wipos P3 24-5
wipos P3 24-5
Switching power supply
24 V DC / 5 A
81.000.6160.0
Primary switching power supply, three phase
Output: 24 V DC / 5 A (adjustable 22.5 – 28.5 V DC)
Short circuit proof
Input: 340 - 575 V AC; 480 - 820 V DC
Full load up to 60 °C
PFC technology
Vertical mount
100 % burn-in
Block diagram
Dimensional diagram
Technical Data
wipos P3 24-5 Part number: 81.000.6160.0
Rated output power [PO ] 120 W
Rated output voltage [UO] 24 V DC
Rated output current [ION] 5 A DC
Efficiency typ. / min. 89 % / 87 %
Minimum load none
Output voltage trim range
(U
, 0.8 x ION)
IN_AC
Output voltage accuracy (U
Line regulation ±1 %
Load regulation (U
Temperature coefficient (U
Rated overload protection 115 % - 135 %
Output short circuit (UO, ION) Current limited (hiccup mode)
Ripple & noise (U
Operation indicator
output voltage OK (UI , I0N)
output voltage too low (UI, I0N)
Parallel operation no
Derating (61 °C . . . 71 °C) 2.5 % / K (see Fig. 1 Derating)
Overvoltage protection (U
Relay contact ("OK") closes at UO > 19.4 V DC (UO 17.6 ... 19.4 V)
Relay contact load current (60 V DC) max. 0.3 A
Relay contact isolation voltage 500 V DC
Wieland Electric GmbH, Brennerstr. 10–14, D - 96052 Bamberg Type: wipos P3 24-5
www.wieland-electric.com Rev.: 05/2010 – Page 1 of 2
IN_AC
IN_AC
, ION) -0 % / +1 %
IN_AC
) ±1 %
, I
IN_AC
, ION, BW = 20 MHz) <100 mVss
IN_AC
) ± 0.03 % / K
Omin
, ION) 30 . . . 33 V
22.5 V . . . 28.5 V
Temperature switch-off at 100 – 110 °C; autorestart after cool down
Display range
"DC OK", LED green (UO 17.6 ... 19.4 V)
"DC LOW", LED red (UO < 17.6 ... 19.4 V)
Fig. 1 Derating
wipos P3 24-5
Technical Data
wipos P3 24-5 Part number: 81.000.6160.0
Rated input voltage AC [U
Line frequency AC 47 – 63 Hz
Power factor correction filter (PFC) yes (0.55)
Input voltage range AC [U
Input voltage range 2PH AC [U
Input voltage range DC [U
Rated input current (U
Inrush current (U
Input fuse 3 x T2.0 A / 600 V AC (internal)
Hold up time (U
Internal surge voltage protection Varistor
Isolation voltage (input / output) 3000 V AC / 4242 V DC
Isolation resistance (input / output) 100 MOhm
Switching frequency 70 kHz
Ventilation / Cooling free air convection
Mounting conditions (free space) 25mm free space on all sides recommended
Pollution degree 2
Operating ambient temperature [TU] -40 °C . . . +71 °C
Humidity in operation 20 – 95 % RH
Storage temperature [TU] -40 °C . . . +85 °C
Mounting on DIN rail 35 mm (EN 60715)
Degree of protection IP 20
MTBF 559,000 h
Dimensions (W x H x D) 74.3 x 124 x 119 mm
Weight ca. 0.8 kg
Housing material Metal
Connector cross section screw terminals
min. solid / stranded 0.5 mm² (AWG24)
max. solid / stranded 6 mm² (AWG10)
Strip length 8 mm
Torque input terminals
output terminals
Approvals and standards
UL / cULus UL 508 Listed, UL60950-1 Recognized
TUV / Safety EN60950-1, EN61558-1, EN61558-2-17
CE EN61000-6-3, EN 55022 Class B,
Control Elements
Vout Adjust Trimmer potentiometer for U
Terminal connections
---- 2 x output voltage 24 V, negative output
+ 2 x output voltage 24 V, positive output
OK 2 x relay (normally closed)
L1, L2, L3 AC: phase conductor, DC: no polarity
gggg (PE) PE (Ground), always connect
IN_AC
IN_AC
= 400 V, ION) 0.36 A typ. / 0.5 A max.
I_AC
] 3PH 400-500 V AC
IN_AC
] 3PH 340 ... 575 V
I_AC
] 2PH 340 ... 575 V, IO = 3.75 A max.
I_AC
] 480 ... 820 V
I_DC
, ION) 10 A typ.
, I0N) > 20 ms
for cooling; up to 50 °C no horizontal space
needed
1.0 Nm max.
0.6 Nm max.
(follow EN60204), IRAM
EN61000-3-2, EN61000-3-3, EN61000-6-2,
EN55024, EN61000-4-2, Level 4,
EN61000-4-3 Level 3, EN61000-4-4 Level 4,
EN61000-4-5 L-N Level 3, L/N-FG Level 4,
EN61000-4-6 Level 3, EN61000-4-8 Level 4,
EN61000-4-11, ENV 50204 Level 2,
EN61204-3
terminal (internally connected)
terminal (internally connected)
adjustment
out
Wieland Electric GmbH, Brennerstr. 10–14, D - 96052 Bamberg Type: wipos P3 24-5
www.wieland-electric.com Rev.: 05/2010 – Page 2 of 2