White Rodgers 36C User Manual

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
The 36C cycle pilot gas valves with redundant pilot sole­noid main gas regulator, integral gas pressure switch and electrical connection on the gas valve for mercury flame sensor connection.
36C
Cycle Pilot Gas Valve
INSTALLATION INSTRUCTIONS
SPECIFICATIONS
Electrical Rating: 0.6 amps End to End Dimensions: 3
15
/16
Maximum Pressure Rating: Agency: A.G.A. and C.G.A. design certified
Ambient Operating Range: –40 to +175°F (–40 to 79°C)
Outlet Pressure
1" Pressure Drop Capacity Rated Range of Regulation
BTU/HR BTU/HR
AGA STD. NAT GAS LP GAS AGA STD. NAT GAS LP GAS
Pipe Size 1000 BTU/CU. FT. 2500 BTU/CU. FT. 1000 BTU/CU. FT. 2500 BTU/CU. FT.
1/2 X 3/8 100,000 162,000 15,000-100,000 15,000-162,000 1/2 X 1/2 230,000 372,600 30,000-290,000 30,000-469,000 1/2 X 3/4 230,000 372,600 30,000-290,000 30,000-469,000 3/4 X 3/4 280,000 453,600 50,000-400,000 50,000-648,000
Model Coil Gas Pipe Opening Regulator Adjustment Convertible Kit Line Flow Bushing Pressure Side See
Number Voltage Type Size Characteristic Setting Range Nat./LP Included Interrupter Direction Kit Tap Taps Figure
36C84-912 24 VAC Natural3/4 x 3/4Fast Open 3.5 2.5–5.0 Yes Yes No Str. Thru Yes Yes No 5 36C84-913 24 VAC Natural 36C84-916 24 VAC Natural3/4 x 3/4Fast Open 3.5 2.5–5.0 No No No Str. Thru Yes No No 8 36C84-921 24 VAC Natural 36C84-923 24 VAC Natural 36C84-926 24 VAC Natural3/4 x 3/4Fast Open 3.5 2.5–5.0 No No No Str. Thru Yes No No 4 36C84-936 24 VAC LP 36C87-944 24 VAC Natural 36C94-906 24 VAC Natural3/4 x 3/4Slow Open 3.5 2.5–5.0 No No No Str. Thru Yes No No 5 36C94-907 24 VAC Natural
Wiring diagrams – see pages 3-6
3
/4 x 3/4Fast Open 3.5 2.5”–5.0” Yes Yes No Str. Thru Yes Yes No 7
3
/4 x 3/4Fast Open 3.5 2.5”–5.0” Yes Yes No Str. Thru Yes Yes No 5
3
/4 x 3/4Fast Open 3.5 2.5”–5.0” No No No Str. Thru No Yes No 9
3
/4 x 3/4Fast Open 11.0 7.5–12.0 No No No Str . Thru Yes No No 4
3
/4 x 3/4Step Open 1.0 1.0”/3.52.5–5.0 No No No Str . Thru Yes No No 6
3
/4 x 3/4Slow Open 3.5 2.5”–5.0” Yes Ye s No Str. Thru Ye s No No 4
Regulator Conversion Reducer Inlet Wiring
LP Internal
1
/2 PSI (14.0 W.C.)
www.white-rodgers.com
PART NO. 37-6517A
0618
PRECAUTIONS
DO NOT BEGIN INSTALLATION UNTIL YOU READ THE FOLLOWING PRECAUTIONS.
!
WARNING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
1. Failure to turn off electric or main gas supply to heating system could cause personal injury and/or property damage by shock, gas suffocation, fire, and/or explosion.
2. Do not use this control on circuits exceeding specified voltage. Higher voltage will damage the control and may cause shock or fire hazard.
3. NEVER USE FLAME OR ANY KIND OF SPARK TO CHECK FOR GAS LEAKS–COULD CAUSE FIRE AND/OR EXPLOSION.
4. Do not use a control set for natural gas with LP gas, or a control set for LP gas with natural gas. Personal injury and/or property damage, gas suffocation, fire, and/or explosion may result.
CAUTION
!
1. Do not short out terminals on gas valve or primary control to test. Short or incorrect wiring can cause
equipment damage, property damage and/or personal injury.
2. This control is not intended for use in locations where it may come in direct contact with water.
Suitable protection must be provided to shield the control from exposure to water (dripping, spraying, rain, etc.).
INSTALLATION
NOTE
All piping must comply with local codes, ordinances, and/or national fuel gas codes.
1. Turn off electrical power to the system at the fuse box or circuit breaker. Also turn off the main gas supply.
2. If replacing an existing valve, disconnect all plumbing and electrical connections from the old control.
3. The control may be installed in any position except upside down (see figure 1). The arrow on the bottom plate indicates the direction of gas flow through the valve.
4. You should use new pipe that is properly chamfered, reamed, and free of burrs and chips. If you are using old pipe, be sure it is clean and free of rust, scale, burrs, chips, and old pipe joint compound.
5. Apply pipe joint compound (pipe dope) or teflon tape that
is approved for all gases, only to the male threads of
the pipe joints. DO NOT apply compound or teflon tape
to the first two threads (see figure 2 for typical piping connections).
6. If you are using a vise or open-end wrench to hold the valve while installing piping, do not tighten excessively, as this may damage the valve.
7. See wiring pages 3-6 when making electrical con­nections. After all gas and electrical connections are completed, turn gas on and check for gas leaks with leak detection solution or soap suds. Bubbles forming indicate a leak. SHUT OFF GAS AND FIX ALL LEAKS IMMEDIATELY.
2
Upright, 90° from upright or vertical
UPRIGHT
LEFT OR RIGHT
NOTE: Control shown may not be identical
to replacement control.
Figure 1. Mounting positions
Drop
Horizontal
NOTE:
Always Include
A Drip Leg In Piping
Drop
Horizontal
3 in.
minimum
Riser
Gas Valve
Piped Gas
Supply
3 in.
minimum
Tub in g Gas
Supply
Piped Gas
Supply
Figure 2. Typical gas valve piping
INLET BOSS UP OR DOWN
Gas Valve
Riser
minimum
Gas Valve
3 in.
INSTALLATION
PILOT GAS CONNECTION
Install fitting into pilot gas outlet (see figure 3), turning until finger-tight. Insert clean, deburred tubing all the way through the fitting. While holding the tubing securely, slowly tighten fitting until you feel a slight "give". Tighten the fitting an additional 1½ turns.
SYSTEM WIRING
REFER TO AND FOLLOW THE APPLIANCE MANUFACT­URER'S WIRING DIAGRAM. USE THE TABLE ON PAGE 1 TO IDENTIFY THE PROPER TERMINAL IDENTIFICATION FIGURE FOR THE GAS VALVE.
Wiring for 36C84-926, -936 & 36C94-907 Gas Valves
Figure 4
Pilot gas
outlet
PILOT
PRESS
TAP
Gas outlet
Figure 3
NOTE
All wiring should be installed in accordance with local and national electrical codes and ordinances.
Always check that the electrical power supply used agrees with the voltage and frequency shown on the gas control.
GREEN
4
WHITE
2
TAN
PRESSURE
SWITCH
TAN
REDUNDANT
COIL
TAN
RED
C
36C84 GAS VALVE
MAIN VALVE RELAY
PILOT/REDUNDANT
SOLENOID VALVE
5059
Pilot Relight Control
2
T1 T2
LIMIT
6
THERMOSTAT
Cycle Pilot System
- For Natural Gas -
PRESSURE
SWITCH
N.O.
24 VAC
LINE
S
3098 MERCURY
FLAME SENSOR
HOT
2
3
COLD
453
WIRING HARNESS
Wiring Harness Available
For Natural Gas
Type Number Length
F115-0060 12 in. F115-0061 18 in. F115-0062 24 in. F115-0063 30 in. F115-0064 36 in.
Wiring Harness consists of two wires, one tan the other black. Both leads are terminated with 1/4 inch female piggyback terminals
RELAY COIL
PRESSURE
SWITCH
N.O.
C
A
G
LIMIT
S
YELLOW
RESISTOR
24 VAC
45326
ORANGE
LINE
3098 MERCURY
FLAME SENSOR
HOT
2
3
COLD
13425
5022
SAFETY
TIMER
4
C
36C84 GAS VALVE
MAIN VALVE RELAY
4
WIRING HARNESS
Wiring Harness Available
For All Gases
Type Number Length
F115-0055 12 in. F115-0056 18 in. F115-0057 24 in. F115-0058 30 in. F115-0059 36 in.
Wiring Harness consists of five wire cable in black sheathing. One end terminated in five-terminal connector for mating to 5022 or 50A22. Other end terminated with six terminal connector to mate with gas manifold.
PILOT/REDUNDANT
SOLENOID VALVE
BLUE
WARP
SWITCH
DIODE
WARP SWITCH
HEATER
Relight Control
THERMOSTAT
RED
5059
Pilot
TAN
SCR
T1 T2
Cycle Pilot System
- For All Gases -
3
Loading...
+ 5 hidden pages