3WIKA Operating instructions pressure gauges Model 6 with 831 per ATEX
1. Safety instructions / 2. Description
1. Safety instructions
!
Caution
GB
The appropriate national safety regulations (i.e. VDE 0100 /
EN 60 079-14 / EN 837-2) must be observed when installing,
putting into operation and running these instruments.
T Do not work on gauge while under voltage
T Serious injuries and/or damage can occur should the appropriate
regulations not be observed
€T Only appropriately qualified persons should work on these
instruments
2. Description
T The pressure gauges measure the pressure by means of resilient capsule
measuring elements
T Themeasuring features follow the example of the standards EN 837-3 and
DIN 16 085
The built-in electrical alarm contacts are non-contact slot-type inductive
proximity sensors, which are supplied from control units with circuits that are
certified to be intrinsically safe. When the adjustable set points are reached,
their output circuits will be opened or closed.
T As a standard slot sensors model 831 are used according to EC-type
examination certificate PTB 99 ATEX 2219 X (see enclosure 2) and
ZELM 03 ATEX 0128 X (see enclosure 4)
T SN sensors models 831-SN and -S1N according to PTB 00 ATEX 2049 X
(see enclosure 3) and ZELM 03 ATEX 0128 X (see enclosure 4) are special
designs with safety features (that are not relevant to explosion protection)
for special applications
The connection values of the switches are in accordance with EN 60 947-5-6
("NAMUR").
4WIKA Operating instructions pressure gauges Model 6 with 831 per ATEX
2030660 12/2004 GB/D/F
3. Technical data and use in accordance with intended use
3. Technical data and use in accordance with intended use
Working pressure
Steady:full scale value
Fluctuating:0.9 x full scale value
Short time:1.3 x full scale value (special versions up to 3 × resp.
10 × full scale value)
Pressure connection
T According to the general technical regulations for pressure gauges,
respectively (i.e. EN 837-2 "Selection and installation recommendations for
pressure gauges").
When screw-fitting the gauges the force required for sealing must not be
applied through the case or terminal box but, using a suitable tool, only through
the spanner flats provided for this purpose at the square of the connector.
Installation with
open-end wrench
Temperature effect
GB
When temperature of the pressure element deviates from reference temperature
(+20 °C): max. ±0.6 %/10 K of true scale value
IP Ingress protection
IP 54 per EN 60 529 / IEC 60 529
(with liquid filling IP 65)
2030660 12/2004 GB/D/F
5WIKA Operating instructions pressure gauges Model 6 with 831 per ATEX
3. Technical data and use in accordance with intended use
Operating Temperature
Ambient: -20 ... +60 °C
Attention: Footnote 1) under table 1 must be absolutely taken into account!
GB
Medium: see table 1
Attention! With gaseous substances the temperature may increase as a result
of the compression temperature. In such cases the pressure change rate has to
be slowed down resp. the permissible medium temperature has to be reduced.
Table 1: Permissible medium temperature (only mechanical part)
Ignition temperature ofPermissible maximum medium temperature
the ambient atmosphere(in the pressure system)
(temperature class)
> 85 °C(T 6)+70 °C
> 100 °C (T 5)+85 °C
> 135 °C (T 4)+100 °C
> 200 °C (T 3)+100 °C
> 300 °C (T 2)+100 °C
> 450 °C (T 1)+100 °C
1) The permissible uppper ambient temperature for the electrical components is determined by the
electrical connection values and the ignition temperature of the ambient gases, vapours and dusts.
Therefore the maximum permissible ambient temperatures specified in the EC-type examination
certificates for slot-type sensors and SN sensors must be observed as well. The lower of these two
values is to be considered the maximum permissible ambient temperature!
Materials (wetted parts)
PartModel 612.20 Model 63X.50Model 614.11 Model 634.11
6WIKA Operating instructions pressure gauges Model 6 with 831 per ATEX
2030660 12/2004 GB/D/F
3. Technical data ... / 4. Alarm contacts
Installation
T Nominal position per EN 837-1 / 9.6.7 Figure 9: 90° ()
T Pressure connection: lower mount (LM) or lower back mount (LBM)
T In order to avoid any additional heating, the instruments must not be
exposed to direct solar irradiation while in operation!
T With filled versions the ventilating valve at the top of the case must be
opened prior to commissioning!
Permissible vibratory stress at the mounting location
T As a matter of principle the instruments should only be mounted at locations
without vibratory stresses
T Where required, a decoupling from the mounting location can be achieved
e.g. by a flexible connecting line from the measuring point to the pressure
gauge and mounting via a measuring instrument bracket.
4. Alarm contacts
EC-type examination certificates
T Standard version Model 831.XX
PTB 99 ATEX 2219 X (enclosure 2) and ZELM 03 ATEX 0128 X (enclosure 4)
Depending on the number of switches and on the case diameter either
Model SJ2-N... or Model SJ3.5-...-N... is used.
T Safety pattern version Models 831.XX - SN or - S1N
PTB 00 ATEX 2049 X (enclosure 3) and ZELM 03 ATEX 0128 X (enclosure 4)
Depending on the number of switches and on the case diameter either
Models SJ 2-SN..., SJ 2-S1N..., SJ 3.5-SN.. or SJ 3.5-S1N... are used.
GB
The built-in sensor type is stated on the product label of the pressure gauge.
Wiring details
T The electrical connections should be made by qualified electricians
T Connection of the switches via screw terminals in the terminal box
2
T Conductor cross section max. 1.5 mm
T The terminal assignment is stated on the connection plate at the
pressure gauge
2030660 12/2004 GB/D/F
7WIKA Operating instructions pressure gauges Model 6 with 831 per ATEX
4. Alarm contacts
The permissible limits for Ui, Ii and Pi of the intrinsically safe supply circuits
depend on the sensor type. They can be taken from the corresponding EC-type
examination certificates. (The sensor type is stated on the connection plate of
the pressure gauge.)
GB
Suitable switch amplifiers are e.g.:
CircuitSensor type Model designationEC-type exami-WIKA-
(s. Ex-certific.)Fa. Pepperl & Fuchsnation certificateModel
EMC according to EN 60 947-5-2.
The instruments are to be protected against strong electromagnetic fields.
To set desired value indicator
The desired value indicators for the alarm contacts are adjustable over the
adjustment lock in the window with the aid of adjustment key (included in delivery; to be found on standard gauges on the outside edge of the junction box).
Desired value
indicators
(red set pointer)
Adjustment lock
Adjustment key
removable
The desired value indicators for the alarm contacts are adjustable over the full
range of the instrument. Switching points shall be set in the ranges between
10 % und 90 % of the scale, to ensure switching accuracy and long life of the
mechanical measuring system.
8WIKA Operating instructions pressure gauges Model 6 with 831 per ATEX
2030660 12/2004 GB/D/F
5. Commissioning ... 7. Repairs
5. Commissioning
During the commissioning process pressure peaks must be absolutely avoided.
Open the shut-off valves slowly.
6. Maintenance and servicing / cleaning
The instruments require no maintenance or servicing.
The indicator and switching function should be checked once or twice every
12 months. The instrument must be disconnected from the process to check
with a pressure testing device.
The instruments should be cleaned with a damp cloth moistened with soap
solution. For cleaning inside the instrument the mains power supply should be
disconnected by means of the plug box. It must be ensured that all the parts are
dry before the power is switched on again.
7. Repairs
Repairs are to be only carried out by the manufacturer or appropriately trained
personnel.
For further details see WIKA data sheet AC 08.01 or the data sheet for the
respective basic gauge.
GB
2030660 12/2004 GB/D/F
9WIKA Operating instructions pressure gauges Model 6 with 831 per ATEX
Enclosure 1:
GB
Konformitätserklärung
Richtlinie 94 / 9 / EG (ATEX)
Wir erklären in alleiniger Verantwortung, dass
nachstehend genannte Produkte, Druckmessgeräte
mit Kapselfeder, gemäß gültigem Datenblatt mit der
Richtlinie übere instimmen und dem
Konformitätsbewertungsverfa hren
'Interne Fertigungskontrolle'
unterzogen wurden.
WIKA-Typen / WIKA models
61X.20 / 6XX.50 / 6X4.11
Die Unterlagen werden aufbewahrt
unter der Aktennummer 8000318215
bei der benannten Stelle 0032
TÜV NORD CERT
Am TÜV 1
D-30519 Hannover
Die Geräte werden gekenn zeichnet mit
Angewandte Normen:
EN 13463-1 Grundlagen und Anforderungen
EN 13463-5 Schutz durch konstruktive Sicherheit "c"
Die eingebauten Grenzsignalgeber 831 sind EG-
baumustergeprü ft. Die Nummer n der Prüfbescheinigungen und di e Kennzeichnu ng
PTB 99 AT EX 2219 X bzw./resp. PTB 00 ATEX 2049 X II 2 G EEx ia IIC T6
und/and Z ELM 03 ATEX 012 8 X II 1 D Ex iaD 20 T...°C
WIKA Alexander Wiegand GmbH & Co. KG
MANOMETER AG, Industriestr. 11, CH-6285 Hitzkirch
Hitzkirch, 05.11.2004
Peter Barmettler Daniel Tschopp
Leiter Technik Leiter Qualitätssicherung
Technical Mana ger Quality Assurance Manager
Declaration of Conformity
Directive 94 / 9 / E C (ATEX)
We declare under our sole responsibility that the
products me ntioned below, pressure gauges with
capsule element, according to th e current data sheet
correspond with the directive and were subjected to
the conformity assessment procedure
'Internal Control of Production'.
Datenblätter / da ta sheets
PM 06.02 / PM 06.03 / PM 06.05
The dossier is ret ained
under file nr. 8000318215
at the notified bo dy 0032
TÜV NORD CERT
Am TÜV 1
D-30519 Hannover
The gauges are ma rked with
II 2 GD c
Applied standards:
EN 13463-1 Basic method and requirements
EN 13463-5 Protection by constructional safety "c"
The built-in alarm contacts 831 are EC-type-certified.
Numbers of certificates and marking
10WIKA Operating instructions pressure gauges Model 6 with 831 per ATEX
2030660 12/2004 GB/D/F
Enclosure 2:
GB
2030660 12/2004 GB/D/F
11WIKA Operating instructions pressure gauges Model 6 with 831 per ATEX
Enclosure 2:
GB
12WIKA Operating instructions pressure gauges Model 6 with 831 per ATEX
2030660 12/2004 GB/D/F
Enclosure 2:
GB
2030660 12/2004 GB/D/F
13WIKA Operating instructions pressure gauges Model 6 with 831 per ATEX
Enclosure 3:
GB
14WIKA Operating instructions pressure gauges Model 6 with 831 per ATEX
2030660 12/2004 GB/D/F
Enclosure 3:
GB
2030660 12/2004 GB/D/F
15WIKA Operating instructions pressure gauges Model 6 with 831 per ATEX
Enclosure 3:
GB
16WIKA Operating instructions pressure gauges Model 6 with 831 per ATEX
2030660 12/2004 GB/D/F