FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE IN-
STALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY
AND/OR PROPERTY DAMAGE.
DESCRIPTION
The B50 Electric Heat Thermostat is designed for use on all
types of electrical heating installations such as cable heat,
baseboards, wall insert heaters, etc.
The B50 thermostat is intended for use on 240 or 277 VAC where
local codes require that a double line disconnect thermostat
be used. This thermostat can also be used on 120 VAC. (See
specific wiring information for 120 VAC.)
Dial Setting: This thermostat may be set anywhere between
40° and 80°F by simply turning the knob so the indicator on
knob points to the desired setting.
The knob may be turned past 40° to the “OFF” position to obtain
temporary shutdown of the heating equipment for short periods
of time such as on weekends, vacation, etc. Turning knob to
“OFF” position will break both sides of line.
NOTE: Only one side of line is broken during normal cycling of
this thermostat.
B50
ELECTRIC-HEAT THERMOSTAT
(Double Line Disconnect)
INSTALLATION INSTRUCTIONS
This Thermostat includes:
• Wall cover plate (required when thermostat will not hide wall
imperfections behind old thermostat)
• Two cover mounting screws
• Three Temperature Limiting Pins
PRECAUTIONS
This control is a precision instrument, and should be handled
carefully. Rough handling or distorting components could cause
the control to malfunction. Take care not to push or damage
the internal bimetal sensing element during installation.
CAUTION
To prevent electrical shock and/or equipment damage,
disconnect electric power to system, at main fuse or
circuit breaker box, until installation is complete.
All wiring must conform to local and national electrical codes
and ordinances.
Do not use on circuits exceeding specified voltages.
Higher voltages will damage control and could cause
shock or fire hazard.
Do not use on inductive loads. Inductive (motor) loads
will damage control and could cause shock, fire hazard
or failure of thermostat.
SPECIFICATIONS
Switch Rating: Non-Inductive
22A (5000W) 240VAC
19A (5000W) 277VAC
22A (2500W) 120VAC
Temperature Range: 40° to 80°F
Differential: 3.0°F
Switch Action: Open on rise
Contact Structure: Double Line Disconnect - DPST
PART NO. 37-7272B
www.white-rodgers.com
1546
INSTALLATION
L1
RED
L2
BLK
RED
BLK
LIMIT
CONTROL
HEATER
POWER
IN
LO
AD
LOAD
L1
RED
L2
BLK
RED
BLK
LIMIT
CONTROL
HEATER
POWER IN
120 VAC ONLY
LO
AD
LOAD
HOT
COMMON
POWER IN
TO LOAD
SWITCH OPENS
IN "OFF" POSITION
HOT (L1)
COMMON (L2)
BLK
RED
RED
BLK
Pins are shown installed at
60 and 65˚. The temperature
setting range is limited
between these two
temperatures.
The third pin is supplied as a
spare in case of accidental
loss.
If the heating equipment manufacturer has made provisions
or recommendations for the location of this control, then follow
those instructions. If not, the following suggestions should be
observed.
1. The control should be mounted in the wall, approximately
five feet from the floor, as near as possible to the center of
the controlled area.
2. It should be mounted on a partitioning wall, not on an outside
wall.
WIRING
All wiring must conform to local and national electrical codes and ordinances.
The thermostat may be mounted in any standard 2" x 3" electrical
outlet box. For ease of installation use a deep type box.
USE WITH COPPER CONDUCTORS ONLY. Use approved
wire connectors for 12 AWG only.
1. Disconnect electrical power to the system at main fuse or circuit box.
2. Make electrical connection to thermostat leads with wire nuts or
other local code approved devices. All connections must be tight.
3. Push the lead wires into the outlet box.
4. Remove thermostat cover. Push thermostat case into junction box
and secure with screws provided.
Take care not to push or damage the bimetal sensing element
during installation.
5. Install thermostat cover and turn knob to desired setting.
3. It should be mounted as far as possible from undesirable
sources of heat and cold such as:
a. Windows and doors
b. Direct rays from sun
c. Hot water or cold water pipes
d. Adjoining outside walls
240/277 VAC Wiring Diagram
120 VAC Wiring Diagram
Schematic Diagram
Temperature Limiting Pins
Temperature Limiting Option is for applications where the temperature
setting of the control is to be set and "protected" from unauthorized
adjustment. To limit the temperature range, follow the directions below:
1. Remove cover from thermostat.
2. On inside of cover, firmly press small tapered end of a pin into the
approximate maximum and minimum temperature positions.
3. After pressing pins into place on inside of cover, rotate temperature
knob to be sure the knob is between the pins.
4. Replace cover on thermostat. Check that knob rotation is limited in
travel as set by the pins. If rotation of knob is outside of limits, check
that the pins are installed properly.
5. Install supplied screws at top and bottom of thermostat to secure
cover.