Commercial Stacked Dryer, Gas or Electric
PRODUCT MODEL NUMBERS OVERALL DIMENSIONS
RECESSED AREA AND CLOSET INSTALLATION
EXHAUST VENTING
CSP2770K
CSP2771K
GAS
DRYER
Gas supply: Dryer is equipped for use with
NATURAL gas. Dryer can be converted to L.P. gas.
When rigid pipe is used it should be 1/2 inch IPS.
When acceptable to the gas supplier and local
codes, 3/8-inch approved tubing may be used for
lengths under 20 feet. For lengths over 20 feet,
larger tubing should be used. If local codes permit,
it is recommended that new flexible metal tubing,
design-certified by AGA or CSA, be used for
connecting the appliance to the rigid gas supply
line. The supply line shall be equipped with a
shutoff valve installed within 6 feet of the dryer in
accordance with the National Fuel Gas Code ANSI
Z223.1.
Electrical: 120-volt, 60-Hz, AC-only,
15- or 20-amp. electrical supply. Use copper wire
only. A time-delay fuse or circuit breaker and
separate circuit is recommended.
ELECTRIC
DRYER
Electrical: A four-wire or three-wire, single-
phase, 120/240-volt, 60-Hz, AC-only electrical
supply (or four-wire or three-wire, 120/208-volt, if
specified on the model/serial rating plate) is
required on a separate, 30-ampere circuit, fused
on both sides of the line. A time-delay fuse or
circuit breaker is recommended.
Exhaust venting: Exhaust your dryer to the
outside. four-inch diameter vent is required. Rigid
or flexible metal exhaust vent must be used. Do
Not use plastic or metal foil vent. Exhaust outlet
hood must be at least 12 inches from the ground
or any object that may be in the path of the
exhaust.
A main exhaust vent can be used for exhausting a
group of dryers. Main exhaust vent should be
sized to remove 200 CFM of air per dryer.
Each exhaust vent should enter the main vent at an
angle pointing in the direction of the airflow. Vents
Maximum length of exhaust
system depends upon the type of
vent used, number of elbows and
type of exhaust hood. The
maximum length for both rigid
and flexible vent is shown in the
chart.
For exhaust systems not covered
by the exhaust length chart, see
Whirlpool Service Manual,
“Exhausting Whirlpool Dryers,”
Part No. 603197, available from
your Whirlpool parts distributor.
Ref. 8527892
10-15-02
Because Whirlpool Corporation policy includes a continuous commitment to improve
our products, we reserve the right to change materials and specifications without notice.
Dimensions are for planning purposes only. For complete details, see Installation
Instructions packed with product. Specifications subject to change without notice.
BACK VIEW
SIDE VIEW
MAXIMUM LENGTH OF 4-INCH (10.2 cm) DIAMETER
RIGID METAL VENT
No. of
90°
turns
EXHAUST HOOD TYPE
2-1/2"
(6.4 cm)
4"
(10.2 cm)
4"
(10.2 cm)
4"
(10.2 cm)
4"
(10.2 cm)
4"
(10.2 cm)
64 FT. (19.5 m)
54 FT. (16.5 m)
44 FT. (13.4 m)
35 FT. (10.7 m)
27 FT. (8.2 m)
0
1
2
3
4
58 FT. (17.7 m)
48 FT. (14.6 m)
38 FT. (11.6 m)
29 FT. (8.8 m)
21 FT. (6.4 m)
MAXIMUM LENGTH OF 4-INCH (10.2 cm) DIAMETER
FLEXIBLE METAL VENT
36 FT. (11.0 m)
31 FT. (9.4 m)
27 FT. (8.2 m)
25 FT. (7.6 m)
23 FT. (7.0 m)
0
1
2
3
4
28 FT. (8.5 m)
23 FT. (7.0 m)
19 FT. (5.8 m)
17 FT. (5.2 m)
15 FT. (4.6 m)
dryer exhaust vent
dryer exhaust vent
main collector vent
air flow
30° max.
30° max.
dryer exhaust vent
dryer exhaust vent
30° max.
entering from the opposite side should be
staggered to reduce the exhausted air from
interfering with the other vents.
The maximum angle of each vent entering the
main vent should be no more than 30°.
29-1/4"
(74.3 cm)
approx. 1"
(2.5 cm)
23-3/4"
(60.3 cm)
door
76-3/4"
(195 cm)
27" (68.6 cm)
top
exhaust
bottom
exhaust
41"
(104.1 cm)
13-1/2"
(34.3 cm)
Additional clearances may be required for
wall, door and floor moldings if external
exhaust elbow is used.
Recessed Front View
closet
door
closet
door
Front
View
3" (7.6 cm)
3" (7.6 cm)
24" sq. in.
(155 sq. cm)
48" sq. in.
(310 sq. cm)
Opening is minimum for closet door. Louvered
door with equivalent air openings is acceptable.
7"
(17.8 cm)
Closet Side View
0" (0 cm)
0" (0 cm)
0"
(0 cm)
0"
(0 cm)
6"
(15.2 cm)
Back Sides Top Front
Recessed 0 in 0 in 6 in —
(0 cm) (0 cm) (15.2 cm)
Closet 0 in 0 in 0 in 7 in
(0 cm) (0 cm) (0 cm) (17.8 cm)
Minimum Installation Clearances