WIKA operating instructions air2guide model A2G-05
40387565.02 10/2013 GB/D/F/E/I
Contents
Contents
1.General information4
2.Safety5
3.Specications6
Design and function
4.
5.Transport, packaging and storage8
6.Commissioning, operation8
7.Zero point adjustment11
8.Options and accessories11
9.Maintenance and cleaning11
10.Disposal12
GB
7
40387565.02 10/2013 GB/D/F/E/I
WIKA operating instructions air2guide model A2G-05
3
1. General information
1. General information
■
The pressure gauge described in the operating instructions has been
manufactured using state-of-the-art technology. All components
GB
are subject to stringent quality and environmental criteria during
production. Our management systems are certied to ISO 9001 and
ISO 14001.
■
These operating instructions contain important information on
handling the instrument. Working safely requires that all safety
instructions and work instructions are observed.
■
Observe the relevant local accident prevention regulations and
general safety regulations for the instrument's range of use.
■
The operating instructions are part of the product and must be kept
in the immediate vicinity of the instrument and readily accessible to
skilled personnel at any time.
■
Skilled personnel must have carefully read and understood the
operating instructions, prior to beginning any work.
■
The manufacturer's liability is void in the case of any damage caused
by using the product contrary to its intended use, non-compliance
with these operating instructions, assignment of insuciently
qualied skilled personnel or unauthorised modications to the
instrument.
■
The general terms and conditions contained in the sales
documentation shall apply.
■
Subject to technical modications.
■
Further information:
- Internet address:www.wika.de / www.wika.com
www.air2guide.com
- Relevant data sheet:PM 07.42
4
WIKA operating instructions air2guide model A2G-05
40387565.02 10/2013 GB/D/F/E/I
1. General information / 2. Safety
Explanation of symbols
WARNING!
... indicates a potentially dangerous situation which can
result in serious injury or death if not avoided.
Information
… points out useful tips, recommendations and information
for ecient and trouble-free operation.
2. Safety
WARNING!
Before installation, commissioning and operation, ensure
that the appropriate pressure gauge has been selected in
terms of measuring range, design and specic measuring
conditions.
Non-observance can result in serious injury and/or damage
to the equipment.
Further important safety instructions can be found in the
individual chapters of these operating instructions.
2.1 Intended use
This pressure gauge is designed for measuring very low pressures in
dry, clean, non-aggressive gases, primarily air.
GB
The instrument has been designed and built solely for the intended use
described here, and may only be used accordingly.
The manufacturer shall not be liable for claims of any type based on
operation contrary to the intended use.
40387565.02 10/2013 GB/D/F/E/I
WIKA operating instructions air2guide model A2G-05
5
2. Safety / 3. Specications
2.2 Personnel qualication
WARNING!
Risk of injury if qualication is insucient!
GB
Improper handling can result in considerable injury and
damage to equipment.
■
The activities described in these operating instructions
may only be carried out by skilled personnel who have
the qualications described below.
Skilled personnel
Skilled personnel are understood to be personnel who, based on their
technical training, knowledge of measurement and control technology
and on their experience and knowledge of country-specic regulations,
current standards and directives, are capable of carrying out the work
described and independently recognising potential hazards.
Explanation of symbols
CE, Communauté Européenne
Instruments bearing this mark comply with the relevant
European directives.
3. Specications
Pressure limitation
Steady: Full scale value
Fluctuating: Full scale value
Overpressure safety
Plus and minus side 20 kPa
Max. working pressure (static pressure)
20 kPa
6
WIKA operating instructions air2guide model A2G-05
40387565.02 10/2013 GB/D/F/E/I
3. Specications / 4. Design and function
Process connection
In accordance with the general technical regulations for pressure
gauges (e.g. EN 837-2 "Selection and installation recommendations for
pressure gauges"), plastic, G 1/8 female threads
Permissible temperature
Ambient: -30 … +80 °C
Medium: -16 … +50 °C
Temperature eect
When the temperature of the measuring system deviates from the reference temperature (+20 °C): max. ±0.5 %/10 K of full scale value
Ingress protection
IP 54 per EN 60529 / lEC 529, optional IP 65
EMC directive
Per EN 61000-6-4 and EN 61000-6-2 (cable length max. 30 m)
For further specications see WIKA data sheet PM 07.42 and the order
documentation.
4. Design and function
Description
■
Nominal size 110 mm
GB
■
The instruments measure the pressure by means of separating
diaphragms (silicone)
■
The measuring characteristics are in accordance with the EN 837-3
standard and ventilation and air conditioning (VAC) regulations
Scope of delivery
Cross-check the scope of delivery with the delivery note.
40387565.02 10/2013 GB/D/F/E/I
WIKA operating instructions air2guide model A2G-05
Check the pressure gauge for any damage that may have been caused
by transport. Obvious damage must be reported immediately.
GB
5.2 Packaging
Do not remove packaging until just before mounting.
Keep the packaging as it will provide optimum protection during transport (e.g. change in installation site, sending for repair).
5.3 Storage
Permissible conditions at the place of storage
Storage temperature: -30 ... +80 °C
Protect the instruments from moisture and dust.
6. Commissioning, operation
Installation and mechanical connection
In accordance with the general technical regulations for pressure
gauges (e.g. EN 837-2 "Selection and installation recommendations for
pressure gauges").
■
Process connection back mount (BM)
■
Protect measuring instruments from contamination, high temperature
changes and vibrations
■
air2guide Eco dierential pressure gauges are calibrated in vertical
position and should be installed in the same position to avoid loss of
class accuracy. If a dierent installation position is required please
specify when ordering. Gauges with high pressure ranges can
be installed in dierent non-vertical mounting position, by simply
adjusting the zero point.
8
WIKA operating instructions air2guide model A2G-05
40387565.02 10/2013 GB/D/F/E/I
6. Commissioning, operation
Panel mounting
Detailed mounting steps
GB
1. Fasten the mounting ring using the supplied
three screws.
2. Insert the measuring instrument into the
mounting ring.
3. Turn the measuring instrument clockwise
or anti-clockwise, until an exactly horizontal
positioning is reached.
40387565.02 10/2013 GB/D/F/E/I
WIKA operating instructions air2guide model A2G-05
9
6. Commissioning, operation
Option screw built-in variant
GB
Ø 111
After tting the measuring element into the case
it can be moved in a clockwise and counterclockwise direction respectively for 15 angular
degrees in order to ensure precise horizontal
positioning of the instrument.
Commissioning
■
During the commissioning process pressure surges must be avoided
at all costs
■
Install the pressure connection according to the symbols
⊕ high pressure ⊖ low pressure
■
Use the pressure gauge only if the diaphragm is undamaged and if it
is in perfect condition with regard to safety.
10
WIKA operating instructions air2guide model A2G-05
40387565.02 10/2013 GB/D/F/E/I
7. Zero point adjustment ... 9. Maintenance and cleaning
7. Zero point adjustment
In general, the zero point should only be checked and adjusted after the
system has been depressurised.
Mechanical zero point
If there is a zero point deviation (in depressurised condition), the zero
point can be adjusted by turning the adjustment screw.
8. Options and accessories
Mark pointer
The mark pointer indicates the maximum allowable dierential pressure
on the dial. It can be adjusted manually to the desired value.
Standard accessories
3 mounting screws
Measuring hose
Plastic, for inner diameter 4 or 6 mm, reels available at 25 m
9. Maintenance and cleaning
Eco dierential pressure gauges are maintenance-free and oer long
service life provided they are handled and operated properly.
GB
Clean the instruments with a moist cloth (soap water).
Repairs must only be carried out by the manufacturer or appropriately
qualied skilled personnel.
40387565.02 10/2013 GB/D/F/E/I
WIKA operating instructions air2guide model A2G-05
11
10. Disposal
10. Disposal
Incorrect disposal can put the environment at risk.
GB
Dispose of instrument components and packaging materials in an
environmentally compatible way and in accordance with the country-
specic waste disposal regulations.
12
WIKA operating instructions air2guide model A2G-05
40387565.02 10/2013 GB/D/F/E/I
Inhalt
Inhalt
1.Allgemeines14
2.Sicherheit15
3.Technische Daten16
Aufbau und Funktion
4.
5.Transport, Verpackung und Lagerung18
6.Inbetriebnahme, Betrieb18
7.Nullpunkteinstellung21
8.Optionen und Zubehör21
9.Wartung und Reinigung21
10.Entsorgung22
17
D
40387565.02 10/2013 GB/D/F/E/I
WIKA Betriebsanleitung air2guide Typ A2G-05
13
1. Allgemeines
1. Allgemeines
■
Das in der Betriebsanleitung beschriebene Druckmessgerät wird
nach dem aktuellen Stand der Technik konstruiert und gefertigt.
Alle Komponenten unterliegen während der Fertigung strengen
Qualitäts- und Umweltkriterien. Unsere Managementsysteme sind
D
nach ISO 9001 und ISO 14001 zertiziert.
■
Diese Betriebsanleitung gibt wichtige Hinweise zum Umgang mit
dem Gerät. Voraussetzung für sicheres Arbeiten ist die Einhaltung
aller angegebenen Sicherheitshinweise und Handlungsanweisungen.
■
Die für den Einsatzbereich des Gerätes geltenden örtlichen Unfallverhütungsvorschriften und allgemeinen Sicherheitsbestimmungen
einhalten.
■
Die Betriebsanleitung ist Produktbestandteil und muss in unmittelbarer Nähe des Gerätes für das Fachpersonal jederzeit zugänglich
aufbewahrt werden.
■
Das Fachpersonal muss die Betriebsanleitung vor Beginn aller
Arbeiten sorgfältig durchgelesen und verstanden haben.
■
Die Haftung des Herstellers erlischt bei Schäden durch bestimmungswidrige Verwendung, Nichtbeachten dieser Betriebsanleitung,
Einsatz ungenügend qualizierten Fachpersonals sowie eigenmächtiger Veränderung am Gerät.
■
Es gelten die allgemeinen Geschäftsbedingungen in den Verkaufsunterlagen.
… weist auf eine möglicherweise gefährliche Situation hin,
die zum Tod oder zu schweren Verletzungen führen kann,
wenn sie nicht gemieden wird.
Information
… hebt nützliche Tipps und Empfehlungen sowie Infor-
mationen für einen ezienten und störungsfreien Betrieb
hervor.
2. Sicherheit
WARNUNG!
Vor Montage, Inbetriebnahme und Betrieb sicherstellen,
dass das richtige Druckmessgerät hinsichtlich Messbe-
reich, Ausführung und spezischen Messbedingungen
ausgewählt wurde.
Bei Nichtbeachten können schwere Körperverletzungen
und/oder Sachschäden auftreten.
Weitere wichtige Sicherheitshinweise benden sich in den
einzelnen Kapiteln dieser Betriebsanleitung.
2.1 Bestimmungsgemäße Verwendung
D
Dieses Druckmessgerät dient zum Messen von sehr niedrigen Drücken
bei trockenen, sauberen, nicht aggressiven Gasen, hauptsächlich Luft.
Das Gerät ist ausschließlich für den hier beschriebenen bestimmungsgemäßen Verwendungszweck konzipiert und konstruiert und darf nur
dementsprechend verwendet werden.
Ansprüche jeglicher Art aufgrund von nicht bestimmungsgemäßer
Verwendung sind ausgeschlossen.
40387565.02 10/2013 GB/D/F/E/I
WIKA Betriebsanleitung air2guide Typ A2G-05
15
2. Sicherheit / 3. Technische Daten
2.2 Personalqualikation
WARNUNG!
Verletzungsgefahr bei unzureichender Qualikation!
Unsachgemäßer Umgang kann zu erheblichen Personen-
D
und Sachschäden führen.
■
Die in dieser Betriebsanleitung beschriebenen Tätigkeiten nur durch Fachpersonal nachfolgend beschrie-
bener Qualikation durchführen lassen.
Fachpersonal
Das Fachpersonal ist aufgrund seiner fachlichen Ausbildung, seiner
Kenntnisse der Mess- und Regelungstechnik und seiner Erfahrungen
sowie Kenntnis der landesspezischen Vorschriften, geltenden Normen
und Richtlinien in der Lage, die beschriebenen Arbeiten auszuführen
und mögliche Gefahren selbstständig zu erkennen.
Symbolerklärung
CE, Communauté Européenne
Geräte mit dieser Kennzeichnung stimmen überein mit den