CMM-3U & CMM-3UK Zoning Panel
Installation & Operating Instructions
Product Data
• Single Stage gas and electric systems
• Multi Stage (2H/1C) gas and electric systems
• Heat Pump (3H/1C)
• 2-3 zones
• 5-Year Warranty
Specifications
• Construction: ABS Plastic
• Dimensions: 7 ⅝” x 7 ¼” x 1 ⅜”
• Voltage: 24 Volts AC, 50/60 Hz
• Operating Temperature: 0°- 120°
• Shipping/Storage Temperature: -20°- 140°
• Humidity Range: 5% - 95% Non-Condensing
Kit Contents (CMM-3UK)
• CMM-3U
• CLAS (leaving air sensor)
• COAS (outdoor air sensor for heat pumps)
• 24V Transformer
Recommended Dampers
• CRDS – round damper (24V)
• CZDS – rectangular, side mount motor (24V)
• CZDB – rectangular, bottom mount motor (24V)
• CSPRD – static pressure relief dampers
24V dampers are power close, spring open and are
convertible to power open, spring close
Recommended Thermostats
• 1F78-151 (5+2 programming)
• 1F78-144 (non-programmable)
• 1F85-0471 (5+1+1,5+2,0 programming)
• 1F80-0471 (5+1+1,5+2,0 programming)
• 1F97-1277 (7, 5+1+1,0 programming)
• 1F95-1277 (7, 5+1+1,0 programming)
• 1F85RF-275 (5+1+1,5+2,0 programming) (wireless)
Terminal
Destination
W2/E….…… 2nd Stage Heat (Emergency heat for Heat Pumps)
G…………… Fan Relay
Y…………… Compressor
R…………… Power for Heating/Cooling
W/OB……… Heat Relay/Changeover Valve for Heat Pump
C…………… Common Wire
Description
To prevent electrical shock and/or
equipment damage, disconnect electric
power to system at main fuse or circuit
breaker box until installation is complete
SAVE THESE INSTRUCTIONS FOR
Failure to read and follow all instructions
carefully before installing or operating
this control could cause personal injury
and/or property damage.
FUTURE USE!
1 of 6
© 2004 White-Rodgers by Permission
Form 37-6863A
System Mode Indicator Power Indicator LED
Zone Terminal
Blocks for Zone
Thermostats
CLAS and COAS
Terminal Blocks
Zone Calling Indicators
Sensor Limits
Mounting Keyholes
Two at Top also.
Table of Contents
Installation 2
Operation 3
Set-Up for
Various HVAC Equipment 3
Leaving Air Sensor Air Sensor 3-4
Outdoor Air Sensor 4
Timers 4
Checkout 4
Wiring 4-5
Troubleshooting 5-6
Wiring Diagram 6
INSTALLATION
The CMM-3U Control is a three (3) zone control panel that
can be used with conventional single stage, two stage heating
and cooling, heat pumps with or without dual fuel and up to
three stages of heating. The CMM-3U panel is the central
control panel that all zone dampers, zone thermostats, Heat
HVAC Equipment
Connections
Zone Terminal
Blocks for Zone
Dampers
24V Transformer
Terminal Blocks
Automatic Resetting
Fuse
Pump Controls, power transformer, Outdoor Air Sensor and
Leaving Air Sensor are wired.
When installing the CMM-3U panel it is important to pick a
central location where it is most convenient to bring all the
wires. Most often this is at the furnace or air handler. It is
often the most convenient location and closest to power, the
HVAC unit controls and the zone dampers when typically
located at or near the plenum.
The CMM-3U panel case is made of sturdy ABS plastic and
can be mounted to any flat surface. It is recommended that
the panel be mounted to a wall or return plenum and NOT on
the furnace or plenum where it will be in contact with the
excessive hot temperatures.. The panel can be located in an
attic space or in an enclosed cabinet of a rooftop unit. Insure
the panel is not in direct exposure to the elements.
The cover easily removes from the case by pulling firmly and
separating the cover from the case exposing the circuit board.
There are 4 key-hole mounting points in each corner of the
case. The case has openings in the rear of the case as well
as the side for all wiring. Wiring can come from the back as
well as the side in order to make a neat installation.
2 of 6
© 2004 White-Rodgers by Permission
Form 37-6863A