flare 230VAC/48VDC-0,5A
Wiring diagram |
|
Dimensional diagram |
||
Technical Data |
|
|
|
|
|
|
|
|
|
flare 230VAC/48VDC-0,5A |
Order no. 80.020.4103.0 |
|
|
|
|
|
|
|
|
Coil circuit |
|
|
|
|
|
|
|
|
|
Operating voltage |
230 V AC |
|
|
|
Minimum input voltage |
0 … 40 V AC |
|
|
|
Maximum input voltage |
90 … 250 V AC |
|
|
|
Nominal input current |
6,5 … 7,5 mA |
|
|
|
Status display |
LED yellow |
|
|
|
|
|
|
|
|
Switching characteristics |
|
|
|
|
|
|
|
|
|
Nominal switching voltage |
4,4 … 53 V DC |
|
|
|
Max. switching voltage |
53 V DC |
|
|
|
Max. switching current |
0,5 A (see Fig. 1 Load limiting curve) |
|
|
|
DC1 30 / 110 / 220 V DC |
|
|
|
|
|
|
|
|
|
Min. switching voltage |
4,4 V DC |
|
|
|
Min. switching current |
0,1 mA |
|
|
|
Maximum switching frequency |
10 Hz |
|
|
|
Pick-up delay |
25 ms |
|
|
|
Release delay |
25 ms |
|
|
|
|
|
|
|
|
General Data |
|
|
|
|
|
|
|
|
|
Width |
6,2 mm |
|
|
Fig. 1 Load limiting curve |
Height |
89 mm |
|
|
|
|
|
|
Type: flare 230VAC/48VDC-0,5A
Rev.: 06/2012 – Page 1 of 2