Wieland 81.000.6134.0 Data Sheet

wipos P1 48-5
(illustration similar)
wipos P1 48-5
Switching Power Supply 48 V DC / 5 A
81.000.6134.0
Primary switching power supply, single phase
Output: 48 V DC / 5 A (adjustable 47 - 56 V DC)
Short circuit proof
Input: 115/230 V AC auto select; 210 - 375 V DC
Full load up to 60 °C
PFC Technology
Vertical mount
Parallel operation (max. 3 devices)
100 % Burn-In
Block diagram
Technical Data
wipos P1 48-5 Part number: 81.000.6134.0
Rated power [PO ] 240 W Rated output voltage [UO] 48 V DC Rated output current [ION] 5 A DC Efficiency typ. / min. 90 % / 88 % Minimum load none Output voltage trim range (UO, ION) Output accuracy (ION) -0 % / +1 % Line regulation ±0.5 % Load regulation (UO) at single operation: parallel operation: Temperature coefficient (UO, I
Rated overload protection 120 % - 145 % Output short circuit (UO, ION) Current limited (fold forward) Ripple & noise (UO, ION, BW = 20 MHz) <100 mVss Operation indicator Output voltage OK (UI , I0N) Output voltage low (UI, I0N) Parallel operation (0.9 I Derating (61 °C ... 71 °C) 2.5 % / K (see Fig. 1 Derating) Overvoltage protection (ION) 120 % ... 145 %
) ± 0.03 % / K
Omin
) yes, max. 3 devices
O max
Dimensional diagram
47 V ... 56 V
±1 % ±5 %
Display range "DC OK", LED green (UO 37 ... 43 V) "DC LOW", LED red (UO < 37 ... 43 V)
Fig.
Fig. 1111 Derating
Fig. Fig.
Derating
Derating Derating
Wieland Electric GmbH, Brennerstr. 10–14, D - 96052 Bamberg Type: wipos P1 48-5 www.wieland-electric.com Rev.: 11/2010 – Page 1 of 2
wipos P1 48-5
Technical Data
wipos P1 48-5 Part number: 81.000.6134.0
Rated input voltage AC [U
Line frequency AC 47 – 63 Hz Power correction filter (PFC) yes (0.7) Rated input voltage DC [U Rated input current 115 V / 230 V 5.4 A / 2.2 A Inrush current 115 V AC / 230 V AC 30 A / 60 A max. Input fuse T6.3 A / 250 V (intern) Hold up time (UI, I0N) U U
Isolation voltage (input/output) 3000 V AC / 4242 V DC Isolation resistance (input/output) 100 MOhm
Cooling / ventilation free convection Mounding conditions (free space) 25 mm in all directions / up to 50 °C no
Operating temperature range [TU] -40 °C ... +71 °C (UL: max. 50 °C) Humidity in operation 20 – 95 % RH Storage temperature [TU] -40 °C ... +85 °C
Mounting on 35 mm DIN rail acc. EN60715 Protection degree IP 20
MTBF (Bellcore issue 6 @ 40 °C, GB) 423.000 h
Dimensions (W x H x D) 83 x 123.6 x 123 mm Weight ca. 1.3 kg Housing material metal
Connector cross section (min.) solid stranded Connector cross section (max.) solid stranded Strip length 8 mm Torque input clamps output clamps
Approvals and standards UL / cULus UL 508 Listed, UL60950-1 Recognized TUV / savety EN60950-1, EN61558-1, EN61558-2-17
CE EN55022 & EN61000-6-3, EN61000-3-2,
Terminal connections
---- 2 x output voltage 48 V, negative terminal
+ 2 x output voltage 48 V, positive terminal
NC not connected L AC: Phase, DC: no polarity N AC: Neutral, DC: no polarity gggg (PE) PE (ground), always connect
= 115 V
I_AC
= 230 V
I_AC
] 115 V AC (90 ... 132 V) auto select
IN_AC
230 V AC (180 ... 264 V) auto select
] 210 – 375 V DC
IN_DC
> 25 ms > 30 ms
horizontal space required
0.5 mm² (AWG24)
0.5 mm² (AWG24) 6 mm² (AWG10) 6 mm² (AWG10)
1.0 Nm max.
0.6 Nm max.
(follow EN60204) , IRAM
EN61000-3-3, EN55024 & EN61000-6-2, EN61000-4-2, EN61000-4-3, EN61000-4-4, EN61000-4-5, EN61000-4-6, EN61000-4-8, EN61000-4-11, EN60204-1, EN61204-3
(internally connected)
(internally connected)
Wieland Electric GmbH, Brennerstr. 10–14, D - 96052 Bamberg Type: wipos P1 48-5 www.wieland-electric.com Rev.: 11/2010 – Page 2 of 2
Loading...