■
Die Haftung des Herstellers erlischt bei Schäden durch bestimmungswidrige Verwendung, Nichtbeachten dieser Betriebsanleitung,
Einsatz ungenügend qualizierten Fachpersonals sowie eigenmächtiger Veränderung am Gerät.
■
Es gelten die allgemeinen Geschäftsbedingungen in den Verkaufsunterlagen.
… weist auf eine möglicherweise gefährliche Situation hin,
die zum Tod oder zu schweren Verletzungen führen kann,
wenn sie nicht gemieden wird.
Information
… hebt nützliche Tipps und Empfehlungen sowie Infor-
mationen für einen ezienten und störungsfreien Betrieb
hervor.
2. Sicherheit
WARNUNG!
Vor Montage, Inbetriebnahme und Betrieb sicherstellen,
dass der richtige Dierenzdruckschalter hinsichtlich
Messbereich, Ausführung und spezischen Messbedin-
gungen ausgewählt wurde.
Bei Nichtbeachten können schwere Körperverletzungen
und/oder Sachschäden auftreten.
Weitere wichtige Sicherheitshinweise benden sich in den
einzelnen Kapiteln dieser Betriebsanleitung.
2.1 Bestimmungsgemäße Verwendung
Dieser elektronische Dierenzdruckschalter dient zur Überwachung
des Dierenzdruckes von Luft und anderen nicht brennbaren und nicht
aggressiven Gasen sowie zur Überwachung von Luftltern, Gebläsen in
Lüftungskanälen, Regelung von Luft- und Brandschutzklappen und zur
Überdrucküberwachung von Reinräumen und Labors.
Das Gerät ist ausschließlich für den hier beschriebenen bestimmungsgemäßen Verwendungszweck konzipiert und konstruiert und darf nur
dementsprechend verwendet werden.
Ansprüche jeglicher Art aufgrund von nicht bestimmungsgemäßer
Verwendung sind ausgeschlossen.
40389228.01 09/2012 GB/D/F/E/I
WIKA Betriebsanleitung air2guide Typ A2G-45
D
17
2. Sicherheit / 3. Technische Daten
2.2 Personalqualikation
WARNUNG!
Verletzungsgefahr bei unzureichender Qualikation!
Unsachgemäßer Umgang kann zu erheblichen Personenund Sachschäden führen.
■
D
Die in dieser Betriebsanleitung beschriebenen Tätigkeiten nur durch Fachpersonal nachfolgend beschrie-
bener Qualikation durchführen lassen.
Fachpersonal
Das Fachpersonal ist aufgrund seiner fachlichen Ausbildung, seiner
Kenntnisse der Mess- und Regelungstechnik und seiner Erfahrungen
sowie Kenntnis der landesspezischen Vorschriften, geltenden Normen
und Richtlinien in der Lage, die beschriebenen Arbeiten auszuführen
und mögliche Gefahren selbstständig zu erkennen.
Symbolerklärung
CE, Communauté Européenne
Geräte mit dieser Kennzeichnung stimmen überein mit den
zutreenden europäischen Richtlinien.
3. Technische Daten
Prozessanschluss
Anschlussstutzen (Kupferlegierung), für Schläuche mit Innendurchmesser 4 oder 6 mm
Messelement
Piezo-Messzelle
Gehäuse/Deckel
Kunststo (ABS)/Kunststo (PC)
18
WIKA Betriebsanleitung air2guide Typ A2G-45
40389228.01 09/2012 GB/D/F/E/I
3. Technische Daten
Elektrischer Anschluss
Kabelverschraubung M16 und M20, Schraubklemmen max. 1,5 mm²
Ausgangssignal
0 … 10 V, 2-Leiter, Lastwiderstand mind. 1 kOhm
Spannungsversorgung
AC 24 V ±10 % oder DC 21 ... 35 V
Langzeitstabilität
≤ ±8 Pa
≤ ±1 Pa mit automatischer Nullpunktkorrektur (Option)
Abmessungen in mm
Gewicht
150 g
Schutzart
IP 54 nach EN 60529 / lEC 529
Weitere technische Daten siehe WIKA-Datenblatt SP 69.08 und
Bestellunterlagen.
40389228.01 09/2012 GB/D/F/E/I
WIKA Betriebsanleitung air2guide Typ A2G-45
D
19
4. Aufbau und Funktion / 5. Transport, Verpackung ...