To prevent electrical shock and/or equipment damage,
disconnect electric power to system at main fuse or
circuit breaker box until installation is complete.
This product does not contain mercury. However, this product may replace a product that contains mercury.
Mercury and products containing mercury must not be
discarded in household trash. Do not touch any spilled
mercury. Wearing non-absorbent gloves, clean up any
spilled mercury and place in a sealed container. For proper
disposal of a product containing mercury or a sealed
container of spilled mercury, place it in a suitable shipping
container. Refer to www.white-rodgers.com for location to
send the product containing mercury.
PART NO. 37-6914D
Replaces 37-6914C
0905
INSTALLATION
WARNING
!
Thermostat installation and all components of the
control system shall conform to Class II circuits per
the NEC code.
Remove Old Thermostat
Before removing wires from old thermostat, mark wires for
terminal identifi cation so the proper connections will be made
to the new thermostat.
Installing New Thermostat
1. Pull the thermostat body off the thermostat base. Forcing
or prying on the thermostat will cause damage to the unit.
2. Place base over hole in wall and mark mounting hole
locations on wall using base as a template.
3. Move base out of the way. Drill mounting holes. If you
are using existing mounting holes and the holes drilled
are too large and do not allow you to tighten base snugly,
use plastic screw anchors to secure the base.
4. Fasten base snugly to wall using mounting holes shown
in Figure 1 and two mounting screws. Leveling is for
appearance only and will not affect thermostat operation.
5. Connect wires to terminal block on base using appropriate
wiring schematic.
6. Push excess wire into wall and plug hole with a fi re resistant material (such as fi berglass insulation) to prevent
drafts from affecting thermostat operation.
7. Carefully line the thermostat up with the base and snap
into place.
Thermostat Power MethodSwitch Position/Description
Battery Powered, no 24
Volt system power available.
Hardwired with Battery
Back-up, for 24 Volt systems
with common connection from
transformer to "C" terminal
on thermostat.
*Battery Powered with
Power Stealing Assist,
for 24 Volt systems with no
common connection from
transformer to "C" terminal on
thermostat.
Switches "On", thermostat
runs on batteries.
Switches "On", thermostat
runs on power directly from
transformer with battery backup.
Switches "On", thermostat
runs on batteries and
supplemental power drawn
through the heat or cool circuit.
*Power Stealing Assist is very reliable to increase battery life,
but on a small number of heating or cooling systems with high
impedance electronic modules you may observe one of the
following conditions:
1. The furnace draft inducer motor may run with no call for
heat.
2. The furnace fan may turn on with no call for heat or may
not turn off.
3. The furnace may not turn off when the call for heat ends.
4. The air conditioner may not turn off when the call for cool
ends.
If the Power Stealing Assist method is not compatible with
your system, place the Power Stealing Switches to "Off". This
cancels Power Stealing Assist, operates the thermostat on
batteries and corrects the condition.
Figure 1 – Thermostat Base Multi-Stage 1F95-1291
Battery Location
2 "AA" alkaline batteries are included in the thermostat at the
factory with a battery tag to prevent power drainage. Remove
the battery tag to engage the batteries.
To replace batteries, set system to OFF, remove thermostat
from wall and install the batteries in the rear along the top of
the thermostat (see Figure 1). For best results, use a premium brand "AA" alkaline battery such as Duracell
®
gizer
. If the home is going to be unoccupied for an extended
period (over 3 months) and
is displayed, the batteries
®
or Ener-
should be replaced before leaving.
Power Stealing Switches
The Power Stealing Switches (Fig. 1) should be left in the
"On" position for most systems. The information in the
following table details the thermostat power method and
switch options.
Mounting
Hole
Place Level
across Mounting Tabs
(for appearance only)
Rear view of thermostat
O/B
L
Y2
Y
+
S
-
HM
W2
W/E
6
DHM
Mounting
Hole
Place Level
across Mounting Tabs
(for appearance only)
2 "AA" Batteries
Stack
Power
Stealing
Switch
Power
Stealing
Switches
2
WIRING DIAGRAMS
Figure 2 – Single Stage or Multi-Stage System
(No Heat Pump) with Single Transformer
System
Single Stage 1
(SS1)
Multi Stage 2
(MS2)
RCRHCYY2W/EW2GO/B6L
24 volt
power for
cooling
24 volt
power for
heating
24 volt
common
(optional
for system
operation,
required
for remote
sensor)
Call for cool
Cool mode-1st
stage
No Output
Cool mode-2nd
stage
Call for heat
Heat mode-1st
stage
Single Stage and Multi-Stage Connections
Refer to equipment manufacturers’ instructions for specifi c system
wiring information.
This thermostat is designed to operate a single-transformer or twotransformer system.
You can confi gure the thermostat for use with the following fossil fuel
systems:
Figure 3 – Heat Pump Systems
System
RCRHCYY2*W/E*W2GO6L
Heat mode-2nd
stage, Emergency
stage,
stage,
Mode-1st stage
*Note: Dual Fuel
energizes Heat
mode stage 1
(compressor)
when auxiliary
heat is energized
Heat mode-3rd
stage, Emergency
Mode-1st stage
*Note: Dual Fuel
energizes Heat
mode stages 1
compressors)
when auxiliary
heat is energized
Heat
Pump 1
(HP1)
Heat
Pump 2
(HP2)
24 volt
power for
cooling
24 volt
power for
heating
24 volt
common
(optional
for system
operation,
required
for remote
sensor)
Heat mode-1st
stage,
Cool mode-1st
stage,
(Compressor)
No Output
Heat mode-2nd
Cool mode-2nd
(Compressor)
No output
Heat mode-2nd
stage
Blower/Circulator fan
energized on a call
for cool or Fan On
(also energized in
heating if configured
for Electric Heat)
Installer
Configuration
Menu selects
“O” or “B” for
changeover
function. Set
to “O” terminal
energized in Cool
& Off mode. Set
to “B” terminal
energized in
Heat & mergency
mode
Power closed
connection for
SPDT 3-wire
zone valve
Fault or System
Malfunction
Indicator for
Heat Pumps
with “L” terminal
connection.
Original production
1F95-1291’s
do not have this
connection
NEUTRAL
24VAC
HOT
SINGLE STAGE (SS 1) gas, oil or electric.
TRANSFORMER
MULTI-STAGE (MS 2)gas, oil or electric.
After wiring, see INSTALLER CONFIGURATION section for proper
thermostat confi guration.
Heat mode-3rd
stage, Emergency
Mode-2nd stage
option de-
option de-
and 2 (both
*Note: Dual Fuel
option de-
energizes Heat
mode stage 1
(compressor)
when auxiliary
heat is energized
Heat mode-4th
stage, Emergency
Mode-2nd stage
*Note: Dual Fuel
option deenergizes Heat
mode stages 1
and 2 (both
compressors)
when auxiliary
heat is energized
Blower/Circulator fan
energized on a call
for cool or Fan On
(also energized in
heating if configured
for Electric Heat)
Installer
Configuration
Menu selects
“O” or “B” for
changeover
function. Set
to “O” terminal
energized in Cool
& Off mode. Set
to “B” terminal
energized in
Heat & mergency
mode
Power closed
connection for
SPDT 3-wire
zone valve
Fault or System
Malfunction
Indicator for
Heat Pumps
with “L” terminal
connection.
Original production
1F95-1291’s
do not have this
connection
120VAC
CLASS II
120VAC
HEATING
120VAC
CLASS II
TRANSFORMER
24VAC
HOT
*Dual fuel option, if selected turns off compressor(s) when Auxiliary stages energize.
Heat Pump Connections
If you do not have a heat pump system, refer to fi gures 3 & 4.
Refer to equipment manufacturers’ instructions for specifi c system
wiring information.
You can confi gure the thermostat for use with the following heat pump
systems.
NEUTRAL
NEUTRAL
24VAC
HOT
TRANSFORMER
120VAC
COOLING
CLASS II
HEAT PUMP TYPE 1 (HP 1). Single stage compressor system;
gas or electric backup.
HEAT PUMP TYPE 2 (HP 2).Multi-stage compressor or two
compressor system with gas or electric backup.
After wiring, see INSTALLER CONFIGURATION section for proper
thermostat confi guration.
3
WIRING DIAGRAMS
Figure 4 – Humidity and Sensors
HM
Humidification Terminal,
Energizes on call for
heat if Humidity setpoint
is above room humidity.
Can also be used to
provide humidification
independent of a call for
heat and/or in cooling
mode if Automatic
Humidification is
selected in Configura-
tion Menu item #34
DHM
De-energizes on call for
Dehumidification to
lower the fan speed.
The DHM terminal is
only used on systems
with a compatible
dehumidification feature
that have the required
terminal connection on
the contol module or
have a relay installed to
lower the fan speed
+
Supply voltage
to remote
temperature
sensor
S
Remote
temperature
sensor signal
-
Supply voltage
to remote
temperature
sensor
Dehumidifi cation wiring without an electronically controlled variable speed blower system for
single stage compressor system only.
If you have a single stage compressor system see the diagram below. A relay (customer provided) should be installed
as shown in Fig 7 to switch the fan speed to the next lower
speed on a call for dehumidifi cation from the thermostat. The
reduction in air fl ow allows the coil to remove more humidity
from the air. The relay should be rated for blower motor load.
Since this confi guration reduces the air fl ow in cooling, the
Figure 5 – Typical Wiring for Dehumidifi er System
Normal High
DHM
No
Relay
90-293Q
or equivalent
N
“Cool Fan Output”
1
Normal Cool speed position (DHM energized)
2
Dehum speed mode (DHM de-energized)
NC
1
2
Dehum
Speed Fan
anti-freeze-up control (White-Rodgers CAFC) or equivalent is
recommended. The CAFC prevents the air conditioning coil
from freezing due to low air fl ow, dirty fi lters, low refrigerant
pressure, etc. The CAFC snaps onto the suction line close to
the evaporator coil as possible and breaks the compressor
circuit when the suction line drops below 38 °F and re-make
the circuit at 46°F.
Med
Low
“Heat Fan Output”
N
HM
Humidifier
System
Figure 6 – Typical Wiring for 120V Humidifi er System
HM
Relay
90-290Q
or equivalent
Humidifier
System
HOT
NEUTRAL
120 VAC
Figure 7 – Typical Wiring for 24V Humidifi er System
R
24 VAC
NEUTRAL
TRANSFORMER
HOT
24 VAC
120 VAC
R
NEUTRAL
TRANSFORMER
HOT
120 VAC
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
THERMOSTAT QUICK REFERENCE
Home Screen Description
Figure 8 – Home Screen Display
Day of Week
Room
Temperature
Time of Day
Note: If is displayed, the
thermostat is battery powered.
When battery power remaining
is approximately half, will
System
Switch
be displayed. If the home is
going to be unoccupied for an
extended period (over 3 months)
and is displayed, the batteries
should be replaced before leaving.
Fan
Switch
Programming and Confi guration Items
Displays and "Keypad Lockout" when in keypad
1
lockout mode.
Displays
Lockout" when limited range is activated and locked.
Displays only "Temperature Limit" when limited range
is activated.
2
Indicates period of day being programmed.
3
RUN SCHEDULE (run program) key.
SET TIME key or HOLD temperature key.
4
Displays "Change Filter"/"Change Pad"/"Change UV
Lamp" when the system has run for the programmed
fi lter/humidity pad/UV lamp time period as a reminder
to change or clean your fi lter/humidity pad or to replace
UV lamp.
COPY key or INSTALLER CONFIG key.
CLEAN DISPLAY key allows 30 seconds to wipe off
the display or ADVANCE DAY key for programming.
Used in programming to set time and in confi guration
menu to change selections.
"Hold Until" indicates the time when a temporary hold
period will end.
"Hours" and "Days" displays during steps in installer
confi guration.
The words "Hold At" are displayed when the
thermostat is in the HOLD mode. "Temporary Hold
At" is displayed when the thermostat is in a temporary
HOLD mode.
"Humidity" indicates that the "Set At" display is Hu-
midity setpoint.
"System On" indicates when heating or cooling stage
is energized. "+2" indicates when a second stage is
energized.
"Copy" indicates the copy program feature is being
used during programming.
and "Temperature Limit" and "Keypad
Indicates when
thermostat is calling
for Heat or Cool
18
14
13
15
19
20
Set Temperature/Humidity
Temperature
UP/Down used for
modifying setpoint
as well as to
navigating the menus
Press to view
Humidity setpoint
Menu key for entering
different modes such as
Cleaning, Configuration, Set
Battery Level Indicator
Time and Set Schedule
Indicating the current power level
of the 2 “AA” batteries.
Full power remaining.
Half power remaining.
Change The batteries should be replaced at this time.
Figure 9 – Programming & Confi guration Items
1617
123456789
1
011
1112
10
1
1
1
1
1
171
516
3
2
4
2
2
222
2
2
021
8
9
272
3
6
5
4
82930
3
3
323
373
1
6
33435
839
9
8
1
20
3
19
7
6
4
5
A steady "Cool Savings" display indicates the feature
is enabled in the installer menu. A fl ashing "CoolSavings" display indicates the feature is active.
"Remote" indicates that the indoor remote temperature
sensor, is being accessed. "Outdoor Remote" indicates the outdoor remote temperature sensor is being
accessed.
Display time, remote temperature or humidity.
"Heat Pump" displays when the system confi guration
is set in HP1/HP2.
"Call for Service" indicates a fault in the heating/cooling
systems. It does not indicate a fault in the thermostat.
Auto Schedule key for Auto Schedule function or
Humidity key to display current Humidity and Humidity
setpoint.
2
5
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.