1 ) If the medium water is measured, a higher overload safety is recommended.
The given measuring ranges are also available in mbar, kg/cm2, MPa and kPa.
Other measuring ranges available on request.
3-fold overload safety available on request.
Vacuum tightness
Yes (for restrictions see overload safety)
WIKA data sheet PE 81.60 ∙ 10/2017Page 3 of 12
Output signals
Output signals
Current (2-wire)4 ... 20 mA
Voltage (3-wire)DC 0 ... 10 V
DC 0 ... 5 V
DC 1 ... 5 V
DC 0.5 ... 4.5 V
Ratiometric (3-wire)DC 0.5 ... 4.5 V
Other output signals on request
Load in Ω
Current (2-wire):≤ (power supply - 8 V) / 0.02 A
Voltage (3-wire):> maximum output signal / 1 mA
Ratiometric (3-wire): > 10k
Voltage supply
Output signalPower supply
StandardOption
4 ... 20 mADC 8 ... 30 VDC 8 ... 35 V
DC 0 ... 10 VDC 14 ... 30 VDC 14 ... 35 V
DC 0 ... 5 V
DC 1 ... 5 VDC 8 ... 30 VDC 8 ... 35 V
DC 0.5 ... 4.5 VDC 8 ... 30 VDC 8 ... 35 V
DC 0.5 ... 4.5 V ratiometricDC 5 V ± 10 %-
3)
DC 8 ... 30 VDC 8 ... 35 V
1) 2)
1) Not possible with non-linearity 0.25 % BFSL
2) Only possible for temperatures up to 80 °C (176 °F)
3) Not possible with measuring ranges ≤ 0.1 bar (or equivalent)
The power supply for the pressure transmitter must be made via an energy-limited electrical circuit in accordance with section
9.3 of UL/EN/IEC 61010-1, or an LPS per UL/EN/IEC 60950-1, or class 2 in accordance with UL1310/UL1585 (NEC or CEC).
The power supply must be suitable for operation above 2,000 m should the pressure transmitter be used at this altitude.
Total current consumption
Current (2-wire):Signal current, max. 25 mA
Voltage (3-wire):8 mA
Ratiometric (3-wire): 8 mA
Page 4 of 12WIKA data sheet PE 81.60 ∙ 10/2017
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.