Switching power supply
12 V DC / 10 A
81.000.6142.0
Primary switching power supply, single phase
Output: 12 V DC / 10 A (adjustable 11.4 - 14.5 V DC)
Short circuit proof
Input: 115/230 V AC auto select; 210 - 375 V DC
Full load up to 60 °C
PFC Technology
Vertical mount
Parallel operation (max. 3 devices)
100 % Burn-In
Block diagram
Dimensional diagram
Technical Data
wipos P1 12-10 Part number: 81.000.6142.0
Rated power [P0 ] 120 W
Rated output voltage [UO] 12 V DC
Rated output current [ION] 10 A DC
Efficiency typ. / min. 86 % / 84 %
Minimum load none
Output voltage trim range
(UO, ION)
Output voltage accuracy (ION) -0 % / +1 %
Line regulation ±0.5 %
Load regulation (UO) at single operation:
parallel operation:
Temperature coefficient (UO, ION) ± 0.03 % / K
Rated overload protection 125 % - 145 %
Output short circuit (UO, ION) current limited (fold forward)
Ripple & noise (UO, ION, BW = 20 MHz) <50 mVss
Operation indicator
output voltage OK (UI , ION)
output voltage too low (UI, ION)
Parallel operation (0.9 I0N) yes, max. 3 devices
Derating (61 °C ... 71 °C) 2.5 % / K (see Fig. 1 Derating)
Overvoltage protection (UO, ION) 125 % ... 145 %
Wieland Electric GmbH, Brennerstr. 10–14, D - 96052 Bamberg Type: wipos P1 12-10
www.wieland-electric.com Rev.: 11/2010 – Page 1 of 2
11.4 V ... 14.5 V
±1 %
±5 %
Display range
"DC OK", LED green (UO 10.0 ... 11.2 V)
"DC LOW", LED red (UO < 10.0 ... 11.2 V)
Fig. 1 Derating
wipos P1 12-10
Technical Data
wipos P1 12-10 Part number: 81.000.6142.0
Rated input voltage AC [U
Line frequency AC 47 – 63 Hz
Power correction filter (PFC) yes (0.7)
Rated input voltage DC [U
Rated input current 115 V / 230 V 2.8 A / 1.4 A
Inrush current 115 V AC / 230 V AC 24 A / 48 A max.
Input fuse T3.15 A / 250 V (intern)
Hold up time (at I0N) U
U
Isolation voltage (input/output) 3000 V AC / 4242 V DC
Isolation resistance (input/output) 100 MOhm
Cooling / ventilation free convection
Mounting conditions (free space) 25 mm in all directions / up 50 °C no
Operating ambient temperature [TU] -35 °C ... +71 °C (UL: max. 50 °C)
Humidity in operation 20 – 95 % RH
Storage temperature [TU] -35 °C ... +85 °C
Mounting on DIN rail 35 mm (EN 60715)
Degree of protection IP 20
MTBF (Bellcore issue 6 @ 40 °C, GB) 450.000 h
Dimensions (W x H x D) 63.2 x 123.6 x 123 mm
Weight ca. 920 g
Housing material metal
Connector cross section (min.) solid
stranded
Connector cross section (max.) solid
stranded
Strip length 8 mm
Torque input terminals
output terminals
Approvals and standards
UL / cULus UL 508 Listed, UL60950-1 Recognized
TUV / safety EN60950-1, EN61558-1, EN61558-2-17
CE EN55022 & EN61000-6-3, EN61000-3-2,
Terminal connections
---- 2 x output voltage 12 V, negative output
+ 2 x output voltage 12 V, positive output
NC not connected
L AC: Phase, DC: no polarity
N AC: Neutral, DC: no polarity
gggg (PE) PE (ground), always connect
= 115 V
I_AC
= 230 V
I_AC
] 115 V AC (90 ... 132 V) auto select
IN_AC
230 V AC (180 ... 264 V) auto select
] 210 – 375 V DC
IN_DC
> 25 ms
> 30 ms
horizontal space needed
0.5 mm² (AWG24)
0.5 mm² (AWG24)
6 mm² (AWG10)
6 mm² (AWG10)
1.0 Nm max.
0.6 Nm max.
(follow EN60204) , IRAM
EN61000-3-3, EN55024 & EN61000-6-2,
EN61000-4-2, EN61000-4-3, EN61000-4-4,
EN61000-4-5, EN61000-4-6, EN61000-4-8,
EN61000-4-11, EN60204-1, EN61204-3
terminal (internally connected)
terminal (internally connected)
Wieland Electric GmbH, Brennerstr. 10–14, D - 96052 Bamberg Type: wipos P1 12-10
www.wieland-electric.com Rev.: 11/2010 – Page 2 of 2